SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS March 2013 No. OCS25 TECHNICAL DATA BOOK R410A INVERTER <Indoor unit> [Model names] SLZ-KA·VAL SLZ-KA·VAL2 SLZ-KA·VAQ SLZ-KA·VAQ2 SEZ-KD·VAL SEZ-KD·VAQ PLA-RP·BA PCA-RP·KAQ PEAD-RP·JAQ PEAD-RP·JALQ <Outdoor unit> [Model names] SUZ-KA25/35/50/60/71VA3 CONTENTS 1. REFERENCE SERVICE MANUAL ............................................. 2 2. SPECIFICATIONS....................................................................... 3 3. OUTLINES AND DIMENSIONS .................................................. 8 4. WIRING DIAGRAM ................................................................... 20 5. REFRIGERANT SYSTEM DIAGRAM ...................................... 29 6. PERFORMANCE CURVES ...................................................... 32 7. APPLICABLE EXTENSION PIPE FOR EACH MODEL .......... 34 8. AIR FLOW DATA ...................................................................... 35 9. NOISE CRITERION CURVES .................................................. 50 10. OPTIONAL PARTS ................................................................... 63 kW Model 1 REFERENCE SERVICE MANUAL For information on service, please refer to the service manual as follows. 1-1. Indoor Unit Model name Service Ref. Service Manual No. SLZ-KA25VAL2 SLZ-KA35/50VAL SLZ-KA25VAL2.TH SLZ-KA35/50VALR3.TH OC320 SLZ-KA25VAQ2 SLZ-KA35/50VAQ SLZ-KA25VAQ2.TH SLZ-KA35/50VAQR2.TH OCH493 OCB493 SEZ-KD25/35/50/60/71VAL SEZ-KD25/35/50/60/71VALR2.TH HWE07110 BWE10205 SEZ-KD25/35/50/60/71VAQ SEZ-KD25/35/50/60/71VAQR2.TH HWE10080 BWE10204 PLA-RP35/50/60/71BAR3.UK OCH412 OCB412 PLA-RP35/50/60/71BAR1 OCH416 OCB416 PCA-RP50/60/71KAQ PCA-RP50/60/71KAQ OCH491 OCB491 PEAD-RP35/50/60/71JAQ PEAD-RP35/50/60/71JALQ PEAD-RP35/50/60/71JAQR1.UK PEAD-RP35/50/60/71JALQR1.UK PLA-RP35/50/60/71BA HWE10090 BWE01208 1-2. Outdoor Unit Model name Service Ref. Service Manual No. SUZ-KA25/35/50/60/71VA3 SUZ-KA25/35/50/60/71VA3.TH OCH530 OCB530 (Note) When you connect P series indoor units with SUZ, always make sure to follow the piping size of SUZ. Never use bigger sized pipings in order to ensure not only the system performance but also for your safety. OCS25 2 2 SPECIFICATIONS 2-1. CEILING CASSETTE TYPE Model name Indoor unit Cooling Outdoor unit Capacity Heating Total input EER Energy label class SHF Capacity Power supply Indoor unit Total input COP Energy label class Booster heater Phase Cycle Voltage Breaker size Air flow (Low - Medium - High) External static pressure Sound level (Low - Medium - High) External finish (Panel) Dimension Unit(Panel) Weight Unit (Panel) Field drain pipe O.D. Outdoor unit Air flow at cooling (Rated) [High] Air flow at heating (Rated) [High] Sound level at cooling (Rated) Sound level at heating (Rated) External finish Dimension Weight Refrigerant pipe size Gas side O.D. Liquid side O.D. Refrigerant pipe length NOTE: Height difference Length SLZ-KA25VAL2 SLZ-KA25VAQ2 SUZ-KA25VA3 8,900 2.6(0.9 - 3.2) 0.706 3.68 A 0.86 9,600 2.8(0.9 - 4.5) 0.744 3.76 A — 1 50 230 10 8 - 9 - 11 280 - 320 - 390 0 29 - 33 - 38 SLZ-KA35VAL SLZ-KA35VAQ SUZ-KA35VA3 11,900 3.5(1.0 - 3.9) 1.041 3.36 A 0.77 13,300 3.9(0.9 - 5.0) 1.123 3.47 A — 1 50 230 10 8 - 9 - 11 280 - 320 - 390 0 29 - 33 - 38 SLZ-KA50VAL SLZ-KA50VAQ SUZ-KA50VA3 15,700 4.6(1.1 - 5.2) 1.528 3.01 B 0.68 17,100 5.0(0.9 - 6.5) 1.552 3.22 C — 1 50 230 20 8 - 9 - 11 280 - 320 - 390 0 30 - 34 - 39 W : mm D : mm H : mm W : inch D : inch H : inch kg lbs mm inch CMM CFM CMM CFM dB(A) 30.1 1,060 35.1 1,240 47 White Munsell 6.4Y 8.9/0.4 570(650) 570(650) 235(20) 22 - 7/16(25 - 9/16) 22 - 7/16(25 - 9/16) 9-1/4(8-3/16) 16.5(3) 36(7) 32 1 - 1/4 30.1 1,060 35.1 1,240 49 47.8 1,690 46.3 1,630 52 dB(A) 48 50 52 W : mm D : mm H : mm W : inch D : inch H : inch kg lbs mm inch mm inch m m 800 285 550 31 - 1/2 11 - 1/4 21 - 5/8 30 66 9.52 3/8 6.35 1/4 Max. 12 Max. 20 Ivory Munsell 3.0Y 7.8/1.1 800 285 550 31 - 1/2 11 - 1/4 21 - 5/8 35 77 9.52 3/8 6.35 1/4 Max. 12 Max. 20 840 330 880 33 - 1/16 13 34 - 5/8 54 119 12.7 1/2 6.35 1/4 Max. 30 Max. 30 Btu/h kW kW Btu/h kW kW kW : Hz V A CMM CFM Pa dB(A) 1. Rating conditions (ISO T1) Cooling Indoor : D.B. 27 (80°F) W.B. 19 (66°F) Heating Indoor : D.B. 20 (68°F) Refrigerant piping length (one way) : 5m (16ft.) 2. Guaranteed operating range Indoor Upper Lower Upper Heating Lower Cooling OCS25 limit limit limit limit 32°C D.B. , 23°C W.B. 21°C D.B. , 15°C W.B. 27°C D.B. 20°C D.B. Outdoor : D.B. 35 (95°F) W.B. 24 (75°F) Outdoor : D.B. 7 (45°F) W.B. 6 (43°F) Outdoor KA25, KA35, KA50 46°C D.B. -10°C D.B. 24°C D.B. , 18°C W.B. -10°C D.B. ,-11°C W.B. 3 3. Guaranteed voltage 198~264V, 50Hz 4. Above data are based on the indicated voltage. Indoor unit Single phase, 230V 50Hz Outdoor unit Single phase, 230V 50Hz Model name Cooling Indoor unit Outdoor unit Capacity Heating Total input EER Energy label class SHF Capacity Power supply Indoor unit Outdoor unit Refrigerant pipe size Refrigerant pipe length NOTE: Btu/h kW kW Btu/h kW kW Total input COP Energy label class Booster heater kW Phase : Cycle Hz Voltage V Breaker size A Air flow CMM (Low-Medium2-Medium1-High) CFM External static pressure Pa Sound level dB(A) (Low-Medium2-Medium1-High) External finish (Panel) Dimension W : mm Unit (Panel) D : mm H : mm W : inch D : inch H : inch Weight kg Unit (Panel) lbs Field drain pipe O.D. mm inch Air flow at cooling CMM CFM (Rated) [High] Air flow at heating CMM CFM (Rated) [High] Sound level at cooling dB(A) (Rated) Sound level at heating dB(A) (Rated) External finish Dimension W : mm D : mm H : mm W : inch D : inch H : inch Weight kg lbs Gas side O.D. mm inch Liquid side O.D. mm inch Height difference m Length m PLA-RP35BA PLA-RP50BA PLA-RP60BA PLA-RP71BA SUZ-KA35VA3 SUZ-KA50VA3 SUZ-KA60VA3 SUZ-KA71VA3 12,300 18,800 20,800 24,200 3.6(1.0 - 3.9) 5.5(1.1 - 5.6) 6.1(1.1 - 6.3) 7.1(0.9 - 8.1) 1.090 1.708 1.871 2.100 3.30 3.22 3.26 3.38 A A A A 0.84 0.81 0.76 0.73 12,300 20,500 23,500 27,300 3.6(0.9 - 5.0) 6.0(0.9 - 7.2) 6.9(0.9 - 8.0) 8.0(0.9 - 10.2) 0.939 1.749 1.971 2.247 3.83 3.43 3.50 3.56 A B B B — — — — 1 1 1 1 50 50 50 50 230 230 230 230 10 20 20 20 11 - 12 - 13 - 15 12 - 14 - 16 - 18 12 - 14 - 16 - 18 14 - 16 - 18 - 21 390 - 425 - 460 - 530 425 - 495 - 565 - 635 425 - 495 - 565 - 635 495 - 565 - 635 - 740 0 0 0 0 27 - 28 - 29 - 31 28 - 29 - 31 - 32 28 - 29 - 31 - 32 28 - 30 - 32 - 34 White Munsell 6.4Y 8.9/0.4 840 (950) 840 (950) 258 (35) 33 - 1/16 (37 - 3/8) 33 - 1/16 (37 - 3/8) 10 - 3/16 (1 - 3/8) 22 (6) 49 (13) 32 1 - 1/4 Upper Lower Upper Heating Lower Cooling OCS25 limit limit limit limit 32°C D.B. , 23°C W.B. 21°C D.B. , 15°C W.B. 27°C D.B. 20°C D.B. 30.1 1,060 35.1 1,240 49 47.8 1,690 46.3 1,630 52 58.2 2,060 49.2 1,740 55 57.1 2,020 48.2 1,700 55 50 52 55 55 Ivory Munsell 3.0Y 7.8/1.1 840 840 330 330 880 880 33 - 1/16 33 - 1/16 13 13 34 - 5/8 34 - 5/8 54 50 119 110 12.7 15.88 1/2 5/8 6.35 6.35 1/4 1/4 Max. 30 Max. 30 Max. 30 Max. 30 800 285 550 31 - 1/2 11 - 1/4 21 - 5/8 35 77 9.52 3/8 6.35 1/4 Max. 12 Max. 20 1. Rating conditions (ISO T1) Cooling Indoor : D.B. 27 (80°F) W.B. 19 (66°F) Heating Indoor : D.B. 20 (68°F) Refrigerant piping length (one way) : 5m (16ft.) 2. Guaranteed operating range Indoor 23 (6) 51 (13) 840 330 880 33 - 1/16 13 34 - 5/8 53 117 15.88 5/8 9.52 3/8 Max. 30 Max. 30 Outdoor : D.B. 35 (95°F) W.B. 24 (75°F) Outdoor : D.B. 7 (45°F) W.B. 6 (43°F) Outdoor KA50, KA60, KA71 KA35 46°C D.B. 43°C D.B. -10°C D.B. -15°C D.B. 24°C D.B. , 18°C W.B. -10°C D.B. ,-11°C W.B. 4 3. Guaranteed voltage 198~264V, 50Hz 4. Above data are based on the indicated voltage. Indoor unit Single phase, 230V 50Hz Outdoor unit Single phase, 230V 50Hz 2-2. CEILING-SUSPENDED TYPE Model name Indoor unit Outdoor unit Capacity Cooling Total input Btu/h kW kW EER Energy label class SHF Capacity Heating Total input COP Energy label class Booster heater Phase Cycle Voltage Breaker size Air flow (Low-Medium2-Medium1-High) Power supply Indoor unit External static pressure Sound level (Low-Medium2-Medium1-High) External finish Dimension Weight Field drain pipe O.D. Outdoor unit Air flow at cooling (Rated) Air flow at heating (Rated) Sound level at cooling (Rated) Sound level at heating (Rated) External finish Dimension Weight Refrigerant pipe size Gas side O.D. Liquid side O.D. Refrigerant pipe length NOTE: Height difference Length Btu/h kW kW kW : Hz V A CMM CFM Pa dB(A) Upper limit Lower limit Upper limit Heating Lower limit OCS25 PCA-RP60KAQ SUZ-KA60VA3 19,400 5.7(1.1-6.3) 1.770 3.22 A 0.81 23,500 6.9(0.9-8.0) 2.017 3.42 B — 1 50 230 20 15 - 16 - 17 - 19 530 - 565 - 600 - 670 0 33 - 35 - 37 - 40 PCA-RP71KAQ SUZ-KA71VA3 24,200 7.1(0.9-8.1) 2.057 3.45 A 0.76 27,000 7.9(0.9-10.2) 2.182 3.62 A — 1 50 230 20 16 - 17 - 18 - 20 565 - 600 - 635 - 705 0 35 - 37 - 39 - 41 960 680 230 37 - 13/16 26 - 3/4 9 - 1/16 25 55 26 1 White Munsell 6.4Y 8.9/0.4 1,280 680 230 50 - 3/8 26 - 34 9 - 1/16 32 71 26 1 1,280 680 230 50 - 3/8 26 - 3/4 9 - 1/16 32 71 26 1 W : mm D : mm H : mm W : inch D : inch H : inch kg lbs mm inch CMM CFM CMM CFM dB(A) 47.8 1,690 46.3 1,630 57.1 2,020 52 58.2 2,060 49.2 1,740 55 dB(A) 52 55 55 W : mm D : mm H : mm W : inch D : inch H : inch kg 840 330 880 33 - 1/16 13 lbs mm inch mm inch m m 1. Rating conditions (ISO T1) Cooling Indoor : D.B. 27 (80°F) W.B. 19 (66°F) Heating Indoor : D.B. 20 (68°F) Refrigerant piping length (one way) : 5m (16ft.) 2. Guaranteed operating range Cooling PCA-RP50KAQ SUZ-KA50VA3 17,100 5.0(1.1-5.6) 1.661 3.01 B 0.79 18,800 5.5(0.9-6.6) 1.708 3.22 C — 1 50 230 20 10 - 11 - 13 - 15 355 - 390 - 460 - 530 0 32 - 34 - 37 - 40 Indoor 32°C D.B., 23°C W.B. 21°C D.B., 15°C W.B. 27°C D.B. 20°C D.B. Ivory Munsell 3.0Y 7.8/1.1 840 330 8 80 33 - 1/16 13 34 - 5/8 54 119 34 - 5/8 50 110 12.7 1/2 6.35 1/4 Max. 30 Max. 30 15.88 5/8 6.35 1/4 Max. 30 Max. 30 48.2 1,700 55 840 330 880 33 - 1/16 13 34 - 5/8 53 117 15.88 5/8 9.52 3/8 Max. 30 Max. 30 Outdoor : D.B. 35 (95°F) W.B. 24 (75°F) Outdoor : D.B. 7 (45°F) W.B. 6 (43°F) Outdoor 43°C D.B. -15°C D.B. 24°C D.B., 18°C W.B. -10°C D.B., -11°C W.B. 5 3. Guaranteed voltage 198~264V, 50Hz 4. Above data are based on the indicated voltage. Indoor unit Single phase, 230V 50Hz Outdoor unit Single phase, 230V 50Hz 2-3. CEILING-CONCEALED TYPE Model name Indoor unit Cooling Outdoor unit Capacity Heating Total input EER Energy label class SHF Capacity Btu/h kW kW Btu/h kW kW Total input COP Energy label class Booster heater kW Power supply Phase : Cycle Hz Voltage V Breaker size A Indoor unit Air flow CMM (Low - Medium - High) CFM External static pressure Pa Sound level dB(A) (Low - Medium - High) External finish Dimension W : mm D : mm H : mm W : inch D : inch H : inch Weight kg lbs mm Field drain pipe O.D. inch Outdoor unit Air flow at cooling CMM (Rated) CFM Air flow at heating CMM (Rated) CFM Sound level at cooling dB(A) (Rated) Sound level at heating dB(A) (Rated) External finish Dimension W : mm D : mm H : mm W : inch D : inch H : inch Weight kg lbs Refrigerant pipe size Gas side O.D. mm inch Liquid side O.D. mm inch Refrigerant pipe length Height difference m Length m NOTE: SEZ-KD25VAL SEZ-KD25VAQ SUZ-KA25VA3 8,500 2.5(0.9 - 3.2) 0.750 3.33 A 0.80 9,900 2.9(0.9 - 4.5) 0.838 3.46 B — 1 50 230 10 5.5 - 7.0 - 9.0 190 - 250 - 320 5 - 15 - 35 - 50 23 - 26 -30 SEZ-KD35VAL SEZ-KD35VAQ SUZ-KA35VA3 11,900 3.5(1.0 - 3.9) 1.032 3.39 A 0.76 13,000 3.8(0.9 - 5.0) 1.021 3.72 A — 1 50 230 10 7.0 - 9.0 - 11.0 250 - 320 - 390 5 - 15 - 35 - 50 23 - 28 -33 790 700 200 31 - 1/8 27 - 9/16 7 - 7/8 18 40 990 700 200 39 27 - 9/16 7 - 7/8 21 47 30.1 1,060 35.1 1,240 47 30.1 1,060 35.1 1,240 49 Galvanized sheets 990 700 200 39 27 - 9/16 7 - 7/8 23 51 32 1 - 9/32 47.8 1,690 46.3 1,630 52 48 50 800 285 550 31 - 1/2 11 - 1/4 21 - 5/8 30 66 9.52 3/8 6.35 1/4 Max. 12 Max. 20 800 285 550 31 - 1/2 11 - 1/4 21 - 5/8 35 77 9.52 3/8 6.35 1/4 Max. 12 Max. 20 1. Rating conditions (ISO T1) Cooling Indoor : D.B. 27 (80°F) W.B. 19 (66°F) Heating Indoor : D.B. 20 (68°F) Refrigerant piping length (one way) : 5m (16ft.) 2. Guaranteed operating range Indoor Upper Lower Upper Heating Lower Cooling OCS25 limit limit limit limit 32°C D.B. , 23°C W.B. 21°C D.B. , 15°C W.B. 27°C D.B. 20°C D.B. SEZ-KD50VAL SEZ-KD50VAQ SUZ-KA50VA3 17,400 5.1(1.1 - 5.6) 1.639 3.11 B 0.76 21,800 6.4(1.1 - 7.2) 1.807 3.54 B — 1 50 230 20 10.0 - 12.5 - 15.0 350 - 440 - 530 5 - 15 - 35 - 50 30 - 34 -37 SEZ-KD60VAL SEZ-KD60VAQ SUZ-KA60VA3 19,100 5.6(1.1 - 6.3) 1.860 3.01 B 0.79 25,200 7.4(0.9 - 8.0) 2.202 3.36 C — 1 50 230 20 12.0 - 15.0 - 18.0 420 - 530 - 640 5 - 15 - 35 - 50 30 - 34 -38 SEZ-KD71VAL SEZ-KD71VAQ SUZ-KA71VA3 24,200 7.1(0.9 - 8.3) 2.358 3.01 B 0.74 27,600 8.1(0.9 - 10.4) 2.268 3.57 B — 1 50 230 20 12.0 - 16.0 - 20.0 420 - 570 - 710 5 - 15 - 35 - 50 30 - 35 -40 1190 700 200 46 - 27/32 27 - 9/16 7 - 7/8 27 60 1190 700 200 46 - 27/32 27 - 9/16 7 - 7/8 27 60 58.2 2,060 49.2 1,740 55 57.1 2,020 48.2 1,700 55 52 55 55 Ivory Munsell 3.0Y 7.8/1.1 840 330 880 33 - 1/16 13 34 - 5/8 54 119 12.7 1/2 6.35 1/4 Max. 30 Max. 30 840 330 880 33 - 1/16 13 34 - 5/8 50 110 15.88 5/8 6.35 1/4 Max. 30 Max. 30 840 330 880 33 - 1/16 13 34 - 5/8 53 117 15.88 5/8 9.52 3/8 Max. 30 Max. 30 Outdoor : D.B. 35 (95°F) W.B. 24 (75°F) Outdoor : D.B. 7 (45°F) W.B. 6 (43°F) Outdoor KA25, KA35 KA50, KA60, KA71 46°C D.B. 43°C D.B. -15°C D.B. -10°C D.B. 24°C D.B. , 18°C W.B. -10°C D.B. ,-11°C W.B. 6 3. Guaranteed voltage 198~264V, 50Hz 4. Above data are based on the indicated voltage. Indoor unit Single phase, 230V 50Hz Outdoor unit Single phase, 230V 50Hz Model name Indoor unit Cooling Outdoor unit Capacity Heating Total input EER Energy label class SHF Capacity Total input COP Energy label class Booster heater Phase Cycle Voltage Breaker size Air flow (Low - High) External static pressure Sound level (Low - High) External finish Dimension Power supply Indoor unit Weight Field drain pipe O.D. Outdoor unit Air flow at cooling (Rated) Air flow at heating (Rated) Sound level at cooling (Rated) Sound level at heating (Rated) External finish Dimension Btu/h kW kW Btu/h kW kW kW : Hz V A CMM CFM Pa dB(A) PEAD-RP35JAQ PEAD-RP50JAQ PEAD-RP35JALQ PEAD-RP50JALQ SUZ-KA35VA3 SUZ-KA50VA3 12,300 16,700 3.6 (1.0-3.9) 4.9 (1.1-5.6) 1.058 (1.039) 1.521 (1.465) 3.40 (3.46) 3.22 (3.27) A A 0.85 0.85 12,300 20,100 3.6 (0.9-5.0) 5.9 (0.9-7.2) 0.975 1.620 3.69 3.64 A A — — 1 1 50 50 230 230 16 20 10 - 12 - 14 12 - 14.5 - 17 353 - 424 - 494 424 - 512 - 600 35/50/70/100/150 23 - 27 - 30 26 - 31 - 35 PEAD-RP60JAQ PEAD-RP71JAQ PEAD-RP60JALQ PEAD-RP71JALQ SUZ-KA71VA3 SUZ-KA60VA3 24,200 19,400 7.1 (0.9-8.1) 5.7 (1.1-6.3) 2.100 (2.068) 1.681 (1.656) 3.38 (3.41) 3.39 (3.43) A A 0.83 0.86 27,300 23,900 8.0 (0.9-10.2) 7.0 (0.9-8.0) 2.040 1.939 3.61 3.92 A A — — 1 1 50 50 230 230 20 20 17.5 - 21 - 25 14.5 - 18 - 21 618 - 742 - 883 512 - 636 - 742 35/50/70/100/150 26 - 30 - 34 25 - 29 - 33 Galvanized sheets 900 732 250 35 - 7/16 28 - 7/8 9 - 7/8 26 (25) 28 (27) 58 (56) 62 (60) Galvanized sheets 1,100 732 250 43 - 5/16 28 - 7/8 9 - 7/8 28 (27) 33 (32) 62 (60) 73 (71) W : mm D : mm H : mm W : inch D : inch H : inch kg lbs mm inch CMM CFM CMM CFM dB(A) 32 1 - 1/4 dB(A) 30.1 1,060 35.1 1,240 49 47.8 1,690 46.3 1,630 52 58.2 2,060 49.2 1,740 55 57.1 2,020 48.2 1,700 55 50 52 55 55 800 W : mm 285 D : mm 550 H : mm 31 - 1/2 W : inch 11 - 1/4 D : inch 21 - 5/8 H : inch 35 Weight kg 77 lbs 9.52 Refrigerant pipe size Gas side O.D. mm 3/8 inch 6.35 mm Liquid side O.D. 1/4 inch Max. 12 Refrigerant pipe length Height difference m Max. 20 Length m The values in the parentheses indicate the specification values for PEAD-RP·JALQ. NOTE: 1. Rating conditions (ISO T1) Cooling Indoor : D.B. 27 (80°F) W.B. 19 (66°F) Heating Indoor : D.B. 20 (68°F) Refrigerant piping length (one way) : 5m (16ft.) 2. Guaranteed operating range Indoor Upper Lower Upper Heating Lower Cooling OCS25 limit limit limit limit 32°C D.B. , 23°C W.B. 21°C D.B. , 15°C W.B. 27°C D.B. 20°C D.B. Ivory Munsell 3.0Y 7.8/1.1 840 840 330 330 880 880 33 - 1/16 33 - 1/16 13 13 34 - 5/8 34 - 5/8 54 50 119 110 12.7 15.88 1/2 5/8 6.35 6.35 1/4 1/4 Max. 30 Max. 30 Max. 30 Max. 30 840 330 880 33 - 1/16 13 34 - 5/8 53 117 15.88 5/8 9.52 3/8 Max. 30 Max. 30 Outdoor : D.B. 35 (95°F) W.B. 24 (75°F) Outdoor : D.B. 7 (45°F) W.B. 6 (43°F) Outdoor KA25, KA35 KA50, KA60, KA71 46°C D.B. 43°C D.B. -15°C D.B. -10°C D.B. 24°C D.B. , 18°C W.B. -10°C D.B. ,-11°C W.B. 7 3. Guaranteed voltage 198~264V, 50Hz 4. Above data are based on the indicated voltage. Indoor unit Single phase, 230V 50Hz Outdoor unit Single phase, 230V 50Hz W 100 25 420 Suspension bolt pitch Refrigerant pipe (liquid) Refrigerant pipe (gas) Emergency operation switch(cooling) Receiver Emergency operation switch(heating) MITSUBISHI ELECTRIC W 73.4 Cut out hole Fresh air intake 17 202 230 35 55 V/M V/M 377 Air intake hole Grille Terminal block (Case of Wired remote controller)Terminal block 650 301 Air outlet hole 15~37 199 352 335 576~620 Ceiling hole 570 530 Suspension bolt pitch V/M V/M Ceiling surface 15~37 Brand label Vane motor Air intake grille Auto vane Drain hole Grille Wiring entry Suspension bolt M10 or 3/8 (procure locally) Drain pipe VP-25 connection (O.D. W 32) KA50 KA35 KA25 Models W 9.52mm flared connection 3/8 inch W 6.35mm flared connection 1/4 inch W 12.7mm flared connection 1/2 inch W 9.52mm flared connection 3/8 inch W 6.35mm flared connection 1/4 inch W 6.35mm flared connection 1/4 inch Refrigerant pipe (gas) Refrigerant pipe (liquid) INDOOR UNIT SLZ-KA25VAL2 SLZ-KA25VAQ2 SLZ-KA35/50VAL SLZ-KA35/50VAQ DEFROST/STAND BY lamp Operation lamp (WIRELESS PANEL) Ceiling surface 118 3- W 2.8 hole Burring hole 66 121 Detail drawing of fresh air intake 12 0° 15~37 576~620 Ceiling hole 15~37 93 650 335 193 570 87 235 20 31 208 +5 27 0 57 56 38~58 55 35 Suspension bolt lower edge 301 Air outlet hole 8 377 Air intake hole 182 OCS25 0° 12 48 3 OUTLINES AND DIMENSIONS Unit : mm Unit : mm SEZ-KD25/35/50/60/71VAL SEZ-KD25/35/50/60/71VAQ 20 12 157.5 37 100 37 H 100×J=K 23 20 12 57 625 (Suspension bolt pitch) 49 Terminal block Terminal block (Indoor/outdoor connecting line) (Remote controller transmission line) 70 270 1 Refrigerant piping flare connection (gas) Drain pipe(O.D.W32)(Spontaneous draining) Access door 50 7 77 G Note2 Knockout hole W27 (Indoor/outdoor connecting line) 200 102 23 25 116 2×2-W2.9 Knockout hole W27 (Remote controller transmission line) Control box 100 150 (Duct) 700 677 23 10 Air filter Suspension bolt hole 4-14×30 Slot 170 2 Refrigerant piping flare connection (liquid) L-W2.9 90 10 2×E-W2.9 More than 10mm More than 20mm 25 20 30 88 100 100 Air inlet C A Air outlet B (Suspension bolt pitch) D (Duct) 100×(E-1)=F 88 15 50 50 ~1 50 45 0 0 00 45 n3 tha e r Mo Ceiling surface Access door Make the access door at the appointed position properly for service maintenance. Required space for service and maintenance Model A B C D SEZ-KD25VA(L)(Q) 700 752 798 660 SEZ-KD35VA(L)(Q) 900 952 998 860 SEZ-KD50VA(L)(Q) SEZ-KD60VA(L)(Q) 1100 1152 1198 1060 SEZ-KD71VA(L)(Q) E 7 F 600 G 800 H 660 J 5 K 500 L 16 9 800 1000 860 7 700 20 11 1000 1200 1060 9 900 24 1 Gas pipe 2 Liquid pipe W9.52 W12.7 W15.88 W6.35 W9.52 Note1.Use M10 screw for the suspension bolt (field supply). 2.Keep the service space for the maintenance at the bottom. 3.This chart indicates for SEZ-KD50VA(L)(Q) model, which has 3 fans. SEZ-KD25,35VA(L)(Q) models have 2 fans. SEZ-KD60,71VA(L)(Q) models have 4 fans. 4.In case an inlet duct is used, remove the air filter (supply with the unit), then install the filter (field supply) at suction side. OCS25 9 Unit : mm PLA-RP35BA PLA-RP50BA PLA-RP60BA PLA-RP71BA Ceiling hole 20~45 860~910 810 90 100 100 90 Cut out hole 620 860~910 Indoor power supply terminal block(Option part) Ceiling hole 167 + + 605 +35 -5 840 Branch duct hole Suspension bolt pitch Remote controller terminal block Indoor unit/Outdoor unit connecting terminal block 155 70° 160 (7.5) 100 Suspension bolt pitch 160 Detail connecting of branch duct(Both aspects) 20~45 Fresh air intake hole 130 20~45 Branch duct hole 350 :175 14-:2.8 Burring hole Burring hole pitch :150 Detail drawing of fresh air intake hole (7.5) 24 1 60 284 Drain pipe connected to VP-25 377 B A + 190 156 105 140 + Control wire entry Ceiling ) Cut out hole :100 + Ceiling In case of standard grille : PLP-6BA / PLP-6BAMD 35 Power supply wire, Indoor unit/Outdoor unit connecting wire entry 17 +50 50~70 170 Connect the attached drain socket. + + + + Suspension bolt lower edge ( Keep approximately 10 to 15mm space between unit ceiling and ceiling slab. 2 + Burring hole pitch :125 120° 120° 840 3-:2.8 158 160 Suspension bolt M10 or W3/8 Burring hole 20~45 187.5 160 D C 90 150 Cut out hole MITSUBISHI ELECTRIC Grille 597 Drain hole Drain pump clean hole and Drain emergency drainage hole M 597 Auto vane (Air outlet) switch<Cooling>and Emergency Up/Down switch<Up> Emergency operation switch<Heating>and Emergency Up/Down switch<Down> Air intake hole 500 Air outlet hole 950 M In case of Auto-Grille : PLP-6BAJ In case of wireless remote controller : PLP-6BALM Auto Grille Air intake grille up/down discharge Emergency operation Air intake grille Receiver M 83 M 83 36 500 36 Indoor unit 1500mm or more 1000mm or more Indoor unit 3000mm or more Obstacle Air intake grille Vane motor 950 Grille 1800mm or more from floor For high attachment Note : 1. Please choose the Grille from a standard grille, auto-grille. 