8 June 2017 TECHNICAL SPECIFICATIONS MEXICO

8 June 2017
TECHNICAL SPECIFICATIONS
MEXICO - HCFC PHASE-OUT MANAGEMENT PLAN (HPMP) Stage II
EQUIPMENT FOR REFRIGERATION RECLAMATION CENTRES
Grant: 2000002933
I.
General Background Information and Objective of the Project
1. Project Objective
The Government of Mexico is the first country that has approved both
Stage I and Stage II HCFC Phase-out Management Plans (HPMPs) in the
consumption sector that help the Government of Mexico to reach compliance
with the Freeze in 2013, 10% reduction target in 2015, 35% reduction by
2018, 50% reduction by 2020 and 67.5% reduction in 2022. Stage I HPMP of
Mexico is addressing mainly the phase-out of HCFC-141b in the foam and
appliance manufacturing sectors however, HCFC-141b and HCFC-22
consumption is also addressed in the aerosol/solvents and service sectors.
Stage II HPMP focuses on the complete phase-out of HCFC-141b consumption
in all sectors as well as on the further reduction of HCFC-22 consumption in
the service and aerosol/solvent sectors.
These technical specifications focus on the reclamation of refrigerants in
centralized operation. Since Recovery, Recycling and Reclaim of refrigerants
will be made mandatory by law, it is proposed to upgrade two national HCFC
Reclamation Centers selected by the Government of Mexico. The success in
establishing and operating of these centers can lead to smoothening of the
phase-out of HCFC-22.
2. Expected Outputs
Two national HCFC Reclamation Centers upgraded to ensure supply of
recovered and reclaimed HCFC-22 to the local servicing market, thereby
reducing demand for virgin HCFC-22.
1
II. Scope of Supply
II.1 – Equipment, parts, supplies to ECOFRIGO company
i)
System Evacuation and Cleaning/Drying station for Refrigerant
cylinders equipped with (1 set)
a. Complete Kit for refrigerant Cylinder Valve removal AND valve
installation - equipped with:
 Electric Valving and De-valving unit, floor mounted with two
sections, one to remove valve and the lower to hold cylinder, one
electrical and the other pneumatic;
 Front heavy type operator protection panel
 Self-supported once mounted on floor
 Operating front panel with mechanical or electrical panel control
b. Hot water pressure washer













Mobile (mounted on wheels)
Hot water dispenser washer able to produce 2900 to 3400 psi, and
3.5 Min GPM of Hot Water pressure washing power
7.5 HP Motor for hot water pump 230-240V 1phase, 60Hz, 25 Amp
Gun and wand with insulated grips and quick connects
Angle lance with a set of 3 rotating nozzles, nozzle and lance
diameter to be ¼” for easy insertion and internal cleaning of
refrigerant cylinders
All hoses 50’ in length for high pressure to match washer pressure
output of 1500 psi
Heater to deliver 120-130 F hot water with diesel burner
Diesel tank with a minimum of 8 gallon capacity
Adjustable Thermostat
Brake and Reel kits
Safety Relief valve protection
Pump to be Belt Driven
Mobile unit cart to be powder coated
c. Cylinder drying equipment kit






To hold cylinders upside down
Cylinder Rack shaft to be made out of 300 series stainless steel to
prevent corrosion
Able to hold 30, 50 and 100 lbs cylinders
Must have drip pan with 50 gallon capacity and 20 mesh screen
and drain valve, all stainless
Drip pan to have gravity flow floor for easy draining
Rack must be able to hold up to 10 cylinders at a time
d. Cylinder filling holder



Air driven Vice to hold cylinders prior to filling
The Vice Cylinder Holder must be base mounted
With Rubber covered jaws to protect and hold cylinder
2

Pressure regulator kit for clamping force adjustment
e. Vacuum pump cart mounted








Class 1 div 2 vacuum pump system, mounted on Aluminum Cart,
mobile, with swivel wheels and locks
Able to pull 0.75 Torr/29.92” HgV in any cylinder and or ISO tank
Pump to be 10 HP, 180 CFM, 230-240 V, 1ph, 60 Hz
Inlet filter, stainless steel piping and P/Vac gauges
To be used to vacuum cylinders and containers for any refrigerant,
flammable and non-flammable.
Include up to 25’ of electrical cord and ground reel and clamp
Inspection mirror/camera for cylinder internal inspection. Mirror or
camera shall have a dimension allowing for insertion into the cylinder
through valve opening;
Instruction manual in Spanish
3
II.2 – Equipment, parts, supplies to SILVER BREEZE company
i)

















ii)


















