PB_T8_05 2017
T8200, T8600 and T8800
T8 Touch Thermostat Series
Product Bulletin
The T8 Series includes the T8200, T8600 and T8800 touch screen thermostats
designed to control heating and cooling in commercial, industrial and residential
installation.
Typical applications include the control of Fan Coil units, Packaged terminal air
conditioners and combination of heating and cooling equipment. As part of the
system, the T8 thermostats control two-way or three-way valves and multi-speed
line voltage fans.
In the T8 range beside the T8200 Stand Alone models, the T8600 and T8800
can communicate with any Building Automation System. The T8800 models are
designed to be connected to the Johnson Controls Building Automation System
Metasys® using BACnet MS/TP communication, while the T8600 models offer
connection in Modbus RTU. The integration in Metasys improves usability and
enhances energy saving strategies.
The large LCD touchscreen display of the T8 thermostat provides the status
of current working mode, the fan speed, the indoor temperature and the
temperature set point.
The T8 range is equipped with a capacitance touch screen enhancing the user
experience when operating the thermostat.
Keypad includes: Power on/off
Mode selection
Clock/Timer
and two Adjustment buttons
&
, Fan Speed Selection
.
,
■■ Touch screen
The touch screen provides clear information and easy operation. When required by building policy it can show Set
Point only.
■■ Backlit Black Crystal Display
Offers Easy-to-Read graphical messages through International icons with backlight timeout.
■■ 6 Function Keys lockable
Protected against misuse in public space, operation can be fully or partially locked to comply with the building energy
policy.
■■ Stylish appearance
Flush mount for stylish low profile installation.
■■ Energy Saving
Occupancy mode reducing energy consumption when the room unoccupied.
■■ Smart Restart
Thermostat retains the last events and parameter settings after power loss.
■■ Timing Function
Daytime, Fan Coil Runtime, and On/Off timer functions are available.
■■ Stand-Alone or Communicating
From simple stand-alone applications to system managed by a Building Automation System through BACnet MS/TP
or Modbus RTU communication buses.
PB_T8_05 2017
Product Overview
The T8 thermostat models cover 2-pipe and 4-pipe cooling and heating applications with Auto-High-Med-Low fan speed
control.
The On-board high accuracy NTC sensor allows precision comfort control over occupied space area. Some models can
connect an alternative remote passive temperature cable sensor and other models can manage an Occupancy status
switch.
The T8 thermostats are equipped with Touch screen display, with backlight that has a timeout function to reduce
consumption and avoid disturbing occupants during the night.
All models can be equipped with ON/OFF valve control and three speed Fan outputs. All relay outputs provide max. 5Amp
(Res.) @ 250Vac.
Fahrenheit unit
Fan auto
Fault
Auto
Timer on
Ventilation
Day of Week
Sleep
Timer off
Heating
Centigrade unit
Occupancy
Time
Lock
Internal sensor
Valve
Fan speed
Communication
Low temperature protection
High, mid, low
Cooling
Ambient temperature
The
button on the front panel for the 2-pipe solution selects the thermostat mode: heating, cooling and ventilation only.
The 4-pipe models offer the heating and cooling AUTO mode.
The Clock button
sets the daytime, and the Timer On/Off functions. The Timer function allows user to set the
thermostat ON or OFF after a programmable period, programmable from 30 min to 12 hours.
The
buttons are often used to change values during the configuration of the thermostat but their main function is
to change the set point. Usually the thermostat is displaying the temperature of the room, when one of those keys are
touched the Set point is shown. Where the building policy requires the thermostat to show only the Set Point, this can be
configured during the start up.
The fan mode Auto-High-Med-Low fan speeds can be changed pressing the
Fan button.
The On/Off button allows user to shutdown the thermostat and cutoff the output power for the Fan and for Valve
Actuators.
The T8200 is offering Stand-Alone control only, the models T8600 and T8800 can be integrated in any Building
Automation systems using, respectively, Modbus RTU and BACnet MS/TP buses.
For any of the above models the display buttons can be locked to avoid misuse in public space. The Thermostats allow
the following locking configuration: Lock all keys, Lock all except Fan and Set point, lock On/Off and Clock functions only.
When the Key-Lock function is active for a temporary unlock press and hold Fan Key for 5 sec.