2. As for drain pipe, please use VP-25(O.D. :32 PVC TUBE). Drain pump is included. Max. lifting height is 850mm from the ceiling. 3. As for suspension bolt, please use M10 or W3/8. (Procured at local site) 4. Electrical box may be removed for the service purpose. Make sure to slack the electrical wire little bit for control/ power wires connection. 5. The height of the indoor unit is able to be adjusted with the grille attached. 6. For the installation of the optional high efficiency filter or optional multi-functional casement. 1) Requires E or more space between transom and ceiling for the installation. 2) Add 135 mm to the dimensions + marked on the figure. 3) The optional high efficiency filter must be used jointly with optional multi-functional casement. 7. When installing the branch ducts, be sure to insulate adequately. Otherwise condensation and dripping may occur. (It becomes the cause of dew drops/water dew.) 8. As for necessary installation/service space, please refer to the left figure. Models Floor PLA-RP35/50BA PLA-RP60BA PLA-RP71BA OCS25 DEFROST/STAND BY lamp Operation lamp Air outlet hole Ceiling Ceiling L.L Filter MITSUBISHI ELECTRIC 10 Refrigerant pipe ···:6.35 Flared connection ···1/4 inch Refrigerant pipe :6.35 Flared connection 1/4 inch Refrigerant pipe ···:9.52 Flared connection ···3/8 inch Refrigerant pipe ···:12.7 Flared connection ··1/2 inch Refrigerant pipe ···:15.88 Flared connection ···5/8 inch A B C D E 80 74 241 258 87 85 77 400 Max. 4.0m Air intake hole 1 2 3 4 5 6 7 8 9 190 121 Ceiling 461 25 ø1 9 38 38 24 7 387 18 120° 85 260 2 8 48 233 246 When drain socket is installed (Drainage) 2 2 Drainage pipe connection (26mmI.D.) Drainage pipe connection (for the left arrangement) Knockout hole for left drain-piping arrangement Refrigerant-pipe connection (gas pipe side/flared connection) Refrigerant-pipe connection (liquid pipe side/flared connection) Knockout hole for upper drain pipe arrangement Knockout hole for fresh air intake ø100 Knockout hole for wiring arrangement 2-ø22 Knockout hole for wiring arrangement 2-ø26 Air intake Accessory···Drain socket (I.D. 26) Electrical box 138 86 126 4 Air outlet 878 853 960 917(Suspension bolt pitch) 182 140 62 80 1 In case of the rear pipe arrangement, make sure to remove the shaded portions from the independent piece. Then put the independent piece back in initial position. (The heat exchanger might be clogged because of dust) 75 3 When electrical box is pulled down 46 1 190 2 169 37 76 124 (71) 8 5 2 85 6 680 230 Electrical box 84 88 254 320 195 57 11 680 150 18 OCS25 476 [FRONT VIEW] 5 10 51 184 (liquid ø6.35) (gas ø12.7) When drain socket is installed (Drainage) (236) NOTES. 1.Use M10 or W3/8 screw for anchor bolt. 2.Please be sure when installing the drain pump (option parts), refrigerant pipe will be only upward. 246 233 203 PCA-RP50KAQ Unit : mm 121 37 190 46 1 2 3 4 5 6 7 8 9 12 461 25 ø1 9 38 7 387 18 120° 2 8 48 246 233 (Drainage) When drain socket is installed 138 85 86 260 2 4 2 Air outlet 1198 1173 1280 1237(Suspension bolt pitch) 182 140 62 80 1 Drainage pipe connection (26mmI.D.) Drainage pipe connection (for the left arrangement) Knockout hole for left drain-piping arrangement Refrigerant-pipe connection (gas pipe side/flared connection) Refrigerant-pipe connection (liquid pipe side/flared connection) Knockout hole for upper drain pipe arrangement Knockout hole for fresh air intake ø100 Knockout hole for wiring arrangement 2-ø22 Knockout hole for wiring arrangement 2-ø26 Air intake Accessory···Drain socket (I.D. 26) Flare nut ø6.35 (RP60 only) Electrical box Ceiling 38 24 5 In case of the rear pipe arrangement, make sure to remove the shaded portions from the independent piece. Then put the independent piece back in initial position. (The heat exchanger might be clogged because of dust) When electrical box is pulled down 75 169 3 124 76 (71) 2 8 126 1 190 Electrical box 84 88 2 85 254 320 195 57 680 230 680 OCS25 476 150 [FRONT VIEW] 6 5 10 60 179 203 71 A B 246 233 180 200 (gas ø15.88) When drain socket is installed (Drainage) (liquid ) 236 4 GAS SIDE ø15.88 :Initial flare nut size ø9.52 5 LIQUID SIDE ø6.35 RP60 ø9.52 ø15.88 RP71 Use the current nuts meeting the pipe size of the outdoor unit. Available pipe size NOTES. 1.Use M10 or W3/8 screw for anchor bolt. 2.Please be sure when installing the drain pump (option parts), refrigerant pipe will be only upward. 51 A B PCA-RP60KAQ PCA-RP71KAQ Unit : mm 18 D (Duct) 58 40 100x (E-1) =F 1 Refrigerant piping Flare connection (gas) 2X2-ø2.9 2 Refrigerant piping Flare connection (liquid) 32 10 10 57 136 238 67 356 Air inlet 18 210 Control box Terminal block (Remote controller transmission line) C 217 41 A 900 1100 1100 Model PEAD-RP35,50JAQ PEAD-RP60JAQ PEAD-RP71JAQ NOTE 1. Use M10 screw for the Suspension bolt (field supply). 2. Keep the service space for the maintenance at the bottom. 3. This chart indicates for PEAD-RP60·71JAQ models,which have 2 fans. PEAD-RP35·50JAQ models have 1 fan. 4. In case of the inlet duct is used,remove the air filter (supply with the unit), then install the filter (field supply) at suction side. 1154 1154 B 954 1200 1200 C 1000 1060 1060 D 860 11 11 E 9 1000 1000 F 800 1058 1058 G 858 Drain pipe(O.D.ø32) Terminal block (Spontaneous draining) (Indoor/Outdoor connecting line) Drain pipe Drain pump (O.D.ø32) 732 700 643 (Suspension bolt pitch) Suspension bolt hole 4-14x30 Slot B (Suspension bolt pitch) 23 Air outlet 100 57 G 21 2xE-ø2.9 A 250 78 20 30 23 40 178 (Duct) 100 122 33 1200 1200 H 1000 49 49 J 54 Air Filter More than 10mm 330 330 K 260 N-ø2.9 More than 20mm 6 50 J 25 0~ 50 30 0 45 0 4 4 L 4 Drain hose (I.D.ø32) <accessory> Less than 300mm Access door 990 990 M 780 K 10 10 N 10 1 ø15.88 ø12.7 Gas pipe 2 Liquid pipe ø6.35 ø9.52 Outdoor unit (SUZ) : 6.35 Other Outdoor unit : 9.52 Setting at shipment. Kx (L-1) =M J Make the access door at the appointed position properly for service maintenance. Ceiling surface (Actual length) 0 65 -10 0 45 00 n3 a h t Access door re Mo Required space for service and maintenance Note2 H 7 77 Less than 700mm 11 112 13 112 OCS25 15 PEAD-RP35JAQ PEAD-RP50JAQ PEAD-RP60JAQ PEAD-RP71JAQ Unit : mm 23 178(Duct) 32 10 57 10 136 67 356 732 700 Air inlet B(Suspension bolt pitch) C 18 210 Control box Terminal block (Remote controller transmission line) 23 A 250 217 A 900 1100 1100 Model PEAD-RP35,50JALQ PEAD-RP60JALQ PEAD-RP71JALQ 1154 1154 B 954 1200 1200 C 1000 1060 1060 D 860 11 11 E 9 1000 1000 F 800 1058 1058 G 858 Terminal block Drain pipe(O.D.ø32) (Indoor/Outdoor connecting line) 643 (Suspension bolt pitch) Suspension bolt hole 4-14x30 Slot G 21 Air outlet 100 57 1 Refrigerant piping Flare connection (gas) 2X2-ø2.9 40 100 24 2 Refrigerant piping Flare connection (liquid) 15 1200 1200 H 1000 49 49 J 54 N-ø2.9 Air Filter 50 330 330 K 260 6 More than 10mm J H 25 0~ 50 30 0 45 0 4 4 L 4 0 32 -10 Drain hose (I.D.ø32) <accessory> Access door (Actual length) Access door 990 990 M 780 K 10 10 N 10 1 ø15.88 ø12.7 Gas pipe 2 Liquid pipe ø6.35 ø9.52 Outdoor unit (SUZ) : 6.35 Other Outdoor unit : 9.52 Setting at shipment. Kx(L-1)=M J Make the access door at the appointed position properly for service maintenance. Ceiling surface 0 45 00 n3 tha re Mo Required space for service and maintenance Note2 More than 20mm 7 77 11 D (Duct) 100x(E-1)=F 20 78 30 122 33 14 112 OCS25 112 2xE-ø2.9 PEAD-RP35JALQ PEAD-RP50JALQ PEAD-RP60JALQ PEAD-RP71JALQ Unit : mm NOTE 1. Use M10 screw for the Suspension bolt (field supply). 2. Keep the service space for the maintenance at the bottom. 3. This chart indicates for PEAD-RP60·71JALQ models, which have 2 fans. PEAD-RP35·50JALQ models have 1 fan. 4. In case of the inlet duct is used, remove the air filter (supply with the unit), then install the filter (field supply) at suction side. Unit: mm OUTDOOR UNIT SUZ-KA25VA3 SUZ-KA35VA3 304~325 Air in 17.5 40 2-oval holes 10X21 Service panel Air out 22.3 Bolt pitch for installation Drain hole :42 44 23 Liquid refrigerant pipe joint Refrigerant pipe (flared) :6.35 150 69 302.5 100 mm Basically open 100mm or more without any obstruction in front and on both sides of the unit. ore or m m m 100 or m ore ore or m mm 0 0 2 350 mm or m ore Open two sides of left, right, or rear side. OCS25 170.5 Service port 500 Bolt pitch for installation 800 REQUIRED SPACE Gas refrigerant pipe joint Refrigerant pipe (flared) :9.52 99.5 10 164.5 280 35 550 Handle 15 43 285 344.5 400 Air in SUZ-KA50VA3 SUZ-KA60VA3 SUZ-KA71VA3 Unit: mm Open as a rule 500mm or more if the front and both sides are open REQUIRED SPACE 417.5 Drain hole 40 50 Bolt pitch for installation 360 42 Air in 100 mm 100mm or more 200mm or more if there are obstacles to both sides or m ore Air out 2-Oval holes 10 21 175 350 500 840 Open as a rule 500mm or more if the back, both sides and top are open 81 109 mm or m ore Service panel Liquid refrigerant pipe joint Refrigerant pipe (flared) Ø 6.35...(SUZ-KA50, 60VA3) Ø 9.52...(SUZ-KA71VA3) 880 35 164.5 99.5 44 452 330 Air in 195 OCS25 16 Gas refrigerant pipe joint Refrigerant pipe (flared) Ø 12.7...(SUZ-KA50VA3) Ø 15.88...(SUZ-KA60, 71VA3) Unit : mm WIRED REMOTE CONTROLLER (Option) PAR-21MAA PAR-30MAA, 31MAA 120 19 19 43.5 120 120 130 83.5 83.5 46 46 OCS25 17 Unit : mm WIRELESS REMOTE CONTROLLER SLZ-KA25VAL2 SLZ-KA35VAL SLZ-KA50VAL 57 17.5 h 140 ON/OFF AUTO COOL HEAT DRY TOO WARM TOO COOL FAN SELECT VANE TIME MODE RESET OCS25 Installation area • Area in which the remote controller is not exposed to direct sunshine • Area in which there is no heating source nearby • Area in which the remote controller is not exposed to cold (or warm) winds • Area in which the remote controller can be operated easily • Area in which the remote controller is beyond the reach of children Installation method Attach the remote controller holder to the desired location using two tapping screws. Place the lower end of the controller into the holder. Wireless remote controller (Accessory) Wall Remote controller holder (Accessory) Fixing screw (Accessory) • The signal can travel up to approximately 7 meters (in a straight line) within 45 degrees to both right and left of the center line of the receiver. In addition, the signal may not be received if there are interferences of fluorescent lights or strong sunlight. 