DRAKE 25 Ton nominal dual circuit Scroll chiller with separate
recirculation system or Similar (one)
For cooling (air-cooled) and condensation of refrigerant being reclaimed,
Packaging and drying process
Voltage 220 V/3 Ph/60 Hz
Ambient Air 95 deg F
Entering Fluid : P. Glycol 55 deg F / Leaving fluid 40 deg F at flow rate
32.8 (GPM)
Nominal BTU 300,263 Actual BTU 245,892
PSG Microprocessor Control (CTRL-STD)
Evaporator Sized For Glycol (EVAP-UP)
Aluminium Fin Condenser (CND-STD)
Low Ambient 40 Deg F (LA-STD)
High Efficiency Brazed Plate Evaporator (BP-STD)
Suction Line Accumulator (s) (SLA-STD)
Fused Disconnect and Phase Monitor (FUSE-OPT D500-801)
200 Gallons Stainless Steel Recirculation Tank (TSR200S-SS)
36 GPM @ 30 psi 1HP Process Pump with Isolation Ball Valves with
Unions. (ISO-STD)
96 GPM @ 30 psi 3HP Process Pump with Isolation Ball Valves with
Unions. (ISO-STD)
Tank sight glass
Instruction manual in Spanish
EVAC High Pressure Electromechanical Commercial Recovery
System (REF TEC) with cleaning module or Similar (one)
To service chillers and other large cooling systems
Services R12, R22, R134a, R502 & other high pressure refrigerants
Application: On site portable refrigerant recovery
Minimum Recovery Rate 324 lb/min (R22 liquid) and 6lb/min (vapour)
to service chillers & other large cooling systems
Voltage 220 V/1 Ph/60 Hz 15 Amps
Air cooled condenser
Final vacuum 15” Hg
AHRI 700 certified
3 HP single phase 1,725 RPM electric motor
Open drive reciprocating compressor
Actuated valving system and electromechanical controls
48 cubic inch dryer core to remove moisture, acids and particulates
Connections ¾” flare with ball valves
100-ft power cords for controls (3 Phase only) 50-ft power cord for the
system
12 ft tank float cable 3 pin BH
2 of ¾” x 10 ft refrigerant hoses and 2 of ¾’’ x 20 ft hose
Instruction manual in Spanish
Suggested additional requirements:
o Built-in low pressure / high pressure gauges
o Replaceable inlets filters
o Self-evacuating to ensure refrigerants are not mixed when
changing refrigerant
o Protection against overpressure
o Thermal overload protection
o Cylinder overfill protection
4
The recovery unit should be delivered with an external cleaning
module comprising oil-separator with draining capability as well
as a filter drier. All necessary hoses required to operate the
recovery unit AND the cleaning module should be supplied.
o Two copies of complete operating and maintenance instructions
(Spanish)
Accessories and Spares to be included for each unit:
o 5x
Replaceable inlet filters for unit & cleaning module
o 1x
Sight glass
o 2x
Spare pressure gauges
o Any other recommended spare parts and consumables for one
year of normal use
o

iii)





















LOVAC Low Pressure Commercial Recovery System (REF TEC) with
cleaning module or Similar (one)
For low pressure chillers and other large cooling systems
To service R11, R-113, R-123, R-114 & other low pressure refrigerants
Application: On-site portable refrigerant recovery (liquid and vapour
transfer)
Minimum Recovery Rate 100 lb/min (R11 liquid) and 0.66lb/min
(vapour)
Voltage 220 V/1 Ph/60 Hz 15 Amp
Electromechanical water-cooled condenser
Final vacuum 29” Hg
AHRI 700 certified
2 HP single phase 1,725 RPM electric motor
Open drive compressor
3 Way hand valves and re-routing Hoses
48 cubic inch dryer core to remove moisture, acids and particulates
Connections ¾” flare or optional quick connects
50-ft power cord for the system
12 ft tank float cable 3 pin BH
2 of ¾” x 10 ft refrigerant hoses and 2 of ¾’’ x 20 ft hose with ball
valves
Low pressure cut off switch 29” Hg
Instruction manual in Spanish
Suggested additional requirements:
o Built-in low pressure / high pressure gauges
o Replaceable inlets filters
o Self-evacuating to ensure refrigerants are not mixed when
changing refrigerant
o Protection against overpressure
o Thermal overload protection
o Cylinder overfill protection
o The recovery unit should be delivered with an external cleaning
module comprising oil-separator with draining capability as well
as a filter drier. All necessary hoses required to operate the
recovery unit AND the cleaning module should be supplied.
o Two copies of complete operating and maintenance instructions
(Spanish)
Accessories and Spares to be included for each unit:
o 5x
Replaceable inlet filters for unit & cleaning module
o 1x
Sight glass
o 2x
Spare pressure gauges
Any other recommended spare parts and consumables for one year of
normal use
5
iv)


