Metron Fire Pump Controls and Accessories

Metron Fire Pump Controls and Accessories
Microprocessor Based Wye-Delta
Reduced Current Type Starting
NEW
PRODUCT
‘PILOT’ SERIES MPT430 (Open Transition) - MPT435 (Closed Transition)
Wye-Delta controllers require six leads from the motor to the
controller. These leads are connected by the controller first in the
Wye configuration which draws 33% of normal starting current
and develops 33% of normal starting torque. After a short time
delay, the controller then connects the motor winding in a Delta
configuration, applying full voltage, drawing full load running current
and developing full running torque.
Only the highest quality components, UL Listed or Recognized, are
used throughout to assure the best possible reliability. The cabinet
is fabricated of heavy 12 gauge reinforced steel, with Type 3R
supplied as standard and rated 60°C. All field wiring and service
connections may be made from the front, allowing the controller to
be mounted flush against a wall.
Metron fire pump controllers conform to the latest requirements of
the NFPA 20, UL 218 and FM 1321/1323, and bear the labels of
Underwriters Laboratories and Factory Mutual.
Controllers are completely wired, assembled, and tested at the
factory before shipment and ready for immediate installation.
PATENTED
TECHNOLOGY
MPT430-435 0817
UL218
FM1321/1323
MEMBERS
Metron Fire Pump Controls and Accessories
Touch Screen Features
Standard Features
»» The Microprocessor based logic with real time/date clock
capable of running 7+ years without AC power. Includes low
battery indicator.
»» Large 7” color LCD touch screen
»» Simultaneous display on Home screen for 3 phase
amperage/voltage, system pressure, start pressure, stop
pressure, system status, alarm status, date and time.
»» On-screen Icons for Pilot/Quick Start, System Set Points,
User Settings, Data Log, Diagnostics, and others for ease of
installation and data log/event history retrieval.
»» Let Metron’s “Pilot” feature guide you through the controllers
startup settings. The “Pilot” feature guides the user
automatically step-by-step through the settings required at
start up. Searching through multiple menus to locate settings
is eliminated. “Pilot” appears on the touch screen on initial
power up, or by pressing the “Pilot” Icon.
»» View data log/event history in Calendar screen to easily find
a specific event by touching the day on the calendar month
»» The on-board data log memory can store up to 18 months of
event history (approx. 112,000 events), and over 10 years of
event history with a 2G USB Flash Drive. Data/Event log can
store over 10+ years of time and date stamped events. Real
time clock is accurate to plus/minus 2 minutes per year over
the full temperature range. The event history can be viewed
by scrolling on the display or by saving it to a USB flash
drive. The event history is recorded as a .CSV file and can
be easily opened as an Excel file.
»» Multi level password protection
»» 60°C rated with Type 3R enclosure as standard
»» For added safety a through door USB port is provided to
access data logs/event history without opening the controller
door.
»» Internal controller temperature monitored and data logged as
standard
»» Status LED’s on PB board inputs/outputs provide visual
indication of on/off status
»» Pressure transducer fault LED
»» System Self Test on power up
»» Serial communication to PC boards reduces number of wire
for improved reliability.
»» Single logic control for operation of both the fire pump
controller and transfer witch.
»» Monitoring of the PC board inputs/outputs through the touch
screen
»» Phase rotation selectable through “Pilot feature” or Congif
Icon
»» Foreign language selectable
»» Modbus communication Protocol via RS485 port
»» Controllers are suitable for use as Service entrance
equipment
»» 600 PSI rating provided as standard.
Utilizes a manifold block for the pressure
transducer and drain solenoid valve that
eliminates the need for copper plumbing
with Teflon tape, significantly reducing
the possibility of water leaks.
MPT430-435 0817
www.metroninc.com
Metron Fire Pump Controls and Accessories
Auxiliary Programs
The controller includes as standard six (6) discrete
auxiliary inputs and six (6) outputs. These auxiliary I/O
are in addition to those required by NFPA 20 UL and
FM.
All auxiliary I/O can be field programmed on the touch
screen. Expandable 12 channel I/O board for additional
alarms, expandable to 168 I/O. All 48 aux programs
can have a custom message.
