air to water air to water installation &

SYSTEMES
SYSTEMS
INSTALLATION & INSTRUCTION
MANUAL
AIR TO WATER
HEAT PUMP
Notice
1.1 In order to use this product better and safer, please read this instruction
care full y befor e insta ll and operate it. Please pay attention to all the notice in
operation and maintenance. Save all manuals and doc umen tati on for f utur e
reference.
1.2 Air to water pump is a special appliance. Improper installation will cause
damage and danger. It should be installed and maintained by the professionals.
Please conta ct our authorized loca l service point for installation and maintenance.
Please read and follow this instruction carefully before and during ins tallati on.
Remarks:
We will not bear the responsibility for any personal injury or unit damage caused
by non-Compliance of the regulations and instruction in this manual.
1.3 Please check whether the distribution power capacity, switch and socket
are compliance with the requirements of our unit power. Details please refer
to the rating label or parameter table in this manual.
1.4 The power should be equipped with leakage protection separately.
Power cable should be chosen in accordance with the operation
requirements of the unit.
1.5 The unit must be grounded safely. Do not use the unit if grounded unsafely.
Do not connect the ground line to the neutral and or tap water pipe.
1.6 The wire must be joined in compliance with the requirements of the wiring chart.
Do not alternate and or repair the unit personally.
1.7 Do not install the unit closed to inflammable, explosive and naked light spot.
1.8 To ensure the unit operate properly, please equipped with a filter in the water
input when installation.
Contents
I.Specification.................................................................. 1
1. Model Nomenclature ............................................................. 1
2. Parameter of air to water heat pump....................................... 1
3. Product appearance and installation dimension...................... 2
II.Installation.................................................................... 4
1. Unit installation position........................................................ 4
2. The refrigerant piping connection for split type unit................... 5
3.Water pipe connections......................................................... 7
4.Select of electrical wire......................................................... 8
5.The unit connection......... ...................................................... 8
6.Trial operation ...................................................................... 10
III.Use............................................................................. .. 11
1. Function diagram of the remote controller............................... 11
2. Use of remote controller........................................................ 11
3. Operation parameter setting...................................................16
IV.Installations sketch.................................................... .. 18
1. The installation way for domestic hot water model.................... 18
2. The installation way for single room(Parameter 18 for 1) ......... 18
3. The installation way for single room(Parameter 18 for 0).......... 19
4. The installation way for many room(Parameter 18 for 1) ......... 20
5. The installation way for many room(Parameter 18 for 0)......... 21
6. The installation way for multi-function (Parameter 18 for 0)..... 22
7. The installation way for multi-function (Parameter 18 for 1) ..... 23
V. Maintenance and repair............................................. ... 24
1. Malfunction Indicating Table................................................. 24
2.Judgement and solution of malfunctions................................. 25
VI.Wiring diagram ............................................................ 26
1. Mk3068PCB input and output port definition......................... 26
2.The electrical box of internal structure .................................... 27
3.Wiring diagram...................................................................... 28
VII.Performance curves.................................................... 30
VIII.Appendix.................................................................... 36
I. Specification
1. Model Nomenclature
MA CHR W S
WA /PS(B 01 D)
Source medium
MA: Air source
MW: Ground source
D:With electrical heating
(Without electrical heating omitted)
01:One plate heat exchanger
02:Two plate heat exchangers
B: Inverter
E: EVI
(Without inverter or EVI omitted)
S:3phase (single phase omitted)
P:With built in pump
(Without built in pump omitted)
Function of the unit
C: Air cooling
R: Air heating
CH: Air cooling and hot water
CR: Air cooling and heating
CHR: Air (heating+cooling) and hot water
