Power Monitoring Single-Circuit | Power and Energy Meters
E61C20
Basic Power Monitoring with Ethernet
Connection
Ethernet
Easy installation
Easier Internet connection Standard 96x96 mm size…easy
installation with standard size
and no-tool clips
Multi-tariff
Digital I/O
Track power use at peak and
off-peak times
Synchronize with external pulses
APPLICATIONS
E61C20
• Basic THD monitoring
• Energy and cost allocation
• Industrial monitoring
• Billing verification and energy
procurement
The E61C20 Panel Mount Power and Energy Meter provides basic four
quadrant metering capability with Modbus communication via Ethernet
cable. It includes voltage and current inputs with digital and optical
outputs with a multi-tariff feature for storing accumulated energy data.
The E61C20 requires external power to operate.
LED OPTICAL OUTPUT
SPECIFICATIONS
CONTROL POWER
Pulse Width (orange LED)
200 µsec
Pulse Frequency
50 Hz max.
AC
100 to 277 VacL-N ± 10%; 100 to 415 VacL-L ± 10%
COMMUNICATION
DC
125 to 250 Vdc ± 20%
Ethernet Port
AC Burden
5 W/11 VA max. at 415 Vac
MEASUREMENT ACCURACY
DC Burden
4 W max. at 125 Vdc
Accuracy
0.5%; IEC 61557-12 PMD/[SD|SS]/K70/0.5
Frequency
50/60 Hz ± 5 Hz
Fuses
500 mA
Real Power
and Energy
0.5%; Class 0.5 as per IEC 61557-12; Class 0.5S as
per IEC 62053-22
Wire Size
0.82 to 3.31 mm2 (18 to 12 AWG)
Terminal Block Torque
0.5 to 0.6 N·m (4.4 to 5.3 in·lb)
Reactive Power
and Energy
Class 2 as per IEC 61557-12; Class 2S as per IEC
62053-23
Current, Phase
0.5%; Class 0.5 as per IEC 61557-12
Voltage, L-N
0.5%; Class 0.5 as per IEC 61557-12
VOLTAGE INPUTS
Measured Voltage
UL CAT III, 20-347VL-N /35-600VL-L (Delta)
IEC CAT III, 20-400VL-N /35-690VL-L
Frequency
50/60 Hz
10/100 Mbps; Modbus TCP/IP; 1 port
OPERATING CONDITIONS
Operating Temp. Range
-25 to 70 °C (-13 to 158 °F)
5 to 95% RH noncondensing
Display functions to -25 °C with reduced
performance
CURRENT INPUTS
Nominal Current
1 A or 5 A
Measured Current
5 mA to 8.5 A
Storage Temp. Range
-40 to 85 °C (-40 to 185 °F)
Withstand
20 A continuous; 50 A@10 sec/hr;
500 A@1 sec/hr
Altitude of Operation
< 2000 m
50/60 Hz
Limited Warranty
Frequency
DIGITAL OUTPUT
WARRANTY
Maximum Load Voltage
40 Vdc
Maximum Load Current
50 mA
On Resistance
50 Ω max.
Pulse Width
50% duty cycle
Pulse Frequency
25 Hz max.
Leakage Current
0.03 µA
Isolation
5 kV RMS
Approvals
CE; UL61010-1; IEC 61010-1; IEC62052-11;
IEC61557-12
Housing
Pollution Degree 2, Installation Category III
*
* The CE mark indicates RoHS2
compliance. Please refer to the CE
Declaration of Conformity for additional
details.
800.354.8556 | +1 503.598.4564 | sales@veris.com | intl@veris.com | www.veris.com
TM
2 years
COMPLIANCE INFORMATION
HQ0005956.C 0117
Power Monitoring Single-Circuit | E61C20
ORDERING INFORMATION
WIRING DIAGRAMS
E61C20
Voltage Inputs
INSTANTANEOUS RMS VALUES
Control Power
UL CAT III, 20 to 347 V L-N/35 to 600 V L-L
IEC CAT III, 20 to 400V L-N/35 to 690 V L-L
Bi-directional energy measurements current (per phase and
neutral)
•
Voltage (total, per phase L-L and L-N)
•
Frequency
•
Real, reactive, and apparent power (total and per phase)
•
True power factor (total and per phase)
•
V1
(1)
V2
(2)
V3
(3)
100 to 277 V L-N/415 V L-L ±10% ~
50/60 ± 5 Hz < 11 VA
125 to 250 V ± 20% < 4 W
L1 L2
(8) (9)
V4
(4)
ENERGY VALUES**
Accumulated active, reactive and apparent energy
•
POWER QUALITY MEASUREMENTS
THD, thd (Total Harmonic Distortion) I, VACL-N , VACL-L per phase
•
OTHER MEASUREMENTS
Alarm counters and alarm logs
•
DATA RECORDING
Min/max of instantaneous values, plus phase identification
•
Alarms with 1s timestamping
•
Data logging
•
Status Input/Digital Output
40 V
max. 36 V
max. 24 V
20 mA max.
8 mA max.
D1+ D2+
S1+ S2+ −/C +
(60) (62)
(40) (42) (57) (56)
DEMAND VALUES
Current average
•
Active power
•
Reactive power
•
Apparent power
•
Demand calculation (sliding, fixed and rolling block, thermal
methods)
•
Synchronization of the measurement window to input,
communication command or internal clock
•
Settable demand intervals
•
INPUTS & OUTPUTS
Two digital outputs (form A relay)
•
Two digital inputs with timestamp
•
Whetting voltage
•
Act
(30)
Link
10/100
Modbus TCP/IP
(10) (11) (12) (13) (14) (15)
I1+ I1- I2+ I2- I3+ I3-
Current Inputs
1 A/5 A nom., 0.0005-5(6) A
DIMENSIONAL DRAWING
0.5”
(13 mm)
3.1”
(79 mm)
2.8”
(72 mm)
3.6”
(91 mm)
3.8”
(96 mm)
4.2”
(108 mm)
3.8”
(96 mm)
800.354.8556 | +1 503.598.4564 | sales@veris.com | intl@veris.com | www.veris.com
HQ0005956.C 0117
TM
Download PDF