Crompton AC Current and Voltage Transducers

Crompton AC Current and Voltage Transducers
• CE Compliant (CE Marked)
• Flexible Design with up to Three Transducers
in One Housing
• UL Approved
• Enclosure to IEC529 (IP50)
• Flame Retardant
• 35 mm DIN Rail Mount or Key Hole Slots
AC Current, Voltage, Frequency and DC
• Average Sensing and True RMS
• Self Powered and Auxiliary
• Current Measuring to 0.5% Accuracy
• Isolated Input and Output
L
253
FREQUENCY
Frequency
45–55 Hz
55–65 Hz
45–65 Hz
360–440 Hz
Output
0–1 mADC
0–1 mADC
0–1 mADC
0–1 mADC
Catalog Number
253-THZU-PQFA-AG
253-THZU-PQFA-AN
253-THZU-PQFA-AJ
253-THZU-PQFA-BI
TRANSDUCERS /
SENSORS
Input
120 VAC
120 VAC
120 VAC
120 VAC
AC CURRENT
Input
AC Current—Average Sensing, Single-Phase
5A AC/60 Hz
5A AC/60 Hz
AC Current—Average Sensing, 3-Phase, 3 DC Outputs 5A AC/60 Hz
5A AC/60 Hz
AC Current—True RMS Sensing, Single-Phase
5A AC/60 Hz
AC Current—True RMS Sensing, 3-Phase, 3 DC Outputs 5A AC/60 Hz
AC Current—Bi-Directional
5A AC/60 Hz
Auxiliary Power
Self
120 VAC
120 VAC
120 VAC
120 VAC
120 VAC
Self (120 VAC)
Output
0–1 mADC
4–20 mADC
0–1 mADC
4–20 mADC
0–1 mADC
0–1 mADC
±1 mADC
Catalog Number
253-TAAU-LSFA-C6
253-TALU-LSHG-C6-DG
256-TASU-LSFA-C6-DG
256-TALU-LSHG-C6-DG
253-TARU-LSFA-C6-DG
256-TARU-LSFA-C6-DG
256-TABU-LSM1-C6-PQ-T3
AC VOLTAGE
Input
Auxiliary Power
Output
AC Voltage—Average Sensing, Single-Phase
120 VAC/60 Hz
Self
0–1 mADC
120 VAC/60 Hz
120 VAC
4–20 mADC
AC Voltage—True RMS Sensing, Single-Phase
120 VAC/60 Hz
120 VAC
0–1 mADC
AC Voltage—True RMS Sensing, 3-Phase, 3 DC Outputs
120 VAC/60 Hz
120 VAC
0–1 mADC
Input
System
Output
AC Voltage—Average Sensing, 3-Phase, 3 DC Outputs
120 VAC/60 Hz
3-Phase, 3-Wire
4–20 mADC
120 VAC/60 Hz
3-Phase, 4-Wire
0–1 mADC
Input
Auxiliary Power
Output
AC Voltage—Suppressed Zero AC, Expanded Scale
108–132 VAC
Self
0–1 mADC
Catalog Number
253-TVAU-PQFA-C6
253-TVLU-PQHG-C6-DG
253-TVRU-PQFA-C6-DG
256-TVRU-PQFA-C6-DG
Catalog Number
256-TVLU-PQHG-C6-DG
256-TVSU-PQFA-C6-DG
Catalog Number
253-TVZU-A9FA-C6
100
Crompton Transducers
AC Power Transducers
• Wide Range of Transducers to Measure All Forms of Power
• Available in Single-Phase, 3-Phase 3- or 4-Wire
• Self Powered Units Permit Voltage Variations Up to 20% of
Nominal Input
• Measures both Import and Export Power
• Accuracy Class 0.5
DC/DC & TEMPERATURE
Input
Auxiliary Power
Output
Catalog Number
DC Current
120 VAC
0–1 mADC
256-TTAU-**FA-DG
DC Millivolts
120 VAC
0–1 mADC
256-TTMU-**FA-DG
DC Voltage
120 VAC
0–1 mADC
