SOYAL
®
AR-725 (E-V2)
V130116
ACCESS CONTROL SYSTEM
Contents
AR-725 (E-V2-M)
2 User Guide
1 Products
3 Terminal Cables
4 Tools
P1
P2
c x2
P3
d x1
A.
B.
C.
P4
D.
P5
P6
※ P7
AR-725 (E-V2)
1 Products
2 User Guide
3 Terminal Cables
4 Tools
P1
P2
P3
e x2
A1.
E.
P4
F.
AR-725 (X)
1 Products
P5
P6
※ P7
2 Tools
a x2
d x1
b x2
c x2
A2.
A3.
B.
C.
G.
H.
D.
Parts Description
a.
Button Head Pozidriv
Tapping Screw: M3x10
d.
Security Torx Screw:
M3.5x15
b.
Button Head Pozidriv
Slotting Screw: 2.5x10
e.
Flat Head Hex Socket
Screw: M3x8
c.
Flat Head Cap Philips
Tapping Screw: 4x19.1
Installation
AR-725 (E-V2-M)
Pull the cables from the square access hole of the mounting plate C.
2
C.
A.
3
B.
1
B.
A.
4
C.
A.
A.
B.
C.
6
5
c.
Use a screwdriver to screw the metal plate C to the wall.
7
Assemble plate B with the body A, and embed the water proof strip D
onto the plastic side frame.
d.
8
D.
Take off the plastic mounting plate B from the body A, and pull the cables
through the access hole of C and B, then connect to the body A.
Assemble the body A onto the mounting plate C with the Allen key and
screws (accessories supplied).
g.
Turn on the power and LED will light and beep will sound.
AR-725 (E-V2)
A1.
F.
1
F.
E.
Use a screwdriver to screw the base F onto the wall.
Attach the water proof gasket to the body A1, and pull the cables
from the square hole of the base F, and connect to the body A1.
2
3
Assemble the body A1 with the base F.
Screw A1 and F tight with the Allen key and screws (accessories
supplied).
4
e.
f.
Turn on the power and LED will light and beep will sound.
5
AR-725 (X)
A1.
A3.
1
2
H.
A1.+A3.
Put on G, and attach A1 onto the plastic plate A3, and screw it with
the Allen key and screws (accessories supplied).
D.
Put the ring O on the metal frame, and put them together onto the
reader A1+A3, and screw them and buckle up the 4 buckles on the
back.
A2.
b.
4
G.
a.
e.
f.
3
5
Embed the water proof strip D onto the frame side of the base.
Following by the install process of AR-725 (E-V2-M).
Access controller
Illuminated Touch-panel
V130116
Notice
1. Tubing: The communication wires and power line should NOT be bound in the same conduit or tubing.
2. Cable selection: Use AWG 22-24 Shielded Twist Pair to avoid star wiring. Use CAT5 for TCP/IP connection.
3. Power supply: Don’t equip reader and lock with the same power supply. The power for reader may be unstable when the lock is activating, that may make the
reader malfunction. The standard installation: Door relay and lock use the same power supply, and reader use independent power supply.