Energy exchange medium
A: Refrigerant
W: Water
S:with solar
(Without solar omitted)
A: Horizontal fan direction
B: Upward fan direction
C:Double air duct type
(Omit the split type unit model)
The figure represents the horse power of unit
eg:010 means 1 horse power
Z: Integrated type
W: Split type(indoor unit )
Outdoor unit model nomenclature
MA FP
A (
Energy exchange medium
MA: Refrigerant
MW: Water
FP: Fan coil
)
Design alternative serial number
A: Horizontal fan direction
B: Upward fan direction
The figure represents the horse power of unit
eg:010 means 1 horse power
2.Parameter of air to water heat pump
Indoor Unit Model
MACHRWS
020W(01D)
040W(01D)
060W(01D)
MAFP
020A
040A
060A
kW
5.0
12.5
18.0
BTU/h
17100
42700
61400
Rated Input Power
kW
1.55
4.15
6.0
Rated Input Current
A
7.0
19.0
27.5
Outdoor Unit Model
Rated Cooling Capacity
kW
6.5
14.0
20
BTU/h
22200
47800
68400
Rated Input Power
kW
1.75
4.65
6.5
Rated Input Current
A
8.0
21.5
31.0
Auxiliary electric heater power
kW
7.5
7.5
7.5
Auxiliary electric heater current
A
36
36
36
Rated Heating Capacity
Power Supply
Noise
(208~230)VAC/1PH/60Hz
V/PH/Hz
50
54
54
Rotary
Scroll
Scroll
Compressor Qty
1
1
1
Fan Qty
1
1
2
dB(A)
Compressor
Refrigerant Liquid Pipe
inch
1/4
12
12
34
Refrigerant Gas Pipe
inch
1/2
34
Water Outlet/Water Inlet
inch
1
1
1
Water Flow Volume
m /h
3
1.12
2.41
3.44
R410A
Refrigerant Gas Type
1
Indoor Unit Net Dimensions(L/M/H
mm
560/380/740
Indoor Unit Shipping Dimensions L/M/H
mm
665/480/770
Outdoor Unit Net Dimensions(L/M/H
mm
840/355/610
Outdoor Unit Shipping Dimensions L/M/H
mm
980/410/665
Indoor Unit Net Weight
kg
52
Indoor Unit Shipping Weight
kg
57
Outdoor Unit Net Weight
kg
32
Outdoor Unit Shipping Weight
kg
37
675/600/760
675/600/760
730/650/810
730/650/810
Note:
Auxiliary electric heater is optional.
Note:
(1)The manual is a technical parameters
880/420/800 930/450/1270 measured in the following conditions:
1020/450/830 1080/480/1310 outdoor dry temperature is 44.6 and
wet bulb temperature is 43 ,the
110
145
temperature of water inflow is 104
125
160
and of water outflow is 113 .
60
80
(2)Using in ambient temperature:
65
85
5
113
.
AIR TO WATER HEAT PUMP
3. Product appearance and installation dimension
3.1 Dimension of indoor unit
Units: inch
MODEL
MACHRWS020W(01D)
A
F
I
H
G
C
Size
B
J
E
K
L
M
N
O
D
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
23,58
17,32
28,85
14,17
15,94
4,40
26,02
3,62
5,83
1
1/4
1/2
1
Water outlet
High pressure gauge
Low pressure gauge
Check valve(to liquid)
Check valve(to gas)
Water inlet
Note :Electrical box near the side.
F
G
H
C
Units: inch
A
B
I
J
E
D
K
L
M
N
MODEL
MACHRWS040W(01D)
MACHRWS060W(01D)
Size
A
B
C
D
E
F
G
H
I
J
K
L
M
N
23,62
26,38
29,92
15,35
25,00
5,47
24,29
27,60
1/2
3/4
1
1
Check valve(to liquid)
Check valve(to gas)
Water outlet
High pressure gauge
Low pressure gauge
Water inlet
Note :Electrical box near the side.
AIR TO WATER HEAT PUMP
2
3.2 Dimension of outdoor unit
Units: inch
MODEL
MAFP020A
Size
A
B
C
D
E
F
D
B
C
A
E
F
33,07
24,02
11,81
19,68
1/2
1/4
Check valve(to liquid)
Check valve(to gas)
Units: inch
MODEL
MAFP040A
Size
B
D
C
A
E
F
A
B
C
D
E
F
34,64
31,50
15,35
24,01
3/4
1/2
Check valve(to gas)
Check valve(to liquid)
Units: inch
MODEL
MAFP060A
Size
B
D
C
A
3
E
F
A
B
C
D
E
F
36,61
50,00
16,54
23,03
3/4
1/2
Check valve(to gas)
Check valve(to liquid)
AIR TO WATER HEAT PUMP
II. Installation
1. Unit installation position
The pretty high condensation temperature (cooling) and pretty low evaporation temperature(heating)
will affect the operation of outdoor unit. To achieve maximum efficiency, please select the installation
position under below regulations: To avoid ventilation short, the outdoor unit discharged air should not
return when installation. Please keep enough space around the outdoor unit for repair. Right and wrong
means as below:
Wrong
Right
As the upwards fan
direction unit
exhausts air
upwards, do not
place any object up
the unit.
Please built an
introductory
equipment if cantu
avoid this object.
Notice:
1. To get enough air for ventilation of the unit, the installation position should be with good ventilation.
2. The installation position can hold the outdoor unit without noise and shake.
3. No sunlight to the unit. Set an awning if necessary.
4. The water from rain and defrosting can be discharged in the installation position.
5. The unit will not be covered by snow in the installation position.
6. The discharged air will not face strong air in the installation position.
7. Assure the noise caused by the unit ventilation and operation will not affect the neighbor.
8. The installation position will not be affected by garbage, oil and mist.
9. The outdoor unit will be damaged under the condition with oil(engine oil), salt(sea area) and
sulfide air(near thermal spring and refining factory).