256-TTVU-**FA-DG
K Thermocouple
120 VAC
0–1 mADC
256-TTNU-KTFA-DG
T Thermocouple
120 VAC
0–1 mADC
256-TTCU-TTFA-DG
J Thermocouple
120 VAC
0–1 mADC
256-TTFU-JTFA-DG
AC POWER
TRANSDUCERS /
SENSORS
System
Input
Type
Output
Catalog Number
1 Ph, 2 Wire
120V/5A
1 Element
0-1 mADC
256-TWKU-QQFA-C6-**
1 Ph, 3 Wire
240V/10A
1 Element
0-1 mADC
256-TWKU-Q8FA-C6-**
3 Ph, 3 Wire
120V/5A
2 Element
0-1 mADC
256-TWMU-QQFA-C6-**
3 Ph, 4 Wire
120V/5A
2 /2 Element
0-1 mADC
256-TWNU-QQFA-C6-**
AC Watts (Active Power)
1
** Specify Range
AC VARS (Reactive Power)
1 Ph, 2 Wire
120V/5A
1 Element
0-1 mADC
256-TXKU-QQFA-C6-**
1 Ph, 3 Wire
240V/10A
1 Element
0-1 mADC
256-TXKU-Q8FA-C6-**
3 Ph, 3 Wire
120V/5A
2 Element
0-1 mADC
256-TXMU-QQFA-C6-**
3 Ph, 4 Wire
120V/5A
2 /2 Element
0-1 mADC
256-TXNU-QQFA-C6-**
1 Element
0-1 mADC
256-TYKU-QQFA-C6-**
1
** Specify Range
AC VA (Apparent Power)
1 Ph, 3 Wire
120V/10A
3 Ph, 3 Wire
120V/5A
2 Element
0-1 mADC
256-TYMU-QQFA-C6-**
3 Ph, 4 Wire
120V/5A
2 1/2 Element
0-1 mADC
256-TYNU-QQFA-C6-**
** Specify Range
Power Factor (Suits Analog Meters) - Accuracy Class 0.2
101
1 Ph, 2 Wire
120V/5A
0-1-0
1-0-1 mADC
256-XFSU-QQFA-C3-Z1-DG
1 Ph, 2 Wire
120V/5A
1-0-1-0-1
1-0-1 mADC
256-XFAU-QQFA-C3-E4-DG
3 Ph, 3 Wire
120V/5A
0-1-0
1-0-1 mADC
256-XFWV-QQFA-C3-Z1-DG
3 Ph, 3 Wire
120V/5A
1-0-1-0-1
1-0-1 mADC
256-XFGU-QQFA-C3-E4-DG
3 Ph, 4 Wire
120V/5A
0-1-0
1-0-1 mADC
256-XFVU-QQFA-C3-Z1-DG
3 Ph, 4 Wire
120V/5A
1-0-1-0-1
1-0-1 mADC
256-XFDU-QQFA-C3-E4-DG
Crompton Power & Energy Transducer Systems
L
• Replaces multiple single function transducers
• Measures up to 50 electrical parameters
• True 3 and 4 wire measurement
• Power, energy & power quality data
• Pulsed, analogue and digital outputs
• Programmable VT and CT ratios
• Local or remote configuration & monitoring
• DIN rail or base mounted styles
1560
Up to 50 electrical and power quality parameters can be measured
and communicated into building management systems or viewed
through the PC configuration software.
ORDERING INFORMATION
To Order: Insert Code for Each Letter to Select Catalog Number.
These transducers can be programmed using the configuration
software or the optional Integra display unit. The display unit can
be permanently mounted near the transducer, or connected when
configuration or status information is required.
Example INT-1563-M-5-M-013-1
INT- A – B – C – D – E
A
SPECIFICATIONS
Volt age
120% nominal
2x for 1 sec.
< 0.2 VA
up to 400kV **
9999:5A **
Cur rent
120% nominal
20x for 1 sec.
