MODEL
HMW-1015 T5
HEAVY RANGE
Container
Powered by MTU
20FT
WATER-COOLED
THREE PHASE
50 HZ
DIESEL
Generating Rates
SERVICE
Power
Power
Rated Speed
Standard Voltage
Available Voltages
Rated at power factor
PRP
STANDBY
kVA
1006
1109
kW
r.p.m.
805
887
1.500
V
400/230
V
Cos Phi
380/220 - 415/240
0,8
HIMOINSA Company with quality certification ISO 9001
HIMOINSA gensets are compliant with EC mark which includes the following directives:
• 2006/42/CE Machinery safety.
• 2014/30/UE Electromagnetic compatibility.
• 2014/35/UE electrical equipment designed for use within certain voltage limits
• 2000/14/EC Sound Power level. Noise emissions outdoor equipment. (amended by 2005/88/EC)
• 97/68/EC Emissions of gaseous and particulate pollutants. (amended by 2002/88/EC & 2004/26/EC)
• EN 12100, EN 13857, EN 60204
Ambient conditions of reference according to ISO 8528-1:2005 normative: 1000 mbar, 25ºC, 30% relative humidity.
Prime Power (PRP):
According to ISO 8528-1:2005, Prime power is the maximum power which a generating set is capable of delivering continuously whilst supplying a variable
electrical load when operated for an unlimited number of hours per year under the agreed operating conditions with the maintenance intervals and procedures
being carried out as prescribed by the manufacturer. The permissible average power output (Ppp) over 24 h of operation shall not exceed 70 % of the PRP.
Emergency Standby Power (ESP):
According to ISO 8528-1:2005, Emergency standby power is the maximum power available during a variable electrical power sequence,
under the stated operating conditions, for which a generating set is capable of delivering in the event of a utility power outage
or under test conditions for up to 200 h of operation per year with the maintenance intervals and procedures being carried out as
prescribed by the manufacturers. The permissible average power output over 24 h of operation shall not exceed 70 % of the ESP
G2 class load acceptance in accordance with ISO 8528-5:2013
HIMOINSA HEADQUARTERS:
Fábrica: Ctra. Murcia - San Javier, Km. 23,6 | 30730 SAN JAVIER (Murcia) Spain
Tel.+34 968 19 11 28 Fax +34 968 19 12 17 Fax +34 968 19 04 20 info@himoinsa.com www.himoinsa.com
Manufacture facilities:
SPAIN • FRANCE • INDIA • CHINA • USA • BRASIL • ARGENTINA
Subsidiaries:
ITALY | PORTUGAL | POLAND | GERMANY | SINGAPORE | UAE | MEXICO | PANAMÁ | ANGOLA | UK
Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:info@himoinsa.com | www.himoinsa.com
01
MODEL
HMW-1015 T5
HEAVY RANGE
Container
Engine Specifications 1.500 r.p.m.
Powered by MTU
ENGINE
Rated Output
kW
PRP
STANDBY
846,6
935,6
Manufacturer
MTU
Model
Engine Type
16V2000G26F
4-stroke diesel
Injection Type
Aspiration Type
Direct
Turbocharged and after-cooled
Number of cylinders and arrangement
Bore and Stroke
Displacement
16-V
mm
L
135 x 156
35,7
Cooling System
Lube Oil Specifications
Water
ACEA E4, E6, E7, E9
Compression Ratio
17,5
Fuel Consumption Standby
Fuel Consumption 100% PRP
l/h
l/h
218,57
197,66
Fuel Consumption 75 % PRP
Fuel Consumption 50 % PRP
l/h
l/h
150,58
104,52
Fuel Consumption 25 % PRP
l/h
58,21
Lube oil consumption with full load
0,8 % of fuel consumption
Total oil capacity including tubes,
filters
L
114
Total coolant capacity
L
150
Heat dissipated by coolant
Governor
kW
Type
390
Electrical
Air Filter
Type
Dry
Generator
Generator
Poles
Connection type (standard)
No.
Mounting type
Insulation
Enclosure (according IEC-34-5)
Exciter system
Voltage regulator
Bracket type
Coupling system
Coating type
4
Star-series
S-0 18''
Class
H class
IP23
Self-excited, brushless
A.V.R. (Electronic)
Single bearing
Flexible disc
Standard (Vacuum impregnation)
Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:info@himoinsa.com | www.himoinsa.com
02
MODEL
HMW-1015 T5
HEAVY RANGE
Container
Powered by MTU
Application Data
Exhaust System
Maximum exhaust temperature
ºC
540
m 3/min
3,06
mbar
mm
50
200
Intake air flow
m 3 /h
4068
Cooling Air Flow
Alternator fan air flow
m3 /s
m3 /s
24,37
1,614
Starting power
kW
7,5
Starting power
CV
10,2
Recommended battery
Auxiliary Voltage
Ah
Vdc
200
24
Exhaust Gas Flow
Maximum allowed back pressure
Exhaust Flange Size (external diameter)
Necessary Amount Of Air
Starting System
Fuel System
Fuel Oil Specifications
Fuel Tank
Diesel
L
Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:info@himoinsa.com | www.himoinsa.com
999
03
MODEL
HMW-1015 T5
HEAVY RANGE
Container
Dimensions
Powered by MTU
Weight and Dimensions
(L)
Length
mm
6.058
(H)
Height
mm
2.591
(W)
Width
Maximum shipping volume
mm
m3
2.438
38,27
kg
L
12.160
999
Hours
7
(*)
Weight with liquids in radiator and sump
Fuel tank capacity
Autonomy
Sound pressure level
dB(A)@7m
(*) (with standard accessories)
90 ± 2,3
STANDARD VERSION
Himoinsa has the right to modify any feature without prior notice.
