Carbon Monoxide Alarm Guide

Carbon Monoxide Alarm Guide
This CO detector guide has been produced to help Operatives identify the status of an alarm to ensure the correct action is taken when called to a potential CO
activation. Relevant information has been extracted from the user manuals to help assist with the identification of the operating mode of CO detectors that you may
encounter so you can establish the correct action to take.
If you encounter an alarm that is not included within this guide then you can check the availability of the instructions with the end user. Where an alarm is sounding
and you cannot identify the mode then always take the safest course of action by making the situation safe and advising the consumer to have the appliances
checked by a Gas Safe registered installer.
All CO detectors manufactured for the UK market have to meet the requirements of BS EN 50291. This standard sets the minimum requirements for the design and
manufacturer of CO detector . More recent detectors have enhanced functionality, such as LCD displays that provide a greater level of information to the
homeowner.
Placement Of CO detectors
Correct location of the CO detector is an important to ensure the CO detector is operating in an effective zone and helps to eliminate false activations.
The recommendation for the placement of a CO detector is:




in every room that contains a fuel burning appliance,
at least 300 mm from any wall (for ceiling mounted alarms)
at least 150 mm from the ceiling, above the height of any door or window (for wall mounted alarms)
between 1 and 3 m (measured horizontally) from the potential source of CO
CO Detectors must not be placed in the following:



in an enclosed space,
where it can be obstructed,
directly above a sink,
Page 1 of 51


next to a door, window, extractor fan, air vent or similar ventilation opening,
where the temperature may drop below –5 ºC or exceed 40 ºC.
Where a premises has multiple fuel burning appliances in different rooms, the standard recommends that if there are restrictions in placing an alarm in each room
that the priority should be given to putting a detector in rooms containing flueless or open-flued appliances.
CO Detectors are designed to sound a continual audible alarm when the following criteria is met:
CO Concentration
30 PPM
50 PPM
100 PPM
300 PPM
Without Alarm Before
120 mins
60 mins
10 mins
-
With Alarm Before
90 mins
40 mins
3 mins
Where a detector activates when the above criteria is met then the alarm must continue to sound until the CO PPM readings drop below 50 PPM. When the CO
reading drops below this threshold then the alarm should stop alerting within 10 minutes. The CO detection functionality on an alarm is still operating even when
the detector is indicating low battery.
Many new detectors contain an LCD display, which indicates the highest PPM reading obtained. This value is displayed even when the alarm stops activating,
however it is important to note that the display can be reset therefore removing any information on activation.
Dual Mode CO detectors
It is becoming more common to encounter alarms that have a dual mode, typically these are combined with smoke alarms in a single unit. In some cases they may
also contain other functions, such as panic alerts for elderly customers.
Even when you encountered a combined unit the CO element of the alarm must operate independently of any other mode and this must comply with the mimum
requirements set out in the CO alarm standard.
Page 2 of 51
CO Detector Catalogue
FireAngel
Kidde
Honeywell
Ei Electronics
FirstAlert
BRK
NEST
CO-9B
5CO
XC70
Ei208
SCO5
CO4000EN
PROTECT
CO-9D
7CO
XC100
Ei261ENRC
SCO7
CO850
CO-9X
7DCO
XC100D
CO-9X-10
10LLCO
CO400
W2-CO-10X
10LLDCO
SCO500
10SCO
CO250
GCO1
CO600
CO605
CO615
PC900V
CO710
Page 3 of 51
FireAngel
CO-9B
Contact Details
Telephone
08001 412 561 (support line – Mon-Fri from 09:00 to 17:00)
Email
technicalsupport@fireangel.co.uk
Website
www.fireangel.co.uk/product-category/carbon-monoxide-alarms/
Main Features
Feature
Function
Power LED (Green)
Indicates that the unit is receiving power and is fully operational
Alarm LED (Red)
Indicates and emergency situation
Test/Reset Button
Used to test/reset/silence the unit
Operating Features
Light Indicator
Sound Emitted
What This Means
Required Action
Alarm LED flashing Red once per second
Loud audible signal
Dangerous levels of CO has been
detected
Follow Emergency Procedures
Off
Single chirp once per minute
Low battery/Fault/End of Life
Replace batteries. If warning
indicators persist despite having
new batteries and the product is still
under warranty contact technical
support for advice. If the product is
no longer under warranty replace it
immediately
Power LED flashing Green once per
minute
Silent
Normal Operating Mode
None
Page 4 of 51
FireAngel
CO-9D
Page 5 of 51
Contact Details
Telephone
Email
08001 412 561 (support line – Mon-Fri from 09:00 to 17:00)
technicalsupport@fireangel.co.uk
Website
www.fireangel.co.uk/product-category/carbon-monoxide-alarms/
Main Features
Feature
Power LED [
Function
] (Green)
Indicates that the unit is receiving power and is fully operational
Alarm LED [ ] (Red)
Indicates an emergency situation
Test/Mode Button
Switch between CO/Temperature view and to test/silence the unit
Operating Features – Part 1 of 2
Digital Screen
Light Indicator
Sound Emitted
What This Means
Alarm [ ] LED flashing Red once
per second
Loud audible signal
Dangerous levels of CO has been
detected
Alarm has been silenced during a recent
alarm situation – this can be identified
from the presence of a PPM reading on
the silence alarm symbol [
] on the
display
The peak level symbol[ ] indicates
that CO has been detected in your
absence
Required Action
