UL 40-12
12V 40AH
General
UL40-12
Terminal Type
Container Material
Rated Capacity
Part Number:
UL40-12
Length:
197 ± 2 mm (7.76 inches)
Width:
165 ± 2 mm (6.49 inches)
Container Height:
170 ± 2 mm (6.69 inches)
Total Height (with terminal):
170 ± 2 mm (6.69 inches)
Approx Weight:
Approx 13kg (28.66lbs)
Normal Voltage
12V
Normal Capacity (20HR)
40AH
Standard Terminal
F10
Optional Terminal
F6
Standard Option
ABS
Flame Retardant Option (FR)
UL94:VO
40.0 AH/4.08A
(20hr, 1.80V/cell, 25°C / 77°F)
38.5 AH/4.00A
(10hr, 1.80V/cell, 25°C / 77°F)
31.5 AH/6.89A
(5hr, 1.75V/cell, 25°C / 77°F)
31.2 AH/10.4A
(3hr, 1.75V/cell, 25°C / 77°F)
24.4 AH/24.4A
(1hr, 1.60V/cell, 25°C / 77°F)
Max Discharge Current
480A (5s)
Internal Resistance
Approx 9mΩ
Discharge Characteristics
Operating Temp. Range
Discharge: -15 ~ 50°C (5 ~ 122°F)
Charge: 0 ~ 40°C (5 ~ 104°F)
Storage: -15 ~ 40°C (5 ~ 104°F)
Nominal Operating Temp. Range
25 ± 3°C (77 ± 5°F)
Cycle Use
Initial Charging Current less than 12.0A.Voltage
Standby Use
No limit on Initial Charging Current Voltage
Capacity affected by Temperature
40°C (104°F) 103%
25°C (77°F) 100%
0°C (32°F) 86%
Design Floating Life at 20°C
10 Years
Self Discharge
Ultracell batteries may be stored for up to 6 months at 25°C(°77F) and then a refresh charge is required. For
higher temperatures the time interval will be shorter.
Dimensions
F10 Terminal
2
2
203
199
6 [0.236]
8.5 [0.335]
16 [0.63]
97 2
71 2
8 [0.315]
17 [0.669]
156
255
2
2
ALL DATA IS SUBJECT TO CHANGE WITHOUT NOTICE
1
Ultracell (UK) Ltd | Vesty Business Park | Vesty Road | Liverpool | L30 1NY | United Kingdom
Tel: +44 (0) 151 523 2777 Fax: +44 (0) 151 523 0855 Email: info@ultracell.co.uk
www.ultracell.co.uk
ISO9001
Constant Current Discharge (Amperes) at 25°C (77°F)
F.V/Time
5 min
10 min
15 min
20 min
30 min
45 min
1h
2h
3h
4h
5h
6h
8h
10h
20h
1.85V/cell
68.5
53.8
45.8
38.3
30.4
23.0
18.9
12.0
9.50
7.76
6.25
5.44
4.42
3.78
2.06
1.80V/cell
91.9
68.8
55.3
45.3
35.9
26.8
21.1
13.1
10.2
8.28
6.72
5.84
4.69
4.00
2.08
1.75V/cell
103.6
75.6
60.4
48.7
37.3
27.8
22.1
13.6
10.4
8.47
6.88
6.00
4.77
4.04
2.10
1.70V/cell
114.1
82.4
64.5
51.2
38.8
28.9
22.8
14.1
10.7
8.69
7.06
6.12
4.84
4.08
2.14
1.65V/cell
125.8
88.9
68.6
54.4
40.9
29.6
23.6
14.5
11.2
8.99
7.26
6.26
4.91
4.16
2.17
1.60V/cell
138.8
96.5
73.3
57.9
43.2
30.9
24.4
15.0
11.5
9.27
7.50
6.40
4.96
4.21
2.18
Constant Power Discharge (Watts) at 25°C (77°F)
F.V/Time
5 min
10 min
15 min
20 min
30 min
45 min
1h
2h
3h
4h
5h
6h
8h
10h
20h
1.85V/cell
125.2
99.4
85.4
72.2
58.0
44.3
36.4
23.3
18.5
15.2
12.3
10.7
8.73
7.47
4.08
1.80V/cell
166.2
125.5
101.8
84.1
67.4
51.1
40.5
25.3
19.8
16.1
13.1
11.4
9.23
7.90
4.11