2
PB_T8_05 2017
T8200-TFE0-9JR0
T8200-TFE0-9JS0
T8600-TB20-9JR0
T8600-TB20-9JS0
T8600-TF20-9JR0
T8600-TF20-9JS0
T8800-TB20-9JS0
T8800-TF20-9JS0
Application
T8200-TBE0-9JS0
Type
T8200-TBE0-9JR0
Product Range and Models
2-pipe heating or cooling
●
●
---
---
●
●
---
---
●
---
4-pipe heating and cooling
---
---
●
●
---
---
●
●
---
---
Feature
Communication
Output
STAND-ALONE
Energy Saving
Certificate
BACNET MS/TP
ON/OFF
●
●
●
●
●
●
●
●
●
●
Touch Screen with Graphic Icons
●
●
●
●
●
●
●
●
●
●
Display Temp/SP or Set Point only
●
●
●
●
●
●
●
●
●
●
Fan Speed (Low, Mid, High, Auto)
●
●
●
●
●
●
●
●
●
●
Display Key Lock
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
---
●
---
●
---
●
---
●
●
Auto Mode (3)
---
---
●
●
---
---
●
●
---
●
RTC (4)
●
●
●
●
●
●
●
●
●
●
Run Time (Hours)
●
●
●
●
●
●
●
●
●
●
Low-temperature protection (Anti-Freezing)
●
●
●
●
●
●
●
●
●
●
Restart after power failure
●
●
●
●
●
●
●
●
●
●
Ventilation only mode
●
●
●
●
●
●
●
●
●
●
Remote Occupancy (dry-contact NO/NC)
---
●
---
●
---
●
---
●
●
●
Unoccupied Heating/Cooling Set-Points
---
●
---
●
---
●
---
●
●
●
Low Fan when unoccupied
---
●
---
●
---
●
---
●
●
●
Adjustable Upper/Lower Set Point Limits
●
●
●
●
●
●
●
●
●
●
Timer ON/OFF (6)
●
●
●
●
●
●
●
●
●
●
CE
●
●
●
●
●
●
●
●
●
●
BACnet BTL (7)
---
---
---
---
---
---
---
---
●
●
(1)
C°/F° field selectable
Function
MODBUS RTU
Remote Passive Sensor
(2)
(5)
(1) Key-Lock function has 4 options: No Lock. Lock all keys. Lock the keys except Fan Speed and Set Point keys. Lock the ON/OFF and Clock
keys. When the Key lock function is active for a temporary unlock press and hold fan key for 5 Sec or temporary remove power.
(2) T8600 and T8200 models -9JR0 are supplied with own specific cable sensor in the box. The T8800 do not include the sensor, a TS-6300 10K
NTC can be order separately.
(3) Auto mode is available only on 4-Pipe application, deviation from SP of more than + 1 °C change the heating/cooling mode.
(4) Equipped with Standby battery (CR1220) with 1 year life time
(5) After a power loss the thermostat can restart ON, OFF mode or as it was before the event (last condition)
(6) Timer Set On or OFF the thermostat after a programmable time, from 30 min to 12 hours
(7) BACnet MS/TP, BLT certified, up to 100 devices per network controller (NAE55), Auto Baud Rate and Segmentation.
3
PB_T8_05 2017
Products description
T8200 Stand Alone
Model T8200-TBE0-9Jx0
The Model T8200-TBE0-9Jx0 are Stand Alone, line voltage, thermostats designed for cooling or heating in a 2-pipe fan
coil unit with ON/OFF valve actuator.
T8200-TBE0-9JS0 has a digital input for Occupancy mode that allows better comfort control and energy cost saving.
T8200-TBE0-9JR0 can connect one remote passive temperature sensor, while the remote sensor is connected, the builtin sensor will be automatically disabled. Please use the 10K NTC cable sensor supplied with the thermostat.
N
L
Val
Low
Med
High
L
N
L
Val
Low
Med
High
Valve
FAN
N
S1
S2
L
Valve
FAN
N
S1
S2
T8200-TBE0-9JR0
T8200-TBE0-9JS0
N
L
N
N L
Cool Valve
Heat Valve
L
N L
Cool Valve
Heat Valve
S1
Val1
Val1
L
L
S2
Val2
Val2
Model
Val
Valve
Val
Valve
Low
Lowcooling or heating in a 4-pipe fan
The Model T8200-TFE0-9Jx0 are
Stand Alone, line voltage, thermostats designed for
Med
Med
FAN
FAN
coil unit with ON/OFF valve actuator.
High
High
HighOccupancy mode that allows better
Highand energy cost saving.