Power [ ] LED flashing Green
once per minute
Silent
Power [ ] LED flashing Green
once per minute
Silent
Power [ ] LED flashing Green
once per minute
Single chirp once per
minute
A fault has been detected in the alarms
sensor/circuitry settings
Power [ ] LED flashing Green
once per minute
Single chirp once per
minute
Power Pack Low
If the product is still under warranty
contact technical support for advice. If
the product is no longer under warranty
replace it immediately
Power [ ] LED flashing Green
once per minute
Silent
The spanner icon [ ] indicates that the
alarm is in sensor test mode
Perform sensor test or end the test by
holding down the Test/Mode button until
the spanner icon disappears
Power [ ] LED flashing Green
once per minute
Silent
Temperature Display View
To switch between CO and temperature
view, press the Test/Mode button briefly
Page 6 of 51
Follow Emergency Procedures
FireAngel
CO-9X
Contact Details
Page 7 of 51
Telephone
08001 412 561 (support line – Mon-Fri from 09:00 to 17:00)
Email
technicalsupport@fireangel.co.uk
Website
www.fireangel.co.uk/product-category/carbon-monoxide-alarms/
Main Features
Feature
Function
Power LED (Green)
Indicates that the unit is receiving power and is fully operational
Fault LED (Yellow)
Indicates low battery/fault
Alarm LED (Red)
Indicates an emergency situation
Test/Reset Button
Used to test/reset/silence the unit
Operating Features
Light Indicator
Sound Emitted
What This Means
Required Action
Alarm LED flashing Red once per
second
Loud audible signal
Dangerous levels of CO has been
detected
Follow Emergency Procedures
Fault LED Yellow flashing once per
minute
Single chirp once per minute
Low Battery/Fault
If the product is still under warranty
contact technical support for advice. If
the product is no longer under
warranty replace it immediately
Power LED flashing Green once per
minute
Silent
Normal Operating Mode
None
Page 8 of 51
FireAngel
CO-9X-10
Contact Details
Telephone
08001 412 561 (support line – Mon-Fri from 09:00 to 17:00)
Email
technicalsupport@fireangel.co.uk
Website
www.fireangel.co.uk/product-category/carbon-monoxide-alarms/
Main Features
Feature
Function
Power LED (Green)
Indicates that the unit is receiving power and is fully operational
Fault LED (Yellow)
Indicates low battery/fault/end of life
Alarm LED (Red)
Indicates an emergency situation
Test/Reset Button
Used to test/reset/silence the unit
Operating Features
Light Indicator
Sound Emitted
What This Means
Required Action
Alarm LED flashing Red once per
second
Loud audible signal
Dangerous levels of CO has been
detected
Follow Emergency Procedures
Fault LED flashing Yellow once per
minute
Single chirp once per minute
Low Battery/Fault/End of life
If the product is still under warranty
contact technical support for advice. If
the product is no longer under
warranty replace it immediately
Power LED flashing Green once per
minute
Silent
Normal Operating Mode
None
Page 9 of 51
FireAngel
W2-CO-10X
Contact Details
Telephone
+44 (0) 8001 412 561 (support line – Mon-Fri from 09:00 to 17:00)
Email
technicalsupport@fireangel.co.uk
Website
www.fireangel.co.uk/product-category/carbon-monoxide-alarms/
Main Features
Feature
Function
Power LED (Green)
Indicates that the unit is receiving power and is fully operational
Fault LED (Yellow)
Indicates low battery/fault/end of life
Alarm LED (Red)
Indicates an emergency situation
Test/Silence Button
Used to test/silence the unit
Operating Features
Light Indicator
Alarm LED flashing Red once
every 5 seconds
Fault LED flashing Yellow once
per minute
Fault LED flashing Yellow once
per minute
Power LED flashing Green once
per minute
Sound Emitted
Four chirps repeated
Single chirp once per minute (In
sync with fault LED flashes)
Single chirp once per minute (nonconcurrent with fault LED flashes)
Silent
What This Means
Dangerous levels of CO has been
detected
Low Battery/End of Life
Required Action
Follow Emergency Procedures
Sensor Fault
If the product is still under warranty contact
technical support for advice. If the product is no
longer under warranty replace it immediately
Normal Operating Mode
None
Page 10 of 51
Kidde
5CO
Contact Details
Telephone
Email
Website
08009 170 722
admin@kiddesafety.co.uk
www.TenYCO.kiddefyrne0cs.co.uk
Main Features
Feature
Function
Operate LED (Green)
Indicates that the unit is receiving power and is fully operational
Alarm LED (Red)
Indicates an emergency situation/fault/low batteries/end of life
Test/Reset Button
Used to test/reset/silence the unit
Operating Features
Light Indicator
Sound Emitted
What This Means
Required Action
Alarm LED flashing Red
Loud continual signal (4 beeps – 5
seconds pause – 4 beeps…)
Dangerous levels of CO has been
detected
Follow Emergency Procedures
Alarm LED on (Red)
Constant audible signal
Malfunction
Two chirps every 30 seconds
End of life
Single chirp every 30 seconds
Fault
Single chirp once per minute
Low Battery
Replace Batteries
Silent
Normal Operating Mode
None
Alarm LED flashing Red twice every 30
seconds
Alarm LED flashing Red once every 30
seconds
Alarm LED flashing Red once per
minute
Operate LED flashing Green once
every 30 seconds
Page 11 of 51
Replace the Alarm
Kidde
7CO
Contact Details
Telephone
Email
08009 170 722
admin@kiddesafety.co.uk
Website
www.TenYCO.kiddefyrne0cs.co.uk
Main Features
Feature
Function
Operate LED (Green)
Indicates that the unit is receiving power and is fully operational
Alarm LED (Red)
Indicates an emergency situation/fault/low batteries/end of life
Test/Reset Button
Used to test/reset/silence the unit
Operating Features
Light Indicator
Sound Emitted
What This Means
Required Action
Alarm LED flashing Red
Loud continual signal (4 beeps – 5
seconds pause – 4 beeps…)
Dangerous levels of CO has been
