CONTEMPORARY WATER COOLERS
A171.8-VR & VRB Series
Barrier Free, Vandal Resistant & Resistance Button,
Wall Mounted Water Cooler
RATED FOR INDOOR
AND OUTDOOR USE
A171408S-VR / A171108S-VRB
TECHNICAL ASSISTANCE TOLL FREE TELEPHONE NUMBER:
1.800.591.9360
Technical Assistance Fax: 1.626.855.4894
NOTES TO INSTALLER:
1. Please leave this documentation with the owner of the fixture when finished.
2. Please read this entire booklet before beginning the installation.
3. Check your installation for compliance with plumbing, electrical and other applicable codes.
LIMITED WARRANTY - UNITED STATES & CANADA
Murdock warrants that its products are free from defects in material or workmanship under normal use and service for a period of one year from date of install or for 18 months after the date of shipment from the factory, whichever comes first. The sealed refrigeration system is warranted for five years. Murdock’s liability under this warranty shall be discharged solely by replacement or repair of defective material, provided Murdock is notified in writing within one year from date of shipment, F.O.B. Industry, California.
This warranty does not cover installation or labor charges and does not apply to materials, which have been damaged by other causes such as mishandling or improper care or abnormal use. The repair or replacement of the defective materials shall constitute the sole remedy of the Buyer and the sole remedy of Murdock under this warranty. Murdock shall not be liable under any circumstances for incidental, consequential or direct charges caused by defects in the materials, or any delay in the repair or replacement thereof. This warranty is in lieu of all other warranties expressed or implied. Product maintenance instructions are issued with each unit and disregard or non-compliance with these instructions will constitute an abnormal use condition and void the warranty.
Stainless steel must be protected on job site during construction and must be properly maintained after the water has been introduced into the water cooler or drinking fountain, or Murdock’s limited warranty is void.
LIMITED EXPORT WARRANTY - One year on parts only.
Murdock assumes no responsibility for use of void or suspended data. © Copyright Murdock, City of
Industry, CA Member of Morris Group International.
Please visit www.murdockmfg.com for most current specifications.
7020-915-001
Date: 12/26/17
Federal
Public Law
111-380
(No Lead)
Test rating conditions are compliant with ARI 1010.
Member of
MURDOCK
15125 Proctor Ave.
City of Industry, CA
91746 U.S.A.
Phone 800-591-9360
626-336-4561
Fax 626-855-4894
www.murdockmfg.com
CONTEMPORARY WATER COOLERS
IMPORTANT
This fixture is intended to dispense water that has been lowered in temperature, but otherwise remains unchanged by the materials in the water cooler. It is common for electrical equipment to be grounded to water lines either within a structure or away from it. Every attempt should be made to prevent this kind of grounding from generating electrical feedback into the water cooler creating electrolysis. Electrolysis will cause a metallic taste or cause water metal content to increase.
NOTICE
A dielectric coupling must be used to connect the water cooler to the water supply . A nonmetallic coupler is furnished with this water cooler to meet this requirement.
ROUGHING-IN AND DIMENSIONAL DRAWING
Prior to roughing consult with local, state, and federal codes for proper mounting height.
A171408 Wall Mounted Drinking Fountain
A. 3/8" NCT SUPPLY INLET
B. WASTE OUTLET FOR 1-1/4" P-TRAP BY OTHERS.
C. ELECTRICAL SERVICE ROUGH.
D. Ø3/8" HANGER BRACKET PUNCHING, 3 PLACES
FOR ANCHORING HARDWARE BY OTHERS.
E. Ø1/4" PUNCHING, 2 PLACES FOR ANCHORING HARDWARE
BY OTHERS.
F. CAULK FOR OUTDOOR UNITS (SEE PAGE 4 )
GENERAL NOTES:
1.
ALL DIMENSIONS ARE IN INCHES [MM]
2.
ALLOW 4 INCHES [102 MM] MINIMUM CLEARANCE PER SIDE FOR
*3.
VENTILATION
DIMENSIONS SHOWN ARE FOR ADA ADULT HEIGHT. ADJUST
VERTICAL DIMENSIONS AS NECESSARY TO COMPLY WITH
FEDERAL, STATE, & LOCAL CODES
4.
5.
