Installation Guide
Models: H65-EC
Covered by the following United States and International Patents:
D631148S, 138172, 001790452-001, 338608 and other patents pending
©2017 ZOO FANS INC. ALL RIGHTS RESERVED
1650 38th St, Suite 201W
Boulder, CO 80301
(303) 557-1852
zoofans.com
REV 10042017
IMPORTANT SAFETY INFORMATION
READ AND SAVE THESE INSTRUCTIONS
WARNING – TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS: Installation work and electrical wiring must
be done by qualified person(s) in accordance with all applicable codes and standards.
CAUTION: The installation of a ZOO Fan must be in accordance with the requirements specified in this installation manual and with
any additional requirements set forth by the national electric code (NEC), ANSI/NFPA 70-1999, and all local codes. If you are
unfamiliar with wiring, use a qualified electrician.
WARNING: To reduce the risk of fire, electric shock, or personal injury, mount directly to a structural framing member.
WARNING: To prevent electrical shock and/or injury disconnect fan from power source before you move or service the fan.
Not Suitable for use with solid-state speed controls.
WARNING: To reduce the risk of fire, electric shock, and injury to persons, ZOO Fans must be installed only with controllers
supplied by ZOO Fans. Other parts cannot be substituted.
CAUTION: When service or replacement of a component in the fan requires the removal or disconnection of a safety device, the
safety device is to be reinstalled or remounted as previously installed.
WARNING: Risk of fire, electric shock, or injury to persons during cleaning and user maintenance. Disconnect the fan from the
power supply before servicing.
WARNING – TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:
a) Use this unit only in the manner intended by the manufacturer. If you have questions, contact the manufacturer.
b) Before servicing or cleaning unit, switch power off at service panel and lock the service disconnecting means to prevent power
from being switched on accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent
warning device, such as a tag, to the service panel.
WARNING: Do not install in a cooking area.
WARNING: Fatal electric shock from metal cable glands in the plastic terminal box is possible if incorrectly connected – do not use
metal cable glands in plastic terminal boxes.
WARNING: Do not operate the fan in spaces with hazardous or Explosive Material and Vapors.
DANGER: Rotating equipment. Death, severe injury and property damage may result. ZOO Fans are intended to be hung outof-reach of people. The bottom of the fan must be no less than 3.05m (10’) from any area capable of receiving pedestrian
traffic.
WARNING: Stay alert and use common sense when installing fans. Do not install fans if tired or under the influence of drugs,
alcohol, or medication.
CAUTION: Only operate the fan within the ranges specified on the motor’s type plate.
WARNING: Do not bend the blade brackets when installing, adjusting, or cleaning the fan. Do not insert foreign objects in
between rotating fan blades.
CAUTION: The ZOO Fans product warranty will not cover equipment damage or failure that is caused by improper installation.
©2017 ZOO FANS INC. ALL RIGHTS RESERVED
1650 38th St, Suite 201W
Boulder, CO 80301
(303) 557-1852
zoofans.com
REV 10042017
INFORMATIONS DE SÉCURITÉ IMPORTANTES
LISEZ ET SAUVEGARDEZ CES INSTRUCTIONS
AVERTISSEMENT – POUR RÉDUIRE LE RISQUE DE DÉPART D’INCENDIE, DE COMMOTION ÉLECTRIQUE OU DE BLESSURE POUR LES
PERSONNES : Le travail d’installation et le câblage électrique doivent être réalisés par du personnel qualifié, en conformité avec la
norme électrique américaine, ANSI/NFPA 70-1999, et toutes les normes locales.
AVERTISSEMENT: Risque de départ d’incendie, de commotion électrique ou de blessure pour les personnes durant le nettoyage
ou la maintenance par l’usager! Débranchez l’appareil de la source d’alimentation avant toute intervention.
QUI NE POUVANT être utilisé avec des contrôles de vitesse à semi-conducteurs.
AVERTISSEMENT: Pour réduire le risque de départ d’incendie, de commotion électrique et de blessure aux personnes, les
ventilateurs ZOO Fans doivent être installés avec des commandes de ventilateur fournis par ZOO Fans. D’autres pièces ne
peuvent pas être substituées.
AVERTISSEMENT: Ne pas installer pres d »un appareil de cuisson.
ATTENTION : Quand le service ou le remplacement d'un composant dans le ventilateur exige le déplacement ou le débranchage
d'un dispositif de sécurité, le dispositif de sécurité doit être réinstallée ou remounted comme précédemment installé.
