SAS810FHL-7 Thermostat for floor heating

SAS810FHL-7 Thermostat for floor heating
SAS810FHL-7 is a programmable thermostat designed for floor warming application or helping to limit
floor temperature. This thermostat can be used for hot water radiant heating systems.
SPECIFICATION:
Power source ……………………… 100-240VAC 50/60Hz
Maximum load electric current:………250VAC 16A
Room temperature setting range……5
to 90
Floor temperature control range…… 5
to 99
Accuracy……………………………… ±0.5
Dimensions…………………………….86mm X 86mm X18mm
Color……………………………………White
FEATURE:
Large LCD display with backlight
Permanent user setting retention during power loss,
Optional temperature display of Celsius or Fahrenheit scale
Optional economic operation or comfort operation
Optional type of control for different heating application including room thermostat; floor thermostat or room
thermostat with floor limitation
Optional programming Period: 7 individual day programming with 48 separate time to select economic or
comfort mode.(Every half hour as a period of time) /cancel the programming function.
Display temperature recalibrates
IMPORTANT SAFETY INFORMATION:
Always turn off power at the main power source by unscrewing fuse or switching circuit breaker to the off
position before installing, removing, cleaning, or servicing this thermostat.
Read all of the information in this manual before installing this thermostat.
Only a professional contractor should install this thermostat.
All wiring must conform to local and national building and electrical codes and ordinances.
If system is not operating properly, check wiring and replace fuse if necessary.
Use this thermostat only as described in this manual.
1
KEYBOARD, DISPLAY AND SWITCH DESCRIOPTION
1
17 16 15
14 13
2
3
7
12
8
11
9
4
5
6
10
Figure 1
(1)
Figure 2
Clock button : Short press to enter into time setting mode;Hold the time setting button for 2 seconds to
enter into floor temperature inquiry interface in dual sensor control mode.
(2)
System button: AUTO mode / Comfort mode /Energy saving mode change over
(3)
Alternative inquiry button for Program setting /Configuration menu option button.
When the display shows OFF stand-by state, Hold button
(4)
(5)
for 3 seconds to enter the configuration menu.
Raise temperature setting
Power/OK button, long press power button to enter into OFF.
(6)
Lower temperature setting
(7)
Shows clock.
(8) Shows current room temperature or set temperature or time clock in different mode.
(9)
Shows when there is a call for heating
(10) Shows current programming time
(11) Shows temperature display in
(12)
(13)
(14)
(Mode
)
or
Shows when thermostat is in room temperature sensor control mode
(Mode
)
Shows when thermostat is in floor temperature sensor control mode.
(Mode
)
Shows when thermostat is configured in dual sensor control mode
Shows when thermostat is in AUTO mode
Shows when thermostat is in comfort mode
(15)
Shows when thermostat is in program operation.
(16)
Shows when thermostat is in energy saving mode
(17)
Shows when thermostat is in Manual temperature overide operation
2
INSTALL THE THERMOSTAT
ATTACH THERMOSTAT BASE TO WALL
1
2
Panel
B ase
p u ll t h e c o n t r o l p a n e l
s tr a ig h t o ff th e b a s e
4
3
screw for mounting
thermostat to wall
Fix the cover on the base
Figure 3
1. Remove the packing material from the thermostat. Gently pull the control panel straight off the base. Forcing or
prying on the thermostat will cause damage to the unit. See figure 3-1 & 3-2.
2.
The floor sensor cable must be installed to terminal block in heating type F or RF,
3.
Connect wires beneath terminal screws on power base using appropriate wiring schematic.
4.
Push power base into conduit box.
5.
Using two mounting screws mount the power base to the wall. Place a level against bottom of base, adjust until
See figure 3-3.
level, and then tighten screws. (Leveling is for appearance only and will not affect thermostat operation.)
6.
Replace control panel on the power base by snapping it in place. See figure 3-4.
WIRING DIAGRAM
Figure 4
Attention :
N: Neutral Wire ; L: Live Wire.
Item 1-2: Connected with power.
Item 3-4: Connected with heating load.
Item 6-7: Connected with sensor (NTC100K).
3
OPERATION
1. Configuration Menu
The configuration menu allows you to set certain thermostat operating characteristics to your system or
personal requirements. When the display shows OFF stand-by state, Hold button
for 3 seconds to enter the
configuration menu. The display will show the first item in the configuration menu. Press
next menu item. Use
or
button to shift to the
to select.
To exit the menu, press
button. The thermostat will exit the configuration menu If no action within 20
seconds,.
