PRECAUTION

Window WDF Series

Models:

AWWR-WDF009-C11

AWWR-WDF012-C11

CONTENTS

CONTENTS

1.1 Safety Precaution. ..................................................................................................................................... 1

 

1.2 Warning ....................................................................................................................................................... 1

 

2. Specification. ................................................................................................................................................ 6

 

3. Dimension. .................................................................................................................................................... 7

 

4. Function and control panel. ........................................................................................................................ 8

 

4.1 Function. ..................................................................................................................................................... 8

 

4.2 Control panel. ............................................................................................................................................. 8

 

5. Refrigerant Cycle Diagram. ....................................................................................................................... 10

 

6. Wiring Diagram ...........................................................................................................................................11

 

7. Protection Function. .................................................................................................................................. 12

7.1 Proper symbols and their meaning ....................................................................................................... 12

7.2 Protection Function ................................................................................................................................. 12  

7.2.1 Three minutes delay at restart for compressor. ...................................................................................... 12 

7.2.2Anti-freezing protection at cooling or dry mode. ...................................................................................... 12 

7.2.3 Anti-frosting protection and defect at cooling or dry mode. .................................................................. 12 

7.2.4 Electronic function. ...................................................................................................................................... 13 

7.3 Temperature sensor is open circuit or short circuit. .................................................................................. 14 

8 Installation details ....................................................................................................................................... 15

 

8.1 Select the best location. .......................................................................................................................... 15

 

8.2 Check off installation............................................................................................................................... 16

 

8.3 How to drain. ............................................................................................................................................ 16

 

8.4 How to install. ........................................................................................................................................... 17

 

9 Operation characteristics .......................................................................................................................... 17

 

10 Characteristic of temperature sensor. .................................................................................................... 19

 

11 Troubleshooting ........................................................................................................................................ 20

 

12 Exploded view and part list ..................................................................................................................... 28

 

PRECAUTION

1. Precaution

1.1 Safety Precaution.

z To prevent injury to the user or other people and property damage, the following instructions

must be followed.

z Incorrect operation due to ignoring instruction will cause harm or damage.

Before service unit, be sure to read this service manual at first.

1.2 Warning

Installation

z Do not use a defective or underrated circuit breaker. Use this appliance on a dedicated circuit.

There is risk of fire or electric shock. z For electrical work, contact the dealer, seller, a qualified electrician, or an Authorized service

center.

Do not disassemble or repair the product, there is risk of fire or electric shock. z Always ground the product.

There is risk of fire or electric shock. z Install the panel and the cover of control box securely.

There is risk of fire of electric shock. z Always install a dedicated circuit and breaker.

Improper wiring or installation may cause fore or electric shock. z Use the correctly rated breaker of fuse.

There is risk of fire or electric shock. z Do not modify or extend the power cable.

There is risk of fire or electric shock. z Do not install, remove, or reinstall the unit by yourself(customer).

There is risk of fire, electric shock, explosion, or injury. z

Be caution when unpacking and installing the product.

Sharp edges could cause injury, be especially careful of the case edges and the fins on the condenser

Window WDF 1 Version - 0

PRECAUTION

and evaporator. z For installation, always contact the dealer or an Authorized service center.

There is risk of fire, electric shock, explosion, or injury. z Do not install the product on a defective installation stand.

It may cause injury, accident, or damage to the product. z Be sure the installation area does not deteriorate with age.

If the base collapses, the air conditioner could fall with it, causing property damage, product failure, and personal injury. z Do not let the air conditioner run for a long time when the humidity is very high and a door or a

window is left open.

Moisture may condense and wet or damage furniture. z Take care to ensure that power cable could not be pulled out or damaged during operation.

There is risk of fire or electric shock. z Do not place anything on the power cable.

There is risk of fire or electric shock. z Do not plug or unplug the power supply plug during operation.

There is risk of fire or electric shock. z Do not touch (operation) the product with wet hands.

There is risk of fire or electric shock. z Do not place a heater or other appliance near the power cable.

There is risk of fire and electric shock. z Do not allow water to run into electric parts.

It may cause fire, failure of the product, or electric shock. z Do not store or use flammable gas or combustible near the product.

There is risk of fire or failure of product. z Do not use the product in a tightly closed space for a long time.

Oxygen deficiency could occur. z When flammable gas leaks, turn off the gas and open a window for ventilation before turn the

product on.

