08 product range - Air Conditioning

PRODUCT
RANGE
08
WATER CHILLERS
HEAT PUMPS
FAN COIL UNITS
AIR HANDLING UNITS
Rhoss takes part in the Eurovent
certification programme.
Concerned products are included in
the guide to Eurovent certified
products, which can be consulted at
www.eurovent-certification.com
Residential
Hotels
Airports
Offices
Meeting & Congress Rooms
Industrial Processes
Shopping Centres
Health Care
P.3
Rhoss: your partner in innovation
Since 1968, Rhoss has been a guarantee for innovation, quality and
top level service. This is what makes us the ideal partner for the most
demanding companies.
Our know-how, born from 40 years’ experience, enables us to meet
innumerable requirements while adhering to the new technological
and design trends of the HVAC sector.
In all these years, we at Rhoss have constantly evolved to the point of
specialising in the manufacture of units for residential and industrial air
conditioning.
Our evolution has followed market development and customers'
needs providing state-of-the-art products which are both highly
efficient and environmentally friendly.
In particular, technological innovation is the driving force behind the
development of our new products and is guaranteed by R&D Lab, the
state-of-the-art trial and testing laboratory.
This is where research is carried out in conjunction with the most
prestigious university institutes and the products are certified
according to Eurovent regulations.
Thanks to these strong points Rhoss is and will be your ideal partner.
P.5
Guarantee of quality, certainty of service.
The reliability of our products is ensured by constant trials and
demanding functional tests that allow us to maintain the highest
standards of quality.
All this is proven by Vision 2000 certification and by participation in
the Eurovent programme which attests the performance of our
products.
In our search for continuous improvement we have always dedicated
great effort and strong investments, like the implementation of the
Lean manufacturing philosophy in the company's organisation which
makes us even more competitive and more rapid in our response to
customers.
Ultimately, certainty of service has always been one of our primary
objectives: through Rhoss Smile Service product assistance is
guaranteed, thanks to highly specialised technicians who are focused
on customers' needs.
Wherever you breathe clean conditioned air through safe advanced
systems, Rhoss is there.
P.7
Adaptive Function Plus:
the revolution in low consumption
Continuous research and testing, combined with a deep knowledge
in air conditioning, has assisted our designer staff in creating Adaptive
Function Plus, an innovative technology developed to reduce energy
consumption.
Adaptive Function Plus is an exclusive patent by Rhoss born of the
partnership with the University of Padua and applied to the new
ranges of water chillers and heat pumps.
Quality of life and care for the environment thus take shape through a
project aimed at the well-being of the individual, without neglecting
the planet where we live.
PRODUCT RANGE
WATER CHILLERS - HEAT PUMPS
Air cooled - Axial fans
TCAEY-THAEY 105÷111
Mini-Y Range
Hermetic rotary Scroll compressors
P.14
Microsystem
15,4÷32,5 kW
16,8÷37,5 kW
P.18
P.22
Y-Mich Range
Hermetic rotary Scroll compressors
P.26
Macrosystem
68,2÷316,2 kW
76,7÷356,2 kW
P.30
Y-Power Range
Hermetic rotary Scroll compressors
P.34
P.32
Q-Power Range
Semi-hermetic screw compressors
TCAVZ 2310÷2670
P.36
Z-Power Range
Semi-hermetic screw compressors
Z-Power Range
Semi-hermetic screw compressors
Macrosystem
297,5÷665,9 kW
Macrosystem
324,8÷693,2 kW
Macrosystem
764,5÷1.283,4 kW
TCAV 1280÷2450
Macrosystem
264,05÷445,50 kW
Macrosystem
331,4÷455,1 kW
353,4÷486,2 kW
Z-Power Range
Semi-hermetic screw compressors
TCAE-THAE 270÷2160/4155÷4320 P.28
Q-Pack Range
Hermetic rotary Scroll compressors
Macrosystem
138÷325 kW
159,6÷342 kW
TCAVZ 2770÷21290 H.E.
P.24
Macrosystem
67÷161 kW
79÷175 kW
Y-Pack Range
Hermetic rotary Scroll compressors
TCAVZ 2330÷2700 H.E.
TCAEY-THAEY 270÷2160
Y-Pack Range
Hermetic rotary Scroll compressors
Microsystem
23,8-48,1 kW
27,3-52,9 kW
TCAEY-THAEY 5350÷6450
P.20
Microsystem
44,2÷64 kW
47,8÷67,9 kW
Microsystem
13,4÷27,8 kW
15,6÷31,7 kW
TCAEY-THAEY 4160÷4320
TCAEY-THAEY 245÷265
Compact-Y Range
Hermetic rotary Scroll compressors
Compact-Y Range
Hermetic rotary Scroll compressors
TCAIY-THAIY 124-150
P.16
Compact-Y Range
Hermetic rotary Scroll compressors
Microsystem
5,5÷11,1 kW
5,8÷12,4 kW
TCAEY-THAEY 118÷136 H.E.
TCAEY-THAEY 115÷233
P.38
TCAVZ 2750÷21250
Z-Power Range
Semi-hermetic screw compressors
Macrosystem
732÷1.251,5 kW
P.40
Radiant Systems
Air-cooled - Centrifugal fans
TCCEY-THCEY 105÷111
P.42
Mini-Y Range
Hermetic rotary Scroll compressors
Microsystem
7,5÷14,8 kW
6,0÷12,6 kW
P.44
Compact Range
Hermetic rotary Scroll compressors
TCAEY-THAEY 118÷136 H.E.
P.18
Compact-Y Range
Hermetic rotary Scroll compressors
Microsystem
13,5÷22 kW
13,6÷24 kW
TCCE-TCPE-THCE-THPE 130÷270
P.14
Mini-Y Range
Hermetic rotary Scroll compressors
Microsystem
4,8÷10,4 kW
5÷11 kW
TCCE-THCE 114÷126
TCAEY-THAEY 105÷111
Microsystem
17,4÷36,5 kW
15,8÷32,4 kW
P.46
TCHEY-THHEY 105÷112
Comby-Flow Range
Hermetic rotary Scroll compressors
Hermetic rotary Scroll compressors
Macrosystem
30,1÷66,3 kW
34,9÷77,1 kW
P.48
Microsystem
7,6÷16,5 kW
6,9÷14,8 kW
Water-cooled - Condenserless units
TCHEY-THHEY 105÷112
Comby-Flow Range
Hermetic rotary Scroll compressors
P.48
Microsystem
5,4÷12 kW
6,5÷13,9 kW
TCHE-THHE 280÷4260
P.50
Mini-Q Flow / Compact Flow Range
Hermetic rotary Scroll compressors
12,3÷63,6 kW
15,2÷72,4 kW
P.52
Q-Flow Range
Hermetic rotary Scroll compressors
TCHVZ 1200÷31630
P.54
Z-Flow Range
Semi-hermetic screw compressors
Macrosystem
76,5÷255,3 kW
86,6÷289,9 kW
TCEE 105÷165
TCHE-THHE 115÷165
Macrosystem
199,7÷1.629,2 kW
P.56
TCEE 280÷4260
P.58
Q-Flow E Range
Hermetic rotary Scroll compressors
Mini-Q Flow E / Compact Flow E Range
Hermetic rotary Scroll compressors
Macrosystem
74,2÷249 kW
5,5÷62,2 kW
TCEVZ 1200÷31630
P.60
Z-Flow E Range
Semi-hermetic screw compressors
Macrosystem
171,9÷1.424,8 kW
EXP - Polyvalent system
TXAEY 117÷133
P.64
Compact-Y EXP Range
Hermetic rotary Scroll compressors
Microsystem
42,6÷61,9 kW
47,8÷67,9 kW
P.68
Q-Pack EXP Range
Hermetic rotary Scroll compressors
Condensing units
Hermetic rotary blade and Scroll
compressors
Microsystem
5,1÷26,3 kW
6÷29,9 kW
TXHEY 105÷112
Comby-Flow EXP Range
Hermetic rotary Scroll compressors
Microsystem
5,4÷12 kW
6,5÷14,5 kW
Macrosystem
70,4÷307,1 kW
75,5÷357,3 kW
MCAE-MHAE 105÷127
P.66
Compact-Y EXP Range
Hermetic rotary Scroll compressors
Microsystem
17,4÷34 kW
17,9÷39,1 kW
TXAE 475÷4315
TXAEY 245÷265
P.72
P.70
SYSTEM ACCESSORIES
P.74
CCAM 105÷2130
CEHV-CEHP 46÷2791
Remote condensers
Cooling towers
Axial fans
Axial fans
P.78
AS 0300÷2500
Pumping group
PBHI 0200-0400
P.76
P.80
Pumping group
Macrosystem
50,2÷249 kW
FAN COIL UNITS - TERMINAL UNITS
IDROWALL
P.82
FREND
Wall-mounted fan coil units
Floor and ceiling fan coil units
Tangential fans
Tangential fans
Unit-System
1,3÷2,5 kW
3,2÷5,4 kW
Unit-System
1÷2,9 kW
2,2÷5,7 kW
BRIOEV
P.86
YARDYEV
Floor and ceiling fan coil units
Floor and ceiling fan coil units
Centrifugal fans
Centrifugal fans
Unit-System
1÷6,9 kW
2,2÷16,5 kW
P.91
Recessed fan coil units for vertical
and horizontal installation
Centrifugal fans
YARDYEV
P.91
Ductable fan coil units for horizontal
installation
Centrifugal fans
Unit-System
1,1÷7,2 kW
2,4÷17,4 kW
Unit-System
3,5÷6,2 kW
7,6÷13,6 kW
UTNC-EV
P.94
VTNC
P.96
Cassette-type fan coil units
Cassette-type fan coil units
Unit-System
2,5÷8,5 kW
5,4÷20,4 kW
Unit-System
2,4÷10 kW
5,4÷23,6 kW
UTNB 011÷017
P.98
Ductable terminal air handling units
in sections
Air flow rate: 1.100÷1.680 m3/h
UTNA 015÷150
P.100
Ductable terminal air handling units in
sections
Air flow rate: 1.800÷16.500 m3/h
Unit-System
4,1÷10,5 kW
10,3÷23 kW
Unit-System
7,2÷108 kW
11,3÷174 kW
UTNV 030÷150
P.102
Air conditioning and ventilation
terminal units
Air flow rate: 3.150÷15.600 m3/h
UTNR 012÷041
Air renewal terminal units with heat
recovery
Air flow rate: 3.150÷15.600 m3/h
Unit-System
14,5÷98,2 kW
22,3÷226,8 kW
Unit-System
5,4÷18,6 kW
P.106
CONTROLS
for fan coil units and terminal units
AIR HANDLING UNITS
Advance Range
Air handling units
Air flow rate:: 850÷140.000 m3/h
P.89
Unit-System
1,1÷7,2 kW
2,4÷17,4 kW
YARDYEV
CTA ADV 240÷22920
P.84
P.112
P.104
INTEGRATED SOLUTIONS
FOR SYSTEM MANAGEMENT
home
office
P.108
Price list
range:
Microsystem
hotel
iDRHOSS is an advanced system for the management of
hydronic air conditioning systems, developed to meet the
Unit-System
comfort needs of any civil or residential location.
Macrosystem
P.110
SUPERVISION SOFTWARE
Refrigerant
gases:
RHOSS SUPERVISOR is
the Rhoss supervision system
that allows monitoring and
remote management of Rhoss
units used in a hydronic system.
PACKAGED
DE-HUMIDIFIERS FOR POOLS
DRESY - DAESY 108÷2111
Meaning of
symbols:
Cooling
only
Heat
pump
Outdoor
installation
Indoor
installation
Non-ductable
unit
Ductable
unit
P.116
Dry Pool ADV range
Dehumidification capacity: 8÷111 l/h
WATER CHILLERS
HEAT PUMPS
P. 14
SYSTEM ACCESSORIES
P. 74
FAN COIL UNITS
P. 82
TERMINAL UNITS
P. 98
CONTROLS
P. 106
iDRHOSS
P. 108
SUPERVISION SOFTWARE
P. 110
AIR HANDLING UNITS
P. 112
TCAEY-THAEY 105÷111
Mini-Y Range
Fan coil systems
Radiant Systems
Packaged air-cooled reversible water chillers
and heat pumps with axial fans.
Range with hermetic Scroll compressors and
R410A refrigerant gas.
Construction features
Compressor: hermetic, rotary Scroll compressor, complete
with thermal protection.
Water side heat exchanger: adequately insulated stainless
steel plate exchanger, complete with antifreeze heater and
water flow differential pressure switch
Air side heat exchanger: finned coil exchanger, with copper
pipes and aluminium fins or coil with aluminium micro-channel
pipes, complete with protection grille.
Fan: axial fan with external rotor, equipped with internal thermal
protection and complete with protection grille.
Control: microprocessor electronic control available in 2
versions: Standard, with Adaptive Function logic, and
iDRHOSS compatible, with Adaptive Function Plus logic
Structure: in galvanised and painted sheet steel, complete
with condensation drain pan for THAEY.
Models
TCAEY: unit designed for cooling only.
THAEY: heat pump unit.
PUMP unit
• With standard pump.
• With high-pressure pump.
Pumping group complete with: standard or high-pressure
circulation pump for models 105÷107 only, expansion tank with
membrane, manual air bleed valve and safety valve.
TANK & PUMP unit
• With standard pump.
• With high-pressure pump.
Pumping group complete with: water buffer tank, standard or
high-pressure circulation pump for models 105÷107 only,
expansion tank with membrane, manual air bleed valve,
automatic air bleed valve and safety valve.
Factory fitted accessories
• Soft-start device (for models with power supply 230 V).
• -10°C condensation control.
• Low pressure switch.
• Compressor heater.
• Unit base antifreeze electric heater for operation in heat pump
mode at external air temperature of below –5°C.
Option with control
• Digital input for double set-point
• 4-20 mA analogue input for shifting set-point.
Accessories supplied loose
• Antivibration rubber mountings
• -10°C condensation control.
• Water filter
• Low pressure switch.
• Antifreeze electric heater on the buffer tank
• Remote keyboard with display.
• Serial interfaces for connection to BMS (proprietary protocol,
Modbus RTU, LonWorks).
• Serial converters (RS485/RS232, RS485/USB) in the case
of centralised unit management.
Option with control
• Clock card
• Serial interface (CAN-bus - Controller Area Network) for the
iDRHOSS system.
• GSM 900/1800 modem kit for remote unit management.
• Rhoss supervision system for unit monitoring and remote
management.
P. 15
Microsystem
5,5÷11,1 kW
5,8÷12,4 kW
PUMP unit
Expansion tank
H
Circulation pump
L
105
107
109
111
5,5
6,9
8,8
10,8 / 11,1
❶ E.E.R.
2,74
2,58
2,66
2,62 / 2,62
● E.S.E.E.R.
3,15
2,77
3,16
3,11 / 3,15
TCAEY-THAEY MODEL
❶ Nominal cooling capacity
kW
❶ Absorbed power (*)
kW
2,00
2,67
3,32
4,12 / 4,25
➋ Nominal heating capacity
kW
5,8
7,5
9,7
12,0 / 12,4
2,74
2,71
2,83
2,72 / 2,78
2,13
2,77
3,41
4,42 / 4,42
14,5 / 14,8
➋ C.O.P.
➋ Absorbed power (*)
kW
❸ Cooling capacity (radiating)
kW
❸ E.E.R. (radiating)
7,5
8,9
12,1
3,71
3,27
3,53
3,20 / 3,27
2,72
3,43
4,53 / 4,53
12,2 / 12,6
❸ Absorbed power (radiating) (*)
kW
2,02
❹ Heating capacity (radiating)
kW
6,00
7,90
9,90
3,70
3,91
3,76
3,66 / 3,77
1,62
2,02
2,63
3,33 / 3,34
❹ C.O.P. (radiating)
❹ Absorbed power (radiating) (*)
kW
➎ Sound pressure level
dB(A)
Scroll/step compressor
No.
Circuits
No.
Water tank content
l
❶ Available head pressure of pump
kPa
Main supply
V-ph-Hz
46
47
47
47
1/1
1/1
1/1
1/1
1
1
1
1
19
19
30
30
55
55
85
75
230-1-50
230-1-50 /
400-3+N-50
230-1-50 /
400-3+N-50
230-1-50 /
400-3+N-50
105
107
109
111
L - Width
mm
990
990
990
990
H - Height PUMP
mm
905
905
1.085
1.085
H - Height TANK & PUMP
mm
905
905
1.295
1.295
P - Depth
mm
380
380
380
380
➏ Weight TCAEY
kg
131
133
157
166
➏ Weight THAEY
kg
141
143
167
176
DIMENSIONS AND WEIGHTS
In the following conditions:
❶ Air: 35°C - Water: 7/12°C
➋ Air: 7°C D.B. - 6°C W.B. - Water: 45/40°C.
❸ Air: 35°C - Water: 18/23°C - ❹ Air: 7°C D.B. - 6°C W.B. - Water 35/30°C
➎ At 5 m from the unit, coil side, in free field (Q = 2).
➏ The weight refers to the unit in its most complete form
● ESEER (European Seasonal EER) - European seasonal average efficiency
(*) Unit without pump
WATER CHILLERS - HEAT PUMPS
P
TCAEY-THAEY 115÷233
Compact-Y Range
Packaged air-cooled reversible water chillers
and heat pumps with axial fans.
Range with hermetic Scroll compressors and
R410A refrigerant gas.
TANK & PUMP unit
Construction features
Factory fitted accessories
Compressor: hermetic, rotary Scroll compressor, complete
with thermal protection and crankcase heater for mod.
127÷233.
Water side heat exchanger: adequately insulated stainless
steel plate exchanger, complete with antifreeze heater and
water flow differential pressure switch.
Air side heat exchanger: finned coil exchanger, with copper
pipes and aluminium fins.
Fan: axial fan with external rotor, equipped with internal thermal
protection and complete with protection grille.
Control: microprocessor electronic control available in 2
versions: Standard, with Adaptive Function logic, and
iDRHOSS compatible, with Adaptive Function Plus logic.
Structure: in galvanized and painted sheet steel, complete
with condensation drain pan.
Models
TCAEY: unit designed for cooling only.
THAEY: heat pump unit.
STANDARD unit (for mod. 133-233 only)
Without pumping group and buffer tank.
PUMP unit
Pumping group complete with: circulation pump, expansion
tank with membrane, manual air bleed valve, safety valve and
pressure gauge.
Pumping group complete with: water buffer tank, circulation
pump, expansion tank with membrane, manual air bleed valve,
automatic air bleed valve, safety valve and pressure gauge.
• -10°C condensation control.
• Antifreeze electric heater on the buffer tank.
• Crankcase heater compressor (mod. 115÷124).
• Protection coil grilles.
• Desuperheater 15% (mod. 133-233).
• 100% heat recovery (mod. 133-233).
• Single pump with increased head pressure
(mod. 133-233).
• Single pump with increased head pressure + buffer (mod.
133-233).
Option with control
• Digital input for double set-point
• 4-20 mA analogue input for shifting set-point.
Accessories supplied loose
• Protection coil grilles.
• Antivibration rubber mountings.
• -10°C condensation control.
• Remote keyboard with display.
• Serial interfaces for connection to BMS (proprietary protocol,
Modbus RTU, LonWorks).
• Serial converters (RS485/RS232, RS485/USB) in the case
of centralised unit management.
Option with control
• Clock card
• Serial interface (CAN-bus - Controller Area Network) for the
iDRHOSS system.
• GSM 900/1800 modem kit for remote unit management.
• Rhoss supervision system for unit monitoring and remote
management.
P. 17
Microsystem
15,4÷32,5 kW
16,8÷37,5 kW
TCAEY-THAEY MODEL
❶ Nominal cooling capacity
kW
115
117
122
124
127
130
133
233
15,4
17,4
22,7
24,3
26,9
29,1
34,0
32,5
❶ E.E.R.
2,76
2,67
2,76
2,62
2,59
2,44
2,56
2,64
● E.S.E.E.R.
3,15
3,11
3,44
3,09
3,18
2,89
2,85
2,92
12,3
❶ Absorbed power (*)
kW
5,6
6,5
8,2
9,3
10,4
11,9
13,3
➋ Nominal heating capacity
kW
16,8
17,9
23,9
26,1
30,7
34,4
39,1
37,5
3,05
2,94
3,02
2,92
3,07
3,10
2,94
3,05
12,3
➋ C.O.P.
➋ Absorbed power (*)
kW
5,5
6,1
7,9
8,9
10,0
11,1
13,3
❸ Sound pressure level
dB(A)
50
50
52
52
53
54
55
55
Scroll/step compressor
No.
1/1
1/1
1/1
1/1
1/1
1/1
1/1
2/2
Circuits
No.
Water tank content
l
❶ Available head pressure of standard pump
kPa
Main supply
V-ph-Hz
1
1
1
1
1
1
1
1
35
35
45
45
45
45
80
80
147
130
130
125
110
105
134
134
400-3+N-50
400-3+N-50
400-3+N-50
400-3+N-50
400-3+N-50
400-3+N-50
400-3+N-50 400-3+N-50
In the following conditions:
❶ Air: 35°C - Water: 7/12°C
❷ Air: 7°C D.B. - 6°C W.B. - Water: 45/40°C.
❸ At 5 m from the unit in free field (Q = 2).
● ESEER (European Seasonal EER) - European seasonal average efficiency
115
117
122
124
127
130
133
233
L - Width STANDARD
mm
–
–
–
–
–
–
1660
1660
L - Width PUMP
mm
1230
1230
1230
1230
1535
1535
1660
1660
L - Width TANK & PUMP
mm
1522
1522
1522
1522
1822
1822
1660
1660
H - Height
mm
1090
1090
1280
1280
1510
1510
1570
1570
P - Depth
mm
580
580
600
600
695
695
1000
1000
❹ Weight TCAEY
kg
210
220
270
280
310
370
450
465
❹ Weight THAEY
kg
215
225
278
288
320
380
460
475
DIMENSIONS AND WEIGHTS
❹ The weight refers to the unit in its most complete form
WATER CHILLERS - HEAT PUMPS
(*) Unit without pump
TCAEY-THAEY 118÷136 H.E.
Compact-Y Range
Radiant Systems
Fan coil systems
C.O.P. > 3.8
High energy efficiency packaged air-cooled
reversible water chillers and heat pumps with
axial fans.
Range with hermetic Scroll compressors and
R410A refrigerant gas.
Construction features
Compressor: hermetic, rotary Scroll compressor, complete
with thermal protection and crankcase heater.
Water side heat exchanger: adequately insulated stainless
steel plate exchanger, complete with antifreeze heater and
water flow differential pressure switch.
Air side heat exchanger: finned coil exchanger, with copper
pipes and aluminium fins.
Fan: axial fans with external rotor, equipped with internal
thermal protection, protection grilles and proportional electronic
device for continuous fan rotation speed regulation.
Control: microprocessor electronic control, iDRHOSS
compatible, with Adaptive Function Plus logic.
Structure: in galvanized and painted sheet steel, complete
with condensation drain pan for THAEY.
Models
TCAEY: unit designed for cooling only.
THAEY: heat pump unit.
PUMP unit
Pumping group complete with: standard circulation pump,
expansion tank with membrane, manual air bleed valve, safety
valve and gauge.
TANK & PUMP unit
• With tank and pump
• With tank, pump and water bypass between primary
and secondary circuit
Pumping group complete with: circulation pump and water
buffer tank or circulation pump, water buffer tank and water
bypass which disconnects the primary from the secondary
water circuit, expansion tank with membrane, manual air bleed
valve, automatic air bleed valve, safety valve and pressure
gauge.
Factory fitted accessories
• Antifreeze electric heater on the buffer tank.
• Protection coil grilles
• Unit base antifreeze electric heater for operation in heat pump
mode at external air temperature of below –5°C.
• Digital input for double set-point
• 4-20 mA analogue input for shifting set-point.
Accessories supplied loose
• Protection coil grilles
• Antivibration rubber mountings.
• Remote keyboard with display.
• Clock card
• Serial interfaces for connection to BMS (proprietary protocol,
Modbus RTU, LonWorks).
• Serial converters (RS485/RS232, RS485/USB) in the case
of centralised unit management.
• Serial interface (CAN-bus - Controller Area Network) for the
iDRHOSS system.
• GSM 900/1800 modem kit for remote unit management.
• Rhoss supervision system for unit monitoring and remote
management.
P. 19
Microsystem
13,4÷27,8 kW
15,6÷31,7 kW
TCAEY-THAEY H.E. MODEL
❶ Nominal cooling capacity (radiating)
kW
❶ E.E.R. (radiating)
❶ Absorbed power (radiating) (*)
kW
➋ Nominal heating capacity (radiating)
kW
➋ C.O.P. (radiating)
118
120
125
129
132
136
17,4
20,1
24,6
28,9
31,5
36,5
3,13
3,16
3,33
3,27
3,37
3,19
5,57
6,35
7,39
8,85
9,36
11,46
15,8
16,2
20,4
23,9
28,2
32,4
3,94
3,89
4,19
4,02
4,08
3,96
➋ Absorbed power (radiating) (*)
kW
4,01
4,16
4,87
5,94
6,91
8,18
❸ Cooling capacity
kW
13,4
15,5
18,7
22,6
24,3
27,8
❸ E.E.R.
2,70
2,92
2,97
2,97
2,96
2,74
● E.S.E.E.R.
3,48
3,51
3,45
3,42
3,58
3,31
10,12
❸ Absorbed power (*)
kW
4,95
5,33
6,30
7,61
8,20
❹ Heating capacity
kW
15,6
16,1
20,3
23,8
27,7
31,7
3,14
3,09
3,32
3,19
3,20
3,13
4,97
5,23
6,10
7,48
8,63
10,12
48
50
52
52
53
54
1/1
1/1
1/1
1/1
1/1
1/1
❹ C.O.P.
❹ Absorbed power
kW
➎ Sound pressure level
dB(A)
Scroll/step compressor
No.
Circuits
No.
Water tank content
l
❶ Available head pressure of pump T
kPa
Main supply
V-ph-Hz
1
1
1
1
1
1
35
35
45
45
45
45
129
108
116
98
95
81
400-3+N-50
400-3+N-50
400-3+N-50
400-3+N-50
400-3+N-50
400-3+N-50
In the following conditions:
❶ Air: 35°C - Water: 18/23°C
❷ Air: 7°C D.B. - 6°C W.B. - Water 35/30°C
❸ Air: 35°C - Water: 7/12°C - ❹ Air: 7°C D.B. - 6°C W.B. - Water: 45/40°C.
➎ At 5 m from the unit, coil side, in free field (Q = 2).
● ESEER (European Seasonal EER) - European seasonal average efficiency
118
DIMENSIONS AND WEIGHTS
120
125
129
132
136
1.230
1.230
1.230
1.535
1.535
1.522
1.522
1.822
1.822
1.280
1.280
1.510
1.510
600
600
695
695
220
270
280
310
370
225
278
288
320
380
L - Width PUMP
mm
1.230
L - Width TANK & PUMP
mm
1.522
1.522
H - Height
mm
1.090
1.090
P - Depth
mm
580
580
➏ Weight TCAEY
kg
210
➏ Weight THAEY
kg
215
➏ The weight refers to the unit in its most complete form
WATER CHILLERS - HEAT PUMPS
(*) Unit without pump
TCAEY-THAEY 245÷265
Compact-Y Range
3 capacity steps
Packaged air-cooled reversible water chillers
and heat pumps with axial fans.
Range with hermetic Scroll compressors and
R410A refrigerant gas.
Construction features
Compressor: hermetic, rotary Scroll compressor, complete
with thermal protection and crankcase heater. 3 capacity steps
with high efficiency at partial loads.
Water side heat exchanger: adequately insulated stainless
steel plate exchanger, complete with antifreeze heater and
water flow differential pressure switch.
Air side heat exchanger: finned coil exchanger, with copper
pipes and aluminium fins.
Fan: axial fans with external rotor, equipped with internal
thermal protection, protection grilles and proportional electronic
device for continuous fan rotation speed regulation.
Control: microprocessor electronic control, iDRHOSS
compatible, with Adaptive Function Plus logic.
Structure: in galvanized and painted sheet steel, complete
with condensation drain pan for THAEY.
Models
TCAEY: unit designed for cooling only.
THAEY: heat pump unit.
Factory fitted accessories
• PUMP with single or double pump, including an automatic
pump in standby, complete with expansion tank, air bleed
valve, safety valve and water pressure gauge. The pumps are
available in the low or high pressure versions.
• TANK&PUMP with water buffer tank and single or double
pump, including an automatic pump in standby, complete with
expansion tank, air bleed valve, safety valve and water
pressure gauge. The pumps are available in the low or high
pressure versions.
• 15% desuperheater.
• 100% heat recovery.
• Refrigerant circuit high and low pressure gauges.
• Protection coil grilles.
• Antifreeze electric heater for buffer tank and pumps.
• Digital input for double set-point
• 4-20 mA analogue input for shifting set-point.
Accessories supplied loose
• Protection coil grilles
• Antivibration rubber mountings.
• Remote keyboard with display.
• Clock card
• Serial interfaces for connection to BMS (proprietary protocol,
Modbus RTU, LonWorks).
• Serial interface (CAN-bus - Controller Area Network) for the
iDRHOSS system.
• Serial converters (RS485/RS232, RS485/USB) in the case
of centralised unit management.
• GSM 900/1800 modem kit for remote unit management.
• Rhoss supervision system for unit monitoring and remote
management.
P. 21
Microsystem
44,2÷64,0 kW
47,8÷67,9 kW
TCAEY-THAEY MODEL
245
250
260
265
44,2
51,3
59,2
64,0
❶ E.E.R.
2,55
2,60
2,68
2,67
● E.S.E.E.R.
3,78
4,31
4,38
4,03
24,0
❶ Nominal cooling capacity
kW
❶ Absorbed power (*)
kW
17,4
19,7
22,1
➋ Nominal heating capacity
kW
47,8
55,8
62,2
67,9
2,89
3,00
3,04
2,91
16,6
18,6
20,5
23,3
56
56
57
57
2/3
2/3
2/3
2/3
➋ C.O.P.
➋ Absorbed power (*)
kW
❸ Sound pressure level
dB(A)
Scroll/step compressor
No.
Circuits
No.
Main supply
V-ph-Hz
1
1
1
1
400-3+N-50
400-3+N-50
400-3+N-50
400-3+N-50
DIMENSIONS AND WEIGHTS
L - Width
mm
245
250
260
265
2.260
2.260
2.260
2.260
H - Height
mm
1.570
1.570
1.570
1.570
P - Depth
mm
1.000
1.000
1.000
1.000
❹ Weight TCAEY
kg
725
750
775
820
❹ Weight THAEY
kg
745
770
795
840
In the following conditions:
❶ Air: 35°C - Water: 7/12°C
❷ Air: 7°C D.B. - 6°C W.B. - Water: 45/40°C.
❸ At 5 m from the unit in free field (Q = 2).
❹ The weight refers to the unit in its most complete form
● ESEER (European Seasonal EER) - European seasonal average efficiency
H
(*) Unit without pump
P
TANK & PUMP
TCAEY-THAEY MODEL
Nominal flow
l/h
Water tank content
l
245
250
260
265
7.600
8.800
10.200
11.000
150
150
150
150
Pump available head pressure
Pump P1
KPa
113
103
88
75
Pump P2
KPa
186
179
169
150
PUMP
TCAEY-THAEY MODEL
Nominal flow
l/h
245
250
260
265
7.600
8.800
10.200
11.000
Pump available head pressure
Pump P1
KPa
122
114
102
92
Pump P2
KPa
195
190
184
167
WATER CHILLERS - HEAT PUMPS
L
TCAIY-THAIY 124-150
Y-Mich Range
Modulating cooling
capacity range: 39-100%
E.S.E.E.R. > 3,9
Packaged air-cooled reversible water chillers
and heat pumps with axial fans.
Range with hermetic Scroll Inverter
compressors.
Construction features
Compressor:hermetic, rotary Scroll compressor, complete
with thermal protection and crankcase heater, activated by
Inverter.
Expansion valve: electronic.
Water side heat exchanger: stainless steel plate exchanger
closed cell polyurethane foam rubber insulation, complete with
antifreeze heater and water flow differential pressure switch.
Air side heat exchanger: featuring finned coil with copper
pipes and aluminium fins, complete with protection grille (model
150 only).
Fan: axial fan with external rotor, equipped with internal thermal
protection and complete with protection grille and modulating
speed control.
Control: microprocessor electronic control, iDRHOSS
compatible
Structure: in galvanized and painted sheet steel (model 124)
or in peraluman (model 150), complete with condensation drain
pan for THAIY.
PUMP unit
• With pump
• With pump and pump in standby
(model 150 only)
Pumping group complete with: single or double circulation pump,
including one standby pump that is automatically activated in the
event of an alarm (model 150 only), expansion tank with
membrane, manual air bleed valve, safety valve, water drain tap
and pressure gauge.
TANK & PUMP unit
• With tank and pump.
• With tank, pump and pump in standby (model 150 only)
Pumping group complete with: water buffer tank complete with
antifreeze electric heater (model 150 only), single or double
pump, including a pump in standby which is automatically
activated in the event of an alarm (model 150 only), expansion
tank with membrane, manual air bleed valve, safety valve, water
drain valve and pressure gauge.
Factory fitted accessories
•
•
•
•
Buffer tank antifreeze electric heater (for mod. 124 only).
Protection coil grilles (for mod. 124 only).
Digital input for double set-point
4-20 mA analogue input for shifting set-point.
Models
Accessories supplied loose
TCAIY: unit designed for cooling only.
THAIY: heat pump unit.
•
•
•
•
•
STANDARD unit
Without pumping group and buffer tank (for model 150 only).
•
•
•
•
Protection coil grilles (for mod. 124 only).
Antivibration rubber mountings.
Remote keyboard with display.
Clock card
Serial interfaces for connection to BMS (proprietary protocol,
Modbus RTU, LonWorks).
Serial converters (RS485/RS232, RS485/USB) in the case of
centralised unit management.
Serial interface (CAN-bus - Controller Area Network) for the
iDRHOSS system.
GSM 900/1800 modem kit for remote unit management.
Rhoss supervision system for unit monitoring and remote
management.