AVERTISSEMENT: Risque de départ d’incendie, de commotion électrique ou de blessure pour les personnes durant le nettoyage
ou la maintenance par l’usager! Débranchez l’appareil de la source d’alimentation avant toute intervention.
AVERTISSEMENT – POUR RÉDUIRE LE RISQUE DE DÉPART D’INCENDIE, DE COMMOTION ÉLECTRIQUE OU DE BLESSURE POUR
LES PERSONNES, APPLIQUEZ CECI:
a. N’utilisez cette unité que de la manière voulue par le constructeur. Si vous avez des questions, contactez le constructeur.
b. Avant d’installer, de réparer ou de nettoyer l’unité, arrêtez son alimentation au panneau de distribution électrique et
verrouillez le dispositif de coupure pour éviter une remise sous tension accidentelle. Si ce dispositif de coupure ne peut pas
se verrouiller, fixez bien une signalisation très visibles, comme un étiquetage, au niveau du panneau de distribution.
AVERTISSEMENT : Une commotion électrique fatale à partir de raccords de câbles métalliques dans le boîtier de raccordement
en plastique est possible en cas de connexion incorrecte – n’utilisez pas de raccords de câbles métalliques dans des boîtiers de
raccordement en plastique.
ATTENTION : À ne pas utiliser dans des espaces avec des matières ou vapeurs dangereuses ou explosives.
DANGER : Équipement rotatif. La mort, une blessure grave ou des dégâts matériels peuvent en résulter. Les ventilateurs ZOO
Fans sont conçus pour être suspendus hors de portée des gens. Le bas du ventilateur ne doit pas être à moins de 3,05 m (10
pieds) par rapport à toute zone pouvant recevoir du trafic piétonnier.
AVERTISSEMENT : Restez vigilent, faites attention à ce que vous faites, et faites preuve de bon sens lors de l’installation de
ventilateurs ZOO Fans. N’installez pas de ventilateurs si vous êtes fatigué ou sous l’influence de drogues, d’alcool ou de
médicaments.
ATTENTION : Ne faites fonctionner le ventilateur que dans les plages spécifiées sur la plaque signalétique du moteur.
AVERTISSEMENT : Pour réduire le risque de blessure personnelle, ne pas tordre les supports de pales lors de leur installation, ou
à l’équilibrage des pales, ou au nettoyage du ventilateur. N’insérez pas d’objets étrangers entre les pales de ventilateur en
rotation.
©2017 ZOO FANS INC. ALL RIGHTS RESERVED
1650 38th St, Suite 201W
Boulder, CO 80301
(303) 557-1852
zoofans.com
REV 10042017
Contents
PRE-INSTALLATION ...................................................................................................................................................................... 1
PARTS ENCLOSED ......................................................................................................................................................................... 1
ZOO FANS SPECIFICATIONS .......................................................................................................................................................... 2
LAYOUT ........................................................................................................................................................................................ 2
INSTALLATION .............................................................................................................................................................................. 3
HANGING THE FAN .................................................................................................................................................................. 3
STEP 1: Fasten Main Hanging Cable ..................................................................................................................................... 3
STEP 2: Fasten Stabilization Tether ...................................................................................................................................... 4
STEP 3: Secure the Gripples ................................................................................................................................................. 5
WIRING THE FAN ..................................................................................................................................................................... 7
STEP 3: WIRING THE CONTROL SIGNAL ................................................................................................................................... 8
OPTION 1 - Wiring 10k Ohm Potentiometer ........................................................................................................................ 8
OPTION 2 - Wiring 0 – 10VDC Analog Signal ........................................................................................................................ 9
OPTION 3 - Wiring MODBUS Control Signal......................................................................................................................... 9
STEP 4: START-UP AND COMMISSIONING ............................................................................................................................. 10
©2017 ZOO FANS INC. ALL RIGHTS RESERVED
1650 38th St, Suite 201W
Boulder, CO 80301
(303) 557-1852
zoofans.com
REV 10042017
PRE-INSTALLATION
The safe installation and operation of equipment supplied by ZOO Fans is the responsibility of the system designer, installer,
maintainer, and operator (collectively, the “User”). The need for protective safety accessories to meet company standards,
applicable codes, and the requirements of the Occupational Safety and Health Act (“OSHA”) must be determined by the
User since safety requirements may vary depending on the location and application of the equipment.
The elements of a successful installation consist of:
1.
2.
3.
4.
5.