Restore factory default setting: In the configuration menu, push
button for 3 seconds. Display will
show “dEF” blinking 3 times and return to Menu item 1 indicates all the configuration setting has reverted to
factory default setting. The configuration menu chart summarizes the configuration options. An explanation of
each option is given below:
Item
1
Press
buttons
3 sec.
Displayed
(factory default
(
Press
)
or to select
Descriptions
Select temperature display adjustment
higher or lower
-4 --- +4
2
20 (68 )—90 (194 )
Select maximum room setting temperature
3
5 (41 )—20 (68 )
Select minimum room setting temperature
4
20 (68 ) —99 (210 )
5
5 (41 )—20 (68 )
/
6
( )
7
/
Select maximum floor temperature
limitation
Select minimum floor temperature
limitation
Temperature control mode option
1/2/3
Select display backlight mode
8
/
Select fast heating or slow heating
9
/
Changes the display readout to
Centigrade or Fahrenheit as required
10
(
11
( )
)
/
/
Select output load.
0/7
Programme option
1) Select temperature recalibrates adjustment 4LO to 4 HI –
You can adjust the room temperature display up to 4 higher or lower. Your thermostat was accurately
calibrated at the factory but you have the option to change the display temperature to match your previous
thermostat. The current or adjusted room temperature will be displayed on the right side of the display. The default
setting is 0.
2) Select maximum set point
For room sensor control mode, This feature provides a maximum set point temperature for room setting. The
default setting is 35 (95 ), It can be changed between 20
(68 ) to 90 (194 ).
4
3) Select minimum set point
For room sensor control mode,This feature provides a mixnimum set point temperature for room setting. The
default setting is 5 (41 ), It can be changed between 5
(41 )to 20 (68 ).
4) Select maximum floor temperature limitation
Press
or
button to select you desire maximum floor temperature limitation. It can be changed between
20 (68 )-99 (210 ),factory default setting is 40 (104 ). If floor temperature over the limitation, then stop
output work.
5) Select minimum floor temperature limitation
Press
or
button to select you desire minimum floor temperature limitation. It can be changed between
5 (41 )to 20 (68 ),factory default setting is 5 (41 ).
6) Select Type of heating.
There are 3 temperature control modes: Mode
Mode
, Mode
and Mode
.
is room sensor with floor limiter sensor control mode.
To control room temperature in living rooms etc. The thermostat will activate or deactivate the heating system
by comparing the set temperature with the actual room temperature and comparing the preset floor temperature
limit with the actual floor temperature. The factory default maximum floor limit is 40
or 104 . You can change it
in configuration menu item 4. Assuming that the floor temperature is below the maximum floor temperature limit,
the heating should begin to operate if the set temperature is 1 or 2
Mode
higher than the actual room temperature.
is room sensor control mode.
A floor sensor is not present, and cannot be installed. The unit will be controlled via room sensor in the
thermostat and the thermostat will determine to activate/deactivate heating system by comparing set temperature
with room temperature. Press
to adjust thermostat setting above room temperature 1 or 2 . The heating
should begin to operate immediately.
Mode
is Floor sensor control mode.
Constant temperature on the floor in bathrooms and other rooms where a comfortable warm surface is
required. The unit will be controlled via external floor sensor. It will determine to activate/deactivate heating
system by comparing set temperature with actual floor temperature. Press
to adjust thermostat setting above
floor temperature 1 or 2 . The heating should begin to operate immediately.
7) Select display backlight mode
The display backlight improves display contrast in low lighting conditions. Factory default is 2.
Select 1 the display will keep the light off.
Select 2 the light will be on when any button of the thermostat is touched.
Select 3 the display will keep the light on continuously.
8) Select
or
readout.
Changes the display readout to Centigrade or Fahrenheit as required.
9) Select fast heating or slow heating
Select FA to start heating immediately when the set point is 1
Select SL to start heating only when the set point is 3
above the room temperature.
above the room temperature.
5
10) Select output maximum load.
According to the actually output heating load, to select the corresponding load current.
The factory default setting is
-
. The options are
load current are 16 (A ).
-
load current is 8 (A ).
-
load current is 3 (A ).
11) Select Programme option.
7 indicate 7 individual day programming; 0 indicate cancel the programming function
2. Manual Operation
1) Set current day and time
a)
Turn on the thermostat , press
b)
Press
c)
Press and hold either
d)
Press
e)
Press and hold either
f)
Press
Press
button to enter the time setting.
button again, The display will only show minutes flashing
until you reach the correct minutes
button once again. The display will show the hour flashing.
until you reach the correct hour
button once again. The display will show the day of the week flashing.
until you reach the correct day of the week.
