Instruction Bulletin
80254-199-01F
September 1997
Seneca, SC, USA
OEM Mounting
Drawout SE Circuit Breaker with
MICROLOGIC™ Trip Unit
400 A to 3000 A Frames
CONTENTS
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Page
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Compartment Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Terminal Marking Labels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Warning Label . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Arcing Clearance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Enclosure Ventilation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Cover Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Wiring Harness . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2000 A and 3000 A SE Cradle Bottom Mounting . . . . . . . . . . . . . . . . . . . . 7
2000 A SE Cradle Side Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3000 A SE Cradle Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Bus Bars and Lug Landings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Wire Size and Wire Bending . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Lifting the Cradle Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Courtesy of NationalSwitchgear.com
Drawout SE Circuit Breaker with MICROLOGIC™ Trip Unit
400 A to 3000 A Frames
INTRODUCTION
Bulletin No. 80254-199-01F
September 1997
This instruction bulletin contains minimum requirements for mounting 400 A
through 3000 A drawout SE circuit breakers in enclosures.
NOTE: This bulletin is intended for original equipment manufacturers. It is not intended for
field installations in existing facilities. Refer to bulletin 48040-495 for operating instructions.
Table 1: Circuit Breaker Ratings
Breaker Type
SE
COMPARTMENT SIZE
Sensor (Frame)
Amperes
400 to 3000
UL Listed Interrupting Ratings
RMS Symmetrical Amperes
240 V
480 V
600 V
150,000
100,000
85,000
30-Cycle Short
Time Rating
50,000 A
The compartment size depends on the sensor (frame) size of the SE circuit breaker.
It is recommended that tests be conducted per UL 891 if any one or a combination
of the following conditions exist (Figure 1 lists minimum compartment sizes):
1.
2.
3.
4.
More than one device is mounted in a single compartment.
The compartment width is less than the minimum.
The compartment height is less than the minimum.
The compartment volume is less than the minimum.
12.00
(305)
29.50
SE
Circuit
Breaker
(749)
Minimum
Compartment
Width
Dimensions are in inches (millimeters).
NOTE: The shaded area is the minimum SE circuit breaker mounting area. Do not locate
additional equipment or structural members in this area.
Sensor (Frame) Size
(A)
Min. Width [1]
mm
in
mm
in3
mm3
400, 800, 1200, 1600
30
762
29.50
749
42,480
1,078,992
2000, 2500, 3000
36
914
29.50
749
50,976
1,294,790
Additional width is required for neutral bussing if 3Ø4W service entrance is used. Additional width and/or
height is required if the enclosure is front-accessible only and/or accessories are included. Contact local
field office for application data.
Figure 1: Minimum Compartment Sizes
Courtesy of NationalSwitchgear.com
Min. Volume
in
[1]
2
Min. Height [1]
© 1990 Square D All Rights Reserved
27009701.eps
min.
Bulletin No. 80254-199-01F
September 1997
Drawout SE Circuit Breaker with MICROLOGIC™ Trip Unit
400 A to 3000 A Frames
Four line labels (A80254-127-01) and two load labels (A80254-127-02) are included
in the SE cradle assembly. These labels must be affixed to the plastic bus supports
beside the appropriate terminals. See Figure 2 for location of the terminal labels.
TERMINAL MARKING
LABELS
NOTE: Because the line (supply) side terminals will remain energized with the circuit breaker
removed, it is important that the labels properly mark which terminals are line terminals.
When the SE circuit breaker is used as a main, feeder, or branch breaker, use two
line labels and two load labels, and discard the remaining two line labels.
On a multiple source tie system, either set of terminals may be line side terminals.
In this situation, use four line labels to indicate that either set of terminals may be
energized, and discard the load labels.
WARNING LABEL
One warning label (A80254-126-01) is included in the SE cradle assembly. Affix this
label to the front side of the front arc barrier as shown in Figure 2.