AIR TO WATER HEAT PUMP
4
2. The refrigerant piping connection for split type unit
2.1 Each component's names and function of refrigerant stop valve
Adapter connector
The connecting pipe joint of indoor unit and
outdoor unit .
Indoor unit and outdoor unit
copper connecting pipe
Adapter connector
Adapter connector nut
Needle valve
To discharge the air in the connecting pipe
and outdoor unit by refrigerant pressure or
connect a vacuum pump.
valve plug
valve plug nut
Needle valve
Valve plug
Turn on or turn off the stop valves.
Needle valve nut
Stop Valves
2.2 The unit refrigerant pipe connecting
A: According to the indoor and outdoor unit fixed
location and location of holes through the wall,
choose a good direction lead to pipe. Then begin
the indoor pipe connection work.
B: Use a wrench to remove the adapter
connector nut;
C: As shown on the right, press the trumpet on the
connector cone, then hold the connection pipe
with one hand, so that keep the connector axis
in the first line, the other hand the gradually
screw the flare nut on the connector, then
tighten with wrench.
Connecting pipe
Copper pipe
Copper pipe
Flare nut
Adapter
connector
High pressure valve
Low pressure valve
2.3 Air discharge ( by indoor unit refrigerant)
If the system is small, use refrigerant empty way to discharge the pipe and outdoor unit air, to discharge the
air in the connecting pipe and outdoor unit, when there's refrigerant in the pipes originally, just open the
low pressure side needle valve of indoor unit to discharge the air by refrigerant pressure.
As the following steps:
A: Unscrew the valve plug nut on the stop valve , and unscrew the needle nut on the indoor unit low
pressure side.
B: Open the stop valve at outdoor unit high/low pressure side by valve plug.
C: Open the stop valve at indoor unit's high pressure side by valve plug,
Note: don't open the one at low pressure side.
D: Open the needle valve by small screwdriver , and this outlet will discharge the air in connecting
pipe and outdoor unit at the same time.
E: Close the needle valve after open it about 10-20 seconds ,The time is according to the size of
outdoor unit and the length of the connecting pipe.
F: After the air discharging, open the stop valve at the indoor unit low pressure side
G: Screw and close the screw cap on the stop valve
5
AIR TO WATER HEAT PUMP
As the picture show
Steam pipe
Liquid pipe
1
Low pressure
side
Low pressure
side
High pressure
side
valve plug
Needle valve
2
NOTE
NOTE
1
2
valve plug
Needle valve
valve plug nut
valve plug
Needle valve
Indoor unit
High pressure
side
valve plug
Needle valve
valve plug nut
Outdoor unit
: The direction of the arrow is the air discharging flow direction which is same as the refrigerant flow direction.
: The air is discharged from this outlet
2.4 Air discharge ( by vacuum pump)
If the system large or after maintenance of outdoor system, should use the vacuum pump discharge way
to empty the air and water within the system.
As the following steps:
A: As the picture show, connect the vacuum pump
with the pressure gauge, and then connect the
Outdoor unit
vacuumed connecting pipe with the needle valve
on the indoor unit low pressure side.
B: Unscrew the valve plug nut on the stop valve ,
Low pressure side
High pressure side
and unscrew the needle nut on the indoor unit
Stop valve
low pressure side.
C: Open the stop valve at outdoor unit high/low
pressure side by valve plug.
Hose
Note: Do not open the indoor unit high/low
Stop valve
pressure side stop valve.
D: Open the compound pressure gauge and vacuum
pump to vacuum the outdoor unit and pipe, so that
Vacuum pump
Composite table
the absolute pressure not higher than 130Pa, and
keep the pressure does not rise within 5 minutes
Indoor unit
after vacuum.
E: After the air discharging(vacuumming),disconnect
the connecting between the pressure gauge and
indoor unit stop valve .
F: Open the stop valve at indoor unit high/low pressure
side by valve plug, then let the indoor unit's refrigerant
flow in outdoor unit(if need to add more refrigerant, please refer to 2.4).
AIR TO WATER HEAT PUMP
6
2.5 Add refrigerant
When the pipe is too long, please add
additional refrigerant as following formula:
Additional refrigerant amount=
(one-way tube length -5) x (0.015~0.02) kg,
choose 0.015 or 0.02 according to the size
of diameter.
When the tracheal diameter = 12.7,
choose 0.015;
when the diameter = 15.88, choose 0.02 .