STOP VALVE, P-TRAP, & ELECTRICAL OUTLET NOT SUPPLIED
IMPORTANT: COOLERS MUST BE ATTACHED TO WALL WITH
APPROPRIATE ANCHOR SCREWS
6
5
8
"
[168]
18
1
2
"
[470]
4
1
4
"
[108]
1
3
8
"
[35]
F
D
12"
[305]
6"
[152]
A
*29"
[737]
*22"
[559]
3
4
"
[19]
*15
5
8
[397]
"
B
C
6
1
2
"
[165]
5
1
4
"
[133]
E
20
3
4
"
*33"
[838]
1-1/4" [32]
P-TRAP BY
OTHERS
7
7
8
"
[200]
7
7
8
"
[200]
FRONT VIEW SIDE VIEW
NOTES: Dimensions indicated (*) are for ADA frontal approach installation. Adjust vertical dimension (*) as required to comply with federal, state, and local codes. For Child ADA compliant parallel approach, decrease spout height to 30” maximum above finished floor. Provide clear floor space as required.
MURDOCK MFG. • 15125 Proctor Avenue • City of Industry, CA 91746 USA
Phone 800-453-7465 or 626-333-2543 • Fax 626-855-4860 • www.murdockmfg.com
Member of
7020-915-001
Page 2 of 13
A171.8VR
Revised:
12/26/17
CONTEMPORARY WATER COOLERS
PRIOR TO INSTALLATION:
Important: some options may slightly alter installation. To ensure proper installation review the manual thoroughly and verify rough-ins before beginning work. File this manual wit the owner or maintenance personnel upon completion of installation.
—
Fixture mounting requirements: industry standard wall construction, adequate to support the fixture and installer provided wall anchors sufficient to secure the fixture.
—
Receptacle(s) must be wired to a GFCI protected circuit. Fixture must be earth grounded per NEC (National Electric Code).
—
Inspect fixture an all parts from damages and all parts are bolted on.
IMPORTANT:
1. Waste P-Trap, Water Supply Service Angle Stop Valve and 2” x 4” Electrical Plug-In Receptacle to be supplied by others in accordance with local codes. A metallic p-trap (by others) must be used for the drain connection.
2. Provide 4” minimum clear space on fixture sides to allow for proper ventilation through cabinet louvers.
3. Water supply is 3/8” Outer Diameter copper tube. Waste is 1-1/4” Outer Diameter.
4. Completely flush supply lines of all foreign debris before connecting TO fixture. Water cooler is designed to not cause problems with taste, odor, color, or sediment. Optional water filter (WF1) is available should any of these problems arise from the water supply.
5. If possible, limit exposure of the refrigerated cooler to direct sun light. The actual surface temperature of a cooler in direct sunlight on a 90°F day, the cooler temperature would be about 140°F.
6. Do NOT solder tubes inserted into the coupler as damage to the o-ring may result.
7. All burrs must be removed from outside of cut tubes before inserting into coupler or other components.
8. Power supply must be identical in voltage, cycle and phase to that specified on the cooler data plate. Electrical outlet and furnished power cord with plug must be used to supply power to fixture. Do NOT wire compressor directly to the power supply.
9. This unit must be grounded per the requirements of applicable electrical codes.
10. Warranty is voided if installation is not made following current Acorn Engineering installation instructions and if components are assembled to the fixture that is not approved by Acorn Engineering.
11. Fixture operates within water pressure range of 20 to 105 psig. Acorn Engineering will not warranty fixtures damaged when connected to supply lines with flow pressure lower than 20 psig or higher than 105 psig. A pressure regulator must be furnished by others on supply line if inlet pressure is greater than 105 psig.
12. Due to cold waste water, Acorn Engineering recommends that p-trap supplied by installer be insulated to prevent excessive condensation.
13. Per UPC 609.10- All building water supply systems in which quick acting valves are installed shall be provided with
devices to absorb the hammer caused by high pressure resulting from the quick closing of the valve. These pressureabsorbing devices shall be approved mechanical devices. Water pressure-absorbing devices will be installed as close as possible to the quick closing valve.
INSTALLATION:
1. Mount hanger bracket to wall horizontally level as shown in Roughing-In and Dimensional Drawing. Note: Adjust height of bracket if bubbler outlet height is required to vary from that shown. Hanger Bracket MUST be securely anchored to wall with fasteners sufficient to support 3 times weight of cooler. If wall can not provide adequate support, order and install optional fixture support carrier.
