Safety Instrumented Fire & Gas Systems
aeSolutions Provides Full-Service
Fire & Gas Engineering and Products
The aeSolutions FM-approved family of Fire & Gas safety systems
ensures compliance with the latest NFPA 72 standards to meet
all of OSHA’s requirements. The FGS1400 MK II is listed for Fire
Command Center and proprietary Supervising Station functions.
FGS1400 MK II
Industrial designed system, SIL
3-capable logic solver, scalable to
large I/O count.
Are you Compliant?
With aeSolutions on your team, you can rest assured that your Fire
and Gas System is designed to the latest safety standards utilizing
our first-hand industry experience of the process safety lifecycle.
Benefits of aeSolutions Fire & Gas Systems:
• Scalability provides you with customization options
• Listed for use with a wide variety of end devices for
maximum flexibility
• Customized functionality and listings available
• Siemens PCS7 platform integration for increased
operator visibility
• FM-Listed for Fire & Gas detection and suppression to
satisfy regulations
• Industrial grade hardware for increased reliability in
plant applications
• Factory training available to enable end users to maintain
their systems
FGS1300
FM-approved for lower I/O count
applications. Class 1 Div 2 area
classification status.
PS1400 20 / 50 / 100 / 150
Power supplies that meet NFPA
72 requirements. The power you
need, when you need it.
PS1400-20-DIV2
Battery set FM-listed for Class 1
Div 2 areas. Rugged and reliable.
FGS1400 & FGS1300 Fire & Gas Alarm & Control Systems
Life Safety Solutions
The FGS1400 MK II and FGS1300 combine the required functionality into the latest
generation of TÜV-certified safety PLC.
A critical component of the FGS1400 MK II and the FGS1300 is an FM-approved
secondary power supply system consisting of a charger panel and an associated selfcontained battery system. To support system design, aeSolutions has developed an
FM-approved battery sizing tool which confirms the battery system design based on the
specific requirements of each application.
By using the same hardware / software platform as the Siemens Simatic PCS7 series, the
FGS1400 MK II and FGS1300 can be integrated into the entire plant system solution. It
offers the advantages of common HMIs, spare parts, training, engineering / configuration
tools, maintenance, and procedures to produce a dramatic saving in both installed cost
as well as lifecycle costs.
Fire System Monitoring & Control
The FGS1400 MK II and FGS1300 have been FM-approved to be in conformance with the
requirements of NFPA 72 for fire alarming and mitigation control. The FGS 1400 MK II
has approval for either simplex or redundant processors, a variety of I/O configurations
including remote I/O, and a battery back-up/ charger subsystem.
Gas Monitoring and Control
The FGS1400 MK II and FGS1300 have been FM-approved
to be in conformance with FM Approval’s Combustible
Gas Standard 6320, Toxic Gas Detection Standard 6340
and ANSI/ISA 12.13.01 Performance Requirements for
Combustible Gas Detectors standard.
FGS1400 MKII Fire & Gas
Alarm & Control System
Field Device Options
•
•
•
•
•
•
•
•
•
Heat & smoke detectors
Temperature rate-of-rise sensors
Toxic and combustible gas detectors
Suppression subsystems
Local alarm horn / beacon
Environmental protection
Host communication capability
IR fire detectors
Multi-spectrum fire detectors
System Integration Options
aeSolutions’ qualified engineers can apply years of fire &
gas system expertise to provide:
• Implementation of all phases of design, fabrication,
configuration, and documentation
• System verification and validation including factory
acceptance, integration, and client acceptance testing
• Training at both the engineering and technician levels
• Commissioning and startup support
Contact Warren Johnson, Fire & Gas Product Manager,
today for a free demo or more information.
