fleet broadband_ura

SPECIFICATIONS
BR-1000
Model
GENERAL
IMO MSC. 128(75)
Standards
Bridge Panel
BR-1010
Cabin Panel
BR-1030
2.1 kg 4.6 lb
0.3 kg 0.7 lb
18.5 0.7"
BRIDGE PANEL
7" color LCD
480 x 234
Screen Size
Pixel Number
123 4.8"
114 4.5"
CABIN PANEL
12 VDC
Duty Lamp
Alarm Lamp
Buzzer
Panel Test
Input
Output
1.9 kg 4.1 lb
0.3 kg 0.7 lb
39
1.5"
250 9.8"
4.5
0.2"
18.5 0.7"
65.5 2.6"
9.5 0.4"
75 3.0"
120 4.7"
4- 5
82 3.2"
100 3.9"
Processor Unit
BR-1020
Watertight Timer Reset Panel
BR-1060
28.5
13.0 kg 28.6 lb
0.9 kg 1.9 lb
1.1"
88 3.5"
12 0.5"
440 17.3"
360 14.1"
158 6.2"
155 6.1"
354 13.9"
368 14.5"
392 15.4"
2- 11
POWER SUPPLY
PR-240
75
3.0"
61 2.4" 110 4.3" 61 2.4"
12 VDC
Watch Alarm Lamp
Bridge Alarm Lamp
Buzzer
Timer Reset
Output
75 3.0"
120 4.7"
Timer Reset Panel
BR-1040
6-R2.25
221 8.7"
TIMER RESET PANEL
Input
Bridge Panel (Flush Mount Type)
BR-1010
160 6.3"
Input
145 5.7"
178 7.0"
12 VDC
Duty Lamp
Alarm Lamp
Buzzer
12 VDC
Watch Alarm Lamp
Bridge Alarm Lamp
Buzzer
Timer Reset
82 3.2"
100 3.9"
145 5.7"
Output
1 ch
1 ch
118 4.6"
Timer Reset Panel Control
Output
4- 5
30
21 0.8"
12 0.5"
MODBUS
Cabin Panel Control
Power Fail
Panel Test
Remote ACK
System Failure
External Alarm
2 ch
Output
48 ch
12 ch
7 ch
Auto Mode
TCS Mode
1 ch
1 ch
12 ch
2 ch
1 ch
63
63
2.5" 2.5"
100base-TX
Alarm Input
Local ACK
Operator's Fitness
Autopilot Mode
196 7.7"
PROCESSOR UNIT
LAN
Input
65.5 2.6"
9.5 0.4"
21 0.8"
264 10.1"
250 9.8"
24 VDC
ENVIRONMENT
Temperature (IEC 60945-4)
Waterproofing (IEC 60529)
-15°C to +55°C
-15°C to +55°C
-15°C to +55°C
-15°C to +55°C
-25°C to +55°C
Front: IP22 Back: IP20
IP20
Front: IP22 Back: IP20
Front: IP22 Back: IP20
Front: IP56 Back: IP20
Bridge Panel
Processor Unit
Cabin Panel
Timer Reset Panel
Watertight Timer Reset Panel
Bridge Panel
Processor Unit
Cabin Panel
Timer Reset Panel
Watertight Timer Reset Panel
R6
3A
Fuse
LAN
EQUIPMENT LIST
24 VDC
100-115/
200-230 VAC
LAN
Remote ACK
.........