Enviropurge HP Portable, Air/Water cooled (REF TEC EHP-611)
Purger or Similar (one)
Application: Removes non-condensable gases from high pressure
refrigerants to service chillers, large cooling systems and storage
refrigerant tanks
Power requirements: 120V/60Hz/1Ph/30 Amps
Air or Water cooled condenser
Discharge efficiency as high as 0.2 lbs/refg/lbs-non-condensable
ETL, CE, CSA and EPA compliant and UL 1963
0.5 HP semi hermetic compressor with internal overload and
microprocessor controls
Aluminium or steel portable cart on wheels
48 cubic inch dryer core to remove moisture, acids and particulates (20
pieces)
1/2 and 3/8-inch flare connections and shut off valves
Services R-12, R-134a, R-22, and R-502 refrigerants
25-ft power cord for the system
2 Isolation valves
1 piece of 20 ft x ½-inch refrigerant hoses and 1 piece of 20 ft x 3/8inch hoses
Low pressure cut off switch 29” Hg
Instruction manual in Spanish














Corken Industrial Gas High Speed High Volume
Refrigerant Recovery Compressor or Similar (one)
Application: Refrigerant Reclaiming Process Unit
Power requirements: 220V/1Ph/ 60 Hz/17amps
Discharge efficiency as high as 300lbs/refg/hr
3 HP/ 1740 RPM motor
Constructed welded steel base, adjustable motor slide base
3/4-inch inlet/outlet connections and shut-off valves
Services R-12, R-134a, R-22, and series 500 refrigerants
S-7057 Vertical Refrigerant Accumulator
11/8” Helical oil separator
Temprite 900 series oil separator
7/8” Vertical Refrigerant Accumulator
100 cubic-inch desiccant block filter dryer
20 psi inlet regulating valve
Instruction manual in Spanish













v)
vi)
In
House
System Evacuation and Cleaning/Drying station for Refrigerant
cylinders equipped with (1 set)
f. Complete Kit for refrigerant Cylinder Valve removal AND valve
installation - equipped with
 Electric Valving and De-valving unit, floor mounted with two
sections, one to remove valve and the lower to hold cylinder, one
electrical and the other pneumatic;
 Front heavy type operator protection panel
 Self-support once mounted on floor
 Operating front panel with mechanical or electrical panel control
6
g. Hot water pressure washer













Mobile (mounted on wheels)
Hot water dispenser washer able to produce 2900 to 3400 psi, and
3.5 Min GPM of Hot Water pressure washing power
7.5 HP Motor for hot water pump 230-240V 1phase, 60Hz, 25 Amp
Gun and wand with insulated grips and quick connects
Angle lance with a set of 3 rotating nozzles, nozzle and lance
diameter to be ¼” for easy insertion and internal cleaning of
refrigerant cylinders
All hoses 50’ in length for high pressure to match washer pressure
output of 1500 psi
Heater to deliver 120-130 F hot water with diesel burner
Diesel tank with a minimum of 8 gallon capacity
Adjustable Thermostat
Brake and Reel kits
Safety Relief valve protection
Pump to be Belt Driven
Mobile unit cart to be powder coated
h. Cylinder drying equipment kit






To hold cylinders upside down
Cylinder Rack shaft to be made out of 300 series stainless steel to
prevent corrosion
Able to hold 30, 50 and 100 lbs cylinders
Must have drip pan with 50 gallon capacity and 20 mesh screen
and drain valve, all stainless
Drip pan to have gravity flow floor for easy draining
Rack must be able to hold up to 10 cylinders at a time
i. Cylinder filling holder