1.75V/cell
183.4
135.7
109.8
89.6
69.4
52.5
42.2
26.1
20.1
16.4
13.4
11.7
9.36
7.97
4.15
1.70V/cell
196.4
144.6
115.6
93.4
71.8
54.4
43.4
27.1
20.6
16.8
13.7
11.9
9.49
8.05
4.23
1.65V/cell
213.5
154.6
122.0
98.5
75.1
55.3
44.5
27.7
21.4
17.3
14.0
12.2
9.61
8.20
4.28
1.60V/cell
230.0
164.0
128.3
103.8
78.8
57.3
45.9
28.5
22.0
17.8
14.5
12.4
9.69
8.27
4.29
Terminal Voltage (V)
Discharge Characteristics
12V
Battery
(V)
6V
4V
2V
Battery Battery Battery
(V)
(V)
(V)
13.0
6.5
4.33
2.16
12.0
6.0
4.00
2.00
11.0
5.5
3.66
1.84
10.0
5.0
3.33
1.68
9.0
4.5
3.00
1.52
8.0
4.0
2.67
1.36
Float Charging Characteristics
Charge Charging Charging
Volume Current Voltage
%
(XCA)
(V)
(V)
Temperature:25°C(77°F)
0.4C
1C
3C
1
2
4
0.207C
120
110
100
90
80
70
60
50
40
30
20
10
0
0.093C 0.05C
0.628C
2C
6 8 10
20
40 60
2
4
Min
6 8 10
20
0.25
0.20
0.15
15.0
7.5
1.40
7.0
13.0
6.5
0.10
12.0
6.0
0.05
11.0
5.5
0.10CA-2.25V/cell temperature 25°C
Charging
Voltage
(V)
2.50
Charged Volume
2.33
Charge Voltage
(Constant 2.25v/cell)
2.17
After 50% Discharge
2.00
After 100% Discharge
1.83
Charging Current
0
0
h
4
8
16
12
20
24
28
32
36
40
Charging Time (Hours)
Discharge Time
Temperature Effects in Relation to Battery Capacity
Effect of Temperature on Long Term Float Life
120
Capacity (%)
Life (years)
0.1CA
100
0.17CA
0.25CA
80
60
10
1
40
20
0.1
-20
-10
0
10
20
30
40
50
60
10
Temperature (°C)
Cycle Life in Relation to Depth of Discharge
Remaining Capacity (%)
Capacity(%)
100
80
40
30%
DOD
Ambient Temperature:
25°C (77°F)
20
0
0
200
400
600
800
1000
25 C
A
0
60
0
0
40
B
30 C
40 C
C
20
0
2
4
6
8
10
Storage Time (Months)
12
A
No supplementary required
(Carryout supplementary charge before use if 100% capacity is required.)
B
Supplementary charge required before use. Optional charging way as below:
1. Charged for above 3 days at limited current 0.25CA and constant voltage 2.25V/cell.
2. Charged for above 20 hours at limited current 0.25CA and constant voltage 2.25Vcell.
3. Charged for 8 ~ 10 hours at limited current 0.05 CA.
C
Supplementary charge may often fail to recover the capacity.
The battery should never be left standing till this is reached.
1200
Number of Cycles
100C
80
0
50%
DOD
60
50
100
120
100%
DOD
40
Temperature (C)
Self Discharge Characteristics
Testing condition
Discharging:current 0.17C (FV 1.7V/cell);
Charging:current 0.25C max, voltage 2.45V/cell;
Charging volume:125% of discharged capacity.
60
30
20
ALL DATA IS SUBJECT TO CHANGE WITHOUT NOTICE
2
Ultracell (UK) Ltd | Vesty Business Park | Vesty Road | Liverpool | L30 1NY | United Kingdom
Tel: +44 (0) 151 523 2777 Fax: +44 (0) 151 523 0855 Email: info@ultracell.co.uk
www.ultracell.co.uk
ISO9001
Download PDF