aesolns.com | info@aesolns.com | +1 864 676 0600
FGS1300 Fire & Gas
Alarm & Control System
FGS1400 Fire & Gas Alarm & Control System Features
• Complete battery backup system with charger
• No on-site programming required
• Multiple operator interface options: 10” TP1200 Touch
Panel; 15” PC677 Operator Interface; PC BOX840 PC with
21” Vartech Monitor
• Powerful engineering workstation incorporating cause
and effect alarm configuration and display using Siemens’
Cause and Effect Safety MatrixTM
FGS1400 System Specifications
Processor: Siemens Simatic S7-400F Series with redundant processor option
I/O: Both analog and discrete supervised circuits and remote I/O option
Inputs/Outputs: Application-dependent
SIL: Design based upon SIL 3-rated components for Fire & Gas circuits
Power Supply: PS1400-50-600: 50 Amp 24VDC Output Nominal; 115/230 VAC Input/600 Amp Hour
Battery Backup.
The FGS1400 MK II is designed to the same levels of safety
availability and reliability as the systems that aeSolutions
designs for Safety Instrumented Systems. By using the latest
generation of a SIL 3 safety-certified PLC as the logic solver,
the FGS1400 MK II provides the same demanding levels of
performance required by the ISA and IEC safety standards for
safety critical applications. While not all fire and gas systems
are required to conform to the safety standards, wise users
recognize the benefits of such a high-reliability system even
for lower-risk applications.
FGS1400 Features
Pre-engineered, pre-configured and pre-packaged system that
is suitable for a wide variety of applications and is available as
a turnkey solution.
• FM-Approved to be compliant with NFPA 72 for both fire
and gas monitoring in the same PLC
• Siemens Simatic S7-400F Series Safety PLC platform
• Simplex I/O and either simplex or redundant processors
support: offers a remote I/O option
• TÜV-approved SIL 3 rated Safety PLC
• Interface to a wide variety of sensors and final control
elements with fully supervised circuits (IDC, NAC, FSF, SDC)
• Designed to levels of reliability and availability with
national safety standards for Safety Instrumented Systems
• Profibus, Industrial Ethernet, hardwired I/O, or Modbus
compatible
PS1400-100-1200: 100 Amp 24VDC Output
Nominal; 115/230 VAC Input/1200 Amp
Hour Battery Backup.
PS1400-150-1800: 150 Amp 24VDC Output
Nominal; 208/240/480 VAC input/1800
amp hour battery set.
Optional Rack assembly to stack charger
and battery set.
Operating: 0 to 50 Deg C.
Storage: -40 to 60 Deg C
Operating: 0 to 95% non-condensing
Nema 12 Gauge 12, powder coated;
size is application-dependent
General purpose
Application-dependent
FM-Approved for compliance with NFPA
72 for both Fire & Gas; FM Approval’s
Combustible Gas Standard 6320, Toxic Gas
Detection Standard 6340 and ANSI/ISA
12.13.01 Performance Requirements for
Combustible Gas Detectors standard.
Temperature: Humidity: Cabinet: Area Class.: Weight: Certifications: Initiating Device
Circuits: Class A & B for discrete dry contact IDCs; Class B for Analog IDCs.
Notification
Appliance
Circuits: Class B
FGS1300 Fire & Gas Alarm & Control System Features
The FGS1300 provides fire and gas monitoring, and suppression
control for modules in remote locations that have less than 40
I/O. It is designed to be installed in either a general area, or as
an option, Class 1 Div 2 groups B-D, temp code T3 zones areas.
FGS1300 Features
The FGS1300 Fire & Gas System is a pre-engineered, preconfigured and pre-packaged system that is suitable for a
variety of applications and is available as a turnkey solution.
• FM-Approved to be compliant with NFPA 72 for both fire
and gas monitoring in the same PLC
• Siemens Simatic S7-315 Series PLC platform
• Interface to a wide variety of sensors and final control
elements with fully supervised circuits (IDC, NAC, FSF, SDC)
• Profibus, Industrial Ethernet, or hardwired I/O compatible
• Complete battery backup system with charger
• No on-site programming required
• 7” TP700 Comfort Touch Panel programmed with Siemens
TIA Portal
FGS1300 System Specifications
Processor:
I/O: Inputs/Outputs: Power Supply: Temperature: Humidity: Cabinet: Area Class.: Weight: Certifications: Initiating Device Circuits:
Notification Appliance Circuits: Siemens Simatic S7-315 series CPU
Both analog and discrete supervised circuits
Application-dependent
PS1400-20-208: 20 Amp 24VDC Output Nominal; 115/230 VAC Input/208 Amp Hour Battery set, Optional Rack assembly to stack charger and battery set
Operating: 0 to 50 Deg C.