Connector Table
Cable: P3
P3
P2
Wire Application Wire
Color
1
--2
--3 Orange White
4
Orange
TCP/IP Output
5 Green White
6
Green
7
---
P4
P7
P5
P6
P1
Cable: P4
Cable: P1
Wire Application Wire
Color
Description
1 Blue White (N.O.)DC24V1Amp
Lock Relay
2 Purple White (N.C.)DC24V1Amp
Common-COM-Point 3
White
(COM)DC24V1Amp
Door Contact
4
Orange Negative Trigger Input
Exit Switch
5
Purple
Negative Trigger Input
Transistor Output Max. 12V/100mA
Alarm Relay
6
Gray
(Open Collector Active Low)
7
Thick Red DC 12V
Power
8 Thick Black DC 0V
Cable: P2
Wire Application Wire
Beeper
1
2
LED
3
Door Output
4
Wiegand
WG Door Contact
WG Exit Switch
5
6
7
8
Color
Pink
Yellow
Brown
Description
Beeper Output 5V/100mA, Low
Red LED Output 5V/20mA, Max
Green LED Output 5V/20mA, Max
Transistor Output Max. 12V/100mA
Blue White
(Open Collector Active Low)
Thin Green Wiegand DAT: 0 Input
Thin Blue Wiegand DAT: 1 Input
Orange Negative Trigger Input
Purple
Negative Trigger Input
Wiring Diagram
AR-321H to Electric Bolt
Connect
Electric Bolt
E
Wire Application Wire
Color
Description
1 Thick Green RS-485(B-)
RS-485 for Lift
Controller
2
Thick Blue RS-485(A+)
Cable: P5
Wire Application Wire
1
Anti-Tamper
2
Switch
3
Description
N.C.
COM
N.O.
Wire Application Wire
Color
Power
1
Red
Security trigger signal 2
Purple
Arming
3
Red White
Duress
4 Yellow White
Description
DC 12V Output
Security trigger signal Output
Arming Output
Duress Output
Cable: P7 Optional:(Request to purchase AR-725L485 additionally)
Wire Application Wire
TTL Port
1
2
3
4
5
6
Color
Black
Yellow
White
Orange
Red
---
Description
DC 0V
TX
TE
RX
DC 5V
---
Connect to Magnet Lock
12V
GND
Exit Switch
12V
GND
POWER
12VDC
12V
GND
12V
GND
Magnet Lock
POWER
12VDC
P1
N.O. 1
2
COM 3
4
PB 5
6
12V 7
GND 8
POWER
12VDC
Color
Red
Orange
Yellow
Cable: P6
P1
Controller
Description
----Net - TX+
Net - TXNet - RX+
Net - RX---
N.O.
GND
EXIT
12V
GND
RTE
Controller
1
N.C. 2
COM 3
4
PB 5
6
12V 7
GND 8
POWER
12VDC
N.O.
GND
EXIT
12V
GND
RTE
SOYAL
®
AR-725 (E-V2)
V130116
ACCESS CONTROL SYSTEM
Connect to Electric Strike
Connect to Door Contact
12V
GND
12V
GND
POWER
12VDC
Electric Strike
P1
Door Contact
N.O.
GND
Controller
Alarm
12V
GND
12V
GND
Electric Bolt
N.C.
N.O.
COM
CTL
12V
Relay Outpot Module
N.C.
12V
GND
Door Contact
Connect to Reader
POWER
12VDC
N.C.
N.O.
COM
CTL
12V
GND
PB
1
2
3
4
5
6
7
8
POWER
12VDC
RTE
Strengthen security with AR-721RB
Electric Bolt
E
12V
GND
Exit Switch
POWER
12VDC
AR-721RB
Reader
12V
GND
RTE
BZ
RLED
GLED
Door Output
WG 0
WG 1
1
2
3
4
5
6
7
8
N.O.
EXIT
12V
GND
Magnet Lock
POWER
12VDC
P1
N.O. 1
2
COM 3
4
PB 5
6
12V 7
GND 8
12V
GND
BZ
RLED
GLED
WG 0
WG 1
12V
GND
N.C.
COM
PB
12V
GND
EXIT
Transistor
IN4007
EXIT
Controller
RTE
POWER
12VDC
POWER
12VDC
Electric Bolt
12V
GND
POWER
12VDC
E
P1
P1
RTE
N.C.
P1
1
2
3
4
5
WG-DS
6
WG-PB
12V 7
GND 8
If any fire emergency, the people can escape by press a switch to open all doors
Electric Strike
Door Contact
P2
N.C.
N.O.
