QuickSpecs
HPE Line Interactive Single Phase UPS
Overview
HPE Line Interactive Single Phase Uninterruptible Power Systems (UPS)
Looking for cost-effective power protection for your small office environments?
HPE Line Interactive Single Phase Uninterruptible Power System (UPS) solutions range from tower-based systems designed to
safeguard tower servers and small office equipment, to rack-based systems that can protect a full rack of servers. Standard features
include intuitive front panel displays for local management, and HPE Enhance Battery Management (EBM) that help to extend the
service-life of your batteries. HPE Power Protector, a power management software application that ships with each model, combined
with a UPS Network Module, optional on some models, enables you to remotely monitor and manage your UPS through HPE Systems
Insight Manager or via a standard web browser.
When you need it, use outstanding HPE support services for your whole data center environment. With HPE Pointnext operational
services, have the security of knowing that your HPE UPS will be covered at the same service level and coverage period as your HPE
server. HPE UPSs are backed by a 3-year limited warranty, with the first year including parts and labor. Also, standard on all HPE
UPS units is our exclusive 30-day Battery Pre-Failure Warranty, which ensures that when customers receive notification from HPE
Power Manager Software that the battery may fail, the battery is replaced free of charge under the warranty. This warranty is offered
worldwide.
Models
Tower UPS Models
HPE T750 G4 UPS Models
HPE T750 G4 NA/JP Uninterruptible Power System
HPE T750 G4 INTL Uninterruptible Power System
HPE T1000 G4 UPS Models
HPE T1000 G4 NA/JP Uninterruptible Power System
HPE T1000 G4 INTL Uninterruptible Power System
HPE T1500 G4 UPS Models
HPE T1500 G4 NA/JP Uninterruptible Power System
HPE T1500 G4 INTL Uninterruptible Power System
J2P85A
J2P88A
J2P86A
J2P89A
J2P87A
J2P90A
Rack/Tower UPS Models
HPE R/T2200 G4 UPS Models
HPE R/T2200 G4 NA/JP Uninterruptible Power System
HPE R/T3000 G4 UPS Models
HPE R/T3000 G4 Low Voltage NA/JP Uninterruptible Power System
HPE R/T3000 G4 High Voltage NA/JP Uninterruptible Power System
HPE R/T3000 G4 High Voltage INTL Uninterruptible Power System
J2R00A
J2R01A
J2R02A
J2R04A
Page 1
QuickSpecs
HPE Line Interactive Single Phase UPS
Overview
Rack UPS Models
R1500 G4 Models
HPE R1500 G4 NA Uninterruptible Power System
HPE R1500 G4 JP/TWN Uninterruptible Power System
HPE R1500 G4 INTL Uninterruptible Power System
R5000 UPS Models
HPE R5000 3U L630 High Voltage NA/JP Uninterruptible Power System
HPE R5000 3U IEC309-32A High Voltage INTL Uninterruptible Power System
R7000 UPS Models
HPE R7000 4U 50A High Voltage NA/JP Uninterruptible Power System
HPE R7000 4U IEC-32A High Voltage INTL Uninterruptible Power System
J2Q99A
J2R05A
J2R03A
AF460A
AF461A
AF462A
AF463A
Page 2
QuickSpecs
HPE Line Interactive Single Phase UPS
Tower UPS Features
Tower UPS Rear Panel
HPE T750 G4 UPS INTL
1. USB Communication Port
2. RS-232 Communication Port
3. Outlets for Connection of Critical Equipment
HPE T750 G4 UPS NA/JPN
1. USB Communication Port
2. RS-232 Communication Port
3. Outlets for Connection of Critical Equipment
HPE T1000 G4 UPS INTL
HPE T1500 G4 UPS INTL
4. Socket for Connection to AC Power Source
5. Ground Screw
HPE T1000 G4 UPS NA/JPN
HPE T1500 G4 UPS NA/JPN
4. Attached 6-ft. Input Power Cord for AC Power Source
5. Ground Screw
Tower UPS Models Provide Power Protection and Management Optimized for Smaller IT
Environments
Key Features
• Manageability through USB and Serial ports
• Ease of configuration via enhanced front panel display.
• Intelligent manageability with bundled Power Manager Software.
NOTE: Certain restrictions and exclusions apply. Consult the HPE Computer Support Center for details.
Page 3
QuickSpecs
HPE Line Interactive Single Phase UPS
Tower UPS Specifications
Towers G4 UPS Specifications
Battery Type
Electrical Input
Electrical Output
Battery
Communications
Environmental and Safety
12 V, sealed, maintenance-free, rechargeable, valve regulated lead-acid batteries with a 3-5
year service life at 25C (77F).
± 20% for nominal voltages of 100, 110, 120, 220, 230, and
Voltage Range
240VAC. NOTE: Nominal voltages to coincide with standard
power ranges.
50/60 Hz
Frequency
>94%
Online Efficiency
N/A
REPO
-10% to +6% of nominal voltage
Online Regulation
±5%, -10% of nominal voltage
On battery Regulation
Sine wave
Voltage Wave Form
See Model Selection Matrix
Connections
Firmware overload sensing and control
Output protection
N/A
Extended Batteries
See Backup Times Chart
Backup Time
<4 hours to charge 90% usable capacity. <24 hours for complete
Recharge Time
recharge
RS232 (via RJ45 connector to DB9) and USB ports (ships with
Serial Ports
communication cables)
N/A
Option Slot
N/A
Option Cards
LCD Display and Button Interface
LCD Interface
HPE Power Protector management software available via
Software
download
Operating Temperature 32° to 104° F (0° to 40° C) ( with battery)
-15° to 55° F (-26° to 13° C) (without battery)
Non-operating
Temperature
5% to 90% (non-condensing)
Operating Humidity
5% to 90% (non-condensing)
Storage Humidity
Up to 1500 m above sea level
Operating Altitude
<40dB in normal operation. <45dB while on inverter
Audible Noise
NA/JPN: UL/cUL, ICES B,NOM,VCCI, Int'l: CE,TUV GS,C-tick,EAC,KC
Safety Markings
UL1778, UL60950-1; CSA22.2 No.107.3-05,; EN609501-,
Safety Certifications
EN62040-1 IEC62040-1-1, IEC 60950-1
N/A
REPO Port
Page 4
QuickSpecs
HPE Line Interactive Single Phase UPS
Tower UPS Specifications
HPE T750 G4 UPS Specifications
See model matrix for other specifications.