2. Remove the bottom cover from the water cooler and set aside in a safe place. Save the screws in a secure location for reuse in later stages of installation.
3. Hang the water cooler on the hanger bracket, ensuring the bracket tabs engage AND seat in the slots in the back of the water cooler. Verify water cooler is level, left to right AND front to back from bottom of unit. NOTE: The bubbler stream may be adversely affected if unit is not square and level. Bottom of unit and louvers should be used as reference to verify unit is square and plumb.
MURDOCK MFG. • 15125 Proctor Avenue • City of Industry, CA 91746 USA
Phone 800-453-7465 or 626-333-2543 • Fax 626-855-4860 • www.murdockmfg.com
7020-915-001
Page 3 of 13
A171.8VR
Member of
Revised:
12/26/17
CONTEMPORARY WATER COOLERS
4. Anchor water cooler to wall at other mounting points in base. Shim lower rear mounting points to level unit if necessary.
5. Thoroughly flush the 3/8” O.D. supply line and then connect water cooler to water supply angle stop valve (by others) with supplied 3/8” O.D. copper tube.
6. Make up 1-1/4” O.D. p-trap (by others) waste connection.
7. For outdoor installation see outdoor installation instructions.
OUTDOOR INSTALLATION INSTRUCTIONS:
1. Caulk all around the basin where it contacts the wall and where apron contacts the wall as shown, to prevent rain water from leaking into the cabinet. DO NOT CAULK THE REMOVABLE ACCESS COVER.
CAULKING
CAULKING
FRONT VIEW
SIDE VIEW
START UP:
1. Before connecting power supply and assembling bottom cover to water cooler, but after thoroughly flushing the supply line and connecting it to the fixture, turn on building water supply and check all connections for leak.
out by incoming water. Covering the bubbler with a clean cup (or similar object) is recommended when first activating water cooler to prevent excessive splashing. Depress the pushbutton until steady water stream is achieved.
3. If water flow requires adjustment, insert a slotted narrow blade screwdriver through the hole centered on the pushbutton to the flow regulator. Turning clockwise will increase flow and turning counterclockwise will decrease flow.
4. Recheck all water and drain connections with water flowing through system.
5. With power still NOT connected, carefully manually rotate cooling fan to insure proper clearance and free fan action.
6. Plug water cooler in to electrical outlet and make sure unit begins to function.
7. Assemble bottom cover to water cooler with screws furnished.
MURDOCK MFG. • 15125 Proctor Avenue • City of Industry, CA 91746 USA
Phone 800-453-7465 or 626-333-2543 • Fax 626-855-4860 • www.murdockmfg.com
Member of
7020-915-001
Page 4 of 13
A171.8VR
Revised:
12/26/17
CONTEMPORARY WATER COOLERS
NON-PRESSURIZED SINGLE UNIT PIPE INSTALLATION (WITHOUT -GF & -BF OPTIONS)
ITEM
1
2
PART NUMBER
7012-055-000
2169-000-000
DESCRIPTION
FOAM INSULATION, PIPE, 3/8" ID x 1/4" THICK
TUBING, LLDPE, BLUE 1/4" OD
QTY.
5.5'
5'
30" Water Supply Tubing
2 1
13" Water Supply Tubing
17" Water Supply Tubing
NON-PRESSURIZED SINGLE UNIT PIPE INSTALLATION WITH FILTER (WITHOUT -GF & -BF OPTIONS)
1. Starting from the wall connection, connect to the inlet of the filter.
2. From the outlet of the filter, connect to the inlet of the cartridge assembly.
3. From the outlet of the cartridge assembly, connect to the inlet of the evaporator assembly.
4. From the outlet of the evaporator assembly, connect to the bubbler.
2 1
Cut 30" Water Supply Tubing to 12” and Connect to Filter
3
ITEM
1
2
3
PART NUMBER
7012-055-000
2169-000-000
7012-311-000
DESCRIPTION
FOAM INSULATION, PIPE, 3/8" ID x 1/4" THICK
TUBING, LLDPE, BLUE 1/4" OD
WF1 FILTER 1500 GALLON
MURDOCK MFG. • 15125 Proctor Avenue • City of Industry, CA 91746 USA
Phone 800-453-7465 or 626-333-2543 • Fax 626-855-4860 • www.murdockmfg.com
7020-915-001
Page 5 of 13
A171.8VR
Member of
QTY.