Storage: -20 to 60 Deg C
Operating - 0 to 95% non-condensing
Nema 12 Gauge 12, powder coated; 30”wide by 42” tall by 10” Deep
General purpose, Class 1 Div 2 Groups B-D, T3
Application-dependent. Typical 250 Lbs
FM-Approved for compliance with NFPA 72 for both Fire & Gas; FM-Approved
Combustible Gas Standard 6320, Toxic Gas Detection Standard 6340 and ANSI/ISA 12.13.01 Performance Requirements for Combustible Gas Detectors standard
Class A & B for discrete dry contact IDCs; Class B for Analog IDCs
Class B
Contact Warren Johnson, Fire & Gas Product Manager,
today for a free demo or more information.
aesolns.com | info@aesolns.com | +1 864 676 0600
PS1400 20 / 50 / 100 / 150 Amp Power Supply
The PS1400 series of power supplies is an FM- approved, power
supply system that is designed to power fire alarm systems
and toxic and combustible gas monitoring systems. Each
system consists of a 24-Volt battery set and a charger system
that has been FM-approved for compliance with the NFPA 72
requirements for primary and secondary power supplies. The
PS1400 series of power supplies are available in 20, 50, 100,
and 150 Amp versions.
Battery Charger Panel Features
The battery charger charges the battery set and provides
unregulated power for powering the Fire and Gas panel.
• AC feed, battery voltage and charger health monitoring
• Individual status contacts that can be wired to a fire alarm
panel for indication and alarming
• Continuous current monitoring displays real-time standby
and alarm currents and calculates remaining battery life
when on standby power
Battery Set Features
The battery set is provided as a secondary power supply as
required by NFPA 72.
• Floor mounted, self-contained, not enclosure-dependent
• Plastic guards protect terminals from damage or shorting
• DC-DC Converter(s) provide a tightly regulated 24 VDC
nominal output
• Regulated power for components and circuits that require
tight voltage regulation and where ground fault detection is
not required
• Separate ground fault detection circuit for unregulated
power, alarming and reporting to a Fire and Gas alarm panel
• Separate regulated and unregulated 24VDC circuits with a
disconnect for over-current protection
• Voltage Regulated Lead Acid (VRLA) 20-year maintenancefree battery set
Class 1 Div 2 Area Classification
The PS1400-20-DIV2 20 Amp Power Supply is designed and FMlisted for installation and use in hazardous locations.