Weights and dimensions based on standard products. Illustrations may include optional equipment.
Technical data described in this catalogue correspond to the available information at the moment of printing.
Industrial design under patent.
Local Distributor
Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:info@himoinsa.com | www.himoinsa.com
04
MODEL
HMW-1015 T5
HEAVY RANGE
Container
Powered by MTU
CONTROL PANEL MODEL
M5
Digital manual Auto-Start control panel and thermal magnetic protection (depending on current and
voltage) and differential with CEM7. Digital control unit CEM7
AS5
Automatic panel WITHOUT transfer switch and WITHOUT mains control with CEM7 unit. (*) AS5 as
optional with CEA7 unit. Automatic panel without transfer switch and WITH mains control.
CC2
Himoinsa Switching cabinet WITH display. Digital control unit CEC7
AS5 + CC2
Automatic panel WITH transfer switch and with mains control. The display will be on the genset and
on the cabinet. Digital control unit CEM7+CEC7
AC5
Automatic mains failure control panel. Wall-mounted cabinet WITH transfer switch and thermal
magnetic protection (depending on current and voltage). Digital control unit CEA7
Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:info@himoinsa.com | www.himoinsa.com
05
MODEL
HMW-1015 T5
Controller features (I)
HEAVY RANGE
Container
• : Standard
x : Not included
• : Optional
Generator Readings
Powered by MTU
CEM 7
CEA 7
CEC 7
CEM7 + CEC7
Voltage between phases
•
•
•
•
Voltage between neutral and phase
•
•
•
•
Current intensities
•
•
•
•
Frequency
•
•
•
•
Apparent power (Kva)
•
•
•
•
Active power (Kw)
•
•
•
•
Reactive power (kVAr)
•
•
•
•
Power factor
•
•
•
•
CEM 7
CEA 7
CEC 7
CEM7 + CEC7
Voltage between phases
x
•
•
•
Voltage between phases and neutral
x
•
•
•
Current intensities
x
•
•
•
Frequency
x
•
•
•
Apparent power
x
•
x
x
Active power
x
•
x
x
Reactive power
x
•
x
x
Power factor
x
•
x
x
CEM 7
CEA 7
CEC 7
CEM7 + CEC7
Coolant temperature
•
•
x
•
Oil pressure
•
•
x
•
Fuel level (%)
•
•
x
•
Battery voltage
•
•
x
•
R.P.M.
•
•
x
•
Battery charge alternator voltage
•
•
x
•
Engine Protections
CEM 7
CEA 7
CEC 7
CEM7 + CEC7
High water temperature
•
•
x
•
High water temperature by sensor
•
•
x
•
Low water temperature by sensor
•
•
x
•
Low oil pressure
•
•
x
•
Low oil pressure by sensor
•
•
x
•
Low water level
•
•
x
•
Unexpected shutdown
•
•
x
•
Mains Readings
Engine Readings
Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:info@himoinsa.com | www.himoinsa.com
06
MODEL
HMW-1015 T5
Controller features (II)
HEAVY RANGE
Container
• : Standard
x : Not included
• : Optional
Engine Protections
Powered by MTU
CEM 7
CEA 7
CEC 7
CEM7 + CEC7
Fuel storage
•
•
x
•
Fuel storage by sensor
•
•
x
•
Stop failure
•
•
x
•
Battery voltage failure
•
•
x
•
Battery charge alternator failure
•
•
x
•
Overspeed
•
•
x
•
Underspeed
•
•
x
•
Start failure
•
•
x
•
Emergency stop
•
•
•
•
CEM 7
CEA 7
CEC 7
CEM7 + CEC7
High frequency
•
•
•
•
Low frequency
•
•
•
•
High voltage
•
•
•
•
Low voltage
•
•
•
•
Short-circuit
•
•
x
•
Asymmetry between phases
•
•
•
•
Incorrect phase sequence
•
•
•
•
Inverse power
•
•
x
•
Overload
•
•
x
•
Genset signal drop
•
•
•
•
CEM 7
CEA 7
CEC 7
CEM7 + CEC7
Total hour counter
•
•
•
•
Partial hour counter
•
•
•
•
Kilowatt meter
•
•
•
•
Starts valid counters
•
•
•
•
Starts failure counters
•
•
•
•
Maintenance
•
•
•
•
CEM 7
CEA 7
CEC 7
CEM7 + CEC7
RS232
•
•
•
•
RS485
•
•
•
•
Modbus IP
•
•
•
•
Modbus
•
•
•
•
Alternator Protections
Counters
Communications
Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:info@himoinsa.com | www.himoinsa.com
07
MODEL
HMW-1015 T5
Controller features (III)
HEAVY RANGE
Container
• : Standard
x : Not included
• : Optional
Communications
Powered by MTU
CEM 7
CEA 7
CEC 7
CEM7 + CEC7
CCLAN
•
•
x
•
Software for PC
•
•
•
•
Analogue modem
•
•
•
•
GSM/GPRS modem
•
•
•
•
Remote screen
•
•
x
•