T750 G4, NA/JP
Load Segments
J2P85A
Unit Dimensions (WxDxH)
T750 G4, INTL
Shipping Dimensions(LxWxH)
J2P88A
Unit Weight
Shipping Weight
1
5.9 x 13.4 x 8.3 inch (150 x 340 x 210 mm)
18.7x 9.4 x 12.1 inch (476 x 238 x 308 mm)
23.6 lbs (10.7kg)
26.4 lbs (12 kg)
HPE T1000 G4 UPS Specifications
T1000 G4, NA/JP
J2P86A
T1000 G4, INTL
J2P89A
Load Segments
Unit Dimensions (WxDxH)
Shipping Dimensions(LxWxH)
Unit Weight
Shipping Weight
1
5.9 x 13.4x 8.3 inch (150 x 340x 210 mm)
18.7 x 9.4 x 12.1 inch (476 x 238 x 308 mm)
25.1 lbs (11.4kg)
28.7 lbs (13 kg)
HPE T1500 G4 UPS Specifications
T1500 G4, NA/JP
J2P87A
T1500 G4, INTL
J2P90A
1
Load Segments
5.9 x 16.1 x 8.3inch (150 x 410 x 210 mm)
Unit Dimensions (WxDxH)
Shipping Dimensions(LxWxH) 19.6 x 9.4 x 12.1 inch (498 x238 x 308 mm)
34.4 lbs (15.6 kg)
Unit Weight
37.3 lbs (16.9 kg)
Shipping Weight
NOTE: Locate which Operating Systems are supported
at: https://www.hpe.com/us/en/product-catalog/detail/pip.hpe-advanced-powermanager.5202410.html.
HPE R/T2200 and R/T3000 Tower Uninterruptible Power System (UPS)
R/T3000 in Rack UPS configuration
R/T3000 with Tower UPS floor stands
Page 5
QuickSpecs
HPE Line Interactive Single Phase UPS
HPE Rack/Tower UPS specifications
HPE R/T2200 Uninterruptible Power System (UPS)
Front panel
1
1
2
3
4
5
6
7
Battery compartment
2
Control buttons and LED display
NA/JPN/TWN rear panel
Load segment 1 (one NEMA 5-15 output receptacle for
8 USB communications port
surge and battery backup protection)
Load segment 2 (one NEMA 5-15 output receptacle for
9 REPO port
surge and battery backup protection)
Load segment 3 (one NEMA 5-15 output receptacle for
10 Voltage configuration and charge rate DIP switches
surge and battery backup protection)
Load segment 4 (one NEMA 5-15 output receptacle for
11 Power sensitivity adjustment dial
surge and battery backup protection)
Input circuit breaker
12 Ground bonding screw
Input power cord with NEMA 5-20 plug
13 ERM connector
Serial communications port
Page 6
QuickSpecs
HPE Line Interactive Single Phase UPS
HPE Rack/Tower UPS specifications
HPE R/T3000 Uninterruptible Power System (UPS)
Front Panel
1
1
2
3
4
5
6
Battery compartment
2 Control buttons and LED display
NA/JPN rear panel
UPS option card
7 Load segment 2 (two NEMA 5-20R T-slot receptacles)
USB communications port
8 PDU output (NEMA L5-30R) receptacle (load segment 1)
Serial communications port
9 Cord retention clip attachment location
Load segment circuit breaker
10 Cord retention clip attachment location
Load segment 1 (two NEMA 5-20R T-slot receptacles)
11 Ground bonding screw
Load segment circuit breaker
12 Power cord with L5-30 plug
Page 7
QuickSpecs
HPE Line Interactive Single Phase UPS
HPE Rack/Tower UPS specifications
HPE R/T2200 and R/T3000 Tower Uninterruptible Power System (UPS)
Flexible Rack/Tower Models Deliver Cost-Effective Power Protection
Key features
•
•
•
•
•
•
•
Convertible design can be used as a 2U rack mountable UPS or as a standalone tower UPS
Power density up to 3000VA / 2700 Watts (200-240V models)
Easy configuration through enhanced front panel display
More efficient voltage regulation using digital signal processing technology
Enhanced system flexibility with two independently controlled load segments
Support for Remote Emergency Power Off (REPO) circuitry
Easy serviceability through modular design
Specifications
R/T2200 G4 UPS (NA/JPN only)
Battery Type
Electrical Input
Electrical Output
Battery
Communications
Environmental and Safety
12 V, 34W, sealed, maintenance-free, rechargeable, valve regulated lead-acid batteries with a
3-5 year service life at 25C (77F).
See Model Matrix for nominal and user selectable voltage settings;
Voltage Range
Battery string voltage 48Vdc
50/60 Hz
Frequency
94%
Online Efficiency
Remote Emergency Power-Off disables AC power to load
REPO
-10% to +6% of nominal voltage
Online Regulation
±5% of nominal voltage
On battery Regulation
Sine wave
Voltage Wave Form
See Model Selection Matrix; divided into 2 Load Segments
Connections
Maintenance-free, sealed, valve-regulated lead acid (VRLA)
Type
Up to four ERMs can be supported; recommendation is up to 2
Extended Batteries
See Backup Times Chart
Backup Time
<3 hours to 90% usable capacity; <48 hours for complete recharge
Recharge Time
Standard DB-9 and USB ports (ships with communication cables)
Serial Ports
One (For Optional Communication Card)
Option Slot
HPE UPS Network Module (not included in kit but orderable
Option Cards
option)
LCD Display and Button Interface
LCD Interface
HPE Power Protector software available via download
Software
Operating Temperature 0°C to 40°C (32°F to 104°F); Long term use at higher temperature
will reduce battery life 25°C (77°F)
-15°C to 50°C (-5°F to 122°F)
Non-operating
Temperature
20% to 90% (non-condensing)
Operating Humidity
10% to 90%
Storage Humidity
Up to 6,562 ft (2000 m) above sea level
Operating Altitude
<40dB in normal operation. <45dBon battery operation
Audible Noise
NA/JPN: UL, cUL, VCCI
Safety Markings
Page 8
QuickSpecs
HPE Line Interactive Single Phase UPS
HPE Rack/Tower UPS specifications
Safety Certifications
Unit Dimensions (LxWxH)
Shipping Dimensions(LxWxH)
Unit Weight
Shipping Weight
UL1778, UL60950-1; CSA22.2 No.107.3-05,; EN60950-1,
EN62040-1IEC62040-1-1, IEC 60950-1,
Meets NEC code 645-10 and 645-11and UL requirements
REPO Port
20.55x 17.36 x 3.39 inches / 522x 441 x 86.2 mm
36.26 x 23.23 x 11.02 inches / 921 x 590 x 280 mm
65.28 lbs/29.61 kg
83.62 lbs UPS and 83.62 lbs ERM / 37.93 kg & 37.93 kg
R/T3000 G4 UPS
Battery Type
Electrical Input
Electrical Output
Battery
Communications
Environmental and Safety
Unit Dimensions (LxWxH)
12 V, 34W, sealed, maintenance-free, rechargeable, valve regulated lead-acid batteries with a
3-5 year service life at 25C (77F).