P. 23
TCAIY - THAIY MODEL
❶ Nominal cooling capacity
124(**)
150
23,8
48,1
I NARY
Microsystem
23,8-48,1 kW
27,3-52,9 kW
2,63
kW
❶ E.E.R.
2,53
● E.S.E.E.R.
3,96
4,10
9,42
18,3
❶ Absorbed power (*)
kW
➋ Nominal heating capacity
kW
➋ Absorbed power (*)
kW
❸ Sound pressure level
dB(A)
Water tank content
l
❶ Available head pressure of pump T
kPa
Inverter scroll compressor
No.
Modulating cooling capacity range
Circuits
No.
Main supply
V-ph-Hz
27,3
52,9
2,95
3,05
9,28
17,35
PR E LI
M
➋ C.O.P.
Refrigerant
52
58
45
150
125
198
1
1
39-100%
39-100%
1
1
400-3+N-50
400-3+N-50
R410A
R407C
In the following conditions:
❶ Air: 35°C - Water: 7/12°C
❷ Air: 7°C D.B. - 6°C W.B. - Water: 45°/40°C
❸ At 5 m from the unit in free field (Q = 2).
● ESEER (European Seasonal EER) - European seasonal average efficiency
124
150
mm
1522
2.270
H - Height
mm
1280
1.650
P - Depth
mm
600
968
Weight TCAIY
kg
330
550
Weight THAIY
kg
338
566
DIMENSIONS AND WEIGHTS
L - Width
H
L
P
WATER CHILLERS - HEAT PUMPS
(*) Unit without pump
(**) Available from April 2008
TCAEY-THAEY 270÷2160
Y-Pack Range
3 capacity steps
Packaged air-cooled reversible water chillers
and heat pumps with axial fans.
Range with hermetic Scroll compressors and
R410A refrigerant gas.
Construction features
Compressor: hermetic, rotary Scroll compressor, complete
with thermal protection and crankcase heater.
2 or 3 capacity steps depending on the models with high
efficiency at partial loads.
Water side heat exchanger: stainless steel plate exchanger,
complete with closed cell polyurethane foam rubber insulation
and water flow differential pressure switch.
Air side heat exchanger: finned coil exchanger, with copper
pipes and aluminium fins.
Fan: axial fans with external rotor, equipped with internal
thermal protection, protection grilles and proportional electronic
device for continuous regulation of fan rotation speed (TCAEBY
excluded).
Control: microprocessor electronic control iDRHOSS
compatible, with Adaptive Function Plus logic for connection
with the main BMS on the market (MODBUS RTU, LON).
Structure: load-bearing structure in galvanised and painted
sheet steel with polyester powder coating.
The unit is also complete with:
• Unit with compressor and fan thermal overload switches.
Versions
• B - Standard version (TCAEBY).
• T - High temperature/efficiency version with larger coil
surface (TCAETY-THAETY).
• S - Silenced version complete with soundproofed
compressor compartment, lower fan speed and larger coil
surface (TCAESY-THAESY).
• Q - Supersilenced version complete with soundproofed
compressor compartment, super-low fan speed and larger
coil surface (TCAEQY).
Models
TCAEBY: standard unit designed for cooling only.
TCAETY: high temperature/efficiency unit designed for cooling
only.
TCAESY: silenced unit designed for cooling only.
TCAEQY: supersilenced unit designed for cooling only.
THAETY: heat pump unit.
THAESY: silenced heat pump unit.
Factory fitted accessories
• PUMP with single or double pump, including an automatic
pump in standby, complete with expansion tank, safety valve
and water pressure gauge. The pumps are available in the low
or high pressure versions.
• TANK&PUMP with built-in buffer tank from 250 to 450 litres
and single or double pump, complete with expansion tank, air
bleed valves, safety valve and water pressure gauge.
• Desuperheater.
• 100% heat recovery.
• Electronic expansion valve
• -10°C condensation control (TCAEBY only).
• Power factor correction capacitors (cosφ > 0.91).
• Soft starter.
• Refrigerant circuit high and low pressure gauges.
• Metal filters or coil protection grilles.
• Unit with copper/copper, copper/tin-plated copper or
copper/pre-painted aluminium coils.
• Digital input for double set-point
• 4-20 mA analogue input for shifting set-point.
• Evaporator antifreeze heater, buffer tank, pumps and heat
exchangers for heat recovery if present.
• Serial interface for connection with external BMS.
Accessories supplied loose
• Antivibration rubber mountings.
• Remote keyboard with display.
• Clock card
• GSM 900/1800 modem kit for remote unit management.
• Rhoss supervision system for unit monitoring and remote
management.
P. 25
TCAEBY MODEL
❶ Nominal cooling capacity
kW
❶ E.E.R.
❶ Absorbed power
kW
TCAETY-TCAESY-TCAEQY MODEL
❶ Nominal cooling capacity
kW
❶ Nominal cooling capacity
kW
❶ Nominal cooling capacity
kW
❶ E.E.R.
❶ E.E.R.
❶ E.E.R.
● E.S.E.E.R.
❶ Absorbed power
kW
❶ Absorbed power
kW
❶ Absorbed power
kW
THAETY-THAESY MODEL
➋ Nominal heating capacity
kW
➋ Nominal heating capacity
kW
➋ C.O.P.
➋ C.O.P.
❶ Nominal cooling capacity
kW
❶ Nominal cooling capacity
kW
➋ Absorbed power
kW
➋ Absorbed power
kW
TCAEY-THAEY MODEL
❸ Sound pressure level TCAEBY
dB(A)
❸ Sound pressure level TCAETY-THAETY dB(A)
❸ Sound pressure level TCAESY-THAESYdB(A)
❸ Sound pressure level TCAEQY
dB(A)
❹ Sound power level TCAEBY
dB(A)
❹ Sound power level TCAETY-THAETY dB(A)
❹ Sound power level TCAESY-THAESY dB(A)
❹ Sound power level TCAEQY
dB(A)
Scroll/step compressor
No.
Circuits
No.
Main supply
V-ph-Hz
DIMENSIONS AND WEIGHTS
L - Width version B
mm
L - Width version T - S - Q
mm
H - Height version B
mm
H - Height version T - S - Q
mm
P - Depth version B
mm
P - Depth version T - S - Q
mm
kg
➎ Weight TCAEBY
➎ Weight TCAETY-TCAESY-TCAEQY
kg
➎ Weight THAETY-THAESY
kg
270
67,5
2,65
25,5
270
70,3
70,3
67,0
2,98
2,98
2,70
4,32
23,6
23,6
24,8
270
79,0
79,0
3,36
3,36
69,4
69,4
23,5
23,5
270
60
55
53
51
82
76
74
72
2/3
1
280
75,3
2,69
28,0
280
79,5
79,5
75,0
2,99
2,99
2,85
4,37
26,6
26,6
26,3
280
86,0
86,0
3,44
3,44
77,7
77,7
25,0
25,0
280
60
56
54
52
82
77
75
73
2/2
1
270
2.650
3.150
1.700
1.520
1.210
1.210
685
745
810
280
2.650
3.150
1.700
1.520
1.210
1.210
725
765
830
In the following conditions:
❶ Air: 35°C - Water: 7/12°C - ❷ Air: 7°C D.B. - 6°C W.U.- Water 40/45°C
❸ At 5 m from the unit, coil side, in free field (Q = 2).
❹ Total sound power level in dB(A) on the basis of measurements taken in
accordance with ISO 3744.
● ESEER (European Sesonal EER) - European seasonal average efficiency
290
2100
83,0
96,0
2,56
2,69
32,4
35,7
290
2100
88,0
101,2
88,0
101,2
82,5
95,0
2,90
2,90
2,90
2,90
2,62
2,73
4,35
4,32
30,3
34,9
30,3
34,9
31,5
34,8
290
2100
96,0
111,0
96,0
111,0
3,29
3,34
3,29
3,34
85,2
99,3
85,2
99,3
29,2
33,2
29,2
33,2
290
2100
60
62
56
57
54
55
52
53
82
84
77
78
75
76
73
74
2/3
2/3
1
1
400-3ph+N-50
290
2100
2.650
3.150
3.150
3.150
1.700
1.700
1.520
1.520
1.210
1.210
1.210
1.210
870
945
910
980
975
1045
2115
110,5
2,72
40,6
2115
114,5
108,0
101,0
2,93
2,67
2,34
4,37
39,1
40,4
43,2
2115
122,0
120,0
3,21
3,22
111,0
107,2
38,0
37,3
2115
68
60
57
54
90
84
81
78
2/3
1
2130
120,5
2,64
45,6
2130
126,0
119,0
108,0
2,91
2,67
2,30
4,31
43,3
44,6
47,0
2130
139,0
135,0
3,31
3,31
123,8
118,5
42,0
40,8
2130
68
60
57
54
90
84
81
78
2/2
1
2145
138,5
2,66
52,1
2145
143,0
136,0
125,0
2,90
2,63
2,32
4,29
49,3
51,7
53,9
2145
157,0
154,0
3,22
3,25
141,3
135,6
48,8
47,4
2145
68
62
58
55
90
85
82
79
2/3
1
2160
155,0
2,61
59,4
2160
161,0
151,0
138,0
2,90
2,60
2,20
4,26
55,5
58,1
62,7
2160
175,0
170,0
3,21
3,21
159,8
150,2
54,5
53,0
2160
69
62
58
55
91
85
82
79
2/2
1
2115
3.150
3.250
1.730
2.000
1.210
1.520
1.020
1.130
1.215
2130
3.150
3.250
1.730
2.000
1.210
1.520
1.040
1.195
1.285
2145
3.150
3.250
1.730
2.000
1.210
1.520
1.100
1.225
1.315
2160
3.450
3.250
1.730
2.000
1.210
1.520
1.160
1.290
1.390
TCAESY-THAESY silenced versions
TCAEQY supersilenced versions
WATER CHILLERS - HEAT PUMPS
Macrosystem
67÷161 kW
79÷175 kW
AVAILABLE FROM JUNE 2008
TCAEY-THAEY 4160÷4320
Y-Pack Range
Packaged air-cooled reversible water chillers
and heat pumps with axial fans.
Range with hermetic Scroll compressors and
R410A refrigerant gas.
Construction features
Compressor: hermetic, rotary Scroll compressor, complete
with thermal protection and crankcase heater.
4 capacity steps with high efficiency at partial loads.
Water side heat exchanger: stainless steel plate exchanger,
complete with closed cell polyurethane foam rubber insulation
and water flow differential pressure switch.
Air side heat exchanger: finned coil exchanger, with copper
pipes and aluminium fins.
Fan: axial fan with external rotor, equipped with internal thermal
protection and complete with protection grille.
Control: microprocessor electronic control iDRHOSS
compatible, with Adaptive Function Plus logic for connection
with the main BMS on the market (MODBUS RTU, LON).
Structure: load-bearing structure in galvanised and painted
sheet steel with polyester powder coating.
The unit is also complete with:
• Unit with compressor and fan thermal overload switches.
Versions
• B - Standard version (TCAEBY).
• T - High temperature/efficiency version with larger coil
surface (TCAETY-THAETY).
• S - Silenced version complete with soundproofed
compressor compartment, lower fan speed and larger coil
surface (TCAESY-THAESY).
• Q - Supersilenced version complete with soundproofed
compressor compartment, super-low fan speed and larger
coil surface (TCAEQY).
Models
TCAEBY: standard unit designed for cooling only.
TCAETY: high temperature/efficiency unit designed for cooling
only.
TCAESY: silenced unit designed for cooling only.
TCAEQY: supersilenced unit designed for cooling only.
THAETY: heat pump unit.
THAESY: silenced heat pump unit.
Factory fitted accessories
• PUMP with single or double pump, including an automatic
pump in standby, complete with expansion tank, safety valve
and water pressure gauge. The pumps are available in the low
or high pressure versions.
• TANK&PUMP with up to 1100-litre built-in buffer tank and
single or double pump, complete with expansion tank, air
bleed valves, safety valve and water pressure gauge.
• Desuperheater.
• 100% heat recovery.
• Electronic expansion valve
• -10°C condensation control.
• Power factor correction capacitors (cosφ > 0.91).
• Soundproofing kit (TCAEBY only).
• Refrigerant circuit high and low pressure gauges.
• Metal filters or coil protection grilles.
• Unit with copper/copper, copper/tin-plated copper or
copper/pre-painted aluminium coils.
• Digital input for double set-point
• 4-20 mA analogue input for shifting set-point.
• Evaporator antifreeze heater, buffer tank, pumps and heat
exchangers for heat recovery if present.
• Serial interface for connection with external BMS.
Accessories supplied loose
• Antivibration mountings.
• Remote keyboard with display.
• Clock card
• GSM 900/1800 modem kit for remote unit management.
• Rhoss supervision system for unit monitoring and remote
management.
P. 27
Macrosystem
138÷325 kW
159,6÷342 kW
TCAEBY MODEL
❶ Nominal cooling capacity
❶ E.E.R.
❶ Absorbed power
TCAETY-TCAESY-TCAEQY MODEL
❶ Nominal cooling capacity
❶ Nominal cooling capacity
❶ Nominal cooling capacity
❶ E.E.R.
❶ E.E.R.
❶ E.E.R.
● E.S.E.E.R.
❶ Absorbed power
❶ Absorbed power
❶ Absorbed power
THAETY-THAESY MODEL
➋ Nominal heating capacity
➋ Nominal heating capacity
➋ C.O.P.
➋ C.O.P.
❶ Nominal cooling capacity
❶ Nominal cooling capacity
➋ Absorbed power
➋ Absorbed power
TCAEY-THAEY MODEL
❸ Sound pressure level TCAEBY
❸ Sound pressure level TCAETY - THAETY
❸ Sound pressure level TCAESY - THAESY
❸ Sound pressure level TCAEQY
❹ Sound power level TCAEBY
❹ Sound power levelTCAETY - THAETY
❹ Sound power level TCAESY - THAESY
❹ Sound power level TCAEQY
Scroll/step compressor
Circuits
Main supply
DIMENSIONS AND WEIGHTS
L - Width version B
L - Width TCAETY/TCAESY/TCAEQY
L - Width THAETY - THAESY
H - Height version B
H - Height version T - S
H - Height version Q
P - Depth version B
P - Depth version T - S - Q
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
No.
No.
V-ph-Hz
mm
mm
mm
mm
mm
mm
mm
mm
4160
152,0
2,57
59,1
4160
160,0
153,0
138,0
2,87
2,74
2,24
4,25
55,7
55,8
61,6
4160
166,0
159,6
3,03
3,00
158,0
151,0
54,8
53,2
4160
70
63
59
56
93
86
83
80
4/4
2
4180
170,0
2,51
67,7
4180
182,0
177,0
164,0
2,80
2,70
2,45
4,20
65,0
65,6
66,9
4180
188,0
182,7
2,85
2,89
179,0
174,0
66,0
63,2
4180
70
67
61
58
93
92
86
83
4/4
2
4160
3.140
3.797
3.797
2.140
2.049
2.049
1.200
2.062
4180
3.140
3.797
3.797
2.140
2.100
2.049
1.200
2.062
In the following conditions:
❶ Air: 35°C - Water: 7/12°C - ❷ Air: 7°C D.B. - 6°C W.U.- Water 40/45°C
❸ At 5 m from the unit, coil side, in free field (Q = 2).
❹ Total sound power level in dB(A) on the basis of measurements taken in
accordance with ISO 3744.
➎ Weight refers to the non-accessorised unit when empty.
● ESEER (European Sesonal EER) - European seasonal average efficiency
TCAESY-THAESY silenced versions
TCAEQY supersilenced versions
4200
191,0
2,51
76,1
4200
200,5
192,0
181,0
2,75
2,60
2,25
4,13
72,9
73,8
80,4
4200
220,0
211,1
2,98
3,00
197,0
189,0
73,8
70,4
4200
70
67
61
58
93
92
86
83
4/4
2
4230
219,0
2,53
86,6
4230
225,0
215,0
211,0
2,75
2,60
2,45
4,13
81,8
82,7
86,1
4230
241,0
233,1
2,96
2,98
222,0
212,0
81,4
78,2
4230
72
68
62
59
95
93
87
84
4/4
2
400-3ph+N-50
4200
4230
3.140
4.100
3.797
4.902
4.902
4.902
2.140
2.140
2.100
2.100
2.049
2.049
1.200
1.200
2.062
2.062
4260
244,0
2,51
97,2
4260
257,0
246,0
228,0
2,79
2,75
2,35
4,19
92,1
89,5
97,0
4260
272,0
263,6
2,93
2,97
253,0
242,0
92,8
88,8
4260
72
69
63
59
95
94
88
84
4/4
2
4290
282,0
2,52
112,0
4290
293,0
281,0
259,0
2,77
2,61
2,25
4,16
106,0
108,0
115,0
4290
309,0
303,5
2,92
3,01
289,0
277,0
106,0
101,0
4290
74
69
64
60
97
94
89
85
4/4
2
4320
315,0
2,55
124
4320
325,0
309,0
2,70
2,55
4,11
120,0
121,0
4320
342,0
332,9
2,91
2,96
320,0
304,0
118,0
112,0
4320
74
69
64
97
94
89
4/4
2
4260
4.100
4.902
4.902
2.140
2.100
2.049
1.200
2.062
4290
5.060
4.902
4.902
2.140
2.100
2.049
1.200
2.062
4320
5.060
4.902
4.902
2.140
2.100
–
1.200
2.062
WATER CHILLERS - HEAT PUMPS
PRELIMINARY
TCAE-THAE 270÷2160
TCAE-THAE 4155÷4320
Q-Pack Range
Packaged air-cooled reversible water chillers
and heat pumps with axial fans.
Range with hermetic Scroll compressors and
R407C refrigerant gas.
Models
Construction features
Factory fitted accessories
Compressor: hermetic, rotary Scroll compressor, complete
with thermal protection and crankcase heater.
2 or 4 capacity steps with high efficiency at partial loads.
Water side heat exchanger: crossed-flow stainless steel
plate exchanger, complete with closed cell polyurethane foam
rubber insulation and water flow differential pressure switch.
Air side heat exchanger: finned coil exchanger, with copper
pipes and aluminium fins.
Fan: axial fan with external rotor, equipped with internal thermal
protection and complete with protection grille.
Control: electronic microprocessor control with Adaptive
Function logic for connection with the main BMS on the market
(MODBUS RTU, LON).
Structure: load-bearing structure, in galvanised and painted
sheet steel with polyester powder coating, complete with
soundproofed compressor compartment (mod. 290÷4320).
The unit is also complete with:
• Unit with compressor and fan thermal overload switches.
Versions
• B - Standard version complete with soundproofed technical
compressor compartment (TCAEB-THAEB - models 270-280
excluded).
• S - Silenced version complete with soundproofed technical
compressor compartment (TCAES-THAES models 270-280),
lower fan speed and larger coil surface (TCAES-THAES
models 290÷4320).
TCAEB: unit designed for cooling only.
TCAES: silenced unit designed for cooling only.
THAEB: heat pump unit.
THAES: silenced heat pump unit.
• PUMP with single or double pump, including an automatic
pump in standby, complete with expansion tank, safety valve
and water pressure gauge. The pumps are available in the low
or high pressure versions.
• TANK&PUMP with built-in buffer tank from 380 to 1,100 litres
and single or double pump, complete with expansion tank, air
bleed valves, safety valve and water pressure gauge.
• 15% desuperheater.
• 100% heat recovery.
• Thermostat with display for the heat recovery/desuperheater.
• –10°C condensation control.
• Power factor correction capacitors (cosφ > 0.91).
• Soft starter.
• Refrigerant circuit high and low pressure gauges.
• Metal filters or coil protection grilles.
• Unit with copper/copper, copper/tin-plated copper or
copper/pre-painted aluminium coils.
• Evaporator antifreeze heater, buffer tank, pumps and heat
exchangers for heat recovery if present.
• Serial interface for connection with external BMS.
Accessories supplied loose
• Antivibration rubber mountings.
• Spring antivibration mountings (mod. 4155-4320).
• Remote keyboard with display.
• Clock card
• GSM 900/1800 modem kit for remote unit management.
• Rhoss supervision system for unit monitoring and remote
management.
P. 29
Macrosystem
68,2÷316,2 kW
76,7÷356,2 kW
TCAEB-TCAES MODEL
❶ Nominal cooling capacity
❶ Nominal cooling capacity
❶ E.E.R.
❶ E.E.R.
● E.S.E.E.R.
❶ Absorbed power
❶ Absorbed power
THAEB-THAES MODEL
➋ Nominal heating capacity
➋ Nominal heating capacity
➋ C.O.P.
➋ C.O.P.
❶ Nominal cooling capacity
❶ Nominal cooling capacity
➋ Absorbed power
➋ Absorbed power
TCAEB-TCAES-THAEB-THAES MODEL
❸ Sound pressure level
❸ Sound pressure level
❹ Sound power level
❹ Sound power level
Scroll/step compressor
Circuits
Main supply
DIMENSIONS AND WEIGHTS
L - Width
H - Height
P - Depth
➎ Weight TCAE
➎ Weight THAE
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
dB(A)
dB(A)
dB(A)
dB(A)
No.
No.
V-ph-Hz
mm
mm
mm
kg
kg
270
280
290
2100
2115
2130
2145
2160
70,1
80,9
92,9
105,6
118,2
130,0
147,4
160,3
70,1
80,9
91,6
104,1
116,6
128,2
145,3
157,1
2,98
2,96
2,81
2,78
2,76
2,73
2,89
2,78
2,98
2,96
2,78
2,73
2,72
2,67
2,85
2,70
3,56
3,48
3,33
3,34
3,29
3,25
3,41
3,27
23,5
27,3
33,0
38,0
42,8
47,7
51,0
57,6
23,5
27,3
33,0
38,1
42,9
48,0
51,0
58,1
270
280
290
2100
2115
2130
2145
2160
76,7
87,5
101,6
116,0
131,1
142,6
163,2
179,6
76,7
87,5
95,8
109,2
123,6
134,5
154,2
170,0
2,96
2,89
2,84
2,83
2,86
2,85
2,91
2,90
2,96
2,89
2,74
2,72
2,75
2,75
2,82
2,81
68,2
78,6
90,3
102,6
115,0
126,5
143,5
156,1
68,2
78,6
89,0
101,1
113,3
124,7
141,4
152,9
25,9
30,3
35,8
40,9
45,8
50,0
56,1
61,9
25,9
30,3
35,0
40,1
44,9
48,9
54,7
60,5
270
280
290
2100
2115
2130
2145
2160
55
55
58
58
60
60
62
62
54
54
55
55
57
57
58
58
76
76
83
83
84
84
85
85
75
75
79
79
81
81
82
82
2/2
2/2
2/2
2/2
2/2
2/2
2/2
2/2
2
2
2
2
2
2
2
2
400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50
270
280
290
2100
2115
2130
2145
2160
3.033
3.033
3.084
3.084
3.484
3.484
3.484
3.484
1.880
1.880
2.049
2.049
2.049
2.049
2.049
2.049
1.585
1.585
1.796
1.796
1.796
1.796
1.796
1.796
1.278
1.346
1.631
1.725
1.846
1.857
1.922
1.931
1.330
1.386
1.693
1.791
1.916
1.928
1.993
2.002
4155
148,2
145,4
2,66
2,59
3,73
55,7
56,1
4155
162,2
152,7
2,65
2,54
144,0
141,3
61,1
60,0
4155
63
59
86
83
4/4
2
400-3+N-50
4155
3.797
2.049
2.062
2.158
2.256
4180
171,5
166,1
2,56
2,42
3,64
66,9
68,6
4180
188,1
176,9
2,65
2,53
166,6
161,3
71,0
69,8
4180
63
59
86
83
4/4
2
400-3+N-50
4180
3.797
2.049
2.062
2.382
2.486
In the following conditions:
❶ Air: 35°C - Water: 7/12°C - ❷ Air: 7°C D.B. - 6°C W.U.- Water 40/45°C
❸ At 5 m from the unit, coil side, in free field (Q = 2).
❹ Total sound power level in dB(A) on the basis of measurements taken in
accordance with ISO 3744.
4205
204,2
201,2
2,74
2,70
3,99
74,5
74,6
4205
223,4
209,7
2,74
2,63
198,4
195,5
81,4
79,7
4205
64
60
87
84
4/4
2
400-3+N-50
4205
4.902
2.049
2.062
2.932
3.000
4235
221,7
218,5
2,59
2,54
3,73
85,6
85,9
4235
245,1
230,4
2,72
2,62
215,5
212,3
90,1
88,2
4235
64
60
87
84
4/4
2
400-3+N-50
4235
4.902
2.049
2.062
2.960
3.064
4260
247,0
236,4
2,66
2,44
3,81
92,7
97,0
4260
276,0
259,4
2,83
2,72
240,3
229,8
97,6
95,5
4260
64
60
87
84
4/4
2
400-3+N-50
4260
4.902
2.049
2.062
3.078
3.180
4290
286,9
275,4
2,68
2,54
3,78
106,9
108,5
4290
320,8
302,2
2,80
2,77
279,5
267,8
114,4
109,1
4290
69
64
93
89
4/4
2
400-3+N-50
4290
4.902
2.100
2.062
3.166
3.268
4320
316,2
306,3
2,62
2,53
3,80
120,7
120,9
4320
356,2
336,2
2,80
2,76
307,9
298,1
127,0
121,7
4320
69
64
93
89
4/4
2
400-3+N-50
4320
4.902
2.100
2.062
3.183
3.285
➎ Weight refers to the fully accessorised unit when empty.
● ESEER (European Seasonal EER) - European seasonal average efficiency
TCAES-THAES silenced versions
WATER CHILLERS - HEAT PUMPS
TCAEB-TCAES MODEL
❶ Nominal cooling capacity
kW
❶ Nominal cooling capacity
kW
❶ E.E.R.
❶ E.E.R.
● E.S.E.E.R.
❶ Absorbed power
kW
❶ Absorbed power
kW
THAEB-THAES MODEL
➋ Nominal heating capacity
kW
➋ Nominal heating capacity
kW
➋ C.O.P.
➋ C.O.P.
❶ Nominal cooling capacity
kW
❶ Nominal cooling capacity
kW
➋ Absorbed power
kW
➋ Absorbed power
kW
TCAEB-TCAES-THAEB-THAES MODEL
❸ Sound pressure level
dB(A)
❸ Sound pressure level
dB(A)
❹ Sound power level
dB(A)
❹ Sound power level
dB(A)
Scroll/step compressor
No.
Circuits
No.
Main supply
V-ph-Hz
DIMENSIONS AND WEIGHTS
L - Width
mm
H - Height
mm
P - Depth
mm
➎ Weight TCAE
kg
➎ Weight THAE
kg
TCAEY-THAEY 5350÷6450
Y-Power Range
Packaged air-cooled reversible water chillers
and heat pumps with axial fans.
Range with hermetic Scroll compressors and
R410A refrigerant gas.
Construction features
Compressor: hermetic, rotary Scroll compressor, complete
with thermal protection and crankcase heater.
5 or 6 capacity steps with high efficiency at partial loads.
Electronic expansion valve: as standard on all models.
Water side heat exchanger: stainless steel plate exchanger
with closed cell polyurethane foam rubber insulation, complete
with water flow differential pressure switch and Victaulic
connections.
Air side heat exchanger: finned coil exchanger with copper
pipes and aluminium fins.
Fan: axial fan with external rotor, equipped with internal thermal
protection and complete with protection grille.
Control: electronic microprocessor control prepared for
connection with the main BMS on the market (MODBUS RTU,
LON).
Structure: in galvanised and painted sheet steel, with
polyester powder coating.
The unit is also complete with:
• Low and high pressure gauges for each refrigerant circuit.
Versions
• B -Standard version (TCAEBY-THAEBY).
• S - Silenced version with lower fan speed and soundproofed
compressor cover (TCAESY-THAESY).
• I -Soundproofed version with soundproofed compressor
cover (TCAEIY-THAEIY).
Models
TCAEBY: unit designed for cooling only.
TCAESY: silenced unit designed for cooling only.
TCAEIY: soundproofed unit designed for cooling only.
THAEBY: heat pump unit.
THAESY: silenced heat pump unit.
THAEIY: soundproofed heat pump unit.
Factory fitted accessories
• PUMP with single or double pump, including an automatic
pump in standby. The pumps are available in the low or high
pressure versions.
• TANK&PUMP with 1,100-litre built-in buffer tank and single or
double pump, complete with expansion tank, air bleed valves,
safety valve and water pressure gauge.
• Desuperheater.
• 100% heat recovery.
• Thermostat with display for the heat recovery/desuperheater.
• -10°C condensation control.
• -15°C condensation control.
• Power factor correction capacitors (cosφ > 0.94).
• Unit with compressor and fan thermal overload switches.
• Bottom compartment protection grilles
• Evaporator antifreeze heater, buffer tank and heat exchangers
for heat recovery if present.
• Digital input for double set-point
• Display of refrigerant circuit high/low pressure.
• Control of min/max power supply voltage.
• 4-20 mA analogue input for shifting set-point.
• Unit with copper/pre-painted aluminium/ copper/copper or
copper/tin-plated copper coils.
• Serial interface for connection with external BMS.
Accessories supplied loose
• Spring antivibration mountings.
• Protection coil grilles
• Remote keyboard with display.
P. 31
TCAEBY-TCAESY MODEL
5350
6370
6410
6450
❶ Nominal cooling capacity
kW
345,1
365,3
410,2
455,1
❶ Nominal cooling capacity
kW
338,2
354,3
397,9
446,0
❶ E.E.R.
2,85
2,81
2,68
2,60
❶ E.E.R.
2,80
2,73
2,58
2,50
● E.S.E.E.R.
4,30
4,35
4,31
4,26
● E.S.E.E.R.
4,01
4,05
4,01
3,97
❶ Absorbed power
kW
121,0
130,2
153,2
175,0
❶ Absorbed power
kW
120,6
129,8
154,3
178,1
5350
6370
6410
6450
THAEBY-THAESY MODEL
➋ Nominal heating capacity
kW
372,0
393,6
434,2
486,2
➋ Nominal heating capacity
kW
353,4
373,9
412,5
461,9
➋ C.O.P.
2,95
2,92
2,89
2,84
➋ C.O.P.
2,93
2,90
2,87
2,82
446,1
❶ Nominal cooling capacity
kW
338,2
357,8
402,0
❶ Nominal cooling capacity
kW
331,4
350,6
394,0
437,2
➋ Absorbed power
kW
126,0
134,7
150,2
170,9
➋ Absorbed power
kW
120,6
128,9
143,8
163,7
5350
6370
6410
6450
78
TCAEBY-TCAESY-THAEBY-THAESY MODEL
➌ Sound pressure level
dB(A)
77
77
78
➌ Sound pressure level
dB(A)
71
71
72
72
❹ Sound power level
dB(A)
95
95
96
96
❹ Sound power level
dB(A)
89
89
90
90
Scroll/step compressor
No.
5/5
6/6
6/6
6/6
Circuits
No.
2
2
2
2
Main supply
V-ph-Hz
400-3-50
400-3-50
400-3-50
400-3-50
DIMENSIONS AND WEIGHTS
5350
6370
6410
6450
mm
4.830
4.830
4.830
4.830
H - Height
mm
2.340
2.340
2.340
2.340
P - Depth
mm
2.260
2.260
2.260
2.260
➎ Weight TCAE
kg
3.300
3.450
3.500
3.520
➎ Weight THAE
kg
3.500
3.640
3.680
3.710
L - Width
In the following conditions:
❶ Air: 35°C - Water: 7/12°C - ❷ Air: 7°C D.B. 6°C B.U. - Water 40/45°C
❸ At 1 m from the unit in free field (Q = 2) (average value measured on 4 sides)
❹ Total sound power level in dB(A) on the basis of measurements taken in
accordance with ISO 3744.
➎ Weight refers to the accessorised unit when empty with RPE - KRP
● ESEER (European Seasonal EER) - European seasonal average efficiency
TCAESY-THAESY silenced versions
H
P
L
WATER CHILLERS - HEAT PUMPS
Macrosystem
331,4÷455,1 kW
353,4÷486,2 kW
TCAV 1280÷2450
Q-Power Range
Packaged air cooled water chillers with axial
fans.
Range with semihermetic screw compressors
and R407C refrigerant gas.
Construction features
Compressor: high energy efficiency semi-hermetic screw
compressor, with star-delta limited start and thermal protection,
crankcase heater and compressor dischage shut-off valve.
Water side heat exchanger: shell and tube exchanger
complete with air bleed valve, water drain tap, closed cell
polyurethane rubber insulation and Victaulic connections..
Air side heat exchanger: finned coil exchanger with copper
pipes and aluminium fins.
Fan: axial fan with external rotor, equipped with internal thermal
protection and complete with protection grille.
Control: electronic microprocessor control prepared for
connection with the main BMS on the market (MODBUS RTU,
LON).
Structure: in galvanised and painted sheet steel, with
polyester powder coating.
The unit is also complete with:
• Low and high pressure gauges for each refrigerant circuit.
Versions
• B -Standard version (TCAVB).
• S - Silenced version with soundproofed compressor, lower
fan speed and larger coil surface (TCAVS).
• I - Soundproofed version with soundproofed compressor
cover (TCAVI).
Models
TCAVB: unit designed for cooling only.
TCAVS: silenced unit designed for cooling only.
TCAVI: soundproofed unit designed for cooling only.
Factory fitted accessories
• 15% desuperheater.
• 100% heat recovery.
• Thermostat with display for the heat recovery/desuperheater.
• -10°C condensation control.
• -15°C condensation control.
• Power factor correction capacitors (cosφ > 0.91).
• Unit with compressor and fan thermal overload switches.
• Unit with inlet compressor shut-off valves.
• Bottom compartment protection grilles.
• Unit with stepless capacity control.
• Electronic expansion valve
• Unit with copper/pre-painted aluminium/ copper/copper or
copper/tin-plated copper coils.
• Water differential pressure switch
• Evaporator antifreeze electric heater.
• Serial interface for connection with external BMS.
Accessories supplied loose
• Antivibration rubber mountings.
• Spring antivibration mountings.
• Protection coil grilles.
• Remote keyboard with display.
• Clock card
P. 33
Macrosystem
264,0÷445,5 kW
1280
1320
1360
2410
2450
❶ Nominal cooling capacity
kW
277,62
318,90
355,93
411,64
445,50
❶ Nominal cooling capacity
kW
425,48
264,05
303,79
336,51
393,99
❶ E.E.R.