detected
Follow Emergency Procedures
Alarm LED on (Red)
Constant audible signal
Malfunction
Two chirps every 30 seconds
End of life
Single chirp every 30 seconds
Fault
Single chirp once per minute
Low Battery
Replace Batteries
Silent
Normal Operating Mode
None
Alarm LED flashing Red twice every 30
seconds
Alarm LED flashing Red once every 30
seconds
Alarm LED flashing Red once per
minute
Operate LED flashing Green once
every 30 seconds
Page 12 of 51
Replace the Alarm
Kidde
7DCO
Contact Details
Telephone
Email
Website
+44 (0) 8009 170 722
admin@kiddesafety.co.uk
www.TenYCO.kiddefyrne0cs.co.uk
Main Features
Feature
Function
Operate LED (Green)
Indicates that the unit is receiving power and is fully operational
Alarm LED (Red)
Indicates an emergency situation/fault/low batteries/end of life
Test/Reset Button
Used to test/reset/silence the unit
Peak Level Button
Displays the peak CO reading
Digital Display
Visual display of product’s indicators
Operating Features
Digital Screen
Light Indicator
Alarm LED flashing Red and
CO level on display
Sound Emitted
Full alarm (4 beeps – pause – 4
beeps)(repeating)
Constant audible signal (not full
alarm)
What This Means
Dangerous levels of CO has been
detected
Alarm LED flashing Red
twice every 30 seconds
Two chirps once every 30 seconds
End of Life
Alarm LED flashing Red
Single chirp once every 30 seconds
Fault
Alarm LED flashing Red
once per minute
Single chirp once per minute
Low Battery
Replace Batteries
Alarm LED flashing Red
1 beep, then 2 sets of 4 beeps,
followed by 1 beep
Successful test or reset sequence
in operation
None
Operate LED flashing
Green once every 30
seconds
Silent
Normal Operating Mode
None
Alarm LED on (Red)
Required Action
Follow Emergency Procedures
Malfunction
Page 13 of 51
Replace the Alarm
Kidde
10LLCO
Contact Details
Telephone
+44 (0) 8009 170 722
Email
Website
admin@kiddesafety.co.uk
www.TenYCO.kiddefyrne0cs.co.uk
Main Features
Feature
Function
Operate LED (Green)
Indicates that the unit is receiving power and is fully operational
Fault LED (Amber)
Indicates low battery/fault/end of life
Alarm LED (Red)
Indicates an emergency situation
Test/Reset Button
Used to test/reset/silence the unit
Operating Features – Part 1 of 2
Light Indicator
Sound Emitted
What This Means
Required Action
Alarm LED on (Red)
Loud continuous signal (four loud alarm
sounds, repeated for four minutes,
followed by two patterns per minute)
Dangerous levels of CO
has been detected
Follow Emergency Procedures
Off
Constant signal
Malfunction
Two chirps every 30 seconds
End of Life
Alarm LED flashing Red twice every 30
seconds and fault LED flashing Amber
once per second
Fault LED flashing Amber once every
30 seconds and operate LED (Green)
blinks error code every other 30
seconds
Fault LED flashing Amber once every
30 seconds
Alarm LED flashing Red once per
minute
Operate LED flashing Green once every
30 seconds
Replace the Alarm
Single beep every 30 seconds
Fault
One beep per minute
Low Battery
If cold allow unit to warm up for a couple of
hours then replace if still beeping
Silent
Historical event in last 14
days
Follow Emergency Procedures
Silent
Normal Operating Mode
None
Page 14 of 51
Kidde
10LLDCO
Page 15 of 51
Contact Details
Telephone
Email
Website
08009 170 722
admin@kiddesafety.co.uk
www.TenYCO.kiddefyrne0cs.co.uk
Main Features
Feature
Function
Operate LED (Green)
Indicates that the unit is receiving power and is fully operational
Fault LED (Amber)
Indicates low battery/fault/end of life
Alarm LED (Red)
Indicates an emergency situation
Test/Reset Button
Used to test/reset/silence the unit
Peak Level Button
Displays the peak CO reading
Operating Features
Digital Screen
Light Indicator
Sound Emitted
What This Means
Required Action
Alarm LED flashing Red
Continual audible signal
Dangerous levels of CO has been
detected
Follow Emergency
Procedures
Off
Constant signal
Malfunction
Two chirps every 30
seconds
End of Life
Single chirp every 30
seconds
Fault
Fault LED flashing Amber once per
second
Single chirp once per
minute
Low Battery
If cold allow unit to warm
up for a couple of hours
then replace if still beeping
Alarm LED flashing Red. Operate (Green)
and Fault (Amber) LED on
1 beep, then 2 sets of 4
beeps, followed by 1
beep
Successful test or reset sequence in
operation
None
Operate LED flashing Green every 30
seconds
Silent
Normal Operating Mode
None
Alarm LED flashing Red twice every 30
seconds. Fault LED flashing Amber once
per second
Fault LED flashing Amber once per
second and operate LED (Green) flashing
error code every other 30 seconds
Page 16 of 51
Replace the Alarm
Contact Details
Telephone
Email
Website
+44 (0) 8009 170 722
admin@kiddesafety.co.uk
www.TenYCO.kiddefyrne0cs.co.uk
Main Features
Feature
Function
Green LED
Indicates that the unit is receiving power
Red LED
Indicates an emergency situation
Test/Reset/Hush
Used to test/reset/silence the unit
Operating Features
Light Indicator
Sound Emitted
Alarm: Four short beeps followed by
the verbal message
Verbal: “WARNING! CARBON
MONOXIDE!” After four minutes the
alarm/voice will sound once every
minute until the unit is reset
Alarm: Three long beeps followed by
the verbal message
Verbal: “FIRE! FIRE!”, repeated until
the smoke is eliminated
Red LED flashes
Red LED flashes
What This Means
Required Action
Dangerous levels of CO has been
detected
Follow Emergency Procedures
Dangerous levels of Smoke has been
detected
Call Emergency Services
Off
2 chirps every 30 seconds
End of Life
Replace the Alarm
Red LED flashes
Single chirp every 30 seconds
Malfunction
Replace the Alarm
Red LED flashes once every minute
Voice: “LOW BATTERY”, this cycle will
occur for the first hour. After the first
hour the voice message “LOW
BATTERY” will sound once every 15
minutes.