ARCING CLEARANCE
As illustrated in Figure 2, the rear arc barrier is mounted to an angle that is part of
the cradle assembly. Mount the top arc barrier to the rear arc barrier with four
angle brackets. Mount the front arc barrier to the top arc barrier with three angle
brackets. The top, rear, and front arc barriers must be made of 3/16 in. (4.76 mm)
thick insulating material with a UL 94V-0 flammability rating. These barriers
isolate arcing during an interruption. For minimum barrier dimensions and
locations, refer to Figure 2 and Detail A. For minimum distance from the center of
the cradle to both sides of the compartment (dimension “X”), see Figure 2.
Extend Top Arc Barrier
to Front of Enclosure
Compartment Width
Angle
Brackets
23.5
Top Arc Barrier
[1]
[1]
(597)
Angle Brackets
12 (305)
Rear Arc Barrier
(See Detail A)
Rear Arc Barrier
8.3
Angle of Cradle
Assembly
(211)
Front Arc Barrier
min.
Front
Arc
Barrier
29.50
(749)
Terminal Labels
Bus
Supports
1.58 (40)
min.
X
Dimensions are in inches (millimeters).
C of Cradle
L
27009702.eps
Warning Label
[1] 1.00 (25.4) minimum clearance required
on both sides of compartment for air flow.
0.28 (6) Dia.
0.88 (22)
Sensor (Frame) Size
1.16 (29)
3.51
13.43
2.6
(89)
(341)
(66)
“X” Min.
in
mm
400 A, 800 A, 1200 A, 1600 A
15.00
381
2000 A, 2500 A, 3000 A
18.00
457
Detail A
Figure 2: Terminal Labels and Arcing Clearance
© 1990 Square D All Rights Reserved
Courtesy of NationalSwitchgear.com
3
Drawout SE Circuit Breaker with MICROLOGIC™ Trip Unit
400 A to 3000 A Frames
ENCLOSURE
VENTILATION
Bulletin No. 80254-199-01F
September 1997
SE enclosures up to 1600 A do not require ventilation. SE enclosures 2000 A require
154 in2 of ventilation on the front of the enclosure. Place half (77 in2) of the
ventilation at the top, and half at the bottom of the enclosure.
SE enclosures 2500 A through 3000 A require 308 in2 of ventilation. Place equal
amounts of ventilation (154 in2) at the top and bottom of the front and rear of the
enclosure.
Ventilation requirements are based on one SE circuit breaker per enclosure. If more
than one device is mounted in an enclosure, it is recommended that tests be
conducted per UL 891.
An SE drawout circuit breaker cover must have at least three 1/4-20 securing
screws on each side. See Figure 3.
0.68 (17)
Flange
12.30
(312)
Dimensions are in inches
(millimeters).
0.50 (13)
Flange
Cutout
for
Breaker
15.48
(393)
29.50
(749)
8.13
(207)
27009703.eps
COVER
REQUIREMENTS
Figure 3: Circuit Breaker Cover
WIRING HARNESS
The wiring harness is the same for all ampere ratings and is supplied with the
cradle assembly. The following are recommendations for mounting a 42 in.
(1067 mm) wiring harness in a 36 in. (914 mm) wide or wider enclosure. See
“Wiring Harness and Connector Detail” on page 5 for illustration.
1. The wiring harness assembly should be mounted to the SE cradle assembly in
four places (locations A, B, C, D).
2. Place spring nuts over the two remaining holes on the front right side of the
cradle assembly.
3. Mount the terminal strip mounting bracket to the cradle assembly with two
1/4-20 machine screws.
4. The wire bundle is mounted in three places with one wire tie and two cable
clamps, and two 10-24x7/16" machine screws.
5. Route wiring harness through connector mounting plate from the front until
plug contacts mounting plate. Rotate harness until number 1 pin is located at
the top right hand position.
6. Align plug tabs with connector plate cutouts and insert plug. Push the plug
down until it rests on the bottom of the mounting plate slot and locks in place.
7. Use the 8-32x1/2" machine screw and lock washer to retain the plug in the
mounting plate (see “Wiring Harness and Connector Detail” on page 5).
NOTE: Insert the retaining screw from the rear. The retaining screw should insert above the
plug connector flange. Inserting the retaining screw through any portion of the plug molding
will result in breakage (see “Wiring Harness and Connector Detail” on page 5). All mounting
hardware for the 42 in. (1067 mm) wiring harness is supplied with the cradle assembly.