2,71
2,66
2,68
2,70
2,67
❶ E.E.R.
2,60
2,54
2,56
2,56
2,54
❶ Absorbed power
kW
102,5
120,0
132,7
152,7
167,0
❶ Absorbed power
kW
101,6
119,7
131,7
153,6
167,3
❸ Sound pressure level
dB(A)
67
67
67
68
68
❸ Sound pressure level
dB(A)
61
61
61
62
62
Screw compressor/steps
No.
1/3
1/3
1/3
2/6
2/6
Circuits
No.
Main supply
V-ph-Hz
1
1
1
2
2
400-3-50
400-3-50
400-3-50
400-3-50
400-3-50
1280
1320
1360
2410
2450
mm
3.550
3.550
3.550
4.550
4.550
H - Height
mm
2.350
2.350
2.350
2.350
2.350
P - Depth
mm
2.325
2.325
2.325
2.325
2.325
❹ Weight TCAVB-TCAVI
kg
2.595
2.720
2.773
3.756
3.816
❹ Weight TCAVS
kg
2.751
2.876
2.929
3.964
4.024
DIMENSIONS AND WEIGHTS
L - Width
In the following conditions:
❶ Air: 35°C - Water: 7/12°C
❸ At 5 m from the unit in free field (Q = 2).
❹ Weight refers to unit when empty.
TCAVS silenced versions
H
L
P
WATER CHILLERS - HEAT PUMPS
TCAVB-TCAVS-TCAVI MODEL
TCAVZ 2330÷2700 H.E.
Z-Power Range
E.E.R. > 3,1
High energy efficiency packaged air cooled
water chillers with axial fans.
Range with semihermetic screw compressors
and R134a refrigerant gas.
Models
Construction features
• Shell and tube evaporator (mod. 2330÷2460).
• PUMP with single or double pump, including an automatic
pump in standby. The pumps are available in the low or high
pressure versions.
• TANK&PUMP (mod. 2330÷2460) with 1,100-litre built-in
buffer tank and single or double pump, complete with
expansion tank, air bleed valves, safety valve and water
pressure gauge.
• Desuperheater.
• 100% heat recovery.
• Thermostat with display for the heat recovery/desuperheater.
• -10°C condensation control.
• -15°C condensation control.
• Power factor correction capacitors (cosφ > 0.94).
• Unit with compressor and fan thermal overload switches.
• Unit with compressor shut-off valves.
• Bottom compartment protection grilles
• Unit with linear capacity control compressors.
(25-100%).
• Evaporator antifreeze heater, buffer tank and heat exchangers
for heat recovery if present.
• Digital input for double set-point
• Display of refrigerant circuit high/low pressure.
• Compressor oil level sensor.
• Control of min/max power supply voltage.
• 4-20 mA analogue input for shifting set-point.
• Unit with copper/pre-painted aluminium/ copper/copper or
copper/tin-plated copper coils.
• Serial interface for connection with external BMS.
Compressor: high energy efficiency semi-hermetic screw
compressor, with star-delta limited start and complete with
thermal protection, crankcase heater and compressor
discharge shut-off valve.
Electronic expansion valve: as standard on all models.
Water side heat exchanger (mod. 2330÷2460): stainless
steel plate exchanger with closed cell polyurethane foam rubber
insulation, complete with water flow differential pressure switch
and Victaulic connections.
Water side heat exchanger (mod. 2510÷2700): dry
expansion shell and tube exchanger with counter-current heat
exchange, complete with closed cell polyurethane rubber foam
insulation, water flow differential pressure switch and Victaulic
connections.
Air side heat exchanger: finned coil exchanger with copper
pipes and aluminium fins.
Fan: axial fan with external rotor, equipped with internal thermal
protection and complete with protection grille.
Control: electronic microprocessor control prepared for
connection with the main BMS on the market (MODBUS RTU,
LON).
Structure: in galvanised and painted sheet steel, with
polyester powder coating
The unit is also complete with:
• Low and high pressure gauges for each refrigerant circuit.
Versions
• B - High energy efficiency standard version (TCAVBZ).
• S - Silenced version with lower fan speed and soundproofed
compressor cover (TCAVSZ).
• I - High energy efficiency soundproofed version with soundproofed compressor cover (TCAVIZ).
TCAVBZ: unit designed for cooling only.
TCAVSZ: silenced unit designed for cooling only.
TCAVIZ: soundproofed unit designed for cooling only.
Factory fitted accessories
Accessories supplied loose
• Spring antivibration mountings.
• Protection coil grilles.
• Remote keyboard with display.
• Clock card
P. 35
TCAVBZ-TCAVSZ-TCAVIZ H.E. MODEL
2330
2350
2370
2390
2420
2460
2510
❶ Nominal cooling capacity
kW
333,1
353,2
373,6
390,5
416,5
458,1
510,3
❶ Nominal cooling capacity
kW
324,8
344,1
361,8
379,4
406,9
443,9
495,4
❶ E.E.R.
3,11
3,11
3,10
3,10
3,11
3,10
3,11
❶ E.E.R.
3,09
3,06
3,04
2,96
3,08
3,04
3,01
● E.S.E.E.R.
4,04
4,06
4,08
4,06
4,04
4,06
4,08
● E.S.E.E.R.
3,97
3,98
3,99
3,99
3,99
3,96
3,93
➋ IPLV
4,20
4,22
4,24
4,22
4,20
4,22
4,24
➋ IPLV
4,13
4,14
4,15
4,15
4,15
4,12
4,09
kW
107,0
113,7
120,4
126,1
134,0
148,0
164,3
❶ Absorbed power
kW
105,1
112,5
118,9
128,1
132,2
145,9
164,4
❸ Sound pressure level
dB(A)
80
80
80
80
81
81
81
❸ Sound pressure level
dB(A)
74
74
74
74
75
75
75
Screw compressor/steps
No.
2/6
2/6
2/6
2/6
2/6
2/6
2/6
Circuits
No.
2
2
2
2
2
2
2
Main supply
V-ph-Hz
400-3-50
400-3-50
400-3-50
400-3-50
400-3-50
400-3-50
400-3-50
❶ Absorbed power
2330
2350
2370
2390
2420
2460
2510
mm
4.830
4.830
4.830
4.830
5.830
5.830
5.830
H - Height
mm
2.430
2.430
2.430
2.430
2.430
2.430
2.430
P - Depth
mm
2.260
2.260
2.260
2.260
2.260
2.260
2.260
❹ Weight TCAVBZ
kg
3.780
3.870
3.960
3.970
4.420
4.530
4.740
❹ Weight TCAVIZ - TCAVSZ
kg
4.080
4.170
4.260
4.270
4.720
4.830
5.040
DIMENSIONS AND WEIGHTS
L - Width
TCAVBZ-TCAVSZ-TCAVIZ H.E. MODEL
2550
2570
2610
2640
2680
2700
❶ Nominal cooling capacity
kW
545,0
570,1
611,1
644,7
674,5
693,2
❶ Nominal cooling capacity
kW
676,2
531,0
554,9
593,1
624,6
657,0
❶ E.E.R.
3,17
3,13
3,14
3,10
3,14
3,12
❶ E.E.R.
3,11
3,08
3,07
3,01
3,08
3,04
● E.S.E.E.R.
4,13
4,17
4,17
4,17
4,18
4,18
● E.S.E.E.R.
3,93
3,92
3,97
4,01
4,04
4,06
➋ IPLV
4,29
4,34
4,34
4,34
4,34
4,35
➋ IPLV
4,08
4,08
4,12
4,17
4,20
4,22
❶ Absorbed power
kW
172,1
182,4
194,7
207,7
214,9
222,5
❶ Absorbed power
kW
171,0
180,2
193,5
207,5
213,5
222,3
❸ Sound pressure level
dB(A)
82
82
82
82
82
82
❸ Sound pressure level
dB(A)
76
76
76
76
76
76
Screw compressor/steps
No.
2/6
2/6
2/6
2/6
2/6
2/6
Circuits
No.
2
2
2
2
2
2
Main supply
V-ph-Hz
400-3-50
400-3-50
400-3-50
400-3-50
400-3-50
DIMENSIONS AND WEIGHTS
2550
2570
2610
2640
2680
2700
mm
6.680
6.680
6.680
6.680
7.680
7.680
H - Height
mm
2.430
2.430
2.430
2.430
2.430
2.430
P - Depth
mm
2.260
2.260
2.260
2.260
2.260
2.260
❹ Weight TCAVBZ
kg
5.070
5.090
5.110
5.210
6.140
6.190
❹ Weight TCAVIZ - TCAVSZ
kg
5.370
5.390
5.410
5.510
6.440
6.490
L - Width
In the following conditions:
❶ Air: 35°C - Water: 7/12°C
❷ IPLV (Integrated Part Load Value) - ARI standard 550/590.
❸ At 1 m from the unit in free field (Q = 2) (average value measured on 4 sides)
❹ Empty weight refers to the accessorised unit with RPE - KRP
● ESEER (European Seasonal EER) - European seasonal average efficiency
TCAVSZ silenced versions
WATER CHILLERS - HEAT PUMPS
Macrosystem
324,8÷693,2 kW
TCAVZ 2310÷2670
Z-Power Range
Packaged air cooled water chillers with axial
fans.
Range with semihermetic screw compressors
and R134a refrigerant gas.
Models
TCAVBZ: unit designed for cooling only.
TCAVSZ: silenced unit designed for cooling only.
TCAVIZ: soundproofed unit designed for cooling only.
Factory fitted accessories
Construction features
Compressor: high energy efficiency semi-hermetic screw
compressor, with star-delta limited start and complete with
thermal protection, crankcase heater and compressor
discharge shut-off valve.
Electronic expansion valve: as standard on all models.
Water side heat exchanger (mod. 2310÷2470): stainless
steel plate exchanger with closed cell polyurethane foam rubber
insulation, complete with water flow differential pressure switch
and Victaulic connections.
Water side heat exchanger (mod. 2500÷2670): dry
expansion shell and tube exchanger with counter-current heat
exchange, complete with closed cell polyurethane rubber foam
insulation, water flow differential pressure switch and Victaulic
connections.
Air side heat exchanger: finned coil exchanger with copper
pipes and aluminium fins.
Fan: axial fan with external rotor, equipped with internal thermal
protection and complete with protection grille.
Control: electronic microprocessor control prepared for
connection with the main BMS on the market (MODBUS RTU,
LON).
Structure: in galvanised and painted sheet steel, with
polyester powder coating.
The unit is also complete with:
• Low and high pressure gauges for each refrigerant circuit.
Versions
• B - Standard version (TCAVBZ).
• S - Silenced version with lower fan speed and soundproofed
compressor cover (TCAVSZ).
• I - Soundproofed version with soundproofed compressor
cover (TCAVIZ).
• Shell and tube evaporator (mod. 2310÷2470).
• PUMP with single or double pump, including an automatic
pump in standby. The pumps are available in the low or high
pressure versions.
• TANK&PUMP (mod. 2310÷2470) with 1,100-litre built-in
buffer tank and single or double pump, complete with
expansion tank, air bleed valves, safety valve and water
pressure gauge.
• Desuperheater.
• 100% heat recovery.
• Thermostat with display for the heat recovery/desuperheater.
• -10°C condensation control.
• -15°C condensation control.
• Power factor correction capacitors (cosφ > 0.94).
• Unit with compressor and fan thermal overload switches.
• Unit with inlet compressor shut-off valves.
• Bottom compartment protection grilles
• Unit with linear capacity control compressors.
(25-100%).
• Evaporator antifreeze heater, buffer tank and heat exchangers
for heat recovery if present.
• Digital input for double set-point
• Display of refrigerant circuit high/low pressure.
• Compressor oil level sensor.
• Control of min/max power supply voltage.
• 4-20 mA analogue input for shifting set-point.
• Unit with copper/pre-painted aluminium/ copper/copper or
copper/tin-plated copper coils.
• Serial interface for connection with external BMS.
Accessories supplied loose
• Spring antivibration mountings.
• Protection coil grilles.
• Remote keyboard with display.
• Clock card
P. 37
TCAVBZ-TCAVSZ-TCAVIZ MODEL
2310
2320
2340
2360
2400
2430
2470
❶ Nominal cooling capacity
kW
307,2
326,0
345,2
367,4
394,8
427,9
467,4
❶ Nominal cooling capacity
kW
297,5
315,0
334,5
353,0
382,9
413,4
450
2,83
2,84
2,82
2,80
2,86
2,83
2,80
2,66
❶ E.E.R.
❶ E.E.R.
2,74
2,73
2,71
2,62
2,78
2,72
● E.S.E.E.R.
3,95
3,96
3,96
3,98
3,99
3,91
3,83
● E.S.E.E.R.
3,75
3,78
3,81
3,83
3,86
3,73
3,60
➋ IPLV
4,11
4,11
4,12
4,13
4,15
4,07
3,98
➋ IPLV
3,90
3,93
3,96
3,99
4,01
3,88
3,74
kW
108,4
114,8
122,3
131,4
138,2
151,1
166,7
❶ Absorbed power
kW
108,5
115,5
123,6
134,9
137,8
152,1
169,0
❸ Sound pressure level
dB(A)
79
79
79
79
80
80
80
❸ Sound pressure level
dB(A)
73
73
73
73
74
74
74
Screw compressor/steps
No.
2/6
2/6
2/6
2/6
2/6
2/6
2/6
Circuits
No.
2
2
2
2
2
2
2
Main supply
V-ph-Hz
400-3-50
400-3-50
400-3-50
400-3-50
400-3-50
❶ Absorbed power
400-3-50
400-3-50
2310
2320
2340
2360
2400
2430
2470
mm
3.830
3.830
3.830
3.830
4.830
4.830
4.830
H - Height
mm
2.430
2.430
2.430
2.430
2.430
2.430
2.430
P - Depth
mm
2.260
2.260
2.260
2.260
2.260
2.260
2.260
❹ Weight TCAVBZ
kg
3.420
3.490
3.500
3.580
3.920
4.100
4.280
❹ Weight TCAVIZ - TCAVSZ
kg
3.720
3.790
3.800
3.880
4.220
4.400
4.580
DIMENSIONS AND WEIGHTS
L - Width
TCAVBZ-TCAVSZ-TCAVIZ MODEL
2500
2540
2580
2600
2650
2670
❶ Nominal cooling capacity
kW
505,7
538,1
575,5
607,4
646,8
665,9
❶ Nominal cooling capacity
kW
490,3
520,9
555,4
584,5
627,9
647,1
❶ E.E.R.
2,87
2,87
2,87
2,81
2,87
2,83
❶ E.E.R.
2,79
2,77
2,74
2,67
2,77
2,71
● E.S.E.E.R.
3,91
3,99
3,97
3,95
3,96
3,96
● E.S.E.E.R.
3,72
3,84
3,83
3,82
3,81
3,80
➋ IPLV
4,07
4,15
4,13
4,11
4,11
4,12
➋ IPLV
3,87
3,99
3,98
3,97
3,96
3,95
kW
176,1
187,3
200,7
215,9
225,4
235,7
❶ Absorbed power
kW
175,8
187,8
202,6
219,2
226,7
238,6
❸ Sound pressure level
dB(A)
81
81
81
81
82
82
❸ Sound pressure level
dB(A)
75
75
75
75
76
76
Screw compressor/steps
No.
2/6
2/6
2/6
2/6
2/6
2/6
Circuits
No.
2
2
2
2
2
2
Main supply
V-ph-Hz
400-3-50
400-3-50
400-3-50
400-3-50
400-3-50
400-3-50
❶ Absorbed power
DIMENSIONS AND WEIGHTS
2500
2540
2580
2600
2650
2670
mm
5.830
5.830
5.830
5.830
6.680
6.680
H - Height
mm
2.430
2.430
2.430
2.430
2.430
2.430
P - Depth
mm
2.260
2.260
2.260
2.260
2.260
2.260
❹ Weight TCAVBZ
kg
4.760
4.780
4.800
4.820
5.160
5.210
❹ Weight TCAVIZ - TCAVSZ
kg
5.060
5.080
5.100
5.120
5.460
5.510
L - Width
In the following conditions:
❶ Air: 35°C - Water: 7/12°C
❷ IPLV (Integrated Part Load Value) - ARI standard 550/590.
❸ At 1 m from the unit in free field (Q = 2) (average value measured on 4 sides)
❹ Empty weight refers to the accessorised unit with RPE - KRP
● ESEER (European Seasonal EER) - European seasonal average efficiency
TCAVSZ silenced versions
WATER CHILLERS - HEAT PUMPS
Macrosystem
297,5÷665,9 kW
TCAVZ 2770÷21290 H.E.
Z-Power Range
E.E.R. > 3,2
High energy efficiency packaged air cooled
water chillers with axial fans.
Range with semihermetic screw compressors
and R134a refrigerant gas.
Construction features
Compressor: high energy efficiency semi-hermetic screw
compressor, with star-delta limited start and complete with
thermal protection, crankcase heater and compressor
discharge shut-off valve.
Electronic expansion valve: as standard on all models.
Water side heat exchanger: dry expansion shell and tube
exchanger with counter-current heat exchange, complete with
closed cell polyurethane rubber foam insulation, water flow differential pressure switch and Victaulic connections.
Air side heat exchanger: finned coil exchanger with copper
pipes and aluminium fins.
Fan: axial fan with external rotor, equipped with internal thermal
protection and complete with protection grille.
Control: electronic microprocessor control prepared for
connection with the main BMS on the market (MODBUS RTU,
LON).
Structure: in galvanised and painted sheet steel, with
polyester powder coating.
The unit is also complete with:
• Low and high pressure gauges for each refrigerant circuit.
Versions
• B - High energy efficiency standard version (TCAVBZ).
• S - Silenced version with lower fan speed and soundproofed
compressor cover (TCAVSZ).
• I - High energy efficiency soundproofed version with soundproofed compressor cover (TCAVIZ).
Models
TCAVBZ: unit designed for cooling only.
TCAVSZ: silenced unit designed for cooling only.
TCAVIZ: soundproofed unit designed for cooling only.
Factory fitted accessories
• 15% desuperheater.
• 100% heat recovery.
• Thermostat with display for the heat recovery/desuperheater.
• -10°C condensation control.
• -15°C condensation control.
• Power factor correction capacitors (cosφ > 0.94).
• Unit with compressor and fan thermal overload switches.
• Unit with inlet compressor shut-off valves.
• Bottom compartment protection grilles
• Unit with linear capacity control compressors.
(25-100%).
• Unit with copper/pre-painted aluminium/ copper/copper or
copper/tin-plated copper coils.
• Evaporator antifreeze heater and heat recovery exchangers if
present.
• Serial interface for connection with external BMS.
Accessories supplied loose
• Spring antivibration mountings.
• Protection coil grilles.
• Remote keyboard with display.
• Lifting chain kit.
P. 39
TCAVBZ-TCAVSZ-TCAVIZ H.E. MODEL
2770
2830
2890
2960
21010
21040
❶ Nominal cooling capacity
kW
764,5
831,5
887,8
956,8
1.009,7
1.037,3
❶ Nominal cooling capacity
kW
746,0
811,2
865,5
924,0
973,5
1.004,2
❶ E.E.R.
3,35
3,31
3,26
3,37
3,35
3,35
❶ E.E.R.
3,24
3,17
3,09
3,16
3,13
3,16
● E.S.E.E.R.
4,45
4,39
4,34
4,48
4,47
4,45
● E.S.E.E.R.
4,31
4,22
4,12
4,20
4,16
4,21
4,63
➋ IPLV
4,63
4,57
4,51
4,66
4,65
➋ IPLV
4,48
4,39
4,28
4,37
4,33
4,37
kW
228,0
251,0
272,0
284,0
301,0
310,0
❶ Absorbed power
kW
230,5
256,1
279,8
292,6
311,5
317,9
❸ Sound pressure level
dB(A)
82
82
82
83
83
83
❸ Sound pressure level
dB(A)
76
76
76
77
77
77
Screw compressor/steps
No.
2/8
2/8
2/8
2/8
2/8
2/8
Circuits
No.
2
2
2
2
2
2
Main supply
V-ph-Hz
400-3-50
400-3-50
400-3-50
400-3-50
400-3-50
400-3-50
❶ Absorbed power
2770
2830
2890
2960
21010
21040
L - Width
mm
7.680
7.680
7.680
8.980
8.980
9.980
H - Height
mm
2.430
2.430
2.430
2.430
2.430
2.430
P - Depth
mm
2.260
2.260
2.260
2.260
2.260
2.260
❹ Weight TCAVBZ
kg
5.950
6.360
6.760
7.900
7.920
7.990
❹ Weight TCAVIZ - TCAVSZ
kg
6.290
6.700
7.100
8.250
8.260
8.340
DIMENSIONS AND WEIGHTS
21080
21130
21150
21220
21290
❶ Nominal cooling capacity
kW
1.079,9
1.125,9
1.154,7
1.217,9
1.283,4
❶ Nominal cooling capacity
kW
1.240,4
TCAVBZ-TCAVSZ-TCAVIZ H.E. MODEL
1.051,1
1.099,9
1.116,2
1.178,1
❶ E.E.R.
3,36
3,23
3,43
3,40
3,39
❶ E.E.R.
3,22
3,08
3,21
3,14
3,08
● E.S.E.E.R.
4,48
4,29
4,57
4,53
4,51
● E.S.E.E.R.
4,29
4,10
4,27
4,16
4,10
➋ IPLV
4,66
4,46
4,75
4,71
4,69
➋ IPLV
4,47
4,26
4,44
4,33
4,26
kW
321,0
349,0
336,2
358,0
379,0
❶ Absorbed power
kW
326,0
357,0
348,0
375,8
402,2
❸ Sound pressure level
dB(A)
84
84
84
84
84
❸ Sound pressure level
dB(A)
78
78
78
78
78
Screw compressor/steps
No.
2/8
2/8
2/8
2/8
2/8
Circuits
No.
2
2
2
2
2
Main supply
V-ph-Hz
400-3-50
400-3-50
400-3-50
400-3-50
400-3-50
❶ Absorbed power
21080
21130
21150
21220
21290
mm
10.980
10.980
10.980
10.980
10.980
H - Height
mm
2.430
2.430
2.430
2.430
2.430
P - Depth
mm
2.260
2.260
2.260
2.260
2.260
❹ Weight TCAVBZ
kg
7.960
8.720
9.160
9.200
9.240
❹ Weight TCAVIZ - TCAVSZ
kg
8.300
9.070
9.510
9.560
9.590
DIMENSIONS AND WEIGHTS
L - Width
In the following conditions:
❶ Air: 35°C - Water: 7/12°C
❷ IPLV (Integrated Part Load Value) - ARI standard 550/590.
❸ At 1 m from the unit in free field (Q = 2) (average value measured on 4 sides)
❹ Empty weight refers to the accessorised unit with RPE - KRP
● ESEER (European Seasonal EER) - European seasonal average efficiency
TCAVSZ silenced versions
WATER CHILLERS - HEAT PUMPS
Macrosystem
764,5÷1.283,4 kW
TCAVZ 2750÷21250
Z-Power Range
Packaged air cooled water chillers with axial
fans.
Range with semihermetic screw compressors
and R134a refrigerant gas.
Versions
• B - Standard version (TCAVBZ).
• S - Silenced version with lower fan speed and soundproofed
compressor cover (TCAVSZ).
• I - Soundproofed version with soundproofed compressor
cover (TCAVIZ).
Construction features
Compressor: high energy efficiency semi-hermetic screw
compressor, with star-delta limited start and complete with
thermal protection, crankcase heater and compressor
discharge shut-off valve.
Electronic expansion valve: as standard on all models.
Water side heat exchanger: dry expansion shell and tube
exchanger with counter-current heat exchange, complete with
closed cell polyurethane rubber foam insulation, water flow differential pressure switch and Victaulic connections.
Air side heat exchanger: finned coil exchanger with copper
pipes and aluminium fins.
Fan: axial fan with external rotor, equipped with internal thermal
protection and complete with protection grille.
Control: electronic microprocessor control prepared for
connection with the main BMS on the market (MODBUS RTU,
LON).
Structure: in galvanised and painted sheet steel, with
polyester powder coating.
The unit is also complete with:
• Low and high pressure gauges for each refrigerant circuit.
Models
TCAVBZ: unit designed for cooling only.
TCAVSZ: silenced unit designed for cooling only.
TCAVIZ: soundproofed unit designed for cooling only.
Factory fitted accessories
• 15% desuperheater.
• 100% heat recovery.
• Thermostat with display for the heat recovery/desuperheater.
• -10°C condensation control.
• -15°C condensation control.
• Power factor correction capacitors (cosφ > 0.94).
• Unit with compressor and fan thermal overload switches.
• Unit with inlet compressor shut-off valves.
• Bottom compartment protection grilles
• Unit with linear compressor capacity control (25-100 %).
• Unit with copper/pre-painted aluminium/ copper/copper or
copper/tin-plated copper coils.
• Evaporator antifreeze heater and heat recovery exchangers if
present.
• Serial interface for connection with external BMS.
Accessories supplied loose
• Spring antivibration mountings.
• Protection coil grilles.
• Remote keyboard with display.
• Lifting chain kit.
P. 41
TCAVBZ-TCAVSZ-TCAVIZ MODEL
2750
2810
2870
2940
2990
❶ Nominal cooling capacity
kW
751,1
809,3
863,4
935,5
984,6
❶ Nominal cooling capacity
kW
732,0
785,9
838,0
908,6
954,0
❶ E.E.R.
2,98
2,96
2,91
3,01
2,98
❶ E.E.R.
2,85
2,82
2,77
2,86
2,81
● E.S.E.E.R.
3,96
3,93
3,88
4,00
3,98
● E.S.E.E.R.
3,79
3,76
3,69
3,80
3,73
➋ IPLV
4,12
4,09
4,03
4,17
4,14
➋ IPLV
3,94
3,91
3,83
3,95
3,89
kW
252,0
273,2
296,2
310,6
329,9
❶ Absorbed power
kW
257,0
278,4
303,0
318,2
339,6
❸ Sound pressure level
dB(A)
82
82
82
82
82
❸ Sound pressure level
dB(A)
76
76
76
76
76
Screw compressor/steps
No.
2/8
2/8
2/8
2/8
2/8
Circuits
No.
2
2
2
2
2
Main supply
V-ph-Hz
400-3-50
400-3-50
400-3-50
400-3-50
400-3-50
❶ Absorbed power
DIMENSIONS AND WEIGHTS
2750
2810
2870
2940
2990
mm
6.680
7.680
7.680
7.680
7.680
H - Height
mm
2.430
2.430
2.430
2.430
2.430
P - Depth
mm
2.260
2.260
2.260
2.260
2.260
❹ Weight TCAVBZ
kg
5.310
6.400
6.620
6.790
6.820
❹ Weight TCAVIZ - TCAVSZ
kg
5.610
6.750
6.970
7.140
7.170
L - Width
TCAVBZ-TCAVSZ-TCAVIZ MODEL
21020
21060
21110
21180
21250
❶ Nominal cooling capacity
kW
1.015,5
1.051,6
1.107,3
1.179,7
1.251,5
❶ Nominal cooling capacity
kW
1.212,2
984,6
1.019,7
1.071,8
1.142,7
❶ E.E.R.
3,05
3,13
2,99
3,07
3,15
❶ E.E.R.
2,87
2,95
2,78
2,85
2,90
● E.S.E.E.R.
4,05
4,18
3,98
4,09
4,19
● E.S.E.E.R.
3,82
3,93
3,70
3,77
3,87
➋ IPLV
4,21
4,34
4,14
4,25
4,35
➋ IPLV
3,97
4,09
3,85
3,93
4,02
kW
333,4
335,7
370,5
384,3
397,7
❶ Absorbed power
kW
343,3
346,0
385,0
401,2
417,3
❸ Sound pressure level
dB(A)
82
83
83
83
83
❸ Sound pressure level
dB(A)
76
77
77
77
77
Screw compressor/steps
No.
2/8
2/8
2/8
2/8
2/8
Circuits
No.
2
2
2
2
2
Main supply
V-ph-Hz
400-3-50
400-3-50
400-3-50
400-3-50
400-3-50
❶ Absorbed power
DIMENSIONS AND WEIGHTS
21020
21060
21110
21180
21250
L - Width
mm
7.680
7.680
8.980
8.980
8.980
H - Height
mm
2.430
2.430
2.430
2.430
2.430
P - Depth
mm
2.260
2.260
2.260
2.260
2.260
❹ Weight TCAVBZ
kg
6.940
6.970
8.530
8.740
8.930
❹ Weight TCAVIZ - TCAVSZ
kg
7.290
7.390
8.880
9.090
9.280
In the following conditions:
❶ Air: 35°C - Water: 7/12°C
❷ IPLV (Integrated Part Load Value) - ARI standard 550/590.
❸ At 1 m from the unit in free field (Q = 2) (average value measured on 4 sides)
❹ Empty weight refers to the accessorised unit with RPE - KRP
● ESEER (European Seasonal EER) - European seasonal average efficiency
TCAVSZ silenced versions
WATER CHILLERS - HEAT PUMPS
Macrosystem
732÷1.251,5 kW
TCCEY-THCEY 105÷111
Mini-Y Range
Packaged air-cooled reversible water chillers
and heat pumps with centrifugal fans.
Range with hermetic Scroll compressors and
R410A. refrigerant gas.
Construction features
Compressor: hermetic, rotary Scroll compressor, complete
with thermal protection.
Water side heat exchanger: adequately insulated stainless
steel plate exchanger, complete with antifreeze heater and
water flow differential pressure switch.
Air side heat exchanger: featuring finned coil with copper
pipes and aluminium fins, complete with protection grille.
Fan: centrifugal electric fan with directly coupled motor, fitted
with internal thermal protection and protection grilles.
Control: microprocessor electronic control available in 2
versions: Standard and iDRHOSS compatible, with
Adaptive Function logic.
Structure: in galvanised and painted sheet steel, complete
with condensation drain pan for THCEY.
TANK & PUMP unit
• with standard pump.
• with high-pressure pump.
Pumping group complete with: water buffer tank, standard or
high-pressure circulation pump for models 105-107 only,
expansion tank with membrane, manual air bleed valve,
automatic air bleed valve and safety valve.
Factory fitted accessories
•
•
•
•
Soft - start device (for models with power supply 230V).
-10°C condensation control.
Low pressure switch.
Crankcase heater compressor.
Option with control
• Digital input for double set-point
• 4-20 mA analogue input for shifting set-point.
Accessories supplied loose
PUMP unit
•
•
•
•
•
•
•
•
•
• with standard pump.
• with high-pressure pump.
Pumping group complete with: standard or high-pressure
circulation pump for models 105-107 only, expansion tank with
membrane and safety valve.
Option with control
Models
TCCEY: unit designed for cooling only.
THCEY: heat pump unit.
Antivibration rubber mountings.
-10°C condensation control.
Water filter
Low pressure switch.
Antifreeze electric heater on the buffer tank.
Inlet antivibration connection.
Outlet antivibration connection.
Remote keyboard with display.
Serial interfaces for connection to BMS (proprietary protocol,
Modbus RTU, LonWorks).
• Serial converters (RS485/RS232, RS485/USB) in the case of
centralised unit management.
• Clock card
• Serial interface (CAN-bus - Controller Area Network) for the
iDRHOSS system.
• GSM 900/1800 modem kit for remote unit management.
• Rhoss supervision system for unit monitoring and remote
management.
P. 43
Microsystem
4,8÷10,4 kW
5÷11 kW
TCCEY-THCEY MODEL
❶ Nominal cooling capacity
kW
105
107
109
111
4,8
5,9
8,2
10,0 / 10,4
❶ E.E.R.
2,34
2,27
2,27
2,27 / 2,36
● E.S.E.E.R.
2,52
2,51
2,61
2,55 / 2,58
❶ Absorbed power (*)
kW
2,05
2,59
3,61
4,40
➋ Nominal heating capacity
kW
5,0
6,3
8,3
10,6 / 11,0
2,33
2,49
2,29
2,52 / 2,62
2,14
2,53
3,62
4,20
49
49
51
52
1/1
1/1
1/1
1/1
➋ C.O.P.
➋ Absorbed power (*)
kW
❸ Sound pressure level
dB(A)
Scroll/step compressor
No.
1
1
1
1
2.450
2.400
2.650
2.600
Circuits
No.
Fan nominal air flow
m3/h
External head pressure
Pa
80
70
80
70
Water tank content
l
19
19
30
30
❶ Available head pressure of pump T
kPa
60
60
87
78
230-1-50
230-1-50 /
400-3+N-50
230-1-50 /
400-3+N-50
230-1-50 /
400-3+N-50
Main supply
V-ph-Hz
In the following conditions:
❶ Air: 35°C - Water: 7/12°C
❷ Air: 7°C D.B. - 6°C W.B. - Water: 45/40°C.
❸ At 5 m from the unit in free field (Q = 2).
● ESEER (European Seasonal EER) - European seasonal average efficiency
105
107
109
111
L - Width
mm
990
990
990
990
H - Height PUMP
mm
940
940
1.125
1.125
H - Height TANK & PUMP
mm
940
940
1.330
1.330
P - Depth
mm
630
630
630
630
❹ Weight TCCEY
kg
143
145
164
178
❹ Weight THCEY
kg
153
155
174
188
DIMENSIONS AND WEIGHTS
❹ The weight refers to the unit in its most complete form
P
H
L
WATER CHILLERS - HEAT PUMPS
(*) Unit without pump
TCCE-THCE 114÷126
Compact Range
Packaged air-cooled reversible water chillers
and heat pumps with centrifugal fans.
Range with hermetic Scroll compressors and
R407C refrigerant gas.
Construction features
Compressor: hermetic, rotary Scroll compressor, complete
with thermal protection.
Water side heat exchanger: adequately insulated stainless
steel plate exchanger, complete with antifreeze heater and
water flow differential pressure switch.
Air side heat exchanger: featuring finned coil with copper
pipes and aluminium fins, complete with protection grille.
Fan: centrifugal electric fans with directly coupled motor, fitted
with internal thermal protection and protection grilles.
Control: microprocessor electronic control available in 2
versions: Standard and iDRHOSS compatible, with
Adaptive Function logic.
Structure: peraluman, complete with condensation drain pan
for THCE.
Models
TCCE: unit designed for cooling only.