See Model Matrix for nominal and user selectable voltage settings;
Voltage Range
Battery string voltage 72Vdc
50/60 Hz
Frequency
94%
Online Efficiency
Remote Emergency Power-Off disables AC power to load
REPO
-10% to +6% of nominal voltage
Online Regulation
On battery Regulation ±5% of nominal voltage
Sine wave
Voltage Wave Form
See Model Selection Matrix; divided into 2 Load Segments
Connections
Re-settable circuit protectors
Output Protection
Maintenance-free, sealed, valve-regulated lead acid (VRLA)
Type
Up to four ERMs can be supported; recommendation up to 2
Extended Batteries
See Backup Times Chart
Backup Time
<3 hours to 90% usable capacity; <48 hours for complete recharge
Recharge Time
Standard DB-9 and USB ports (ships with communication cables)
Serial Ports
One (For optional communication card)
Option Slot
HPE UPS Network Module (not included in kit but orderable
Option Cards
option)
LCD Display and Button Interface
LCD Interface
HPE Power Protector software available
Software
Operating Temperature 0°C to 40°C (32°F to 104°F); Long term use at higher temperature
will reduce battery life at 25°C (77°F)
-15°C to 50°C (-5°F to 122°F)
Non-operating
Temperature
20% to90% (non-condensing)
Operating Humidity
10% to 90%
Storage Humidity
Up to 6,562 ft (2000 m) above sea level
Operating Altitude
<4dB in normal operation. <50bB on battery operation
Audible Noise
NA/JPN LV /HV: UL, cUL, VCCI
Safety Markings
Int'l: GS, CE, C-tick, TUV, EAC
UL1778, UL60950-1; CSA22.2 No.107.3-05,; EN60950-,
Safety Certifications
EN62040-1 IEC62040-1-1, IEC 60950-1
Meets NEC code 645-10 and 645-11and UL requirements
REPO Port
25.47 x 17.4 x 3.4 inches / 647 x 441x 86.2 mm
Page 9
QuickSpecs
HPE Line Interactive Single Phase UPS
HPE Rack/Tower UPS specifications
Shipping Dimensions(LxWxH)
Unit Weight
Shipping Weight
36.26 x 23.23 x 11.02 inches / 921 x 590 x 280 mm
87.17 lbs/39.54 kg
107.48 lbs UPS and 120.59 lbs ERM / 48.75 kg & 54.7kg
HPE R1500 G4 NA and JP/TWN UPS
1. IUSB Communication Port
2. ES-232 Communication Port
3. Slot for optional communication card
6a. Group 1: programmable outlets for equipment connection
6b. Group 2: programmable outlets for equipment connection
7. Attached 6ft input power cord Nema 5-15P for AC power
source,
4. Connector for ROO(Remote On/Off) or RPO (Remote Power 8. LED indicating site wiring fault alarm
Off) Control
5. Outlets for connection of critical equipment (Primary group) 9. Ground screw
HPE R1500 G4 International UPS
1. USB communication port
2. RS-232 communication port
6a. Group 1: programmable outlets for equipment connection
6b Group 2: programmable outlets for equipment connection
Page 10
QuickSpecs
HPE Line Interactive Single Phase UPS
HPE Rack/Tower UPS specifications
3. Slot for optional communication card
7. Input power connection (IEC -320-C14) for powering unit to
AC power source
4. Connector for ROO (Remote On/Off) or RPO (Remote Power 8. Ground screw
Off) control
5. Outlets for connection of equipment (Primary group)
R5000 UPS
Front View
Rear View
1.
2.
Escape Button
Scroll up button
1.
2.
3.
Scroll down button
3.
4.
5.
Enter/Select button
Power button
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
ERM connector for the small plug on the split ERM cable
Load segment 1 circuit breaker (controls the C19 and
C13 receptacles, but does not control the large output
Load segment 1 (two IEC-320-C19 receptacles, two IEC320- C13 receptacles)
Cord retention clip attachment locations
Load segment 2 (two IEC-320-C19 receptacles and two
IEC- 320-C13 receptacles)
REPO port
USB communications port
Serial communications port
HPE UPS Network Module (included)
Ground bonding screw
Input power line cord with NEMA L6-30 plug
Load segment 2 circuit breaker
Large output NEMA L6-30R receptacle or IEC-309-32A
receptacle associated with load segment 1
ERM Connector for large plug
Page 11
QuickSpecs
HPE Line Interactive Single Phase UPS
HPE Rack/Tower UPS specifications
R7000 UPS
Front View
Rear View
1.
Escape Button
1.
2.
Scroll up button
2.
3.
Scroll down button
3.
4.
5.