5.5'
5'
1
Revised:
12/26/17
CONTEMPORARY WATER COOLERS
PRESSURIZED SINGLE UNIT PIPE INSTALLATION (WITH -GF & -BF OPTIONS)
ITEM
1
2
PART NUMBER
7012-055-000
2169-000-000
DESCRIPTION
FOAM INSULATION, PIPE, 3/8" ID x 1/4" THICK
TUBING, LLDPE, BLUE 1/4" OD
QTY.
5.5'
5'
13" Water Supply Tubing
To Bottle Filler or Glass Filler
1 2
17" Water Supply Tubing
MURDOCK MFG. • 15125 Proctor Avenue • City of Industry, CA 91746 USA
Phone 800-453-7465 or 626-333-2543 • Fax 626-855-4860 • www.murdockmfg.com
7020-915-001
Page 6 of 13
A171.8VR
Member of
Revised:
12/26/17
CONTEMPORARY WATER COOLERS
RE-PIPING FROM NON-PRESSURIZED
TO PRESSURIZED (FOR -GF & -BF ONLY)
To re-pipe a single non-pressurized unit to pressurized, you will have to move the water supply tubing around, with “NO” additional tubing needed. Before performing this task you
MUST SHUT OFF THE WATER SUPPLY, and disconnect all supply connections.
STEP 1:
Starting with the supply line coming from the wall, connect to the inlet of the evaporator assembly.
Wall Supply Connection
17" Water Supply Tubing
Evaporator Inlet Connection
STEP 2:
From the outlet of the evaporator assembly, connect to the inlet of the cartridge assembly.
Cartridge Assembly
Inlet Connection
To Bottle Filler or Glass Filler
" Tee for Both BF or GF
Evaporator Outlet Connection
STEP 3:
From the outlet of the cartridge assembly, connect to the bubbler.
13" Water Supply Tubing
Bubbler Connection
Cartridge Assembly
Outlet Connection
MURDOCK MFG. • 15125 Proctor Avenue • City of Industry, CA 91746 USA
Phone 800-453-7465 or 626-333-2543 • Fax 626-855-4860 • www.murdockmfg.com
7020-915-001
Page 7 of 13
A171.8VR
Member of
Revised:
12/26/17
CONTEMPORARY WATER COOLERS
TROUBLE SHOOTING:
IMPORTANT: BEFORE MAKING ANY OF THE REPAIRS LISTED, MAKE SURE THE WATER
COOLER IS DISCONNECTED FROM THE ELECTRICAL SUPPLY AND THE WATER SUPPLY
VALVE IS SHUT OFF.
IMPORTANT : ASSUREZ-VOUS QUE LA FONTAINE D'EAU POTABLE RÉFRIGÉRÉE SOIT
DÉBRANCHÉE DE LA PRISE DE COURANT MURALE ET QUE LE ROBINET D'ALIMENTATION
D'EAU SOIT FRMÉ AVANT D'EFFECTUER LES RÉPARATIONS NÉCESSAIRES.
1. Adjustments: a. Cartridge – The water flow can be adjusted using a slotted narrow blade screwdriver and
turning clockwise to increase flow and counterclockwise to decrease flow.
b. Cold Water Thermostat – The water temperature can be adjusted using a slotted
screwdriver and turning clockwise to make colder and counterclockwise to make warmer.
c. Bubbler Stream – Bubbler can be rotated slightly to direct the stream backwards or
forwards. Adjust the stream to minimize splashing. Splashing may occur from bubbler
stream if the unit is not level. Shim lower mounting points, if necessary, to level cooler.
2. Compressor Does Not Run a. Check the electrical receptacle for power and correct voltage. The incoming voltage must be
within 10% of the rated voltage on the serial nameplate.
b. The cold thermostat is accessible by removing the bottom access cover. If the cold
thermostat capillary bulb loses its charge or becomes kinked it will fail in the open position
causing a disruption of power to the compressor. Unplug the water cooler and using an
ohm meter check for continuity across the two electrical terminals on the thermostat. Install a new thermostat if there is no continuity.
c. Check for loose wires within the compressor box. The incoming power leads must be
connected to the overload and relay. d. If all components check positive for continuity then test the wiring harness plug for
continuity to see if there is a broken wire within the wiring harness insulation.