Operator Presence
VDR
Junction Box
(Local supply)
System Fail, External Alarm
*Necessary if 2 Processor Units are equipped
Remote ACK
*Max. 2 units in one system
Alarm Inputs, Local ACK
Processor Unit
BR-1020
HUB
HUB-101
Cabin Panel
BR-1030
Timer Reset Panel
BR-1040
Watertight Timer Reset Panel
BR-1060
Bracket for BR-1010 with Installation Materials
2nd
Processor Unit
BR-1020
Processor Unit
BR-1020
Alarm Inputs, Local ACK
1 unit
1 unit
1-14 unit(s)
1-4 unit(s)
1 unit
1 set
1 set
MODBUS x 2ch
BR-1010
BR-1020
BR-1030
BR-1040
PR-240
MJ-A3SPF0013-035 (3A)
Operator Presence, Autopilot Mode
Bridge Panel
Processor Unit
Cabin Panel
Timer Reset Panel
AC-DC Power Supply Unit
Cable (3.5 m) with 3A Fuse
Installation Materials and Spare Parts
Option
-
24 VDC
Power
Distribution
Box
Bridge Panel
BR-1010
AC/DC
Power Supply
PR-240
HUB
HUB-101
BR-1000
Standard
1
2
3
4
5
6
7
BR-1000
INTERCONNECTION DIAGRAM
Vibration (IEC 60945-4)
Model
125 4.9"
12 0.5"
360 14.1"
External Equipment
IAS
.........
Timer Reset Panel/
Watertight Timer Reset Panel
(BR-1040 / BR-1060)
External Equipment
Cabin Panel
BR-1030
Option or Local Supply
TRADEMARK REGISTERED
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE
FURUNO ELECTRIC CO., LTD. FURUNO FRANCE S.A.S. FURUNO NORGE A/S
FURUNO POLSKA Sp. Z o.o.
Nishinomiya, Hyogo, Japan
Phone: +81 (0)798 65-2111
Fax: +81 (0)798 65-4200, 66-4622
Bordeaux-Mérignac, France
Phone: +33 5 56 13 48 00
Fax: +33 5 56 13 48 01
Ålesund, Norway
Phone: +47 70 102950
Fax: +47 70 102951
Gdynia, Poland
Phone: +48 58 669 02 20
Fax: +48 58 669 02 21
FURUNO U.S.A., INC.
FURUNO ESPAÑA S.A.
FURUNO SVERIGE AB
FURUNO DEUTSCHLAND GmbH
Camas, Washington, U.S.A.
Phone: +1 360-834-9300
Fax: +1 360-834-9400
Madrid, Spain
Phone: +34 91-725-90-88
Fax: +34 91-725-98-97
Västra Frölunda, Sweden
Phone: +46 31-7098940
Fax: +46 31-497093
Rellingen, Germany
Phone: +49 4101 838 0
Fax: +49 4101 838 111
FURUNO (UK) LIMITED
FURUNO DANMARK AS
FURUNO FINLAND OY
FURUNO EURUS LLC
Havant, Hampshire, U.K.
Phone: +44 23 9244 1000
Fax: +44 23 9248 4316
Hvidovre, Denmark
Phone: +45 36 77 45 00
Fax: +45 36 77 45 01
Espoo, Finland
Phone: +358 9 4355 670
Fax: +358 9 4355 6710
St. Petersburg, Russian Federation
Phone: +7 812 767 15 92
Fax: +7 812 766 55 52
08085U Printed in Japan
Catalogue No. M-1543
FURUNO’s Bridge Alarm System manages the onboard
equipment alarms and monitors watch officer’s
presence for early detection of emergency
Bridge alarm system
The BR-1000 monitors the equipment
alarms and presents the equipment status
in the Bridge Panel.
Bridge Panel
Cabin Panel
Timer Reset Panel
Watertight Timer Reset Panel
2. If the alarm is not acknowledged in the First Stage, the
BR-1000 transmits the alarm to the selected Cabin Panels.
