AX-WLD-DTA
Drip Tray Water Level Alarm Module 230Vac
Product Overview
The AX-WLD-230-A is a single zone Drip tray
water level alarm module which can be supplied in
an enclosure. The module can have a total of
200m of cable connected (cable and header). The
sensitivity is adjustable to ensure false alarms are
not given. A loud alarm buzzer is built in.
Features
•
A total of 200m cable can be connected
•
Loud audible alarm (100db)
•
Adjustable sensitivity
•
Input from point sensors
Product Specifications
Supply Voltage:
Supply Current
Relay:
Relay Output:
Audible alarm output
Alarm Delay Time:
LED Indication:
Electrical Connections
Dimensions:pcb
Ambient Range:
Country of Origin:
230Vac@50Hz +/- 15%
50mA max
SPST
6A inductive@230Vac
100dB@ 1m
15 Minutes (buzzer will switch off after 15mins)
On when energised
Rising cage teminals for 0.5-2.5mm2 cable
105 x 59 x 28mm approx
-10 to +50deg C, 0-90% RH condensing
U.K.
Order Codes:
AX-WLD-DTA
AX-WLD-DTA-ENC
AX-WPS
AX-WLD-ENC
230Vac Drip Tray Water level alarm module
230Vac Drip Tray Water level alarm module complete with enclosure
Point sensor for AX-WLD-230-A c/w 2m cable
Ventilated enclosure for AX-WLD-230-A
Enclosure :
Housing:
White ABS (UL Rated)
Dimensions:
147 x 88 x 42
Protection:
IP20
Weight: complete 305gms
AX-WLD-DTA - Issue 1.2 - Date 9/3/2009
Page 1 of 3
Unit 21, Highview, High Street, Bordon, Hampshire. GU35 0AX.
Tel: +44 (0)1420 487788 Fax: +44 (0)1420 487799
Email: sales@axio.co.uk
www.axio.co.uk
© Copyright Axio 2004. All Rights Reserved
AX-WLD-DTA
Drip Tray Water Level Alarm Module 230Vac
Installation
SAFETY NOTE:
Prior to Installation ensure that all power sources are disconnected and locked-out and remain locked out during
Installation and set-up, as severe injury or death can result from Electric Shock due to contact with High Voltage
Conductors. Ensure all installations are in complance wth applicable electrical codes and that the installation is carried
out by qualified installers familiar with the relevant standards and proper safety procedures for high voltage
installations. Never rely on status indication on any device to determine if power is present .
Sensitivity:
Power the WLD-DTA and adjust the sensitivity potentiometer on the WLD-DTA by turning anti-clockwise until the LED
comes on, and then back clockwise until the LED goes off. Less sensitivity may be needed when long runs of cable are
used. Where short cables are used the LED may not come on even when set to maximum sensitivity.
Testing:
To test the installation put a wet cloth over the probes to simulate a water leak, the buzzer will come on. Remove the cloth
and remove power from unit to turn the buzzer off.
Audible Alarm Output:
Tthe jumper can be temporarily placed in the LO position to attenuate the alarm during commissioning.
Connection
Supply input
230Vac
Sensitivity
Adjustment
L
Transformer
N
Alarm
Buzzer
LED Indication
Com
Relay
Sensor
Input
Relay
HI LO
Sounder
Jumper
Interlock - if used with a fan coil to detect
condensate overflow
Please interlock the 230Vac supply to the supply of the Fan
coil to ensure the only way the sounder can be turned off is to
switch off the fan coil as well as the waterleak detector
Every effort has been taken in the production of this data sheet to ensure it’s accuracy. Axio can not, however, accept responsibility for any damage, expense, injury, loss or consequential loss
resulting from any errors or omissions. Axio has a policy of continuous improvement and reserves the right to change this specification without notice.
AX-WLD-DTA - Issue 1.2 - Date 9/3/2009
Page 2 of 3
Unit 21, Highview, High Street, Bordon, Hampshire. GU35 0AX.
Tel: +44 (0)1420 487788 Fax: +44 (0)1420 487799
Email: sales@axio.co.uk
www.axio.co.uk
© Copyright Axio 2004. All Rights Reserved
AX-WLD-DTA
Drip Tray Water Level Alarm Module 230Vac
AX-WPS Point Sensors
Technical Overview
The AX-WPS water leak point sensor is used to
detect water in a drip-tray, and is used in conjunction
with the AX-WLD-DTA detection module.
Features
• More than one can be connected to AX-WLD-DTA • Robust housing
• Slot lugs for easy installation
• 2 Stainless steel probes
Specifications
Housing
Material:
Protection Rating:
Cable length:
Dimensions:
Black ABS
UL94-HB
2m
50 x 35 x 20mm
Probes:
Material:
Dimensions:
Country of origin:
Stainless steel
13mm x 3mm dia.
UK
Installation
1. Fix the AX-WPS in the location where leak detection is required.
2. The AX-WPS is fitted with a 2 meter leader cable that can be connected to a AX-WLD-DTA alarm
module. (A maximum of 200 meters is allowed for each AX-WLD-DTA).
3. Connect the 2-core leader cable to the AX-WLD-DTA alarm module sensor input (polarity independent).
4. Power the AX-WLD-DTA, and adjust the pot on the PCB anti-clockwise until the LED comes on, and
then back clockwise until the LED goes off
5. Test the sensor by placing a damp cloth over the stainless steel probes to simulate a water leak, the
buzzer will come on. Remove the cloth and power from the unit to turn the buzzer off.
6. More than one AX-WPS can be connected to a AX-WLD-DTA alarm module, as long as the total cable
run does not exceed 200 meters.
Page 3 of 3
AX-WLD-DTA - Issue 1.2 - Date 9/3/2009
Unit 21, Highview, High Street, Bordon, Hampshire. GU35 0AX.
Tel: +44 (0)1420 487788 Fax: +44 (0)1420 487799
Email: sales@axio.co.uk
www.axio.co.uk
© Copyright Axio 2004. All Rights Reserved