COM
CTL
12V
P1
Controller
POWER
12VDC
ALM
12V
GND
EXIT
12V
GND
POWER
12VDC
1
2
P6 1 2 3 4
3
12V DDR
4
5
6
12V 7
GND 8
12V
GND
P1
N.O. 1
2
COM 3
4
PB 5
6
12V 7
GND 8
Controller
12V
GND
POWER
12VDC
RTE
1
2
3
4
5
6
7
8
RTE
N.O. 1
2
COM 3
4
PB 5
6
12V 7
GND 8
EXIT
EXIT
Transistor
IN4007
Fire Emergency
Adding and Deleting Tag
Add Single Tag or Random tags
Input
123456
(or Master Code) → 19 UUUUU 00001
[e.g.] 2 readom cards with user addresses No. 100 and No. 101:
Access programming mode → 19
00100
00001
→ Present the tag(s) with Controller (single tag or random numbered cards one by one) → Done
→ Present the tags one by one → Done
Add the Sequential tags
Input
123456
(or Master Code) → 19
UUUUU
QQQQQ
→ Present the tags (Present the tag with the lowest number first.) → OK
[e.g.] User Address NO.101 to NO.120 have 20 pcs of sequential tags:(62312~62332):
Access programming mode → 19
00101
00120
→ Close Tag into RF Area(only use the tag NO.62312) → OK
Tag Information
Delete a Single Tag
Input
123456
(or Master Code) → 10
[e.g.] Delete User Address: 00058
Access programming mode → 10
SSSSS 9 EEEEE
00058 9 00058
CARD CODE
SITE CODE
CARD CODE
SITE CODE
Access controller
Illuminated Touch-panel
V130116
Delete a batch of Tags
SSSSS 9 EEEEE
Input
123456
(or Master Code) → 10
[e.g.] Delete User Address: 00101~00245
00101 9 00245
Access programming mode → 10
Delete All Tags
Input
123456
(or Master Code) → 29
29
Programming
A. Entering and Exiting Programming Mode
Entering
Input
123456
or
PPPPPP
[e.g.] The Default Value= 123456, if already changed the Master Code= 876112, input
876112
→ Access programming mode
Exiting
Input
Changing the Master Code
Access programming mode → 09 PPPPPPRRRRRR
[e.g.] If want to changing the Master Code= 876112, input
[Input the 6-digit new master code twice.]
123456
→ 09 876112876112
B. Changing the Node ID of Reader
Access programming mode → 00
NNN
MMM
AAA
[NNN= Node ID: 000~254; MMM=AR-725 (E-V2) Door NO.:1~255; AAA=WG Reader Door NO.:1~255
C.Setting up the control mode (M4/M8)
Access programming mode → 04
Mode Support
M4
Networking/
[N=4/8]
120
Event
Duress
Capacity Holidays
User
Capacity
Access Mode
16,000
1.Card only
2.Card and PIN (4-digit PIN)
3.Card or User address (5-digit) + Individual PIN
Stand-Alone (0~15,999)
M8
N
Lift
Anti-passControl
back
32,000
V
V
unlimited
64
V
32,000
V
V
unlimited
64
V
(4-digit individual PIN)
1.Card only
2.Card and PIN (4-digit individual PIN)
Stand-Alone (0~15,999) 3.Card or PIN (4-digit individual PIN)
Networking/
Time
Zone
16,000
D. Setting up the password
Individual PWD (M4/M8)
Card or PIN: Access programming mode → 12
Card and PIN: Access programming mode → 13
UUUUU
PPPP
UUUUU
[e.g. User address: 00001 and PWD: 1234. Input 12
PPPP
[e.g. User address: 00001 and PWD: 1234. Input 13
00001
00001
1234
]
1234
]
E. Anti-pass-back
Usually, anti-pass-back is commonly applied to parking areas in order to prevent from multi-entry with one card at a time, or somewhere wants to
monitor not only the access but also exit condition.
Enable device
Access programming mode → 20 U DDD
U= Enable target unit(0=AR-881EF/EV,1=Reader) [Please refer to function default value for details.]