Good layout of fans, wiring, and controls
Hanging the fans where they’ll be most effective and convenient to control
Completing the electrical hook-up
Start-up and commissioning
Conducting all work in a safe manner consistent with all relevant codes and regulations
PARTS ENCLOSED
If you ordered multiple fans, be sure to keep the components of each fan together.
•
•
H65-EC ZOO Fan
“Bag 1 of 2” Main Hanging Gripple®
o (2) 3/8” Flat Washers
o (1) 3/8” Lock Washer
o (1) 3/8” Nut
o (1) 3/8” Nylock Nut
o 8’ Cable with 3/8” Stud End Fixing (200 lb Safe Working Load)
o Gripple No. 3 Fastener
o Release/Setting Key
•
“Bag 2 of 2” Stabilization Tether
o 12’ Cable with 1/4” Eyelet End Fixing (100 lb Safe Working Load)
o Gripple No. 2 Fastener
o (1) 1/4” x 2 1/4” Hex Head Bolt
o (1) 1/4” Nylock Nut
•
•
•
Installation Guide (this manual)
Operating Manual
Variable speed controller (optional, as ordered)
©2017 ZOO FANS INC. ALL RIGHTS RESERVED
1650 38th St, Suite 201W
Boulder, CO 80301
PHONE: 303-557-1852
zoofans.com
REV 05182017
ZOO FANS SPECIFICATIONS
Model
Width
Weight
Full Load Current
Max RPM
Max CFM
H65-EC
1.75 ft (0.53 m)
25 lbs. (11.3 kg)
1.55 A @ 230V
1360
1825
LAYOUT
This phase should have been completed prior to placing your order. If you don’t have a plan or would like to consider
modifications, please consult with your professional engineer, designer and/or installer. You may also contact your ZOO
Fans’ representative or ZOO Fans directly if you require assistance.
Remember, the number of ZOO Fans required for the job, as well as where they are hung, will depend on a number of
variables, some of which are:
•
•
•
•
•
Ceiling height, as well as the overall volume of air the fans need to
move in order to achieve the targeted level for turnover of air in the
facility every hour (a good design target for destratification is 100%
turnover every hour)
The availability of a sturdy and secure anchor point for attaching the fan
Obstructions, such as merchandise/inventory racks, lighting, overhead
equipment, and other mechanical systems
The location of existing HVAC diffusers and returns
A desire to create air movement at a specific work station, machine or
other locale to dissipate heat, provide spot cooling, dry floors, or
reduce/eliminate condensation
Ask the electrician who will do the wiring for the fan(s) to review the following section to be sure your layout is a good one
for your objectives and that it is sensible given electrical requirements and any existing wiring. Ask the contractor who will
be hanging your fans to review your layout for ease and safety of installation, as well as compatibility with existing
mechanical systems and all applicable codes. If the installer(s) have any questions about where to locate your fan(s) or how
to install them, please contact either your ZOO Fans’ representative or ZOO Fans. A copy of this installation guide can also
be found at www.zoofans.com.
©2017 ZOO FANS INC. ALL RIGHTS RESERVED
1650 38th St, Suite 201W
Boulder, CO 80301
PHONE: 303-557-1852
zoofans.com
REV 05182017
INSTALLATION
HANGING THE FAN
The fan intake must be 12” from any obstruction.
ZOO Fans are designed to be hung vertically or at an angle. For vertical installations, proceed to STEP 1 below.
To install the ZOO Fan at an angle, additional hardware is required. Please contact ZOO Fans or your ZOO Fans’
representative.
STEP 1: Fasten Main Hanging Cable
Use the hardware from the white bag labeled “Bag 1 of 2” containing the 8’ Cable with 3/8” Stud End Fixing, and
attach that cable to the hole at the top of the fan’s handle as shown in Illustration 1, below.
NOTE: Gripple Installation Guidelines are included with your Gripple hardware and should be consulted for
information about installing, adjusting and caring for your Gripple attachment hardware.
TIP: When attaching these cables, leave the cables wound, as shipped, until you are ready to hang the fan.
1.
2.
3.
4.
5.
Place 3/8” Nut on Stud Fixing
Place 3/8” Flat Washer on Stud Fixing
Insert 3/8” Stud Fixing through the center hole in the handle
Place 3/8” Flat Washer, 3/8” Lock Washer, and 3/8” Nylock Nut on thread sticking through the handle
Securely tighten 3/8” Nylock Nut
Illustration 1
©2017 ZOO FANS INC. ALL RIGHTS RESERVED
1650 38th St, Suite 201W
Boulder, CO 80301
PHONE: 303-557-1852
zoofans.com
REV 05182017
STEP 2: Fasten Stabilization Tether
Use the hardware from the white bag labeled “Bag 2 of 2” containing the 12’ cable with eyelet, and attach the
stabilization tether to either attachment point located at 45° on each side of the fan’s handle as shown in
Illustration 2, below.