Do not use the telephone or turn switches on or off. There is risk of explosion or fire. z If strange sounds, or small or smoke comes from product. Turn the breaker off or disconnect

Window WDF 2 Version - 0

PRECAUTION the power supply cable.

There is risk of electric shock or fire. z Stop operation and close the window in storm or hurricane. If possible, remove the product

from the window before the hurricane arrives.

There is risk of property damage, failure of product, or electric shock. z Do not open the inlet grill of the product during operation. (Do not touch the electrostatic filter,

if the unit is so equipped.)

There is risk of physical injury, electric shock, or product failure. z When the product is soaked (flooded or submerged), contact an Authorized service center.

There is risk of fire or electric shock. z Be caution that water could not enter the product.

There is risk of fire, electric shock, or product damage. z Ventilate the product from time to time when operating it together with a stove, etc.

There is risk of fire or electric shock. z Turn the main power off when cleaning or maintaining the product.

There is risk of electric shock. z When the product is not be used for a long time, disconnect the power supply plug or turn off

the breaker.

There is risk of product damage or failure, or unintended operation. z Take care to ensure that nobody could step on or fall onto the outdoor unit.

This could result in personal injury and product damage.

CAUTION

z Always check for gas (refrigerant) leakage after installation or repair of product.

Low refrigerant levels may cause failure of product. z Install the drain hose to ensure that water is drained away properly.

A bad connection may cause water leakage. z Keep level even when installing the product.

To avoid vibration of water leakage z Do not install the product where the noise or hot air from the outdoor unit could damage the

neighborhoods.

It may cause a problem for your neighbors.

Window WDF 3 Version - 0

PRECAUTION

z Use two or more people to lift and transport the product.

Avoid personal injury. z Do not install the product where it will be exposed to sea wind (salt spray) directly.

It may cause corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient operation.

Operational

z Do not expose the skin directly to cool air for long periods of time. (Do not sit in the draft).

This could harm to your health. z Do not use the product for special purposes, such as preserving foods, works of art, etc. It is a

consumer air conditioner, not a precision refrigerant system

There is risk of damage or loss of property. z Do not block the inlet or outlet of air flow.

It may cause product failure. z Use a soft cloth to clean. Do not use harsh detergents, solvents, etc.

There is risk of fire, electric shock, or damage to the plastic parts of the product. z Do not touch the metal parts of the product when removing the air filter. They are very sharp.

There is risk of personal injury. z Do not step on pr put anything on the product. (outdoor units)

There is risk of personal injury and failure of product. z Always insert the filter securely. Clean the filter every two weeks or more often if necessary.

A dirty filter reduces the efficiency of the air conditioner and could cause product malfunction or damage. z Do not insert hands or other object through air inlet or outlet while the product is operated.

There are sharp and moving parts that could cause personal injury. z Do not drink the water drained from the product.

It is not sanitary could cause serious health issues. z Use a firm stool or ladder when cleaning or maintaining the product.

Be careful and avoid personal injury. z Replace the all batteries in the remote control with new ones of the same type. Do not mix old

and new batteries or different types of batteries.

Window WDF 4 Version - 0

PRECAUTION

There is risk of fire or explosion. z Do not recharge or disassemble the batteries. Do not dispose of batteries in a fire.

They may burn of explode. z If the liquid from the batteries gets onto your skin or clothes, wash it well with clean water. Do

not use the remote of the batteries have leaked.

The chemical in batteries could cause burns or other health hazards.

Window WDF 5 Version - 0

PRECAUTION

2. Specification.

Capacity (1)

Pdesign kW 3,3

SEER

Energy efficiency class

Annual energy consumption

W/W 3,6

D kWh

V/Ph/Hz

253

220-240V/Single/50Hz

3,6

D

321

220-240V/Single/50Hz Power supply

Circuit breaker rating

Fan type & quantity

Fan speeds

Air flow (3)

External static pressure

Sound power level (4)

H/M/L

Min-Max

A

RPM

16

Cross flow fan x1

25,1

Cross flow fan x1

890/810/730 870/800/670

Sound pressure level (5)

Moisture removal

Condensate drain tube I.D

Refrigerant control

Compressor type, model

Air flow

Sound power level

(4)

Sound pressure level (5)

H/L

Pa l/hr mm m3/hr

0 0

57

1

49/47/45

1,2

Capillary

Rotary

Capillary

Rotary

65

58

Package dimensions

Packaged weight

Stacking height

Refrigerant type

Refrigerant charge

Operation control type

WxHxD mm kg

685x430x620

36,7 units 5 levels

R410A

746x515x815

50

5 levels

R410A kg 0,48 0,6

Remote Remote control

Window WDF 6 Version - 0

DIMENSION

3. Dimension.

Window WDF 7 Version - 0

FUNCTION AND CONTROL

PANEL

4. Function and control panel.

4.1 Function.

Operation mode: Cooling, FanDry.