• (8 + 4)
• (8 + 4)
x
• (8 + 4)
•
•
x
•
CEM 7
CEA 7
CEC 7
CEM7 + CEC7
Alarm history
• (10) / (opc. +100)
• (10) / (opc. +100)
• (10) / (opc. +100)
• (10) / (opc. +100)
External start
•
•
•
•
Start inhibition
•
•
•
•
Mains failure start
x
•
•
•
Start under normative EJP
•
•
x
•
Pre-heating engine control
•
•
x
•
Genset contactor activation
•
•
•
•
Mains & Genset contactor activation
x
•
•
•
Fuel transfer control
•
•
x
•
Engine temperature control
•
•
x
•
Manual override
•
•
x
•
Programmable alarms
•
•
x
•
Genset start function in test mode
•
•
•
•
Programmable outputs
•
•
x
•
Multilingual
•
•
•
•
CEM 7
CEA 7
CEC 7
CEM7 + CEC7
GPS Positioning
•
•
x
•
Synchronisation
•
•
x
•
Mains synchronization
•
•
x
•
Second Zero elimination
•
•
x
•
RAM7
•
•
x
•
Remote screen
•
•
x
•
Programming timer
•
•
x
•
Tele signal
J1939
Features
Special Functions
Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:info@himoinsa.com | www.himoinsa.com
08
MODEL
HMW-1015 T5
HEAVY RANGE
Container
Powered by MTU
Generator set features
Engine
· Standard air filter
· Standard fuel filter
· Standard oil filter
· Electronic management (ADEC)
· Coolant level sensor
· Exhaust gas compensator
· Diesel engine
· 4-stroke cycle
· Water-cooled
· 24V electrical system
· Radiator with blower fan
· HTW sender
· LOP sender
· Hot parts protection
· Moving parts protection
Alternator
· Self-excited and self-regulated
· IP23 protection
· H class insulation
Container version
· Soundproofing provided by high-density volcanic rock wool
· High mechanical resistance
· Low level of noise emissions
· Door with window to visualize control panel, alarms and measurements
· Reinforced lifting points for crane hoisting and lower ones for transportation by forklift
· Residential steel silencer with -35dB attenuation and tilting cap in the exhaust
· Fuel tank integrated in the chassis
· Anti-vibration shock absorbers
· Steel chassis
· Manual oil extraction pump
· Robust construction designed for continuous or emergency applications
Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:info@himoinsa.com | www.himoinsa.com
09
MODEL
HMW-1015 T5
HEAVY RANGE
Container
Powered by MTU
Generator set features
Container version
· Stainless steel fittings
· Emergency stops
· Easy access to the power connection
· Reinforced chassis for heavy range
· Easy access for chassis cleaning
· Silent-block with anti-corrosion protection between the genset and the chassis
· Easy access to fill radiator through the roof
Electrical System Container
· Control panel and emergency stop button
· Power panel
· Battery charger (standard on automatic control panels)
· Heating resistor (standard on sets with automatic control panels)
· Battery charge alternator with ground connection
· Starter battery/ies installed (cables and bracket included)
· Ground connection electrical installation with connection ready for ground spike (not supplied)
· 4 pole circuit breaker
· Power panel with safety protection in output terminals box (open thermal magnetic protection and alarm)
· Maintenance-free and anti-explosion battery
· Battery isolator
Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:info@himoinsa.com | www.himoinsa.com
10
MODEL
HMW-1015 T5
HEAVY RANGE
Container
PDF Summary
Powered by MTU
Created : 31/01/2018 20:44
Author : Himoinsa
Number of pages : 11
Report Type: Data Sheet - Heavy range
Generated by: HIMOINSA Engineering Dept.
Page 1. Genset data
Page 2. Engine Specifications. Generator Specifications.
Page 3. Installation Data
Page 4. Dimensions
Page 5. Control Panel Model
Page 6. Controller features (I)
Page 7. Controller features (II)
Page 8. Controller features (III)
Page 9. Generator Features & Options
Page 10. Generator Features & Options
Page 11. PDF Summary
11
Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:info@himoinsa.com | www.himoinsa.com
Download PDF
Similar pages