Enter/Select button
Power button
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
Load segment 1 circuit breaker (controls L6-30R
receptacle Item 3)
Load segment 2 circuit breaker (controls L6-30R
receptacle Item 15)
Large output NEMA L6-30R receptacle or IEC-60309
32A receptacle on short cords associated with load
Cord retention clip attachment locations
Load segment 1 circuit breaker (controls the C19
receptacles, but does not control the large output
3 x IEC C19 receptacles on load segment 1
HPE UPS Network Module
Input power line cord with NEMA CS8265C plug or
IEC-309- 32A plug
Ground bonding screw
Serial communications port
USB communications port
REPO port
3 x IEC C19 receptacles on load segment 2
Load segment 2 circuit breaker (controls the C19
receptacles, but does not control the large output
receptacle)
Ultra-Dense Rack UPS Models Scale from Small to Enterprise IT Environments
Key Features
• Front panel LCD display
• Enhanced system flexibility with two independently controlled load segments
Specifications
HPE R1500 G4 UPS
Electrical Input
Voltage Range
± 15% of nominal100 and 120V models and ± 20% of nominal on
230V models. See Model Matrix for nominal and user selectable
voltage settings via LCD Front Display Panel
Page 12
QuickSpecs
HPE Line Interactive Single Phase UPS
HPE Rack/Tower UPS specifications
Electrical Output
Battery
Communications
Environmental and Safety
Unit Dimensions (LxWxH)
Shipping Dimensions
Unit Weight
Shipping Weight
Frequency
Online Efficiency
Online Regulation
On battery Regulation
Voltage Wave Form
Connections
Output Protection
Type
Backup Time
Recharge Time
Voltage
Ports
50/60 Hz ± 5Hz (auto sensing at default voltage )
92%
-10% to +6% of nominal voltage*
-10% / + 6%of nominal voltage
Sine wave
See Model Matrix; divided into3 Load Segments
Firmware overload sensing and control,
Maintenance-free, sealed, valve-regulated lead acid (VRLA)
See Backup Times Chart
<3 hours to 90% usable capacity; <24 hours for complete recharge
36V Battery String
Standard DB-9 port (Kit ships with cable for communication )
USB port (Kit ships with cable for communication)
One ( for Optional Communication Card)
Option Slot
HPE UPS Network Module (Not included in Kit but orderable Option)
Option Cards
LED display integrated into the front panel
LED Indicators
HPE Power Protector management software available via download
Software
32° to 104° F (0° to 40° C) ( with battery)
Operating Temperature
-15° to 55° F (-26° to 13° C) (without battery)
Storage Temperature
0% to 90%
Humidity (Operation)
Humidity (Non-operating) 0% to 90%
up to 2000 meters
Operating Altitude
<40db (at 1m from surface of unit) <45dBA while on inverter
Audible Noise
UL/cUL CE, TUV, C-tick, CES, EAC, VCCI, GS, KC, EK, BSMI
Safety Markings
UL1778; UL60950, CSA22.2 No.107.1,No.107.3,; CB Bulletin
Safety Certifications
IEC62040-1; IEC 60950-1; EN60950-1;EN 62040-1; EN 61000-32+A1 +A2; EN 61000-3-3
FCC-BCISPR 22; VCCI B; CE, BSMI, C-TICK
EMC Markings
FCC CFR 47, Part 15 Class A, EN50091-2
Emissions
EN 55024; EN 50091-2 consisting of IEC 61000-4-2 thru IEC
Immunity
61000-4-6 ; IEC 61000-4-11
Conforms to IEEE 587B and ANSI C62.41
Surge Suppression
21.8x 17.2x 1.69 in (554 x 438 x 43 mm)
30.71x 22.8 x6.1 in (780 x 580 x 155 mm)
39.06 lb (19.72 kg)
54.45 lb (24.7 kg)
* The R1500 G4 UPS regulates the output voltage at -10% / +6% of the selected nominal voltage. The regulation is accomplished by
bucking or boosting the input voltage. The voltage regulation operation is governed by the unit's input voltage spec of +/-20%. The
unit will regulate at -10% / +6% while within the limits set by the input spec. The unit will go to battery operation upon exceeding the
limits set by the input spec. The buck and boost voltage regulation operation, or AVR (Automatic Voltage Regulation), is
accomplished by adjusting output transformer tap selections via electromechanical relays. The transformer tap selection is
controlled via digital transition voltage set point values programmed in the unit's firmware. These programmed values are without
tolerance.
The unit will monitor the input voltage and accept a range of +/-3% of the selected nominal voltage as the target voltage to regulate
at -10% / +6%. For example, a unit configured to 120V nominal voltage will regulate at -10% / +6% for any voltage measured
between 116.4V and 123.6V. The digital transition voltage set point values will adjust accordingly to regulate to -10% / +6% of the
measured input voltage.
Transition set point voltages are subject to a hardware tolerances of +/-3% of the set point value.
R5000 3U UPS
BTU Break Down
BTU On Line
478 BT/hr
Page 13
QuickSpecs
HPE Line Interactive Single Phase UPS
HPE Rack/Tower UPS specifications
Electrical Input
Electrical Output
Battery
Communications
Environmental and Safety
Unit Dimensions (HxWxD)
Shipping Dimensions
Unit Weight
Shipping Weight
BTU On Battery
Battery Type
Voltage Range
1041 BTU/hr
12V 27W
160-253V at 200/208V nominal; 176-253V at 220, 230, and
240V nominal
50/60 Hz
Frequency
94%
Online Efficiency
Remote Emergency Power-Off disables AC power to load
REPO
-10% to +6% of nominal voltage
Online Regulation
On battery Regulation ±5% of nominal voltage
Sine wave
Voltage Wave Form
See Model Matrix; divided into 2 Load Segments
Connections
Re-settable circuit protectors
Output Protection
Maintenance-free, sealed, valve-regulated lead acid (VRLA)
Type
Up to four ERMs supported
Extended Batteries
See Backup Times Chart
Backup Time
<3 hours to 80% usable capacity; <48 hours for complete recharge
Recharge Time
Battery String Voltage 216V
12V 27W
Battery Type
18
Battery Quantity
LED and switch membrane integrated into the front panel with fourLED Indicators
button control (three buttons for UPS power control and one button
under the front bezel for configuration).