The methods to add refrigerant
refer to the right diagram :
Outdoor unit
High pressure
side
Low pressure side
Stop valve
Hose
Stop valve
Refrigerant
charge tank
Scale
Composite table
Indoor unit
2.6 Leak check
After discharge the air, use electronic leak detector or soapy water to test all the
connectors in theindoor and outdoor unit.
3. Water pipe connections
3.1 Pipe should be a kind of pipe that heat-resistant,rust-proof, uneasy-fouling.and in conformity
wit h national health and safety standards, which can be stainless steel pipe, copper pipe, aluminum
water pipe, hot water PPR pipes and so on.
3.2 Water tank outlet pipe and overflow pipe is better to installed around the gutter or sewer,
so that to convenient to drainage.
3.3 The connection of the heat pump unit and water tank must be installed a stop valve or
dismountable loose joint, for maintenance use.
3.4 Water pipes are arranged reasonably to minimize bending and reduce the pressure loss of water
system .
3.5 The connection of tap water pipe and water filling connection must install one-way valve, filter,
supply water solenoid valve (for tank-type water tank) and pressure relief devices (for close-type
valve the parameter value is 0.7MPa), installed when valve body arrow is same as with the flow
direction to prevent water block. The cycle water outlet of the heat pump unit should connect to
the inlet of water tank , The cycle water inlet of the heat pump unit should connect to the outlet of
water tank, the water supply inlet of the tank should connect to the heat water supply outlet .
The entire piping system should be clean, no rust and dirt residue to prevent pipe blockage.
3.6 After the installation of the water filling pipe and cycle water pipe and hot water supply pipe ,
a ll the pipes should take the water tightness test. And ensure that the system is clean. And then
cover insulation on the pipe and valve (including the supply water pipes and valves).
3.7 Power line and signal line layout should be neat, rational, strong and weak lines separating cable
and Can not interfere with each other, without contact with the connecting pipe and valve.
3.8 After the construction of all wiring is completed, carefully check the correct order to connect the
power.
3.9 Unit electric wire connection: connect to the appropriate terminals according to wiring diagram,
and fix it by the pressure line of board in the electrical box.
3.10 All the wiring construction is completed, can be plugged in only after careful examination correctly.
3.11 Unit control board fuse parameters: 5A/220V.
3.12 The unit wire controller must be fixed in the bottom of standard electrical switch box.
7
AIR TO WATER HEAT PUMP
4. Selection of Electrical Wire
4.1 Voltage drop may occur due to the large current draw during compressor starting, and may be result in the
compressor is difficult to stat. So we recommend selecting the wire specification from the table below.
4.2 Specification Table of Electrical Wire
Air to water heat pump
Model
Wire
Circuit
breaker
Voltage
020
12 AWG 3
wire+gnd
20 AMP
208-240/1ph
040
10 AWG 3
wire+gnd
30 AMP
208-240/1ph
060
8 AWG 3
wire+gnd
50 AMP
208-240/1ph
7.5kw Aux.
8 AWG 2
Electric
wire+gnd
heater
50 AMP
208-240/1ph
4.3 Caution of Ground The internal motor protector does not protect the compressor against all
possible conditions Please be sure that the system utilizes the ground connection when installed
in the field.
4.4 Warning: To avoid fire, electric shock and other accidents, keep in mind about these tips:
A: Only use power supply voltage indicated on the label, if you do not know the family of voltage,
contact the dealer or local power company.
B: When you use the unit by the maximum current please view the specifications, so make sure
our home's power supply (current, voltage and cable) to meet the machine's normal load
requirements.
C: To protect the power lines. Power lines should be fixed, so that people will not be trip over or
the lines damaged by other things. Paying particular attention to plugs, which should be easily
plug into the socket, careful the plug position.
D: Do not overload wall plugs or extension the cable. Line overload can cause fire or electric shock.
E: To ensure your safety, you must plug the power lines into the socket with a grounded three-phase,
and check to ensure your socket is accurate and reliable grounding.
5. The unit connection
5.1 The layout of the electrical components of the unit model 040 and 060 are the same,except that
020 are different.
L1
L1
L2
L1
L2
L1
N
L1
N
L1
N
L1
L2
N
L1
L2
L1
L2
AIR TO WATER HEAT PUMP
L2
L1
L2
L1
L2
L2
L1
Terminal layout of 020
L1
L2
N
L1
N
L1
N
L1
N
Terminal layout of 040 and 060
8
5.2 Unit power supply
L1
N
L1
L2
L1
N
L2
L1
L2
L1
L2
N
L1
N
L1
N
L1
N
L1
L2
N
L1
N
L1
N
L1
N
5.3 Hot water cycle pump connection
5.4 Auxiliary electric heater connection
Power supply of auxiliary electrical heating power supply must be separated from power supply of the
unit, you need to connect the auxiliary electric heater input and output.