18 Unit : mm WIRELESS REMOTE CONTROLLER 159.3 58 19 55 OCS25 19 4 WIRING DIAGRAM INDOOR UNIT SLZ-KA25VAL2 SLZ-KA35VAL SLZ-KA50VAL SLZ-KA25VAQ2 SLZ-KA35VAQ SLZ-KA50VAQ TB4 S1 S2 S3 GRILLE MF SKY BLU PINK GRY VLT BLU YLW 9 ORN RED BRN 9 8 7 6 5 4 3 2 1 5 MV 5 MV 5 W.B CNB BZ LED2 LED1 20 1 3 ORN C1 P.B RED 1 3 5 7 9 1 WHT (FAN) FAN 3 RED 1 (D·HEATER) CNC 3 RED 1 (POWER BOARD) CNDK FUSE 3 BLU 1 (D·U·M) CNP X1 ORN BLU MV M 1~ RED BLU 7 6 3 2 1 3 ORN (POWER) CND 1 X6 X5 X4 X7 ON OFF 5 1 CN41 1 4 See fig:*1 1 GRN (VANE) CN6V 5 12345 1 9 CN90 (WIRELESS) WHT 1 9 12345 1 2 1 2 LED1 BLU WHT (LIQUID) (REMOCON) CN22 CN21 2 1 2 t° t° TH5 t° TH1 t° TH2 2 SYMBOL C1 DP DS H2 MF MV TB4 NAME CAPACITOR (FAN MOTOR) DRAIN PUMP DRAIN SENSOR DEW PREVENTION HEATER FAN MOTOR (WITH THERMAL FUSE) VANE MOTOR TERMINAL BLOCK (INDOOR/OUTDOOR CONNECTING LINE) TB15 TERMINAL BLOCK (REMOTE CONTROLLER TRANSMISSION LINE) TH1 ROOM TEMP. THERMISTOR (0°C / 15kΩ, 25°C / 5.4kΩ DETECT) TH2 PIPE TEMP. THERMISTOR/LIQUID (0°C / 15kΩ, 25°C / 5.4kΩ DETECT) TH5 COND. / EVA. TEMP. THERMISTOR (0°C/ 15kΩ, 25°C / 5.4kΩ DETECT) OPTION PART WIRED REMOTE CONTROLLER BOARD R.B TERMINAL BLOCK (REMOTE CONTROLLER TB6 TRANSMISSION LINE) NOTES:1. Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing. 2. Indoor and outdoor connecting wires are made with poIarities, make wiring matching terminal numbers (S1, S2, S3). :Connector, :Terminal (block). 3. SymboIs used in wiring diagram above are, * For details on how to operate self-diagnosis refer to the technical manuals etc. OCS25 2 20 CN2S (WHT) BLK WHT 1 TB15 1 2 R.B TB6 1 2 *Case of wired model [LEGEND] NAME INDOOR POWER BOARD INDOOR CONTROLLER BOARD CONNECTOR (LOSSNAY) CONNECTOR (REMOTE SWITCH) CONNECTOR (HA TERMINAL-A) CENTRALLY CONTROL FUSE (T6.3AL250V) POWER SUPPLY (I.B) POWER SUPPLY (I.B) TRANSMISSION (INDOOR-OUTDOOR) SWITCH (CAPACITY CODE) SWITCH (MODE SELECTION) SWITCH (EMERGENCY OPERATION) DRAIN PUMP/DEW PREVENTION HEATER RELAY (FAN MOTOR LL) RELAY (FAN MOTOR Lo) RELAY (FAN MOTOR Hi) RELAY (FAN MOTOR Me) WIRELESS REMOTE CONTROLLER BOARD RECEIVING UNIT BUZZER LED (RUN INDICATOR) LED (HOT ADJUST) SWITCH (HEATING ON/OFF) SWITCH (COOLING ON/OFF) BLK RED (2 PHASE) (INTAKE) CN29 CN20 1 DS *Case of wireless model 12345 The black square(■)indicates a switch position.<*1> SYMBOL P.B I.B CN2L CN32 CN41 CN51 FUSE LED1 LED2 LED3 SW2 SW3 SWE X1 X4 X5 X6 X7 W.B RU BZ LED1 LED2 SW1 SW2 WHT (DRAIN) CN31 3 KA50 3 CN51 6 LED2 1 2 BLU BLU 1 SW2 ON OFF CN105 5 CN32 KA35 LED3 SKY BLU PINK GRY VLT BLU YLW ORN RED BRN REMOTE CONTROLLER KA25 3 CNSK (RED) DC13.1V WHT (POWER BOARD) CN2D RED ORN YLW WHT BLU SW3 SWE ON ON OFF OFF 12345 SW2 CN2L ON OFF 2 1 12345 RU ON OFF 1 1 SW2 <fig:*1> MODELS I.B 3 BLU (CONTROL) CN3C SW1 W.R TO OUTDOOR UNIT M 1~ RED WHT RED ORN YLW WHT BLU 5 DP YLW YLW 10 5 YLW YLW MV YLW YLW BLK YLW BRN WHT BLU H2 SEZ-KD25VAL SEZ-KD35VAL SEZ-KD50VAL SEZ-KD60VAL SEZ-KD71VAL INSIDE SECTION OF CONTROL BOX TB15 1 2 TO MA REMOTE CONTROLLER I.B ;For SEZ-KD • VA SW1 1 SW2 CN32 CN01 (Black) 3 CN3C (Blue) CN41 CN51 DC310~340V Rectify circuit ZNR01 L1:only SEZ-KD71VA(L) FUSE U LED2 LED3 L1 LED1 CN90 5 U CN22 (Blue) ON OFF SWE 3 ZNR02 12 CN2L 1 DSA CN44 CN4F 123456789 34 123456789 1234 CN20 (Red) 1234 12 X1 CNMF 7654 1 3 1 CNP (Blue) W.B CN4F TB4 S1 S2 CN1 S3 LED1 BZ1 RU RECEIVER SW1 SW2 ;For SEZ-KD • VAL t° FS t° TH2 t° TH5 M 1~ M TH1 Fan motor Optional Parts Drainpump Optional Parts SYMBOL EXPLANATION NAME SYMBOL I.B INDOOR CONTROLLER BOARD FUSE SYMBOL W.B NAME WIRELESS REMOTE CONTROLLER BOARD FUSE AC250V 6.3A RU RECEIVING UNIT ZNR01,02 VARISTOR BZ1 BUZZER DSA ARRESTER LED1 LED (RUN INDICATOR) X1 AUX. RELAY SW1 SWITCH (HEATING ON/OFF) CN2L CONNECTOR (LOSSNAY) SW2 SWITCH (COOLING ON/OFF) CN32 CONNECTOR (REMOTE SWITCH) TH1 INTAKE AIR TEMP. THERMISTOR CN41 CONNECTOR (HA TERMINAL-A) TH2 PIPE TEMP. THERMISTOR/LIQUID CN51 CONNECTOR (CENTRALLY CONTROL) TH5 COND. /EVA. TEMP. THERMISTOR LED1 POWER SUPPLY(I.B.) L1 AC REACTOR(POWER FACTOR IMPROVEMENT) LED2 POWER SUPPLY(I.B.) FS FLOAT SWITCH LED3 TRANSMISSION(INDOOR-OUTDOOR) SW1 SWITCH (FOR MODE SELECTION) TB4 TERMINAL BLOCK (INDOOR/OUTDOOR CONNECTING LINE) SW2 SWITCH (FOR CAPACITY CODE) SWE CONNECTOR (EMERGENCY OPERATION) TB15 TERMINAL BLOCK (REMOTE CONTROLLER TRANSMISSION LINE) NOTE) 1. Since the outdoor side electric wiring may change,be sure to check the outdoor unit electric wiring diagram for servicing. 2. Indoor and outdoor connecting wires have polarities, make sure to match terminal numbers (S1,S2,S3) for correct wirings. 3. Symbols used in wiring diagram above are, :Connector, :Terminal Block. OCS25 21 TO OUTDOOR UNIT SEZ-KD25VAQ SEZ-KD35VAQ SEZ-KD50VAQ SEZ-KD60VAQ SEZ-KD71VAQ INSIDE SECTION OF CONTROL BOX R.B TB15 1 1 2 2 TB6 I.B SW1 1 SW2 CN01 (BLACK) 3 CN3C(BLUE) CN32 CN41 CN51 5 U CN22(BLUE) ON OFF SWE 3 ZNR02 12 CN2L 1 DSA DC310~340V RECTIFY CIRCUIT ZNR01 L1:ONLY SEZ-KD71VAQ FUSE U LED2 LED3 L1 LED1 CN4F CN44 34 X1 CN20(RED) 1234 CNMF 7654 12 1 3 1 CNP (BLUE) CN4F TB4 S1 1234 S2 S3 t˚ FS t˚ TH2 t˚ TH5 M 1~ MS 3~ TH1 FAN MOTOR DRAINPUMP SYMBOL EXPLANATION SYMBOL I.B NAME SYMBOL NAME INDOOR CONTROLLER BOARD TH1 INTAKE AIR TEMP. THERMISTOR FUSE FUSE AC250V 6.3A TH2 PIPE TEMP. THERMISTOR/LIQUID ZNR01,02 VARISTOR TH5 COND. /EVA. TEMP. THERMISTOR DSA ARRESTER L1 AC REACTOR (POWER FACTOR IMPROVEMENT) X1 AUX. RELAY FS FLOAT SWITCH CN2L CONNECTOR (LOSSNAY) CN32 CONNECTOR (REMOTE SWITCH) CN41 CONNECTOR (HA TERMINAL-A) CN51 CONNECTOR (CENTRALLY CONTROL) LED1 POWER SUPPLY (I.B.) LED2 POWER SUPPLY (I.B.) LED3 TRANSMISSION (INDOOR-OUTDOOR) SW1 SWITCH (FOR MODE SELECTION) SW2 SWITCH (FOR CAPACITY CODE) SWE CONNECTOR (EMERGENCY OPERATION) TB4 TERMINAL BLOCK (INDOOR/OUTDOOR CONNECTING LINE) TB15 TERMINAL BLOCK (REMOTE CONTROLLER TRANSMISSION LINE) OPTIONAL PARTS WIRED REMOTE CONTROLLER BOARD R.B TB6 NOTE)1. Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing. 2. Indoor and outdoor connecting wires are made with polarities, make wiring matching terminal numbers(S1,S2,S3). 3. Symbols used in wiring diagram above are, :CONNECTOR :TERMINAL (HEAVY DOTTED LINE):FIELD WIRING (THIN DOTTED LINE) :OPTIONAL PARTS OCS25 22 TERMINAL BLOCK (REMOTE CONTROLLER TRANSMISSION LINE) TO OUTDOOR UNIT PLA-RP35BA PLA-RP50BA PLA-RP60BA PLA-RP71BA [LEGEND] SYMBOL I.B CN2L CN32 CN41 CN51 FUSE LED1 LED2 LED3 SW1 SW2 SWE X1 R.B DCL DP FS MF MV NAME INDOOR CONTROLLER BOARD CONNECTOR (LOSSNAY) CONNECTOR (REMOTE SWITCH) CONNECTOR (HA TERMINAL-A) CONNECTOR (CENTRALLY CONTROL) FUSE (T6.3AL250V) POWER SUPPLY (I.B) POWER SUPPLY (R.B) TRANSMISSION (INDOOR-OUTDOOR) SWITCH (MODEL SELECTION) +See table 1 SWITCH (CAPACITY CODE) +See table 2 CONNECTOR (EMERGENCY OPERATION) RELAY (DRAIN PUMP) WIRED REMOTE CONTROLLER BOARD REACTOR DRAIN PUMP DRAIN FLOAT SWITCH FAN MOTOR VANE MOTOR NAME TERMINAL BLOCK (INDOOR/OUTDOOR CONNECTING LINE) TERMINAL BLOCK (REMOTE CONTROLLER TB5,TB6 TRANSMISSION LINE) TH1 ROOM TEMP. THERMISTOR (0 / 15k, 25 / 5. 4k DETECT) TH2 PIPE TEMP. THERMISTOR/LIQUID (0 / 15k, 25 / 5. 4k DETECT) TH5 COND. / EVA. TEMP. THERMISTOR (0 / 15k, 25 / 5. 4k DETECT) OPTIONAL PARTS PCB FOR WIRELESS REMOTE CONTROLLER W.B BZ BUZZER LED1 LED (OPERATION INDICATION : GREEN) LED2 LED (PREPARATION FOR HEATING : ORANGE) RECEIVING UNIT RU SW1 EMERGENCY OPERATION (HEAT / DOWN) SW2 EMERGENCY OPERATION (COOL / UP) Refer to tables 1 and 2. 1 2 3 4 5 PLA-RP·BA ON OFF <Table 2> SW2 (CAPACITY CODE) SW2 CAPACITY SETTING 1 2 3 4 5 35 1 2 3 4 5 50 1 2 3 4 5 60 1 2 3 4 5 71 ON OFF ON OFF ON OFF ON OFF DCL TB5 2 1 TRANSMISSION WIRES DC12V 2 1 TB6 YLW R.B I.B VANE CNV(WHT) SW1 20 18 16 14 12 10 8 6 4 2 J41 J42 SW2 19 17 15 13 11 9 7 5 3 1 CN32 (WHT) 1 CN51(WHT) Pair No. 5 CN2L LED3 3 1 3 AUTO GRILLE CN3G 1 (BLK) WIRELESS CN90 (WHT) 9 5 5 M M M M MV MV MV MV GRILLE LED2 1 4 4 CNB LED1 2 1 OUTDOOR 1 3 5 CN01 3 INDOOR/OUTDOOR COMMUNICATION CN3C 1 CN41(WHT) 4 (BLU) 1 2 REMOCON CN22 1 SWE 1 M I-SEE SENSOR SW1 LED2 SW2 LED1 I-SEE SENSOR CORNER PANEL (OPTIONAL PARTS) MT 3 1 1 4 4 1 2 t° t° TH2 TH5 t° TH1 1 FUSE DC325V RECTIFICATION (BLU) 7 FAN CNMF (WHT) 4 MS 3 5 BZ RU 6 (BLK) 1 3 ON OFF AUTO GRILLE I-SEE FLOAT SW LIQUID/PIPE INTAKE POWER I-SEE SENSOR SENSOR MOTOR CN4F CN44 CN20 CNAC CN4Y CN6Y (WHT) (WHT) (RED) (WHT) (WHT) (RED) 9 5 SW1 SETTING MODELS The black square (■) indicates a switch position. Please set the voltage using the remote controller. For the setting method, please refer to the indoor unit Installation Manual. 5 <Table 1> SW1 (MODEL SELECTION) SYMBOL TB4 FS U.B 3 1 CN3G 5 3 1 CN3A X1 1 1 D.U.M 3 CNP (BLU) YLW ORN TB4 YLW S1 ORN S2 S3 TO OUTDOOR UNIT ORN BRN M 3~ 1~ MF DP + Be sure to turn off the power source and then disconnect fan motor connector. (Failure to do so will cause trouble in fan motor.) AUTOMATIC FILTER ELEVATION PANEL (OPTIONAL PARTS) W.B Notes: 1.SymboIs used in wiring diagram above are, :Connector, : Terminal (block). 2.Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wirings. 3.Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing. 4.This diagram shows the wiring of indoor and outdoor connecting wires.(specification of 230V), adopting superimposed system for power and signal. + :For power supply system of this unit, refer to the caution label located near this diagram. OCS25 23 PCA-RP50KAQ PCA-RP60KAQ PCA-RP71KAQ [LEGEND] SYMBOL I.B CN2L CN32 CN41 CN51 FUSE LED1 LED2 LED3 SW1 SW2 SWE X1 R.B DCL MF MV TB2 NAME INDOOR CONTROLLER BOARD CONNECTOR (LOSSNAY) CONNECTOR (REMOTE SWITCH) CONNECTOR (HA TERMINAL-A) CONNECTOR (CENTRALLY CONTROL) FUSE (T6.3AL250V) POWER SUPPLY (I.B) POWER SUPPLY (R.B) TRANSMISSION (INDOOR-OUTDOOR) SWITCH (MODEL SELECTION) See table 1 SWITCH (CAPACITY CODE) See table 2 CONNECTOR (EMERGENCY OPERATION) RELAY (DRAIN PUMP) WIRED REMOTE CONTROLLER BOARD REACTOR FAN MOTOR VANE MOTOR TERMINAL BLOCK (Indoor unit Power (option parts)) SYMBOL TB4 TB5,TB6 NAME TERMINAL BLOCK (INDOOR/OUTDOOR CONNECTING LINE) TERMINAL BLOCK (REMOTE CONTROLLER TRANSMISSION LINE) ROOM TEMP. THERMISTOR (0ºC / 15kΩ, 25ºC / 5. 4kΩ DETECT) PIPE TEMP. THERMISTOR/LIQUID (0ºC / 15kΩ, 25ºC / 5. 4kΩ DETECT) COND. / EVA. TEMP. THERMISTOR (0ºC / 15kΩ, 25ºC / 5. 