3. Compressor Runs – Water Is Warm a. The most common cause for a water cooler to run without producing cold water is a
loss of refrigerant. The water cooler must be taken to a certified refrigerant technician
for repairs.
b. Make sure the condenser fan motor is operative. The fan blade must turn freely to help
remove the heat of compression. c. An incorrect refrigerant charge, restriction or defective compressor (not pumping) will
also cause the compressor to run without producing cold water. All these signs indicate
a problem within the refrigeration system and the water cooler must be checked by an
authorized service company.
4. Compressor Cycling On Overload Protector a. A dirty condenser or a blocked fan will cause a high head pressure and frequent cycling
of the overload protector. b. Check the incoming voltage to make sure it is within 10% of the serial nameplate rating. c. A restriction or moisture in the system will also cause intermittent cycling. A certified
refrigeration mechanic should be contacted in this situation. d. Change the overload or relay if defective.
5. Noisy Operation a. Check to make sure the fan blade is rotating freely. b. Make sure the water cooler is correctly mounted to the wall. Absence of the two lower
mounting bolts may cause excess noise and vibration. c. Check the compressor mounting to make sure the pins and clips are not rattling. If the
compressor appears to be noisy internally, it must be replaced.
6. Restricted Or No Water Flow a. Ensure water supply service stop valve is fully open. b. Verify minimum 20 psig supply line flow pressure. c. Check for twists or kinks in bubbler tubing.
MURDOCK MFG. • 15125 Proctor Avenue • City of Industry, CA 91746 USA
Phone 800-453-7465 or 626-333-2543 • Fax 626-855-4860 • www.murdockmfg.com
7020-915-001
Page 8 of 13
A171.8VR
Member of
Revised:
12/26/17
CONTEMPORARY WATER COOLERS
d. Check the water inlet strainer. Sediment from the main supply can get trapped in the
screen along with installation materials such as pipe dope and flux. The screen should
be cleaned and checked on a regular basis and replace if needed.
NOTE: STRAINER SCREEN MUST BE IN PLACE FOR WATER TO FLOW. e. The cartridge valve located in the water control assembly or bubbler can also become
clogged with foreign material. The cartridge valve can only be replaced and not
repaired. f. Check flow adjustment. See start up note #3. g. The water cooler may also develop a freezing condition in which the water will become
frozen inside the evaporator coil. This indicates a refrigeration problem or thermostat
failure in which case the water cooler needs to be checked by a qualified technician.
7. Water Drip Or Will Not Shut Off: a. Remove Pushbutton (See pg.7 for details). Adjust flow regulator to the highest setting using a
flat head screwdriver and turning clockwise. Check if water drip continues, if it is no longer
dripping turn screwdriver counter-clockwise until you have desired flow rate. Assure that
retaining nut is tighten to valve assembly, 25 in-lb torque is required. If issue still continues after
adjusting flow and tightening retainer nut, replacement of the flow regulator cartridge will be
required.
CLEANING & MAINTENANCE GUIDE:
1. Motors have lifetime lubrication and do not require scheduled maintenance.
2. Excess dirt or poor ventilation will cause the compressor overload protector to turn the compressor off and it will cycle on and off with no cold water coming out of bubbler. Periodically clean with vacuum cleaner, air hose or brush the condenser fins and cabinet ventilation louvers. In environments where dirt and dust is more prevalent, clean more frequently.
3. Periodically remove access panels and clean out in-line strainer.
4. Do NOT use harsh chemicals, abrasive or petroleum based cleaners. Use of these will void the Acorn warranty.
5. Exterior panels can be cleaned using mild household detergents or warm, soapy water. Extra care must be used cleaning chrome plated items and mirror finished stainless steel. They can scratch easily and should only be cleaned using a clean, soft cloth and mild soap with water or a mild glass cleaner.
WINTERIZING INSTRUCTIONS:
Important: The water in all the water tubing, evaporator, valve body and Y-Strainer (if equipped) MUST be expelled from the cooler to prevent freezing.
1. Shut off the water supply.
2. Disconnect the water supply to the inlet tube or Y-Strainer (if equipped).
3. Connect compressed air [30 to 85 PSI] to the inlet tube or Y-Strainer (if equipped).
4. Let the cooler pressurize with air, then blow air thru the supply line while depressing the pushbutton until water stops flowing out of the bubbler and all water has been removed.
5. Add RV Anti-Freeze to the P-Trap.
6. Use a protective cover to prevent fresh water from diluting the Anti-Freeze in the waste drains.
7. It is recommended that a bleeder valve be added just above the gate valve to assist in future winter shutdown procedures.