Fresh air switch.

LED display

Sleep mode

Swing function.

Self-diagnosis function

Timer function.

Anti-freezing control in cooling mode or drying mode. Prevent the water being freezed on

evaporator by sensing the evaporator pipe temperature in cooling mode.

Time Delay Safety. Restarting is for approx. 3 minutes.

Auto-restart. When the power supply is interrupted and then restore, the air conditioners

automatically restore the previous function setting.

4.2 Control panel.

1】ON/OFF OPERATION BUTTON

This button turns the air conditioner ON and OFF.

Window WDF 8 Version - 0

FUNCTION AND CONTROL PANEL

2】SWING BUTTON

Press the “SWING” keypad(for the models with swing feature only) to activate the automatic air swing feature.

To stop the air swing feature, press the “SWING” keypad again.

Press the “SWING” keypad for 2 seconds will activate the SLEEP mode which can reduce noise creating a comfortable sleeping.

3】TIMER BUTTON

Press the “TIMER” keypad to activate the “auto start/auto stop” timer function.

Auto Start/Stop programs can be from 0-12 hours. Each depression of the “TIMER” keypad will increase the selected time in 1 hour increments.

4】FAN SPEED BUTTON

Press the button to select the low, Middle and High FAN Speed.

5】TEMP BUTTON

Press the ▲ keypad to increase the set (operating) temperature of the unit and press the ▼ keypad to decrease the set(operating) temperature of the unit. The temperature setting range is from 16-31℃.

6】MODE BUTTON

Press the “MODE” keypad to select the appropriate operating mode. For the Cooling & Heating models, the mode selection will alternate between COOLING, FAN, DRY.

7】SIGNAL RECEIVER

Window WDF 9 Version - 0

FUNCTION AND CONTROL

PANEL

5. Refrigerant Cycle Diagram.

The figure below is a brief description of the important components and their function in what is called the refrigeration system.

This will help to understand the refrigeration cycle and the flow of the refrigerant in the cooling cycle.

F o r o n ly c o o lin g

L I Q U I D S I D E

C A P I L I A R Y T U B E

E V A P O R A T O R

C O N D E N S E R

G A S S ID E C O M P R E S S O R

Window WDF 10 Version - 0

WIRING DIAGRAM

6. Wiring Diagram

Window WDF 11 Version - 0

PROTECTION FUNCTION

7. Protection Function.

     

7.1 Proper symbols and their meaning

 

„ T1: Indoor ambient temperature

„ T2: Indoor evaporator temperature

„ T3: Outdoor condenser temperature

„ Ts: Setting temperature through the remote controller

7.2 Protection Function

 

7.2.1 Three minutes delay at restart for compressor.

7.2.2 Anti-freezing protection at cooling or dry mode.

Anti-freezing control according to T2 (Indoor evaporator temperature).

If the evaporator pipe temperature had been lower than 1 for 14 minutes, the evaporator

anti-freezing protection will be activated. The compressor will keep off in the following 5 minutes

5 minutes later, if the evaporator pipe temperature is still lower than 4, the compressor will stay off.

Otherwise the compressor will be started and the function is cancelled.

Anti-freezing control according to TIME.

If the lasting time of compressor which is continuously running has got to 105 minutes with fan

motor operating under Med or Low speed and the indoor ambient temperature lower than 26, the

anti-freezing function will be activated. The compressor will keep off for 3 minutes.

Note:

If the compressor stops operation, the time will be cleared.

7.2.3 Anti-frosting protection and defect at cooling or dry mode.

3 minutes later when compressor is running, if T2 has been less than -14 for subsequent 3

minutes, the anti-frosting protection is activated and compressor will stop in the following 6 minutes.

After that, if the condition for de-frosting function is met again in the following 10 minutes while the compressor is operating, the unit will display ‘ Ed ’ to indicate that the unit is in the de-frost defect.

Window WDF 12 Version - 0

PROTECTION FUNCTION

The compressor and fan motor will be OFF

Note:

The Defect display can be cancelled only by pressing the ON/OFF button on the unit or the remote controller.

7.2.4 function.