< 0.6 VA
B
Two wire half duplex
2400, 4800, 9600, 19200
Clean contact SPNO, 100V DC 0.5A max
60, 100 or 200 milliseconds
85-287 V AC / 85-312 V DC Absolute,45-66 Hz
10.2-60 V DC Absolute
6VA
80-120% of nominal (functional 5-120%)
5-120% of nominal
45-66Hz
0.8 capacitive to 0.8 inductive
Up to 31st harmonic 0% - 40%
7 digit resolution
±0.17% of range
0.15% of mid frequency
±0.2% of range
1% of unity
±0.5% of range
±0.2% of range
±1%
±0.95% of range
KWh 1% IEC1036
2%
±0.2%
-20 to +60°C, <90% RH
Polycarbonate
5.5"H x 3.72"W x 3.72"D (140 x 95 x 95mm)
5.2"H x 3.74"W x 5.24"D (132 x 95 x 134mm)
4.31"H x 4.31"W x 2.9"D(110 x 110 x 74mm)
4.06" (103mm) diameter, 4 studs
C
D
E
F
Model
1561
single phase 5A CT input, DIN Rail
1562
single phase 3 wire 5A CT input, DIN Rail
1563
3 phase 3 wire 5A CT input, DIN Rail
1564
3 phase 4 wire 5A CT input, DIN Rail
1581
single phase 5A CT input, Base mount
1582
single phase 3 wire 5A CT input, Base mount
1583
3 phase 3 wire 5A CT input, Base mount
1584
3 phase 4 wire 5A CT input, Base mount
Input Volt age
L
57.7 – 139V L-N (1561 & 1581)
114 - 278 V L-L, 57.7 – 139V L-N (1562 & 1582)
100 – 240 V L-L, 57.7 – 139V L-N (1563,4 & 1583,4)
M
140 – 277 V L-N (1561 & 1581)
279 – 480 V L-L, 140 – 240V L-N (1562 & 1582)
241 – 480 V L-L, 140 – 277V L-N (1563,4 & 1583,4)
Input Cur rent
5
5A (CT secondary)
Auxiliar y Suppl y
L
12 – 48V DC
M
100 – 250V AC/DC
Communications Op tions
010
1 Modbus
012
1 Modbus, 2 analog
013
1 Modbus, 3 analog
014
1 Modbus, 4 analog
110
1 pulse/relay, 1 Modbus
112
1 pulse/relay, 1 Modbus, 2 analog
113
1 pulse/relay, 1 Modbus, 3 analog
114
1 pulse/relay, 1 Modbus, 4 analog
210
2 pulse/relay, 1 Modbus
212
2 pulse/relay, 1 Modbus, 2 analog
410
4 pulse/relay, 1 Modbus
412
4 pulse/relay, 1 Modbus, 2 analog
610
6 pulse/relay, 1 Modbus
612
6 pulse/relay, 1 Modbus, 2 analog
Analog Output Range
0
No output
1
0-20 mA, 10V compliance, user configurable as 4-20 mA
(3 channels max)
2
0-1 mA, 10V compliance
3
-1/0/+1 mA, 10V compliance
4
0-5 mA, 10V compliance
6
0-10 mA, 10V compliance
** 360MW max at 120% of relevant input
102
TRANSDUCERS /
SENSORS
Input
Max Continuous:
Max Short Duration:
Burden:
PT Ratio (primary):
CT Primary:
Outputs
RS485:
Baud Rate:
Pulsed:
Pulse Duration:
Auxiliar y Suppl y
AC/DC:
DC:
Supply Burden:
Measur ing Ranges
Voltage:
Current:
Frequency:
Power Factor:
THD:
Energy:
Accur acy
Voltage, Current:
Frequency:
Power:
Power Factor:
Reactive Power (VAr):
Apparent Power (VA):
THD:
Neutral Current:
Energy:
KVArh:
Analog Output:
Operating Temperature:
Enclosure
DIN Transducer:
Base Mount Transducer:
Display:
Panel Cut Out (Display):
– F
Veris Split Core KW Transducers
ORDERING INFORMATION
®
• Meter electronics and current transformers
in a single package
• Split-core system eliminates the need to
remove conductors
• Automatic compensation for CT orientation
• Continuous TRMS Readings
TRANSDUCERS /
SENSORS
SPECIFICATIONS
Input Primary Voltage
Number of Phases Monitored
Internal Isolation
Insulation Class
Temperature Range
Humidity Range
Accuracy
Output
Supply Power (current loop)
CT Opening
208-480VAC rms, 50/60Hz
One or Three
2000VAC rms
600VAC rms
0 to 60°C, 50°C for 2400A
0 to 95% non-condensing
±1%
4-20mA
9-30VDC; 30mA max.