If the wiring harness length is more than 42 in. (1067 mm) or the section width is
less than 36 in. (914 mm) an alternative mounting means for the terminal block is
required.
4
Courtesy of NationalSwitchgear.com
© 1990 Square D All Rights Reserved
Bulletin No. 80254-199-01F
September 1997
Drawout SE Circuit Breaker with MICROLOGIC™ Trip Unit
400 A to 3000 A Frames
27009712.tif and 27009713.tif
Wiring Harness and
Connector Detail
Wire Guard
Wiring Harness Detail
(Front View)
Connector
Mounting Plate
8-32 x 1/2"
Machine Screw
and
Lock Washer
Cable Clamp
Plug Connector
A
C
D
10-24 x 7/16"
Machine Screw
B
Spring Nut
Cable Clamp
1/4-20
Machine
Screw
1/4-20
Machine
Screw
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
Terminal Strip
Mounting Bracket
10-24 x 7/16"
Machine Screw
SE Drawout Frame
Assembly (Cradle)
27009704.eps
Terminal
No. 1
Wire Tie
Connector Detail
8-32 x 1/2"
Machine Screw
and Lock Washer
Note position of connector with
regard to trombone assembly.
Secure wire bundle
to slide assembly
with cable tie.
© 1990 Square D All Rights Reserved
Courtesy of NationalSwitchgear.com
5
Drawout SE Circuit Breaker with MICROLOGIC™ Trip Unit
400 A to 3000 A Frames
Bulletin No. 80254-199-01F
September 1997
DIMENSIONS
18.24
(463)
17.14
(435)
18.44 (468)
5.00
(127)
13.74
(349)
8.52
(216)
8.43
(214)
8.18
(208)
5.00
(127)
1.00
(25.4)
Gas Shield
9.30
(236)
4.23
(107)
0.75 (19) dia.
0.50 (13) dia.
15.95
(405)
0.43
(11)
15.30
(389)
2.16 (55)
11.70
(297)
2.00 (51) dia.
1.50 (38) dia.
6.05
(154)
0.75 Drawout
(0.19) Hex Drive
5.35
(136)
Push to Close
ASKC-659
1.10
(28)
15.44
(392)
17.56
(446)
Push to Open
18.44
(468)
ASKC-669
17.32
(440)
12.95
(329)
4.25
(108)
11.95
(304)
0.55 (14) Conn. Engagement
3.44
(67)
0.38 (10)
4.12
(105)
0.98
(25)
15.60
(397)
5.00
(102) Max.
A
13.38
(340)
40°
8.62
(219)
4.85
(123)
5.00
(102)
Max.
A
1.40
(36)
6.80
(173)
4.95
(126)
Neutral Current Transformer
3000 A and smaller
3.00 (76)
1.29 (33)
1.29 (33)
7.84 (199)
12.96 (329)
Dimensions are in inches
(millimeters).
ASKC-670
Construction
Type
SED
Frame Size
Dimension “A”
in
Courtesy of NationalSwitchgear.com
mm
400–1200 A
2.75
70
1600–3000 A
4.00
102
Figure 4: SE Drawout Circuit Breaker Dimensions
6
3.00
(76)
© 1990 Square D All Rights Reserved
27009705.eps
12.25
(311)
6.58
(167)
Bulletin No. 80254-199-01F
September 1997
2000 A AND 3000 A
SE CRADLE BOTTOM
MOUNTING
Dimensions are in inches
(millimeters).
Drawout SE Circuit Breaker with MICROLOGIC™ Trip Unit
400 A to 3000 A Frames
Figure 5 illustrates 2000 A and 3000 A SE cradle bottom mounting. For more
information, refer to the SE Solid State Trip Circuit Breaker Manual, Bulletin
No. 48040-495. The approximate weight of the breaker and cradle assembly is
500 lbs.
3.00
Front
of
Enclosure
(76)
5.37
4.63
7.93
(136)
(118)
(201)
Six 0.219 holes for mounting
cradle to mounting channels.
Use 1/4-20 thread-forming
screws.
15.00
(381)
21.00
(533)
Mounting
Channels
Top View
0.50 (13) Min.