THCE: heat pump unit.
STANDARD unit
Without pumping group and buffer tank.
TANK & PUMP unit
• With standard pump.
• With high-pressure pump.
Pumping group complete with: water buffer tank, standard or
high-pressure circulation pump for models 114-117 only,
expansion tank with membrane, manual air bleed valve, safety
valve and water drain tap.
Factory fitted accessories
• Horizontal condensation air outlet.
• Antifreeze electric heater on the buffer tank.
Option with control
• Digital input for double set-point
• 4-20 mA analogue input for shifting set-point.
Accessories supplied loose
• Antivibration rubber mountings.
• -10°C condensation control.
• Inlet antivibration connection.
• Outlet antivibration connection.
• Remote keyboard with display.
• Serial interfaces for connection to BMS (proprietary protocol,
Modbus RTU, LonWorks).
• Serial converters (RS485/RS232, RS485/USB) in the case
of centralised unit management.
Option with control
• Clock card
• Serial interface (CAN-bus - Controller Area Network) for the
iDRHOSS system.
• GSM 900/1800 modem kit for remote unit management.
• Rhoss supervision system for unit monitoring and remote
management.
P. 45
Microsystem
13,5÷22 kW
13,6÷24 kW
TANK & PUMP unit
Circulation pump
TCCE-THCE MODEL
❶ Nominal cooling capacity
kW
❶ E.E.R.
❶ Absorbed power (*)
kW
➋ Nominal heating capacity
kW
➋ C.O.P.
➋ Absorbed power (*)
kW
❸ Sound pressure level
dB(A)
Scroll/step compressor
No.
Circuits
No.
Fan nominal air flow
m3/h
External head pressure
Water tank content
114
117
121
126
13,5
15,5
18,2
22,0
2,55
2,53
2,40
2,34
5,31
6,13
7,57
9,40
24,0
13,6
16,4
20,1
2,58
2,72
2,80
2,71
5,27
6,02
7,18
8,86
54
55
56
57
1/1
1/1
1/1
1/1
1
1
1
1
4.720
4.110
5.040
4.485
Pa
90
80
90
80
l
55
55
80
80
❶ Available head pressure of standard pump
kPa
50
48
170
159
❶ Available head pressure of high pressure pump
kPa
179
165
–
–
Main supply
V-ph-Hz
400-3+N-50
400-3+N-50
400-3+N-50
400-3+N-50
DIMENSIONS AND WEIGHTS
114
117
121
126
L - Width
mm
1.320
1.320
1.710
1.710
H - Height STANDARD
mm
1.305
1.305
1.305
1.305
H - Height TANK & PUMP
mm
1.600
1.600
1.600
1.600
P - Depth
mm
558
558
643
643
❹ Weight TCCE
kg
340
360
420
460
❹ Weight THCE
kg
350
370
440
470
In the following conditions:
❶ Air: 35°C - Water: 7/12°C
❷ Air: 7°C D.B. - 6°C W.B. - 70% R.H. - Water: 45/40°C.
❸At 5 m from the unit in free field (Q = 2), with ducted fans.
❹ The weight refers to the unit in its most complete form
(*) Unit without pump
WATER CHILLERS - HEAT PUMPS
Water buffer tank
TCCE-TCPE-THCE-THPE 130÷270
Packaged air-cooled reversible water chillers
and heat pumps with centrifugal fans.
Range with hermetic Scroll compressors and
R407C refrigerant gas.
Construction features
Compressor: hermetic rotary Scroll compressor.
Water side heat exchanger: stainless steel plate exchanger
with closed cell polyurethane foam rubber insulation, complete
with water flow differential pressure switch.
Air side heat exchanger: finned coil exchanger with copper
pipes and aluminium fins.
Fan: centrifugal electric fans with external motor, belt transmission and adjustable pulley.
The condensation air supply is horizontal (suction side).
Control: microprocessor electronic control.
Structure: load-bearing galvanized and painted sheet steel
structure with epoxy powder coating and compressor
compartment lined internally with soundproofing material.
Factory fitted accessories
• TANK&PUMP with integrated buffer tank from 80 to 150 litres
and single or double pump.
• PUMP with pumps for primary circuit or for primary circuits
and secondary circuits.
• CC for unit operation in cooling mode, with external air
temperature up to 10 °C.
• LOW AMBIENT (TCCE-TCPE only) for unit operation with
low external air temperature (down to –10°C).
• Vertical condensation air supply.
• Protection coil grilles
• Refrigerant circuit high and low pressure gauges.
• Evaporator antifreeze electric heater.
Accessories supplied loose
• Antivibration rubber mountings.
• Water filter
• Remote keyboard with display.
• RS 485 serial interface.
• RS 232 hardware key.
Versions
TANK & PUMP Accessory
• B - Standard version with standard fans (TCCEB-THCEB)
and high-pressure fans (TCPEB-THPEB).
• Built-in pumping group complete with: water buffer tank,
circulation pump, expansion tank, pressure gauge, bleed and
safety valve and water drain.
• The pump is available in a single or double configuration,
including one in stand-by, and in 4 sizes for combination with
the TCCE-TCPE and THCE-THPE units.
Models
TCCEB: unit designed for cooling only.
THCEB: heat pump unit.
TCPEB: unit designed for cooling only.
THPEB: heat pump unit.
PUMP Accessory
Version fitted with a maximum of 3 pumps:
• P - Primary circuit pump in single configuration.
• DP - Primary circuit pump in double configuration, with one in
stand-by.
• PU - Secondary circuit pump in single configuration.
• DPU - Secondary circuit pump in double configuration, in
combination with primary circuit pump.
P. 47
Macrosystem
30,1÷66,3 kW
34,9÷77,1 kW
TCCEB-THCEB-TCPEB-THPEB MODEL
130
135
140
150
160
270
❶ Nominal cooling capacity
kW
30,1
34,5
37,3
47,2
59,4
66,3
➋ Nominal heating capacity
kW
34,9
41,2
43,1
55,9
65,3
77,1
❸ Sound pressure level
dB(A)
54
59
57
57
60
64
Scroll/step compressor
No.
1/1
1/1
1/1
1/1
1/1
2/2
1
1
1
1
1
1
8.500
11.000
15.000
15.000
17.000
20.000
Circuits
No.
Fan nominal air flow
m3/h
❶ Max. available head pressure fan
Pa
145
155
125
125
150
155
❶ Absorbed power TCCEB
kW
12,1
14,5
14,9
18,7
22,9
28,8
➋ Absorbed power THCEB
kW
11,4
13,8
13,6
17,8
21,5
28,8
Main supply
V-ph-Hz
400-3+N-50
400-3+N-50
400-3+N-50
400-3+N-50
400-3+N-50
400-3+N-50
130
135
140
150
160
270
mm
1.855
1.855
2.355
2.355
2.355
2.355
H - Height
mm
1.916
1.916
1.916
1.916
1.916
1.916
P - Depth
mm
910
910
1.010
1.010
1.010
1.010
❹ Weight TCCEB-TCPEB
kg
646
666
781
885
946
1.022
❹ Weight THCEB-THPEB
kg
669
687
805
910
982
1.057
DIMENSIONS AND WEIGHTS
L - Width
In the following conditions:
❶ Air: 35°C - Water: 7/12°C - ❷ Air: 7°C D.B. - 6°C W.B. - Water 40/45°C
❸ At 5 m from the unit in free field (Q = 1), with ducted fans.
❹ Weight refers to the fully accessorised unit when empty.
TANK & PUMP
TCCEB-THCEB-TCPEB-THPEB MODEL
Nominal flow
l/h
Water tank content
l
130
135
140
150
160
270
5.177
5.934
6.416
8.118
10.217
11.404
80
80
150
150
150
150
–
Pump P1
KPa
136
132
138
130
–
Pump P3
KPa
218
214
219
215
–
–
Pump P5
KPa
–
–
–
–
138
129
Pump P7
KPa
–
–
–
–
279
275
PUMP P (pump for primary circuit)
TCCEB-THCEB-TCPEB-THPEB MODEL
Nominal flow
l/h
130
135
140
150
160
270
5.177
5.934
6.416
8.118
10.217
11.404
Available head pressure of PUMP P pump
Pump P1
KPa
141
140
139
135
–
–
Pump P3
KPa
222
222
220
215
–
–
Pump P5
KPa
–
–
–
–
141
137
Pump P7
KPa
–
–
–
–
284
280
PUMP P/PU (pumps for primary and secondary circuit)
TCCEB - THCEB - TCPEB - THPEB MODEL
Nominal flow
l/h
130
135
140
150
160
270
5.177
5.934
6.416
8.118
10.217
11.404
–
Available head pressure of PUMP P/PU pump
Pump P1/PU1
KPa
161
160
159
158
–
Pump P1/PU3
KPa
243
242
241
239
–
–
Pump P5/PU5
KPa
–
–
–
–
165
164
Pump P5/PU7
KPa
–
–
–
–
309
305
WATER CHILLERS - HEAT PUMPS
Available head pressure of TANK & PUMP pump
TCHEY-THHEY 105÷112
Comby-Flow Range
Fan coil systems
Radiant Systems
Geothermal applications
Packaged water-cooled reversible water
chillers and heat pumps on the cooling circuit.
Range with hermetic Scroll compressors and
R410A refrigerant gas.
Construction features
Compressor: hermetic, rotary Scroll compressor, complete
with thermal protection.
Primary side heat exchanger (user): adequately insulated
stainless steel plate exchanger, complete with antifreeze heater
and water flow differential pressure switch.
Well or water pipe side heat exchanger (disposal unit):
adequately insulated stainless steel plate exchanger, complete
with antifreeze heater and water flow differential pressure
switch (for THHEY).
Control: microprocessor electronic control available in 2
versions: Standard and iDRHOSS compatible, with
Adaptive Function logic.
Structure: in galvanised and painted sheet steel with polyester
powder coating, complete with soundproofed compressor
compartment.
Models
TCHEY: unit designed for cooling only.
THHEY: heat pump unit.
STANDARD unit
• Without circulation pump.
Primary side (user): expansion tank with membrane, safety
valve, water drain valve, manual air bleed valve, gauge.
PUMP unit
• With circulation pump
Primary side (user): pumping group complete with circulation
pump, membrane expansion tank, safety valve, water drain
valve, manual air bleed valve, gauge.
Factory fitted accessories
• Pressure switch valve
• Pressure switch valve and bypass solenoid valve (only
THHEY).
Option with control
• Water circuit heat pump (for TCHEY only).
• Digital input for double set-point
• 4-20 mA analogue input for shifting set-point.
Accessories supplied loose
• Water buffer tank
• Buffer connection pipes
• Water filter
• Antivibration rubber mountings.
• Antifreeze electric heater on the buffer tank.
• Low pressure switch.
• Remote keyboard with display.
• Serial interfaces for connection to BMS (proprietary protocol,
Modbus RTU, LonWorks).
• Serial converters (RS485/RS232, RS485/USB) in the case
of centralised unit management.
Option with control
• Clock card
• Serial interface (CAN-bus - Controller Area Network) for the
iDRHOSS system.
• GSM 900/1800 modem kit for remote unit management.
• RHOSS supervision software for unit monitoring and remote
management.
P. 49
TCHEY-THHEY MODEL
105
107
109
112
5,4
6,8
9,3
12,0
❶ E.E.R.
3,47
3,20
3,40
3,33
● E.S.E.E.R.
3,54
3,76
3,95
3,91
❶ Nominal cooling capacity
kW
❶ Absorbed power (*)
kW
1,56
2,12
2,74
3,60
➋ Nominal heating capacity
kW
6,5
8,2
10,8
13,9
3,18
2,84
3,05
3,17
2,04
2,88
3,54
4,38
➋ C.O.P.
➋ Absorbed power (*)
kW
❸ Nominal cooling capacity (radiating)
kW
❸ E.E.R. (radiating)
7,6
8,9
13,2
16,5
4,75
4,24
4,89
4,46
❸ Absorbed power (radiating) (*)
kW
1,6
2,1
2,7
3,7
❹ Heating capacity (radiating)
kW
6,9
8,9
11,5
14,8
4,48
❹ C.O.P. (radiating)
4,60
4,05
4,26
❹ Absorbed power (radiating) (*)
kW
1,5
2,2
2,7
3,3
❺ Heating capacity (geothermal)
kW
5,1
6,7
8,3
11,0
3,40
2,91
3,07
3,33
1,5
2,3
2,7
3,3
49,1
51,1
51,3
53,1
1/1
❺ C.O.P. (geothermal)
❺ Absorbed power (geothermal) (*)
kW
➏ Sound pressure level
dB(A)
Scroll/step compressor
No.
1/1
1/1
1/1
Circuits
No.
1
1
1
1
Water buffer tank content KA
l
20
20
30
30
❶ Available head pressure of pump
kPa
47
55
82
78
230-1-50
230-1-50
400-3+N-50
230-1-50
400-3+N-50
230-1-50
400-3+N-50
Main supply
V-ph-Hz
DIMENSIONS AND WEIGHTS
105
107
109
112
L - Width
mm
585
585
660
660
H - Height STANDARD - PUMP
mm
535
535
535
535
H - Height STANDARD - PUMP + KA
mm
855
855
855
855
P - Depth
mm
386
386
420
420
❼ Weight TCHEY P
kg
75
80
90
93
❼ Weight THHEY P
kg
78
83
94
97
Weight KA
kg
28
28
33
33
In the following conditions:
❶ Chilled water: 7/12°C - Condenser water: 30/35°C
❷ Hot water: 40/45°C - Evaporator water: 10°C - Flow in summer mode
❸ Chilled water: 18/23°C - Condenser water: 30/35°C
❹ Hot water: 30/35°C - Evaporator water: 10°C - Flow in summer mode
❺ Hot water: 30/35°C - Evaporator water: 0/–3°C, 30% glycol
➏ At 1 m from the unit, coil side, in free field (Q = 2).
❼ The weight refers to the unit in its most complete form
Circulation pump
● ESEER (European Seasonal EER) - European seasonal average efficiency
(*) STANDARD unit
KA = Water buffer tank
KTC = Connection pipes
Pressure switch valve
H
H
KA
L
P
L
C
KT
P
WATER CHILLERS - HEAT PUMPS
Microsystem
5,4÷12 kW
6,5÷13,9 kW
TCHE-THHE 115÷165
Mini-Q Flow Range
Compact Flow range (models 120-165)
Packaged water-cooled reversible water
chillers and heat pumps on the cooling circuit.
Range with hermetic Scroll compressors and
R407C refrigerant gas.
Construction features
Compressor: hermetic, rotary Scroll compressor, complete
with thermal protection.
Water side heat exchangers: stainless steel plate
exchangers.
The evaporator (TCHE) or evaporator/condenser (THHE) heat
exchanger comes complete with water flow differential
pressure switch.
Control: microprocessor electronic control.
Structure: in galvanised and painted sheet steel with polyester
powder coating, complete with soundproofed compressor
compartment.
Versions
• B - Standard version (TCHEB-THHEB).
Models
TCHEB: unit designed for cooling only.
THHEB: heat pump unit.
Factory fitted accessories
• Refrigerant circuit high and low pressure gauges.
Accessories supplied loose
• Pressure switch valve
• Pressure switch valve and bypass solenoid valve.
(THHE only).
• Antivibration rubber mountings.
• Remote keyboard with display.
• Serial interface for connection to BMS (proprietary protocol,
Modbus RTU).
• RS 485/RS232 serial converter in the event of centralised
unit management.
• Pumping groups with buffer tank PBHI (for models 155-165
only).
P. 51
12,3÷63,6 kW
15,2÷72,4 kW
TCHEB-THHEB MODEL
❶ Nominal cooling capacity
kW
❶ E.E.R.
115
120
125
135
140
155
165
12,3
18,1
25,3
33,5
39,1
51,4
63,6
3,40
3,41
3,35
3,42
3,52
3,59
3,31
❶ Absorbed power
kW
3,6
5,4
7,4
9,5
10,9
15,5
18,7
➋ Nominal heating capacity
kW
15,2
22,4
31,4
41,0
47,7
58,5
72,4
3,38
3,34
3,34
3,50
3,51
3,06
3,12
4,5
6,7
9,4
11,7
13,6
19,1
23,2
➋ C.O.P.
➋ Absorbed power
kW
❸ Sound power level
dB(A)
57
60
64
67
68
71
72
Scroll/step compressor
No.
1/1
1/1
1/1
1/1
1/1
1/1
1/1
Circuits
No.
1
1
1
1
1
1
1
Main supply
V-ph-Hz
400-3+N-50
400-3+N-50
400-3+N-50
400-3+N-50
400-3+N-50
400-3+N-50
400-3+N-50
115
120
125
135
140
155
165
mm
750
750
750
750
750
987
987
H - Height
mm
869
869
869
869
869
869
869
P - Depth
mm
567
567
567
567
567
639
639
Weight TCHEB
kg
177
217
232
258
281
510
530
Weight THHEB
kg
187
227
242
268
291
550
570
DIMENSIONS AND WEIGHTS
L - Width
H
L
P
WATER CHILLERS - HEAT PUMPS
In the following conditions:
❶ TCHEB-THHEB - Condenser water: 30/35°C - Chilled water: 12/7°C.
➋ THHEB - Hot water: 40/45°C - Evaporator water: 10°C - Flow in summer mode
❸ Total sound power level in dB(A) on the basis of measurements taken in
accordance with ISO 3744.
TCHE-THHE 280÷4260
Q-Flow Range
Packaged water-cooled reversible water
chillers and heat pumps on the cooling circuit.
Range with hermetic Scroll compressors and
R407C refrigerant gas.
Construction features
Compressor: hermetic, rotary Scroll compressor, complete
with thermal protection.
Water side heat exchangers: stainless steel plate
exchangers.
The evaporator (TCHE) or evaporator/condenser (THHE) heat
exchanger comes complete with water flow differential
pressure switch.
Control: microprocessor electronic control.
Structure: in galvanised and painted sheet steel, with
polyester powder coating.
The unit is also complete with:
• High and low pressure gauges complete with capillaries.
Versions
• B - Standard version (TCHEB-THHEB).
• I - Soundproofed version with soundproofed compressor
cover (THEY-THHEI).
Models
TCHEB: unit designed for cooling only.
TCHEI: soundproofed unit designed for cooling only.
THHEB: heat pump unit.
THHEI: soundproofed heat pump unit.
Accessories supplied loose
• Pressure switch valve
• Pressure switch valve and bypass solenoid valve.
(THHE only).
• Antivibration rubber mountings.
• Remote keyboard with display.
• Serial interface for connection to BMS (proprietary protocol,
Modbus RTU).
• RS 485/RS232 serial converter in the event of centralised
unit management.
• Inlet and outlet water manifolds (mod.4160÷4260).
• Pumping group with PBHI buffer tank.
P. 53
Macrosystem
76,5÷255,3 kW
86,6÷289,9 kW
❶ Nominal cooling capacity
kW
❶ E.E.R.
280
2110
2130
4160
4190
4220
4240
4260
76,5
103,4
127,6
153,0
180,0
206,9
231,1
255,3
3,41
3,39
3,36
3,41
3,39
3,37
3,36
3,39
❶ Absorbed power
kW
22,6
30,8
37,4
45,2
53,4
61,6
68,2
74,8
➋ Nominal heating capacity
kW
86,6
117,4
145,0
173,1
204,0
234,9
262,4
289,9
➋ C.O.P.
3,06
3,09
3,12
3,06
3,08
3,09
3,11
3,12
28,3
38,0
46,4
56,6
66,3
76,1
84,4
92,8
dB(A)
71
74
75
76
78
79
80
80
❸ Sound power level
dB(A)
69
72
73
74
76
77
78
78
Scroll/step compressor
No.
2/2
2/2
2/2
4/4
4/4
4/4
4/4
4/4
Circuits
No.
1
1
1
2
2
2
2
2
Main supply
V-ph-Hz
➋ Absorbed power
kW
❸ Sound power level
400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50
In the following conditions:
❶ TCHEB-THHEB - Condenser water: 30/35°C - Chilled water: 12/7°C.
➋ THHEB - Hot water: 40/45°C - Evaporator water: 10°C - Flow in summer mode
❸ Total sound power level in dB(A) on the basis of measurements taken in
accordance with ISO 3744.
DIMENSIONS AND WEIGHTS
TCHEI-THHEI soundproofed versions
280
2110
2130
4160
4190
4220
4240
4260
mm
1.214
1.214
1.214
2.407
2.407
2.407
2.407
2.407
H - Height
mm
1.703
1.703
1.703
1.709
1.709
1.709
1.709
1.709
P - Depth
mm
873
873
873
873
873
873
873
873
Weight TCHE
kg
675
825
850
982
1.110
1.217
1.246
1.270
Weight THHE
kg
690
840
865
1.008
1.123
1.231
1.271
1.297
L - Width
H
P
L
WATER CHILLERS - HEAT PUMPS
TCHEB-TCHEI-THHEB-THHEI MODEL
TCHVZ 1200÷31630
Z-Flow Range
E.E.R. > 4,75
Packaged water-cooled water chillers.
Range with semihermetic screw compressors
and R134a refrigerant gas.
Versions
Construction features
Models
Compressor: high energy efficiency semi-hermetic screw
compressor, with part-winding or star-delta limited start
(depending on model) and complete with thermal protection,
crankcase heater and compressor discharge shut-off valve.
Electronic expansion valve: as standard on all models.
Water side heat exchanger (evaporator): dry expansion
shell and tube exchanger with counter-current heat exchange,
complete with closed cell polyurethane rubber foam insulation,
water flow differential pressure switch and Victaulic
connections.
Water side heat exchanger (condenser): shell and tube
complete with safety valve, and service valve on the highpressure refrigerant circuit.
Control: electronic microprocessor control prepared for
connection with the main BMS on the market (MODBUS RTU,
LON).
Structure: in galvanised and painted sheet steel, with
polyester powder coating.
• B - Standard version (TCHVBZ).
• I - Soundproofed version with soundproofed compressor
cover (TCHVIZ).
TCHVBZ: unit designed for cooling only.
TCHVIZ: soundproofed unit designed for cooling only.
Factory fitted accessories
• 15% desuperheater.
• 100% heat recovery.
• Thermostat with display for the heat recovery/desuperheater.
• Prepared for heat pump function.
• Power factor correction capacitors (cosφ > 0.94).
• Unit with thermal overload switches
• Unit with compressor inlet shut-off valves.
• Unit with stepless capacity control compressors (50-100 %
for each compressor).
• Evaporator antifreeze electric heater.
• Digital input for double set-point
• Display of refrigerant circuit high/low pressure.
• Compressor oil level sensor.
• Control of min/max power supply voltage.
• 0-10V analogue input for condensation control performed by
external device.
• 4-20 mA analogue input for shifting set-point.
• Serial interface for connection with external BMS.
Accessories supplied loose
• Spring antivibration mountings.
• Antivibration rubber mountings.
• Clock card
• Remote keyboard with display.
P. 55
TCHVBZ-TCHVIZ MODEL
❶ Nominal cooling capacity
❶ E.E.R.
● E.S.E.E.R.
❶ Absorbed power
❸ Sound power level
❸ Sound power level
Screw compressor/steps
Circuits
Main supply
DIMENSIONS AND WEIGHTS
L - Width
H - Height
P - Depth
➎ Weight TCHVBZ
➎ Weight TCHVIZ
TCHVBZ-TCHVIZ MODEL
❶ Nominal cooling capacity
❶ E.E.R.
● E.S.E.E.R.
❶ Absorbed power
❸ Sound power level
❸ Sound power level
Screw compressor/steps
Circuits
Main supply
DIMENSIONS AND WEIGHTS
L - Width
H - Height
P - Depth
➎ Weight TCHVBZ
➎ Weight TCHVIZ
TCHVBZ-TCHVIZ MODEL
❶ Nominal cooling capacity
❶ E.E.R.
● E.S.E.E.R.
❶ Absorbed power
❸ Sound power level
❸ Sound power level
Screw compressor/steps
Circuits
Main supply
DIMENSIONS AND WEIGHTS
L - Width
H - Height
P - Depth
➎ Weight TCHVBZ
➎ Weight TCHVIZ
TCHVBZ-TCHVIZ MODEL
❶ Nominal cooling capacity
❶ E.E.R.
● E.S.E.E.R.
❶ Absorbed power
❸ Sound power level
❸ Sound power level
Screw compressor/steps
Circuits
Main supply
DIMENSIONS AND WEIGHTS
L - Width
H - Height
P - Depth
➎ Weight TCHVBZ
➎ Weight TCHVIZ
kW
kW
dB(A)
dB(A)
No.
No.
V-ph-Hz
mm
mm
mm
kg
kg
kW
kW
dB(A)
dB(A)
No.
No.
V-ph-Hz
mm
mm
mm
kg
kg
kW
kW
dB(A)
dB(A)
No.
No.
V-ph-Hz
mm
mm
mm
kg
kg
kW
kW
dB(A)
dB(A)
No.
No.
V-ph-Hz
mm
mm
mm
kg
kg
1200
199,7
4,93
5,97
40,5
94
92
1/3
1
400-3-50
1200
3.460
1.460
1.000
1.333
1.588
1230
226,3
4,92
5,72
46,0
94
92
1/3
1
400-3-50
1230
3.460
1.460
1.000
1.359
1.614
1280
277,3
4,91
5,73
56,5
97
95
1/3
1
400-3-50
1280
3.440
1.460
1.000
1.695
1.950
1310
306,3
4,89
5,69
62,7
97
95
1/3
1
400-3-50
1310
3.440
1.460
1.000
1.713
1.968
1350
347,6
4,93
5,97
70,5
97
95
1/3
1
400-3-50
1350
3.450
1.640
1.000
1.865
2.120
1410
404,6
4,93
5,89
82,1
97
95
1/3
1
400-3-50
1410
3.450
1.640
1.000
2.354
2.609
1460
462,4
4,90
5,75
94,3
97
95
1/3
1
400-3-50
1460
3.450
1.640
1.000
2.393
2.648
1530
524,9
4,90
5,72
107,2
98
96
1/3
1
400-3-50
1530
3.450
1.740
1.000
2.642
2.897
1590
589,3
4,92
6,00
119,8
98
96
1/3
1
400-3-50
1590
3.450
1.740
1.000
2.687
2.942
2400
391,7
4,90
5,70
80,0
97
95
2/6
2
400-3-50
2400
3.880
1.840
1.300
2.366
2.796
2420
413,0
4,81
5,68
85,8
97
95
2/6
2
400-3-50
2420
3.880
1.840
1.300
2.393
2.823
2440
432,0
4,75
5,60
91,0
97
95
2/6
2
400-3-50
2440
4.000
1.840
1.300
2.438
2.868
2510
506,8
4,80
5,68
105,6
99
97
2/6
2
400-3-50
2510
4.070
1.960
1.300
2.923
3.353
2560
550,8
4,94
5,93
111,5
99
97
2/6
2
400-3-50
2560
4.070
1.960
1.300
3.257
3.687
2600
592,0
4,92
5,95
120,3
99
97
2/6
2
400-3-50
2600
4.070
1.960
1.300
3.280
3.710
2630
621,6
4,93
5,83
126,1
99
97
2/6
2
400-3-50
2630
4.070
1.960
1.300
3.297
3.227
2680
676,8
4,93
5,73
137,3
99
97
2/6
2
400-3-50
2680
4.070
1.960
1.300
3.364
3.794
2710
709,8
4,93
5,71
144,1
99
97
2/6
2
400-3-50
2710
4.070
1.960
1.300
3.407
3.837
2750
742,0
4,88
5,69
152,0
99
97
2/6
2
400-3-50
2750
4.120
1.840
1.300
3.880
4.310
31300
1.282,9
4,98
6,00
257,7
101
99
3/9
3
400-3-50
31300
4.940
2.220
1.700
6.735
7.335
2790
787,0
4,83
5,72
162,8
99
97
2/6
2
400-3-50
2790
4.000
1.840
1.300
4.366
4.796
31350
1.330,0
4,93
5,89
270,0
101
99
3/9
3
400-3-50
31350
4.940
2.220
1.700
6.767
7.367
In the following conditions:
❶ Chilled water: 7/12°C - Condenser inlet water: 30/35°C
❸ Total sound power level in dB(A) on the basis of measurements taken in
accordance with ISO 3744.
➎ Empty weight
● ESEER (European Seasonal EER) - European seasonal average efficiency
2880
879,1
4,92
5,98
178,7
99
97
2/6
2
400-3-50
2880
4.000
1.910
1.300
4.596
5.026
31390
1.377,2
4,87
5,87
282,9
101
99
3/9
3
400-3-50
31390
4.940
2.220
1.700
6.792
7.392
2930
927,2
4,81
5,82
192,8
99
97
2/6
2
400-3-50
2930
4.000
1.910
1.300
4.629
5.059
21030
1.016,6
4,84
5,81
210,0
99
97
2/6
2
400-3-50
21030
4.000
1.950
1.300
4.739
5.169
31460
1.437,5
4,87
5,83
295,4
102
100
3/9
3
400-3-50
31460
4.940
2.220
1.700
6.831
7.431
TCHVIZ soundproofed version
21110
1.087,3
4,88
5,96
222,8
99
97
2/6
2
400-3-50
21110
4.000
1.950
1.300
4.830
5.260
31520
1.518,5
4,91
5,90
309,0
102
100
3/9
3
400-3-50
31520
4.940
2.220
1.700
6.920
7.520
21180
1.155,8
4,92
5,86
2,34,9
99
97
2/6
2
400-3-50
21180
4.000
1.950
1.300
4.878
5.308
31590
1.580,8
4,91
5,89
321,7
102
100
3/9
3
400-3-50
31590
4.940
2.220
1.700
7.008
7.608
21260
1.208,4
4,87
5,85
248,0
99
97
2/6
2
400-3-50
21260
4.000
1.950
1.300
4.914
5.344
31630
1.629,2
4,87
5,90
334,2
102
100
3/9
3
400-3-50
31630
4.940
2.220
1.700
7.097
7.697
WATER CHILLERS - HEAT PUMPS
Macrosystem
199,7÷1.629,2 kW
TCEE 105÷165
Mini-Q Flow E range (models 105-115)
Compact Flow E range (models 120-165)
Cooling-only condenserless units to be
connected to CCAM remote condensers.
Range with hermetic Scroll compressors and
R407C refrigerant gas.
Construction features
Compressor: hermetic, rotary Scroll compressor, complete
with thermal protection.
Water side heat exchanger: stainless steel plate exchanger
complete with water flow differential pressure switch.
Control: microprocessor electronic control.
Structure: in galvanised and painted sheet steel with polyester
powder coating, complete with soundproofed compressor
compartment.
Versions
• B - Standard version (TCEEB).
Models
TCEEB: unit designed for cooling only.
Factory fitted accessories
• Modulating condensation control (in combination with CCAM
only).
• Refrigerant circuit high and low pressure gauges.
Accessories supplied loose
• Antivibration rubber mountings.
• Remote keyboard with display.
• Serial interface for connection to BMS (proprietary protocol,
Modbus RTU).
• RS 485/RS232 serial converter in the event of centralised
unit management.
• CCAM remote condensers.
• Pumping groups with buffer tank PBHI (for models 155-165
only).
P. 57
5,5÷62,2 kW
TCEEB MODEL
❶ Nominal cooling capacity
kW
❶ E.E.R.
105
115
120
125
135
140
155
165
5,5
11,6
17,2
24,3
31,8
37,1
50,2
62,2
3,30
3,58
3,52
3,58
3,68
3,74
3,40
3,49
❶ Absorbed power
kW
2,0
4,1
6,0
8,4
10,8
12,7
17,1
20,8
➋ Sound power level
dB(A)
51
57
60
64
67
68
71
72
Scroll/step compressor
No.
1/1
1/1
1/1
1/1
1/1
1/1
1/1
1/1
1
Circuits
No.
Main supply
V-ph-Hz
1
1
1
1
1
1
1
400-3+N-50
400-3+N-50
400-3+N-50
400-3+N-50
400-3+N-50
400-3+N-50
400-3+N-50
Recommended combinations with CCAM remote condensers
TCEEB MODEL
CCAM MODEL Version N "Normal"
❸ Sound pressure level
CCAM MODEL Version S "Silenced"
❸ Sound pressure level
CCAM MODEL Version Q "Supersilenced"
❸ Sound pressure level
105
115
120
125
135
140
155
165
–
–
120 N
125 N
135 N
140 N
155 N
165 N
–
–
51
48
48
54
50
56
105 S
115 S
120 S
125 S
135 S
140 S
155 S
165 S
45
42
45
45
42
49
44
51
105 Q
115 Q
120 Q
125 Q
135 Q
140 Q
155 Q
165 Q
33
32
35
35
34
38
40
40
105
115
120
125
135
140
155
165
mm
750
750
750
750
750
750
987
987
H - Height
mm
869
869
869
869
869
869
869
869
P - Depth
mm
615
615
615
615
615
615
636
636
Weight TCEEB
kg
154
172
211
224
247
270
490
505
DIMENSIONS AND WEIGHTS
L - Width
H
L
P
WATER CHILLERS - HEAT PUMPS
In the following conditions:
❶ Chilled water: 12/7°C - Dew point: 50°C.
➋ Total sound power level in dB(A) on the basis of measurements taken in accordance with
ISO 3744.
❸ At 10 m from the unit in free field (Q = 2)
TCEE 280÷4260
Q-Flow E Range
Cooling-only condenserless units to be
connected to CCAM remote condensers.
Range with hermetic Scroll compressors and
R407C refrigerant gas.
Construction features
Compressor: hermetic, rotary Scroll compressor, complete
with thermal protection.
Water side heat exchanger: stainless steel plate exchanger
complete with water flow differential pressure switch.
Control: microprocessor electronic control.
Structure: in galvanised and painted sheet steel, with
polyester powder coating.
The unit is also complete with:
• High and low pressure gauges complete with capillaries.
Versions
• B - Standard version (TCCEB).
• I - Soundproofed version with soundproofed compressor
cover (TCCEI).
Models
TCCEB: unit designed for cooling only.
TCCEI: soundproofed unit designed for cooling only.
Factory fitted accessories
• Modulating condensation control (in combination with CCAM
only).
Accessories supplied loose
• Antivibration mountings.
• Remote keyboard with display.
• Serial interface for connection to BMS (proprietary protocol,
Modbus RTU).