Low Battery
Replace Batteries
Green LED flashes every 30 seconds
Silent
Normal Operating Mode
None
Honeywell
XC70
Page 17 of 51
Contact Details
Telephone
01202 645 577
Email
consumer@honeywell.com
Website
www.homesafety.honeywell.com
Main Features
Feature
Function
Power LED (Green)
Indicates that the unit is receiving power and is fully operational
Fault LED (Yellow)
Indicates low battery or fault
Ventilate LED (Blue)
Early warning of CO build-up
Alarm LED (Red)
Indicates an emergency situation
Test/Hush button
Used to test/silence the unit
Operating Features – Part 1 of 2
Light Indicator
Sound Emitted
What This Means
Alarm LED flashing Red
Continuous 4 chirps for 60 minutes
then once every 30 seconds
Off
Continuous 4 chirps
Alarm LED flashing Red once per
minute
Chirp once per minute
Dangerous levels of CO has been
detected
Dangerous levels of CO has been
detected by another
interconnected CO alarm
Dangerous levels of CO was
detected whilst user was absent.
Currently, no dangerous CO level
present
Honeywell
XC70
Required Action
Follow Emergency Procedures
Follow Emergency Procedures
Check Appliances
Page 2 of 2
Operating Features – Part 2 of 2
Light Indicator
Sound Emitted
What This Means
Page 18 of 51
Required Action
Off
Continuous 3 chirps
Fire detected by an interconnected
fire alarm
Follow Emergency Procedures
Ventilate LED flashing Blue 1 (2, or
3) times once every 30 seconds,
increasing the longer CO is present
Fault LED flashing Yellow 3 times
per minute
Fault LED flashing Yellow once per
minute
Power LED flashing Green once per
minute
1 (2, or 3) chirps once every 30
seconds, increasing the longer CO
is present
A dangerous CO condition is
building up.
Check Appliances
3 chirps per minute
The wireless module is not working
correctly
Refer to the wireless module
manual for further details
Chirp once per minute
End of Life
Replace the Alarm
Silent
Normal Operating Mode
None
Page 19 of 51
Honeywell
XC100
Page 20 of 51
Contact Details
Telephone
01202 645 577
Email
Website
consumer@honeywell.com
www.homesafety.honeywell.com
Main Features
Feature
Function
Power LED (Green)
Indicates that the unit is receiving power and is fully operational
Fault LED (Yellow)
Indicates low battery or fault
Ventilate LED (Blue)
Early warning of CO build-up
Alarm LED (Red)
Indicates an emergency situation
Test/Hush button
Used to test/silence the unit
Operating Features – Part 1 of 2
Light Indicator
Sound Emitted
What This Means
Alarm LED flashing Red
Continuous 4 chirps for 60 minutes
then once every 30 seconds
Dangerous levels of CO has been detected
Off
Continuous 4 chirps
Alarm LED flashing Red once per minute
Chirp once per minute
Off
Continuous 3 chirps
Fire detected by an interconnected fire alarm
Ventilate LED flashing Blue 1 (2, or 3)
times once every 30 seconds, increasing
the longer CO is present
1 (2, or 3) chirps once every 30
seconds, increasing the longer CO
is present
A dangerous CO condition is building up.
Dangerous levels of CO has been detected by another
interconnected CO alarm
Dangerous levels of CO was detected whilst user was
absent. Currently, no dangerous CO level present
Required Action
Follow Emergency
Procedures
Fault LED flashing Yellow 3 times per
minute
3 chirps per minute
The wireless module is not working correctly
Refer to the wireless
module manual for
further details
Fault LED flashing Yellow per minute
Chirp once per minute
End of Life
Replace the Alarm
Power LED flashing Green once per
minute
Silent
Normal Operating Mode
None
Page 21 of 51
Honeywell
XC100D
Page 1 of 2
Contact Details
Telephone
08009 170 722
Email
admin@kiddesafety.co.uk
Website
www.TenYCO.kiddefyrne0cs.co.uk
Main Features
Feature
Function
Power LED (Green)
Indicates that the unit is receiving power and is fully operational
Fault LED (Yellow)
Indicates low battery or fault
Ventilate LED (Blue)
Early warning of CO build-up
Alarm LED (Red)
Indicates an emergency situation
Test/Hush button
Used to test/silence the unit
Digital Display
Visual display of product’s indicators
Operating Features – Part 1 of 2
Digital Screen
Light Indicator
Sound Emitted
What This Means
Required Action
Power LED flashing Green
Continuous 4 chirps for 60
minutes then once every 30
seconds
Dangerous levels of CO has been
detected
Follow Emergency Procedures
Off
Continuous 4 chirps
Dangerous levels of CO has been
detected by another
interconnected CO alarm
Page 22 of 51
Honeywell
Digital Screen
Light Indicator
Alarm LED flashing Red once per
minute
Sound Emitted
Chirp once per minute
XC100D
Page 2 of 2
What This Means
Required Action
Dangerous levels of CO was
detected whilst user was absent.
Currently, no dangerous CO level
present
Dangerous levels of CO was
detected whilst user was absent.
Currently, no dangerous CO level
present
Follow Emergency Procedures
Alarm LED flashes Red once per
minute
Chirp once per minute
Off
Continuous 3 chirps
Fire detected by an
interconnected fire alarm
Contact Emergency Services
Ventilate LED flashing Blue 1 (2,
or 3) times once every 30
seconds, increasing the longer
CO is present
1 (2, or 3) chirps once every 30
seconds, increasing the longer
CO is present
A dangerous CO condition is
building up.