MURDOCK MFG. • 15125 Proctor Avenue • City of Industry, CA 91746 USA
Phone 800-453-7465 or 626-333-2543 • Fax 626-855-4860 • www.murdockmfg.com
7020-915-001
Page 9 of 13
A171.8VR
Member of
Revised:
12/26/17
CONTEMPORARY WATER COOLERS
CARTRIDGE REPLACEMENT/ STRAINER MAINTENANCE
Note: Use the -VR maintenance tool to perform the following:
1. Strainer plug 4 must be removed before cartridge replacement and strainer maintenance (no need to turn the water off at the angle stop). Some residual water will drain during plug removal.
2. Clean strainer 4 as needed using clean water.
3. Cartridge replacement - Rotate and remove -VR pushbutton escutcheon 6 to release pushbutton 7 and springs 8 9 to access cartridge.
4. Remove cartridge retaining nut 10 . Remove and replace cartridge 2 . When replacing cartridge be sure to align the inlet and outlet ports on the cartridge with the ports in the valve body.
5. Install item 10 using maintenance tool 5 (Becareful not to over tighten)
6. Install button assembly items 6 7 8 9 using maintenance tool 5 . Insure springs are installed in button correctly.
7. Reinstall strainer 4 and plug 3 using maintenance tool 5 .
6
7
1
5
8
9
2
5
10
4
ITEM PART NUMBER
1 7003-095-001
DESCRIPTION
VALVE ASSEMBLY
2 7000-060-000 FLOW REGULATOR CARTRIDGE(0.5 GPM)
3
5
6
3
4
7
7003-097-001 O-RING &STRAINER PLUG
7003-864-000 STRAINER FILTER SCREEN
7003-194-199 (-VR) MAINTENANCE TOOL
7003-197-199 (-VR) PUSHBUTTON ESCUTCHEON, CHROME
7003-196-199 (-VR) PUSHBUTTON, CHROME
8
9
10
7003-195-000 (-VR) PUSHBUTTON OVERTRAVEL SPRING
7003-193-000 (-VR) PUSHBUTTON RETURN SPRING
7000-052-000 RETAINING NUT
NOTE: STRAINER FILTER SCREEN
MUST BE IN PLACE FOR
WATER TO FLOW.
MURDOCK MFG. • 15125 Proctor Avenue • City of Industry, CA 91746 USA
Phone 800-453-7465 or 626-333-2543 • Fax 626-855-4860 • www.murdockmfg.com
Member of
7020-915-001
Page 10 of 13
A171.8VR
Revised:
12/26/17
CONTEMPORARY WATER COOLERS
PUSH-IN FITTING INSTALLATION
NOTE: FITTINGS AND TUBE SHOULD BE KEPT
CLEAN, BAGGED AND UNDAMAGED PRIOR TO
INSTALLATION.
TO CUT TUBE:
Cut to fit length of 1/4” PE tubing and remove any burrs or sharp edges. Ensure that the outside diameter is free from score marks. Tube ends should be square.
INSERTING THE TUBE:
1. Firmly and fully insert the tubing end into the push-in fitting up to the tube stop located approximately ½” deep.
O-RING
O-RING
COLLET
TUBE STOP
COLLET
2. Pull on the fitted tubing to ensure it is secure. Tube should not come free from the fitting. Water test the connection assembly prior to leaving the site to ensure there are no leaks.
COLLET
COLLET
DISCONNECTING THE TUBE:
To disconnect the tube from the fitting ensure that the water line is depressurized. Push collet square towards the push-in fitting body and hold. While holding the collet in, pull on the PE tubing to remove from the push-in fitting.
MURDOCK MFG. • 15125 Proctor Avenue • City of Industry, CA 91746 USA
Phone 800-453-7465 or 626-333-2543 • Fax 626-855-4860 • www.murdockmfg.com
7020-915-001
Page 11 of 13
A171.8VR
COLLET
Member of
Revised:
12/26/17
CONTEMPORARY WATER COOLERS
COOLER PARTS BREAKDOWN
NOTE: See page #10 for fixture drawing corresponding to table of parts below.
3
2
1
22
26
Universal Maintenance Tool
-Button Removal
-Cartridge Retaining Nut
-Strainer Plug
-Removal of P.E. Tubing
from Push-in Fittings
4
23 24
NOTE:
** Flow Restrictor Only Available
With Low Flow Bubbler.