• RS 485/RS232 serial converter in the event of centralised
unit management.
• CCAM remote condensers.
• Pumping group with PBHI buffer tank.
P. 59
Macrosystem
74,2÷249 kW
280
2110
2130
4160
4190
4220
4240
4260
kW
74,2
100,4
124,5
148,4
174,6
200,8
224,9
249,0
3,47
3,44
3,51
3,47
3,46
3,44
3,48
3,51
❶ Absorbed power
kW
25,4
34,2
41,7
50,8
59,6
68,4
75,9
83,4
➋ Sound pressure level
dB(A)
71
74
75
76
78
79
80
80
➋ Sound pressure level
dB(A)
69
72
73
74
76
77
78
78
Scroll/step compressor
No.
2
2
2
4
4
4
4
4
Circuits
No.
1
1
1
2
2
2
2
2
Main supply
V-ph-Hz 400-3+N-50
400-3+N-50
400-3+N-50
400-3+N-50
400-3+N-50
400-3+N-50
TCEEB-TCEEI MODEL
❶ Nominal cooling capacity
❶ E.E.R.
400-3+N-50 400-3+N-50
Recommended combinations with CCAM remote condensers
280
CCAM MODEL Version N "Normal"
❸ Sound pressure level
CCAM MODEL Version S "Silenced"
❸ Sound pressure level
CCAM MODEL Version Q "Supersilenced"
❸ Sound pressure level
2110
280 N
2110 N
2130 N
62
64
59
280 S
2110 S
2130 S
51
52
52
280 Q
2110 Q
2130 Q
45
43
45
In the following conditions:
❶ Chilled water: 12/7°C - Dew point: 50°C.
➋ Total sound power level in dB(A) on the basis of measurements taken in
accordance with ISO 3744.
❸ At 10 m from the unit in free field (Q = 2).
▼ Each model must be combined with two condensers (one per circuit) from the
CCAM range.
Circuits
2130
4160(▼)
4190(▼)
4220(▼)
4240(▼)
(1)
280 N
280 N
2110 N
2110 N
4260(▼)
2130 N
(2)
280 N
2110 N
2110 N
2130 N
2130 N
(1/2)
62/62
62/64
64/64
64/59
59/59
(1)
280 S
280 S
2110 S
2110 S
2130 S
(2)
280 S
2110 S
2110 S
2130 S
2130 S
(1/2)
62/62
62/64
64/64
64/59
59/59
(1)
280 Q
280 Q
2110 Q
2110 Q
2130 Q
(2)
280 Q
2110 Q
2110 Q
2130 Q
2130 Q
(1/2)
62/62
62/64
64/64
64/59
59/59
TCEEI soundproofed version
280
2110
2130
4160
4190
4220
4240
4260
mm
1.214
1.214
1.214
2.407
2.407
2.407
2.407
2.407
H - Height
mm
1.703
1.703
1.703
1.079
1.709
1.709
1.709
1.709
P - Depth
mm
873
873
873
873
873
873
873
873
Weight TCEE
kg
645
790
808
906
1.015
1.121
1.140
1.157
DIMENSIONS AND WEIGHTS
L - Width
H
P
L
WATER CHILLERS - HEAT PUMPS
TCEEB-TCEEI MODEL
TCEVZ 1200÷31630
Z-Flow E Range
E.E.R. > 4,75
Cooling-only conderserless units.
Range with semihermetic screw compressors
and R134a refrigerant gas.
Construction features
Compressor: high energy efficiency semi-hermetic screw
compressor, with part-winding or star-delta limited start
(depending on model) and complete with thermal protection,
crankcase heater and compressor discharge shut-off valve.
Electronic expansion valve: as standard on all models.
Water side heat exchanger (evaporator): dry expansion
shell and tube exchanger with counter-current heat exchange,
complete with closed cell polyurethane rubber foam insulation,
water flow differential pressure switch and Victaulic
connections.
Control: electronic microprocessor control prepared for
connection with the main BMS on the market (MODBUS RTU,
LON).
Structure: in galvanised and painted sheet steel, with
polyester powder coating.
Versions
• B - Standard version (TCHVBZ).
• I - Soundproofed version with soundproofed compressor
cover (TCHVIZ).
Models
TCEVBZ: unit designed for cooling only.
TCEVIZ: soundproofed unit designed for cooling only.
Factory fitted accessories
• Power factor correction capacitors (cosφ > 0.94).
• Unit with thermal overload switches
• Unit with inlet compressor shut-off valves.
• Unit with stepless capacity control compressors (50-100 %
for each compressor).
• Evaporator antifreeze electric heater.
• Digital input for double set-point
• Compressor oil level sensor.
• Control of min/max power supply voltage.
• 4-20 mA analogue input for shifting set-point.
• Serial interface for connection with external BMS.
Accessories supplied loose
• Spring antivibration mountings.
• Antivibration rubber mountings.
• Clock card
• Remote keyboard with display.
P. 61
TCEVBZ-TCEVIZ MODEL
❶ Nominal cooling capacity
❶ E.E.R.
❶ Absorbed power
❸ Sound power level
❸ Sound power level
Screw compressor/steps
Circuits
Main supply
DIMENSIONS AND WEIGHTS
L - Width
H - Height
P - Depth
➎ Weight TCEVBZ
➎ Weight TCEVIZ
TCEVBZ-TCEVIZ MODEL
❶ Nominal cooling capacity
❶ E.E.R.
❶ Absorbed power
❸ Sound power level
❸ Sound power level
Screw compressor/steps
Circuits
Main supply
DIMENSIONS AND WEIGHTS
L - Width
H - Height
P - Depth
➎ Weight TCEVBZ
➎ Weight TCEVIZ
TCEVBZ-TCEVIZ MODEL
❶ Nominal cooling capacity
❶ E.E.R.
❶ Absorbed power
❸ Sound power level
❸ Sound power level
Screw compressor/steps
Circuits
Main supply
DIMENSIONS AND WEIGHTS
L - Width
H - Height
P - Depth
➎ Weight TCEVBZ
➎ Weight TCEVIZ
TCEVBZ-TCEVIZ MODEL
❶ Nominal cooling capacity
❶ E.E.R.
❶ Absorbed power
❸ Sound power level
❸ Sound power level
Screw compressor/steps
Circuits
Main supply
DIMENSIONS AND WEIGHTS
L - Width
H - Height
P - Depth
➎ Weight TCEVBZ
➎ Weight TCEVIZ
kW
kW
dB(A)
dB(A)
No.
No.
V-ph-Hz
mm
mm
mm
kg
kg
kW
kW
dB(A)
dB(A)
No.
No.
V-ph-Hz
mm
mm
mm
kg
kg
kW
kW
dB(A)
dB(A)
No.
No.
V-ph-Hz
mm
mm
mm
kg
kg
kW
kW
dB(A)
dB(A)
No.
No.
V-ph-Hz
mm
mm
mm
kg
kg
1200
171,9
3,4
50,5
94
92
1/3
1
400-3-50
1200
3.440
1.460
1.000
1.078
1.333
1230
190,8
3,3
58,1
94
92
1/3
1
400-3-50
1230
3.440
1.460
1.000
1.093
1.348
1280
238,1
3,3
72,2
97
95
1/3
1
400-3-50
1280
3.420
1.460
1.000
1.410
1.665
1310
260,4
3,3
79,0
97
95
1/3
1
400-3-50
1310
3.440
1.460
1.000
1.414
1.669
1350
300,6
3,4
88,1
97
95
1/3
1
400-3-50
1350
3.450
1.640
1.000
1.557
1.812
1410
346,2
3,3
104,0
97
95
1/3
1
400-3-50
1410
3.450
1.640
1.000
2.032
2.287
1460
399,7
3,3
122,2
97
95
1/3
1
400-3-50
1460
3.450
1.640
1.000
2.038
2.293
1530
446,4
3,3
135,3
98
96
1/3
1
400-3-50
1530
3.460
1.740
1.000
2.252
2.507
1590
508,9
3,4
149,7
98
96
1/3
1
400-3-50
1590
3.460
1.740
1.000
2.281
2.536
2400
335,8
3,3
100,7
97
95
2/6
2
400-3-50
2400
3.870
1.490
1.300
1.797
2.227
2420
356,6
3,3
108,3
97
95
2/6
2
400-3-50
2420
3.870
1.490
1.300
1.811
2.241
2440
372,1
3,2
115,7
97
95
2/6
2
400-3-50
2440
3.870
1.490
1.300
1.819
2.249
2510
431,9
3,3
130,6
99
97
2/6
2
400-3-50
2510
4.070
1.610
1.300
2.311
2.741
2560
473,4
3,3
144,4
99
97
2/6
2
400-3-50
2560
4.070
1.610
1.300
2.629
3.059
2600
506,4
3,3
151,5
99
97
2/6
2
400-3-50
2600
4.070
1.610
1.300
2.637
3.067
2630
529,3
3,3
158,4
99
97
2/6
2
400-3-50
2630
4.070
1.610
1.300
2.638
3.068
2680
581,4
3,5
168,0
99
97
2/6
2
400-3-50
2680
4.070
1.610
1.300
2.698
3.128
2710
614,1
3,5
176,6
99
97
2/6
2
400-3-50
2710
4.070
1.610
1.300
2.733
3.163
2750
647,8
3,4
192,1
99
97
2/6
2
400-3-50
2750
4.120
1.490
1.300
3.176
3.606
2790
681,6
3,3
207,6
99
97
2/6
2
400-3-50
2790
4.000
1.490
1.300
3.631
4.061
31300
1.129,6
3,6
314,1
101
99
3/9
3
400-3-50
31300
4.940
1.620
2.000
5.555
6.155
In the following conditions:
❶ Chilled water: 12/7°C - Dew point: 50°C.
❸ Total sound power level in dB(A) on the basis of measurements taken in
accordance with ISO 3744.
➎ Weight of fully accessorised unit when empty.
31350
1.178,3
3,6
331,8
101
99
3/9
3
400-3-50
31350
4.940
1.620
2.000
5.570
6.170
2880
753,9
3,3
226,5
99
97
2/6
2
400-3-50
2880
4.000
1.560
1.300
3.844
4.272
31390
1.227,0
3,5
349,5
101
99
3/9
3
400-3-50
31390
4.940
1.620
2.000
5.585
6.185
2930
801,4
3,3
244,4
99
97
2/6
2
400-3-50
2930
4.000
1.560
1.300
3.859
4.289
21030
896,1
3,5
257,9
99
97
2/6
2
400-3-50
21030
4.000
1.600
1.300
3.936
4.366
31460
1.287,5
3,5
367,1
102
100
3/9
3
400-3-50
31460
4.940
1.620
2.000
5.600
6.200
TCEVIZ soundproofed version
21110
959,4
3,5
271,0
99
97
2/6
2
400-3-50
21110
4.000
1.600
1.300
3.993
4.423
31520
1.340,1
3,5
380,4
102
100
3/9
3
400-3-50
31520
4.940
1.620
2.000
5.678
6.278
21180
1.027,8
3,6
285,5
99
97
2/6
2
400-3-50
21180
4.000
1.600
1.300
4.024
4.454
31590
1.388,5
3,5
393,4
102
100
3/9
3
400-3-50
31590
4.940
1.620
2.000
5.710
6.310
21260
1.101,5
3,7
299,4
99
97
2/6
2
400-3-50
21260
4.000
1.600
1.300
4.044
4.474
31630
1.424,8
3,5
406,4
102
100
3/9
3
400-3-50
31630
4.940
1.620
2.000
5.790
6.390
WATER CHILLERS - HEAT PUMPS
Macrosystem
171,9÷1.424,8 kW
Polyvalent ecological system.
Applications of EXPSYSTEMS
• EXPSYSTEMS is the polyvalent ecological system designed by
RHOSS to satisfy chilled and hot water demands simultaneously or independently with a single unit, according to the
operating mode chosen, i.e. AUTOMATIC or SELECT. It is
designed for use in 2- and 4-pipe systems, at any time of year.
How does it work?
The evoluted microprocessor control manages the two
EXPSYSTEMS operating modes, AUTOMATIC and SELECT,
catering for the demands of 2- or 4-pipe systems.
• AUTOMATIC allows for the simultaneous or separate
production of chilled and hot water, in a completely automatic
fashion.
• SELECT allows for the production of hot water and heating
water on the basis of system demands and the priorities
assigned by the user.
2-pipe systems
• Air conditioning and the production of hot water in a 2-pipe
system is a typical application in residential units, hotels,
hospitals, gyms and hospitality structures in general.
• EXPSYSTEMS in AUTOMATIC mode is used in the summer
months for cooling and the production of hot water.
• EXPSYSTEMS in SELECT mode is used in between seasons
or in winter for heating and the production of hot water on the
basis of the priority assigned.
4-pipe systems
• Increasingly frequently, modern HVAC installations require the
simultaneous production of hot and chilled water. This can
occur more often because of:
- the development of new types of thermal insulation for
buildings;
- increase in internal loads (CED, WEB, etc.);
- lighting systems;
- the presence of large windows;
- the growing importance attributed to air quality, which
requires the use of conditioning systems throughout the year.
• In these kinds of application EXPSYSTEMS can be used in
AUTOMATIC mode throughout the year, catering for simultaneous or separate hot and chilled water demands in a
completely automatic way.
P. 63
5,4÷307,1 kW
6,5÷357,3 kW
2-pipe systems
AUTOMATIC or SELECT mode
Summer months “AUTOMATIC”
Winter months “SELECT”
cooling and hot water
heating and hot water
COLD
WATER
HOT
WATER
HOT
WATER
HOT
WATER
4-pipe systems
AUTOMATIC mode for the entire year
Mid season
Cooling
cooling and heating
SOUTH
COLD
WATER
HOT
WATER
COLD
WATER
Winter months
heating
NORTH
HOT
WATER
COLD
WATER
HOT
WATER
WATER CHILLERS - HEAT PUMPS
Summer months
TXAEY 117÷133
Compact-Y EXP Range
C.O.P. > 6,1
EXPSYSTEMS - Polyvalent ecological aircooled system with axial fans.
Range with hermetic Scroll compressors and
R410A refrigerant gas.
Construction features
Compressor: hermetic, rotary Scroll compressor, complete
with thermal protection and crankcase heater.
Main and secondary heat exchanger: adequately insulated
stainless steel plate exchanger, complete with antifreeze heater
and water flow differential pressure switch.
Air side heat exchanger: finned coil exchanger with copper
pipes and aluminium fins.
Fan: electric axial fans with external rotor, equipped with
internal thermal protection, protection grilles and proportional
electronic device for continuous fan rotation speed regulation.
Control: microprocessor electronic control, iDRHOSS
compatible, with Adaptive Function logic.
Structure: in galvanised and painted sheet steel, complete
with condensation drain pan.
STANDARD unit (for mod. 133 only)
Without pumping group and buffer tank.
PUMP unit
Pumping group for main circuit complete with: circulation
pump, expansion tank with membrane, manual bleed valve and
safety valve, pressure gauge.
TANK&PUMP unit (for mod. 133 only)
Pumping group for main circuit only complete with: water buffer
tank, circulation pump, expansion tank with membrane, manual
air bleed valve, automatic air bleed valve and safety valve,
pressure gauge.
Factory fitted accessories
• Antifreeze electric heater on the buffer tank.
• Protection coil grilles.
• Single pump with increased head pressure (mod. 133).
• Single pump with increased head pressure + buffer tank
(mod. 133)
• Digital input for double set-point
• 4-20 mA analogue input for shifting set-point.
Models
Accessories supplied loose
TXAEY: standard EXPSYSTEMS unit.
• Protection coil grilles
• Antivibration rubber mountings.
• Remote keyboard with display.
• Clock card
• Serial interfaces for connection to BMS (proprietary protocol,
Modbus RTU, LonWorks).
• Serial converters (RS485/RS232, RS485/USB) in the case
of centralised unit management.
• Serial interface (CAN-bus - Controller Area Network) for the
iDRHOSS system.
• GSM 900/1800 modem kit for remote unit management.
• Rhoss supervision system for unit monitoring and remote
management.
P. 65
Microsystem
17,4÷34 kW
17,9÷39,1 kW
TXAEY MODEL
117
124
130
133
❶ Nominal cooling capacity
(AUTOMATIC 1)
kW
17,4
23,6
28,6
34,0
❹ Recovery heating capacity
(AUTOMATIC 2)
kW
20,8
30,4
37,2
44,2
➋ Nominal heating capacity
(SELECT 1-2 AUTOMATIC 3)
kW
17,9
26,1
34,4
39,1
❶ Absorbed power (*)
(AUTOMATIC 1)
kW
6,4
9,4
11,7
13,3
❹ Absorbed power (*)
(AUTOMATIC 2)
kW
4,9
7,4
9,8
11,5
➋ Absorbed power (*)
(SELECT 1-2 AUTOMATIC 3)
kW
6,1
8,9
11,1
13,3
6,62
6,72
6,13
6,25
50
52
54
55
1/1
❹ C.O.P.
(AUTOMATIC 2)
❸ Sound pressure level
dB(A)
Scroll/step compressor
No.
1/1
1/1
1/1
Circuits
No.
1
1
1
1
Water tank content
l
–
–
–
80
❶ Available head pressure of standard pump
kPa
130
131
110
134
Main supply
V-ph-Hz
400-3+N-50
400-3+N-50
400-3+N-50
400-3+N-50
In the following conditions:
❶ Air: 35°C - Water: 7/12°C
❷ Air: 7°C D.B. - 6°C W.B. - Water 40/45°C
❸ At 5 m from the unit in free field (Q = 2).
❹ Evaporator water: 7/12°C. Recovery outlet water 45°C - Nominal flow.
DIMENSIONS AND WEIGHTS
117
124
130
133
mm
1.522
1.522
1.822
1.660
H - Height
mm
1.090
1.280
1.510
1.570
P - Depth
mm
580
600
695
1.000
Weight TXAEY
kg
220
280
370
470
L - Width
H
H
L
L
P
P
WATER CHILLERS - HEAT PUMPS
(*) Unit without pump
TXAEY 245÷265
Compact-Y EXP Range
C.O.P. > 6.9
EXPSYSTEMS - Polyvalent ecological aircooled system with axial fans.
Range with hermetic Scroll compressors and
R410A refrigerant gas.
Construction features
Compressor: hermetic, rotary Scroll compressor, complete
with thermal protection and crankcase heater.
Main and secondary heat exchanger: adequately insulated
stainless steel plate exchanger, complete with antifreeze heater
and water flow differential pressure switch.
Air side heat exchanger: finned coil exchanger with copper
pipes and aluminium fins.
Fan: electric axial fans with external rotor, equipped with
internal thermal protection, protection grilles and proportional
electronic device for continuous fan rotation speed regulation.
Control: microprocessor electronic control, iDRHOSS
compatible, with Adaptive Function logic.
Structure: in galvanised and painted sheet steel, complete
with condensation drain pan.
Models
TXAEY: standard EXPSYSTEMS unit.
Factory fitted accessories
• PUMP (for main circuit only) with single or double pump,
including an automatic pump in standby, complete with
expansion tank, air bleed valves, safety valve and water side
pressure gauge. The pumps are available in the low or high
pressure versions.
• TANK&PUMP (for main circuit only) with water buffer tank and
single or double pump, including an automatic pump in
standby, complete with expansion tank, air bleed valve, safety
valve and water pressure gauge. The pumps are available in
the low or high pressure versions.
• Refrigerant circuit high and low pressure gauges.
• Protection coil grilles.
• Antifreeze electric heater for buffer tank and pumps.
• Digital input for double set-point
• 4-20 mA analogue input for shifting set-point.
Accessories supplied loose
• Protection coil grilles
• Antivibration rubber mountings.
• Remote keyboard with display.
• Clock card
• Serial interfaces for connection to BMS (proprietary protocol,
Modbus RTU, LonWorks).
• Serial converters (RS485/RS232, RS485/USB) in the case
of centralised unit management.
• Serial interface (CAN-bus - Controller Area Network) for the
iDRHOSS system.
• GSM 900/1800 modem kit for remote unit management.
• Rhoss supervision system for unit monitoring and remote
management.
P. 67
Microsystem
42,6÷61,9 kW
47,8÷67,9 kW
245
250
260
265
❶ Nominal cooling capacity
(AUTOMATIC 1)
kW
42,6
50,6
58,2
61,9
❹ Recovery heating capacity
(AUTOMATIC 2)
kW
54,4
65,0
71,8
81,1
➋ Nominal heating capacity
(SELECT 1-2 AUTOMATIC 3)
kW
47,8
55,8
62,2
67,9
❶ Absorbed power (*)
(AUTOMATIC 1)
kW
16,8
18,5
21,6
24,0
❹ Absorbed power (*)
(AUTOMATIC 2)
kW
13,6
15,5
17,1
19,0
➋ Absorbed power (*)
(SELECT 1-2 AUTOMATIC 3)
kW
16,6
18,6
20,5
23,3
6,94
7,30
7,32
7,48
56
56
57
57
TXAEY MODEL
❹ C.O.P.
(AUTOMATIC 2)
❸ Sound pressure level
dB(A)
Scroll/step compressor
No.
2/1
2/1
2/1
2/1
Circuits
No.
1
1
1
1
Main supply
V-ph-Hz
400-3+N-50
400-3+N-50
400-3+N-50
400-3+N-50
245
250
260
265
2.260
2.260
2.260
2.260
DIMENSIONS AND WEIGHTS
L - Width
mm
H - Height
mm
1.570
1.570
1.570
1.570
P - Depth
mm
1.000
1.000
1.000
1.000
Weight TXAEY
kg
735
775
795
825
In the following conditions:
❶ Air: 35°C - Water: 7/12°C
❷ Air: 7°C D.B. - 6°C W.B. - Water 40/45°C
❸ At 5 m from the unit in free field (Q = 2).
❹ Evaporator water: 7/12°C. Recovery outlet water 45°C - Nominal flow.
H
L
P
WATER CHILLERS - HEAT PUMPS
(*) Unit without pump
TXAE 475÷4315
Q-Pack EXP Range
EXPSYSTEMS - Polyvalent ecological aircooled system with axial fans.
Range with hermetic Scroll compressors and
R407C refrigerant gas.
Construction features
Compressor: hermetic, rotary Scroll compressor, complete
with thermal protection and crankcase heater.
Main and secondary heat exchangers: crossed-flow
stainless steel plate exchangers, complete with closed cell
polyurethane foam rubber insulation and water flow differential
pressure switch.
Air side heat exchanger: finned coil exchanger with copper
pipes and aluminium fins.
Fan: electric axial fans with external rotor, equipped with
internal thermal protection, protection grilles and proportional
electronic device for continuous fan rotation speed regulation.
Control: electronic microprocessor control prepared for
connection with the main BMS on the market (MODBUS RTU,
LON).
Structure: in galvanised and painted sheet steel with
polyester powder coating, complete with soundproofed
compressor compartment.
The unit is also complete with:
• Unit with compressor and fan thermal overload switches.
Versions
• B - Standard version complete with soundproofed
compartment (TXAEB).
• I - Silenced version complete with soundproofed
compressor compartment, lower fan speed and larger coil
surface (TXAES).
Models
TXAEB: standard EXPSYSTEMS unit.
TXAES: silenced EXPSYSTEMS unit.
Factory fitted accessories
• PUMP (for main circuit only) with single or double pump,
including an automatic pump in standby, complete with
expansion tank, safety valve and water side pressure gauge.
The pumps are available in the low or high pressure versions.
• TANK&PUMP (for main circuit only) with built-in buffer tank
from 420 to 1,100 litres and single or double pump, complete
with expansion tank, air bleed valves, safety valve and water
pressure gauge.
• Power factor correction capacitors (cosφ > 0,91).
• Refrigerant circuit high and low pressure gauges.
• Unit with copper/copper, copper/tin-plated copper or
copper/pre-painted aluminium coils.
• Main and secondary heat exchanger antifreeze heater, buffer
tank and pumps if present.
• Metal filters or coil protection grilles.
• Serial interface for connection with external BMS.
Accessories supplied loose
• Antivibration rubber mountings.
• Spring antivibration mountings (mod. 4200-4315).
• Remote keyboard with display.
• Clock card
P. 69
475
495
4150
4200
4255
4315
❶ Nominal cooling capacity
(AUTOMATIC 1)
kW
71,6
103,3
149,4
198,0
240,0
307,1
❹ Recovery heating capacity
(AUTOMATIC 2)
kW
91,7
132,7
198,8
260,4
320,4
409,3
➋ Nominal heating capacity
(SELECT 1-2 AUTOMATIC 3)
kW
80,1
113,0
167,9
224,0
276,5
357,3
❶ Absorbed power
(AUTOMATIC 1)
kW
26,6
36,9
58,3
75,9
94,0
122,7
❹ Absorbed power
(AUTOMATIC 2)
kW
24,5
35,3
55,9
73,3
89,6
121,2
➋ Absorbed power
(SELECT 1-2 AUTOMATIC 3)
kW
28,4
39,2
59,8
81,5
97,8
126,7
6,48
6,52
6,11
6,10
6,15
5,75
60
60
63
64
64
69
475
495
4150
4200
4255
4315
TXAEB MODEL
❹ C.O.P.
(AUTOMATIC 2)
❸ Sound pressure level
dB(A)
TXAES MODEL
❶ Nominal cooling capacity
(AUTOMATIC 1)
kW
70,4
101,8
146,9
195,0
229,5
298,1
❹ Recovery heating capacity
(AUTOMATIC 2)
kW
91,7
132,7
198,8
260,4
320,4
409,3
➋ Nominal heating capacity
(SELECT 1-2 AUTOMATIC 3)
kW
75,5
106,6
158,6
211,3
261,2
333,8
❶ Absorbed power
(AUTOMATIC 1)
kW
25,7
36,2
57,1
76,0
96,8
120,7
❹ Absorbed power
(AUTOMATIC 2)
kW
24,5
35,3
55,9
73,3
89,6
121,2
➋ Absorbed power
(SELECT 1-2 AUTOMATIC 3)
kW
26,9
37,7
57,5
79,9
95,8
121,3
❸ Sound pressure level
dB(A)
56
56
58
60
60
64
TXAEB-TXAES MODEL
475
495
4150
4200
4255
4315
Scroll/step compressor
No.
4/2
4/2
4/2
4/2
4/2
4/2
Circuits
No.
2
2
2
2
2
2
Main supply
V-ph-Hz
400-3+N-50
400-3+N-50
400-3+N-50
400-3+N-50
400-3+N-50
400-3+N-50
DIMENSIONS AND WEIGHTS
475
495
4150
4200
4255
4315
mm
3.353
3.353
3.797
4.902
4.902
4.902
H - Height
mm
2.049
2.049
2.049
2.049
2.049
2.100
P - Depth
mm
2.062
2.062
2.062
2.062
2.062
2.062
➎ Weight TXAEB-TXAES
kg
1.802
1.896
2.276
3.030
3.190
3.280
L - Width
In the following conditions:
❶ Air: 35°C - Water: 7/12°C
❷ Air: 7°C D.B. - 6°C W.B. - Water 40/45°C
❸ At 5 m from the unit, coil side, in free field (Q = 2).
❹ Evaporator water: 7/12°C. Recovery outlet water 45°C - Nominal flow.
➎ Weight of fully accessorised unit when empty.
H
L
P
WATER CHILLERS - HEAT PUMPS
Macrosystem
70,4÷307,1 kW
75,5÷357,3 kW
TXHEY 105÷112
Comby-Flow EXP Range
Fan coil systems
Radiant Systems
Geothermal applications
EXPSYSTEMS - Polyvalent ecological watercooled system.
Range with hermetic Scroll compressors and
R410A refrigerant gas.
Construction features
Compressor: hermetic, rotary Scroll compressor, complete
with thermal protection.
Primary side heat exchanger (user), secondary side
exchanger (recovery) and disposal unit: adequately
insulated stainless steel plates, complete with antifreeze
electric heater and water flow differential pressure switch.
Control: microprocessor electronic control, iDRHOSS
compatible, with Adaptive Function logic.
Condensation control: pressure switch valve and bypass
solenoid valve.
Structure: in galvanised and painted sheet steel with polyester
powder coating, complete with soundproofed compressor
compartment.
Models
TXHEY: standard EXPSYSTEMS unit.
PUMP unit
Primary side (user): pumping group complete with circulation
pump, membrane expansion tank, safety valve, water drain
valve, manual air bleed valve, pressure gauge.
Well/tower side (disposal unit): drain valve and bleed valve.
Internal cock for primary side (use) system supply from external
network (disposal unit side: well or tower).
Secondary side (recovery): pumping group complete with
circulation pump, membrane expansion tank, safety valve, water
drain valve, manual air bleed valve, pressure gauge.
Factory fitted accessories
• Digital input for double set-point
• 4-20 mA analogue input for shifting set-point.
Accessories supplied loose
• Water buffer tank
• Buffer tank connection pipes
• Water filter
• Antivibration rubber mountings.
• Antifreeze electric heater on the buffer tank.
• Remote keyboard with display.
• Clock card
• Serial interfaces for connection to BMS (proprietary protocol,
Modbus RTU, LonWorks).
• Serial converters (RS485/RS232, RS485/USB) in the case
of centralised unit management.
• Serial interface (CAN-bus - Controller Area Network) for the
iDRHOSS system.
• GSM 900/1800 modem kit for remote unit management.
• Rhoss supervision system for unit monitoring and remote
management.
P. 71
Microsystem
5,4÷12 kW
6,5÷14,5 kW
TXHEY P MODEL
105
107
109
112
❶ Nominal cooling capacity
(AUTOMATIC 1)
kW
5,4
6,8
9,3
12,0
➋ Recovery heating capacity
(AUTOMATIC 2)
kW
6,7
8,7
11,3
14,5
❸ Nominal heating capacity
(SELECT 1-2 AUTOMATIC 3)
kW
6,5
8,2
10,8
13,9
❶ Total absorbed power (*)
(AUTOMATIC 1)
kW
1,56
2,12
2,74
3,60
➋ Total absorbed power (*)
(AUTOMATIC 2)
kW
2,00
2,83
3,57
4,41
❸ Total absorbed power (*)
(SELECT 1-2 AUTOMATIC 3)
kW
2,04
2,88
3,54
4,38
5,80
5,22
5,42
5,67
49,1
51,1
51,3
53,1
1
➋ C.O.P.
(AUTOMATIC 2)
❹ Sound pressure level
dB(A)
Scroll/step compressor
No.
1
1
1
Circuits
No.
1
1
1
1
Water buffer tank content KA
l
20
20
30
30
❶ Nominal available head pressure at main exchanger
kPa
47,0
54,7
82,2
78,2
➋ Nominal available head pressure at secondary recovery exchanger
kPa
32,4
42,4
72,1
66,7
Main supply
V-ph-Hz
230-1-50
230-1-50
400-3+N-50
230-1-50
400-3+N-50
230-1-50
400-3+N-50
In the following conditions:
❶ Condenser water: 30/35°C - Chilled water: 7/12°C.
❷ Chilled water: 7/12°C - Condenser inlet water: 40/45°C
❸ Evaporator water: 10°C - Water flow rate as in summer operation.
- Hot water 40/45°C
❹ At 1 m from the unit in free field (Q = 2).
KA = Water buffer tank
KTC = Connection pipes
DIMENSIONS AND WEIGHTS
105
107
109
112
L - Width
mm
585
585
660
660
H - Height TXHEY P
mm
535
535
535
535
H - Height TXHEY P & KA
mm
855
855
855
855
P - Depth
mm
520
520
560
560
Weight TXHEY
kg
112
118
122
130
Weight KA
kg
38
38
43
43
H
H
KA
L
P
L
C
KT
P
WATER CHILLERS - HEAT PUMPS
(*) Unit without pump
MCAE-MHAE 105÷127
Air-cooled condensing units and reversible
condensing units, with axial fans.
Range with hermetic compressors and R407C
refrigerant gas.
Construction features
Compressor: hermetic rotary blade compressor complete
with thermal protection (mod. 105÷106); hermetic Scroll
compressor, complete with thermal protection (mod.
108÷127).
Air side heat exchanger: featuring finned coil with copper
pipes and aluminium fins, complete with protection grille.
Fan: electric axial fan with external rotor, equipped with internal
thermal protection and complete with protection grille.
Control: microprocessor electronic control.
Structure: galvanised and painted sheet steel with epoxy
finish, complete with rubber antivibration mountings and cataphoresis-treated sheet steel base (mod. 105÷110), in
peraluman with galvanised sheet steel base and soundproofed
compressor compartment (mod. 115÷127).
Models
MCAE: unit designed for cooling only.
MHAE: heat pump unit.
Accessories supplied loose
• Wall-support shelves (mod.105÷110).
• Connection cover (mod. 105÷110).
• Low pressure switch (mod. 105-106).
• Rubber antivibration mountings (mod. 115÷127)
• –10°C condensation control.
• RS 485 serial interface (mod.115÷127).
• RS 232 hardware key (mod. 115÷127).
P. 73
Microsystem
5,1÷26,3 kW
6÷29,9 kW
105
106
108
❶ Nominal cooling capacity
kW
5,1
6,3
7,6
8,5
❶ Absorbed power
kW
1,87
2,45
3,00
3,40
105
106
108
110
6,0
7,2
9,0
10,4
MHAE MODEL
110
➋ Nominal heating capacity
kW
❶ Nominal cooling capacity
kW
5,1
6,3
7,6
8,5
➋ Absorbed power
kW
1,75
2,10
2,81
3,20
105
106
108
110
54
53
55
54
230-1-50
230-1-50
400-3+N-50
400-3+N-50
MCAE-MHAE MODEL
❸ Sound pressure level
Main supply
dB(A)
V-ph-Hz
230-1-50
105
106
108
110
mm
790
790
830
830
H - Height
mm
600
600
900
900
P - Depth
mm
300
300
300
300
Weight MCAE
kg
59
65
84
85
Weight MHAE
kg
60
66
88
90
DIMENSIONS AND WEIGHTS
L - Width
115
118
122
127
❶ Nominal cooling capacity
kW
14,7
17,6
21,8
26,3
❶ Absorbed power
kW
4,91
5,65
7,41
8,92
115
118
122
127
15,8
19,9
24,5
29,9
MCAE MODEL
MHAE MODEL
➋ Nominal heating capacity
kW
❶ Nominal cooling capacity
kW
14,7
17,6
21,8
26,3
➋ Absorbed power
kW
5,12
5,63
7,23
8,40
115
118
122
127
49
50
51
52
400-3+N-50
400-3+N-50
400-3+N-50
400-3+N-50
MCAE-MHAE MODEL
❸ Sound pressure level
dB(A)
Main supply
V-ph-Hz
115
118
122
127
mm
1.326
1.326
1.716
1.716
H - Height
mm
1.230
1.230
1.230
1.230
P - Depth
mm
527
527
615
615
Weight MCAE
kg
180
200
260
290
Weight MHAE
kg
200
210
280
300
DIMENSIONS AND WEIGHTS
L - Width
In the following conditions:
❶ Air: 35°C - Suctioned saturated gas: 7°C
❷ Air: 6°C W.B. - Condensazione: 45°C (mod. 105÷110); 50°C (mod. 115÷127)
❸ At 5 m from the unit in free field (Q = 2)
H
H
L
L
P
P
WATER CHILLERS - HEAT PUMPS
MCAE MODEL
CCAM 105÷2130
Remote condensers
Remote air condensers with axial fans for
direct expansion units operating with R407C
refrigerant gas.