Follow Emergency Procedures
Fault LED flashing Yellow 3 times
every minute
3 chirps per minute
The wireless module is not
working correctly
Refer to the wireless module
manual for further details
Fault LED flashing Yellow once
every minute
Chirp once per minute
End of Life
Replace the Alarm
Power LED flashing Green once
every minute
Silent
Normal Operating Mode
None
Page 23 of 51
EI Electronics
Ei208
Page 1 of 2
Contact Details
Telephone
+44 (0) 1691 664 100
Email
sales@aico.co.uk
Website
www.aico.co.uk
Main Features
Feature
Function
Power LED (Green)
Indicates that the unit is receiving power and is fully operational
Fault LED (Amber)
Indicates low battery/fault/end of life
Alarm LED (Red)
Indicates an emergency situation
Test & Hush Button
Used to test/silence the unit
Operating Features
Light Indicator
Alarm LED flashing Red 1, 2 or 4
times every 2 seconds (the higher
the CO concentration the more
flashes)
Alarm LED flashing Red 2, 4 or 8
times every 40 seconds (the higher
the CO concentration the more
flashes)
Fault LED flashing Amber 3 times
every 40 seconds
Sound Emitted
What This Means
Required Action
Continual audible signal
Dangerous levels of CO has been
detected
Follow Emergency Procedures
Silent
The detector has alarmed
previously (within 24 hours)
Check appliances and reset
detector memory by holding down
the Test & Hush button for 20
seconds
3 Beeps every 40 seconds
End of Life
Replace the Alarm
Page 24 of 51
EI Electronics
Ei208
Page 2 of 2
Operating Features – Part 2 of 2
Light Indicator
Fault LED flashing Amber twice
every 40 seconds
Fault LED flashing Amber once
every 40 seconds
Power LED on Green
Sound Emitted
What This Means
Required Action
2 Beeps every 40 seconds
Sensor Fault
Replace the Alarm
1 Beep every 40 seconds
Low Battery
Replace the Alarm
Silent
Normal Operating Mode
None
Page 25 of 51
EI Electronics
E261ENRC
Contact Details
Telephone
+44 (0) 1691 664 100
Email
sales@aico.co.uk
Website
www.aico.co.uk
Main Features
Feature
Function
Power LED (Green)
Indicates that the unit is receiving power and is fully operational
Fault LED (Amber)
Indicates low battery/fault/end of life
Alarm LED (Red)
Indicates an emergency situation
Test & Hush Button
Used to test/silence the unit
Operating Features
Light Indicator
Sound Emitted
What This Means
Required Action
Alarm LED flashing Red
Loud continual signal (3 pulses,
followed by a pause. Repeated)
Dangerous levels of CO has been
detected
Follow Emergency Procedures
Silent
The detector has alarmed
previously (within 24 hours)
Check appliances and reset
detector memory by holding down
the Test & Hush button for 20
seconds
1 Beeps every 40 seconds
Sensor Fault
Replace the Alarm
1 Beep every 40 seconds
Low Battery
Replace the Alarm
Silent
Normal Operating Mode
None
Alarm LED flashing Red 2, 4 or 8
times every 40 seconds (the higher
the CO concentration the more
flashes)
Fault LED flashing Amber twice
every 40 seconds
Off
Power LED on (Green)
Page 26 of 51
FirstAlert
SCO5
Page 27 of 51
Contact Details
Telephone
+44 (0) 8001 412 561 / +44 (0) 2477 717 570
Email
info@firstalert.eu
Website
www.firstalert.eu
Main Features
Feature
Function
Power LED (Green)
Indicates that the unit is receiving power
CO/Smoke LED (Red)
Indicates an emergency CO/Smoke situation
Test/Silence
Used to test/silence the unit
Operating Features
Light Indicator
CO LED flashing Red. Power/Smoke
LED off
Power/Smoke LED flashing Red. CO
LED off
Off
Sound Emitted
What This Means
Chirps once per minute
Dangerous levels of CO has been
detected
Dangerous levels of Smoke has
been detected
Low Battery
LED has 3 rapid flashes together
with chirps
Three chirps per minute
Fault
Power LED flashing Green
5 chirps per minute
End of Life
4 beeps, pause, 4 beeps, pause
3 beeps, pause, 3 beeps, pause
Page 28 of 51
Required Action
Follow Emergency Procedures
Follow Emergency Procedures
Replace batteries
If product is still under warranty
contact ‘technical support’ if not
replace alarm
Replace the Alarm
FirstAlert
SCO7
Page 1 of 2
Contact Details
Telephone
+44 (0) 8001 412 561 / +44 (0) 2477 717 570
Email
info@firstalert.eu
Website
www.firstalert.eu
Main Features
Feature
Function
Power LED (Green)
Indicates that the unit is receiving power
CO/Smoke LED (Red)
Indicates an emergency CO/Smoke situation
Test/Silence
Used to test/silence the unit
Operating Features – Part 1 of 2
Light Indicator
Sound Emitted
CO LED flashing Red. Power/Smoke
LED off
Power/Smoke LED flashing Red. CO
LED off
Off
4 beeps, pause, 4 beeps, voice
(“Warning, evacuate carbon
monoxide in ‘location’. Evacuate.”
“___ppm”.)
3 beeps, pause, 3 beeps, voice
(“Warning, evacuate smoke in
‘location’. Evacuate.”)
Chirps once per minute; Voice:
“Replace battery in ‘Location’
every 5 hours”
What This Means
Required Action
Dangerous levels of CO has been
detected
Follow Emergency Procedures
Dangerous levels of Smoke has
been detected
Follow Emergency Procedures
Low Battery
Replace batteries
FirstAlert
SCO7
Page 29 of 51
Page 2 of 2
Operating Features – Part 2 of 2
Light Indicator
LED has 3 flashes together with
chirps
Power LED flashing Green once a
minute
Sound Emitted
Three chirps every minute; Voice:
“Detector error in ‘Location’,
please see manual” every 5 hours
5 chirps every minute; Voice:
“Detector error in ‘Location’,
please see manual.” Repeated
every 5 hours.
Page 30 of 51
What This Means
Required Action
Fault
If product is still under warranty
contact ‘technical support’ if not
replace alarm
End of Life
Replace the Alarm
FirstAlert
GCO1
Page 1 of 2
Contact Details
Telephone
+44 (0) 8001 412 561 / +44 (0) 2477 717 570
Email
info@firstalert.eu
Website
www.firstalert.eu
Main Features
Feature
Function
Green LED
Indicates that the unit is receiving power
Red LED
Indicates an emergency CO/Gas situation
Peak Level
Recalls highest CO level recorded (within 24 hours)
Test/Silence
Used to Test/Silence the unit
Digital Display
Visual display of product’s indicators
Operating Features – Part 1 of 2
Digital Screen
Light Indicator
Sound Emitted
What This Means
Required Action
Red LED flashing in sync with
alarm
4 beeps, pause. Repeating.