Press button
the correct day of the week and the time. Press button
button once. The display will show
button once again or any keys are not pressed within
20 seconds, the thermostat will revert to program operation.
2) Inquiry about floor temperature
This feature is only available in MODE
floor temperature.
.
Hold clock
Shows when display temperature is floor temperature. Pressing
program operation with room temperature shown in the display.
temperature. If press
button for 3 seconds, the thermostat will display
button to revert to
shows when displayed temperature is room
or no key is pressed after inquiry about floor temperature for 20 seconds, the display
will be changed from showing floor temperature to show room temperature.
3) Manual temperature override
When users cancel the programming function,
override operation. During this operation, Press
button
or
Shows when thermostat is in manual temperature
until the temperature you want is displayed. Then press
button or any keys are not pressed within 20 seconds, the thermostat will revert to manul
temperature override operation. If the appropriate temperature is above room temperature , the heating should
begin to operate immediately. All of the buttons are invalid except
and
buttons.
4) System Button
Shortly hold the system button
, the thermostat can select among comfort mode energy saving mode and
Auto mode. Factory default setting for comfort mode in heating is 21
Shows indicate you are now in comfort mode .
and energy mode in heating is 16.5 .
shows indicate you are now in energy saving mode.
6
shows indicate you are now in energy saving mode. Every time you change the setting in comfort mode, the
new setpoint will be memorized as the setpoint of the comfort mode. The same to the energy saving mode and
Auto mode.
Comfort mode
In comfort mode, using
or
to select the appropriate temperature you want. Then press button
button or any keys are not pressed within 20 seconds, the thermostat will revert to program operation.. If the
appropriate temperature is above room temperature , the heating should begin to operate immediately.
Then the thermostat will hold the room temperature at the selected setting temperature until the selected setting
temperature is changed.
Energy Saving Mode
In energy saving mode, using
or
to select the appropriate temperature you want. Then press button
button or any keys are not pressed within 20 seconds, the thermostat will revert to program operation.. If the
appropriate temperature is above room temperature , the heating should begin to operate immediately.Then the
thermostat will hold the room temperature at the selected setting temperature until the selected setting
temperature is changed.
Auto Mode
In Auto mode, using
or
to select the appropriate temperature you want. Then press button
button or
any keys are not pressed within 20 seconds, the thermostat will revert to program operation.. If the appropriate
temperature is above room temperature , the heating should begin to operate immediately.Then the thermostat
will hold the room temperature at the selected setting temperature until the selected setting temperature is
changed.
5)
Planning your program
This feature is only available in Auto mode. Hold button
for 3 seconds to enter the programming mode.
Look at the factory preprogrammed times and system mode that shown in screen. If this program will suit your
needs, simply press the
button to begin running the factory preset program.
If you want to change the preprogrammed time and temperature, follow these steps:
1). Hold
for 3 seconds. 00:00 flashing (indicating you are now planning the first paragraph of programming on
Monday).
2) If the system mode is what you need, press
to next time slot. The time will change in 30-minute increments.
3) If you want to change the system mode,Press
or
button again, mode symbol is flashing .Then you can use
to select the comfort mode or energy saving mode you want.
4) Press
button to the 2nd program period setting.
5) If the system mode is what you need, press
or
until the time slot. you wish to program. The time will change
in 30-minute increments.
6) If you want to change the system mode,Press
or
button again, mode symbol is flashing .Then you can use
to select the comfort mode or energy saving mode you want.
7) Repeat 2)~6) to complete the all program period from Monday to Sunday..
8) When you have completed entering your heating program, pressing
to revert to program operation.
7
9) Press both
and
buttons simultaneously for about 2s,can be programmde to restore factory value
Error Code
LO: Below lowest limitation temperature is detectived by floor sensor in MODE
or
. Thermostat turn on
heating system until the floor temperature is over lowest limitation.
HI :Over high limitation temperature is detectived by floor sensor in MODE
or
. Thermostat shut down all
output
Err.1 flashing in the display: Floor sensor short circuit in type
or
. Thermostat shuts down all heating
output.
Err.2 flashing in the display: Floor sensor not installed or broken in type
or
. Thermostat shuts down all
heating output.
Err.3 flashing in the display: Room sensor has short circuited. Thermostat shuts down all heating output.
Err.4 flashing in the display: Room sensor is broken. Thermostat shuts down all heating output.
CUSTOMER ASSISTANCE
After reading this guide, if you have any question about the operation of your thermostat, please contact your
installer or service provider.