Product Data Sheet
ZCR452
Conventional Wireless Interface Unit
General
The ZCR452 is an interface between a conventional fire
detection zone and a range of wireless, 868 MHz field devices.
It provides a method of interfacing a conventional system with a
zone of wireless field devices in areas where the installation of
system wiring is not an option.
Usage
The ZCR452 allows for any compatible conventional fire
detection zone to be connected directly to the unit. The ZCR452
in turn provides fire and fault notifications from the wireless field
devices to these conventional circuits. In addition any
conventional notification circuit may also be wired to the
ZCR452, allowing wireless notification devices to be controlled
from the conventional notification controller in a similar way to
any hardwired conventional notification device.
Standard Features
E
E
The system
E
From the conventional interfaces the ZCR452 relays all signals
wirelessly to a ZCR868-C wireless cluster communicator that in
turn controls a complete zone of wireless detectors, remote
indicators, manual call points, input/output units and/or audio,
visual or audio visual notification devices. Any abnormalities
from the wireless field devices such as faults, alarms, device
removal, low battery etc. are relayed back from the cluster
communicator to the ZCR452 where they are converted into
basic conventional signals that are interpreted by the
conventional interface and relayed and displayed on the fire
system.
E
Power supply
The ZCR452 is powered by 6 Duracell AA MN1500 LR6 alkaline
batteries providing up to 5 years of operational life under normal
site conditions. Any abnormal battery condition is reported to
the fire system.
E
E
E
Provides conventional systems with wireless capabilities
No special conventional interfaces required
Flexible impedance matching for conventional circuits
Monitors all wireless alarm and fault messages
Conventional control interface for wireless notification
devices and IO
Two way radio communication
Fully EN54 compliant and CPR certified
ZCR452
Conventional Wireless Interface Unit
Specifications
Compatibility
Application
Installation
Mounting
Monitoring
Indications
Power supply
Environmental
Storage temperature
Operating temperature
Relative humidity range
(noncondensing)
IP Rating
Outputs
Hardwired
Wireless transmitter power
Physical
Dimensions (w x h x d)
Weight
Material
Colour
Approval
Ordering Information
All ZP conventional panels and conventional
interfaces
Indoor (Type A)
Surface
Continuously self-checking
6 LEDs Illuminated by push switch operation
6 x Duracell AA MN1500 LR6 alkaline batteries
-10°C to +70°C
0 to +35°C
10% to 95%
IP65
Volt free contacts, 2A@24VDC
Variable 0-14 dBm
240 x 120 x 50 mm
600g
Moulded ABS
Cool grey
CPD certified to EN54:18, and EN54:25 ENTSI
300-220 approved
As a company of innovation, UTC Fire & Security reserves the right to change product
specifications without notice. For the latest product specifications, visit UTC Fire & Security
online or contact your sales representative.
ZCR452-2018-03-22 03:33:13 Released :04-OCT-17