5
6
19
23 24
20
18
8
9
** 25
7
15
17
16
23 24
11
30
29
14
13
27
10
26
28
32
35
34
33
28
32
31
VANDAL RESISTANT BUTTON &
VALVE BREAKDOWN
SCALE x 1-1/2"
21
12
Standard A171.8 series refrigerated ADA cooler shown. All 1/4" O.D. Plastic tubing 24 must be insulated with 25 foam insulation.
NOTE: See next page for table of part numbers corresponding to drawing above.
MURDOCK MFG. • 15125 Proctor Avenue • City of Industry, CA 91746 USA
Phone 800-453-7465 or 626-333-2543 • Fax 626-855-4860 • www.murdockmfg.com
Member of
7020-915-001
Page 12 of 13
A171.8VR
Revised:
12/26/17
CONTEMPORARY WATER COOLERS
COOLER PARTS BREAKDOWN TABLE
NOTE: See previous page for fixture drawing corresponding to table of parts below.
30
31
32
33
26
27
28
29
34
35
22
23
24
25
18
19
20
21
ITEM # PART NUMBER DESCRIPTION
1
7003-001-199 BASIN TOP
7003-161-299 BF12 BASIN TOP WITH HOLE FOR BF11/12
2
3
7000-012-001 STAINLESS STEEL BUBBLER ASSEMBLY
0124-032-000 #8 x 3/4" LG PHIL FLAT HD SELF TAPPING SCREW
6
7
4
5
8
7000-006-000 FLAT DRAIN GASKET
7003-180-001 DRAIN TAILPIECE
7003-003-199 BACK PANEL
7003-007-199 SUPPORT STRUT
9
10
7003-250-000 COLD CONTROL
7003-212-020 APRON ASSEMBLY - GRANITE
7003-211-002 APRON ASSEMBY - STAINLESS STEEL
7003-095-001 VALVE ASSEMBLY (N/A FOR -SO)
11
12
13
14
15
7003-004-020 COVER - GRANITE
7003-035-299 COVER - STAINLESS STEEL
7003-201-000 CONDENSER
7012-801-000 COMPRESSOR
7012-030-001 COMPRESSOR - 220V
7012-802-000 START RELAY
7012-031-000 START RELAY - 220
7012-803-000 START CAPACITOR
16
17
7012-032-000 START CAPACITOR - 220
7003-350-000 FAN BLADE
7003-302-000 FAN MOTOR
7012-062-001 FAN MOTOR - 220V
7003-115-001 EVAPORATOR ASSEMBLY
7003-014-199 HANGER BRACKET
1895-123-000 SUPPLY INLET CONNECTION
0124-031-000 #8 x 3/8" LONG SLOTTED HEX WASHER HD SCREW
0124-056-000 #8 x 3/8" LONG PHILLIP HEAD SHEET METAL SCREW
2169-000-000 1/4" O.D. TUBING
7012-055-000 TUBE INSULATION
7003-093-001 FLOW RESTRICTOR - LOW-FLOW BUBBLER ONLY
7003-194-199 (-VR) MAINTENANCE TOOL
7003-198-199 (-VR) PUSHBUTTON MOUNTING SLEEVE
0124-055-000 #8x3/4 PHILLIPS ROUND HEAD SS SM SCREW
7003-199-000 AUTO-STOP CONDENSATION GASKET, UPPER
7003-200-000 AUTO-STOP CONDENSATION GASKET, LOWER
7003-193-000 (-VR) PUSHBUTTON RETURN SPRING
0161-062-000 #6-32 x 1/2" S/S PHIL FLAT HD SCREW
7003-195-000 (-VR) PUSHBUTTON OVERTRAVEL SPRING
7003-196-199 (-VR) PUSHBUTTON, CHROME
7003-197-199 (-VR) PUSHBUTTON ESCUTCHEON, CHROME
Repairs must be made with Acorn Engineering parts only. Please order through your local representative or distributor. The phone number to locate your local representative is 1.800.591.9360.
MURDOCK MFG. • 15125 Proctor Avenue • City of Industry, CA 91746 USA
Phone 800-453-7465 or 626-333-2543 • Fax 626-855-4860 • www.murdockmfg.com
Member of
7020-915-001
Page 13 of 13
A171.8VR
Revised:
12/26/17