The output you can connect the signal of the auxiliary heating.
L1
N
L1
L2
L1
N
L2
Input
port
L1
L2
Output
port
Input
port
Output
port
5.5 Between outdoor unit and indoor unit connection
Outdoor unit electric box
Outdoor fan
L1 L2
power output
L1
L2
Electric three way
valve power output
L1
L2
L1
L2
Outdoor unit
Indoor unit electric box
PCB
Indoor unit
Coil temp
Ambient temp
020 refrigerant pipe
liquid: 1 / 4 inch
Steam: 1 / 2 inch
9
Coil temp
Ambient temp
040 and 060 refrigerant pipe
liquid: 1 / 2 inch
Steam: 3 / 4 inch
AIR TO WATER HEAT PUMP
6.Trial operation(should be operated by professionals)
5.1 Check before trial operation
A: Check the pipe system. Check the whole pipe system. Ensure the water volume in the system is
full and the air is exhausted complet ely. Check whether the valve is open throughout the system
and the thermal insulating of the pipe is well.
B: Check the power supply and distribution system. Check whether the power supply voltage is
normal, the power distribution accessory screws all tighten, supply power is in compliance with
the wiring diagram and the wire is grounded well.
C: Check the air cooled water chiller. Check whether any screw loose. Check the signal indicator
light (green) of the outdoor unit control panel is illuminated normally and the fault indicating
lamp(red) is illuminated. Connect the pressure gauge to the freon feed mouth for checking the
pressure during operation. Disconnect them after test is ok.
5.2 Trial operation
A: Press on/off in the remote controller turn on the hot water circulating pump whether the
water pump operates normally. Observe and determine whether air pipe is exhausted completely,
flow switch is closed, hydraulic pressure indicated in the pressure gauge is more than 0.2MPa.
Come to next step after confirm the circulating water system works normally.
B: Press on/off in the remote controller, the water pump and fan start immediately.
The compressor start after the unit operates for some time. Observe and determine if there's
any abnormal soun d during operatio n. Stop to check the unit if there's abnormal sound. The unit
can continue to run only when there's no abnormal sound. Check whether the cooling system
pressure is normal at the same time.
C: Check whether the input power and current of the unit are compliance with the parameter in this
Instruction. If not, stop to check the unit.
D: Observe whether the outlet water temperature is normal.
E: Parameter of the remote controller has been set before leave of the factory. Never alternate them
personally.
AIR TO WATER HEAT PUMP
10
III. Use
1. Function diagram of the remote controller.
The remote controller is designed and
employed standard electrical box dimensions
(86*86, fixed hole distance 60mm). The
electrical box and three core can be built
in the wall before decoration, which makes
the interior decoration more perfect.
The user interface and function shows as below:
operate mode display
Operate status,
parameter setting
display
%
%
1
2
Buttons locking icon
M
Button operate
SET
Indoor environment
temperature sensor
Open the wire controller
from this button(push it)
2. Use of remote controller
2.1 Initial power on and stand by status: Power on after check and confirm the unit is normal.
T he remote controller will be full-screen display. The main unit will be on stand by status 10 seconds
later. Distance will display the standby.
Water inlet
temperature icon
Indoor environment
temperature icon
Initialization staus
%
%
1
2
M
Hot water tank
temperature icon
SET
M
SET
2.2 Under boot-up status ,press < M >button to switch the running mode ,when the parameter 22 is set
be < 0 > to switch off the cooling function, so theunit will has 3 modes at that time :
1. air heating mode
2. domestic hot water mode
11
SET
Air heating and domestic
hot water mode
Domestic hot
water mode
Air heating mode
M
3. Air heating and domestic hot water mode
M
SET
M
SET
AIR TO WATER HEAT PUMP
2.3 When the parameter 22 is setbe < 1 >(that means switch on the cooling function),
t her e wil l be more the following 2 modes, andyou also can press <M > to switch the modes.
Cooling and domestic
hot water mode
Cooling mode
M
SET
M
SET
2.5 Clock setting. Press button SET , the place of hour keeps flicking, press
to
adjust the setting of hour . Then press button SET and the place of minute will keep flicking .
Press the button
to adjust the setting of minute. Press button SET again to
complete and exit the time setting mode.