Air driven Vice to hold cylinders prior to filling
The Vice Cylinder Holder must be base mounted
With Rubber covered jaws to protect and hold cylinder
Pressure regulator kit for clamping force adjustment
j. Vacuum pump cart mounted








Class 1 div 2 vacuum pump system, mounted on Aluminum Cart,
mobile, with swivel wheels and locks
Able to pull 0.75 Torr/29.92” HgV in any cylinder and or ISO tank
Pump to be 10 HP, 180 CFM, 230-240 V, 1ph, 60 Hz
Inlet filter, stainless steel piping and P/Vac gauges
To be used to vacuum cylinders and containers for any refrigerant,
flammable and non-flammable.
Include up to 25’ of electrical cord and ground reel and clamp
Inspection mirror/camera for cylinder internal inspection. Mirror or
camera shall have a dimension allowing for insertion into the cylinder
through valve opening;
Instruction manual in Spanish
7
vii) Reclamation unit with 2HP compressor (1)
 Suitable for multi-refrigerants use (R-12, R-134a , R-22 , R-500 , R502,
and other refrigerants)
 Hermetic compressor, 2HP
 Capable of vacuum operation;
 Liquid Injection for compressor protection under vacuum operation;
 Sub-cooling feature;
 Measurable oil out
 Cylinder overfill protection feature
 Reclamation capacity 2.3 kg/minute in the liquid phase
 Storage capacity of 40 kg
 Pressure gauges
 1 ph / 220 volt / 60 hz electric supply
 Accessories and Spares to be include for each unit:
 5 x filter driers
 1 set of spare hoses
 Any other recommended spare parts and consumables for one year
of normal use
III.
Guarantee Requirements
The supplier should give guarantee for at least one year after delivery,
installation, commissioning and training of the equipment.
IV.
Delivery Period
As soon as possible, but within maximum 4 months (DAP).
8
V.
Additional requirements
The supplier(s) shall:
 Provide, in Spanish language, technical advice and detailed
requirements for the site preparation, proper installation and
operation of the equipment.
 Provide, in Spanish language, theoretical and practical training on
the operation and preventive maintenance of the equipment at the
beneficiaries’ sites.
 Quote spare parts and consumables for one year of operation for all
above items.
 Have a representative office in the country and administrative and
technical personnel to give technical support and to repair defective
equipment.
 Warrant during 12 months that goods supplied under the contract
shall be free from defects. The supplier shall repair or replace at his
own expense and as soon as practicable any defective goods within
the warranty period.
 Provide, in Spanish language, all instructions, manuals, rules and
recommendations to operate the equipment (at least two manuals
for each item).
 Warrant the availability of spare parts and equipment for a
minimum period of four years.
9
ANNEX I
Scope of Supply
UNIDO RFP Reference No.
Scope of supply
UNIDO REQUIREMENTS
Item
i
Name and required parameters
II.1. Equipment, parts, supplies - ECOFRIGO
System Evacuation and cleaning/drying station for
cylinders
Qty
TO BE COMPLETED BY THE INVITEE
unit
total item Complia Remark
price
price
nce
s**)
US$
US$
yes/no
1 set
II.2. Equipment, parts, supplies – SILVER BREEZE
i
ii
iii
iv
v
vi
vii
DRAKE 25 Ton nominal dual circuit Scroll chiller with
separate recirculation system or Similar
EVAC High Pressure Electromechanical Commercial
Recovery System (REF TEC) with cleaning module or
Similar
LOVAC Low Pressure Commercial Recovery System
(REF TEC) with cleaning module or Similar
Enviropurge HP Portable, Air/Water cooled (REF TEC
EHP-611) or Similar
Corken Industrial Gas High Speed High Volume In
House Refrigerant Recovery Compressor or Similar
System Evacuation and cleaning/drying station for
cylinders
Reclamation unit with 2HP compressor
1
1
1
1
1
1 set
1
III. Cost of transportation & insurance
Total price:
10
ANNEX II - Delivery details and addresses
RRR Centre
1
2
ECOFRIGO, S.A. DE C.V.
SILVER BREEZE- CENTRO DE RECICLADO
DE REFRIGERANTES
ADDRESS
Carretera Celaya Salvatierra Km.
6.5, Rancho Santa María del
Refugio
Celaya, Guanajuato
México
Luis de Velazco 1501, Colonia
Vista Hermosa
Mexicali, Baja California
México
CONTACT PERSON