Operation conditon

(T1-Ts)℉ compressor on

Electronic

2

7.2.4.1 Cooling

The speed of

-2

mode indoor fan can be

compressor off

optionally chosen as

/Low

Compressor running rules:

T1>TS+2

°F, compressor on

T1≤TS-2

°F, compressor off

7.2.4.2 Auto mode

The machine will choose cooling, fan-only mode according to ΔT (ΔT =T1-Ts).

High/ Mid (optional)

Window WDF 13 Version - 0

PROTECTION FUNCTION

ΔT>2℃ Cooling

-1≤ΔT≤2℃ Fan-only

The machine will choose actual running mode in auto mode in the below cases:

¾

Power on or change mode to auto mode or adjust temperature in auto mode, the machine will choose actual running mode again.

¾ A: In auto mode, if the compressor keeps not running for 15 minutes. judge condition B

B: If 1<ΔT or ΔT <-4℃, the machine will choose actual running mode again according to T1-Ts till the compressor stops..

7.2.4.3 Fan mode

(1) Compressor stops.

(2) Temperature setting function is disabled.

(3) The speed of indoor fan can be optionally chosen as High/ Mid /Low.

7.3 Temperature sensor is open circuit or short circuit.

Defect code

Er

En

Eo

Ed

malfunction explanation

Room temperature sensor error.

Evaporator temperature sensor error.

Condenser temperature sensor error.

Evaporator de-frosting defect.

Malfunction display:

When the malfunction happened at the same time, the priority is: Er> En> E0>Ed

Window WDF 14 Version - 0

INSTALLATION

8 Installation details

8.1 Select the best location.

1. To avoid vibration and noise, make sure the unit is installed securely and firmly.

2. Install the unit where the sunlight does not shine directly on the unit. If the unit receives. direct sunlight, build an awning to shade the cabinet.

3. There should be no obstacle, such as a fence or wall, within 500mm from the back of the

ambient because it will prevent heat radiation of the condenser.

4. Restriction of outside air will greatly reduce the cooling and heating efficiency of the air

Conditioner.

5. Install the unit on a slight angle so that an condensate formed will not enter the room

(about 10mm or 1/4”bubble with level).

6. Install the unit with its bottom portion 75~1500mm above the floor level.

7. The power cord must be connected to an independent circuit. The yellow/green wire must be grounded.

Window WDF 15 Version - 0

INSTALLATIOIN

8.2 Check off installation.

¾ The setting conditions must be checked prior to initial starting. The under mentioned items are

especially important checking points when the installation is finished.

¾ Grounding wire (yellow/Green) is provided in the power cord. The wire must be grounded.

¾ Ensure that the unit is connected to a suitably rated and dedicated circuit.

¾ To avoid vibration or noise, make sure the air conditioner is installed securely.

¾ Avoid placing furniture of draperies in front of the air inlet and outlet.

8.3 How to drain.

To get the maximum cooling efficiency, the air conditioner is designed to splash the condensation water on the condenser coil.

If the splashing sound annoys you, you can provide an outside drain by using the following procedure, which may however cause a small loss of performance.

1. Slide out the chassis from the cabinet.

2. Remove the rubber plug from the body base plate.

3. Install the drain pan to the corner of the cabinet with 2 screws.

4. Connect the drain hose to the outlet on the drain pan bottom.

5. Slide the chassis into its original place in the cabinet.

Window WDF 16 Version - 0

INSTALLATION

8.4 How to install.

z Use iron support

The installation hole should be strong enough to support the air conditioner. If it cannot, iron support has to be used outdoors.

Iron support should be fixed on the building. z

Use sunshade board

Air conditioner should avoid anything to be dropped into it and avoid direct sunshine. If there is no cover on it, you should contact the seller for installing the sunshade board. When installing the sunshade board, don’t let it block the air

1) Remove the sticker from the front panel.

2) Put the unit into the installation hole.

— When installing the unit, it should be slanted down to the back to avoid the enlargement of noise or vibration.(Slant between 6-10mm.)

— The installation place should be strong enough to avoid the enlargement of noise or vibration.

3) Fill up sews in the cabinet with sponge or foam.

Window WDF 17 Version - 0

INSTALLATIOIN

Window WDF 18 Version - 0

CHARACTERISTIC OF TEMPERATURE SENSOR

10 Characteristic of temperature sensor.

Temp.

Resistance KΩ

Temp.

Resistance KΩ

Temp.