T8200-TFE0-9JS0 has
a digital Ninput for
comfortN control
N
N
Med
Med
S1
FAN
T8200-TFE0-9JR0 can connectS1
one remote
passive temperature sensor, while the remote
sensorFAN
is connected, the builtL
L
S2
Low
Low
S2
S1
S2
T8200-TFE0-9Jx0
in sensor will be automatically disabled. Please use the 10K NTC cable sensor supplied with the thermostat.
T8200-TBE0-9JR0
T8200-TFE0-9JR0
N
NTC 10K Type
S1
S2
Val1
Val2
N
High
Med
Low
L
T8200-TFE0-9JR0
NTC 10K Type
Cool Valve
Heat Valve
FAN
L
T8200-TBE0-9JS0
T8200-TFE0-9JS0
N
L
AC 230 V 50/60 Hz
S1
S2
Val1
Val2
N
High
L
Med
Low
Cool Valve
Heat Valve
FAN
T8200-TFE0-9JS0
AC 230 V 50/60 Hz
4
PB_T8_05 2017
N
L
A
B
T8600 Modbus RTU
S1
1Val1
2Val2
S2
Model T8600-TB20-9Jx0
N
A
B
S1
S2
Cool
Heat
1Val1
2Val2
L
Cool
Heat
The Model T8600-TB20-9Jx0 are MODBUS RTU, line voltage, thermostats designed for cooling or heating in a 2-pipe fan
coil unit with ON/OFF valve actuator.
High
High
N
N
T8600-TB20-9JR0 has a digital input for Med
Occupancy
mode that allows better comfort controlMed
andFAN
energy cost saving.
FAN
L
L
Low
Low
T8600-TB20-9JS0 can connect one remote passive temperature sensor, while the remote sensor is connected, the builtin sensor will be automatically disabled. Provided with specific NTC 10K cable sensor.
T8600-TF20-9JR0
A
B
S1
S2
N
N
N
Val
A
B
S1
S2
Val
High
N
High
Med FAN
Low
L
T8600-TF20-9JS0
L
Med FAN
Low
L
T8600-TB20-9JR0
L
T8600-TB20-9JS0
NTC 10K Type
AC 230 V 50/60 Hz
Model T8600-TF20-9Jx0
The Model T8600-TF20-9Jx0 are MODBUS RTU, line voltage, thermostats designed for cooling or heating in a 4-pipe fan
coil unit with ON/OFF valve actuator.
T8600-TF20-9JR0 has a digital input for Occupancy mode that allows better comfort control and energy cost saving.
T8600-TF20-9JS0 can connect one remote passive temperature sensor, while the remote sensor is connected, the builtin sensor will be automatically disabled. Provided with specific NTC 10K type cable sensor.
N
A
B
S1
S2
1Val1
2Val2
N
High
L
Cool
Heat
Med FAN
Low
L
T8600-TF20-9JR0
A
B
S1
S2
1Val1
2Val2
N
High
A
B
S1
S2
Val
A
B
S1
S2
Val
N
High
N
High
Med FAN
Low
L
T8600-TB20-9JR0
NTC 10K Type
L
N
L
Cool
Heat
T8600-TF20-9JS0
L
L
Med FAN
Low
L
N
N
Med FAN
Low
T8600-TB20-9JS0
AC 230 V 50/60 Hz
5
PB_T8_05 2017
T8800 BACnet MS/TP
The T8800 are BACNET MS/TP, 24VAC Powered, thermostats designed for cooling or heating control. These thermostats
can connect a dry NC/NO contact to manage occupancy mode, or they can be wired to a remote passive temperature
sensor like the TS-6340K-F00. While the remote sensor is connected to the thermostat, the built-in sensor will be
automatically disabled.
T8800-TB20-9JS0 is BACNET MS/TP, 24VAC Powered, thermostat designed for cooling or heating in a 2-pipe fan coil
unit with ON/OFF valve actuator.
T8800-TF20-9JS0 is BACNET MS/TP, 24VAC Powered, thermostat designed for cooling and heating in a 4-pipe fan coil
unit with ON/OFF valve actuator.
N
or
TR
S1
S2
A
B
COM1
Valve
NC
L
24 V
High
COM
Med FAN
Low
T8800-TB20-9JS0
NTC 10K Type
Cool/Heat
L
N
S1
S2
A
B
COM1
or
24 V
TR
COM
Valve1
Valve2
L
L
Cool
Heat
High
Med FAN
Low
T8800-TF20-9JS0
AC 230 V 50/60 Hz
When the T8800 is the last device on a BACnet network, please add EoL resistor (½ W) at the end, across
terminal A & B.
When connected, the On/Off switch of the thermostat does not disconnect power to the unit;
only the LCD and Relay outputs are turned OFF.