4kΩ DETECT) TH1 TH2 TH5 OPTION PARTS W.B BZ LED1 LED2 RU SW1 SW2 DP FS <Table 1> SW1 (MODEL SELECTION) SW1 Service 1 2 3 4 5 ON OFF <Table 2>SW2 (CAPACITY CODE) SW2 MODELS Service PCB FOR WIRELESS REMOTE CONTROLLER BUZZER LED (OPERATION INDICATION : GREEN) LED (PREPARATION FOR HEATING : ORANGE) RECEIVING UNIT EMERGENCY OPERATION (HEAT / DOWN) EMERGENCY OPERATION (COOL / UP) DRAIN PUMP DRAIN FLOAT SWITCH 1 2 3 4 5 PCA-RP50KAQ 1 2 3 4 5 PCA-RP60KAQ 1 2 3 4 5 PCA-RP71KAQ ON OFF ON OFF The black square(■)indicates a switch position. (OPTION PARTS) TB5 2 1 2 DCL TRANSMISSION WIRES DC12V 1 2 TB6 R.B YLW Refer to tables 1 and 2 I.B VANE CNV(WHT) SW1 20 18 16 14 12 10 8 6 4 2 J41 J42 SW2 19 17 15 13 11 9 7 5 3 1 Pair No. CN32 (WHT) 1 CN51(WHT) 5 CN2L LED3 LED2 2 1 LED1 OUTDOOR 1 3 5 CN01 3 1 CN41(WHT) 4 FUSE (BLU) 1 2 – REMOCON CN22 1 SWE (BLK) 1 3 INDOOR/OUTDOOR COMMUNICATION CN3C + (BLU) ON OFF WIRELESS CN90 (WHT) 1 9 FLOAT SW CN4F (WHT) 1 LIQUID/PIPE INTAKE CN44 CN20 (WHT) (RED) 1 4 4 1 2 7 FAN CNMF (WHT) YLW ORN X1 4 D.U.M 1 CNP 3 1 CNB BZ 5 SW1 LED2 SW2 LED1 RU MV M MS 9 When attaching drain pump (option parts), remove the jumper connector CN4F and fit the drain float switch (FS). t˚ t˚ TH2 TH5 When attaching drain pump (option parts) FLOAT SW CN4F (WHT) 1 t˚ TH1 4 TB4 YLW S1 ORN S2 S3 ORN BRN (BLU) M ON OFF 3~ 1~ MF DP (OPTION PARTS) *Be sure to turn off the source power and then disconnect fan motor connector. (Failure to do so will cause trouble in fan motor) FS W.B (OPTION PARTS) Notes: 1. SymboIs used in wiring diagram above are, : Connector, :Terminal (block). 2. Indoor and outdoor connecting wires are made with poIarities, make wiring matching terminal numbers (S1, S2, S3). 3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring for servicing. 4. This diagram shows the wiring of indoor and outdoor connecting wires.(specification of 230V), adopting superimposed system of power and signal. *1: When work to Supply power separately to indoor and outdoor units was applied, refer to Fig 1. *2: For power supply system of this unit, refer to the caution label located near this diagram. OCS25 *1 (Fig. 1) CN01 I.B (BLK) YLW 5 3 1 DCL YLW ORN TB2 L N YLW TB4 ORN S1 ORN S2 BRN S3 I.B 1 3 INDOOR/OUTDOOR CN3C COMMUNICATION (BLU) 24 RED BLU GRN/YLW POWER SUPPLY (1PHASE) 230V 50Hz TO OUTDOOR UNIT TO OUTDOOR UNIT PEAD-RP35JAL PEAD-RP35JALQ PEAD-RP50JAL PEAD-RP50JALQ PEAD-RP60JAL PEAD-RP60JALQ PEAD-RP71JAL PEAD-RP71JALQ INSIDE SECTION OF CONTROL BOX TB15 1 TO MA REMOTE CONTROLLER 2 ACL I.B. TB4 1 1 S1 2 2 S2 TO OUTDOOR UNIT S3 SW6 1 CN3C 3 (Blue) CN32 SW1 P.B. CN105 (Red) LED2 CN41 SW2 1 3 CND 5 (Red) A CN2A (Black) OFF SWE DSA CN51 ON SW5 F01 CN22 (Blue) 2 1 LED1 (Blue) CNXA2 U ZNR01 ZNR02 CN90 U LED3 CN44 CN4F 1 2 3 4 1 2 3 4 CNXB2 1 2 3 4 5 (Red) (Red) CN20 CN2L 1 2 CNXC2 1 2 (Blue) CNP 4 3 2 1 1 < A> (IN CASE OF CONNECT X10 X01 3 CNXB1 1 2 3 4 5 CNXC1 1 2 (Blue) CNXA1 1 2 3 4 ACL DC280-340V Rectifier circuit CNMF 7654 1 2 1 2 1 2 1 TO CN3C CN4F L N S1 S2 S3 POWER SUPPLY ~ (1PHASE) 220-240V 50Hz TO OUTDOOR UNIT TO CND 1 2 3 4 B THE REPLACEMENT WIRING) t˚ TH1 t˚ TH2 t˚ TH5 FS M FOR PEAD-RP·JA REFER TO "B" FOR PEAD-RP·JAL MS 3~ 1~ Drainpump ONLY FOR PEAD-RP·JAL Fan motor SYMBOL EXPLANATION SYMBOL I.B. CN2A CN2L CN32 CN41 CN51 CN90 CN105 LED1 LED2 LED3 NAME Indoor controller board Connector (0-10V Analog input) Connector (Lossnay) Connector (Remote switch) Connector (HA terminal-A) Connector (Centrally control) Connector (Wireless) Connector (IT terminal) LED(Power supply) LED(Remote controller power supply) LED(Transmission indoor-outdoor) SYMBOL I.B. SW1 SW2 SW5 SW6 SWE P.B. F01 ZNR01,02 DSA X01 X10 OCS25 NAME Indoor controller board Switch (for mode selection) Switch (for capacity code) Switch (for model selection) Switch (for model selection) Connector (emergency operation) Power supply board Fuse AC250V 6.3A Varistor Arrester Aux. relay Aux. relay SYMBOL NAME TH1 Intake air temp. Thermistor TH2 Pipe temp. Thermistor/liquid TH5 Cond./eva.temp. Thermistor ACL FS AC reactor(Power factor improvement) Float switch TB4 Terminal block (Indoor/outdoor connecting line) TB15 Terminal block (Remote controller transmission line) 25 NOTE:1.Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring for servicing. 2.Indoor and outdoor connecting wires are made with polarities,make wiring matching terminal numbers(S1,S2,S3). 3.Symbols used in wiring diagram above are, terminal block, connector. OUTDOOR UNIT SUZ-KA25VA3 SUZ-KA35VA3 OCS25 26 SUZ-KA50VA3 OCS25 27 SUZ-KA60VA3 SUZ-KA71VA3 OCS25 28 5 REFRIGERANT SYSTEM DIAGRAM 5-1. INDOOR UNIT SLZ-KA·VAQ SEZ-KD·VAQ PEAD-RP·JAQ Unit : mm SLZ-KA·VAQ2 SEZ-KD·VAL PEAD-RP·JALQ SLZ-KA·VAL PLA-RP·BA SLZ-KA·VAL2 PCA-RP·KAQ Strainer(#50) Heat exchanger Refrigerant GAS pipe connection (Flare) Thermistor TH5 (Cond./Eva. temperature) Refrigerant flow in cooling Refrigerant flow in heating Refrigerant LIQUID pipe connection (Flare) Distributor with strainer(#50) Thermistor TH1 (Room temperature) OCS25 Thermistor TH2 Pipe temperature (Liquid) Strainer(#50) 29 5-2. OUTDOOR UNIT SUZ-KA25VA3 Unit: mm Refrigerant pipe ø9.52 (with heat insulator) 4-way valve Muffler Stop valve (with service port) Discharge temperature thermistor RT62 Flared connection Outdoor heat exchanger Muffler Outdoor heat exchanger temperature thermistor RT68 Ambient temperature thermistor RT65 Compressor Defrost thermistor RT61 Flared connection Refrigerant pipe ø6.35 (with heat insulator) Strainer #100 Capillary tube ø3.0×ø2.0×240 LEV R.V. coil heating ON cooling OFF Stop valve (with strainar) Refrigerant flow in cooling Refrigerant flow in heating SUZ-KA35VA3 Unit: mm Refrigerant pipe ø9.52 (with heat insulator) 4-way valve Muffler Stop valve (with service port) Discharge temperature thermistor RT62 Flared connection Outdoor heat exchanger Muffler Outdoor heat exchanger temperature thermistor RT68 Ambient temperature thermistor RT65 Compressor Defrost thermistor RT61 Capillary tube ø3.0×ø1.8×600(×2) Flared connection Refrigerant pipe ø6.35 (with heat insulator) OCS25 Strainer #100 Capillary tube ø3.0×ø2.0×240 LEV R.V. coil heating ON cooling OFF Stop valve (with strainar) Refrigerant flow in cooling Refrigerant flow in heating 30 SUZ-KA50VA3 Unit: mm Muffler 4-way valve #100 Refrigerant pipe ø12.7 (with heat insulator) Stop valve (with service port) Flared connection Discharge temperature thermistor RT62 Defrost thermistor RT61 Outdoor heat exchanger Ambient temperature thermistor RT65 Compressor Outdoor heat exchanger temperature thermistor RT68 Flared connection Strainer #100 Stop valve Refrigerant pipe ø6.35 (with heat insulator) LEV Muffler Strainer #100 Capillary tube ø4.0×ø2.4×100 R.V. coil heating ON cooling OFF Refrigerant flow in cooling Refrigerant flow in heating SUZ-KA60VA3 SUZ-KA71VA3 Unit: mm Muffler 4-way valve #100 Refrigerant pipe ø15.88 (with heat insulator) Stop valve (with service port) Flared connection Discharge temperature thermistor RT62 Defrost thermistor RT61 Outdoor heat exchanger Ambient temperature thermistor RT65 Compressor Outdoor heat exchanger temperature thermistor RT68 Flared connection LEV Strainer #100 Stop valve Refrigerant pipe ø9.52 (KA71VA3) Refrigerant pipe ø6.35 (KA60VA3) (with heat insulator) OCS25 Capillary tube ø4.0×ø2.4×100 31 Strainer #100 R.V. coil heating ON cooling OFF Refrigerant flow in cooling Refrigerant flow in heating 6 PERFORMANCE CURVES FOR THE COMBINATION OF OUTDOOR UNIT SUZ-KA25/35/50/60/71VA3 <COOLING> Cooling capacity Capacity correction factors 1.5 Indoor intake air Wet-bulb temperature( ) 1.4 1.3 1.2 26 1.1 24 1.0 22 20 18 0.9 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 Outdoor intake air Dry-bulb temperature(°C) Total input (Cooling) Input correction factors 1.3 1.2 22 20 18 24 26 1.1 1.0 0.9 Indoor intake air Wet-bulb temperature( ) 0.8 -15 -10 -5 0 5 10 15 20 25 30 Outdoor intake air Dry-bulb temperature (°C) Lower limit of guaranteed operating range in cooling SUZ-KA25/35VA3: -10°C SUZ-KA50/60/71VA3: -15°C OCS25 32 35 40 45 <HEATING> Heating capacity Capacity correction factor 1.3 1.2 e( 1.1 ur rat ) 15 20 26 pe 1.0 0.9 0.8 r oo ir ea ulb y-b Dr tem ak int Ind 0.7 0.6 0.5 0.4 -10 -5 0 5 10 15 Outdoor intake air Wet-bulb temperature (°C) Total input (Heating) Input correction factor 1.3 1.2 1.1 0.9 lb te y-bu 1.0 ( ) 26 20 15 tak or in Indo Dr e air ure rat mpe 0.8 0.7 0.6 0.5 0.4 -10 -5 0 5 10 15 Outdoor intake air Wet-bulb temperature (°C) OCS25 33 7 APPLICABLE EXTENSION PIPE FOR EACH MODEL SUZ-KA25VA3 SUZ-KA60VA3 SUZ-KA35VA3 SUZ-KA71VA3 SUZ-KA50VA3.TH 7-1. MAX. REFRIGERANT PIPING LENGTH Refrigerant piping: m Max. Height difference B Max. Length A Models SUZ-KA25VA3 SUZ-KA35VA3 SUZ-KA50VA3 SUZ-KA60VA3 SUZ-KA71VA3 20 12 Gas Piping size O.D: mm Liquid 9.52 12.7 30 30 15.88 6.35 9.52 7-2. MAX. HEIGHT DIFFERENCE Indoor unit * Max. Height difference B Max. Length A Outdoor unit * Height difference limitations are binding regardless of which unit, indoor or outdoor, is position high. 7-3. ADDITIONAL REFRIGERANT CHARGE (R410A: g) Models SUZ-KA25VA3 SUZ-KA35VA3 Outdoor unit precharged 800 1,150 7m 0 0 8m 30 30 Refrigerant piping length (one way) 9m 10m 11m 12m 13m 14m 60 90 120 150 180 210 60 90 120 150 180 210 15m 240 240 20m 390 390 Calculation: Xg = 30g/m o (Refrigerant piping length(m)-7) Models SUZ-KA50VA3 SUZ-KA60VA3 Outdoor unit precharged 1,600 1,800 7m 0 0 10m 60 60 Refrigerant piping length (one way) 15m 20m 25m 160 260 360 160 260 360 30m 460 460 Calculation : Xg = 20g/m o (Refrigerant piping length(m)-7) Models SUZ-KA71VA3 Outdoor unit precharged 1,800 7m 0 10m 165 Refrigerant piping length (one way) 15m 20m 25m 440 715 990 30m 1,265 Calculation : Xg = 55g/m o (Refrigerant piping length(m)-7) OCS25 34 AIR FLOW DATA 8 8-1. OUTLET AIR SPEED AND COVERAGE RANGE Air flow Air speed Air speed Air speed SLZ-KA50VAQ SLZ-KA50VAL 11 11 11 m/sec. 3.7 3.7 3.7 m 4.1 4.1 4.1 PLA-RP35BA PLA-RP50BA PLA-RP60BA PLA-RP71BA m³/min. 15 18 18 21 m/sec. 2.6 3.2 3.2 3.7 m 4.1 4.8 4.8 5.6 PCA-RP50KAQ PCA-RP60KAQ PCA-RP71KAQ 15 19 20 Coverage range Air flow SLZ-KA35VAQ SLZ-KA35VAL m³/min. Coverage range Air flow SLZ-KA25VAQ2 SLZ-KA25VAL2 m³/min. m/sec. 3.3 3.1 3.2 m 9.0 9.6 10.1 Coverage range * The air coverage range is the distance to which the 0.25m/sec air can reach, when air is blown out horizontally from the unit at the High notch position. The coverage range should be used only as a general guideline since it varies according to the size of the room and the furniture inside the room. 8-2. SLZ-KA•VAL SLZ-KA•VAQ 8-2-1. Fresh air intake (Location for installation) At the time of installation, use the duct holes (cut out) located at the positions shown in following diagram, as and when required. Fresh air intake Detail drawing of fresh air intake 25 :100 :73.4 Cut out hole 0° 12 12 0° 118 3-:2.8 hole Burring hole Ceiling surface Refrigerant pipe Electrical Box Drain pipe 8-2-2. Fresh air intake amount & static pressure characteristics How to read curves 2.5 1 Curve in the left graphs. 