A U T O - T E S T TM & S I M P L E - T E S T TM
FIRE DOOR CLOSING SYSTEMS
The Cookson Company, Inc.
A U T O - T E S T TM F I R E D O O R C L O S I N G S Y S T E M S
Operating System Benefits
x Automatic resetting of the automatic closing system yields dramatic savings for building owners in
testing and resetting costs as well as minimized opening downtime.
x Any application where mechanical testing and resetting is
failure without requiring connection to a separate alarm interface, fusible link release device.
x Activation by fire alarm system or smoke detector is
and larger doors.
‡ System automatically resets to normal operation upon clearing of alarm signal and / or
restoration of power.
‡ Routine testing of the automatic closing system occurs in minutes from floor level by factory
personnel.
‡ Required annual inspection by a trained fire door systems technician is simplified.
Safe, controlled automatic closing speed will not exceed 12” per second.
UL approval allows Cookson to retrofit Auto-Test motor, chain, and crank operators to most
manufacturers’ fire doors while maintaining the door’s listing agency ratings.
x Where fire doors are installed within pedestrian
x Auto-Test systems are directly wired for activation by fire alarm systems, local detectors or power
x Eliminate mechanical spring release and complicated testing and resetting, especially on recessed
x
x
Recommended Applications for
Auto-Test Fire Door Closing Systems:
AUTO-TEST
TM
impractical or not desired.
desired or required.
thoroughfares.
x Fire-rated units in recessed applications.
x Units in areas susceptible to frequent power outages.
MOTOR OPERATORS
These systems close the fire door in response to an alarm signal and are fail-safe by design, safely closing the door
during a prolonged power failure. When the alarm is cleared and/or power is restored, resetting is done at floor level
with the touch of the “open” button. Unlike conventional fire door operators, Auto-Test Motor Operators do not require an
additional mechanical release device to respond to central alarm signals or local smoke detectors.
Benefits:
Slower, safer, uniform closing speed not to exceed 9” per second.
1 to 10 second selectable time delay.
Recommended Applications: All motor operated fire doors.
Options: Battery Back-Up, Horn Strobe, Voice Warning Module, Sensing Devices and more.
AUTO-TEST
TM
TUBE MOTOR OPERATORS
For Counter Fire Doors with or without Integral Frame and Sill
Auto-Test Tube Motor Operators are concealed in the Counter Fire Door’s shaft assembly making them ideal for
openings with tight clearances around the coil area or to neatly conceal the operator and drive components. Closing
speed not to exceed 12” per second. 115 VAC power required for motor, 24 VDC, 115 VAC or 24 VAC required for
control panel. Available for Counter Fire Doors up to 14’ 0” wide, 9’ 0” high up to 90 square feet or Counter Fire Doors
with Integral Frame and Sill up to 10’ 0” wide by 4’ 9” high.
Benefits:
x Convenience of ergonomic motor operation in an aesthetic, low profile design.
x Full height openings from floor to 9’ 0” high.
Recommended Applications:
x Fire shutters that require the convenience of a motor operator in limited headroom conditions.
x Aesthetic motor operation that eliminates the need for a bulky motor cover.
Options: Control Stations, Key Test Stations, Sensing Devices, Battery Back-Up and more.
AUTO-TEST
TM
Protected by U.S. Patent # 6155324
CHAIN & CRANK OPERATORS
These compact designs include a built-in automatic reset device for connection to a central alarm system or local
detectors - no external device is required. Units will close automatically upon alarm or power failure in excess of 10
seconds. Resetting spring tension or re-engaging the operator is not required. Auto-Test Chain and Crank Operators
are available for use on Fire Doors, Insulated Fire Doors, and Counter Fire Doors.
Benefits:
x Integral governing device provides safer closing speed, not to exceed 12” per second.
x Accepts 24V DC, 115V AC or 24V AC power supply.
x UL 864 Listing.
x 10 second alarm and power failure time delay.
x 24V DC output for close warning device.
Recommended Applications:
x Use for fire products that do not require the daily operating convenience of a motor operator.
x Clearance and access to the hand chain or crank eye is required.
Options: Electric Key Switch, Battery Back-Up, Horn Strobe and more.
S I M P L E - T E S T TM F I R E D O O R C L O S I N G S Y S T E M S
Operating System Benefits:
Recommended Applications for
Simple-Test Fire Door Closing Systems:
x Close fire rated doors without releasing spring tension, avoiding dangerous resetting process.
x Fuselink activated.
x Simple system reset by reconnecting the fuselink.
x Annual inspection by a trained fire door system technician is required.
x Systems will not automatically close upon power failure.
x Economical
x Opening is not a pedestrian thoroughfare.
x Connection to Central Alarm System or Local Smoke
Detectors is not required by local building officials.
x Applications where the installation of fusible links,
turnbuckles, chains and eyebolts to the face of both sides
of the wall above the opening will not detract from the
intended aesthetics.
System Options:
x Floor level test device - allows system testing at floor level rather than above coil at fuselink location.
SIMPLE-TEST
TM
MOTOR OPERATORS
UL and FM listed, industrial duty gear head operator recommended for units that normally cycle up to 20 times
per day. HP available: 1/3, 1/2 and 3/4. Available for Fire Doors, Insulated Fire Doors, and Counter Fire Doors.