Small 1.5" x 1.25" (38x32mm)
Medium 2.9" x 2.45" (73x62mm)
Large 5.5" x 2.45" (140 x 62mm)
Models with Modbus and Pulse Outputs also available.
Single CT Models for Use w/ Balanced 3Ø Loads or 1Ø 2 Wire Installations
Max.
Model
Voltage
Amps
CT Size
VE/H8041-0100-2
208/240
100
small
VE/H8041-0300-2
208/240
300
small
VE/H8041-0400-3
208/240
400
medium
VE/H8041-0800-3
208/240
800
medium
VE/H8041-0800-4
208/240
800
large
VE/H8041-1600-4
208/240
1600
large
VE/H8041-2400-4
208/240
2400
large
VE/H8042-0100-2
480
100
small
VE/H8042-0300-2
480
300
small
VE/H8042-0400-3
480
400
medium
VE/H8042-0800-3
480
800
medium
VE/H8042-0800-4
480
800
large
VE/H8042-1600-4
480
1600
large
VE/H8042-2400-4
480
2400
large
Three CT Models for Use with Any 3Ø Load or 1Ø 3 Wire Installations
Max.
Model
Voltage
Amps
CT Size
VE/H8043-0100-2
208
100
small
VE/H8043-0300-2
208
300
small
VE/H8043-0400-3
208
400
medium
VE/H8043-0800-3
208
800
medium
VE/H8043-0800-4
208
800
large
VE/H8043-4600-4
208
1600
large
VE/H8043-2400-4
208
2400
large
VE/H8044-0100-2
480
100
small
VE/H8044-0300-2
480
300
small
VE/H8044-0400-3
480
400
medium
VE/H8044-0800-3
480
800
medium
VE/H8044-0800-4
480
800
large
VE/H8044-1600-4
480
1600
large
VE/H8044-2400-4
480
2400
large
Veris Current Switch & Relay
• Independent switch & relay operation
• Command & status in one device
• Adjustable setpoint
• Relay & switch status LEDs simplify setup
®
SPECIFICATIONS
Current Range:
Sensor Power:
Insulation Class:
Frequency Range:
Temperature Range:
Humidity Range:
Setpoint Adjustable:
Hysteresis:
Dimensions:
Sensor Opening:
1-135A
Induced
600VAC rms
50/60Hz.
-15° to 60°C
0-95% non-condensing
1-135A
10% Typical
2.95" x 2.68" x 1.04"
0.75" (19mm) Dia.
ORDERING INFORMATION
H735
L
Model
Relay
Contacts*
VE/H735 Form A (SPST) 5(3)A@250VAC, 30VDC, 1/6HP
VE/H738 Form A (SPST) 10(5)A@250VAC, 30VDC, 1/3HP
VE/H739 Form A (SPST) 10(5)A@250VAC, 30VDC, 1/3HP
VE/H748
Form C (SPDT) 8(3.5)A@250VAC, 30VDC, 1/4HP
VE/H749
Form C (SPDT) 8(3.5)A@250VAC, 30VDC, 1/4HP
VE/H758 Form A (SPST) 10(5)A@250VAC, 30VDC, 1/3HP
VE/H759 Form A (SPST) 10(5)A@250VAC, 30VDC, 1/3HP
* Resistive load (inductive load).
Also available in split core style (H930 series)
103
Coil
24VAC/DC 10mA
24VAC/DC 10mA
24VAC/DC 10mA
24VAC/DC 10mA
24VAC/DC 10mA
9-12VDC 10mA
9-12VDC 10mA
Solid State Output
0.1A@30VAC/DC N.O.
1.0A@30VAC/DC N.O.
0.2A@120VAC/DC N.O.
1.0A@30VAC/DC N.O.
0.2A@120VAC/DC N.O.
1.0A@30VAC/DC N.O.
0.2A@120VAC/DC N.O.
Download PDF