6
88
PB_T8_05 2017
Dimensions
T8200 models
39.8
88
15.3
60
15.3
60
15.3
60
15.3
60
15.3
60
88
T8200-TBE0-xxxx
40.8
88
88
T8200-TFE0-xxxx
39.8
T8800 / T8600 models
88
40.8
88
88
88
39.8
88
88
Use this T8800 series thermostat only for operating control. Where failure or malfunction of
the T8800 series thermostat could lead to personal injury or property damage to the controlled
equipment or other property, additional precautions must be designed into the system.
Incorporate and maintain other devices such as supervisory/alarm systems or safety/ limit
controls intended to warn of, or protect against, failure or malfunction of the T8800 series
thermostat.
7
PB_T8_05 2017
Installation
Thermostat requires wall or flush box with max external size of 88x88mm with a suitable internal size of 75x75x35mm.
1
2
3
4
5
IMPORTANT:
The power supply to the thermostat must include overload protection.
Failure to include overload protection may result in damage to the thermostat.
8
PB_T8_05 2017
Ordering Informations
Item Code
Tyme
T8200-TBE0-9JR0
T8200-TBE0-9JS0
T8200-TFE0-9JR0
Application
2-pipe Fan Coil, on/off, with occupancy input.
Stand-Alone line thermostat
with touch screen
2-pipe, Fan Coil on/off, with remote sensor
4-pipe, Fan Coil on/off, with occupancy
T8200-TFE0-9JS0
4-pipe, Fan Coil on/off, with remote sensor
T8600-TB20-9JS0
2-pipe, Fan Coil on/off, with occupancy
T8600-TB20-9JR0
T8600-TF20-9JS0
MODBUS RTU line thermostat
with touch screen
T8600-TF20-9JR0
T8800-TB20-9JS0
T8800-TF20-9JS0
2-pipe, Fan Coil on/off, with remote sensor
4-pipe, Fan Coil on/off, with occupancy
4-pipe, Fan Coil on/off, with remote sensor
BACnet MS/TP 24 VAC thermostat
with touch screen
2 pipe, Fan Coil On/off, with Occupancy or remote sensor
4 pipe, Fan Coil On/off, with Occupancy or remote sensor
NOTE:T8200 and T8600: the Cable sensor included is a NTC10K type specific, cable lenght is 1,5 mt
T8800 does not include Cable Sensor, when required please order TS-6340K-F00 (10K NTC Type II)
9
PB_T8_05 2017
Technical Specifications
T8200
Power Requirements
T8600
T8800
AC 85 - 230 V, 50/60Hz
AC 20 - 30 V, 50/60Hz
Accuracy
±1 °C
Display Range
0 to 55 °C
Setpoint Range
5 to 35 °C
Occupancy Input
External Voltage-Free Contact only
on models
T8200-xxx-9JS0
External Voltage-Free Contact only
on models
T8600-xxx-9JS0
Input for 10K NTC
only on models
T8200-xxx-9JR0
Input for 10K NTC
only on models
T8600-xxx-9JR0
Remote Sensor Input
Remote Sensor Type
TS-6340K-F00
Max distance 20 m (1 mm2)
10K NTC cable 1,5 m (included)Max distance 20 m (1 mm2)
Fan Control
3 x Single-Pole, Single Throw (SPST), Relay Output for Hi-Med-Low Fan
Valve Control Relay
Up to 2 SPST Relays 5A (Res.) 250 VAC depending on Thermostat model
Communication
Stand-Alone
Termination
Screw terminals
Operating Conditions
0 to 45 °C 90% Non-Condensing RH
Storage Conditions
-10 to 60 °C 90% Non-Condensing RH
Housing Material
PC: UL 94-V0
Protection Class
IP20
Dimensions in mm
88 x 88 x 40,8 mm
Shipping Weight
Approximately: 214 g
Compliance
Modbus
1 input for Occupancy
voltage-free contact
OR
passive 10 K NTC sensor
10 K Type II
remote TS-6300 sensor
BACnet (BTL)
Johnson Controls declares that this product is in compliance with the essential requirements and other relevant
provisions of the Low Voltage Directive (LVD), the EMC Directive, and the RoHS Directive.
Building Efficiency
Headquarters: Milwaukee, Wisconsin, USA
Branch Officies: Principal Cities World-wide
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls.
All other marks herein are the marks of their respective owners.
© Copyright 2017 Johnson Controls. All rights reserved. Any unauthorized use or copying is strictly prohibited.
www.johnsoncontrols.com
Download PDF