Construction features
Heat exchanger: featuring high efficiency finned coil with
copper pipes joined to aluminium fins by mechanical expansion.
The unit undergoes pressure and seal tests, guaranteeing a
maximum working pressure of 29 bar.
The refrigerant circuit connections need brazing.
The units are supplied pressurised with nitrogen.
Fans: axial fans with external rotor; rotating body of motor and
fan blades with aerodynamic configuration that guarantees
quiet operation and high performance.
The electric fans are also speed-adjustable (by means of the
TCEE 105÷2130 evaporator unit PSC accessory) and are
protected against overloads by thermal overload switch
breakers.
Structure: in galvanised and painted sheet steel with epoxy
powder coating.
• The remote condensers come equipped with a support
bracket kit for vertical/horizontal air flow. The support brackets
are made from AISI 304 stainless steel for the condensers
with fans measuring from 400-500 mm, and in galvanised
steel for the condensers with fans measuring from 630-910
mm.
• The brackets are of an optimum length for uniform air suction
into the coil.
• The motors are wired in compliance with VDE 0530/12.84.
• IP54 protection, in compliance with DIN 40050.
• Electrical panel compliant with IEC standards. Sealed box
with IP55 protection, complete with:
- Main switch with door interlock;.
- Power contactors.
- Thermal overload switch;
- Indicator lights and remote-controlled alarms.
- The electric panel for condensers with fans measuring from
400 to 500 mm is not installed upon delivery. The client is
responsible for its installation.
Versions
The CCAM 105÷2130 range remote condensers are available
in 3 construction options that meet the different system requirements concerning ambient noise emission:
• Versione “N” Normal (mod. 105-115 excluded);
• Version "S" Silenced;
• Version “Q” Supersilenced.
P. 75
CCAM MODEL
120N
125N
135N
140N
155N
165N
280N
2110N
2130N
23,7
35,0
42,7
51,8
63,9
77,6
97,1
130
161,4
51
48
48
54
50
56
62
64
59
1
VERSION N “Normal”
❶ Nominal heating capacity
kW
➋ Sound pressure level
dB(A)
Refrigerant circuits
No.
1
1
1
1
1
1
1
1
Fans
No.
1
2
2
2
3
3
2
3
4
Fan nominal air flow
m3/h
6.891
11.840
10.322
13.035
15.482
19.553
29.278
45.998
46.879
Rotation speed
rpm
1.326
1.059
1.059
1.326
1.059
1.326
1.340
1.340
1.070
❶ Absorbed power
kW
0,78
1,10
1,10
1,56
1,65
2,34
3,80
5,70
5,40
Main supply
V-ph-Hz 400/3+N/50 400/3+N/50
CCAM MODEL
400/3+N/50 400/3+N/50 400/3+N/50 400/3+N/50 400/3+N/50 400/3+N/50 400/3+N/50
105S
115S
120S
125S
135S
140S
155S
165S
280S
2110S
2130S
VERSION S "Silenced"
❶ Nominal heating capacity
kW
8,9
14,9
21,3
33,1
43,2
52,6
64,8
79,0
95,1
127,7
159,8
➋ Sound pressure level
dB(A)
45
42
45
45
42
49
44
51
51
52
52
Refrigerant circuits
No.
1
1
1
1
1
1
1
1
1
1
1
Fans
No.
1
1
1
2
2
2
3
3
3
4
3
Fan nominal air flow
m3/h
3.241
4.700
5.161
8.696
14.342
19.747
21.534
29.647
28.532
38.067
47.411
Rotation speed
rpm
1430
842
1.059
842
650
900
650
900
900
900
640
❶ Absorbed power
kW
0,18
0,32
0,55
0,64
0,66
1,38
0,99
2,07
2,07
2,76
2,70
Main supply
V-ph-Hz
CCAM MODEL
230/1/50 400/3+N/50 400/3+N/50 400/3+N/50 400/3+N/50 400/3+N/50 400/3+N/50 400/3+N/50 400/3+N/50 400/3+N/50400/3+N/50
105Q
115Q
120Q
125Q
135Q
140Q
155Q
165Q
280Q
2110Q
2130Q
10,3
15,8
23,4
31,4
41,7
52,6
67,8
79,5
98,3
133,2
161,9
33
32
35
35
34
38
40
40
45
43
45
1
VERSION Q “Supersilenced”
❶ Nominal heating capacity
kW
➋ Sound pressure level
dB(A)
Refrigerant circuits
No.
1
1
1
1
1
1
1
1
1
1
Fans
No.
1
2
2
4
2
4
2
2
4
4
4
Fan nominal air flow
m3/h
3.665
3.658
6.789
7.316
10.828
13.089
21.630
19.331
27.493
43.328
43.888
Rotation speed
rpm
632
455
614
455
480
624
440
440
650
440
440
❶ Absorbed power
kW
0,15
0,18
0,24
0,36
0,38
0,8
0,66
0,66
1,32
1,32
1,88
Main supply
V-ph-Hz
Subcooling 3°K - Superheating 25°K.
Maximum speed
➋ At 10 m from the unit in free field (Q = 2)
In the following conditions:
❶ External temperature: 35°C D.B., 24°C W.B.
Dew point: 50°C.
Sound pressure level correction for distances other than 10 m
Distance
(m)
Correction
dB(A)
2
3
4
5
7
10
15
20
30
40
50
60
80
11
8.5
7
5
2.5
0
–3
–5.5
–9
–11
–12
–14
–16
SYSTEM ACCESSORIES
230/1/50 400/3+N/50 400/3+N/50 400/3+N/50 400/3+N/50 400/3+N/50 400/3+N/50 400/3+N/50 400/3+N/50 400/3+N/50 400/3+N/50
CEHV CEHP 46÷2791
Cooling towers
Cooling towers for water-cooled chillers.
Axial fans.
Construction features
Distribution system: polyvinyl chloride pipes and plastic
spray nozzles.
Heat exchange package: panel exchanger with plastic
cellular structure with large slots.
Drop separator: plastic.
Fan: axial fan directly coupled with protection grille.
Condensation drain pan: in polyester resin strengthened
with fibreglass complete with spray protection fins, drain
connections, float re-integration and overflow.
Structure: in polyester resin strengthened with fibreglass and
load-bearing for models of the CEHV range; with hotgalvanised steel sections and with lateral damping using 22
mm sandwich panels in polyester resin strengthened with
fibreglass for models of the CEHP-CEHPS range.
Models
CEHV 46÷639 Cooling towers with load-bearing polyester
resin structure strengthened with fibreglass.
CEHP 744÷2791 Cooling towers with hot- galvanised steel
sections and with lateral damping using 22 mm sandwich
panels in polyester resin strengthened with fibreglass.
CEHPS 744÷2791 Silenced cooling towers with hotgalvanised steel sections and with lateral damping using 22
mm sandwich panels in polyester resin strengthened with
fibreglass.
Factory fitted accessories
CEHV Range
• Inspection pothole.
• Electrical anti-freeze heater on condensation drain pan
complete with minimum level switch.
CEHP – CEHPS range
• Manhole.
• Dismantable side wall.
• Electrical anti-freeze heater on condensation drain pan
complete with minimum level switch.
P. 77
46
87
105
139
169
203
238
337
395
477
506
599
639
kW
46,5
87,2
104,7
139,5
168,6
203,5
238,4
337,2
395,3
476,7
505,8
598,8
639,5
CEHV MODEL
Installed fan electrical power
Sound power level
➋ Sound pressure level
Main supply
kW)
0,55
0,75
0,75
1,1
1,1
1,1
1,1
2,2
2,2
4
4
4
4
dB(A)
74
75
75
75
75
77
77
80
80
83
83
85
85
dB(A)
46
47
47
47
47
49
49
52
52
55
55
57
57
220/380-3-50
V-ph-Hz
DIMENSIONS AND WEIGHTS
46
87
105
139
169
203
238
337
395
477
506
599
639
mm
800
1000
1000
1200
1200
1400
1400
1740
1740
2100
2100
2300
2300
H - Height
mm
2110
2595
2595
2800
2800
2860
2860
3140
3140
3380
3380
3450
3450
P - Depth
mm
800
1000
1000
1200
1200
1400
1400
1740
1740
1900
1900
2100
2100
Empty weight
kg
75
85
95
155
170
195
210
380
410
500
525
555
580
Operating weight
kg
180
215
285
470
485
755
780
1380
1410
1800
1825
1955
1980
1488
1651
L - Width
CEHP MODEL
❶ Nominal heating capacity consumption
Installed fan electrical power
Sound power level
➋ Sound pressure level
Main supply
744
826
878
744,2
825,6
877,9
kW
4
5,5
5,5
7,5
7,5
11
11
11
2X4
2X5,5
2X5,5
2X7,5
2X7,5
2X11
2X11
2X11
dB(A)
dB(A)
90
90
92
92
94
94
95
95
93
93
95
95
97
97
98
98
62
62
64
64
66
66
67
67
65
65
67
67
69
69
70
70
2791
kW
971
1070
970,9 1069,8
1186
1256
1756
1948
2139
2366
2512
2791
380/660-3-50
V-ph-Hz
DIMENSIONS AND WEIGHTS
1395
1186 1255,8 1395,3 1488,4 1651,2 1755,8 1947,7 2139,5 2366,3 2511,6 2790,7
744
826
878
971
1070
1186
1256
1395
1488
1651
1756
1948
2139
2366
2512
L - Width
mm
2025
2025
2365
2365
2875
2875
3370
3370
4080
4080
4750
4750
5770
5770
6770
6770
H - Height
mm
3650
3650
3650
3650
3650
3650
3650
3650
3650
3650
3650
3650
3950
3950
3950
3950
P - Depth
2365
mm
2365
2365
2365
2365
2365
2365
2365
2365
2365
2365
2365
2365
2365
2365
2365
Empty weight
kg
885
920
965
1000
1115
1165
1220
1270
1630
1700
1790
1860
2125
2225
2375
2475
Operating weight
kg
2485
2520
2865
2900
3815
3865
4320
4370
4680
4750
5430
5500
7325
7425
8375
8475
744
826
878
971
1070
1186
1256
1395
1488
1651
1756
1948
2139
2366
2512
2791
kW
744,2
825,6
877,9
CEHPS MODEL
❶ Nominal heating capacity consumption
Installed fan electrical power
970,9 1069,8
1186 1255,8 1395,3 1488,4 1651,2 1755,8 1947,7 2139,5 2366,3 2511,6 2790,7
kW
5,5
5,5
7,5
7,5
11
11
11
11
2X5,5
2X5,5
2X7,5
2X7,5
2X11
2X11
2X11
Sound power level
dB(A)
79
79
80
80
82
82
83
83
82
82
83
83
85
85
86
86
➋ Sound pressure level
dB(A)
51
51
52
52
54
54
55
55
54
54
55
55
57
57
58
58
744
826
878
971
1070
1186
1256
2791
Main supply
V-ph-Hz
DIMENSIONS AND WEIGHTS
2X11
380/660-3-50
1395
1488
1651
1756
1948
2139
2366
2512
L - Width
mm
2025
2025
2365
2365
2875
2875
3370
3370
4080
4080
4750
4750
5770
5770
6770
6770
H - Height
mm
3905
3905
3905
3905
3905
3905
3905
3905
3905
3905
3905
3905
4205
4205
4205
4205
P - Depth
mm
2365
2365
2365
2365
2365
2365
2365
2365
2365
2365
2365
2365
2365
2365
2365
2365
Empty weight
kg
885
920
965
1000
1115
1165
1220
1270
1630
1700
1790
1860
2125
2225
2375
2475
Operating weight
kg
2485
2520
2865
2900
3815
3865
4320
4370
4680
4750
5430
5500
7325
7425
8375
8475
In the following conditions:
❶ Air: 24°C W.B. - Water 35/30°C
➋ At 10 m from the unit in free field (Q = 2).
SYSTEM ACCESSORIES
❶ Nominal heating capacity consumption
AS 0300÷2500
Pumping groups
Pumping groups with buffer tank
Versions
AS - Standard version with two connections.
Construction features
Buffer tank: in carbon steel with a capacity of 300, 500, 750,
1000, 1500, or 2500 litres.
Water circuit components: single or double centrifugal
pump, inlet and outlet shut-off ball valve of each pump,
automatic re-integration tap, manual re-integration tap, safety
valve, automatic air bleed valve, tank water drain tap, expansion
tank with membrane, no-return valve (with double pump only),
pressure gauge.
The water circuit is insulated with closed cell expanded
polyurethane of adequate thickness.
Structure: Load-bearing structure made of aluminium sheet
metal panelling and base in galvanised and painted steel.
Control: electromechanical.
Models
AS 0300 PU or DPU 1÷5: pumping group equipped with
pump on user side (PU) or double pump on user side (DPU).
AS 0500 PU or DPU 1÷5: pumping group equipped with
pump on user side (PU) or double pump on user side (DPU).
AS 0750 PU or DPU 6÷10: pumping group equipped with
pump on user side (PU) or double pump on user side (DPU).
AS 1000 PU or DPU 6÷10: pumping group equipped with
pump on user side (PU) or double pump on user side (DPU).
AS 1500 PU or DPU 6÷14: pumping group equipped with
pump on user side (PU) or double pump on user side (DPU).
AS 2500 PU or DPU 6÷14: pumping group equipped with
pump on user side (PU) or double pump on user side (DPU).
Accessories supplied loose
• Victaulic connections.
• Tank antifreeze electric heater with activator.
single
single
single
single
single
single
P. 79
MODEL
Tank capacity
l
AS 0300
AS 0500
AS 0750
AS 1000
AS 1500
AS 2500
300
500
750
1000
1500
2500
1-2-3-4-5
Pump model
6-7-8-9-10
6-7-8-9-10-11-12-13-14
l
25
25
25
25
2X25
X25
Expansion tank calibration
bar
1,5
1,5
1,5
1,5
1,5
1,5
Safety valve calibration
bar
Maximum working pressure
bar
Expansion tank capacity
3,0
3,0
W
1300
1300
1300
1300
1300X2
Water connections (female)
Ø (Gas)
21/2”
21/2”
3”
3”
4”
Main supply
V-pH-Hz
AS 1000
AS 1500
Electric heater (optional)
DIMENSIONS AND WEIGHTS
1300X2
4”
400-3-50
AS 0300
AS 0500
AS 0750
AS 2500
mm
1504
2044
H - Height
mm
1265
1510
1782
P - Depth
mm
1120
1200
1900
Weight (*)
kg
L - Width
231
253
2260
501
528
878
930
PUMP
TANK
Flow
Available head pressure(*)
Flow
Available head pressure (*)
Model
litres
mc/h
Available head pressure (*) Flow
m.c.a.
mc/h
m.c.a.
mc/h
m.c.a.
1
300 or 500
12
15.5
15
13.5
18
11.1
2
300 or 500
12
19.0
15
17.0
18
14.7
3
300 or 500
21
12.4
24
10.8
30
7.5
4
300 or 500
21
18.2
24
16.6
30
13.3
15.6
5
300 or 500
21
20.4
24
18.8
30
6
750 or 1000
36
17.0
42
16.0
48
14.1
7
750 or 1000
42
27.4
48
25.2
60
20.5
8
750 or 1000
60
17.9
72
15.0
84
12.0
9
750 or 1000
72
20.5
84
17.5
96
15.0
10
750 or 1000
72
29.0
84
26.0
96
23.0
11
1500 or 2500
72
36.0
84
33.0
96
30.0
12
1500 or 2500
108
29.0
120
27.0
138
24.0
13
1500 or 2500
108
34.0
120
32.5
138
30.0
14
1500 or 2500
108
43.1
120
41.0
138
37.0
(*) available head pressure of the pumping group only
Diagram with AS pumping group on the outlet
Diagram with AS pumping group on return
SYSTEM ACCESSORIES
(*) Weight of fully accessorised unit when empty.
PBHI 0200-0400
Pumping groups with buffer tank for
combination with TCHE - THHE - TCEE units
with hermetic Scroll compressors (models
155 ÷ 4260).
Construction features
Buffer tank: in carbon-plated and pre-painted steel sheet, with
a 200 or 425 litre capacity.
Water circuit components: primary circuit complete with
single pump, secondary circuit complete with single standard
head pressure pump, buffer tank, expansion tank, safety valve,
shut-off valves, tank water charge/drain taps and automatic and
manual air bleed valves.
Heat exchanger: brazed plate exchanger complete with
adjustable flow switch (freecooling version only).
Control: electromechanical.
Structure: load-bearing structure in galvanised and painted
sheet steel with polyester powder coating. The panels are
removable in order to allow for easy access to the internal
components.
Versions
• B - Standard version: with single primary and secondary
circuit pump (standard head pressure).
• F - Freecooling version: fitted with indirect freecooling heat
exchanger.
Models
PBHI 0200 B: standard pumping group for combination with
units TCHE-THHE-TCEE - 155-165
PBHI 0400 B: standard pumping group for combination with
units TCHE-THHE-TCEE - 280-4260
PBHI 0200 B: freecooling version pumping group for
combination with units TCHE-THHE-TCEE - 155-165
PBHI 0400 B: freecooling version pumping group for
combination with units TCHE-THHE-TCEE - 280-4260
Factory fitted accessories
• single secondary circuit pump with high pressure.
• double secondary circuit pump with standard or increased
head pressure, including one in standby with automatic
activation.
• single centrifugal pump with built-in inverter, able to maintain
a constant pressure despite variations in system demands.
• antifreeze heater 300 W (230V) with activator.
Accessories supplied loose
• Antivibration rubber mountings.
• Flexible tubes for connection to the water chiller/heat pump.
P. 81
Macrosystem
50,2÷249 kW
PBHI MODEL
0200
0400
Tank capacity
l
200
425
Expansion tank capacity
l
8
12
Expansion tank calibration
kPa
150
150
Safety valve calibration
kPa
600
600
Maximum working pressure
kPa
600
600
Electric heater (optional)
W
300
300
Water connection (female)
∅ (Gas)
2ll F
21/2ll F
Sound power level
dB(A)
71
74
Main supply
V-ph-Hz
400-3+N-50
400-3+N-50
DIMENSIONS AND WEIGHTS
L - Width
mm
1.340
1.919
H - Height
mm
1.206
1.706
P - Depth
mm
861
863
PBHI water circuit with single pump on user side
FREECOOLING ONLY
FREECOOLING
VSA
VSM
PZ
R
R1
P
R
FL
PZ
PHF
PZ
PZ
RA
USER
UTENZA
VE
SECONDARY
CIRCUIT
CIRCUITO
SECONDARIO
PRIMARY
CIRCUIT
CIRCUITO
PRIMARIO
M
R
R
VS
SA
MAC
R1
P
PU
DPU
PUI
FL
M
PZ
PHF
RA
R
R1
S
SA
VE
=
=
=
=
=
=
=
=
=
=
=
=
=
=
VR
VS
VSA
VSM
=
=
=
=
=
S
PU
SECONDARY CIRCUIT PUMP ACCESSORIES:
PBHI water circuit with double pump on user side
Primary circuit circulation pump
Secondary circuit circulation pump
Double secondary circuit circulation pump (factory fitted accessory)
Secondary circuit circulation inverter pump (factory fitted accessory)
Flow switch
Pressure gauge
Sockets with internal diameter 6.2 mm
Plate heat exchanger for freecooling
Buffer tank antifreeze heater (factory fitted accessory)
Tap
Tap to be fitted by the installer (provided)
Water drain/charge tap (outside the buffer tank)
Buffer tank
Expansion tank calculated to contain the water from the buffer tank
only (–10°C ÷ +60°C)
Non-return valve
Safety valve
Automatic air bleed valve
Manual air bleed valve
Connections
FREECOOLING ONLY
FREECOOLING
VSA
PZ
R
R1
P
R
FL
PZ
PHF
PZ
PZ
RA
USER
VE
SECONDARY CIRCUIT
CIRCUITO SECONDARIO
UTENZA
VR
PRIMARY
CIRCUIT
CIRCUITO PRIMARIO
M
R
R
VS
SA
VR
MAC
PUMP WITH INVERTER
Regulation at constant pressure
R1
DPU
S
FREECOOLING ONLY
FREECOOLING
VSA
VSM
PZ
R
R1
P
R
FL
PZ
PZ
PHF
PZ
RA
USER
UTENZA
SECONDARY
CIRCUIT
CIRCUITO
SECONDARIO
R
R
PUI
VE
VS
SA
M
PRIMARY
CIRCUIT
CIRCUITO
PRIMARIO
50 Hz
H - Head pressure kPa
PBHI water circuit with single inverter pump on user
side
25 Hz
MA
R1
S
Q - Capacity m3/h
SYSTEM ACCESSORIES
VSM
Louver: motorized with double fin
Wall-mounted fan coil units.
Versions
Construction features
• MPCV - Heating and cooling unit complete with 3-way
ON/OFF solenoid valve.
• MPCB - Heating-only unit without 3-way valve.
Heat exchanger: with finned coil with rapid connections and
pipe outlets in several directions.
Fan: tangential 3-speed.
Louver: motorized with 5-position double fin.
Control: microprocessor electronic control.
Regulation functions: full auto, cool, dry, fan, autofan, heat.
Comfort functions: orienting, swing, timer, sleep, hot start,
memory.
Advanced functions: economy, lock function, on/off remote
control, summer/winter remote control, security control, probe
in/out, continuos ventilation, comfort control, occupancy, alarm.
Structure: in heat-resistant ABS polymer complete with
renewable polypropylene filter, direction-adjustable fins and
condensation drain pan with natural drainage.
ACCESSORIES
➔
Recessed box with rapid connections, ball valves and flexible
connection pipes.
ADVANCED CONTROLS
➔
➔
➔
➔
❖
❖
Remote control
Electronic control panel for wall mounting.
Wall-mounted electronic panel
Serial converters (RS485/RS232, RS485/USB) in the case
of centralised unit management.
Serial interfaces for connection to BMS (proprietary protocol,
Modbus RTU).
CAN-bus (Controller Area Network) serial interface for the
iDRHOSS system.
Key:
❖ Factory fitted
➔ Supplied loose
P. 83
Unit-System
1,3÷2,5 kW
3,2÷5,4 kW
Wall-mounted
electronic
panel
Remote
control with
bracket for wall
installation
IDROWALL MODEL
❶ Cooling capacity
(total heat)
Maximum absorbed power
kW
kW
kW
kW
kW
kW
kW
m3/h
m3/h
m3/h
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
W
Main supply
V-ph-Hz
DIMENSIONS AND WEIGHTS
L - Width
H - Height
P - Depth
Weight
mm
mm
mm
kg
❷ Heating capacity (70°C)
❸ Heating capacity (50°C)
Air flow
Sound power level
❹ Sound pressure level
MAX
MED
MIN
MAX
MED
MIN
MAX
MAX
MED
MIN
MAX
MED
MIN
MAX
MED
MIN
22
1,32
1,11
0,98
3,24
2,89
2,69
1,80
415
352
311
46
41
39
38
33
31
28
33
1,95
1,67
1,45
3,65
3,02
2,54
2,16
457
389
336
47
43
40
39
35
32
33
44
2,48
2,00
1,56
5,41
4,46
3,49
3,15
573
468
363
54
48
42
46
40
34
39
230-1-50
230-1-50
230-1-50
22
960
280
180
12
33
960
280
180
12
44
960
280
180
12
In the following conditions:
❶ Air: 27°C D.B.; 19°C W.B. - Water: 7/12°C.
❷ Air: 20°C - Water: 70/60°C.
❸ Air: 20°C - Water: 50°C, flow rate as in cooling.
❹ At 1 m from air outlet with directionality factor of 2.
P
L
H
FAN COIL UNITS
Electronic
control panel
for wall mounting
Particular speed selector
Floor and ceiling fan coil units
STANDARD CONTROLS
10, 13, 20, 23, 33 for 2-pipes-systems; 11, 21,31for 4-pipessystems
For wall installation
➔ Panel with speed and summer/winter switch.
➔ Panel with room thermostat and summer/winter switch.
➔ Panel with room thermostat, summer/winter switch, ON/OFF
valve signal.
➔ Minimum temperature thermostat (for installation on the
machine).
➔ Electronic panel with automatic summer/winter changeover
for 2-pipe-systems.
➔ Electronic panel with automatic summer/winter changeover
and automatic speed regulation for 2-pipe-systems or 4-pipesystems.
For installation on machine.
➔
❖ Speed switch
Versions
ADVANCED CONTROLS
• MVP - Vertical unit with cabinet equipped with lower air inlet
and upper outlet intended for wall installation, on ground with
feet, on floor with front air inlet plenum.
• MOP - Horizontal unit with cabinet equipped with rear air
inlet and front outlet intended for ceiling installation with or
without lower air inlet plenum and auxiliary condensation drain
pan.
Remote control
Electronic panel for wall or onboard mounting
➔ Wall-mounted electronic panel
For installation on machine.
➔
❖ Master electronic card with electronic control panel (only for
MVP version).
➔
❖ Master/slave electronic card.
➔
❖ Temperature probe for hot row.
➔
❖ ON/OFF valves management module.
➔ Serial interfaces for connection to BMS (proprietary protocol,
Modbus RTU).
➔ Serial converters (RS485/RS232, RS485/USB) in the case
of centralised unit management.
➔ Serial interface (CAN-bus - Controller Area Network) for the
iDRHOSS system.
Construction features
Heat exchanger: with finned coil with left-hand,
reversible connections.
Fan: tangential 3-speed.
Louver: manual with variable opening.
Structure: in heat-resistant ABS polymer complete
thermo-acoustic insulation, renewable polypropylene
direction-adjustable fins and condensation drain pan
natural drainage; cover panel in painted sheet metal.
non-
with
filter,
with
Models
ACCESSORIES
➔
❖
➔
❖
➔
➔
➔
➔
➔
➔
➔
❖
3-way ON/OFF solenoid valve for 2-pipe-systems.
3-way ON/OFF solenoid valves for 4-pipe-systems.
Air inlet grille.
Rear panel for installation with feet.
Rear panel for installation with grille.
Rear panel.
Support feet.
Micro-pump for condensation.
Auxiliary condensation drain pan.
➔
➔
Key:
❖ Factory fitted
➔ Supplied loose
P. 85
Unit-System
1÷2,9 kW
2,2÷5,7 kW
Wall-mounted
electronic
panel
Remote
control with
bracket for wall
installation
Electronic
panel for
wall mounting
FREND MODEL
❶ Cooling capacity
(total heat)
Maximum absorbed power
Main supply
V-ph-Hz 230-1-50
❸ Heating capacity (50°C)
❷ Heating capacity
hot row
Air flow
Sound power level
❹ Sound pressure level
DIMENSIONS AND WEIGHTS
L - Width
H - Height
H2 - Height of feet and grille
P - Depth
Weight
MOP
P
10
1,01
0,88
0,67
2,21
1,91
1,46
1,28
–
–
–
230
180
120
55
49
41
47
41
33
22
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
m3/h
m3/h
m3/h
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
W
❷ Heating capacity (70°C)
MAX
MED
MIN
MAX
MED
MIN
MAX
MAX
MED
MIN
MAX
MED
MIN
MAX
MED
MIN
MAX
MED
MIN
mm
mm
mm
mm
kg
10
765
450
100
175
12
11
1,01
0,88
0,67
–
–
–
–
1,46
1,26
0,97
13
1,29
1,12
0,87
2,63
2,25
1,73
1,54
–
–
–
230
180
120
55
49
41
47
41
33
22
230-1-50
11
20
1,71
1,37
1,06
3,60
2,89
2,24
2,12
–
–
–
370
260
180
56
50
43
48
42
35
33
21
1,71
1,37
1,06
–
–
–
–
2,39
1,91
1,48
230-1-50
13
230-1-50
20
990
450
100
175
14
765
450
100
175
13
23
2,15
1,65
1,37
4,31
3,44
2,67
2,55
–
–
–
370
260
180
56
49
40
48
41
32
33
21
23
990
450
100
175
15
MOP with
intake grille
L
H
In the following conditions:
❶ Air: 27°C D.B.; 19°C W.B. - Water: 7/12°C.
❷ Air: 20°C - Water: 70/60°C.
❸ Air: 20°C - Water: 50°C, flow rate as in cooling.
❹ At 1 m from air outlet with directionality factor of 2.
MVP with
intake grille
MVP
H
H2
L
P
31
2,35
2,00
1,41
–
–
–
–
3,21
2,72
1,93
33
2,90
2,47
1,73
5,72
4,85
3,42
3,40
–
–
–
490
380
230
55
50
40
47
42
32
36
230-1-50
31
33
1.215
450
100
175
18
FAN COIL UNITS
Frend in MVP version
with support feet
Floor and ceiling fan coil units
Construction features
Heat exchanger: with finned coil with left-hand connections
reversible to right.
Fan: centrifugal 3-speed.
Structure: cover panel in painted galvanized sheet metal
complete with renewable filter and condensation drain pan with
natural drainage; direction-adjustable grilles in heat-resistant
ABS polymer.
Versions
• MVP - Vertical unit with cabinet equipped with lower air inlet
and upper outlet for wall mounting or with feet on ground.
• MVT - Vertical unit with cabinet equipped with front air inlet
and upper outlet for floor installation.
• MOP - Horizontal unit with cabinet equipped with rear air inlet
and front outlet for ceiling installation.
• MOT - Horizontal unit with cabinet equipped with lower air
inlet and front outlet for ceiling installation.
ACCESSORIES
➔
❖
➔
❖
➔
❖
➔
➔
➔
➔
❖
➔
❖
➔
➔
➔
➔
Additional water heating coil.
Electric heater.
Auxiliary condensation drain pan.
Manual damper.
Motorized damper.
Valve and balancing valve.
3-way ON/OFF solenoid valves for 2-pipe-systems.
3-way ON/OFF solenoid valves for 4-pipe-systems.
Rear panel.
Rear closure panel.
Rear closure panel with grille and filter.
Support feet with pipe cover.
STANDARD CONTROLS
For wall installation
➔ Panel with speed and summer/winter switch.
➔ Panel with room thermostat and summer/winter switch.
➔ Panel with room thermostat, summer/winter switch, ON/OFF
valve signal and electric heater.
➔ Minimum temperature thermostat (for installation on the
machine).
➔ Electronic panel with automatic summer/winter changeover
for 2-pipe-systems.
➔ Electronic panel with automatic summer/winter changeover
and automatic speed regulation for 2-pipe-systems with
electric heater or 4-pipe-systems.
For installation on machine ( MVP and MVT versions)
➔
❖ Panel with speed switch.
➔
❖ Panel with room thermostat, summer/winter switch and
speed switch.
➔
❖ Minimum temperature thermostat.
➔
❖ Panel with room thermostat, summer/winter switch,
ON/OFF valve signal and electric heater.
➔
❖ Electronic panel with automatic summer/winter changeover
for 2-pipe systems.
➔
❖ Electronic panel with automatic summer/winter changeover
and automatic speed regulation for 2-pipe-systems with
electric heater or 4-pipe-systems.
Key:
❖ Factory fitted
➔ Supplied loose
P. 87
Unit-System
1÷6.9 kW
2.2÷16.5 kW
ADVANCED CONTROLS
➔
Remote control
➔ Electronic panel for wall or onboard mounting.
➔ Wall-mounted electronic panel
For installation on machine.
➔
❖ Master electronic card with electronic control panel ( only for
MVP - MVT versions).
➔
❖ Master/slave electronic card.
➔
❖ Temperature probe for hot row.
➔
❖
➔
➔
➔
Module for management of ON/OFF valves and electric heater.
Serial interfaces for connection to BMS (proprietary protocol,
Modbus RTU).
Serial converters (RS485/RS232, RS485/USB) in the case
of centralised unit management.
Serial interface (CAN-bus - Controller Area Network) for the
iDRHOSS system.
Key:
❖ Factory fitted
➔ Supplied loose
UNITS:
RANGE OF COLOURS:
Standard
RHOSS special colours (*)
PEARL WHITE
Bi-colour
METALLIC SILVER
GREY
METALLIC
NIGHT BLUE
FAN COIL UNITS
SATIN-FINISH
BRONZE
Mono-colour
GRAPHITE
BLACK
METALLIC
PURPLE
RAL colours (*)
Customised colour selection
It is possible to choose the desired colour
from the RAL range.
I.e.