[e.g.] If the AR-881EF/EV set to exit reader, WG Reader set to access reader.
Access programming mode → 20
0
128
→ 20
1
192
[Please refer to function default value for details.]
Enable card user
SSSSS= starting user address; EEEEE= ending user address [P=0 Enable/ P=1 Disable/ P=2 Reset]
Access programming mode → 26 SSSSS EEEEE P
[e.g.] User address from 00152 to 00684 enable the anti-pass-back function: 26 00152 00684 0
F. Auto Open Zone
Door will keep opening after first man flashing card. When the reader is stand-alone, supporting only 16 sets of auto-open zone by device setting.
Auto-open zone can extend up to unlimited sets by Networking.
Enable/Disable auto open zone
Access programming mode → 20
U
DDD
U= Enable target unit(0=AR-725(E-V2),1=Reader) [Please refer to function default value for details.]
[e.g.] If the AR-725 (E-V2) set to Enable aut open zone.
Access programming mode → 20
0
004
[Please refer to function default value for details.]
Enable/Disable auto open door without presenting card
Access programming mode → 24
U
DDD
U= Enable target unit(0=AR-725(E-V2),1=Reader) [Please refer to function default value for details.]
[e.g.] If the WG Reader set to Enable aut open door without presenting card.
Access programming mode → 24
1
128
[Please refer to function default value for details.]
Setting up access time
Access programming mode → 08
MW
NN
HHMMhhmm
7123456H
[M=AR-725 (E-V2); W=Reader(0=disable,1=enable); NN: 16 sets of
auto-open zone (NN=00~15); HHMMhhmm=Starting time to ending time; 7123456H= 7 days of week + Holiday (F= 0: disable; 1: enable)]
[e.g.]AR-725 (E-V2) (without WG reader), to set second time zone which could be passed only at 9:30am to 4:20pm on Mon, Wed and Fri.
Access programming mode → 08
10
01
09301620
01010100
→ setting is completed
SOYAL
®
AR-725 (E-V2)
V130116
ACCESS CONTROL SYSTEM
G. Lift control
Connect with AR-401RO16B to control floors which the user will be able to access. [BAUD9600]
Single floor
Access programming mode → 27
UUUUU
UUUUU
G
00045
0
1
2
3
4
5
6
7
24
LLLLLLLL
[UUUUU=User address G: 8 sets of lift control (Input: 0~7) LLLLLLLL:
8 floors setting (L=0=Disable, L=1=Enable)
[e.g.] User address NO. 168 can reach only the 6th and 20th floor:
Access programming mode → 21
H. Setting Up the Arming
00168
0
L
8
16
24
32
40
48
56
64
(G)
LL
UUUU=User Address LL=Floor number (01~64 floor)
[e.g.] User address NO. 45 only can reach the elevator to the 24th floor: 27
Multi floors
Access programming mode → 21
Set Floor
00100000
L
7
15
23
31
39
47
55
63
L
6
14
22
30
38
46
54
62
L
5
13
21
29
37
45
53
61
L
4
12
20
28
36
44
52
60
L
3
11
19
27
35
43
51
59
L
2
10
18
26
34
42
50
58
Conditions:
Application:
1. Arming is enabled
1. Door open too long: Door is open longer than door relay time plus door close time.
2.Alarm system connected
2. Force open (Opened without a valid user card): Access by force or illegal procedure.
L
1
9
17
25
33
41
49
57
3. Door position abnormal: Arming is enabled and the power is suddenly off then on.
Enable Arming status:
Standby Mode
Card only
Enable all devices
Enable particular device
Input 5 digit user address → Input 4
Induct valid card → Input 4 digit
Induct valid card → Input 4 digit
digit pass code →
arming code →
arming code →
arming code →
Card or Passcode
U
or
Enter Program Mode
Enable all devices: Access programming mode →
Card and Passcode
Induct valid card → Input 4 digit pass
→ Input 4 digits code →
code →
or U
→ Input 4 digits arming
or
U
Enable particular device: Access programming mode →
U
Disable Arming status:
Standby Mode
Card only
Disable all devices
Induct valid card → Input 4 digit
9
arming code →
Card or Passcode
Disable particular device
Input 5 digit user address → Input 4
Induct valid card → Input 4 digit
digit pass code →
arming code →
arming code →
U
or
9
Card and Passcode
Induct valid card → Input 4 digit pass
→ Input 4 digits code →
code →
or
U
→ Input 4 digits arming
9
or
※ Factory default armingcode is: 1234. U=Reader unit (0=AR-725 (E-V2), 1=WG Reader).
Restoring Factory Settings
Reset all device parameters and user card data
Reset all device parameters and user card data:
Access programming mode → 29
29 9
Reset all user card data:
Access programming mode → 29
29
Reset IP Setting:
Press “IP Resent Button” of main board for few seconds. (Reference to picture)
※ After operation as above, you will hear the long reminder sound,and wait until the
sound disappear then reset the power of the controller,the device will restore factory setting.
Firmware Upgrade
Get the upgrade software from SOYAL or our distributor and run “UdpUpdater” software
2
Execute the software
The software is within SOYAL CD or Login the
4
1
SOYAL web to downloads
Update the firmware
[Please login the SOYAL web to download the new ISP Firmware.]
3
1. Input the Target Address and Port
2. [Load F/W] open the documents that have the new ISP Firmware
3. Click the new ISP Firmware and [Open] it
4. Click [Update Device] to start the firmware update
5. Till the screen shown [Firmware Update is Complete]
5
U
Access controller
Illuminated Touch-panel
IP Setting
Open your Web Browser and input factory default IP
address: http://192.168.1.127
If the IP address of AR-725 (E-V2)
has changed We must enter the
new IP address.
Page menu
Monitor the on-line computer
IP Setting
Change the Log-in information
Current State
Online Status is able to monitor and show which computer is linking on
Ethernet Module
Show which computer is linking
on Ethernet Module.
Current IP address of the AR-725 (E-V2)
Log-in User Password
When you choose the "Networking Setting" or "User Password" at first.
Log-in window will pop out and please input
※ At the Factory Default
User name: admin
Password: No as default value,so please just press “OK” to log-in
Networking Setting
You will find initial IP Address 192.168.1.127 and check
MAC Address is the same as sticker on Ethernet Module
device. Please revise IP address you want, and then click
“Update” button. After updating the IP, please re-connect
the Web Browser by new IP address.
User Password
Change the log-in password to lock the IP setting of
Ethernet Module.
The password composes of 10 characters at most, it can be
either A~Z or 0~9.
admin
V130116
SOYAL
®
AR-725 (E-V2)
V130116
ACCESS CONTROL SYSTEM
Command List
Function
Node ID setting
Command
PPPPPP
Entering programming mode
Exiting programming mode
Exiting programming mode and enabling all device
into arming status.
Enabling each device into arming status.
Exposition
PPPPPP: Master Code, (Default value: 123456)
Including AR-725 (E-V2), WG Reader
U=Enable target unit (0=AR-725 (E-V2) , 1=WG Reader)
NNN=Node ID,(001~254)
U
00
NNN
MMM
AAA
MMM=AR-725 (E-V2) Door Number,(001~255)
AAA=WG Reader Door Number,(001~255)
default value = 192.168.1.127
01
0
CCCCCCCCCCCC
01
01
1
2
255255255000
192168001254
02
U
IP Address assign (Must power reset)
CCCCCCCCCCCC = 192168001127
If set to 000.000.000.000 will enable DHCP otherwise
will disable DHCP
Netmask
Gateway assign
U=Enable target unit (0=AR-725(E-V2) , 1=WG Reader)
Door relay time setting
TTT
TTT=Door relay time;000 (Output constantly)
001~600=1-600 Sec.;601~609=0.1~0.9Sec.