Features and Benefits:
x Economical.
x Spring tension is not released upon fuselink closing.
x Convenience of motor operation.
x Auxiliary Chain for emergency operation, just pull to operate.
x Average closing speed of 6 - 24” per second.
Options: Floor Level Test Switch, Sensing Devices, Release Devices, Battery Back-Up.
SIMPLE-TEST
TM
CHAIN AND CRANK OPERATORS
Available for use on Fire Doors, Insulated Fire Doors, and Counter Fire
Doors.
Features and Benefits:
x Economical.
x Power not required.
x Spring tension is not released upon fuselink closing.
x Maximum closing speed of 12” per second.
Options: Floor Level Test Switch, Releasing Devices, Battery Back-Up.
RETROFIT OPERATORS
Special UL approval allows Cookson to retrofit Auto-Test
and Simple-Test operators to most manufacturers’ fire
doors while still maintaining the door’s listing agency
ratings. See chart on the next page for models.
PUSH UP OPERATION, SPECIALTY OPERATORS
Specialty Operators and Push-Up Operators are available. These conventional systems
release spring tension and require mechanical resetting by a trained door system technician.
The Cookson Company, Inc.
A U T O - T E S T TM A N D S I M P L E - T E S T TM F I R E D O O R C L O S I N G S Y S T E M
FIRE DOOR CLOSING SYSTEMS ALTERNATIVES
Auto-Test
Motor
Auto-Test
Auto-Test
Tube Motor Chain & Crank
Simple-Test
Simple-Test
Fuselink Closing
Motor
Chain & Crank
(Push Up Only)
Activation by fire alarm systems, local detectors or power failure without
separate interface / device.
„
„
„
Fail safe operation: fire doors will close during power failure.
„
„
„
System automatically resets on clearing of alarm or restoration of power.
„
„
„
No mechanical spring release, avoiding tension reset at coil.
„
„
„
„
„
Routine testing of closing system occurs in minutes from floor level by
factory personnel.
„
„
„
†
†
Required annual inspection by trained fire systems technician is simplified.
„
„
„
„
„
9 ips
12 ips
12 ips
6-24 ips
avg.
12 ips
Controlled rate of descent not to exceed (inches per second).
Power is unavailable at opening.
UL approval for retrofit while maintaining door’s listing.
„
„
„
„
„
Fuselink closing. Testing releases spring tension, causing extended
opening down time and requiring mechanical reset at coil by trained
technician. Not fail safe. Consistent with conventional systems.
„
†Available as an option
FIRE DOOR CLOSING SYSTEM ACCESSORIES
Battery Back-Up Devices
Release Devices for Simple-Test Operating Systems
Available for Auto-Test and Simple-Test Motor, Chain, and
Crank Operators. Prevents the door from closing due to a
power failure for a minimum of 4 hours. For Auto-Test Motor
Operators the battery back-up also functions as a DC power
source for local warning devices and detectors to keep them
functioning during a power outage and can be programmed to
cycle the door a selected number of times should the sensing
edge contact an obstruction during alarm signal AC power closing.
Electro-mechanical devices enable Simple-Test Closing systems to respond
to alarm signals from detection devices such as smoke detectors, heat
sensors and central alarm systems, permitting doors to close long before
high temperatures melt fusible links. Fusible links should always be used as
a backup to the release device.
Note that Auto-Test Closing Systems include the functionality of release
devices as standard.
Firefly IV MVTM - A fail-safe and UL listed tri-voltage releasing device that accepts 120 or 24 VAC or
24 VDC input voltage. Does not require or have a battery back-up system or require up front electrical
coordination with alarm system providers. Down limit detection prevents mechanical release of a fully
closed door upon alarm signal: requires closed door signal.
UL 325 Compliant Entrapment Protection Devices for Motor
Operated Systems
Per UL 325-2010, doors without a connected and properly functioning primary
entrapment protection device will only function by constant pressure close operation.
The primary entrapment protection devices below enable momentary contact to close
operation:
ELR Electric Sensing Edge - 2 wire monitored electric sensing/smoke seal edge.
Contact with the edge before the door fully closes causes the door to immediately stop
downward travel and reverse direction to the fully open position. Requires a retracting
safety cord and reel or a self-coiling cable connection to control the circuit.
Photo Eyes - Interruption of the beam before the door fully closes causes the door to
immediately stop downward travel and reverse direction to the fully open position.
Optional Secondary Entrapment Protection Device may be used in conjunction with
a set of primary entrapment photo eyes or with constant pressure to close operation.
Electric Sensing Edge with Wireless Edge Kit - Eliminates the need for a physical
traveling electric cord connection between the bottom bar sensing edge device and the
motor operator. This system is self-monitoring and fail-safe.
Annunciators
Optional safety devices that provide a visual and/or audible advanced warning when
the door is about to close. Can be activated upon alarm signal or loss of power when
supported by a battery back-up device.
Horn Strobe - ADA compliant, 24 VDC warning devices that are powered by a release
device power source to provide an advanced fire door closing warning. Activation upon
alarm signal and power failure and/or alarm signal only depending on release device.
Voice Warning Module - An ADA compliant warning device. Provides up to four
different voice warning messages upon activation. Messages are in English and are
field selectable.
Floor Level Test Device for Simple-Test Chain & Crank
Safely and conveniently test and reset the fire door at floor level rather than by the