Operating Temperature 50° to 104° F (10° to 40° C )
32° to 77° F (0° to 25° C )
Storage Temperature
-13° to 131° F (-25° to 55° C)
Transit Temperature
5 5 in (12.7 cm) x 17.2 in (43.7 cm) x 29.3 in (74.4 cm)
14.4 in ( 36.58 cm) x 23.6 in ( 60 cm) x 38.78 in ( 98.5 cm)
126 lbs (57kg)
192 lbs ( 87 kg)
R7000 4U UPS
BTU Break Down
Electrical Input
Electrical Output
BTU On Line
BTU On Battery
Battery Type
Voltage Range
Frequency
Online Efficiency
REPO
Online Regulation
On battery Regulation
Voltage Wave Form
Connections
Output Protection
581 BT/hr
1501 BTU/hr
12V 45W
160-253V at 200/208V nominal
50/60 Hz
95%
Remote Emergency Power-Off disables AC power to load
-10% to +6% of nominal voltage
±5% of nominal voltage
Sine wave
See Model Matrix; divided into 2 Load Segments
Re-settable circuit protectors
Page 14
QuickSpecs
HPE Line Interactive Single Phase UPS
HPE Rack/Tower UPS specifications
Battery
Maximum wattage based on
voltage input
Communications
Environmental and Safety
Unit Dimensions (HxWxD)
Shipping Dimensions
(H x L x W)
Unit Weight
Shipping Weight
Type
Extended Batteries
Backup Time
Recharge Time
Battery String Voltage
Battery Type
Battery Quantity
Maintenance-free, sealed, valve-regulated lead acid (VRLA)
Up to four ERMs supported
See Backup Times Chart
<3 hours to 80% usable capacity; <48 hours for complete recharge
216V
12V 45W
18
200-240V: 7200VA/7200W
Serial Ports
Option Cards
LED Indicators
Standard DB-9 and USB ports (ships with communication cables)
HPE UPS Network Module
LED and switch membrane integrated into the front panel with fourbutton control (three buttons for UPS power control and one button
under the front bezel for configuration).
Operating Temperature 50° to 104° F (10° to 40° C )
32° to 77° F (0° to 25° C )
Storage Temperature
-13° to 131° F (-25° to 55° C)
Transit Temperature
20% to 80% (non-condensing)
Operating Humidity
5% to 95%
Storage Humidity
Up to 6,562 ft (2000 m) above sea level
Operating Altitude
49,212 ft (15,000 m) above sea level
Transit Altitude
<46db in normal operation(at 1m from surface of unit)
Audible Noise
NA/JPN: UL, cUL
Safety Markings
Int'l: GS, CE, GOST
UL1778, UL60950-1; CSA22.2 No.107.3, No.60-1950; EN50091Safety Certifications
1-1; EN60950-1 IEC62040-1-1
NA/JPN: FCC, VCCI, ICES, CISPR
EMC Markings
Int'l: BSMI, C-Tick, CISPR
FCC CFR 47, Part 15 Class A, EN50091-2
Emissions
IEC 801-2, IEC 801-3, IEC 801-4, IEC 801-5
Immunity
Meets NEC code 645—11 intent and UL requirements
REPO Port
6.75 in (17.1 cm) x 17.2 in (43.7 cm) x 28.9 in (73.4 cm)
16.10 in (40.9cm) x 23.6 in. (59.9cm) x 38.8 (98.6cm)
165 lbs/75 kg
210 lbs/100 kg
Page 15
QuickSpecs
HPE Line Interactive Single Phase UPS
Related Options
UPS Network Module
The HPE UPS Network Module enables you to monitor and manage power environments through
comprehensive control of HPE UPSs. The HPE UPS Management Module can support either a single
UPS configuration or provide additional power protection with support for dual redundant UPS
configuration for no-single-point-of-failure. The additional serial ports will provide greater power
management control and flexible monitoring.
The management module can be configured to send alert traps to HPE Systems Insight Manager and
other SNMP management programs or used as a standalone management system. This flexibility
enables you to monitor and manage UPSs through the network. To facilitate day-to-day maintenance
tasks, the embedded management software provides detailed system logs.
The HPE UPS Network Module provides remote management of a UPS by connecting the UPS directly
to the network. Configuration & Management of the UPS from anywhere and at anytime via a standard
web browser.
Extended Runtime
Module (ERM)
Extended Runtime Modules increase the available runtime for the larger rack mounted UPS units to
allow customers to ensure all of their applications can be gracefully shutdown in the event of a power
failure.
•
•
R/T2200 G4 & R/T3000 G4 Extended Runtime Module – 2U
R5000 & R7000 Extended Runtime Module – 3U
2U R/T UPS ERM
Shipping Kit
HPE 2U Rack/Tower UPS Shipping Kit
NOTE: The optional 2U shipping kit consists of heavy duty rails, front and back
CTO brackets and required mounting hardware for attaching the UPS or ERM to
the rack. This kit is an option that is required if the UPS and or ERM are going to
be mounted into a rack that will be shipped via transport. One of these kits is
required per unit, whether UPS or ERM.
L4Q11A
Extended Runtime
Modules (ERM)
HPE R/T2200 G4 Extended Runtime Module
HPE R/T3000 G4 Extended Runtime Module
HPE R/T3000 2U Extended Runtime Module
NOTE: AF455A can only be used with the G2 models.
HPE R5KVA and R7KVA 3U Extended Runtime Module
NOTE: #0D1 will appear after the part number on the sales order if HPE factory
integration is indicated.
J2R09A
J2R10A
AF455A
HPE UPS Network Module Mini-slot Kit
AF465A
UPS Management
AF464A
Page 16
QuickSpecs
HPE Line Interactive Single Phase UPS
Warranty and Care Pack
Warranty
When you need it, use outstanding HPE support services for your whole data center environment. With
HPE Pointnext operational services, have the security of knowing that your HPE UPS will be covered at
the same service level and coverage period as your HPE server. HPE UPSs are backed by a 3-year
limited warranty, with the first year including parts and labor. Also, standard on all HPE UPS units is our
exclusive 30-day Battery Pre-Failure Warranty, which ensures that when customers receive notification
from HPE Power Manager Software that the battery may fail, the battery is replaced free of charge
under the warranty. This warranty is offered worldwide.
NOTE: $250,000 Computer/Load Protection Guarantee is also provided (applicable in North America
only).
The HPE UPS is covered by a three year warranty, with the first year including parts and labor. Also,
standard on all HPE UPS units, is our exclusive Battery Pre-Failure Warning, which extends the
advantage of a HPE three-year, limited warranty by applying it to the battery before it actually fails. This
warranty is offered worldwide. Specifically, the Battery Pre-Failure Warning ensures that when customers
receive notification from HPE Power Management Software that the battery may fail, the battery is
replaced free of charge under the warranty.
NOTE: $250,000 Computer/Load Protection Guarantee is also provided in North America, in addition
to the HPE three year, limited warranty.
Warranty Upgrade Options:
• Response - Upgrade on-site response from next business day to same day 4-hours
• Coverage - Extend hours of coverage from 5 days x 9 hours to 7 days x 24 hours
• Duration - Select duration of coverage for a minimum period of 1 year or multiple years
Service and Support
HPE Technology Services
HPE Technology Services offers you consultants and support experts to solve your most complex
infrastructure problems. We help keep your business running, boost availability and avoid downtime.