TTT=Alarm relay time;000 (Output constantly)
Alarm relay time setting
03
TTT
Mode setting
04
M
M=4 (Mode 4);M=8 (Mode 8)
Arming delay time setting
05
TTT
Base on second, range: 001~255
Alarm delay time setting
06
TTT
Base on second, range: 001~255
Master card setting
07
SSSSS
001~600=1~600 Sec.
SSSSS-EEEEE=00000~15999
EEEEE
SSSSS= starting user address; EEEEE= ending user address
M=AR-725(E-V2); W=WG Reader (0=disable; 1=enable)
NN=16 sets of auto-open zone (Range: 00~15)
Auto-open zone setting
08
MW
NN
HHMMhhmm
7123456H
HHMMhhmm=staring time to ending time
(e.g.: 08301200=08:30 to 12:00)
7123456: 7 days of week -Sun/Mon/Tue/Wed/Thu/Fri/Sat
(Input value: 0=disable; 1=enable)
Master code settings
Suspend or delete tags
09
H: Holiday (Input value: 0=disable; 1=enable)
PPPPPP= New master code
PPPPPPRRRRRR
Suspend:10
Delete:
10
SSSSS
SSSSS 9 EEEEE
Recover tag
11
SSSSS
EEEEE
Setting up Card or PIN mode by user address
12
UUUUU
PPPP
Setting up Card and PIN mode by user address
13
UUUUU
PPPP
Arming output setting
14
TTT
Duress code setting
15
PPPP
Card number modification
16
UUUUU
Arming PWD setting
17
PPPP
Enabling or Disabling into arming status
Card+NNNN
Enabling or Disabling each device into arming status.
Card+NNNN
Enabling all device into arming status.
Card+NNNN
Disabling all device into arming status.
Card+NNNN
Door open waiting time
18
U
Set the card by induction
19
UUUUU
Reader additional setting
20
U
RRRRRR= Repeat the new master code
:Suspend 9 :Delete
SSSSS= starting user address; EEEEE= ending user address
SSSSS= starting user address; EEEEE= ending user address
UUUUU= user address; PPPP=4-digit individual PWD
(Access mode: Card or PIN)
UUUUU= user address; PPPP=4-digit individual PWD
(Access mode: Card and PIN)
Base on 1ms, range:1~255, default value=10,
Input 0= Timeless
PPPP=4-digit PWD (0001-9999)
SSSSSCCCCCC
Default value:0000
UUUUU=user address
SSSSS=5 digit site code ; CCCCC=5 digit card code
PPPP=4-digit PWD (0001-9999)
Default value:1234
NNNN:Arming PWD
U=Enable target unit (0=AR-725(E-V2) , 1=WG Reader)
U
9
U=Enable target unit (0=AR-725(E-V2) , 1=WG Reader)
TTT
DDD
EEEEE
TTT=Door open waiting time:001~600;default value:15 sec.
QQQQQ
UUUUU=user address
QQQQQ=Card quantity(00001=Continuously inducting)
U=Enable target unit (0=AR-725(E-V2) , 1=WG Reader)
DDD=Function default value
Access controller
Illuminated Touch-panel
Command List
Function
Command
Lift control setting: multi-doors
21
UUUUU
G
AR-401RO16/ AR-401RO16B relay time setting
23
MMM
Factory setting
24
U
Real time clock setting
25
YYMMDDHHMMSS
Anti-pass-back (Enable user)
26
SSSSS
EEEEE
Lift control setting: single door
27
UUUUU
LL
Exposition
UUUUU=user address;G=4 sets of lift control(0~3);
LLLLLLLL=8 assigned floor (F=0: Disable, 1: Enable)
MMM=Node ID of lift controller
LLLLLLLL
TTT
TTT= relay time: 000~600=1~600 sec.