Resistance KΩ

-10 62.2756 17 14.6181 44 4.3874

-9 58.7079 18 13.918 45 4.2126

-8 56.3694 19 13.2631 46 4.0459

-7 52.2438 20 12.6431 47 3.8867

-6 49.3161 21 12.0561 48 3.7348

-5 46.5725 22 11.5

-4 44

49 3.5896

23 10.9731 50 3.451

-3 41.5878 24 10.4736 51 3.3185

-2 39.8239 25 10 52 3.1918

-1 37.1988 26 9.5507 53 3.0707

10 20.7184 37 5.8736 64 2.0373

11 19.6891 38 5.6296 65 1.9653

12 18.7177 39 5.3969 66 1.8963

13 17.8005 40 5.1752 67 1.830

14 16.9341 41 4.9639 68 1.7665

15 16.1156 42 4.7625 69 1.7055

16 15.3418 43 4.5705 70 1.6469

Window WDF 19 Version - 0

TROUBLESHOOTING

11 Troubleshooting

In general, possible trouble is classified in three kinds. One is called Starting Failure which is caused from an electrical defect, another is ineffective Air Conditioning caused by a defect in the refrigeration circuit and improper application, and the other is called the Structure Damage.

Operation panel don't work.

Check the power supply.

No

Press the "LED" button of remote controller several times and check whether the problem is settled down.

No

Yes

Check the wiring of display board.

Repair the wiring.

No

Replace the display board.

No

Replace the main control board.

Fan motor speed can't change.

Check the wiring.

No

Check the capacitor of fan motor. Replace if failed.

No

Replace the PCB.

No

Check the resistance of fan motor and replace the motor if failed.

Window WDF 20 Version - 0

TROUBLESHOOTING

The air-con doesn't work.

Check the power supply.

No

Check the wiring.

No

Check whether the transformer is failed. Measure the output voltage of transformer and check whether it is the range from

+5V to 12V. If not, replace the transformer.

No

Replace the PCB.

Window WDF 21 Version - 0

TROUBLESHOOTING

Display keeps showing "Ed".

Check whether the evaporator frosts.

No

Check whether the indoor air inlet is blocked.

No

Check whether the indoor ambient temperature is too low.

No

Check whether the indoor dust filter is too dirty.

No

Check whether there is too much water on the chassis.

No

Check the wiring of pipe temperature sensor.

No

Check the pipe temperature sensor.

Yes

No

Replace the pipe temperature sensor.

Replace the main control board.

Window WDF 22 Version - 0

TROUBLESHOOTING

Compressor doesn't work.

Check whether the indoor temperature is lower than 15° C or larger than 31° C.

No

Check the power supply.

No

Check whether the voltage is too high or too low.

No

Check the wiring.

No

Check whether the compressor is under overload protection.

No

Check the relay of compressor in PCB works normally.

No

Check whether the external protector works noamally.

Yes

No

Remove the overload protector and cool to normal temperature. then check whether it is open circuit. replace if failed.

Comparing whit compressor specification,.check the resistance of compressor.

No

Replace the compressor.

Window WDF 23 Version - 0

TROUBLESHOOTING

Cooling mode don't work or cooling not enough.

Check the operation mode.

No

Check the setting temperature.

No

Check whether dust filter is too dirty.

No

Start the unit with cooling mode, check whether the temperature of the compressor's discharge pipe is smaller than 90 ℃ , if no, recharge refrigerant.

No

Replace the capillary.

The air-con doesn't work.

Check the power supply.

No

Check the wiring.

No

Check whether the transformer is failed. Measure the output voltage of transformer and check whether it is the range from

+5V to 12V. If not, replace the transformer.

No

Replace the PCB.

Window WDF 24 Version - 0

TROUBLESHOOTING

The compressor operates run-stop frequently.

Check whether the airflow passage is blocked.

Replace the PCB.

No

Check whether the fan motor doesn't work.

No

Check whether capacitor of compressor work normally.

No

Check whether the relay of compressor on PCB works normally.

No

No

Check whether the capillary is blocked.

No

Replace the capillary.

No

Replace the compressor.

Window WDF 25 Version - 0

TROUBLESHOOTING

Water drips from the unit.

Check whether the ambient humidity is too high.

No

Check whether the indoor outlet airflow foam is too wet, and louver drip.

No

Check whether the unit is correctly installed.

No

Check whether the air outlet foam install normally.

No

Check whether the foam of evaporator base is damaged.

No

Check whether the drain passage of evaporator is blocked. Replace if failed.

