db en psi-rep-profibus/12mb - Phoenix Contact by Protocol Power

PSI-REP-PROFIBUS/12MB
Repeater for PROFIBUS systems up to 12 Mbps
Data sheet
102986_en_08
1
© PHOENIX CONTACT 2017-05-22
Description
The PSI-REP-PROFIBUS/12MB modular PROFIBUS
repeater is designed to meet the high requirements of highperformance PROFIBUS systems. The device is snapped
onto standard DIN rails in the control cabinet and supplied
with 24 V DC.
Possible applications:
– Electrical isolation and bus segmentation
– Increasing system availability
– Increasing the range
– Increasing the transmission speed
– Extending the number of devices to n x 32
– Creation of mixed and network structures
– Modular PROFIBUS hubs
Features
–
–
–
–
–
–
–
–
–
Automatic data rate detection or fixed data rate setting
via DIP switches
Data rates of up to 12 Mbps
High-quality 4-way isolation between all interfaces
Automatic transmit/receive changeover
Bit retiming for unrestricted cascading of devices
Bit oversampling for reliable detection of sporadic
disturbances
Filtering of faulty telegrams based on start delimiter
detection
Integrated surge protection with transient discharge to
the DIN rail
Can be combined with PSI-MOS FO converters in a
modular way using DIN rail connectors
WARNING: Explosion hazard when used in potentially explosive areas
The device is a category 3 item of electrical equipment. Follow the instructions provided here during
installation and observe the safety notes.
Make sure you always use the latest documentation.
It can be downloaded from the product at phoenixcontact.net/products.
PSI-REP-PROFIBUS/12MB
2
Table of contents
1
Description .............................................................................................................................. 1
2
Table of contents ..................................................................................................................... 2
3
Ordering data .......................................................................................................................... 3
4
Technical data ......................................................................................................................... 5
5
Safety regulations and installation notes.................................................................................. 8
5.1
Installation and operation ....................................................................................................... 8
5.2
Installation in Zone 2............................................................................................................. 8
5.3
UL Notes ........................................................................................................................... 9
6
Application examples ............................................................................................................ 10
6.1
Bit retiming ....................................................................................................................... 11
6.2
Bit oversampling ................................................................................................................ 11
7
Product description................................................................................................................ 12
7.1
Dimensions ...................................................................................................................... 12
7.2
Block diagram ................................................................................................................... 12
7.3
Function elements ............................................................................................................. 13
8
Configuration via DIP switches .............................................................................................. 14
8.1
Set the data rate (DIP switches 1 - 4) ...................................................................................... 14
8.2
Set the operating mode (DIP switch 5) .................................................................................... 14
9
Cable configuration................................................................................................................ 15
9.1
Configuring the network parameters in STEP 7 ......................................................................... 15
10
Assembly............................................................................................................................... 17
10.1 Mounting on a DIN rail ........................................................................................................ 17
10.2 Combined assembly ........................................................................................................... 17
10.3 Removal .......................................................................................................................... 17
11
Supply voltage ....................................................................................................................... 18
11.1 Operation as a single device................................................................................................. 18
11.2 Operation in a topology ....................................................................................................... 18
12
Connecting data cables ......................................................................................................... 19
13
Switching output .................................................................................................................... 19
102986_en_08
PHOENIX CONTACT 2 / 19
PSI-REP-PROFIBUS/12MB
3
Ordering data
Description
Type
Order No.
Pcs./Pkt.
Modular repeater for electrical isolation and range
increase for PROFIBUS up to 12 Mbps, 4-way isolation,
rail-mountable, supply 24 V DC
PSI-REP-PROFIBUS/12MB
2708863
1
Accessories
Type
Order No.
Pcs./Pkt.
PROFIBUS cable, Fast Connect type, up to 12 Mbps
PSM-CABLE-PROFIB/FC
(02YSY (ST)CY 1x2x22 AWG) by the meter, Bus system
cable, PROFIBUS (12 Mbps), shielded, PVC FR VI/PVC,
violet, 2-wire (1X2XAWG22/1), color, single wire: Red,
green, cable length: Free entry (1.0 ... 1000.0 m)
2744652
1
Primary-switched MINI POWER supply for DIN rail
mounting, input: 1-phase, output: 24 V DC/1.5 A
2866983
1
MINI-SYS-PS-100-240AC/
24DC/1.5
DIN rail connector for DIN rail mounting. Universal for
ME 17,5 TBUS 1,5/ 5-ST-3,81 2709561
TBUS housing. Gold-plated contacts, 5-pos. Header,
GN
nominal current: 8 A, number of positions: 5, pitch: 3.81 mm,
Articles with gold-plated contacts, bus connectors for
connecting with electronic housings
10
Active termination resistor for PROFIBUS and RS-485 bus PSI-TERMINATOR-PB-TBUS 2702636
systems, redundant power supply, routing of the supply
voltage via DIN rail connector, electrical isolation,
switchable termination, integrated programming interface
1
D-SUB connector, 9-pos., male connector, cable entry
SUBCON-PLUS-PROFIB/90/
< 90°, bus system: PROFIBUS DP up to 12 Mbps with
PG/SC
PG D-SUB socket for connecting a programming device,
termination resistor can be switched on via slide switch,
pin assignment: 3, 5, 6, 8;
screw connection terminal blocks
2313708
1
D-SUB connector, 9-pos., male connector, cable entry
SUBCON-PLUS-PROFIB/PG/ 2708245
< 35°, bus system: PROFIBUS DP up to 12 Mbps with
SC2
PG D-SUB socket for connecting a programming device,
termination resistor can be switched on via slide switch,
pin assignment: 3, 5, 6, 8;
screw connection terminal blocks
1
D-SUB connector, 9-pos., male connector, cable entry
SUBCON-PLUS-PROFIB/90/
< 90°, bus system: PROFIBUS DP up to 12 Mbps with
PG/IDC
PG D-SUB socket for connecting a programming device,
termination resistor can be switched on via slide switch,
pin assignment: 3, 5, 6, 8; IDC terminal block connection
2313685
1
SUBCON-PLUS-PROFIB/AX/ 2902321
M12
1
D-SUB plug, 9-pos., pin, assignment: 3, 5, 6, 8;
two M12 cable glands (B-coded) under 180° (axial).