Environment Specifications
Specification
Data
Ambient Temperature Range:
Operating -20 to 50 Deg C, 0.5 Deg C/min
Storage -40 to 50 Deg C, 10 Deg C/min
Relative Humidity: Operating
5 to 95% non-condensing
Vibration:
10-150 Hz, 1 g. max
Power Requirements
20 Amp Battery Charger System:
120/240 VAC 1-Phase, 60 Hz @ 6.3 Amps
50 Amp Battery Charger System Available Options:
120/208/240 VAC 1-Phase, 60 Hz @ 23/13/11 Amps
400 VAC 1-Phase, 60 Hz @ 6.8 Amps
480 VAC 1-Phase, 60 Hz @ 5.6 Amps
100 Amp Battery Charger System Available Options:
120/208/240 VAC 1-Phase, 60 Hz @ 44/25/22 Amps
400 VAC 1-Phase, 60 Hz @ 13 Amps
480 VAC 1-Phase, 60 Hz @ 11 Amps
150 Amp Battery Charger System Available Options:
480 VAC 1-Phase, 60 Hz @ 16 Amps
Full Engineering Services
Core Competencies
Process Risk Management (PRM)
Safety Instrumented System Design
• Thought leaders in Functional
Safety and Industrial Cybersecurity
Lifecycle Management
• Professional team formed by
more than 40 CFSE/CFSP/TÜV/PE
certified professionals and more
than 30 ISA-trained professionals
• Principals are voting members of
IEC 61511, 61508, and 62443
• International Society of
Automation (ISA) involvement:
• Process Hazard Analysis (PHA)
• Design and Verification
• Safety Requirement
Specification (SRS)
• Protection Layer Requirements
Specification
• Cause & Effects
• Test Plans
• Safety Lifecycle Plan
• Lifecycle Cost Analysis
• Safety Integrity Level (SIL)
Calculations
• Test Plan Validation
• Functional Safety Assessment
• Fault Tree Analysis
• Event Tree Analysis
»» Five Certified Instructors
»» S84 Fire & Gas (F&G) Working
Group Chair
»» Safety Division Chair
»» Professional Development
Department VP Elect
• Manage 25 facilities for Functional
Safety Management and
Management of Change (MOC)
• Own 10 patents
»» HAZOP/What-If/Checklist/
Fault Tree/HAZID
• Risk Assessment
»» LOPA/QRA
• Facility Siting
• PHAST Modeling/Consequence
Assessment
• Process Safety Management (PSM)
Development & Implementation
• Risk Management Program (RMP)
Development & Implementation
• PSM/RMP Compliance Auditing
• Functional Safety Assessments
• Standard Operating Procedure
(SOP) Development
»» Safe Operating Limit Tables (SOLTs)
»» Training Programs
• Safety and Environmental
Management Systems (SEMS)
Automation
Industrial Cybersecurity
Safety Lifecycle Management Tools
•
•
•
•
•
•
•
• Cybersecurity Audits, Risk
Assessments, & Asset Inventory
• As-Built Network & Dataflow
Diagrams
• Cybersecurity Requirements
Specification Development
• Countermeasure Cost/Benefit
Analysis
• Zone & Conduit Modeling
• System Network Architecture
Countermeasure Design & Review
• Cybersecurity Testing
• Firewall Design/Design Review
• Industrial Firewall Commissioning
• Intrusion Detection Design
• Cybersecurity Configuration
Management
• Patch Management Support
• Vulnerability Management
Support
• Alarm Management
• Alarm Philosophy Development
• aeShield™/aeFacilitator™ —
integrated solution for executing,
monitoring and sustaining the
Safety Lifecycle via Enterprise
level toolset
• Follows IEC 61511 Workflow/
Lifecycle
• Applications Support:
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Hazardous Area Classification
Distributed Control Systems
Programmable Logic Controllers
Human-Machine Interfaces
Control Systems Integration
Communication Networks
Electrical & Instrumentation
Design
Control Panel Design
Fieldbus Design
Advanced Process Control
Modeling & Optimization
Online Documentation and Help
System Simulation and Validation
Post-Project Support
F&G Panel Design
F&G Coverage Modeling
F&G Survey Compliance
BMS Survey Compliance
BMS Panel Design
BPCS Panel Design
F&G and BMS FM-listed products
»»
»»
»»
»»
PHA (HAZOP) / LOPA
Gap Tracking
SIL Calculation Engine
Safety Requirement Specification
(SRS)
»» Test Plans & Failure Data Collection
»» Cause & Effects
»» Health Meters to Monitor IPL
Performance
• Additional Key Functionality
»»
»»
»»
»»
»»
Management of Change
Concurrent Projects
Unlimited Users
Confirgurable Standards
Interface to Historian and Other Key
Databases
Safety Instrumented Fire & Gas Systems
Contact us today for a free demo or more information
aesolns.com | info@aesolns.com | +1 864 676 0600
Visit aesolns.com/white-papers for
downloadable Fire & Gas white papers.
Download PDF