RAL 2000
(*)The RHOSS special colours
and the RAL colours are available with BI-COLOUR and
MONO-COLOUR set-up
Wall-mounted
electronic
panel
Remote control
with bracket
for wall installation
Electronic
control panel
for wall mounting
BrioEV MODEL
❶ Cooling capacity
(total heat)
Maximum absorbed power
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
m3/h
m3/h
m3/h
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
W
Main supply
V-ph-Hz
DIMENSIONS AND WEIGHTS
L - Width
H - Height
Height of feet
P - Depth
Weight
mm
mm
mm
mm
kg
MOP
MOT
❷ Heating capacity (70°C)
❸ Heating capacity (50°C)
❷ Heating capacity
additional coil
Air flow
Sound power level
❹ Sound pressure level
MAX
MED
MIN
MAX
MED
MIN
MAX
MAX
MED
MIN
MAX
MED
MIN
MAX
MED
MIN
MAX
MED
MIN
15
0,94
0,74
0,62
2,21
1,73
1,35
1,30
1,34
1,15
0,98
183
138
100
40
32
30
32
24
22
26
20
1,49
1,14
1,09
3,39
2,64
2,34
1,82
1,96
1,64
1,48
238
177
155
41
34
31
33
26
23
23
22
1,92
1,49
1,14
4,30
3,39
2,64
2,52
2,22
1,97
1,64
339
238
177
48
40
32
40
32
24
38
25
2,16
1,95
1,56
5,12
4,39
3,53
2,99
2,78
2,37
1,96
405
339
252
42
37
29
34
29
21
34
30
2,71
2,37
1,71
6,27
5,07
3,85
3,67
3,00
2,56
2,07
483
383
281
46
40
32
38
32
24
44
35
3,26
2,74
1,99
7,22
6,15
4,79
4,24
3,83
3,41
2,89
587
472
365
48
43
35
40
35
27
58
40
3,91
3,19
2,70
8,07
6,58
5,35
4,79
4,03
3,41
3,00
627
474
392
50
43
38
42
35
30
61
50
4,71
3,78
3,23
10,37
7,86
6,81
6,09
5,46
4,55
4,03
916
662
537
56
47
41
48
39
33
95
60
5,92
5,11
4,28
13,33
11,37
10,01
7,84
5,89
5,67
5,58
1.109
882
757
60
54
50
52
46
42
139
70
6,92
5,97
5,51
16,49
14,92
13,42
9,59
6,52
6,20
5,64
1.388
1.171
994
65
61
57
57
53
49
173
230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50
15
700
583
100
220
25
20
800
583
100
220
31
22
800
583
100
220
31
25
1.000
583
100
220
38
MVP
30
1.000
583
100
220
39
35
1.200
583
100
220
43
40
1.200
583
100
220
44
50
1.500
583
100
220
53
60
1.500
583
100
220
55
70
1.500
583
100
220
57
MVT
P
H
H
L
In the following conditions:
❶ Air: 27°C D.B.; 19°C W.B. - Water: 7/12°C.
❷ Air: 20°C - Water: 70/60°C.
❸ Air: 20°C - Water: 50°C, flow rate as in cooling.
❹ At 1 m from air outlet with directionality factor of 2.
L
MVP+feet
P
P. 89
Construction features
Heat exchanger: with finned coil with left-hand connections
reversible to right.
Centrifugal fan: 3-speed.
Structure: covering cabinet in pre-painted sheet metal
complete with renewable filter, grilles in ABS polymer and condensation drain pan with natural drainage.
Versions
• MVP - Vertical unit with cabinet equipped with lower air inlet
and upper outlet for wall mounting or with feet on ground.
• MVT - Vertical unit with cabinet equipped with front air inlet
and upper outlet for floor installation.
• MOP - Horizontal unit with cabinet equipped with rear air inlet
and front outlet for ceiling installation.
• MOT - Horizontal unit with cabinet equipped with lower air
inlet and front outlet for ceiling installation.
ACCESSORIES
➔
❖
➔
❖
➔
❖
➔
➔
➔
➔
❖
➔
❖
➔
➔
➔
➔
Additional water heating coil.
Electric heater.
Auxiliary condensation drain pan.
Manual damper.
Motorized damper.
Valve and balancing valve.
3-way ON/OFF solenoid valves for 2-pipe-systems.
3-way ON/OFF solenoid valves for 4-pipe-systems.
Rear panel.
Rear closure panel.
Rear closure panel with grille and filter.
Support feet with pipe cover.
STANDARD CONTROLS
For wall installation
➔ Panel with speed and summer/winter switch.
➔ Panel with room thermostat and summer/winter switch.
➔ Panel with room thermostat, summer/winter switch, ON/OFF
valve signal and electric heater.
➔ Minimum temperature thermostat (for installation on the
machine).
➔ Electronic panel with automatic summer/winter changeover
for 2-pipe-systems.
➔ Electronic panel with automatic summer/winter changeover
and automatic speed regulation for 2-pipe-systems with
electric heater or 4-pipe-systems.
For installation on machine ( MVP and MVT versions)
➔
❖ Panel with speed switch.
➔
❖ Panel with room thermostat, summer/winter switch and
speed switch.
➔
❖ Minimum temperature thermostat.
➔
❖ Panel with room thermostat, summer/winter switch,
ON/OFF valve signal and electric heater.
➔
❖ Electronic panel with automatic summer/winter changeover
for 2-pipe systems.
➔
❖ Electronic panel with automatic summer/winter changeover
and automatic speed regulation for 2-pipe-systems with
electric heater or 4-pipe-systems.
Key:
❖ Factory fitted
➔ Supplied loose
FAN COIL UNITS
Floor and ceiling fan coil units
Unit-System
1,1÷7,2 kW
2,4÷17,4kW
ADVANCED CONTROLS
➔
Electronic panel for wall or onboard mounting.
Wall-mounted electronic panel
For installation on machine.
➔
❖ Master electronic card with electronic control panel ( only for
MVP - MVT versions).
➔
❖ Master/slave electronic card.
➔
❖ Temperature probe for hot row.
➔
❖ Module for management of ON/OFF valves and electric
heater.
➔ Serial interfaces for connection to BMS (proprietary protocol,
Modbus RTU).
➔ Serial converters (RS485/RS232, RS485/USB) in the case
of centralised unit management.
➔ Serial interface (CAN-bus - Controller Area Network) for the
iDRHOSS system.
➔
Key:
❖ Factory fitted
➔ Supplied loose
YardyEV MOP-MOT-MVP-MVT MODEL
❶ Cooling capacity
MAX
kW
(total heat)
MED
kW
MIN
kW
❷ Heating capacity (70°C)
MAX
kW
MED
kW
MIN
kW
❸ Heating capacity (50°C) MAX
kW
❷ Heating capacity
MAX
kW
additional coil
MED
kW
MIN
kW
Air flow
MAX
m3/h
MED
m3/h
MIN
m3/h
Sound power level
MAX
dB(A)
MED
dB(A)
MIN
dB(A)
❹ Sound pressure level
MAX
dB(A)
MED
dB(A)
MIN
dB(A)
Maximum absorbed power
W
Main supply
V-ph-Hz
DIMENSIONS AND WEIGHTS
L - Width
H - Height
Height of feet
P - Depth
Weight
MOP
mm
mm
mm
mm
kg
MOT
15
1,02
0,87
0,62
2,40
2,02
1,35
1,41
1,40
1,16
0,98
209
163
100
43
35
26
35
27
18
32
20
1,71
1,32
1,09
3,74
2,81
2,34
2,20
2,16
1,72
1,48
288
207
155
44
35
28
36
27
20
30
22
1,92
1,49
1,14
4,30
3,39
2,64
2,52
2,22
1,97
1,64
339
238
177
48
40
32
40
32
24
38
25
2,42
1,95
1,56
5,66
4,39
3,53
3,31
3,01
2,56
2,07
484
339
252
48
38
30
40
30
22
45
35
2,96
2,49
2,00
6,51
5,45
4,31
3,82
3,24
2,78
2,30
547
434
329
50
43
36
42
35
28
54
40
3,61
2,74
2,38
8,32
6,15
5,26
4,88
3,92
3,41
3,02
676
472
390
51
43
38
43
35
30
72
45
4,12
3,19
2,89
8,88
6,58
6,08
5,26
3,93
3,41
3,04
681
474
431
52
43
41
44
35
33
70
55
5,23
4,27
3,78
11,70
9,32
7,86
6,83
6,11
5,16
4,55
1.077
802
662
58
52
47
50
44
39
115
65
6,34
5,28
4,28
14,23
11,72
10,01
8,36
6,31
5,80
5,58
1.235
948
757
62
56
50
54
48
42
161
75
7,19
5,97
5,51
17,37
14,92
13,42
10,08
6,81
6,20
5,64
1.480
1.171
994
66
61
57
58
53
49
184
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
15
700
570
100
220
25
20
800
570
100
220
31
22
800
570
100
220
31
25
1.000
570
100
220
38
35
1.000
570
100
220
39
40
1.200
570
100
220
43
45
1.200
570
100
220
44
55
1.500
570
100
220
55
65
1.500
570
100
220
55
75
1.500
570
100
220
57
MVT
MVP
P
H
H
L
In the following conditions:
❶ Air: 27°C D.B.; 19°C W.B. - Water: 7/12°C.
❷ Air: 20°C - Water: 70/60°C.
❸ Air: 20°C - Water: 50°C, flow rate as in cooling.
❹ At 1 m from air outlet with directionality factor of 2.
P
MVP+feet
L
P. 91
Construction features
Heat exchanger: with finned coil with left-hand connections
reversible to right.
Centrifugal fan: 3-speed for versions IVP, IVF and IOP; 5speed for COP version.
Structure: in galvanized sheet steel, complete with condensation drain pan with natural drainage and renewable filter (class
G2 for COP version).
Versions
• IVP - Recessed vertical unit equipped with lower air inlet and
upper outlet for wall installation.
• IVF - Recessed vertical unit equipped with lower air inlet and
front outlet for wall installation.
• IOP - Recessed horizontal unit equipped with rear air inlet and
front outlet for ceiling installation.
• COP - Ductable recessed horizontal unit equipped with rear
air inlet and front outlet for ceiling installation.
ACCESSORIES
➔
❖
➔
❖
➔
❖
➔
➔
➔
❖
➔
❖
➔
➔
➔
➔
➔
➔
➔
➔
➔
Additional water heating coil.
Electric heater.
Auxiliary condensation drain pan.
Motorized damper.
Valve and balancing valve.
3-way ON/OFF solenoid valves for 2-pipe-systems.
3-way ON/OFF solenoid valves for 4-pipe-systems.
Straight outlet connection.
90° outlet connection.
90° inlet connection.
Telescopic outlet/inlet connection.
Inlet grille with filter.
Outlet grille.
Cover panel with grilles (only IVF and IOP).
Inlet plenum with circular nozzles.
Outlet plenum with circular nozzles.
STANDARD CONTROLS
For wall installation
➔ Panel with speed and summer/winter switch.
➔ Panel with room thermostat and summer/winter switch.
➔ Panel with room thermostat, summer/winter switch, ON/OFF
valve signal and electric heater.
➔ Minimum temperature thermostat (for installation on the
machine).
➔ Electronic panel with automatic summer/winter changeover
for 2-pipe-systems.
➔ Electronic panel with automatic summer/winter changeover
and automatic speed regulation for 2-pipe-systems with
electric heater or 4-pipe-systems.
ADVANCED CONTROLS
➔
Remote control
Electronic control panel for wall mounting.
➔ Wall-mounted electronic panel
For installation on machine.
➔
❖ Master/slave electronic card.
➔
❖ Temperature probe for hot row.
➔
❖ Module for management of ON/OFF valves and electric
heater.
➔ Serial interfaces for connection to BMS (proprietary protocol,
Modbus RTU).
➔ Serial converters (RS485/RS232, RS485/USB) in the case
of centralised unit management.
➔ Serial interface (CAN-bus - Controller Area Network) for the
iDRHOSS system.
➔
Key:
❖ Factory fitted
➔ Supplied loose
FAN COIL UNITS
Ductable and recessed fan coil units.
Wall-mounted
electronic panel
Electronic
control panel
for wall mounting.
YardyEV IOP-IVP-IVF MODEL
❶ Cooling capacity
MAX
(total heat)
MED
MIN
❷ Heating capacity (70°C)
MAX
MED
MIN
❸ Heating capacity (50°C) MAX
❷ Heating capacity
MAX
additional coil
MED
MIN
Air flow
MAX
MED
MIN
Sound power level
MAX
MED
MIN
❹ Sound pressure level
MAX
MED
MIN
Maximum absorbed power
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
m3/h
m3/h
m3/h
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
W
Main supply
V-ph-Hz
DIMENSIONS AND WEIGHTS
L - Width
H - Height
P - Depth
Weight
mm
mm
mm
kg
IOP
15
1,02
0,87
0,62
2,40
2,02
1,35
1,41
1,40
1,16
0,98
209
163
100
43
35
26
35
27
18
32
20
1,71
1,32
1,09
3,74
2,81
2,34
2,20
2,16
1,72
1,48
288
207
155
44
35
28
36
27
20
30
22
1,92
1,49
1,14
4,30
3,39
2,64
2,52
2,22
1,97
1,64
339
238
177
48
40
32
40
32
24
38
25
2,42
1,95
1,56
5,66
4,39
3,53
3,31
3,01
2,56
2,07
484
339
252
48
38
30
40
30
22
45
35
2,96
2,49
2,00
6,51
5,45
4,31
3,82
3,24
2,78
2,30
547
434
329
50
43
36
42
35
28
54
40
3,61
2,74
2,38
8,32
6,15
5,26
4,88
3,92
3,41
3,02
676
472
390
51
43
38
43
35
30
72
45
4,12
3,19
2,89
8,88
6,58
6,08
5,26
3,93
3,41
3,04
681
474
431
52
43
41
44
35
33
70
55
5,23
4,27
3,78
11,70
9,32
7,86
6,83
6,11
5,16
4,55
1.077
802
662
58
52
47
50
44
39
115
65
6,34
5,28
4,28
14,23
11,72
10,01
8,36
6,31
5,80
5,58
1.235
948
757
62
56
50
54
48
42
161
75
7,19
5,97
5,51
17,37
14,92
13,42
10,08
6,81
6,20
5,64
1.480
1.171
994
66
61
57
58
53
49
184
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
15
450
545
212
22
20
550
545
212
28
22
550
545
212
28
25
750
545
212
35
35
750
545
212
36
40
950
545
212
39
45
950
545
212
40
55
1.250
545
212
48
65
1.250
545
212
50
75
1.250
545
212
52
IVP
IVF
H
P
H
H
L
P
In the following conditions:
❶ Air: 27°C D.B.; 19°C W.B. - Water: 7/12°C.
❷ Air: 20°C - Water: 70/60°C.
❸ Air: 20°C - Water: 50°C, flow rate as in cooling.
❹ At 1 m from air outlet with directionality factor of 2.
L
P
L
P. 93
Unit-System
1,1÷7,2 kW
2,4÷17,4 kW
Electronic
control panel
for wall mounting.
Wall-mounted
electronic panel
YardyEV COP with inlet and outlet plenum
with circular nozzles
Maximum absorbed power
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
m3/h
m3/h
m3/h
m3/h
m3/h
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
W
Main supply
V-ph-Hz
DIMENSIONS AND WEIGHTS
L - Width
H - Height
P - Depth
Weight
mm
mm
mm
kg
❷ Heating capacity (70°C)
❸ Heating capacity (50°C)
❷ Heating capacity
additional coil
Air flow
Sound power level
❹ Sound pressure level
V
IV
III
II
I
V
IV
III
II
I
V
IV
III
II
I
V
IV
III
II
I
V
IV
III
II
I
V
IV
III
II
I
V
IV
III
II
I
33
3,46
3,28
2,98
2,50
2,32
7,64
7,25
6,58
5,51
5,11
4,48
4,24
3,85
3,23
3,00
3,83
3,64
3,31
2,78
2,58
695
645
560
440
400
60
58
55
49
47
52
50
47
41
39
100
44
5,38
4,53
4,16
3,83
3,41
11,19
9,44
8,66
7,96
7,10
6,63
5,60
5,13
4,72
4,21
5,57
4,72
4,31
3,97
3,54
970
765
685
615
535
66
62
60
58
55
58
54
52
50
47
120
66
6,17
5,96
5,61
5,33
4,99
13,57
13,1
12,3
11,7
11,0
7,95
7,66
7,23
6,86
6,44
6,07
5,85
5,50
5,24
4,91
1.195
1.130
1.040
970
890
65
63
61
60
59
57
55
53
52
51
150
230-1-50
230-1-50
230-1-50
33
750
545
212
35
44
950
545
212
40
66
1.250
545
212
52
In the following conditions:
❶ Air: 27°C D.B.; 19°C W.B. - Water: 7/12°C.
Available head pressure 0 Pa.
❷ Air: 20°C - Water: 70/60°C.
Available head pressure 0 Pa.
❸ Air: 20°C - Water: 50°C, flow rate as in cooling;
max. speed Available head pressure 0 Pa.
❹ At 1 m from air outlet with directionality factor of
2, non-ducted unit.
FAN COIL UNITS
MODEL YardyEV COP
❶ Cooling capacity
(total heat)
COP
P
H
L
Cassette-type fan coil units
Construction features
Fan coils: cassette-type for installation in false ceilings, with
air inlet and outlet directly into the room.
Heat exchanger: with finned coil.
Fan: 3-speed.
Structure: load-bearing, in galvanised sheet metal, complete
with condensation drain pump (up to 200 mm above the unit).
Air supply panel: in ABS polymer with manually adjustable
outlet fins, inlet grille and renewable filter.
Versions
• Standard - for 2-pipes-systems.
• B4 - for 4-pipes-systems.
• REL - for 2-pipes-systems supplementary electric heater.
Accessories supplied loose
•
•
•
•
•
•
3-way ON/OFF solenoid valve for 2-pipe-systems.
3-way ON/OFF solenoid valves for 4-pipe-systems.
Micro-pump for condensation.
Auxiliary condensation drain pan.
Outlet nozzle lock.
Photocatalytic and passive electrostatic filter.
STANDARD CONTROLS
For wall installation
➔ Panel with speed and summer/winter switch.
➔ Panel with room thermostat, summer/winter switch, ON/OFF
valve signal and electric heater.
➔ Electronic panel with automatic summer/winter changeover
for 2-pipe-systems.
➔ Electronic panel with automatic summer/winter changeover
and automatic speed regulation for 2-pipe-systems with
electric heater or 4-pipe-systems.
ADVANCED CONTROLS
➔
Remote control
Electronic control panel for wall mounting.
➔ Wall-mounted electronic panel
For installation on machine.
➔ Master/slave electronic card.
➔ Temperature probe for hot row.
➔ Module for management of ON/OFF valves and electric
heater.
➔ Serial interfaces for connection to BMS (proprietary protocol,
Modbus RTU).
➔ Serial converters (RS485/RS232, RS485/USB) in the case
of centralised unit management.
➔ Serial interface (CAN-bus - Controller Area Network) for the
iDRHOSS system.
➔
Key:
➔ Supplied loose
P. 95
Unit-System
2,4÷10 kW
5,6÷23,8 kW
Wall fitted
panel
Infrared remote
control with
bracket for wall
installation
UTNC-EV MODEL
❶ Cooling capacity
(total heat)
UTNC/B4 UTNC-UTNC/REL
25
40
1,90
4,00
1,43
2,85
1,23
1,90
–
7,03
–
5,94
–
3,47
–
4,19
1,77
–
1,34
–
1,16
–
–
2,5
–
–
662
698
450
490
360
310
49
54
43
45
40
34
41
46
35
37
32
26
70
90
UTNC/B4 UTNC-UTNC/REL
40
50
3,23
4,70
2,42
3,5
1,61
2,85
–
10,42
–
7,58
–
6,4
–
6,03
4,27
–
3,20
–
2,14
–
–
2,5
–
–
698
850
490
601
310
472
55
59
45
50
33
44
47
51
37
42
25
36
85
100
UTNC/B4 UTNC-UTNC/REL UTNC-UTNC/REL UTNC-UTNC/REL
50
60
85
110
4,00
6,30
7,60
10,00
3,05
4,50
5,10
7,10
2,50
3,40
3,17
3,90
–
13,76
18,36
23,77
–
9,99
12,6
17,03
–
7,43
7,54
9,35
–
8,12
10,80
12,90
4,64
–
–
–
3,51
–
–
–
2,74
–
–
–
–
–
–
–
–
3,0
3,0
3,0
850
1.019
1.217
1.685
601
731
871
1.134
472
540
529
641
58
49
56
63
50
41
49
55
42
36
41
42
50
41
48
55
42
33
41
47
34
28
33
34
95
90
120
200
UTNC/B4
110
8,45
6,29
3,53
–
–
–
–
7,92
6,95
4,49
–
–
1.685
1.134
641
63
55
42
55
47
34
200
Maximum absorbed power
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
m3/h
m3/h
m3/h
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
W
Main supply
V-ph-Hz
230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50
DIMENSIONS AND WEIGHTS
L2/H2/P2 - Width/Height/Depth
L/H/P - Width/Height/Depth
Weight UTNC - UTNC/REL
Weight UTNC/B4
Air supply panel weight
mm
mm
kg
kg
kg
25
25
40
40
50
50
60
85
110
110
575/298/575 575/298/575 575/298/575 575/298/575 575/298/575 575/298/575 825/298/825 825/298/825 825/298/825 825/298/825
720/30/720 720/30/720 720/30/720 720/30/720 720/30/720 720/30/720 960/30/960 960/30/960 960/30/960 960/30/960
18,5
–
20
–
20
–
37
39
39
–
–
18,5
–
20
–
20
–
–
–
40
4
4
4
4
4
4
6
6
6
6
❷ Heating capacity (70°C)
❸ Heating capacity (50°C)
❷ Heating capacity
additional coil B4
Electric heater REL
Electric heater REL
Air flow
Sound power level
❹ Sound pressure level
MAX
MED
MIN
MAX
MED
MIN
MAX
MAX
MED
MIN
230-1-50 V
400-3-50 V
MAX
MED
MIN
MAX
MED
MIN
MAX
MED
MIN
UTNC-UTNC/REL
25
2,40
1,80
1,55
5,55
4,38
3,85
3,16
–
–
–
1,5
–
662
450
360
49
38
34
41
30
26
70
In the following conditions:
❶ Air: 27°C D.B.; 19°C W.B. - Water: 7/12°C.
❷ Air: 20°C - Water: 70/60°C.
❸ Air: 20°C - Water: 50°C, flow rate as in cooling.
❹ At 1 m from air outlet with directionality factor of 2.
L2
P2
H2
P
L
FAN COIL UNITS
Electronic
control panel
for wall mounting
VTNC 25÷85
Cassette-type fan coil units
Versions
Standard - for 2-pipes-systems.
Construction features
Fan coils: cassette-type for installation in false ceilings, with
air inlet and outlet directly into the room.
Heat exchanger: with finned coil.
Fan: 3-speed.
Structure: load-bearing, in galvanised sheet metal, complete
with condensation drain pump (up to 200 mm above the unit)
and auxiliary condensation drain pan.
Air supply panel: in ABS polymer
(RAL9010) with motorised outlet fins adjustable in various
positions, inlet grille and renewable filter.
Remote control: supplied as standard
Accessories supplied loose
• 3-way ON/OFF solenoid valve for 2-pipe-systems.
• Outlet nozzle lock.
STANDARD CONTROLS
For wall installation
➔ Electronic control panel for wall mounting.
P. 97
Unit-System
2,5÷8,5 kW
5,4÷20,4 kW
VTNC MODEL
❶ Cooling capacity
(total heat)
Maximum absorbed power
kW
kW
kW
kW
kW
kW
kW
m3/h
m3/h
m3/h
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
W
Main supply
V-ph-Hz
❷ Heating capacity (70°C)
❸ Heating capacity (50°C)
Air flow
Sound power level
❹ Sound pressure level
MAX
MED
MIN
MAX
MED
MIN
MAX
MAX
MED
MIN
MAX
MED
MIN
MAX
MED
MIN
DIMENSIONS AND WEIGHTS
L2/H2/P2 - Width/Height/Depth
L/H/P - Width/Height/Depth
Weight VTNC
Air supply panel weight
mm
mm
kg
kg
VTNC
25
2,50
2,29
2,01
5,81
5,33
4,66
3,63
603
524
416
49
46
40
41
38
32
69
P
VTNC
30
3,06
2,79
2,47
5,70
5,21
4,61
4,09
680
599
468
54
51
44
46
43
36
69
L
E
R
I
VTNC
50
4,83
4,57
3,95
10,45
9,90
8,55
5,99
914
842
756
62
59
56
54
51
48
87
N
I
M
VTNC
60
5,75
4,38
3,13
13,26
10,10
7,22
8,65
1401
1176
967
59
50
43
51
42
35
118
VTNC
85
7,83
7,13
5,92
19,61
17,86
14,83
11,36
1720
1585
1333
62
60
58
54
52
50
162
Y
R
A
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
25
580/254/580
650/30/650
21
3
30
580/254/580
650/30/650
21
3
50
580/254/580
650/30/650
21
3
60
840/240/840
950/40/950
36
6
85
840/310/840
950/40/950
40
6
In the following conditions:
❶ Air: 27°C D.B.; 19°C W.B. - Water: 7/12°C.
❷ Air: 20°C - Water: 70/60°C.
❸ Air: 20°C - Water: 50°C, flow rate as in cooling.
❹ At 1 m from air outlet with directionality factor of 2.
L2
P2
H2
P
L
FAN COIL UNITS
Remote control
UTNB 011÷017
UTNB with air inlet
via inlet panelling
and multi-duct outlet
Wall-mounted
electronic panel
Electronic control
panel for wall
mounting
Ductable terminal air handling units in
sections
Construction features
Air handling unit: in modules for installation in false ceiling,
with ducting or panelling (29 cm in height).
Heat exchanger: with finned coil with right-hand connections
reversible to left.
Fan: centrifugal 3-speed (IP44).
Structure: load-bearing in galvanized sheet metal complete
with thermo-acoustic insulation, renewable filter, connection for
attachment to inlet duct and condensation drain pan with
natural drainage.
STANDARD CONTROLS
For wall installation
➔ Panel with speed and summer/winter switch.
➔ Panel with room thermostat, summer/winter switch, ON/OFF
valve signal.
➔ Control panel for modulating valves in 4-pipe systems.
➔ Humidistat panel.
➔ Electronic panel with automatic summer/winter changeover
for 2-pipe-systems.
➔ Electronic panel with automatic summer/winter changeover
and automatic speed regulation for 2-pipe-systems with
electric heater or 4-pipe-systems.
ADVANCED CONTROLS
Accessories supplied loose
• Additional water heating coil.
• Inlet/outlet plenum (KPAM).
• Electric coil module of 1.5-3-4.5 kW (KBAE).
• Plenum with steam humidifier (KUMI).
• Outlet nozzles module (KBOM).
• Inlet panelling.
• Solid panelling.
• Outlet panelling.
➔
Remote control
Electronic control panel for wall mounting.
➔ Wall-mounted electronic panel
For installation on machine.
➔ Master/slave electronic card.
➔ Temperature probe for hot row.
➔ Module for management of ON/OFF valves and electric
heater.
➔ Serial interfaces for connection to BMS (proprietary protocol,
Modbus RTU).
➔ Serial converters (RS485/RS232, RS485/USB) in the case
of centralised unit management.
➔ Serial interface (CAN-bus - Controller Area Network) for the
iDRHOSS system.
➔
Key:
➔ Supplied loose
P. 99
Unit-System
4,1÷10,5 kW
10,3÷23 kW
100
290
Humidistat
panel for
KUMI
99
0
130
660
(*)
290
290
UTNB
Base unit
KBOM
Outlet
nozzles
module
KUMI
Plenum with
humidifier
011 2R
011 4R
011 6R
014 2R
014 4R
014 6R
017 2R
017 4R
❶ Nominal cooling capacity
kW
4,11
6,76
7,78
4,82
8,23
9,64
5,14
8,92
10,52
➋ Nominal heating capacity
kW
10.35
(•)
(•)
12.66
18.83
(•)
13.76
20.78
23.04
➋ Nominal heating capacity additional coil
kW
10,02
10,02
10,02
12,37
12,37
12,37
13,49
13,49
13,49
Air flow
MAX
m3/h
1.100
1.100
1.100
1.480
1.480
1.480
1.680
1.680
1.680
MED
m3/h
990
990
990
1.260
1.260
1.260
1.440
1.440
1.440
MIN
m3/h
850
850
850
1.100
1.100
1.100
1.200
1.200
1.200
6
3
0
16
4
0
23
7
0
dB(A)
41
41
41
47
47
47
50
50
50
MED
dB(A)
40
40
40
44
44
44
46
46
46
MIN
dB(A)
38
38
38
41
41
41
41
41
41
165
165
165
205
205
205
245
245
245
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
UTNB MODEL
➍ Available head pressure at maximum speed Pa
❸ Sound pressure level
MAX
❶/➋ Absorbed power
W
Main supply
V-ph-Hz
017 6R
011 2R
011 4R
011 6R
014 2R
014 4R
014 6R
017 2R
017 4R
017 6R
L - Width
mm
990
990
990
990
990
990
990
990
990
H - Height
mm
290
290
290
290
290
290
290
290
290
KPAM - Depth
mm
290
290
290
290
290
290
290
290
290
UTNB - Depth
mm
738
738
738
738
738
738
738
738
738
KBAE - Depth
mm
130
130
130
130
130
130
130
130
130
KUMI - Depth
mm
290
290
290
290
290
290
290
290
290
KBOM - Depth
mm
100
100
100
100
100
100
100
100
100
Weight UTNB
kg
38
42
46
38
42
46
40
44
48
DIMENSIONS AND WEIGHTS
In the following conditions:
❶ Air: 27°C D.B.; 19°C W.B. - Water: 7/12°C. Maximum speed
❷ Air: 20°C - Water: 70/60°C. Maximum speed
❸ At 3 m from the point of air outlet, with open outlet.
➍ With filter and coil.
(•) Not to be used with water at 70°C, capacities at different temperatures are
shown in the technical catalogue.
(*) Unit dimensions in combination with KPAM plenum
TERMINAL UNITS
KPAM
Inlet/outlet plenum
KBAE
Electric coil
module
UTNA 015÷150
Wall-mounted
electronic panel
Base
composition
Electronic control
panel for wall
mounting.
BA
Coil
module
SV
Fan
module
Ductable terminal air handling units in
sections
Construction features
Air handling unit: in sections for horizontal installation either
with or without ducting.
Structure: in galvanized steel sheet metal, with fully removable
pre-painted sheet metal panelling, complete with self-extinguishing thermo-acoustic insulation.
Module BA 2R, BA 4R, BA 6R: complete with pleated filter in
2 sections with degree of efficiency G3, can be slid out in all
directions; heat exchanger with finned coil, with 2 or 4 or 6
rows with reversible right-hand connections; condensation
drain pan with natural drainage.
Fan module SV: complete with centrifugal fan with double
inlet with motor (IP55) directly coupled, 3-speed for models
015÷038; 2-speed for model 051; with 4-pole single speed
motor (4/6 or 4/8 poles on request) coupled by means of
trapezoidal belt and variable pulley for models 078-150.
Electrical board: standard for models 051÷150; accessory
for models 015÷038.
Accessory modules
• Inlet/outlet plenum with pre-cut side outlets (PMA).
• Plenum with absorbent cartridge silencer to be placed for inlet
or outlet (SIL).
• Plenum with steam humidifier and external electric generator
(MUV - PRV).
Accessories supplied loose
• Additional water heating coil to be inserted in module BA.
• Supplementary electric heater from 1.5 kW to 36 kW, to be
inserted in module BA.
• Droplet eliminator for models 078÷150, to be inserted in
module BA.
• Combined fresh air damper (max 25%) and re-circulation, to
be attached to the PMA inlet plenum.
• Solid pre-cut panel for connection to duct, to be attached to
the PMA inlet plenum.
• Panel with rectangluar outlet nozzle with double row of
adjustable fins, to be attached to PMA outlet plenum.
• Panel with circular nozzles, to be attached to PMA inlet/outlet
plenum (only for models 015÷051).
• Manual control for KSER damper.
• Electrical panel in waterproof box (IP55 for UTNA 015÷038).
• Humidistat panel for humidifier.
STANDARD CONTROLS
For wall installation
➔ Panel with speed and summer/winter switch.
➔ Panel with room thermostat, summer/winter switch, ON/OFF
valve signal.
➔ Control panel for modulating valves in 4-pipe systems.
➔ Humidistat panel.
➔ Electronic panel with automatic summer/winter changeover
for 2-pipe-systems.
➔ Electronic panel with automatic summer/winter changeover
and automatic speed regulation for 2-pipe-systems with
electric heater or 4-pipe-systems.
ADVANCED CONTROLS
➔
Remote control
Electronic control panel for wall mounting.
➔ Wall-mounted electronic panel
For installation on machine.
➔ Master/slave electronic card.
➔ Temperature probe for hot row.
➔ Module for management of ON/OFF valves and electric
heater.
➔ Serial interfaces for connection to BMS (proprietary protocol,
Modbus RTU).
➔ Serial converters (RS485/RS232, RS485/USB) in the case
of centralised unit management.
➔ Serial interface (CAN-bus - Controller Area Network) for the
iDRHOSS system.
➔
Key:
❖ Factory fitted
➔ Supplied loose
P. 101
Unit-System
7,2÷108 kW
11,3÷174 kW
Complete composition
KSER
Damper
P
KB2R
Additional
heating
coil
SIL
Plenum
with silencer
L
PRV
Steam
producer
H
KPBC
Panel with
circular nozzles
BA
Coil
module
MUV
Plenum
with humidifier
SV
Fan
module
Humidistat
panel
KPBM
Panel with
outlet nozzle
PMA
Inlet/outlet
plenum
UTNA MODEL
015
020
029
038
051
078
107
130
150
➋ Nominal heating capacity additional coil BA 2R/KB2R kW
11,3
14,2
20,7
25,8
35,2
57,5
82,6
92,7
106,0
❶ Nominal cooling capacity BA 4R
kW
7,2
8,8
13,9
17,3
21,4
41,8
60,6
67,8
77,1
➋ Nominal heating capacity BA 4R
kW
18,5
24,0
33,7
42,8
57,6
92,9
133,0
152,0
174,0
❶ Nominal cooling capacity BA 6R
kW
9,9
12,5
17,9
22,4
30,9
55,6
82,7
94,4
108,0
➋Nominal heating capacity BA 6R
kW
(•)
(•)
(•)
(•)
(•)
(•)
(•)
(•)
(•)
230V-1ph-50Hz kW
1,5-3-4,5
3-4,5-6
4,5-6-9
6-9-12
–
–
–
–
–
400V-3ph-50Hz kW
1,5-3-4,5
3-4,5-6
4,5-6-9
6-9-12
9-12-18
12-18-24
18-24-36
18-24-36
24-36
Electric heater
power
Air flow
MAX
m3/h
1.800
2.640
3.220
4.260
6.120
MED
m3/h
1.370
2.240
2.400
3.500
–
–
–
–
MIN
m3/h
1.060
1.480
1.560
2.850
4.390
–
–
–
–
90
90
90
90
130
170
160
145
140
61,9
➍ Available head pressure at maximum speed Pa
❸ Sound pressure level
8.580 (*) 11.770 (*) 14.300 (*) 16.500 (*)
–
MAX
dB(A)
50,9
55,6
54,9
59,8
61,5
59,7
61,7
65,4
MED
dB(A)
44,3
50,2
48,3
55,7
–
–
–
–
–
MIN
dB(A)
37,1
42,1
38,7
51,4
54,4
–
–
–
–
❶/➋ Absorbed power
W
370
700
700
1.250
1.850
1.500
1.500
2.200
3.000
Main supply
V-ph-Hz
230-1-50
230-1-50
230-1-50
230-1-50
400-3-50
400-3-50
400-3-50
400-3-50
400-3-50
015
020
029
038
051
078
107
130
150
mm
928
928
1.228
1.228
1.328
1.658
2.058
2.058
2.058
H - Height
mm
398
398
463
518
568
768
918
918
1.018
PMA - Depth
mm
370
370
435
490
540
740
890
890
990
BA - Depth
mm
645
645
645
645
645
910
910
910
910
SV - Depth
mm
370
370
435
490
490
1.040
1.040
1.040
1.040
SIL-MUV - Depth
mm
960
960
960
960
960
1.040
1.040
1.040
1.040
➎ Weight UTNA
kg
51
51
68
71
79
140
200
200
220
DIMENSIONS AND WEIGHTS
L - Width
In the following conditions:
❶ Air: 27°C D.B.; 19°C W.B. - Water: 7/12°C. Maximum speed
❷ Air: 20°C - Water: 70/60°C. Maximum speed
❸ At 3 m from the point of air outlet, with open outlet.