2.6 Timed ON/OFF setting. Press
botton, and the of place hour and < 1 > Timing ON symbol
keep flicking. Press
to adjust the setting of the hour. Press
button again,
and the bit minute flicks. Press
buttons to adjust the setting of minute; Press
button again and the place of hour and timing OFF symbol flicks. Press
to adjust
the setting of hour. Press
button again, and the bit minute flickers. Press
buttons to adjust the setting of minute. Press
botton, and the of place hour and < 2 >
Timing ON symbol keep flicking. Press
to adjust the setting of the hour. Press
button again, and the bit minute flicks. Press
buttons to adjust the setting of minute;
Press
button again and the place of hour and timing OFF symbol flicks. Press
t o adjus t the sett ing of hou r. Press
button again, and the bit minute flickers. Press
buttons to adjust the setting of minute. Press
button again to complete and exit the timed
ON/OFF setting mode. Cancel timing setting operation. Press
button and press SET
button to cancel the timing
Note:
A: The Timing function only can be used under the parameter 26 is set be < 1 > ,otherwise, there's
no the timing function.
B: Keyboard locking / unlocking operation
In non-parameter setting mode, press and hold down
and
buttons for 10 seconds,
and the system will lock the keyboard automatically and the wire controller will display
icon.
Press and hold down
and
buttons for 10 seconds again, the keyboard will be unlocked,
and the icon of
will disappear .
C: In the working state, press the
buttons can set up the user common use setting
SET
parameters ,press the
buttons to switch to modified parameters, press
button
to modify the parameters, press the
buttons, exit the setting interface.
D: press the
fahrenheit.
button for 5 seconds to switch the display between centigrade degree and
E: When working state and on standby, press M
button for 5 seconds for the manual operation
electric heater heating output, press the M
button for 5 seconds again, shutdown the
manual operation electric heater heating output.
Icon constantly flickering,
enter into manual electrical
heating output mode.
Icon do not twinkle, enter
into automatic electric
heat output mode.
M
AIR TO WATER HEAT PUMP
SET
12
2.7 These settings are for Engineers only, please call if you require to change any of the Optional
Parameters. Under the standby status, press SET buttons at the same time for 10 seconds
to enter Operation Parameter setting interface. Press
or
to view 01-39
SET
parameter,press
button again to set data you need. Parameter setting as below:
M
SET
Parameter 01
Domestic hot water tank
temperature setting
Alternative range:
50 to 140 .
Default: 131
M
SET
Parameter 05
Domestic hot water temp.
difference between the unit stop
heating and restart heating
Alternative range: 2 to 30 .
Default: 10
M
SET
Parameter 09
Heating defrost cycle
Alternative range:
30minutes to 90minutes.
Default: 40minutes
13
M
SET
Parameter 02
cooling inlet water
temperature setting
Alternative range:
46 to 82 .
Default: 53
M
M
SET
Parameter 03
heating inlet water
temperature setting
Alternative range:
59 to 140 .
Default: 104
SET
Parameter 06
Cooling inlet water temp.
difference between the unit stop
heating and restart heating .
Alternative range: 2 to 30 .
Default: 10
M
M
SET
Parameter 10
Enter defrost temperature
Alternative range: -22 to 32
Default: 20
M
Parameter 04
Room temperature setting
Alternative range:
50 to 113 .
Default: 77
M
SET
Parameter 07
Heating inlet water temp.
difference between the unit stop
heating and restart heating .
Alternative range: 2 to 30 .
Default: 10
M
SET
SET
Parameter 11
Exit defrost temperature.
Alternative range: 36 to 86
Default: 55
SET
Parameter 08
Room temp. difference
between the unit stop heating
and restart heating .
Alternative range: 2 to 30 .
Default: 4
M
SET
Parameter 12
Exit defrost time condition
. Alternative range:
1 minutes to 12 minutes.
Default: 8 minutes
AIR TO WATER HEAT PUMP
M
SET
Parameter 13
Whether turn on the
economy model
0: turn off,
1: turn on
Default: 0
M
SET
Parameter 17
Domestic hot water priority,
or heating and cooling priority
0: Domestic hot water priority
1 : Air heating and air cooling
priority
Default: 0
M
SET
M
SET
Parameter 14
Whether power-down memory
0:without memory function
1:with memory function
Default: 1
M
SET
Parameter 18
Hot water pump working way
1:long time working for hot
water pump,
0:hot water pump turns off after
the compressor power off for 30s
Default:0
M
SET
Parameter 21
Parameter 22
The room temp. difference setting Whether turn on air cooling
between non-sleeping status mode function model
and sleeping status mode
0: turn off
Alternative range: -30 to 30 . 1: turn on
Default: 10
Default: 0
AIR TO WATER HEAT PUMP
M
SET
Parameter 15
wire cotrol sensor or the multi
-room switch
Selection.
SET
Parameter 19
Aux.electric heater start ambient
temp.