Protect your business beyond warranty with HPE Pointnext operational services
When you buy HPE Options, it's also a good time to think about what level of service you may need.
HPE Pointnext operational services provide total care and support expertise with committed response
choices designed to meet your IT and business need.
Insight Remote Support Delivers secure remote monitoring and support for Hewlett Packard Enterprise servers and storage,
24x7 at no additional cost. Available as part of HPE Warranty, Care Pack and Service Contract offers.
Parts and materials
Hewlett Packard Enterprise will provide HPE-supported replacement parts and materials necessary to
maintain the covered hardware product in operating condition, including parts and materials for
available and recommended engineering improvements.
Parts and components that have reached their maximum supported lifetime and/or the maximum usage
limitations as set forth in the manufacturer's operating manual, product QuickSpecs, or the technical
product data sheet will not be provided, repaired, or replaced as part of these services.
The defective media retention service feature option applies only to Disk or eligible SSD/Flash Drives
replaced by HPE due to malfunction.
Coverage
For ProLiant servers and storage systems, this service covers HPE-branded hardware options qualified
for the server, purchased at the same time or afterward, internal to the enclosure, as well as external
monitors up to 22" and tower UPS products; these items will be covered at the same service level and for
the same coverage period as the server unless the maximum supported lifetime and/or the maximum
usage limitation has been exceeded. Coverage of the UPS battery is not included; standard warranty
terms and conditions apply.
Page 17
QuickSpecs
HPE Line Interactive Single Phase UPS
Warranty and Care Pack
The defective media retention service feature option applies only to Disk or eligible SSD/Flash Drives
replaced by HPE due to malfunction. It does not apply to any exchange of Disk or SSD/Flash Drives that
have not failed. SSD/Flash Drives that are specified by HPE as consumable parts and/or that have
exceeded maximum supported lifetime and/or the maximum usage limit as set forth in the
manufacturer's operating manual or the technical data sheet are not eligible for the defective media
retention service feature option.
For more information
To learn more on services for HPE ESSN Options, please contact your Hewlett Packard Enterprise sales
representative or Hewlett Packard Enterprise Authorized Channel Partner. Or
visit: https://www.hpe.com/us/en/support.html
or https://www.hpe.com/us/en/services/operational.html
Recommended HPE Pointnext operational services for optimal satisfaction with your HPE product
Recommended Services 3-Year HPE 24x7 4 hour Response, Hardware Support Onsite Service
Provides you with rapid remote support and if required a Hewlett Packard Enterprise Authorized
representative who will arrive on site any time and day of the year to begin hardware maintenance
service within 4 hours of the service request being logged.
HPE ProLiant Server Hardware Installation
Provides for the basic hardware installation of Hewlett Packard Enterprise branded servers, storage
devices and networking options to assist you in bringing your new hardware into operation in a timely
and professional manner
3-Year HPE 6 hour Hardware Support Onsite Call-to-Repair Service
Provides an IT manager with a team of support specialists who will quickly begin troubleshooting the
system to help return the hardware to operating condition within 6 hours of the initial service request to
the HPE Global Solution Center
HPE Proactive Select Service
Provides a flexible way to purchase HPE best-in-class consultancy and technical services. You can buy
Proactive Select Service Credits when you purchase your hardware and then use the credits over the
next 12 months.
HPE Pointnext
operational services
HPE Install Universal Power Supply 3KVA to Below 6KVA Service
HPE Install Universal Power Supply Less Than 3KVA Service
U4693E
U4690E
Page 18
QuickSpecs
HPE Line Interactive Single Phase UPS
HPE Model Matrix
HPE T750 G4 UPS Model
Part Number
Operating Voltage Power Out (VA/Watts) Input Connection
Settings
110V to 120V
750VA/525W
Attached NEMA 5-15
100V- Japan
750VA/500W
Plug type power cord,
16AWG
100V- Japan
750VA/500W
220V/230V/240V
750VA/525W
C14 Inlet ( For
detachable country
specific power cord
J2P85A
(North America/Japan)
J2P88A
International model
Output Connection
6 – NEMA 5-15
receptacles
6 – IEC C13 receptacles
HPE T1000 G4 UPS Model
Part Number
J2P86A NA/JP
J2P89A INTL
Operating Voltage Power Out (VA/Watts) Input Connection
Settings
100V (Japan) to 110V
1000VA/680W
Attached Nema 5-15
120V
1000VA/700W
Plug type power cord,
16AWG
220V/230V/240V
1000VA/700W
C14 Inlet ( For
detachable country
specific power cord
Output Connection
8 – Nema 5-15
receptacles
8 – IEC C13 receptacles
HPE T1500 G4 UPS Model
Part Number
Operating Voltage Power Out (VA/Watts) Input Connection
Settings
100V Japan
1200VA/980W
Attached Nema 5-15
110V
1325VA/994W
Plug type power cord,
120V
1440VA/1080W
14AWG
220V/230V/240V
1500VA/1050W
C14 Inlet ( For
detachable country
specific power cord
J2P87A NA/JP
J2P90A INTL
Output Connection
8 – Nema 5-15
receptacles
8 – IEC C13 receptacles
HPE R1500 G4 UPS Models
Part Number
Operating Voltage
Settings
Power Out
(VA/Watts)
Input Connection
Output Connection
120V to 125V
100V
100V
120V to 125V
1440/1100
1200/900
1200/900
1440/1100
NEMA 5-15P
5- Nema 5-15R
receptacles
5- Nema 5-15R
5-Nema 5-15R
220V/230V/240V
200V to 208V
1550/1100
1395/990
Operating Voltage
Settings
120V to 125V
100V
Power Out
(VA/Watts)
1920/1920
1500/1400
Low-Voltage Models
J2Q99A NA
J2R05A JP/TWN
High Voltage Model
J2R03A INTL
NEMA 5-15P
Nema 5-15P With
Taiwan approval
C14 inlet (for
detachable country
specific power cord
NOTE: Voltage is user selectable via LCD Front Display Panel
6- IEC 320-C13
receptacles
HPE R/T2200 G4 UPS
Part Number
J2R00A NA/JP
Input Connection
Output Connection
Nema 5-20P 20A 3m
cord
8 –Nema 5-20
Receptacles
HPE R/T3000 G4 UPS Models
Part Number
Operating Voltage
Settings
Power Out
(VA/Watts)
Input Connection
Output Connection
Page 19
QuickSpecs
HPE Line Interactive Single Phase UPS
HPE Model Matrix
J2R01A LV NA/JP
120V1 to 125V
100V
2880/2700
1500/1400
J2R02A HV NA/JP
208V1 to 240V
200V
3000/2700
2490/2241
J2R04A HV INTL
208V to 240V (230V1 )
3000/
2700
2490/2241
200V
L5-30P, 2.4m cord
LS1-LS42: 6x NEMA 5-20
outlets,
LS53: 1X NEMA L5-30
receptacle
L6-20P, 2.4m cord
LS1-LS32:8xIEC C13
LS53: 1x IEC C-19 (16A
outlet)
Detachable IEC C-20
LS1-LS32: 8x IEC C13
inlet plug for attaching LS53: 1x IEC C-19 (16A
country specific power
outlet)
cord
Factory default setting.