Dangerous levels of CO has
been detected
Follow Emergency Procedures
Red LED flashing in sync with
alarm
1 beeps per second
Dangerous levels of Gas has
been detected
Follow Emergency Procedures
GCO1
Page 2 of 2
FirstAlert
Page 31 of 51
Operating Features – Part 2 of 2
Digital Screen
Light Indicator
Sound Emitted
What This Means
Required Action
Green LED flashing 5 times
per minute in sync with chirps
5 chirps per minute
End of Life
Replace the Alarm
Green LED flashing 3 times
per minute in sync with chirps
3 chirps per minute
Malfunction
Replace the Alarm
OFF
Single chirp per minute
Low/Missing Battery
Replace/Insert batteries
Green LED on
Silent
Normal Operating Mode
None
Page 32 of 51
FirstAlert
CO400
Contact Details
Telephone
+44 (0) 8001 412 561 / +44 (0) 2477 717 570
Email
info@firstalert.eu
Website
www.firstalert.eu
Main Features
Feature
Function
Red LED
Indicator of different alarm states
Test/Silence button
Used to test/silence the unit
Operating Features
Light Indicator
Sound Emitted
What This Means
Required Action
Red LED flashing rapidly
Loud signal (4 beeps, pause, 4
beeps. Repeating)
Dangerous levels of CO has been
detected
Follow Emergency Procedures
5 chirps per minute
End of Life
Replace the Alarm
Red LED flashing 5 times per
minute in sync with chirps
Red led flashing 3 times per minute
in sync with chirps
Red LED flashing once per minute
3 chirps per minute
Malfunction
Replace the Alarm
Single chirp per minute
Low Battery
Replace Batteries
Red LED flashing once per minute
None
Normal Operating Mode
None
Page 33 of 51
FirstAlert
SCO500
Page 1 of 2
Contact Details
Telephone
+44 (0) 8001 412 561 / +44 (0) 2477 717 570
Email
info@firstalert.eu
Website
www.firstalert.eu
Main Features
Feature
Function
Power/Smoke LED
(Green/Red)
CO LED (Red)
Indicates that the unit is receiving power/Indicates an emergency
smoke situation
Indicates an emergency CO
Test/Silence button
Used to test/silence the unit
Operating Features – Part 1 of 2
Light Indicator
Power/Smoke LED: Off
CO LED: During Alarm: Flashes Red
in sync with the alarm.
After Alarm: Flashes Red (On for 2
seconds/Off for 2 seconds)
Power Smoke LED: During Alarm:
Flashes Red in sync with alarm.
After Alarm: Flashes Red (On for 2
seconds/Off for 2 seconds)
CO LED: Off
Sound Emitted
What This Means
Required Action
Alarm: 4 beeps, pause, 4 beeps,
voice (Repeated)
Voice: “Warning, evacuate carbon
monoxide in [Location]. Evacuate,”
“___ ppm.”
Dangerous levels of CO has been
detected
Follow Emergency Procedures
Alarm: 3 beeps, pause, 3 beeps,
voice
(Repeated)
Voice: “Warning, evacuate smoke
in [Location]. Evacuate”
Dangerous levels of Smoke has
been detected
Follow Emergency Procedures
Page 34 of 51
FirstAlert
SCO500
Page 2 of 2
Operating Features – Part 2 of 2
Light Indicator
Power/Smoke LED: flashing Red 5
times per minute
Power/Smoke LED: flashing Green
3 times once a minute. CO LED: Off
Power/Smoke LED: flashing Green
(On for 2 seconds/Off for 2
seconds)
CO LED: Off
Power/Smoke LED: Flashing Green
once per minute
CO LED: Off
Sound Emitted
What This Means
Required Action
Horn: 5 chirps every minute
Voice: “Detector error in
[Location], please see manual.”
Repeated every 5 hours
Horn: 3 chirps every minute
Voice: “Detector error in
[Location].” Repeated every 5
hours
Chirps once a minute
Voice: “Replace battery in
[Location].” Repeated every 5
hours
End of Life
Replace the Alarm
Malfunction
Replace the Alarm
Low Battery
Replace Batteries
Silent
Normal Operating Mode
None
Page 35 of 51
FirstAlert
CO250
Contact Details
Telephone
+44 (0) 8001 412 561 / +44 (0) 2477 717 570
Email
info@firstalert.eu
Website
www.firstalert.eu
Main Features
Feature
Power/Alarm LED (Red)
Test/Silence Button
Function
Indicates that the unit is receiving power/Indicates an emergency CO
situation
Used to test/silence the unit
Operating Features
Light Indicator
Sound Emitted
What This Means
Required Action
Power/Alarm LED flashing Red
rapidly
Power/Alarm LED flashing Red
rapidly 5 times per minute in sync
with chirps
Power/Alarm LED flashing Red 3
times per minute in sync with
chirps
Power/Alarm LED flashing Red
once per minute
Power/Alarm LED flashing Red
once per minute
Loud signal (4 beeps, pause, 4
beeps. Repeating)
Dangerous levels of CO has been
detected
Follow Emergency Procedures
5 chirps per minute
End of Life
Replace the Alarm
3 chirps per minute
Malfunction
Replace the Alarm
Single chirp per minute
Low Battery
Replace Batteries
None
Normal Operating Mode
None
Page 36 of 51
FirstAlert
CO600
Contact Details
Telephone
+44 (0) 8001 412 561 / +44 (0) 2477 717 570
Email
info@firstalert.eu
Website
www.firstalert.eu
Main Features
Feature