TIP: When attaching these cables, leave the cables wound, as shipped, until you are ready to hang the fan.
1. Insert 1/4” Hex Head bolt through the Eyelet of Gripple
2. Insert 1/4” Hex Head bolt through the hole located at 45° on either side of the handle
3. Securely tighten 1/4” Nylock Nut
Illustration 2
©2017 ZOO FANS INC. ALL RIGHTS RESERVED
1650 38th St, Suite 201W
Boulder, CO 80301
PHONE: 303-557-1852
zoofans.com
REV 05182017
STEP 3: Secure the Gripples
Illustration 3 shows how to secure the Main Hanging Cable to the Truss, I-Beam, unistrut or other appropriate
attachment point that can easily support the load of the fan.
1.
2.
3.
4.
Insert cable through Gripple
Loop cable over Truss, I-Beam, or support beam
Insert end of cable into Gripple
Adjust to desired height
Illustration 3
©2017 ZOO FANS INC. ALL RIGHTS RESERVED
1650 38th St, Suite 201W
Boulder, CO 80301
PHONE: 303-557-1852
zoofans.com
REV 05182017
Illustration 4 shows how to secure the Stabilization Tether to the Truss, I-Beam, or support beam.
WARNING: The Stabilization Tether MUST be installed properly to ensure safe operation of your ZOO Fan.
1.
2.
3.
4.
5.
Insert cable through Gripple
At a 45 ° angle, loop cable over Truss, I-beam, or support beam
Push end of cable into Gripple
Adjust cable so there is no slack
Excess cable should be neatly rolled up and taped or cut for a clean installation
Illustration 4
©2017 ZOO FANS INC. ALL RIGHTS RESERVED
1650 38th St, Suite 201W
Boulder, CO 80301
PHONE: 303-557-1852
zoofans.com
REV 05182017
WIRING THE FAN
The H120 and H140 are equipped with EC motors that will accept a range of voltages. See below.
Single Phase installation ONLY
208V – 277V
50Hz or 60Hz
Alternatively, these motors will accept DC voltage. Please contact Zoo Fans for details.
•
Electrical connection should be made according to Illustration 8, the wiring diagram below:
Illustration 8, Wiring Diagram
Line
Neutral (277V)
Line 2 (208-230V)
Ground
©2017 ZOO FANS INC. ALL RIGHTS RESERVED
1650 38th St, Suite 201W
Boulder, CO 80301
PHONE: 303-557-1852
zoofans.com
REV 05182017
STEP 3: WIRING THE CONTROL SIGNAL
The H65-EC has multiple control options available including:
-
10k Ohm Potentiometer
0 – 10 Volt DC analog signal
PWM signal (contact Zoo Fans for wiring instructions)
MODBUS RS-485 (must be preconfigured at factory)
WARNING: Never apply line voltage to the digital input
Contact Zoo Fans for other control options.
OPTION 1 - Wiring 10k Ohm Potentiometer
Illustration 9
+10VDC
GND
OUTPUT
(0-10VDC)
©2017 ZOO FANS INC. ALL RIGHTS RESERVED
1650 38th St, Suite 201W
Boulder, CO 80301
PHONE: 303-557-1852
zoofans.com
REV 05182017
OPTION 2 - Wiring 0 – 10VDC Analog Signal
Illustration 10
GND
(-)
OUTPUT
(0-10VDC)
(+)
OPTION 3 - Wiring MODBUS Control Signal
Illustration 11
(+)
(-)
©2017 ZOO FANS INC. ALL RIGHTS RESERVED
1650 38th St, Suite 201W
Boulder, CO 80301
PHONE: 303-557-1852
zoofans.com
REV 05182017
STEP 4: START-UP AND COMMISSIONING
IMPORTANT: To enable the fan for electronic operation, a jumper wire MUST be installed, as shown below:
Illustration 12
Place a jumper wire here.
WARNING: Never apply line voltage to the digital input
ZOO Fans
1650 38th St. Suite 201W
Boulder, CO 80301
Phone: 303.557.1852
Fax: 859.765.0027
customerservice@zoofans.com
zoofans.com
©2017 ZOO FANS INC. ALL RIGHTS RESERVED
1650 38th St, Suite 201W
Boulder, CO 80301
PHONE: 303-557-1852
zoofans.com
REV 05182017