LS1 thru LS4 = Load Segment 1 thru 4 (or less depending on unit)
3
LS5 = Load Segment 5
1
2
HPE R5000 and R7000 UPS Models
Part Number
AF462A
AF460A
Operating Voltage
Settings
200/208*
200/208*, 220,
230, 240
Power Out
(VA/Watts)
7200VA/7200W
5000/4500
Input Connection
Output Connection
Hubble CS8265C, 3m LS1: 15A CB - 3 x C19 +
cord
1 x L6-30R
LS2: 15A CB - 3 x C19 +
1 x L6-30R
L6-30P, 3m cord
LS1: 15A CB - 2 x C19 +
2 x C13
LS2: 15A CB - 2 x C19 +
2 x C13
Plus one pigtailed
receptacle (LS1)
1 x L6-30R
HPE R/T2200 G4 UPS
Part Number
J2R00A NA/JP
Operating Voltage
Settings
120V to 125V
100V
Power Out
(VA/Watts)
1920/1920
1500/1400
Input Connection
Output Connection
Nema 5-20P 20A 3m
cord
8 –Nema 5-20
Receptacles
HPE R/T3000 G4 UPS Models
Part Number
Operating Voltage
Settings
120V1 to 125V
100V
Power Out
(VA/Watts)
2880/2700
1500/1400
J2R02A HV NA/JP
208V1 to 240V
200V
3000/2700
2490/2241
J2R04A HV INTL
208V to 240V (230V1 )
3000/
2700
2490/2241
J2R01A LV NA/JP
200V
Input Connection
Output Connection
L5-30P, 2.4m cord
LS1-LS42: 6x NEMA 5-20
outlets,
LS53: 1X NEMA L5-30
receptacle
L6-20P, 2.4m cord
LS1-LS32:8xIEC C13
LS53: 1x IEC C-19 (16A
outlet)
Detachable IEC C-20
LS1-LS32: 8x IEC C13
inlet plug for attaching LS53: 1x IEC C-19 (16A
country specific power
outlet)
cord
Factory default setting.
LS1 thru LS4 = Load Segment 1 thru 4 (or less depending on unit)
3
LS5 = Load Segment 5
1
2
Page 20
QuickSpecs
HPE Line Interactive Single Phase UPS
Estimated Backup Times
Battery runtimes are approximate and may vary with equipment, configuration, battery age, temperature, etc.
Tower UPS Models
Load
(Percent)
Load
(Watts)
Estimated battery runtime at 100%
battery charge
(Minutes)
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
53W
105W
158W
210W
263W
315W
368W
420W
473W
525W
68
37
21
16
15
10
9
7
7
6
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
70W
140W
210W
280W
350W
420W
490W
560W
630W
700W
65
32
21
16
12
10
9
8
7
6
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
108W
216W
324W
432W
540W
648W
756W
864W
972W
1080W
80
36
23
16
13
10
9
7
7
6
T750 UPS
T1000 UPS
T1500 UPS
Rack UPS Models
R1500 G4 UPS
Page 21
QuickSpecs
HPE Line Interactive Single Phase UPS
Estimated Backup Times
Load
(Percent)
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
Load
(Watts)
109W
219W
328W
438W
547W
656W
766W
875W
985W
1094W
Minutes of Back up time
97
39
23
16
12
10
8
7
6
5
Estimated Runtime with Extended Runtime Module (ERM)
R/T2200 G4 UPS
Load
(Percent)
191W (10%)
382W (20%)
573W (30%)
764W (40%)
956W (50%)
1147W (60%)
1338W (70%)
1529W (80%)
1720W (90%)
1911W (100%)
With internal batteries
(Minutes)
80
30
17
12
9
7
5
4
4
3
With One ERMs
(Minutes)
287
123
75
53
40
32
27
23
20
17
With Two ERMs
(Minutes)
491
218
135
97
74
60
50
43
37
33
With Three ERMs
(Minutes)
725
311
189
133
101
81
67
57
49
44
With Four ERMs
(Minutes)
898
406
255
184
142
115
97
83
73
64
With One ERMs
(Minutes)
259
122
78
57
45
37
31
27
24
21
With Two ERMs
(Minutes)
457
219
143
105
83
68
58
50
45
40
With Three ERMs
(Minutes)
655
317
207
153
121
100
85
74
65
59
With Four ERMs
(Minutes)
854
414
271
201
159
132
112
97
86
77
R/T3000 G4 UPS High Voltage
Load
(Percent)
270W (10%)
540W (20%)
810W (30%)
1080W (40%)
1350W (50%)
1620W (60%)
1890W (70%)
2160W (80%)
2430W (90%)
2700W (100%)
With internal batteries
(Minutes)
83
31
18
12
9
7
5
4
4
3
Page 22
QuickSpecs
HPE Line Interactive Single Phase UPS
Estimated Backup Times
R/T3000 G4 UPS Low Voltage
Load
(Percent)
270W (10%)
540W (20%)
810W (30%)
1080W (40%)
1350W (50%)
1620W (60%)
1890W (70%)
2160W (80%)
2430W (90%)
2700W (100%)
With internal batteries
(Minutes)
61
28
17
12
10
8
7
6
5
4
With One ERMs
(Minutes)
281
127
79
57
44
36
30
26
22
20
With Two ERMs
(Minutes)
475
219
140
101
79
65
54
47
41
37
With Three ERMs
(Minutes)
665
311
200
146
114
93
79
68
60
53
With Four ERMs
(Minutes)
860
405
260
190
149
122
104
90
79
70
R5000 UPS
Load
With internal batteries
With One ERM (Minutes)
With Four ERMs (Minutes)
(Percent*)
(Minutes)
450W (10%)
87
206
755
900W (20%)
36
99
349
1350W (30%)
22
64
222
1800W (40%)
15
47
162
2250W (50%)
12
37
126
2700W (60%)
9
31
103
3150W (70%)
8
26
87
3600W (80%)
6
23
75
4050W (90%)
6
20
66
4500W (100%)
5
18
58
NOTE: Backup times are estimated for typical applications. Actual performance will depend on load and battery conditions.