0 Q -50 -100 Duct characteristics at site A 2.0 Airflow : Q [m3/min] 3.0 3.5 C A 2 E -150 -200 Q -250 OCS25 35 D 3 A -300 NOTE: Fresh air intake amount should be 20% or less of whole air amount to prevent dew dripping. Q Qa C Static pressure : P [Pa] 50 0.5 1.0 1.5 0 B Taking air into the unit Q…Designed amount of fresh air intake <m3/min> A…Static pressure loss of fresh air intake duct system with airflow amount Q <Pa> B…Forced static pressure at air conditioner inlet with airflow amount Q <Pa> C…Static pressure of booster fan with airflow amount Q <Pa> D…Static pressure loss increase amount of fresh air intake duct system for airflow amount Q <Pa> E…Static pressure of indoor unit with airflow amount Q Qa…Estimated amount of fresh air intake without D <m3/min> 8-3. SEZ-KD•VAL SEZ-KD•VAQ INDOOR FAN PERFORMANCE AND CORRECTED AIR FLOW SEZ-KD25VAL SEZ-KD25VAQ (External static pressure 5Pa) 220-240V 50/60Hz (External static pressure 15Pa) 220-240V 50/60Hz 40 50 Limit Limit 40 External static pressure (Pa) External static pressure (Pa) 30 20 High High 30 20 Middle Rated point 10 Middle Low 10 Low Rated point 0 0 4 5 6 7 8 Airflow rate(m3/min) 9 10 (External static pressure 35Pa) 220-240V 50/60Hz 4 5 6 7 8 Airflow rate(m3/min) 9 10 (External static pressure 50Pa) 220-240V 50/60Hz 80 80 Limit Limit 70 70 60 60 External static pressure (Pa) External static pressure (Pa) High 50 High 40 Rated point 30 Middle 20 50 Rated point 40 Middle 30 Low 20 Low 10 10 0 0 4 5 OCS25 6 7 8 Airflow rate(m3/min) 9 10 4 36 5 6 7 8 Airflow rate(m3/min) 9 10 SEZ-KD35VAL SEZ-KD35VAQ (External static pressure 5Pa) 220-240V 50/60Hz (External static pressure 15Pa) 220-240V 50/60Hz 40 50 40 External static pressure (Pa) External static pressure (Pa) 30 Limit 20 High Limit 30 High 20 Middle Rated point 10 Middle 10 Low Rated point Low 0 6 7 8 9 10 Airflow rate(m3/min) 11 (External static pressure 35Pa) 220-240V 50/60Hz 6 80 70 70 External static pressure (Pa) 50 40 Rated point High Middle 20 8 9 10 Airflow rate(m3/min) 11 12 Limit 60 Limit 30 7 (External static pressure 50Pa) 220-240V 50/60Hz 80 60 External static pressure (Pa) 0 12 50 Rated point High 40 Middle 30 20 Low 10 Low 10 0 0 6 OCS25 7 8 9 10 Airflow rate(m3/min) 11 12 37 6 7 8 9 10 Airflow rate(m3/min) 11 12 SEZ-KD50VAL SEZ-KD50VAQ (External static pressure 5Pa) 220-240V 50/60Hz (External static pressure 15Pa) 220-240V 50/60Hz 50 40 Limit Limit 40 External static pressure (Pa) External static pressure (Pa) 30 20 High Middle 30 High 20 Middle Rated point Low 10 10 Low Rated point 0 0 8 9 10 11 12 13 Airflow rate(m3/min) 14 15 8 16 (External static pressure 35Pa) 220-240V 50/60Hz 9 10 11 12 13 Airflow rate(m3/min) 14 15 16 (External static pressure 50Pa) 220-240V 50/60Hz 80 80 70 70 Limit Limit High 60 External static pressure (Pa) External static pressure (Pa) 60 50 High 40 Middle 30 Rated point 20 50 Rated point Middle 40 30 Low 20 Low 10 10 0 0 8 9 OCS25 10 11 12 13 Airflow rate(m3/min) 14 15 16 8 38 9 10 11 12 13 Airflow rate(m3/min) 14 15 16 SEZ-KD60VAL SEZ-KD60VAQ (External static pressure 5Pa) 220-240V 50/60Hz (External static pressure 15Pa) 220-240V 50/60Hz 40 50 Limit Limit 40 External static pressure (Pa) External static pressure (Pa) 30 20 High Middle 10 High 30 Middle 20 Low Rated point 10 Low Rated point 0 0 9 10 11 12 13 14 15 Airflow rate(m3/min) 16 17 18 19 (External static pressure 35Pa) 220-240V 50/60Hz 9 10 11 12 13 14 15 Airflow rate(m3/min) 17 18 19 (External static pressure 50Pa) 220-240V 50/60Hz 80 80 Limit Limit 70 70 60 60 External static pressure (Pa) External static pressure (Pa) 16 High 50 40 Middle Rated point 30 Low 20 High 50 30 Low 20 10 Rated point Middle 40 10 0 0 9 OCS25 10 11 12 13 14 15 Airflow rate(m3/min) 16 17 18 19 39 9 10 11 12 13 14 15 Airflow rate(m3/min) 16 17 18 19 SEZ-KD71VAL SEZ-KD71VAQ (External static pressure 5Pa) 220-240V 50/60Hz (External static pressure 15Pa) 220-240V 50/60Hz 40 50 40 20 Limit External static pressure (Pa) External static pressure (Pa) 30 30 Limit 20 High Rated point 10 High 10 Middle Middle Rated point Low Low 0 0 11 12 13 14 15 16 17 Airflow rate(m3/min) 18 19 20 21 80 70 70 60 60 Limit 50 High 40 Rated point 30 12 13 14 15 16 17 Airflow rate(m3/min) 18 19 20 21 (External static pressure 50Pa) 220-240V 50/60Hz 80 Middle External static pressure (Pa) External static pressure (Pa) (External static pressure 35Pa) 220-240V 50/60Hz 11 20 Limit High 50 Rated point 40 Middle 30 20 Low Low 10 10 0 0 11 12 13 OCS25 14 15 16 17 Airflow rate(m3/min) 18 19 20 21 11 40 12 13 14 15 16 17 Airflow rate(m3/min) 18 19 20 21 8-4. PLA-RP·BA 8-4-1 FRESH AIR INTAKE AND BRANCH DUCT 1. Branch duct hole and fresh air intake hole (Fig. 1) At the time of i nstallation, use the duct holes ( cut out) located at the positions shown in Fig.1, as and when required. • A fresh air intake hole for the optional multi function casement can also be made. Note: The figure marked with * in the drawing represent the dimensions of the main unit excluding those of the optional multi function casement. When installing the optional multi function casement, add 135 mm to the dimensions marked on the figure. When installing the branch ducts, be sure to insulate adequately. Otherwise condensation and dripping may occur. When installing the fresh air intake hole, be sure to remove the insulator that is pasted on the indoor unit. Unit : mm Fresh air intake hole Detailed figure of removing the insulator Branch duct hole Fresh air intake hole diagram 3-:2.8 burring hole :125 burring 120 hole pitch *158 120 Indoor unit :100 cut out hole Ceiling Insulator Drain pipe Refrigerant pipe 100 90 100 100 130 90 Branch duct hole diagram (view from either side) *167 *155 70 350 :175 burring hole pitch 14-:2.8 burring hole :150 cut out hole Fig. 1 2. Fresh air intake (Installation at site) ● By mounting the optional multi-function casement to the indoor unit main body, and mounting the duct and duct flange (option) onto it further, fresh exterior air intake can be accomplished. (The mounting of the multi-function casement increases the height of the ceiling plenum by 135 mm.) OCS25 41 3. Fresh air intake volume & static pressure characteristics PLA-RP35~71BA At using multi-function casement, standard filter 50 -50 2 - inlet -100 How to read the chart 1 - inlet 0 1 2 3 4 5 Line of chart 0 6 Field duct characteristics A -200 1 Air flow rate [m3/min] Q Direct intake to unit 2 C A 50 E 0 D 3 -100 A Static pressure[Pa] Q -50 Q Qa -150 -200 0 1 2 3 4 5 6 Air flow rate [m3/min] At using multi-function casement, high efficiency filter 50 Static pressure[Pa] 0 -50 2 - inlet -100 -150 -200 1 - inlet 0 1 OCS25 2 3 Air flow rate [m3/min] 4 5 6 42 C -150 B Static pressure[Pa] 0 Q…Designed fresh air intake volume <m3/min> A…Static pressure loss [Pa] of fresh air intake duct at airflow rate of Q B…Required boost pressure [Pa] of air conditioner inlet at airflow rate of Q C…Required static pressure [Pa] of booster fan at airflow rate of Q D…Required compensation [Pa] for static pressure loss of fresh air intake duct to make airflow rate Q E…Static pressure [Pa] of indoor unit at airflow rate of Q Qa…Estimated fresh air intake [m3/min] without compensation of D 4. Change of outlet numbers Indoor unit [The optional air outlet is necessary.] To change the air outlet number to 3-, or 2-way outlet, the outlet number should be closed with the operational air outlet shutter. (When the air outlets are closed, close the vane by removing the vane connector.) Outlet concave portion Button Vane motor Up/down vanes Connector Air outlet shutter plate (Option) Vane motor Connector Button 5. Branch duct and change of outlet numbers * Branch duct should be connected to one of the branch duct holes on the main unit. <4- way air flow and branch duct> Branch duct Air intake Air outlet * Close the outlet on the side of branch duct and air flows in 3 directions. <3- way air flow and branch duct> Branch duct Air intake Air outlet Air outlet closed position * The outlet on the side of branch duct and one of the other outlets are closed. Air flows in 2 directions. <2- way air flow and branch duct> Branch duct Air intake Air Air outlet outlet closed closed position position OCS25 Air outlet closed position 43 PLA-RP71BA 4-way airflow (horizontal vane) Round duct 4-way airflow (horizontal vane) Rectangular duct 30 Duct Static pressure [Pa] Static pressure [Pa] 30 20 10 High Duct 20 10 High Low Low 0 0 0 2 4 6 Airflow rate [m3/min] 0 8 3-way airflow (horizontal vane) Round duct 2 80 70 70 Duct Duct 60 Close Static pressure [Pa] Static pressure [Pa] 60 50 40 30 Close 50 40 30 High 20 20 High Low 10 0 Low 10 2 4 6 8 Airflow rate [m3/min] 0 10 2-way airflow (horizontal vane) Round duct 0 100 90 90 Duct 2 Duct 80 Close Close 10 Close Close Static pressure [Pa] 70 60 50 40 30 High 20 4 6 8 Airflow rate [m3/min] 2-way airflow (horizontal vane) Rectangular duct 100 80 Static pressure [Pa] 8 3-way airflow (horizontal vane) Rectangular duct 80 0 4 6 Airflow rate [m3/min] 70 60 50 40 30 20 Low Low High 10 10 0 0 0 2 4 6 8 10 Airflow rate [m3/min] 0 12 2 4 6 8 10 Airflow rate [m3/min] • Use 1 of the 2 duct holes on the indoor unit. • Air flow rate of PLA-RP35~60BA can be calculated from the airflow rate based on the characteristic of the duct for PLA-RP71BA. • Use the optional air outlet shutter plate (PAC-SH51SP-E) for 3-way and 2-way air flow. OCS25 44 12 8-5. PCA-RP·KAQ 8-5-1. Fresh air intake amount & static pressure characteristics PCA-RP60, 71KAQ 50 50 0 0 Static pressure[Pa] Static pressure[Pa] PCA-RP50KAQ -50 -100 -150 -200 -250 -300 -50 -100 -150 -200 -250 -300 0 1 2 3 0 4 1 2 3 4 Airflow rate[m³/min] Airflow rate[m³/min] How to read the chart A 0 Duct characteristics at site Q E C A 2 Q A D 3 Q Qa OCS25 45 C Curve in the graphs B 1 Q…Designed amount of fresh air intake <m3/min> A…Static pressure loss of fresh air intake duct system with airflow amount Q <Pa> B…Forced static pressure at air conditioner inlet with airflow amount Q <Pa> C…Static pressure of booster fan with airflow amount Q <Pa> D…Static pressure loss increase amount of fresh air intake duct system for airflow amount Q <Pa> E…Static pressure of indoor unit with airflow amount Q Qa…Estimated amount of fresh air intake without