Power/Alarm LED (Red)
Test/Silence Button
Function
Indicates that the unit is receiving power/Indicates an emergency CO
situation
Used to test/silence the unit
Operating Features
Light Indicator
Sound Emitted
What This Means
Required Action
Power/Alarm LED flashing Red
rapidly
Power/Alarm LED flashing Red
rapidly 5 times per minute in sync
with chirps
Power/Alarm LED flashing Red 3
times per minute in sync with
chirps
Power/Alarm LED flashing Red
once per minute
Power/Alarm LED flashing Red
continuously
Loud signal (4 beeps, pause, 4
beeps. Repeating)
Dangerous levels of CO has been
detected
Follow Emergency Procedures
5 chirps per minute
End of Life
Replace the Alarm
3 chirps per minute
Malfunction
Replace the Alarm
Single chirp per minute
Low Battery
Replace Batteries
None
Normal Operating Mode
None
Page 37 of 51
FirstAlert
CO605
Page 1 of 2
Contact Details
Telephone
+44 (0) 8001 412 561 / +44 (0) 2477 717 570
Email
info@firstalert.eu
Website
www.firstalert.eu
Main Features
Feature
Power/Alarm LED (Red)
Test/Silence Button
Function
Indicates that the unit is receiving power/Indicates an emergency CO
situation
Used to test/silence the unit
Operating Features – Part 1 of 2
Light Indicator
Sound Emitted
What This Means
Required Action
Power/Alarm LED flashing Red in
sync with alarm
Power/Alarm LED flashing Red
rapidly 5 times per minute in sync
with chirps
Power/Alarm LED flashing Red 3
times per minute in sync with
chirps
Power/Alarm LED flashing Red
once per minute
Power/Alarm LED flashing Red
continuously
Loud signal (4 beeps, pause, 4
beeps. Repeating)
Dangerous levels of CO has been
detected
Follow Emergency Procedures
5 chirps per minute
End of Life
Replace the Alarm
3 chirps per minute
Malfunction
Replace the Alarm
Single chirp per minute
Low Battery
Replace Batteries
None
Normal Operating Mode (AC)
None
Page 38 of 51
FirstAlert
SCO605
Page 2 of 2
Operating Features – Part 2 of 2
Light Indicator
Sound Emitted
What This Means
Required Action
Power/Alarm LED flashing Red
continuously
None
Normal Operating Mode (Battery
Back-Up)
None
Page 39 of 51
FirstAlert
CO615
Page 1 of 2
Contact Details
Telephone
+44 (0) 8001 412 561 / +44 (0) 2477 717 570
Email
info@firstalert.eu
Website
www.firstalert.eu
Main Features
Feature
Power/Alarm LED
(Green/Red)
Test/Silence Button
Indicates that the unit is receiving power/Indicates an emergency CO
situation
Used to test/silence the unit
Peak Level Button
Peak Level Button
Digital Display
Visual display of product’s indicators
Operating Features
Digital Screen
Light Indicator
Sound Emitted
What This Means
Required Action
Red LED flashing in sync with
alarm
4 beeps, pause. Repeating.
Dangerous levels of CO has
been detected
Follow Emergency Procedures
Green LED flashing 5 times
per minute in sync with chirps
5 chirps per minute
End of Life
Replace the Alarm
Green LED flashing 3 times
per minute in sync with chirps
3 chirps per minute
Malfunction
Replace the Alarm
Page 40 of 51
FirstAlert
GCO1
Page 2 of 2
Operating Features – Part 2 of 2
Digital Screen
Light Indicator
Sound Emitted
What This Means
Required Action
Power/Alarm LED on Green (if
AC power is present)
Power/Alarm LED Off (if AC
power is not present)
Single chirp per minute
Low/Missing Battery
Replace/Insert battery
Green LED on
Silent
Normal Operating Mode
None
Page 41 of 51
FirstAlert
PC900V
Page 1 of 2
Contact Details
Telephone
+44 (0) 8001 412 561 / +44 (0) 2477 717 570
Email
info@firstalert.eu
Website
www.firstalert.eu
Main Features
Feature
Power LED (Green/Red)
Test/Silence Button
Function
Indicates that the unit is receiving power/Indicates an emergency CO
situation
Used to test/silence the unit
Operating Features – Part 1 of 2
Light Indicator
Power LED: flashing Red
Power LED: flashes Red
Power LED: flashing Green five
times per minute
Sound Emitted
Voice: “Warning, evacuate carbon
monoxide in [Location]. Evacuate.”
“___ ppm.”
Horn: 4 beeps, pause, 4 beeps,
voice
Voice: “Warning, evacuate smoke
in [Location]. Evacuate.”
Horn: 3 beeps, pause, 3 beeps,
voice
Voice: “Detector error in
[Location], please see
manual.”(repeated every 5 hours)
Horn: 5 chirps every 5 minutes
What This Means
Required Action
Dangerous levels of CO has been
detected
Follow Emergency Procedures
Dangerous levels of Smoke has
been detected
Follow Emergency Procedures
End of Life
Replace the Alarm
Page 42 of 51
FirstAlert
PC900V
Page 2 of 2
Operating Features – Part 2 of 2
Light Indicator
Power LED: three Green flashes
approximately once per minute
Power LED: flashes Green
approximately once per minute
Power LED: flashes Green once a
minute
Sound Emitted
Voice: “Detected error in
[Location], please see manual.”