(Second Stage)
sMeets IMO resolution MSC.128(75) for “Bridge Navigational Watch Alarm System”
sCollectively manages and presents the alarm information on the display unit
sAlarm information is sorted and displayed according to the set priority
sWatch Safety System to monitor the watch officer’s presence to minimize failure at avoiding
Normal (No Alarm) Mode
1. When an equipment alarm is activated, the Bridge Panel
automatically displays a list of the equipment generating
alarm. “Bridge Alarm” icon flashes and the alarm is
generated in 30 seconds. (First Stage)
3. If the alarm is not acknowledged within the pre-set time, the
system transmits the alarm to all Cabin Panels. (Third Stage)
The list of the equipment
generating alarm is shown, and
“Bridge Alarm” icon flashes.
4. The buzzer stops when the officer presses the [BUZ STOP] /
[ACK] button. When the cause of the alarm is removed, the
Bridge Panel returns to the normal mode.
The buzzer stops when the officer
presses the [BUZ STOP] / [ACK] button.
However, if the problem is not resolved,
the equipment name and “Bridge Alarm”
icon will be shown in a different color.
When the problem is resolved, the
display turns to the normal mode.
approaching danger
sTransmits alarm to the backup officer in accommodation, if watch officer fails to respond to the
active alarm or emergency call
s3 operation modes available: One-Man, Bridge Attended and Harbour
Watch safety system
The Bridge Alarm System BR-1000 collectively controls the
Cabin Panels installed other sections of the vessels in order
warning notice from equipment onboard and monitors watch
to inform backup officers of the watch officer’s absence.
officer’s presence for maritime casualty avoidance. The
BR-1000 performs the following two functions: Bridge alarm
system and Watch safety system.
The BR-1000 offers 3 operation modes: One-man, Bridge
Attended and Harbour. In One-Man operation mode, both
bridge alarm system and watch safety system work. In
In the bridge alarm system function, the Bridge Panel of the
Bridge Attended mode, visual and audible alarm will be
BR-1000 in the wheelhouse generates the visual and audible
generated in the wheelhouse, but the alarm will not
alarms upon the equipment alarm’s activation. If the alarm is
transferred to the Cabin Panels. In Harbour mode, visual
not acknowledged at this stage, the BR-1000 will transmit the
alarm will be activated only on the Bridge Panel in the
alarm to the Cabin Panels in other sections of the vessel.
wheelhouse, not be transferred to the Cabin Panels.
Also, the BR-1000 monitors the watch officer’s presence
The BR-1000 meets the IMO MSC. 128(75). The Processor
through watch safety system function. A watch officer is
Unit has total of 48 ports to interface the equipment onboard
required to press any keys of the equipment or Timer Reset
and watches their alarm status. It also has 7 ports for the
Panel at certain intervals. When the officer fails to press the
operator’s presence inputs. Watertight Timer Reset Panel
key within pre-set intervals, the visual and audible alarms will
can also be selected (optional supply). Up to 14 Cabin
be generated in the wheelhouse. If the officer doesn’t
Panels can be installed on a ship.
respond to the alarm, the BR-1000 transmits the alarm to the
The BR-1000 detects the watch officer’s
presence to ensure constant watch.
1. While the watch safety system is active, the watch officer in
the wheelhouse have to press the button on Timer Reset
Panel or operate interfaced equipment at certain intervals.
(3-12 min.)
If the watch officer does not press the button on Timer Reset
Panel or operate interfaced equipment, the Bridge Panel and
the Timer Reset Panel generate the visual and audible
alarms in 30 seconds. (First Stage)
The progress bar at bottom left
marked out by degrees.
2. If the alarm is not acknowledged in the First Stage, the
BR-1000 transmits the alarm to the selected Cabin Panels in
the back-up officer’s room and pubic room. (Second Stage)
3. If the alarm is not acknowledged within the pre-set time, the
system transmits the alarm to all Cabin Panels. (Third Stage)
4. The buzzer stops when the officer presses the [BUZ STOP] /
[ACK] button. The Bridge Panel will reset the timer and show
the normal mode, when the alarm is acknowledged by the
watch officer.
If the watch officer does not press the
button on Timer Reset Panel or
operate interfaced equipment, the panel
will turn to the visual alarm mode.