➍ 4-row coil (BA 4R) and filter..
➎ Empty weight BA 6R.
(•) Not to be used with water at 70°C, capacities at different temperatures are
shown in the technical catalogue.
(*) Belt transmission with variable ratio.
TERMINAL UNITS
PMA
Inlet/outlet
plenum
UTNV 030÷150
Air conditioning and ventilation terminal
units.
Construction features
Air conditioning and ventilation unit: for vertical installation
with or without ducting.
Structure: packaged composed of treatment section and fan
assembly with load-bearing frame in double-chamber extruded
aluminium profiles with concealed screws, corner joints in black
nylon, glass reinforced.
Removable panelling in double sheet metal, in galvanized steel
on the inside and pre-painted with protection film on the
outside, with expanded polyurethane inserted (density 45
kg/m3) and total thickness of 25 mm.
Base with extruded aluminium profiles.
Treatment section composed of: pleated renewable multisection filters with degree of efficiency G3, can be extracted
from front (or from side with KEF accessory), heat exchanger
with finned coil with 2-4-6 rows with connections on right
or left on request and galvanized steel condensation drain pan
with natural drainage. On request the water connections can be
located on the right or left side of the unit.
Electric fan assembly: with upper or front outlet composed
of double inlet centrifugal fans with forward rotors with antivibration joint on pressing mouth, tri-phase motor (IP55),
variable pulley and trapezoidal belt drive (up to model 080),
anti-vibration rubber mountings.
Versions
• M - Single-phase motor for models 030-050 with adjustable
pulley.
• T6 - Tri-phase 4/6-pole motor with adjustable pulley.
• T8 - Tri-phase 4/8-pole motor with adjustable pulley.
• E - Treatment section with side opening for fresh air inlet.
• B2R - Additional coil with 2 rows for 4-pipe systems for UTNV
4R and UTNV 6R.
• B2P - Additional coil with 2 post-heating rows for UTNV 4R
and UTNV 6R.
• EFL - Side extraction of filters on opposite side from water
connections.
Accessory modules
• Outlet plenum, with aluminium nozzles with double row of
adjustable fins.
• Outlet plenum, with galvanized steel nozzles with double row
of fins.
Accessories supplied loose
• Inlet grille in galvanized steel.
• Inlet grille in aluminium.
• Side extraction of filters on opposite side from water
connections.
• Panel with room thermostat, summer/winter switch,
ON/OFF valve signal.
P. 103
Unit-System
14,5÷98,2 kW
22,3÷226,8 kW
UTNV with outlet
plenum.
Front filter
extraction and
inlet grille.
030
050
080
100
125
150
➋ Nominal heating capacity UTNV 2R
kW
22,3
40,5
61,3
77,5
95,1
114,9
❶ Nominal cooling capacity UTNV 4R
kW
14,5
27,6
40,5
52,6
63,6
77,6
➋ Nominal heating capacity UTNV 4R
kW
37,6
68,3
101,6
130,1
159,2
190,8
❶ Nominal cooling capacity UTNV 6R
kW
19,2
33,9
51,8
65,5
81,4
98,2
➋ Nominal heating capacity UTNV 6R
kW
44,9
80,6
122,1
153,8
189,2
226,8
UTNV MODEL
➋ Nominal heating capacity of additional coil B2R-B2P kW
Air flow speed max.
m3/h
Available head pressure max. UTNV 4R
Pa
❸ Sound pressure level max. speed
dB(A)
❶/➋ Absorbed power
kW
22,3
40,5
61,3
77,5
95,1
114,9
3.150
5.600
8.500
10.600
13.100
15.600
170
170
170
173
170
172
60,0
62,9
62,7
69,2
66,0
64,6
0,75
1,50
2,20
3,00
4,00
4,00
230-1-50
400-3-50
230-1-50
400-3-50
230-1-50
400-3-50
400-3-50
400-3-50
400-3-50
030
050
080
100
125
150
mm
1.000
1.200
1.500
1.750
2.050
2.400
H - Height UTNV 2R/4R/6R/4R+2R/2R+4R mm
1.600
1.800
2.000
2.000
2.000
2.000
H - Height 6R+2R
mm
1.800
2.000
2.200
2.200
2.200
2.200
P - Depth
mm
680
760
840
840
840
840
Weight
kg
165
270
360
465
520
570
Main supply
V-ph-Hz
DIMENSIONS AND WEIGHTS
L - Width
In the following conditions:
❶ Air: 27°C D.B.; 19°C W.B. - Water: 7/12°C. Maximum speed
❷ Air: 20°C - Water: 70/60°C. Maximum speed
❸ At 3 m from the point of air outlet.
H
L
P
TERMINAL UNITS
Side filter extraction
on request.
UTNR 012÷041
Air renewal terminal units with heat recovery
Accessory modules
Construction features
• KPAV - Plenum with side openings for vertical unit installation,
designed to house the filter accessory and dampers.
Unit for environment air renewal with heat recovery: for
horizontal or vertical installation with dedicated accessory
(KPAV).
Structure: load-bearing frame with extruded 30-mm aluminium
sections, glass-loaded nylon or painted aluminium nylon
corners, and closed cell seals.
Sandwich panels with a total thickness of 25 mm, in double
galvanised sheet steel, hot-injected polyurethane insulation,
density 45 kg/m3.
Removal side panels for external bypass of the recovery unit.
Module with recovery unit: aluminium air-air type package
recovery unit with rough surface plates, housed in a built-in condensation collection tray in galvanised steel.
Filters: folded, thickness 48 mm (thickness 98 mm on UTNR
032 and 041), as standard on external air, with efficiency rating
of G3, extractable from below.
Fan module: double inlet centrifugal electric fans directly
connected at 3 speeds with protection rating IP44 (IP 20 on
UTNR 041).
Accessories supplied loose
• Two-range additional water heating coils, with left-hand
connections.
• Electric heater in carbon steel with galvanised steel fins
(available in versions with single-phase and three-phase
power supply).
• Air outlet synthetic filters.
• Air outlet metal filters.
• Galvanised steel damper on external air inlet and/or outlet.
STANDARD CONTROLS
For wall installation
➔ Panel with speed and summer/winter switch.
➔ Panel with room thermostat, summer/winter switch, ON/OFF
valve signal and electric heater.
Key:
❖ Factory fitted
➔ Supplied loose
P. 105
Unit-System
5,4÷18,6 kW
012
017
023
032
50
52
52
50
50
kW
5,44
8,02
10,89
14,51
18,59
➋ Nominal heating capacity of additional coil
kW
10,30
15,68
21,08
28,78
37,59
❸ Air flow
MAX
m3/h
1.200
1.700
2.300
3.200
4.100
MED
m3/h
1.050
1.450
1.850
2.600
3.400
MIN
m3/h
925
1.150
1.550
2.100
2.600
❸ Supply available static pressure
Pa
100
120
150
120
160
❹ Sound pressure level
Supply
MAX
dB(A)
57
56
58
60
60
MED
dB(A)
54
53
56
58
58
❶ Recovery efficiency
%
❶ Nominal heating capacity
041
MIN
dB(A)
52
52
53
52
55
MAX
m3/h
1.200
1.550
2.300
2.880
4.000
MED
m3/h
1.050
1.300
1.650
2.430
2.850
MIN
m3/h
925
1.150
1.020
2.020
1.850
❸ Available outlet head pressure
Pa
100
90
130
100
90
❹ Sound pressure level
Return
MAX
dB(A)
53
55
58
62
58
MED
dB(A)
52
54
54
59
55
MIN
dB(A)
49
50
49
54
50
❸ Return air flow
Supply/return motor absorbed power
W
300/184
300/300
420/350
550/550
600/600
Main supply
V-ph-Hz
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
DIMENSIONS AND WEIGHTS
L - Width
mm
012
017
023
032
041
1.000
1.140
1.200
1.260
1.480
H - Height
mm
440
520
520
600
620
P - Depth
mm
1.260
1.380
1.500
1.700
1.760
UTNR weight (with water coil)
kg
90
90
90
150
230
Weight KPAV
kg
20
24
28
30
35
❸ Unit without accessories, with standard filter
❹ At 3 m from air outlet, with free nozzle and directionality factor of 2.
In the following conditions:
❶ Outdoor air: 20°C D. B. - 50% R.H.; Renewal air –5°C D.B., 80% R.H.
Maximum speed - ❷ Water 70°C with Δt 10°C. Maximum speed
VERTICAL INSTALLATION
WITH KPAV ACCESSORY
HORIZONTAL INSTALLATION
INTERNAL
EXTERNAL
INTERNAL
P
EXTERNAL
H
L
TERMINAL UNITS
UTNR MODEL
CONTROLS
◆
◆
◆
◆
◆
◆
Output 0 - 10 V DC
4-pipe systems
◆
2-pipe systems
◆
Continuous
ventilation or
thermostat.
Air sensor with
remote control option
◆
◆
◆
◆
◆ ◆
◆
◆
◆ ◆
AUTOMATIC
AUTOMATIC
SPEED
◆
MINIMUM
SPEED
REGULATION
±5°C
◆
◆ ◆
◆
◆
◆
◆
◆
AUTOMATIC
◆
◆
◆
◆
◆ ◆
◆
◆
➔ Wall-mounted electronic
panel
➔ ❖ MASTER electronic
card
◆
◆
◆
◆
◆
➔ Wall-mounted electronic
panel
➔ ❖ MASTER electronic
card
◆
◆
◆
◆
◆
➔ Remote control
➔ ❖ MASTER electronic
card
➔ ❖ Receiver
on the machine
◆
◆
◆
◆
◆
◆
◆
◆
➔ ❖ SLAVE electronic
card
Additional modules:
➔ ❖ Probe for additional coil
➔ ❖ ON/OFF valves management module
➔ ❖ Electric heater module
Key:
❖ Factory fitted
➔ Supplied loose
◆
◆
◆
Serial
interface.
◆
Electric
heater
◆
INSTALLATION:
➔ ❖ Electronic panel on
machine
➔ ❖ MASTER electronic
card on machine
ON/OFF
valves
control
◆
ADVANCED CONTROLS
RECEIVER
◆
Electric heater
control
➔ KTCV2 wall mounted
➔ KBTCV2 - ❖ TCV2
on the machine
➔ KTCVA wall mounted
➔ KBTCVA - ❖ TCVA
on the machine
➔ KTCVR wall mounted
➔ KBTCVR - ❖ TCVR
on the machine
➔ KTCVM
wall mounted
◆
4-pipe
systems
KTCVR
➔ KTIE1
wall mounted
◆
2-pipe
systems
KTIE1
◆
Master/Slave
KTCVA
◆
Comfort
functions
KTCV2
◆
Regulation
functions
KCV2
◆
ON/OFF valves
control
➔ KCV2
wall mounted
◆
Summer/winter
switch
TATM
C
➔ KTA - ❖ TATM
on the machine
Minimum
thermostat
INSTALLATION:
➔ KC - ❖ C
on the machine
Room
thermostat
STANDARD CONTROLS
3-speed
ON/OFF
switch
for fan coil units and terminal units
◆
◆
◆
P. 107
ELECTRONIC CONTROL FOR TERMINAL UNITS
REGULATION
FUNCTIONS
TOO COOL
Summer on/off signal.
FULL AUTO
Automatic management.
FULL AUTO
MEMORY
Memorisation
of operating mode.
COOL
Cooling.
ADVANCED FUNCTIONS
DRY
Dehumidification.
ECONOMY (ECO)
Energy savings.
FAN - AUTOFAN
Manual/automatic
ventilation.
LOCK
FUNCTION
HEAT (HEAT+ELECTRIC HEATER)
Heating (Heating with electrical
heater).
REMOTE
CONTROL
LOCK FUNCTION
Locked operation
for hotel room.
ON/OFF remote control
Remote start-up
and shutdown.
COMFORT FUNCTIONS
ORIENTING/SWING
Fixed/swinging louver.
SUMMER/WINTER remote
control
Summer/winter remote signal
LOCK
FUNCTION
CLOCK
Display of set time.
ON
SECURITY control
External security
(window contact).
TIMER
Programmed
on/off.
OFF
PROBE IN/PROBE OUT
Remote working probe.
PROBE IN
SLEEP
Night-time air conditioning.
CONTINUOUS VENTILATION
Continuous ventilation or thermostat.
CONT
COMFORT
CONTROL
OCCUPANCY
SLAVE 1
SLAVE 2
SLAVE 3
SLAVE 4
COMFORT CONTROL
Regulator +/- 3°C
OCCUPANCY
Occupancy
for hotel rooms
ALARM
Alarm signals.
SLAVE 5
MASTER/SLAVE
FUNCTION
MASTER - SLAVE
Master/slave function
MASTER/SLAVE FUNCTION
✔ The MASTER/SLAVE function allows centralized management
of up to 5 units (called SLAVE) via a single unit (called
MASTER) equipped with a control panel or remote control.
MASTER
FAN COIL UNITS AND TERMINAL UNITS
IDROWALL
FREND
BrioEV
YardyEV
UTNC-EV
UTNB
UTNA
CONTROLS
HOT START
Winter on/off signal
Integrated solutions for system management
iDRHOSS is an advanced system for the
management of hydronic air conditioning
systems, developed to meet the comfort needs of
any civil or residential location.
iDRHOSS offers a series of functions, such as
centralized management, automatic summerwinter changeover and operating times, whilst
always working towards energy saving.
Area
controller
Advanced controls for
terminal units
Flush panel
Control panel for centralized
management of all the units
in the system.
Recessed panel
Cooling
Remote
control
unit
P. 109
iDRHOSS SYSTEM AREA CONTROLLER FUNCTIONS
✔ Start-up and shutdown of the entire system (chiller/heat
pump and terminal units).
✔ Display and modification of central unit.
✔ Centralised management of a number of zones and modification of the terminal units (ON/OFF, set-point, operating
mode, fan speed, sleep/economy mode).
✔ Management of daily time bands (ON/OFF) for the
terminals, different for each zone, and for the chiller/heat
pump with possible variations of set-point.
✔ Automatic seasonal switchover and real time status and
system operating display in real time (ON/ON by timer OFF/OFF
by
timer
OFF
by
alarm,
SUMMER/WINTER/BOILER).
✔ Automatic boiler management (and of any bypass valve on
the water system) in the event of shutdown of the heat
pump.
✔ Start-up and shutdown by GSM.
✔ Display and setting of current date and time.
✔ Configuration of the serial network and of the terminals
installed in the zones.
CHILLER ASSEMBLIES
TCAEY-THAEY
105÷265
TCCEY-THCEY
105÷111
TCAI-THAI 150
TCCE-THCE
114÷126
TCHEY-THHEY
105÷112
TXHEY 105÷112
TXAEY 117÷265
FAN COIL UNITS AND TERMINAL UNITS
IDROWALL
FREND
BrioEV
YardyEV
UTNC-EV
UTNB
UTNA
iDRHOSS
✔ Display for the main unit and for the terminal units of
possible alarm conditions (identified by a code and corresponding description).
RHOSS SUPERVISOR
RHOSS supervision software
RHOSS SUPERVISOR is the Rhoss supervision system that
allows monitoring and remote management of Rhoss units used
in a hydronic system.
This makes it possible to monitor, via a computer, the operation
of Rhoss chillers, heat pumps or terminal units, or the entire
iDRHOSS integrated hydronics system.
RHOSS SUPERVISOR is easy to use both in terms of
system configuration and access to characteristic unit parameters because it uses the Microsoft Internet Explorer interface.
RHOSS SUPERVISOR makes it possible to set up a local
supervision system via serial connection of the microprocessor
cards of the RHOSS units to a computer. If the local computer
is connected to the information system network of the building
(Ethernet with TCP/IP protocol), the information can be shared
with any other computer on the network. Supervision can also
be carried out remotely via GSM modem connection.
In both cases, access to supervisor information can be protected by various levels of password.
P. 111
RHOSS SUPERVISOR FOR CHILLERS AND HEAT PUMPS
RHOSS SUPERVISOR allows:
✔ control of unit start-up and shutdown;
✔ display and modification of summer/winter operation of the
heat pump units;
✔ display of temperature of water coming into and going out
of the unit;
✔ display of values of the three power supply voltages (QPack range);
✔ display of alarms;
✔ scheduling of actions to be performed in the event of an
alarm in a unit. In fact, it is possible to send a fax or e-mail
with all information required for remote service of the
cooling unit.
✔ scheduling/programming of periodic maintenance.
RHOSS SUPERVISOR FOR FAN COIL UNITS AND TERMINAL UNITS:
RHOSS SUPERVISOR allows:
✔ control of unit start-up and shutdown;
✔ display and modification of fan speed;
✔ display and modification of operating mode (Auto, Cool,
Dry, Fan, Heat, Heater);
✔ display and modification of set-point values;
✔ display of alarms;
✔ scheduling of actions to be performed in the event of an
alarm in a unit. In fact, it is possible to send a fax or e-mail
with all information on the event);
✔ set daily time zones with start/stop function, modification of
set-point and setting of operating mode.
SUPERVISION SOFTWARE
✔ display and modification of set-point values;
CTA ADV 240÷22920
Advance Range
Air handling units in sections
Construction features
Main modules: mixing box, discharge and re-circulation
section, recovery section, air treatment section, fan section,
filtering and silencing section.
Dampers: with opposing galvanized or aluminium fins.
Filters: pleated, rotary, bags, absolute and with active carbons.
Humidifiers: with spray nozzles, with humidifying package,
steam, by atomization, with compressed air.
Heat exchangers: finned package coils supplied in different
materials depending on their use and the vector fluid used, all
fully extractable on runners.
Droplet eliminator: in polypropylene, in galvanized steel, in
aluminium, in stainless steel.
Fans: with forward blades, reversed blades with a wing profile,
plug fan, with air flow regulator. The optimal choice in terms of
aeraulic performance, efficiency and noise levels can always be
found among the wide range of products available.
Heat recovery: with twin coils, with cross flows, rotary, with
heat pipes. All our heat recovery units are selected to obtain the
maximum possible energy saving in keeping with current
standards.
Structure: load-bearing in aluminium profiles, glass-loaded
nylon or painted aluminium nylon corners, continuous base or
base with modular sections depending on installation requirements.
PROFILES
• Standard: available from 40mm with the possibility of
installing an insulating panel measuring 25 or 42 mm or from
60mm with the possibility of installing a 46 or 63 mm panel.
• Curved profiles: with internal perfectly rounded corners for
use in sterile facilities.
• Thermal block profiles: constructed with double profiles,
with a rolled polyamide bar in between to eliminate thermal
transfer.
PANELS
• Realized in double box-bent sheet metal with insulating
material in the middle, available in:
- hot-injected polyurethane with an average density of 45
kg/m3;
- rock wool with oriented fibres with an average density of 95
kg/m3.
• Internal and/or external materials available for panels:
galvanized sheet steel, peraluman, pre-painted or prelaminated galvanized sheet metal, stainless steel.
Versions
• Standard: with single fan with a rectangular cross-section.
• Narrow range: with a square cross-section single fan.
• Lowered range: with paired fans.
• For use in specialized sectors (food service, hospitals, pharmaceutical, etc.).
Sizes: a total of 55 sizes subdivided between standard and
slim series are available and are shown in the dimension table.
The CTA ADV's are compliant with the essential safety requirements as set forth by EC Directives 89/392/EC and
subsequent modifications concerning machine safety,
73/23/EC and subsequent modifications concerning electrical
components that operate within given voltage ranges. The ADV
units comply with the provisions of standards UNI EN 292, UNI
EN 294, CEI EN 60204-1, UNI EN 563, UNI EN 1050, UNI
10893, UNI EN ISO 3744, ISO 3864, UNI EN 1886.
471
541
661
741
881
1071
1241
1700
1950
2400
2700
3200
3850
4500
mm
730
730
770
810
870
880
880
1030
mm
680
740
740
800
800
900
940
980
1461
1751
2021
2361
2831
3371
3941
4571
Air flow rate at 2.5 m/s
m3/h
Front dimension B
Front dimension H
Slim range MODEL
Air flow rate at 2.5 m/s
m3/h
5300
6300
7300
8500
10200
12200
14000
16500
Front dimension B
mm
1030
1030
1050
1220
1410
1610
1610
1630
Front dimension H
mm
1120
1280
1310
1340
1350
1350
1520
1700
5441
6561
7611
9131
10711
12751
15041
18361
Slim range MODEL
Air flow rate at 2.5 m/s
m3/h
19500
23500
27500
33000
38500
46000
55000
66000
Front dimension B
mm
1740
2020
2150
2500
2780
2900
3350
3800
Front dimension H
mm
1880
1880
2000
2000
2060
2300
2300
2420
Standard range MODEL
240
300
380
440
570
710
800
920
850
1080
1360
1700
2050
2450
2850
3300
950
970
1080
1080
1080
1080
660
720
720
750
820
880
1530
1720
2080
2300
2500
Air flow rate at 2.5 m/s
m3/h
Front dimension B
mm
730
820
Front dimension H
mm
630
630
1070
1220
1380
Standard range MODEL
Air flow rate at 2.5 m/s
m3/h
3850
440
4950
5500
6200
7500
8300
9000
Front dimension B
mm
1230
1360
1360
1430
1480
1550
1630
1630
Front dimension H
mm
Standard range MODEL
880
880
920
920
990
1070
1070
1170
2920
3270
3600
4300
5250
6060
7500
8480
Air flow rate at 2.5 m/s
m3/h
10500
12000
13000
15500
19000
21800
27000
30500
Front dimension B
mm
1630
1650
1650
1930
2130
2310
2700
2850
Front dimension H
mm
1300
1300
1400
1560
1560
1700
1700
1700
9750
11400
12600
13900
16580
19860
22920
Standard range MODEL
Air flow rate at 2.5 m/s
m3/h
35000
41000
45500
50000
59500
71500
82500
Front dimension B
mm
3000
3000
3200
3600
3850
4040
4540
Front dimension H
mm
1870
2050
2210
2210
2210
2420
2490
CURVED
40
42
25
42
STANDARD
40
40
60
60
63
46
63
H
60
60
WITH THERMAL BLOCK
60
63
46
63
B
60
AIR HANDLING UNITS
371
1300
Slim range MODEL
CTA ADVR: RHOSS completes its offer with the ADV units
equipped with their own electrical panel with dedicated thermal
regulation system. The units are supplied with a detailed
aeraulic diagram, a wiring diagram and a description of the
regulation. The air handling units are wired in all the regulation
and power components such as: electric motors, electronic
humidifiers, inverters, servo-motors and sensors. All the water
circuit components: are carefully selected, installed and precalibrated in the factory. The unit is functionally tested in all its
components in the factory. Start-up of the units is performed by
Rhoss qualified personnel to ensure reliability over time.
Selection software:
The innovative CTA ADV selection programme allows rapid and
correct unit sizing. The programme guides the user in the
choice of components, provides a technical sheet for professionals complete with a detailed description and drawing and
an up-to-date economic report.
The resulting configuration allows the order to be transmitted
directly to the production department, thus considerably
reducing the delivery times of the units.
PACKAGED
DE-HUMIDIFIERS FOR SWIMMING-POOLS
P. 116
DRESY-DAESY 108÷2111
Dry-Pool ADV Range
DE-HUMIDIFIERS FOR SWIMMING-POOLS with
or without heat recovery for pool water, air-cooled
and with centrifugal fans.
Range with hermetic Scroll compressors and
R410A refrigerant gas.
Construction features
Refrigerant circuit: optimised to keep the refrigerant charge to a
minimum.
Compressor: hermetic, rotary Scroll compressor, complete with
thermal protection .
Evaporating coil with copper pipes and pre-painted aluminium
fins: ensures durability even in aggressive environments like the
swimming-pool.
Condensing coil: with copper pipes and aluminium fins. Anticorrosion treatments are available for applications in saline air environments (coastal areas) or environments with chemically aggressive air.
Partial or total condensation heat recovery: thermally insulated,
with brazed plates and made of materials suitable for the treatment of
pool water. The water circuit is complete with water flow differential
pressure switch.
G3 grade air filter: it is installed inside the machine and protects the
unit from dirt thus improving the quality of re-circulation air.
Condensation drain pan: in stainless steel.
Pressure gauge: refrigerant circuit high and low pressure gauges.
Fans: Centrifugal fans with adjustable belt and pulley transmission. The
treated air outlet is vertical: horizontal air outlet is also available.
Available external head pressure is equal to 150 Pa (100 Pa with
additional hot water coil).
Power supply: main 400V three-phase 50 Hz.
Structure: the frame is made of highly resistant extruded aluminium
thermal block profiles with a 40x40 mm cross-section.
The panels are in double sheet steel (galvanized steel on the inside and
RAL 9002 pre-painted on the outside) which encloses a hot-injected
polyurethane insulation with an average density of 45 Kg/m3.
Concealed screws are used.
Control: microprocessor electronic control.
Models
DRESY: de-humidifier equipped with 45% water side and +55% air
side heat recovery.
DTESY: de-humidifier equipped with 100% water side heat recovery.
DAESY: de-humidifier with 100% air heat exchange.
The water-side heat recovery are available both with plate heat
exchanger in special stainless steel suitable for operation with chlorine
water and with Cupro/Nichel shell and tube heat exchanger for
operation with water treated with salt chlorination.
Versions
• For outdoor installation
• Fan horizontal outlet
Factory fitted accessories
•
•
•
•
Room thermostat.
Room humidistat.
Auxiliary electric heaters installed to assist the condenser.
Additional hot water coil with copper pipes and aluminium fins. Also
available with pre-painted aluminium fins or with copper pipes and
fins.
• Condensing coil with pre-painted aluminium fins or with copper pipes
and fins.
• 200 Pa pressure fans available both for the standard version and the
version with auxiliary water coil.
• Versions with greater head pressure available on request.
Accessories supplied loose
• Anti-vibration joint for fan oulet ducts.
ADDITIONAL MODULES:
• DAHR - Heat recovery with cross flows heat exchanger which
can be installed next to the base module.
Heat recovery: with highly efficient cross flows and acrylic prepainted aluminium fins (suitable for unclean/aggressive air). Possibility
of carrying out 100% free-cooling with the same module.
• DAFC - Free-cooling which can be installed next to the base
module.
With fresh air, discharge and re-circulation 0-100% modulating
dumpers.
Construction features
Fan: centrifugal fan with adjustable belt and pulley transmission. A
safety micro-switch is provided on the door of the fan module.
Structure: the frame is made of highly resistant extruded aluminium
thermal block profiles with a 40x40mm cross-section.
The panels are in double sheet steel (galvanized steel on the inside and
RAL 9002 pre-painted on the outside) which encloses a hot-injected
polyurethane insulation with an average density of 45 Kg/m3.
Concealed screws are used.
Dampers: motorised in alluminium.
The inlet and outlet dampers can be provided either towards the top or
the rear side.
Control: the microprocessor electronic control fully manages the unit
through energy saving logical management systems.
P. 117
l/h
kW
l/h
kW
No.
No.
Pa
m3/h
kW
kg/h
KPa
mm
mm
mm
DRESY-DAESY MODEL
❶ Dehumidification capacity
❶ Total absorbed power
➋ Dehumidification capacity
➋ Total absorbed power
Compressors/circuits
Fans
❸ Fan available head pressure
Fan nominal air flow
Standard fan motor power
Heat recovery water flow
Pressure drops
Width
Height
Depth
l/h
kW
l/h
kW
No.
No.
Pa
m3/h
kW
kg/h
KPa
mm
mm
mm
108
7,78
2,63
7,74
3,20
1/1
1
150
2.200
1 x 0,55
921,6
6,4
1.300
1.380
790
237
37,29
10,81
33,98
9,02
2/2
2
150
9.000
1 x 1,5
3.569,0
34,0
2.370
1.890
850
112
11,34
4,14
11,30
4,85
1/1
1
150
3.000
1 x 0,75
1.337,3
6,9
1.300
1.380
790
242
42,02
11,89
38,30
15,13
2/2
2
150
9.300
1 x 2,2
4.148,0
88,7
2.370
1.890
850
115
14,52
4,39
13,17
5,43
1/1
1
150
3.500
1 x 0,75
1.479,0
10,6
1.600
1.580
850
250
48,71
14,17
43,59
18,53
2/2
2
150
11.000
1x3
5.180,0
69,0
2.370
1.890
850
118
18,14
5,61
16,45
6,98
1/1
1
150
4.500
1 x 1,1
1.835,0
10,2
1.600
1.580
850
254
53,89
16,00
49,35
20,08
2/2
2
150
12.400
1 x 2,2
5.490,0
34,0
2.870
1.975
1.230
122
21,60
5,85
19,46
7,37
1/1
1
150
4.700
1 x 0,75
2.111,0
88,7
1.600
1.890
850
262
61,24
18,13
56,00
22,12
2/2
2
150
14.400
1x3
6.215,0
54,0
2.870
1.975
1.230
128
27,43
8,26
25,16
9,99
1/1
1
150
6.200
1 x 1,5
2.537,0
34,0
1.600
1.890
850
271
70,95
21,82
64,82
26,97
2/2
2
150
16.500
1x4
7.307,0
78,7
2.870
1.975
1.230
281
80,74
25,18
72,44
32,11
2/2
2
150
18.000
1 x 5,5
8.746,2
68,0
2.870
1.975
1.230
131
30,46
9,42
28,07
11,35
1/1
1
150
7.200
1 x 2,2
3.107,5
54,0
1.600
1.890
850
294
93,74
28,52
83,37
35,89
2/2
3
150
21.000
1 x 5,5
9.986,0
64,1
3.470
1.975
1.230
AVAILABLE VERSIONS
DRESY
air
DRESY+BA
Pool
water
air
Pool
water
air
boiler
DRESY+BA+DAFC
air
DRESY+BA+DAHR
Pool
water
boiler
2111
111,13
34,58
96,44
44,91
2/2
3
150
22.000
1 x 5,5
11.168,5
35,2
3.970
1.975
1.230
➋ Exchanging heat only with air. Ambient air temperature: 27°C, 65% R.H.
❸ Without additional coil.
In the following conditions:
❶ Exchanging heat with air and water. Ambient air temperature: 27°C,
65% R.H. Pool inlet/outlet water temperature 26/32°C.
DAESY
136
36,19
10,51
33,04
13,10
1/1
1
150
8.200
1 x 1,5
3.731,0
78,7
2.100
1.890
850
air
Pool
water
boiler
DE-HUMIDIFIERS FOR SWIMMING-POOLS
DRESY-DAESY MODEL
❶ Dehumidification capacity
❶ Total absorbed power
➋ Dehumidification capacity
➋ Total absorbed power
Compressors/circuits
Fans
❸ Fan available head pressure
Fan nominal air flow
Standard fan motor power
Heat recovery water flow
Pressure drops
Width
Height
Depth
English edition - 1
PRODUCT
RANGE
WATER CHILLERS
HEAT PUMPS
FAN COIL UNITS
AIR HANDLING
UNITS
08
RHOSS S.P.A.
Via Oltre Ferrovia, 32 - 33033 Codroipo (UD) - Italy
tel. +39 0432 911611 - fax +39 0432 911600
rhoss@rhoss.it - www.rhoss.it - www.rhoss.com
IR GROUP S.A.S.
7 rue du Pont à Lunettes - 69390 Vourles - France
tél. +33 (0)4 72318631 - fax +33 (0)4 72318632
irsaprhoss@irgroup.fr
RHOSS Deutschland GmbH
Hölzlestraße 23, D-72336 Balingen, OT Engstlatt - Germany
tel. +49 (0)7433 260270 - fax +49 (0)7433 2602720
info@rhoss.de - www.rhoss.de
RHOSS MERCOSUR
Benjamin Constant 576 - 1er Piso C.P. 1214 - Asuncion Paraguay
tel/fax +595 21 493 897 - www.rhossmercosur.com
Italy branch offices:
Area Nord-Est: 33033 Codroipo (UD) - Via Oltre Ferrovia, 32
tel. +39 0432 911611 - fax +39 0432 911600
Area Nord-Ovest: 20041 Agrate Brianza (MI)
Centro Colleoni - Palazzo Taurus, 1
tel. +39 039 6898394 - fax +39 039 6898395
Area Centro-Sud: 00199 Roma - Viale Somalia, 148
tel. +39 06 8600699-707 - fax +39 06 8600747
Area Sud: 80143 Napoli - Via G. Porzio - Centro Direzionale - Isola G8
tel. +39 081 7879121 - fax +39 081 7879135
RHOSS S.P.A. declines all responsabilities for possible mistakes in the catalogue and reserves the right to
alter the features of their products without notice in the
interests of continuous improvement.
K10021EN Ed.1 / 2008
02.08 - 6.000 - Printing: gfp.it
Download PDF
Similar pages