OLS3S15KD0015PV-02
Online Topology
Pure Sine Wave
Smart Battery
Management
SNMP /HTTP
LCD Display
Tower Form
Featuring Online Double Conversion UPS topology, the Online S
(3-Phase) Series keeps transforming the 3-Phase input power
into 1-Phase output with quality power supply and provides the
highest level of power protection to demanding businesses who
value versatility, flexibility, manageability and performance.
Numerous engineering excellences showcase in this enterpriselevel application including Economy Mode, Converter Mode
and Smart Battery Management, which further enhance its
overall performance and capability for better operating
efficiency. With the perfect zero transfer time, the Online S
Series ensures continuous and seamless pure sine wave power
to all mission-critical devices.
This product comes with Remote Management Capabilities
which include the PowerPanel® Business Edition management
software and an optional SNMP/HTTP network management
card, enabling users to perform comprehensive network
management and monitoring including unattended-shutdown,
event logging, reporting, and notifications.




Medium Business
Corporate Data Center
Networking, Servers & Workstations
Industrial Equipment














Pure Sine Wave Output
Online (Double Conversion) UPS Topology
Available with Up to 4 Units in Parallel
Tower Form Factor
Economy Mode
Smart Battery Management
EMI, RFI, Surge and Spike Protection
Auto-Restart/Auto-Charge
Emergency Power Off (EPO) Port
Multifunction LCD Readout
USB & Serial Connectivity Ports
Extended Runtime (XL) Models
SNMP/HTTP Remote Management Capability (Optional)
PowerPanel® Business Edition Software
Powerpanel® Business Edition
Auto-shutdown Software
Online Double Conversion Topology
PowerPanel® Business Edition Management
Software, is compatible with Windows8, 7, Vista,
XP, 2000, Windows Server 2012, 2008, 2003,
VMware Esxi, Citrix Xenserver, Linux and Mac.
*Software functions may vary due to firmware version and/or hardware constraints.
Online (Double Conversion) topology provides an extra layer of
insulation from power problems. This is achieved by continuously
operating off battery power and having zero transfer time during
power outages. Online topology also stabilizes output frequency
and voltage, and eliminates any line noise that may be apparent in
industrial settings or when operating off generator power.
CISCO Compatible
CyberPower® works with Cisco on the latest version of
EnergyWise™ Compatibility.
Go to http://www.cpsww.eu/products/pdu/cisco_disclaimer.htm
for complete disclaimer.
CyberPower Systems Inc. All Rights Reserved.
www.cyberpower.com
Model Name
General
UPS Topology
Energy Saving
Active PFC Compatible
Input
Voltage
Input Voltage Range
Input Frequency Range
Rated Input current
Input Power Factor
Cold Start
Plug Type
Output
VA
Watts
On Battery Waveform
On Battery Voltage
Automatic Voltage Regulation (AVR)
On Battery Frequency
Outlets - Total
Outlet Type
Rated Power Factor
Harmonic Distortion
Transfer Time
Battery
Runtime at Half Load (min)
Runtime at Full Load (min)
Battery Type
Battery Size
Battery Quantity
User Replaceable
Typical Recharge Time
Smart Battery Management (SBM) Mode
Extended Battery Module
Surge Protection & Filtering
Surge Suppression
Management & Communications
LCD Control Panel
HID Compliant USB Port
Serial Port
Emergency Power Off (EPO) Port
LED Indicators
Audible Alarms
Software
SNMP / HTTP Remote Monitoring
Physical
Form Factor
Physical Size
Physical - UPS Module
Dimensions (WxHxD) (mm.)
Weight (kg.)
Environmental
Operating Temperature
Operating Humidity
Operating Elevation
Storage Temperature
Storage Relative Humidity
Online Thermal Dissipation
OLS3S15KE
OLS3S15KEXL
Double-Conversion
ECO Mode Efficiency > 97%
Yes
Double-Conversion
ECO Mode Efficiency > 97%
Yes
220 – 240Vac (Line to Neutral)/380 – 415Vac (Line to 220 – 240Vac (Line to Neutral)/380 – 415Vac (Line to
Line)
Line)
176 – 276Vac (Line to Neutral)/305 – 478Vac (Line to 176 – 276Vac (Line to Neutral)/305 – 478Vac (Line to
Line)
Line)
50/60Hz ± 10% (Auto-sensing)
50/60Hz ± 10% (Auto-sensing)
68.2A
68.2A
0.99
0.99
Yes
Yes
Terminal Block
Terminal Block
15000
13500
Sine Wave
208, 220, 230, 240Vac (Configurable)
15000
13500
Sine Wave
208, 220, 230, 240Vac (Configurable)
50/60Hz ± 0.05Hz
1
Terminal Block
0.9
THD < 2% at Linear Load, < 5% at Non-linear Load
0ms
50/60Hz ± 0.05Hz
1
Terminal Block
0.9
THD < 2% at Linear Load, < 5% at Non-linear Load
0ms
17.6
6.4
Sealed Lead-Acid
12V/9AH
20*2
Yes
Yes
BPSE240V82A
Depends on external batteries
Depends on external batteries
Sealed Lead-Acid
N/A
N/A
Yes
Depends on external batteries
Built-in Charger (4A max. )
Yes
BPSE240V82A
445 Joules
445 Joules
21 different settings options via the UPS Setting
menu
Yes
Yes
Yes
Yes
Yes
PowerPanel® Business Edition
Yes, with optional RMCARD302 / RMCARD303
21 different settings options via the UPS Setting
menu
Yes
Yes
Yes
Yes
Yes
PowerPanel® Business Edition
Yes, with optional RMCARD302 / RMCARD303
Tower
Tower
350 x 890 x 650
172
350 x 890 x 650
56
32 °F to 104 °F / 0 °C to 40 °C
0% - 90% non-condensing
0-3281 feet (0-1000 meters)
5 °F to 113°F / -15°C to 45 °C
0% - 95% non-condensing
3487 BTU/hr
32 °F to 104 °F / 0 °C to 40 °C
0% - 90% non-condensing
0-3281 feet (0-1000 meters)
5 °F to 113°F / -15°C to 45 °C
0% - 95% non-condensing
3487 BTU/hr
8 Hours
#All specifications are subject to change without notice. © 2015 CyberPower Systems. All Trademarks are the property of their owners.
CyberPower Systems Inc. All Rights Reserved.
www.cyberpower.com
Model
Voltage
Amperage
Physical
Dimensions (W x H x D) (mm)
Weight (kg)
Battery
Sealed Maintenance Free Lead Acid Battery
Interface
Typical Recharge Time
Environment
Operating Temperature
Humidity
BPSE240V82A
240VDC
82A
260 x 718 x 550
124
(40) 12V / 9AH
Terminal Block
Depends on external batteries
32~104℉ (0~40℃)
0~90% Non-Condensing
Power Module
Battery Module
OLS3S15KE/EXL
BPSE240V82A
CyberPower Systems Inc. All Rights Reserved.
www.cyberpower.com
Download PDF