(repeated every 5 hours)
Horn: 3 chirps every minute
Voice: “Replace battery in
[Location].” (repeated every 5
hours)
Horn: chirps once a minute
Silent
Page 43 of 51
What This Means
Required Action
Malfunction
Replace the Alarm
Low Battery
Replace Batteries
Normal Operating Mode
None
FirstAlert
CO710
Contact Details
Telephone
+44 (0) 8001 412 561 / +44 (0) 2477 717 570
Email
info@firstalert.eu
Website
www.firstalert.eu
Main Features
Feature
Test Button
Used to test the unit
Silence Button
Used to silence the unit
Digital Display
Visual display of product’s indicators
Operating Features
Digital Screen
Light Indicator
Sound Emitted
What This Means
Required Action
NA
Repeating 4 beeps, pause
Dangerous levels of CO has
been detected
Follow Emergency Procedures
NA
3 chirps every minute
Malfunction
Replace the Alarm
NA
5 chirps every minute
End of Life
Replace the Alarm
NA
Silent
Normal Operating Mode
(Displaying Temperature)
None
Page 44 of 51
BRK
CO4000EN
Contact Details
Page 45 of 51
Telephone
+44 (0) 1452 877 570
Email
sales@brkelectronics.eu
Website
www.brkelectronics.eu
Main Features
Feature
Power/Alarm LED (Red)
Test/Silence Button
Function
Indicates that the unit is receiving power/Indicates an emergency CO
situation
Used to test/silence the unit
Operating Features
Light Indicator
Power/Alarm LED flashes Red
rapidly
Red LED flashes
Power/Alarm LED flashes Red once
every minute
Power/Alarm LED flashes Red once
every minute
Sound Emitted
What This Means
Required Action
3 chirps every minute
Dangerous levels of CO has been
detected
Malfunction/End of Life
1 chirp every minute
Low Battery
Replace Batteries
Silent
Normal Operating Mode
None
Repeating 4 beeps, pause
Page 46 of 51
Follow Emergency Procedures
Replace the Alarm
BRK
CO850
Contact Details
Telephone
+44 (0) 1452 877 570
Email
sales@brkelectronics.eu
Website
www.brkelectronics.eu
Main Features
Feature
Function
Power LED (Green)
Indicates that the unit is receiving power and is fully operational
Fault LED (Yellow)
Indicates low battery/fault/end of life
Alarm LED (Red)
Indicates an emergency situation
Test/Reset Button
Used to test/reset/silence the unit
Operating Features
Light Indicator
Sound Emitted
What This Means
Power LED flashes Red
Repeating 4 beeps, pause
Off
Repeating 4 beeps, pause
Off
3 short beeps every minute
Dangerous levels of CO has been
detected
Dangerous levels of CO has been
detected at an interconnected
alarm
End of Life
Fault LED is on Yellow
2 short beeps every minute
Fault
Replace the Alarm
Fault LED flashes Yellow
Single beep every minute
Low Battery
Replace the Alarm
Power LED is on Green
Silent
Normal Operating Mode
None
Page 47 of 51
Required Action
Follow Emergency Procedures
Follow Emergency Procedures
Replace the Alarm
NEST
PROTECT
Page 1 of 2
Contact Details
Telephone
+44 (0) 8081 692 307 (Support line – Mon-Fri from 07:00 to 19:00 –
Sat-Sun from 09:00 to 17:00)
Email
https://nest.com/uk/support/email-us/
Website
https://nest.com/uk/support/smoke-co-alarm/
Main Features
Feature
Function
Green Light Indicator
Indicates that the unit is receiving AC power and is fully operational
Light Ring (Blue)
White Light
Indicates that the unit is in testing mode
Indicates a build-up of CO/Smoke, low battery and that the alarm has
been hushed
Indicates an emergency CO/Smoke situation and that the alarm has
been hushed
Pathlight in darkness
Nest Button
Used to test/silence the unit
Light Ring (Yellow)
Light Ring (Red)
Operating Features – Part 1 of 3
Light Indicator
Light pulses Red
Light pulses Red
Sound Emitted
“Emergency, there’s carbon
monoxide in (room name). Move
to fresh air now.”
“Emergency, there’s smoke in
(room name).”
What This Means
Required Action
The carbon monoxide in the room
has reached emergency levels
Follow Emergency Procedures
The smoke in the room has
reached emergency levels
Follow Emergency Procedures
Page 48 of 51
NEST
PROTECT
Page 2 of 2
Operating Features – Part 2 of 3
Light Indicator
Light pulses Red
Light pulses Red
Light pulses Yellow
Light pulses Yellow
Light pulses Yellow or Red
None
None
Sound Emitted
“Emergency, there’s carbon
monoxide in (room name). Move
to fresh air now.”
“Emergency, there’s smoke in
(room name).”
“Heads-up, there’s carbon
monoxide in the (room name). The
alarm may sound.”
What This Means
Required Action
The carbon monoxide in the room
has reached emergency levels
Follow Emergency Procedures
The smoke in the room has
reached emergency levels
Carbon monoxide levels are rising.
This heads-up will occur if carbon
monoxide levels stay at 70ppm for
60-240 minutes.”
“Heads-up, there’s smoke in the
(room name). The alarm may
sound.”
“Smoke Alarm has been hushed,”
or “Carbon Monoxide Alarm has
been hushed.”
Voice: “Nest product has expired.
Replace it now.”
Horn: Two chirps every 60 seconds
Voice: “The sensors have failed in
the (room name), replace nest
protect now.”
Horn: Single chirp every 60
seconds
Page 49 of 51
Call the Emergency Services
Follow Emergency Procedures
Smoke levels are rising
Follow Emergency Procedures
You’ve hushed an alert
Follow Emergency Procedures
End of Life
Replace the Alarm
Malfunction
Clean with compressed air. If the
problem persists, replace it
NEST
PROTECT
Page 3 of 3
Operating Features – Part 3 of 3
Light Indicator
Sound Emitted
What This Means
Required Action
Light pulses Yellow
Voice: “The battery is very low in
the (room name). Replace the
battery now.”
Horn: Single chirp every 60
seconds
Batteries have been depleted
Replace Batteries
Page 50 of 51
Light pulses Yellow
“The battery is low in the (room
name). Replace the battery soon.”
Low battery
Replace Batteries
Blue light rotating
“Ready, press to test.”
To setup or run a manual test
Press the Nest button. Nest Protect
will walk you through next steps.
White Light
Silent
Green Light pulses once after lights
have been switched off at night
Silent
Green Light is on
Silent
Pathway lights your way as you
pass under it
The unit has tested its sensors and
batteries to confirm they are
working correctly
The product is connected to AC
power and is fully operational
Page 51 of 51
None
None
None