Metered Rack PDU
Overview
The American Power Conversion (APC®) Metered
Rack Power Distribution Unit (PDU) distributes power
to devices in the rack. It has a sensor that measures the
current that it and its attached devices use. It can be
monitored through Web, Telnet, SNMP, SSH, or
InfraStruXure® Central interfaces.
Outlets. The Rack PDU has twenty IEC-320-C13 out-
lets and four IEC-320-C19 outlets.
Display Interface. A digital display shows
aggregate current being used by the Rack PDU.
Power cord. The 10-foot (3.05-meter) power cord terminates with a NEMA L6-30 connector.
pdu0289b
AP7841
Specifications
Electrical
Input connector
NEMA L6-30 plug
Output connectors
20–IEC-320-C13,
4–IEC-320-C19 outlets
Nominal input voltage
200-240 VAC
Acceptable input voltage
± 10% of normal voltage
Input frequency
50/60 Hz
Maximum input current
30 A (24 A UL (C-UL) derated)
Overcurrent protection
(internal)
(2) 20 A 2-pole circuit breakers
Physical
Size (H × W × D)
Shipping Dimensions
(H × W × D)
63.75 × 2.19× 1.73 in
(161.92 × 5.56× 4.39 cm)
84.00 × 6.00× 5.00 in
(213.36 × 15.24×12.7 cm)
Weight
12.50 lb (5.67 kg)
Shipping weight
14.50 lb (6.58 kg)
Environmental
Elevation (above MSL)
Operating
Storage
0 – 10,000 ft (0 – 3000 m)
0 – 50,000 ft (0 – 15 000 m)
Temperature
Operating
Storage
–5 to 45° C (23 to 115° F)
–25 to 65° C (–13 to 149° F)
Humidity
Operating
Storage
5 – 95% RH Non-condensing
5 – 95% RH Non-condensing
Compliance
EMC verification
FCC Class A,
ICES-003 Class A, VCCI-A
Safety verification
UL (C-UL) listed, PSE
Customer support and warranty information is available at the APC Web site,