U=Enable target unit (0=AR-725(E-V2) , 1=WG Reader)
DDD
Duress Function and Arming output setting
28
FFF
Delete all tag
29
29
Same tag reading interval time
31
TTTT
V130116
DDD:Function default value
YYMMDDHHmmSS: Year/Month/Day/Hour/Min./Sec.
SSSSS= starting user address; EEEEE= ending user address
P
P=0=Enable; P=1=Disable; P=2=Initial
UUUUU=user address;LL:Floor number(01~64 floor)
Arming output and Duress function: FFF= 008 (default value)
Base on 10ms, range from 10 to 6000
Auto ring the clock alarm schedule
32
SS
Holiday Setting
35
MMDD
Enabling or Disabling into Full Access status
36
MW
37
AB
A=0:AR401RO
1:Host (default value)
2:LED Panel
3:Printer
38
DDD
DDD : 001=4800 bps
DDD : 129=19200 bps
RS485 port function setting
(Needs to be restarted after setting)
TTL port BAUD setting
HHMMTT
SS= 16 sets auto alarm schedule, range 0~15
HHMM= HH:MM (ex. 0830: Ring bell at 08:30)
TT=Period of time to ring bell
(Base on second, range 01~99 sec.)
7123456: 7 days of week -Sun/Mon/Tue/Wed/Thu/Fri/Sat
(Input value: 0=disable; 1=enable)
H: Holiday (Input value: 0=disable; 1=enable)
MM= Month of year (01=Jan...10=Oct.)
DD= Date of month (01=1st day of month)
F= 0:Delete ; 1: Add
M=AR-725(E-V2); W=WG Reader (0=disable; 1=enable)
7123456H
F
B=0: 9600(default value)
1: 19200
2: 38400
3: 57600
DDD : 065=9600 bps
Function Default Value
20
U
DDD
Function
Time Attendance
Auto Re-lock
Auto Open
When Access Mode is "Card and PIN", Readers can skip pressing PIN code.
Exit by Push Button
Enable force Open
As Access/Exit Reader
Anti-pass-back
24
U
※0: Yes
※0: Disable
※0: Disable
※0: Disable
0: Disable
※0: Slave
※0: Exit
※0: Disable
DDD
Function
Enable Egress Beep Sounds
Enable Arm/Disarm Zone(62)
Reader and controller share the same door relay (only for reader)
Free Access Mode
Stop Alarm by...
Open door immediately without 1st card presented at auto open zone
※0: Disable
※0: Disable
0: Disable
※0: Disable
※0: None
※0: Disable
Option
1: No
1: Enable
1: Enable
1: Enable
※1: Enable
1: Mater
1: Access
1: Enable
Value
001
002
004
008
016
032
064
128
※Default Value
Application
Networking
Networking/Stand-Alone
Networking/Stand-Alone
Networking/Stand-Alone
Networking/Stand-Alone
Networking
Networking
Networking
※Default Value
Option
Value Application
1: Enable
001 Networking/Stand-Alone
1: Enable
008 Networking/Stand-Alone
016 Networking/Stand-Alone
※1: Enable
1: Enable
032 Networking/Stand-Alone
1: Push button/Door Closed 064 Networking/Stand-Alone
1: Enable
128 Networking/Stand-Alone
※ U=Reader (0=AR-725(E-V2), 1=WG);DDD = Value。
28
FFF
Function
Expiry User Access Trigger Alarm
Option
※0:Disable
Auto Reset Anti-pass on TZ61
Duress Function and Arming output setting
RS-485
1:Enable
1:Enable
※0:Disable
0:Wiegand output ※1: Arming and Duress
401RO16B:00
LED: 10
056
Networking/Stand-Alone
002
Networking/Stand-Alone
008
※HOST: 01
000
016
PRN: 11
032
048
[e.g.]Setting AR-725 (E-V2) : Arming and Duress+PRN→(1x008)+(1x 048)=056
Access programming mode → 28
※Default Value
Application
Networking/Stand-Alone
Value
001
→ setting is completed
Networking/Stand-Alone