Alternative range: -22 to 86
Default: 59
M
SET
Parameter 16
T he working methods of
manual electric heater
0 :heating
1:hot water +heating
Default: 1
1 :wire control sensor
0:multi-room switch
Default: 1
M
M
SET
Parameter 23
The start time of non-sleeping
status mode.
Default: 05:00
M
SET
Parameter 20
Aux.electric heater start delay
time
Alternative range: 0~90Min.
Default: 30Min.
M
SET
Parameter 24
The end time of non-sleeping
status mode.
Default: 23:00
14
M
SET
M
M
SET
Parameter 25
Parameter 26
The temp. difference setting
whether turn on the timing function
between solar temp. and water tank 0: Turn off
temp. for turn on the water pump
1: Turn on
Alternative range: 2 to 40
Default: 0
Default: 12
M
SET
Parameter 28
EVI valve turn on setting
(effective for EVI unit)
Alternative range: -13
to 86
Default:41
M
SET
Parameter 33
Water inlet temp.
Actual testing value:
Unit inlet water temperature
M
SET
Parameter 37
Coil temp.
Actual testing value:
pipe temperature
15
M
SET
Parameter 30
Auxiliary electric heating.
difference between the unit stop
heating and restart heating
Alternative range: 2 to 30 .
Default: 10
M
SET
Parameter 34
water outlet temp.
Actual testing value:
Unit outlet water temperature
M
SET
Parameter 38
discharge temp.
Actual testing value:
discharge temperature
SET
Parameter 27
When the unit turn on the aux.
Electric heater the hot water
cycle pump working way.
0:turn off
1:turn on
Default:1
M
SET
Parameter 31
Ambient temperature too low
protection setting
Alternative range: -22 to 50
Default: 14
M
SET
Parameter 35
Indoor environment temp.
Actual testing value:
Indoor environment
temperature
M
M
SET
Parameter 28
Compressor discharge temp.
Too high protection setting
Alternative range: 86
to 257
Default:230
M
SET
Parameter 32
Domestic hot water tank temp.
Actual testing value:
Hot water tank
temperature
M
SET
Parameter 36
Out door environment temp.
Actual testing value:
Outdoor environment
temperature
SET
Parameter 39
Solar collector temp.
Actual testing value:
AIR TO WATER HEAT PUMP
3. Operation parameter setting
The unit's operation parameter can be set on the wire controller.
Please set according to the table below.
Parameter
Setting data explanation or working state
Parameter
setting range
Default Remarks
01
Domestic hot water tank temperature setting
50
~ 140
131
Adjustable
02
Cooling inlet water temperature setting
46
~ 82
53
Adjustable
03
Heating inlet water temperature setting
59
~ 140
104
Adjustable
04
Room temperature setting
50
~ 113
77
Adjustable
Domestic hot water temp. difference between
the unit stop heating and restart heating
Cooling inlet water temp. Difference between
the unit stop cooling and restart cooling
Heating inlet water temp. difference between the
unit stop heating and restart heating .
2
~ 30
10
Adjustable
2
~ 30
10
Adjustable
2
~ 30
10
Adjustable
08
Room temp. difference between the unit stop
heating/cooling and restart heating/cooling .
2
~ 30
4
Adjustable
09
Heating defrost cycle
10
Enter defrost status coil temperature setting
-22
11
Exit defrost status coil temperature setting
36
12
Exit defrost time condition setting
13
Whether turn on the economy model
14
Whether power-down memory
15
Wire controller sensor or the" multi-room switch"
Selection.
16
The working methods of manual electric heater
17
Domestic hot water priority, or heating and
cooling priority
18
Hot water pump working way in the heating or cooling mode
1:long time working for hot water pump
0:hot water pump turns off after the compressor power off 30s
19
Auxiliary electric heater start ambient temp.
20
Auxiliary electric heater start delay time
(after press the on/off button )
21
The room temp. difference setting between
non-sleeping status mode and sleeping status mode
22
Whether turn on air cooling function model
0:turn off
1:turn on
0
Adjustable
23
The start time of non-sleeping status mode.
00 ~ 24
05
Adjustable
24
The end time of non-sleeping status mode.
00 ~ 24
23
Adjustable
25
The temp. difference setting between solar temp.
and water tank temp. for turn on the water pump
05
06
07
AIR TO WATER HEAT PUMP
40min
Adjustable
~ 32
20
Adjustable
~ 86
55
Adjustable
8min
Adjustable
0
Adjustable
1
Adjustable
1
Adjustable
1
Adjustable
0
Adjustable
1
Adjustable
59
Adjustable
30min
Adjustable
10
Adjustable
30min ~ 90min
1min ~ 12min
0:turn off
1:turn on
0:without
1:with
0:multi-room switch
1:wire control sensor
0:heating
1:hot water &heating
0:hot water
1:cooling &heating
0/1
-22
~ 86
0min ~ 90min
-30
2
~ 30
~ 40
12
Adjustable
16
Cotinued
17
0:turn
1:turn
0:turn
1:turn
off
on
off
on
26
Whether turn on the timing function
27
When the unit turn on the auxiliary electric heater
the hot water cycle pump working way.