26.63 (676)
Inside Surface
of Enclosure Cover
16.88
(429)
7.24
(184)
4.74
6.65
(169)
(120)
Three 2.75 (70) x 1.25 (32)
10 GA mounting channels
(not supplied)
Side View
27009706.eps
Bottom of
Compartment
5.91
(150)
Figure 5: 2000 A and 3000 A SE Cradle Bottom Mounting
© 1990 Square D All Rights Reserved
Courtesy of NationalSwitchgear.com
7
Drawout SE Circuit Breaker with MICROLOGIC™ Trip Unit
400 A to 3000 A Frames
Bulletin No. 80254-199-01F
September 1997
Figure 6 illustrates 2000 A SE cradle side mounting. For more information, refer to
the SE Solid State Trip Circuit Breaker Manual, Bulletin No. 48040-495. The
approximate weight of the breaker and cradle assembly is 500 lbs.
2000 A SE CRADLE
SIDE MOUNTING
21.00 (533)
5.00
(127)
0.50
(13)
Min.
5.00
(127)
25.88 (657)
1.31
(33)
20.83 (529)
Inside
Surface of
Enclosure
Cover
0.56
(14)
dia.
4.61
(117)
1.75
(44)
0.81
(21)
Key
Interlock
Bracket
16.88
(429)
1.12 (28)
1.76 (44)
2.81
(71)
4.00 (101)
7.24 (184)
2.26 (57)
3.50 (89)
Bottom of 29.50 (749) Compartment
3.65
(93)
0.25
(6)
Detail B
0.70
(18)
11.65 (296)
See Detail B
Cradle mounting holes
1/2-13 hardware included.
Two angles of minimum
10 GA material thickness
are recommended to
support cradle assembly.
0.50
(13)
C Conn Typ
L
Note: There is a 0.50 in (12.7 mm) wide
stab for customer connection.
Breaker in Disconnect Position
Dimensions are in inches
(millimeters).
Wiring Harness
Length
12.25
(311)
Key
Interlock
in
mm
SE3CR1K2000
42
1067
Yes
SE3CR12000
42
1067
No
SE3CR2K2000
96
2438
Yes
SE3CR22000
96
2438
No
0.99 (25)
1.46 (37)
3.36 (85)
Figure 6: 2000 A SE Cradle Side Mounting
8
Courtesy of NationalSwitchgear.com
© 1990 Square D All Rights Reserved
20.83 (529)
27009707.eps
Cradle Assembly
Catalog No.
Breaker in Connected Position
Bulletin No. 80254-199-01F
September 1997
Drawout SE Circuit Breaker with MICROLOGIC™ Trip Unit
400 A to 3000 A Frames
Figure 7 illustrates 3000 A SE cradle mounting. For more information, refer to the
SE Solid State Trip Circuit Breaker Manual, Bulletin No. 48040-495. The
approximate weight of the breaker and cradle assembly is 500 lbs.
3000 A SE CRADLE
MOUNTING
21.00 (533)
5.00
(127)
0.50
(13)
Min.
5.00
(127)
26.63 (676)
1.31
(33)
20.83 (529)
Inside
Surface of
Enclosure
Cover
0.56
(14)
dia.
4.61
(117)
1.75
(44)
1.12
(28)
Key
Interlock
Bracket
16.88
(429)
1.63 (41)
1.74 (44)
2.81
(71)
5.00 (126)
7.24 (184)
1.26 (32)
3.50 (89)
Bottom of 29.50 (749) Compartment
3.65
(93)
0.70
(18)
11.65 (296)
Cradle mounting holes,
1/2-13 hardware included.
Two angles of minimum 10 GA
material thickness are recommended
to support cradle assembly.
1.00
(25.4)
Detail C
0.50 (13)
See Detail C
C Conn. Typ.
L
Note: There is a 1.00 in (25.4 mm) wide
stab for customer connection.
Breaker in Disconnect Position
Dimensions are in inches (millimeters).
Wiring Harness
Length
12.25
(311)
Key
Interlock
in
mm
SE3CR1K3000
42
1067
Yes
SE3CR13000
42
1067
No
SE3CR2K3000
96
2438
Yes
SE3CR23000
96
2438
No
0.99 (25)
1.46 (37)
3.36 (85)
20.83 (529)
27009708.eps
Cradle Assembly
Catalog No.