R7000 UPS INTL
Load
With internal batteries
With One ERM (Minutes)
With Four ERMs (Minutes)
(Percent*)
(Minutes)
650W (10%)
185
282
834
1300W (20%)
62
118
357
1950W (30%)
33
70
218
2600W (40%)
21
49
153
3250W (50%)
15
37
117
3900W (60%)
11
29
93
4550W (70%)
9
24
77
5200W (80%)
7
20
66
5850W (90%)
6
18
57
6500W (100%)
5
15
50
NOTE: Backup times are estimated for typical applications. Actual performance will depend on load and battery conditions.
Page 23
QuickSpecs
HPE Line Interactive Single Phase UPS
Estimated Backup Times
R7000 UPS NA/JP
Load
With internal batteries
With One ERM (Minutes)
With Four ERMs (Minutes)
(Percent*)
(Minutes)
720W (10%)
160
237
736
1440W (20%)
53
100
309
2160W (30%)
28
60
186
2880W (40%)
18
42
130
3600W (50%)
12
32
98
4320W (60%)
9
25
78
5040W (70%)
7
21
64
57600W (80%)
6
18
54
6480W (90%)
5
15
47
7200W (100%)
4
13
41
NOTE: Backup times are estimated for typical applications. Actual performance will depend on load and battery conditions.
Page 24
QuickSpecs
HPE Line Interactive Single Phase UPS
Estimated Backup Times
Rack/Tower UPS Models
(Minutes)
With One
Extended
Runtime
Module
(Minutes)
With Two
Extended
Runtime
Modules
(Minutes)
With Three
Extended
Runtime
Modules
(Minutes)
With Four
Extended
Runtime
Modules
(Minutes)
384W 20%
45
142
256
346
448
960W 50%
15
55
99
110
144
1536W 80%
7
34
60
53
78
1920W 100%
5
26
47
36
57
540W 20%
40
125
225
349
452
1350W 50%
12
50
99
107
140
2160W 80%
6
30
60
67
88
2700W 100%
4
24
47
52
68
540W 20%
45
142
256
321
417
1350W 50%
15
55
99
115
152
2160W 80%
7
34
60
72
95
2700W 100%
5
26
47
60
79
Load (Percent*)
Estimates
battery
runtime
R/T2200 G4 UPS
R/T3000 G4 Low Voltage UPS
R/T3000 G4 High Voltage UPS
Environment-friendly
Products and Approach
- End-of-life
Management and
Recycling
Hewlett Packard Enterprise offers end-of-life product return, trade-in, and recycling programs, in
many geographic areas, for our products. Products returned to Hewlett Packard Enterprise will be
recycled, recovered or disposed of in a responsible manner.
The EU WEEE Directive (2012/19/EU) requires manufacturers to provide treatment information for
each product type for use by treatment facilities. This information (product disassembly instructions) is
posted on the Hewlett Packard Enterprise web site. These instructions may be used by recyclers
and other WEEE treatment facilities as well as Hewlett Packard Enterprise OEM customers who
integrate and re-sell Hewlett Packard Enterprise equipment.
Page 25
QuickSpecs
HPE Line Interactive Single Phase UPS
Summary of Changes
Date
05-Mar-2018
23-Oct-2017
Version History
Version 15
Version 14
Action
Changed
Changed
21-Feb-2017
26-Oct-2016
26-Sep-2016
Version 13
Version 12
Version 11
Changed
Changed
Changed
28-Sep-2015
Version 10
Added
Changed
Removed
Changed
04-Jun-2015
Version 9
30-Mar-2015
09-Feb-2015
Version 8
Version 7
Removed
Changed
Added
Changed
08-Feb-2013
24-Aug-2012
15-Aug-2012
09-Jan-2012
Version 6
Version 5
Version 4
Version 3
Changed
Changed
Removed
Changed
20-Jul-2011
20-Jun-2011
Version 2
Version 1
Changed
New
Description of Change
Overview was updated
Care Pack naming and Service and Support- Parts and
Materials updated.
Estimated Backup Times section was updated.
Version reverted.
Overview and Models, Key Features, Tower UPS Compatibility,
and Product Specifications were revised.
Added new Rack UPS Models to the Overview and Models
section.
Towers G4 UPS Specifications table was added to Tower UPS
Specifications.
HPE R/T2200 and R/T3000 Tower Uninterruptible Power
System (UPS) were added to HPE Rack/Tower UPS
Specifications.
Overview and Models, Tower UPS Features, HPE Rack UPS
Specifications were revised.
Tower UPS Front Panel was removed from QuickSpecs.
Overview and Models, HPE Tower UPS Specifications, HPE
Rack UPS Specifications, Related Options, HPE Model Matrix,
and Estimated Backup Times sections were revised.
Obsolete SKUs were removed from the QuickSpecs.
Changes made throughout the entire QuickSpecs.
Added G4 models.
Changed name to HPE Line Interactive Single Phase
Uninterruptible Power Systems (UPS).
Consolidated Tower, Rack/Tower, and Rack Models into one
single QuickSpecs.
Changed G3 to G2 in the Intelligent Manageability section.
Change made in Models section.
Removed inactive links.
Revised an inactive link in the Compatibility section of Standard
Features.
Descriptions for the Models section were updated.
New QuickSpecs.
Sign up for updates
© Copyright 2018 Hewlett Packard Enterprise Development LP. The information contained herein is
subject to change without notice. The only warranties for Hewlett Packard Enterprise products and
services are set forth in the express warranty statements accompanying such products and services.
Nothing herein should be construed as constituting an additional warranty. Hewlett Packard Enterprise
shall not be liable for technical or editorial errors or omissions contained herein.
c04154342 - 14058 - Worldwide - V15 - 5-March-2018