D <m3/min> 8-6. PEAD-RP·JAQ PEAD-RP·JALQ 8-6-1. Fan performance PEAD-RP35JAQ PEAD-RP35JALQ (External static pressure 35Pa) 220-240V 50Hz (External static pressure 100Pa) 220-240V 50Hz 120 60 110 Limit External static pressure (Pa) External static pressure (Pa) Rated point 100 50 40 Rated point High 30 Middle 20 Low 10 Limit 90 High 80 70 Middle 60 50 Low 40 30 20 10 0 7 9 11 13 15 17 19 0 21 7 9 11 13 (External static pressure 50Pa) 220-240V 50Hz 17 19 21 (External static pressure 150Pa) 220-240V 50Hz 70 170 160 Rated point 150 60 140 Limit External static pressure (Pa) External static pressure (Pa) 15 Airflow rate(m3/min) Airflow rate(m /min) 3 Rated point 50 High 40 Middle 30 Low 20 Limit 130 High 120 110 100 Middle 90 80 70 Low 60 50 40 30 10 20 10 0 7 9 11 13 15 17 19 0 21 Airflow rate(m3/min) 90 80 External static pressure (Pa) Rated point Limit High 60 50 Middle 40 Low 30 20 10 0 7 9 11 OCS25 13 15 Airflow rate(m3/min) 9 11 13 15 Airflow rate(m3/min) (External static pressure 70Pa) 220-240V 50Hz 70 7 17 19 21 46 17 19 21 PEAD-RP50JAQ PEAD-RP50JALQ (External static pressure 100Pa) 220-240V 50Hz (External static pressure 35Pa) 220-240V 50Hz 130 70 120 110 60 50 High 40 Rated point Middle 30 Low 20 Rated point Limit 100 External static pressure (Pa) External static pressure (Pa) Limit 90 High 80 70 Middle 60 50 Low 40 30 20 10 10 0 9 14 0 19 9 14 19 Airflow rate(m3/min) Airflow rate(m /min) 3 (External static pressure 50Pa) 220-240V 50Hz (External static pressure 150Pa) 220-240V 50Hz 180 80 170 160 70 External static pressure (Pa) External static pressure (Pa) Rated point 50 High 140 High 60 Middle 40 30 Rated point 150 Limit Low 20 Limit 130 120 110 Middle 100 90 80 Low 70 60 50 40 10 30 20 0 9 14 10 19 0 Airflow rate(m /min) 3 9 14 Airflow rate(m3/min) (External static pressure 70Pa) 220-240V 50Hz 100 90 External static pressure (Pa) 80 Limit Rated point 70 High 60 50 Middle 40 30 Low 20 10 0 9 14 19 Airflow rate(m3/min) OCS25 47 19 PEAD-RP60JAQ PEAD-RP60JALQ (External static pressure 100Pa) 220-240V 50Hz (External static pressure 35Pa) 220-240V 50Hz 120 60 110 50 Rated point 100 External static pressure (Pa) External static pressure (Pa) Limit 40 Rated point 30 High 20 Middle 90 Limit High 80 70 Middle 60 50 Low 40 30 Low 10 20 10 0 10 15 20 25 0 10 30 15 Airflow rate(m3/min) 20 (External static pressure 50Pa) 220-240V 50Hz (External static pressure 150Pa) 220-240V 50Hz 160 Rated point 150 Limit 140 Rated point 50 External static pressure (Pa) External static pressure (Pa) 30 170 70 60 25 Airflow rate(m3/min) High 40 Middle 30 20 Low High 130 Limit 120 110 100 Middle 90 80 70 60 Low 50 40 30 10 20 10 0 10 15 20 25 0 30 Airflow rate(m3/min) 90 80 Rated point External static pressure (Pa) Limit High 60 50 Middle 40 30 Low 20 10 0 10 15 20 25 30 Airflow rate(m3/min) OCS25 15 20 Airflow rate(m3/min) (External static pressure 70Pa) 220-240V 50Hz 70 10 48 25 30 PEAD-RP71JAQ PEAD-RP71JALQ (External static pressure 100Pa) 220-240V 50Hz (External static pressure 35Pa) 220-240V 50Hz 70 130 120 60 High 110 Rated point 50 External static pressure (Pa) External static pressure (Pa) 100 Limit High 40 Rated point 30 Middle 20 Low Limit 90 Middle 80 70 60 Low 50 40 30 10 20 10 0 10 15 20 25 0 30 10 15 Airflow rate(m /min) 3 20 25 30 Airflow rate(m3/min) (External static pressure 50Pa) 220-240V 50Hz (External static pressure 150Pa) 220-240V 50Hz 90 180 170 High 160 80 Rated point 150 140 External static pressure (Pa) External static pressure (Pa) 70 Limit 60 High Rated point 50 Middle 40 30 Low 20 130 Middle Limit 120 110 100 90 80 Low 70 60 50 40 30 10 20 10 0 10 15 20 25 0 30 Airflow rate(m3/min) 100 90 High External static pressure (Pa) 80 Limit Rated point 70 Middle 50 40 Low 30 20 10 0 10 15 20 25 30 Airflow rate(m3/min) OCS25 15 20 Airflow rate(m3/min) (External static pressure 70Pa) 220-240V 50Hz 60 10 49 25 30 NOISE CRITERION CURVES 9 <50Hz> NOTCH SPL(dB) High 38 Medium 33 Low 29 LINE 90 90 80 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 <50Hz> SLZ-KA50VAL SLZ-KA50VAQ OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) SLZ-KA25VAL2 SLZ-KA25VAQ2 SLZ-KA35VAL SLZ-KA35VAQ 70 LINE NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 8000 NOTCH SPL(dB) High 39 Medium 34 Low 30 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 BAND CENTER FREQUENCIES, Hz NC-20 250 500 1000 2000 4000 8000 BAND CENTER FREQUENCIES, Hz UNIT CEILING 1.5m MICROPHONE NOTE: The sound level is measured in an anechoic room where echoes are few, when compressor stops. The sound may be bigger than the indicated level in actual use due to surrounding echoes. The sound level can be higher by about 2 dB than the indicated level during cooling and heating operation. OCS25 50 SEZ-KD25VAL SEZ-KD25VAQ External static pressure: 5Pa NOTCH SPL(dB) High 29 Middle 25 Low 22 External static pressure: 15Pa LINE 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE NC-20 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) 80 10 80 70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 63 125 250 500 1000 2000 4000 NC-70 8000 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 External static pressure: 35Pa NOTCH SPL(dB) High 31 Middle 28 Low 24 500 1000 2000 4000 8000 NOTCH SPL(dB) High 33 Middle 29 Low 25 LINE 90 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) 250 External static pressure: 50Pa LINE 90 10 NC-20 BAND CENTER FREQUENCIES, Hz BAND CENTER FREQUENCIES, Hz 20 LINE 90 90 20 NOTCH SPL(dB) High 30 Middle 26 Low 23 80 70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 8000 BAND CENTER FREQUENCIES, Hz NC-70 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 8000 BAND CENTER FREQUENCIES, Hz NOTE: The sound level is measured in an anechoic room where echoes are few, when compressor stops. The sound may be bigger than indicated level in actual use due to surrounding echoes. The sound level can be higher by about 2 dB than the indicated level during cooling and heating operation. OCS25 51 SEZ-KD35VAL SEZ-KD35VAQ External static pressure: 5Pa NOTCH SPL(dB) High 33 Middle 28 Low 23 LINE External static pressure: 15Pa 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE NC-20 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) 80 10 80 70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 63 125 250 500 1000 2000 4000 NC-70 8000 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 External static pressure: 35Pa NOTCH SPL(dB) High 34 Middle 29 Low 24 LINE 500 1000 2000 4000 8000 NOTCH SPL(dB) High 35 Middle 31 Low 25 LINE 90 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 8000 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) 250 External static pressure: 50Pa 90 10 NC-20 BAND CENTER FREQUENCIES, Hz BAND CENTER FREQUENCIES, Hz 20 LINE 90 90 20 NOTCH SPL(dB) High 33 Middle 28 Low 23 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 BAND CENTER FREQUENCIES, Hz APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 8000 BAND CENTER FREQUENCIES, Hz NOTE: The sound level is measured in an anechoic room where echoes are few, when compressor stops. The sound may be bigger than indicated level in actual use due to surrounding echoes. The sound level can be higher by about 2 dB than the indicated level during cooling and heating operation. OCS25 52 SEZ-KD50VAL SEZ-KD50VAQ External static pressure: 5Pa NOTCH SPL(dB) High 36 Middle 33 Low 29 External static pressure: 15Pa LINE 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 80 70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 8000 NC-70 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 BAND CENTER FREQUENCIES, Hz External static pressure: 35Pa NOTCH SPL(dB) High 38 Middle 35 Low 31 500 1000 2000 4000 8000 NOTCH SPL(dB) High 39 Middle 36 Low 32 LINE 90 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) 250 External static pressure: 50Pa LINE 80 10 NC-20 BAND CENTER FREQUENCIES, Hz 90 20 LINE 90 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) 90 NOTCH SPL(dB) High 37 Middle 34 Low 30 80 70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 8000 NC-70 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 8000 BAND CENTER FREQUENCIES, Hz BAND CENTER FREQUENCIES, Hz NOTE: The sound level is measured in an anechoic room where echoes are few, when compressor stops. The sound may be bigger than the indicated level in actual use due to surrounding echoes. The sound level can be higher by about 2 dB than the indicated level during cooling and heating operation. OCS25 53 SEZ-KD60VAL SEZ-KD60VAQ External static pressure: 5Pa NOTCH SPL(dB) High 37 Middle 33 Low 29 LINE External static pressure: 15Pa 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 8000 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 BAND CENTER FREQUENCIES, Hz External static pressure: 35Pa NOTCH SPL(dB) High 39 Middle 35 Low 31 LINE 500 External static pressure: 50Pa 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) 250 1000 2000 4000 8000 NOTCH SPL(dB) High 39 Middle 36 Low 32 LINE 90 80 10 NC-20 BAND CENTER FREQUENCIES, Hz 90 20 LINE 90 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) 90 NOTCH SPL(dB) High 38 Middle 34 Low 30 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE NC-20 10 8000 63 BAND CENTER FREQUENCIES, Hz 125 250 500 1000 2000 4000 8000 BAND CENTER FREQUENCIES, Hz NOTE: The sound level is measured in an anechoic room where echoes are few, when compressor stops. The sound may be bigger than the indicated level in actual use due to surrounding echoes. The sound level can be higher by about 2 dB than the indicated level during cooling and heating operation. OCS25 54 SEZ-KD71VAL SEZ-KD71VAQ External static pressure: 5Pa NOTCH SPL(dB) High 39 Middle 34 Low 29 External static pressure: 15Pa LINE 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 80 70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 8000 NC-70 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 BAND CENTER FREQUENCIES, Hz External static pressure: 35Pa NOTCH SPL(dB) High 41 Middle 36 Low 31 500 1000 2000 4000 8000 NOTCH SPL(dB) High 42 Middle 37 Low 32 LINE 90 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) 250 External static pressure: 50Pa LINE 80 10 NC-20 BAND CENTER FREQUENCIES, Hz 90 20 LINE 90 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) 90 NOTCH SPL(dB) High 40 Middle 35 Low 30 80 70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 8000 NC-70 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 8000 BAND CENTER FREQUENCIES, Hz BAND CENTER FREQUENCIES, Hz