Window WDF 26 Version - 0

TROUBLESHOOTING

: For reverse cycle model

No/ineffective cooling

No/ineffective heating

Check whether the indoor outlet/inlet of the unit is blocked or the vent door is open

Whether the display panel display one of the following signal? "Er En Eo Ed"

No

Yes

Yes

Whether the compressor can start in cooling/heating mode even if it soon stops?

No

Er…indicates room temp. sensor failure

En indicates indoor pipe sensor failure

Eo indicates outdoor pipe sensor failure

Ed indicates that the evap. Is frosting

Check temperature. setting

Check whether the indoor outlet/inlet of the unit is blocked or the vent is blocked

Check Wiring

Replace the main PCB

No voltage

Check compressor capacitor

Check whether the Evap.is frosting and the compressor stops frequently

Yes

No

Check the speed of motor

Normal

Check whether the temp. of suction pipe is above 7℃

In cooling

Yes

Check the voltage between

RY9 on main PCB and N on power cord

Check leakage

Leakage

Recycle refrigerant and braze the leakage point

Vaccum and recharge

Check the drainage

Replace the capillary tube

Replace the reverse valve

Replace the compressor

Check the fan capacitor

Replace the motor

Replace the compressor

Yes

Check whether the Cond.is frosting and the compressor stops frequently

Recycle refrigerant and recharge

Check the speed of motor

Normal

Check the control wire of the reverse valve

Yes

Replace the reverse valve

Check the voltage between P11 on main PCB and N on power

No voltage

Replace the Main PCB

Window WDF 27 Version - 0

EXPLODED VIEW AND PART LIST

12 Exploded view and part list

AWWR-WDF009-C11

Window WDF 28 Version - 0

EXPLODED VIEW AND PART LIST

Part list:

No.

8

8.1

8.2

8.3

6

7

2

5

1

1.1

1.2

1.3

1.3.1

1.3.2

1.4

8.7

8.8

8.9

8.10

8.11

8.12

9

Part Name

Panel assembly

Front panel

Air filter

Panel frame

Panel frame

Horizontal louver

Air outlet assembly

Remote controller

Display box assembly

Cover of control panel

Cover of electronic control box

Electronic control box assembly

Electronic control box

Capacitor of compressor

Capacitor clip

Power cord

Pipe temperature sensor assembly

Ambient temperature sensor assembly

Capacitor of fan motor

Louver motor

Fresh air door

No. Part Name

22

23

24

25

18

19

20

21

26

27

28

29

11

12

13

14

15

16

17

Chassis assembly

Evaporator base

Cabinet assembly

Ventilation ring

Volute shell (below)

Evaporator coil assembly

Compressor

Suction pipe assembly

Capillary assembly

Discharge pipe assembly

Condenser assembly

Centrifugal fan

Volute shell

Supporter assembly of fan motor

Front separating board

Asynchronous motor

Axial flow fan

Buttstrap

Rear separating

33.1 Drain Connector

33.2 Drain stopper

Window WDF 29 Version - 0

EXPLODED VIEW AND PART LIST

AWWR-WDF012-C11

Window WDF 30 Version - 0

EXPLODED VIEW AND PART LIST

Part list:

No. Part Name

1 Panel assembly

1.1 Front panel

6

7

4

5

1.2 Air filter

1.3 Panel frame

1.4 Horizontal louver

1.5 Air outlet assembly

Remote controller

Display box assembly

Cover of control panel

Fresh air door

8 Electronic control box assembly

8.1 Electronic control box

8.2 Capacitor of compressor

8.3 Capacitor of fan motor

8.8 Pipe temperature sensor assembly

8.9 Ambient temperature sensor assembly

8.10 Capacitor clip

8.11 Main control board assembly

9

10

11

12

Cover of electronic control box

Chassis assembly

Horizontal louver

Foam of volute shell

No. Part Name

13 Drain stopper

14

19

20

21

22

15

16

17

18

23

24

26

27

39.1

Cabinet assembly

Rear separating

Axial flow fan

Asynchronous motor

Supporter assembly of fan motor

Front separating board

Volute shell

Centrifugal fan

Volute shell (below)

Ventilation ring

Evaporator coil assembly

Compressor

Suction pipe assembly

29

30

31

Discharge pipe assembly

Condenser assembly

Front cover

32 Connecting board

33 Buttstrap

34

39

Rear cover

Installation accessory

Drain Connector

Window WDF 31 Version - 0

SERVICE MANUAL

Window WDF Series

Window WDF 1 Version - 0