Breaker in Connected Position
Figure 7: 3000 A SE Cradle Mounting
© 1990 Square D All Rights Reserved
Courtesy of NationalSwitchgear.com
9
Drawout SE Circuit Breaker with MICROLOGIC™ Trip Unit
400 A to 3000 A Frames
Circuit breakers must be bussed per the sensor (frame) size. All bus bars and lug
landings (bussing) must be supported by means other than the cradle assembly.
The cradle assembly is not designed to support the bussing. Excessive weight on
the cradle assembly will affect the connection between the breaker and the cradle
assembly.
BUS BARS AND LUG
LANDINGS
1.00
(25.4)
2500 A
Detail D
27009709.eps
1.00
(25.4)
3000 A
Bulletin No. 80254-199-01F
September 1997
Table 2 lists the minimum size of terminal extensions required for 2500 and 3000 A
circuit breaker sensor (frame) sizes. These terminal extensions must be 11 in.
(279 mm) in length. Place extensions on each side of cradle bus as shown in
Detail D. All other bussing connectors are to be sized per UL 891. Figure 8 shows
the possible configurations for the terminal extensions. Terminal extensions are not
required on 2000 A and below circuit breaker sensor (frame) sizes. Bussing may be
run straight back from the cradle terminals on these lower amperages. Bussing to
be sized per UL 891.
Table 2: Terminal Extensions
Sensor (Frame) Size
Size of Copper Terminal Extensions
(Qty) in
(Qty) mm
2500 A
(3) 0.25 x 6.00
(3) 6.4 x 152
3000 A
(4) 0.25 x 6.00
(4) 6.4 x 152
Terminal
Extensions
11.00
(280)
Do not mount 2500 A and 3000 A
terminal extensions in this position.
Figure 8: Mounting Terminal Extensions
10
Courtesy of NationalSwitchgear.com
© 1990 Square D All Rights Reserved
27009710.eps
Min.
Bulletin No. 80254-199-01F
September 1997
Drawout SE Circuit Breaker with MICROLOGIC™ Trip Unit
400 A to 3000 A Frames
WIRE SIZE AND WIRE
BENDING
Circuit breakers 3000 A must use 90 °C insulated wire. Wire must be sized per
NEC® 75 °C Table 310-16. Circuit breakers 200 A through 2500 A may use 75 °C
insulated wire per NEC Table 310-16. Use UL 891 and NEC for wire bending
requirements. Adequate conduit entry area must be available.
LIFTING THE CRADLE
ASSEMBLY
Two large elongated holes are located on the upper rear of the cradle assembly side
plates for lifting. Use either hooks or a strap to lift the cradle assembly. If hooks are
used, a spreader bar must be used. If a strap is used, the strap must be positioned
to go through the lifting holes and over the top of the cradle bussing with a
spreader bar between the strap. See Figure 9 for both lifting methods. The
approximate weight of the cradle assembly is 225 lbs.
NOTE: Do not install the SE drawout circuit breaker into the cradle assembly until the cradle
assembly is installed in the enclosure, because the weight of the circuit breaker will affect the
balance of the cradle assembly while being lifted.
Spreader
Bar
Cradle
Bus
Lifting
Holes
Spreader
Bar
Cradle
Bus
Lifting with Hooks
Lifting with Straps
27009711.eps
Lifting
Holes
Figure 9: Lifting the Cradle Assembly
NOTE: Drawout crank (Catalog No. SEDC), or a 3/4-in. socket, extension, and ratchet or
breaker bar is required for ratcheting the SE drawout circuit breaker in and out of the cradle
assembly.
© 1990 Square D All Rights Reserved
Courtesy of NationalSwitchgear.com
11
Square D and
are Registered Trademarks and MICROLOGIC is a Trademark of
Square D Company.
NEC is a Registered Trademark of the National Fire Protection Association.
Electrical equipment should be serviced only by qualified electrical maintenance personnel. No
responsibility is assumed by Square D for any consequences arising out of the use of this material.
Bulletin No. 80254-199-01F September 1997 © 1990 Square D All Rights Reserved.