Aux. duct OCS25 55 test unit 1m 2m Measurement location 1.5m NOTE: The sound level is measured in an anechoic room where echoes are few, when compressor stops. The sound may be bigger than the indicated level in actual use due to surrounding echoes. The sound level can be higher by about 2 dB than the indicated level during cooling and heating operation. PLA-RP35BA NOTCH SPL(dB) High 31 Medium1 29 Medium2 28 Low 27 LINE PLA-RP50BA 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 8000 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 BAND CENTER FREQUENCIES, Hz PLA-RP60BA NOTCH SPL(dB) High 32 Medium1 31 Medium2 29 Low 28 LINE 500 PLA-RP71BA 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) 250 1000 2000 4000 8000 NOTCH SPL(dB) High 34 Medium1 32 Medium2 30 Low 28 LINE 90 80 10 NC-20 BAND CENTER FREQUENCIES, Hz 90 20 LINE 90 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) 90 NOTCH SPL(dB) High 32 Medium1 31 Medium2 29 Low 28 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 8000 BAND CENTER FREQUENCIES, Hz OCS25 80 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 BAND CENTER FREQUENCIES, Hz 56 4000 8000 PEAD-RP35JAQ PEAD-RP35JALQ External static pressure 35Pa High Middle Low 80 Ceiling concealed OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) 2m 70 2m Aux.duct NC-70 1.5m 60 NC-60 50 NC-50 Measurement location 40 NC-40 Noise level at anechoic room (Low-Middle-High) Unit: dB(A) 30 NC-30 Approximate minimum audible limit on continuous noise NC-20 10 0 63 125 250 500 1000 2000 4000 8000 BAND CENTER FREQUENCIES, Hz OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) 80 PEAD-RP60JA(L)Q 25-28-32 25-29-33 26-30-34 27-31-35 29-34-38 PEAD-RP71JA(L)Q 25-29-34 26-30-34 27-31-35 28-32-36 30-35-39 External static pressure 100Pa NC-60 50 NC-50 40 NC-40 30 NC-30 NC-20 10 63 125 250 500 1000 2000 4000 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 Approximate minimum audible limit on continuous noise 63 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) NC-60 50 NC-50 40 NC-40 30 NC-30 Approximate minimum audible limit on continuous noise NC-20 10 OCS25 250 500 1000 2000 BAND CENTER FREQUENCIES, Hz 500 1000 2000 4000 8000 4000 High Middle Low 80 60 125 250 External static pressure 150Pa NC-70 63 125 BAND CENTER FREQUENCIES, Hz 70 0 NC-20 10 0 8000 High Middle Low 80 20 High Middle Low 70 BAND CENTER FREQUENCIES, Hz External static pressure 70Pa 150Pa 25-30-34 26-31-35 28-32-36 29-33-37 31-35-39 NC-70 Approximate minimum audible limit on continuous noise 100Pa 23-26-29 23-27-30 24-28-31 26-29-33 29-33-37 60 0 70Pa 80 70 20 50Pa PEAD-RP50JA(L)Q High Middle Low External static pressure 50Pa 35Pa PEAD-RP35JA(L)Q OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) 20 Exrernal static pressure Model 70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 Approximate minimum audible limit on continuous noise NC-20 10 0 8000 NC-70 63 125 250 500 1000 2000 BAND CENTER FREQUENCIES, Hz 57 4000 8000 PEAD-RP50JAQ PEAD-RP50JALQ 80 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) External static pressure 100Pa High Middle Low 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 Approximate minimum audible limit on continuous noise NC-20 10 0 63 125 250 500 1000 2000 4000 70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 Approximate minimum audible limit on continuous noise 63 NC-70 NC-60 50 NC-50 40 NC-40 30 NC-30 Approximate minimum audible limit on continuous noise NC-20 10 63 125 250 500 1000 2000 4000 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 Approximate minimum audible limit on continuous noise NC-20 10 0 63 125 250 500 1000 2000 4000 8000 BAND CENTER FREQUENCIES, Hz OCS25 2000 4000 8000 High Middle Low NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 Approximate minimum audible limit on continuous noise NC-20 10 63 125 250 500 1000 2000 BAND CENTER FREQUENCIES, Hz High Middle Low 80 1000 70 0 8000 BAND CENTER FREQUENCIES, Hz External static pressure 70Pa 500 80 60 0 250 External static pressure 150Pa OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) 70 20 125 BAND CENTER FREQUENCIES, Hz High Middle Low 80 NC-20 10 0 8000 NC-70 BAND CENTER FREQUENCIES, Hz External static pressure 50Pa High Middle Low 80 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) External static pressure 35Pa 58 4000 8000 PEAD-RP60JAQ PEAD-RP60JALQ External static pressure 35Pa 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 Approximate minimum audible limit on continuous noise NC-20 10 0 63 125 250 500 1000 2000 4000 70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 Approximate minimum audible limit on continuous noise 63 NC-70 NC-60 50 NC-50 40 NC-40 30 NC-30 Approximate minimum audible limit on continuous noise NC-20 10 63 125 250 500 1000 2000 4000 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 Approximate minimum audible limit on continuous noise NC-20 10 0 63 OCS25 125 250 500 1000 2000 BAND CENTER FREQUENCIES, Hz 2000 4000 8000 High Middle Low NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 Approximate minimum audible limit on continuous noise NC-20 10 63 125 250 500 1000 2000 BAND CENTER FREQUENCIES, Hz High Middle Low 80 1000 70 0 8000 BAND CENTER FREQUENCIES, Hz External static pressure 70Pa 500 80 60 0 250 External static pressure 150Pa OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) 70 20 125 BAND CENTER FREQUENCIES, Hz High Middle Low 80 NC-20 10 0 8000 NC-70 BAND CENTER FREQUENCIES, Hz External static pressure 50Pa High Middle Low 80 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) 80 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) External static pressure 100Pa High Middle Low 4000 8000 59 4000 8000 PEAD-RP71JAQ PEAD-RP71JALQ 80 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) External static pressure 100Pa High Middle Low 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 Approximate minimum audible limit on continuous noise NC-20 10 0 63 125 250 500 1000 2000 4000 70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 Approximate minimum audible limit on continuous noise 63 NC-70 NC-60 50 NC-50 40 NC-40 30 NC-30 Approximate minimum audible limit on continuous noise NC-20 10 63 125 250 500 1000 2000 4000 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 Approximate minimum audible limit on continuous noise NC-20 10 0 63 125 250 500 1000 2000 BAND CENTER FREQUENCIES, Hz OCS25 2000 4000 8000 High Middle Low NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 Approximate minimum audible limit on continuous noise NC-20 10 63 125 250 500 1000 2000 BAND CENTER FREQUENCIES, Hz High Middle Low 80 1000 70 0 8000 BAND CENTER FREQUENCIES, Hz External static pressure 70Pa 500 80 60 0 250 External static pressure 150Pa OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) 70 20 125 BAND CENTER FREQUENCIES, Hz High Middle Low 80 NC-20 10 0 8000 NC-70 BAND CENTER FREQUENCIES, Hz External static pressure 50Pa High Middle Low 80 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) External static pressure 35Pa 4000 8000 60 4000 8000 PCA-RP50KAQ NOTCH SPL(dB) 40 High 37 Medium1 34 Medium2 32 Low PCA-RP60KAQ LINE 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) 80 10 LINE 90 90 20 NOTCH SPL(dB) High 40 Medium1 37 Medium2 35 Low 33 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 10 8000 63 BAND CENTER FREQUENCIES, Hz PCA-RP71KAQ NOTCH SPL(dB) High 41 Medium1 39 Medium2 37 Low 35 NC-20 125 250 500 1000 2000 4000 8000 BAND CENTER FREQUENCIES, Hz LINE OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) 90 80 70 NC-70 ceiling 1m 60 NC-60 1m 50 about 1.4m NC-50 MICROPHONE 40 NC-40 30 NC-30 20 10 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 8000 BAND CENTER FREQUENCIES, Hz OCS25 61 unit SUZ-KA25VA3 SUZ-KA35VA3 OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR High Med. SPL(dB(A)) COOLING 47 HEATING 48 High Med. 90 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 NC-20 NC-10 10 63 125 250 500 1000 2000 FAN SPEED FUNCTION LINE 4000 8000 OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR FAN SPEED FUNCTION 50 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 NC-20 NC-10 10 63 125 250 500 1000 2000 4000 8000 SUZ-KA60VA3 SUZ-KA71VA3 SPL(dB(A)) COOLING High 52 HEATING High 52 90 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 NC-20 NC-10 125 250 500 FAN SPEED FUNCTION LINE 1000 2000 4000 8000 OCTAVE BAND SOUND PRESSURE LEVEL, 0dB re 0.0002 MICRO BAR FAN SPEED FUNCTION OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR HEATING LINE BAND CENTER FREQUENCIES, Hz SUZ-KA50VA3 63 49 90 BAND CENTER FREQUENCIES, Hz 10 SPL(dB(A)) COOLING SPL(dB(A)) COOLING 55 HEATING 55 90 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 NC-20 NC-10 10 63 125 250 500 1000 2000 4000 8000 BAND CENTER FREQUENCIES, Hz BAND CENTER FREQUENCIES, Hz Test conditions Cooling: Dry-bulb temperature 35°C Heating: Dry-bulb temperature 7°C Wet-bulb temperature 6°C OUTDOOR UNIT 1m MICROPHONE OCS25 LINE 62 10 OPTIONAL PARTS INDOOR UNIT Part Name Model Name Remote sensor PAC-SE41TS-E Multiple remote controller adapter PAC-SA88HA-E(1pc.) PAC-725AD(10pcs.) Applicable model All models Remote on/off adapter PAC-SE55RA-E Remote operation adapter PAC-SF40RM-E All models excpet wireless remote controller use model MA & contact terminal interface MAC-397IF-E All models System control interface MAC-333IF All models Drain pump PAC-KE07DM-E SEZ-KD·VAL/SEZ-KD·VAQ Wired remote controller PAR-30MAA, PAR-21MAA All models Decoration panel PLP-6BA Decoration panel with wireless remote controller PLP-6BALM Decoration panel with wired remote controller PLP-6BAM Automatic filter elevation panel PLP-6BAJ i-see sensor corner panel PAC-SA1ME-E Wireless signal receiver PAR-SA9FA-E Space panel PAC-SH48AS-E Air outlet shutter plate PAC-SH51SP-E Multi-function casement PAC-SH53TM-E Flange for fresh air intake PAC-SH65OF-E High-efficiency filter element (PAC-SH53TM-E is needed.) PAC-SH59KF-E Wireless remote controller kit PAR-SL94B-E PCA-RP·KAQ Drain pump PAC-SH83DM-E PCA-RP50KAQ PAC-SH85DM-E PCA-RP60KAQ PAC-SH84DM-E PCA-RP71KAQ High-efficiency filter Filter box OCS25 63 PLA-RP·BA PAC-SH88KF-E PCA-RP50KAQ PAC-SH89KF-E PCA-RP60, 71KAQ PAC-KE92TB-E PEAD-RP35, 50JA(L)Q PAC-KE93TB-E PEAD-RP60, 71JA(L)Q HEAD OFFICE : TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN CCopyright 2013 MITSUBISHI ELECTRIC CORPORATION Distributed in Mar. 2013 No.OCS25 Made in Japan New publication, effective Mar. 2013 Specifications are subject to change without notice.