Description
Sigcom’s VECP Series includes the VECP-25 and VECP-50
voice evacuation control panels and the DVS-RM remote
microphones. The VECP-25 provides 25 Watts of output
power. The VECP-50 provides 50 Watts of output power.
Both VECP controls have a built-in digital message unit,
UL listed power supply, and a supervised microphone.
The digital message unit includes 2 voice messages and
4 field selectable alert tones. VECP control panels provide
four Class A or Class B supervised speaker circuits which
are configurable for either 25 or 70.7Vrms speaker loop
voltage.
Applications
The VECP Series control panels are designed for the
upgrade of existing fire alarm systems to add voice
evacuation capability without replacing the FACP, as well
as for new system. Typical applications include places
of assembly such as schools, theatres, places of worship,
office buildings, restaurants, and military facilities. In
addition, a built-in auxiliary audio input enables VECP
Series to interface with existing telephone paging
systems increasing the overall functionality of the system.
Operation
VECP Series control panels are extremely easy to add to
an existing fire alarm system interfacing directly to any
addressable or conventional FACP. Both models have
Typical Applications
Upgrade Existing Fire Alarm Systems
• Schools
• Theaters
• Places of Worship
• Healthcare Facilities • Military Facilities • Office Buildings
• Factories
• Restaurants
• Dormitories
two alarm inputs, one triggered by reverse polarity
(NAC output) and one by supervised dry contact
trigger. Additional features include a supervised integral
microphone plus the option for remote supervised
microphone; common alarm and fault relay outputs, an
on-board switch for system test, and digital signal meters
to display the power and voltage output on the speaker
circuits.
Features
• Connects to any FACP
• High efficiency Class D digital amplifier
• Activated with 24 VDC polarity reversing NAC circuit or dry-contact
• 60 seconds of pre-recorded digital voice message
• 4 alert tones and 2 standard voice messages with field selectable options
• 4 supervised speaker loop outputs (Class A or B)
• Field selectable 25/70 Vrms speaker loops
• Integral supervised microphone
• Remote microphone - supervised
• Dead Front locked Cabinet
VECP-25 / VECP-50 Specifications
Power Supply
AC Power
DC Power
50 Watt load
Standby
Battery Saver
120 VAC, 60 Hz; 2A
20.4 – 26.4 VDC regulated
2.75 A max at 24 VDC
0.21 A
80 mA
Alarm Activation Inputs
Primary1, 4-position, Class A, reverse polarity (NAC);
activates fire alarm message and tone;
10 – 30 VDC, 2 mA max.
Secondary
1, 2-position, reverse polarity,
end of NAC or last circuit device;
10 – 30 VDC, 5 mA max.
Auxiliary Message Inputs 2, normally-open (N.O.) dry contact;
5 mA max.; supervised;
activate non-fire auxiliary message and tone
Gnd Fault Impedance
65 KOhm
AC/Power Supply Fault Activation causes system to enter
battery saver mode
Auxiliary Audio Input
Interface to telephone and paging systems;
non-fire use only
Input Level
1 Vrms max
Impedance
10 KOhm
+
–
NAC
From
FACP
+
–
EOL
Auxiliary Message
Activation Inputs
+
–
10K EOL
Reverse
Polarity
Supervised
NAC Input
Microphone Input
Audio Outputs
Output Power
Voltage
Circuits
EOL Resistor
Gnd Fault Impedance
Common Relays
Trouble
Alarm
Installation
Dimensions
Enclosure Cut-in Size
Temperature Range
Humidity
Approvals/Listings
25 Watts (VECP-25), 50 Watt (VECP-50) total
(sinusoidal, RMS)
25 or 70.7 Vrms, field selectable Speaker
4, Class A (style Z) or Class B (style Y)
10 KOhm, 1 Watt; power limited
240 KOhm
Form-C contacts, 30 Vdc, 1 A resistive
Form-C contacts, 30 V , 1 A resistive
Surface or flush mount; indoor
20”h x 153/4”w x 5”d
183/4”h x 141/2”w x 4”d
32°F to 120°F (0°C to 49°C)
90% maximum, non-condensing;
UL 864 Control Units for
Fire Protective Systems (9th Edition)
UL 1711 Amplifiers for Fire Protective Systems
Specifications are subject to change without notice due to product improvements.
60 Second
Digital Messaging
Unit
Supervised
Microphone
VECP Series
10K EOL
Paging System
Interface
Supervised, internal microphone;
overrides pre-recorded messages
when paging during alarm
Internal 24 VDC
Power Supply &
Battery Charger
Common Alarm
& Trouble Relay
Outputs
25 Watt Digital
1
VECP 25/50
(4 Speaker Outputs)
3
25 Watt Digital
VECP 50
(4 Speaker Outputs)
PTT
1C
N.C.
N.O.
2C
N.C.
N.O.
2
4
4- 25 VRMS/70 VRMS
Class A/B
SPEAKER OUTPUTS
Ordering Information
ModelDescription
VECP-25
Voice Evacuation / Industrial Paging Control Panel - 25 Watts, 4 Speaker Circuits w/ Digital Message, Microphone and Power Supply
VECP-50
Voice Evacuation / Industrial Paging Control Panel - 50 Watts, 4 Speaker Circuits w/ Digital Message, Microphone and Power Supply
DVS-RM/P
VECP Series Supervised Remote Microphone - 3 Gang Plate Mount
DVS-RM/B
VECP Series Supervised Remote Microphone in surface mount key-locked enclosure
4 Wheeling Avenue; Woburn, MA 01801
Phone – (781) 933-0998 | Fax – (781) 933-5019
Email – sales@sigcom.com | www.sigcom.com
©2016 Signal Communications Corporation; all rights reserved
170109r0/VECP-25/50
Download PDF
Similar pages