Event Messages
• CRR ENERGIZED/DEENERGIZED
• EVENT MESSAGES
• REMOTE TEST START
• CSR ENGERGIZED/DEENERGIZED
• MANUAL TEST START
• AUTO TEST START
• LOAD SHED
• MODBUS TEST START
• SOFT START ON
• REMOTE START
• MANUAL STOP
• MODBUS START
• HIGH ZONE CALL TO START
• DELUGE START
Each record tracks:
• Date and time
• Pressure
• Voltage and current
• Login state
• Pressure
• Internal temperature
• State of every alarm
• The I/O state of all PCB's (excluding any add-on
boards)
• Active start conditions
• The state of all aux programs (48 aux programs
available)
• Power available
• ACCELERATION TIMER ON
• REMOTE LOCKOUT
• PRESSURE TRANSDUCER
FAILURE START
Events and Alarms
• AUTO STOP
• REMOTE LOCKOUT CLEARED
• SUPERVISORY POWER
FAILURE START
• DUMP VALVE OPENED
• LOW PRESSURE START
• DUMP VALVE INSUFFICIENT
DISCHARGE
• DUMP VALVE CLOSED
• LOCAL START
• SYSTEM REBOOT
• PUMP RUNNING
Alarm Messages
Each alarm occurred or cleared
• PHASE FAILURE
• FAIL TO START
• PHASE REVERSAL
• FAIL TO STOP
• PHASE OVER/UNDER
VOLTAGE
• LOCKED ROTOR
• PHASE OVER/UNDER
FREQUENCY
• LOW SUCTION
• MOTOR OVERLOAD
• PRESSURE TRANSDUCER
FAULT
• LOW/HIGH PRESSURE
• LOW ZONE FAIL TO START
• LOW ZONE QUIT
• SUPERVISORY POWER
FAILURE
• LOSS OF POWER
Model Number Designation
Example: MPT435-75-480-H
MPT435 -- Model Type
- xXX -- Horsepower Rating
- XXX -- Voltage Rating
- X -- Option Designation(s)*
Ratings
VOLTS
200-208
220-240
380-415
460-480
200-208
220-240
380-415
460-480
550-600
*Options are listed on next page.
MPT430-435 0817
www.metroninc.com
HP -- RMS SYMMETRICAL
15-150 -- 100kA
15-200 -- 100kA
15-300 -- 100kA
15-400 -- 100kA
200-250 -- 50kA
250-300 -- 50kA
350-350 -- 50kA
500-600 -- 50kA
15-400 -- 22kA
Metron Fire Pump Controls and Accessories
Contact Us
Options
Option H: Space Heater
If the ambient atmosphere is especially damp, a space
heater rated at 100 watts may be supplied to reduce
moisture in the cabinet. A thermostat is supplied
as standard with this option. A humidistat may be
substituted if specified.
Enclosure Options
Type 3R is standard. The following UL Type enclosures
are available:
Type 4
Type 4X (painted cold roll steel)
Type 4X (304 or 316 Stainless Steel)
Type 12
Consult factory for additional options.
US PATENTS
US 8,482,307 B2 Method For Prevention
of Untested PC Boards from Being Used
In A Fire Pump Control System.
NORTH & SOUTH AMERICA
Hubbell Industrial Controls, Inc.
Metron Fire Pump Control Division
4301 Cheyenne Dr., Archdale, NC 27263
Phone: 336-434-2800, Fax: 336-434-2801
salesmail@metroninc.com
www.hubbell-icd.com
EUROPE
Metron Eledyne
18 Autumn Park, Dysart Road
Grantham, Lincolnshire, NG31 7DD, United Kingdom
Tel:+44 (0) 1476 516120, Fax:+44 (0) 1476 516121
info@metroneledyne.co.uk
TAIWAN
Hubbell-Taian Co. Ltd.
Contact Person: Jimmy Wu
Tel: (02)2522 1862 ext.10, Fax: (02)2522 1872
6th Floor, 156-1, Sung Chiang Road, Taipei, Taiwan
jwu@hubbell-taian.com.tw
CHINA
Hubbell-Anmex (Shanghai) Trading Co., Ltd
Contact Person: Derek Chen
6H, Zhao-Feng Universe Building, No. 1800, West
Zhongshan Rd., Shanghai 200235, China
Tel: 86-21-64400151, 64400156, Fax: 86-21-64400152
Mp: 86-13391373007
dchen@hubbell-anmex.com.cn
PHILIPPINES
Hubbell-Taian Co. Ltd.
Philippine Representative Office
Contact Person: Wency Villas-Besa
Unit 23 Parc House Bldg, #227 EDSA, Greenhills,
Mandaluyong City 1556, Philippines
Tel: 632-6556460, Fax: 632-6556421
DL WL: 632-8717389
wency@hubbelltaian.com.ph
www.metroninc.com
Hubbell Industrial Controls, Inc. • 4301 Cheyenne Dr., Archdale, NC 27263
PH: 336-434-2800 • FAX: 336-434-2809 • Email: salesmail@metroninc.com
MPT430-435 0817
© Hubbell Incorporated. All rights reserved. Specifications subject to change without notice.
Printed in USA.
Download PDF
Similar pages