28
Compressor discharge temp. Too high protection
setting
86
29
EVI valve turn on setting(effective for EVI unit)
-13
30
Auxiliary electric heating. difference between the
auxiliary electric stop heating and restart heating
2
31
Ambient temperature too low protection setting
-22
32
Domestic hot water tank temp.Actual testing value
Adjustable
33
Water inlet temp.Actual testing value
Actual testing
value
34
Water outlet temp.Actual testing value
Actual testing
value
35
Indoor environment temp. Actual testing value
Actual testing
value
36
Outdoor environment temp. Actual testing value
Actual testing
value
37
System coil temp. Actual testing value
Actual testing
value
38
System discharge temp. Actual testing value
Actual testing
value
39
Solar collector temp. Actual testing value
Actual testing
value
0
Adjustable
1
Adjustable
~ 257
230
Adjustable
~ 86
41
Adjustable
10
Adjustable
14
Adjustable
~ 30
~ 50
AIR TO WATER HEAT PUMP
IV.Installation sketch
1. The installation way for domestic hot water model
Unit electric box
L1
L2
L1
L2
L1
Hot water cycle
pump
(115VAC)
N
L1
Floor heating
water cycle
pump (115VAC)
N
L1
N
Single phase
Power input
(208~230VAC)
L1
L2
Aux.electric heating Aux.electric heating
Power input
Power output
(208~230VAC)
(208~230VAC)
L1
N
L2
L1
Hot water Solar collector
tank temp.
temp.
PCB
L2
01 02 03
1
7
29 30
Electric three-way Solar cycle
Outdoor fan
pump
(208~230VAC) valve
(115VAC)
(208~230VAC)
4
3
B
A
Wire controller
Cold water inlet
B
9
8
5
7
4
A
water inlet
water inlet
1
2
3
6
Legend:
Globe valves
Check valve
Water temp. sensor
Expansion Tank
A
B
1
Shower head
Water cycle pump
Hot water tank temp.
Solar collector temp.
Outdoor unit
AIR TO WATER HEAT PUMP
2
Indoor unit
6
Hot water tank
3
Hot water pump
7
Solar water pump
4
Three way valve
8
Solar
5
Backup boiler
9
Bath room
18
2 . The installation way for single room(air heating/air cooling/floor heating )
Parameter 18 for 1.
L1
L2
L1
L2
L1
N
Hot water cycle
pump
(115VAC)
L1
Floor heating
water cycle
pump (115VAC)
N
L1
N
Single phase
Power input
(208~230VAC)
L1
L2
N
Unit electric box
Aux.electric heating Aux.electric heating
Power input
Power output
(208~230VAC)
(208~230VAC)
L1
L2
L1
PCB
L2
01 02 03
1
3
29 30
Electric three-way Solar cycle
Outdoor fan
pump
(208~230VAC) valve
(115VAC)
(208~230VAC)
4
5
9
7
4
1
2
3
8
6
10
Legend:
Expansion Tank
4
Three way valve
8
Floor heating
1
Outdoor unit
5
Backup boiler
9
2
Indoor unit
6
Buffer tank
Wire controller
Room
7
Fan coil
Globe valves
Check valve
Water cycle pump
Electric three way valve
3
Hot water pump
10
3 . The installation way for single room(air heating/air cooling/floor heating )
Parameter 18 for 0.
L1
L2
L1
L2
L1
N
Hot water cycle
pump
(115VAC)
L1
Floor heating
water cycle
pump (115VAC)
N
L1
N
Single phase
Power input
(208~230VAC)
L1
L2
N
Unit electric box
Aux.electric heating Aux.electric heating
Power input
Power output
(208~230VAC)
(208~230VAC)
L1
L2
L1
PCB
L2
01 02 03
1
3
7
29 30
Electric three-way Solar cycle
Outdoor fan
pump
(208~230VAC) valve
(115VAC)
(208~230VAC)
4
5
8
7
4
10
1
2
3
9
6
11
Legend:
19
Globe valves
Check valve
Water cycle pump
Expansion Tank
4
Three way valve
8
Fan coil
1
Outdoor unit
5
Backup boiler
9
Floor heating
2
Indoor unit
6
Buffer tank
10
Electric three way valve
3
7
Air condition pump
11
Hot water pump
Wire controller
Room
AIR TO WATER HEAT PUMP