Ceiling Mount Addressable Speaker Visible (S/V

TrueAlert Addressable Notification Appliances
UL, ULC Approved*
Ceiling Mount Addressable Speaker Visible (S/V) Notification Appliances
Introduction
Ceiling Mount Addressable Speaker Visible (S/V) Notification
Appliances are individually powered, addressed, and controlled from
the Autocall fire alarm control panel IDNAC Signaling Line Circuit (SLC).
S/V notification appliances use a multi-tapped speaker for audio/tone
notification and a multi-candela strobe with synchronized 1 Hz flash
rate and selectable candela rating.
Wiring supervision is electronically monitored and allows audio wiring
to be T-tapped for class B wiring, reducing wiring costs and wiring
distances.
Ceiling mount speaker visible appliances are available in 400 - 4000 Hz
models and high fidelity models capable of operating between 200 –
10000 Hz.
Separate appliance and cover selection greatly simplifies the ordering
and installation process. For more detailed information, please consult
datasheet AC49SWC-0001.
Fig 1: Ceiling Mount Addressable
Speaker/Visible Notification Appliance
Product Selection
Table 1: Ceiling Mount Addressable Speaker S/V Appliances
SKU
Description
TrueAlert ES Addressable S/V appliance dimensions with cover: 8 ⅛ " H x 7 ⅛" W x 3" D ( 206 mm x 180 mm x 76 mm)
A49SV-APPLC
Speaker Visible appliance only. Select cover separately.
A49SV-APPLC-BA
Table 2: High Fidelity Appliances
SKU
A49HFV-APPLC
A49HFV-APPLC-BA
Description
High Fidelity appliance only. Select cover separately.
Table 3: High Candela Appliances
SKU
A49SVH-APPLC-BA
A49SVH-APPLC
Description
High Candela appliance only. Select cover separately.
Table 4: High Fidelity High Candela Appliances
SKU
A49HFVH-APPLC
A49HFVH-APLCA-BA
Description
High Fidelity High Candela appliance. Select cover separately.
High Fidelity High Candela appliance with amber colored lens. Select
cover separately.
* Additional listings may be applicable; contact your local product supplier for the latest status.
AC49SVC-0001 Rev. 2 11/2016
Ceiling Mount Addressable Speaker Visible (S/V) Notification Appliances
Table 4: High Fidelity High Candela Appliances
SKU
Description
High Fidelity High Candela appliance with blue colored lens. Select
cover separately.
A49HFVH-APLCB-BA
Table 5: S/V Covers (Required when ordering APPLC models)
Color
Red
White
Red
White
Red
White
Red
White
Black
Wording
ALERT
/FIRE
100%
SKU
A49SVC-CRALT
A49SVC-CWALT
A49SVC-CRBA
A49SVC-CWBA
A49SVC-CRFIRE
A49SVC-CWFIRE
A49SVC-CRS
A49SVC-CWS
A49SVC-CK
FIRE
Autocall logo only
No logo or lettering
Note: *Model numbers ending in –BA are assembled in the USA.
IDNAC SLC Controller Compatibility Reference
Table 6: IDNAC SLC Controller Compatibility Reference
Compatible Controllers
4100ES with EPS+ or EPS Power Supply
4009 IDNAC Repeater
4100ES Flex 35, 50, and 100 Amplifiers
4100ES Constant Supervision and Signal Cards
Data Sheet
Reference
AC4100-0100
AC4009-0004
Controller Output
IDNAC SLC Output
Voltage
Appliance Voltage
Design Reference
IDNAC SLC
29 VDC (regulated)
23 VDC
(with 6 VDC drop)
AC4100-0034
Ceiling Mount S/V Specifications
Table 7: Specifications
Specification
Environmental
Rating
32° to 120° F (0° to 49° C); 10% to 93%, non-condensing at 104° F (40° C)
Connections
Terminal blocks for 18 AWG to 12 AWG (0.82 mm to 3.31 mm ); two wires per terminal for
in/out wiring. Use Unshielded Twisted Pair (UTP) for IDNAC and audio wiring.
2
2
Maximum of 127 addresses per SLC, 139 unit loads. See device and compatible Fire Panel
Installation Instructions for circuit current load limits.
579-1203AC (49SV, A49SVH and A49HFV models) 579-1206AC (Amber/Blue A49HFVH model)
IDNAC SLC Loading
Installation Instructions
Table 8: Speaker General Specifications
Specification
Input Voltage
Power Taps
Rating
25 or 70.7 Vrms
¼, ½, 1, and 2 W
400 to 4000 Hz (S/V, S/VH), 200 to 10000 Hz (H/
F, HF/VH)
Frequency Response
General Signaling = 125 to 12 kHz
Table 9: Speaker Output Ratings 25 or 70.7 Vrms @ 10 ft (3 m)
Wattage Tap
SKU
Reverberant Chamber Test, per UL 1480 (dBA)
Page 2
¼W
S/V
79
H/F
76
½W
S/V
83
H/F
80
1W
S/V
86*
H/F
84
2W
S/V
89*
H/F
87*
AC49SVC-0001 Rev. 2 11/2016
Ceiling Mount Addressable Speaker Visible (S/V) Notification Appliances
Table 9: Speaker Output Ratings 25 or 70.7 Vrms @ 10 ft (3 m)
Wattage Tap
SKU
Anechoic Chamber Test, per ULC-S541 (dBA)*
¼W
S/V
79
H/F
78
½W
S/V
83
H/F
82
* Select taps as indicated to satisfy the ULC fire alarm applications requirement of 85 dBA minimum
Attenuation
Angle
Polar Dispersion Reference (per ULC-S541 Anechoic Chamber
Testing)
-3 dB
70°
1W
S/V
86*
H/F
85*
Attenuation
-6 dB
2W
S/V
89*
H/F
88*
Angle
80°
Table 10: Percentage of rated light output at room temperature
Angle
UL required output
Typical output
On-Axis
0°
100%
327%
Vertical, Below Axis
45°
90°
45%
25%
134%
83%
Horizontal, Left/Right of Axis
45°
90°
45%
25%
129%
47%
Table 11: Appliance Specifications
Specification
Operating Voltage Range
Supervisory Requirements
Flash Rate and Synchronized SLC Loading
Rating
23 VDC to 30 VDC, Special Application
1 unit load (= 0.8 mA control panel current)
1 Hz; with up to 63 synchronized strobes maximum per powered
circuit, max 127 S/V appliances per IDNAC channel
Table 12: Current consumption**
Candela Setting
15 cd
30 cd
75 cd
110 cd
135 cd
185 cd
A49SV and A49HFV
59 mA
82 mA
145 mA
193 mA
N/A
N/A
models
A49SVH and
N/A
N/A
N/A
235 mA
255 mA
295 mA
A49HFVH models
** Measured at 23VDC on IDNAC Addressable SLC
Speakers are for connection to compatible fire alarm audio circuits. Anechoic speaker output ratings are typically more representative of actual
installed sound output.
Page 3
AC49SVC-0001 Rev. 2 11/2016
Ceiling Mount S/V Installation Reference
© 2017 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision and are subject to change without notice. Additional listings
may be applicable, contact your local Autocall product supplier for the latest status. Listings and approvals under Tyco Fire & Security GmbH, and the product names listed in this material
are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National Fire Alarm Code are registered trademarks of the National Fire Protection Association
(NFPA).
AC49SVC-0001 Rev. 2 11/2016
Download PDF
Similar pages