Repair Kit for Dual Check Valve Installation

5
1
6
2
3
4
8
RUBBER DAMPER SHOWN
INSTALLED IN VALVE
ACCESS CAP
7
ITEM
1
2
DESCRIPTION
Small Stem
Large Stem
ITEM
3
4
DESCRIPTION
Small Spring
Large Spring
ITEM
5
6
DESCRIPTION
"O" - Ring
"O" - Ring
ITEM
7
8
DESCRIPTION
"O" - Ring
Rubber Damper
8.
Position springs as shown in drawing. The straight large spring (4) must fit into the spring groove of the large
stem (2). The large spring (4) must also fit squarely against the rubber damper (8) in the access cap. Large
spring coils should not catch on the leading edge of the rubber damper when compressed.
9.
The large end of the small conical spring (3) must fit inside the large stem guides (2), and the small end of the
conical spring fits over the stem of the small check stem (1).
10.
The cross-shaped stem of the small check stem (1) must be aligned with the receiver of the large check stem (2)
when the check stems are installed in the valve body. Rotate the large stem very slightly to insure that the large
check stem's receiver will slide over the small check stem during assembly.
11.
Compress the large spring with the access cap and tighten the cap into the valve body.
12.
Turn on the inlet water supply and insure the access cap is water tight.
#020275
7/98
FORD DUAL CHECK VALVE REPAIR KIT FIELD INSTRUCTIONS
1.
Locate the stamped model number on the valve body to be sure that you have the correct repair kit.
Models HHA - 3/4, HHS - 3/4 and HHS - 5/8 x 3/4 require kit number HHRK - 3.
Model HHA - 5/8 x 3/4 requires kit number HHRK - 2.
2.
Shut off the inlet water supply going to the Dual Check Valve and shut off or drain the house side water supply.
3.
Carefully remove the access cap as the internal parts are spring loaded.
4.
Inspect the check valve brass seats in the valve body for signs of wear or corrosion.
If the seats are worn and provide a rough sealing surface, replace the entire valve.
5.
Reassemble the Dual Check Valve by following the assembly instructions #6 through #12.
(Refer to diagram on reverse side of card)
6.
Remove O-ring from access cap and replace with the new O-ring (7).
If valve has flat rubber washer in the access cap, remove and discard.
7.
Install Rubber Damper (8) over the access cap stem housing and make sure that it fits squarely against the base
of the access cap.