Bus system: PROFIBUS DP up to 12 Mbps.
Termination resistor via separate M12 terminator
102986_en_08
PHOENIX CONTACT 3 / 19
PSI-REP-PROFIBUS/12MB
Accessories
Type
Order No.
Pcs./Pkt.
D-SUB plug, 9-pos., pin, assignment: 3, 5, 6, 8;
two M12 cable glands (B-coded) under 90°.
Bus system: PROFIBUS DP up to 12 Mbps.
Termination resistor via separate M12 terminator.
Long version; S7-compatible.
SUBCON-PLUS-PROFIB/
90X/M12
2902729
1
D-SUB plug, 9-pos., pin, assignment: 3, 5, 6, 8;
two M12 cable glands (B-coded) under 90°.
Bus system: PROFIBUS DP up to 12 Mbps.
Termination resistor via separate M12 terminator.
SUBCON-PLUS-PROFIB/90/
M12
2902318
1
D-SUB plug, 9-pos., pin, assignment: 3, 5, 6, 8;
two M12 cable glands (B-coded) under 35°.
Bus system: PROFIBUS DP up to 12 Mbps.
Termination resistor via separate M12 terminator.
SUBCON-PLUS-PROFIB/35/
M12
2902320
1
FO converter with integrated optical diagnostics,
alarm contact, for PROFIBUS up to 12 Mbps,
T-coupler with two FO interfaces (FSMA), 660 nm,
for polymer/PCF fiber cable
PSI-MOS-PROFIB/FO 660 T
2708287
1
FO converter with integrated optical diagnostics,
alarm contact, for PROFIBUS up to 12 Mbps,
terminal device with one FO interface (FSMA), 660 nm,
for polymer/PCF fiber cable
PSI-MOS-PROFIB/FO 660 E
2708290
1
FO converter with integrated optical diagnostics,
alarm contact, for PROFIBUS up to 12 Mbps,
T-coupler with two FO interfaces (BFOC), 850 nm,
for PCF/fiberglass cable (multimode)
PSI-MOS-PROFIB/FO 850 T
2708261
1
FO converter with integrated optical diagnostics,
alarm contact, for PROFIBUS up to 12 Mbps,
terminal device with one FO interface (BFOC), 850 nm,
for PCF/fiberglass cable (multimode)
PSI-MOS-PROFIB/FO 850 E
2708274
1
Fiber optic converter with integrated optical diagnostics,
alarm contact, for PROFIBUS up to 12 Mbps,
T-coupler with two fiber optic interfaces (SC-Duplex),
1300 nm, for fiberglass cable
PSI-MOS-PROFIB/FO1300 T
2708892
1
Fiber optic converter with integrated optical diagnostics,
alarm contact, for PROFIBUS up to 12 Mbps,
termination device with one fiber optic interface
(SC-Duplex), 1300 nm, for fiberglass cable
PSI-MOS-PROFIB/FO1300 E 2708559
1
Industrial PROFIBUS extender, for point-to-point
PSI-MODEM-SHDSL/PB
connections, linear structures, and mixed operation with
repeaters and fiber optic converters. Distances of up to
20 km, PROFIBUS data rates of up to 1.5 Mbps via simple
copper wires, such as in-house phone lines.
102986_en_08
2313656
1
PHOENIX CONTACT 4 / 19
PSI-REP-PROFIBUS/12MB
4
Technical data
Supply
Supply voltage range
18 V DC ... 30 V DC
(via pluggable COMBICON screw terminal block)
Nominal supply voltage
24 V DC (With UL approval)
Typical current consumption
< 90 mA (24 V DC )
Electrical isolation
VCC // TBUS // PROFIBUS (A) // PROFIBUS (B)
Test voltage data interface/power supply
1.5 kVrms (50 Hz, 1 min.)
Torque
0.6 Nm ... 0.8 Nm
PROFIBUS acc. to IEC 61158, RS-485 2-conductor
Transmission channels
2 (1/1), TD, RD, half duplex
Operating mode
Through PROFIBUS connector
Connection method
D-SUB-9 female connector
Output nominal voltage
5 V DC ±5 %
Output current
50 mA
Conductor cross section
0.2 mm² ... 2.5 mm² (24 AWG ... 14 AWG)
Data format/encoding
UART (11 Bit, NRZ)
Data direction switching
Automatic control, min. station response time 2 bits
Transmission speed
9.6/19.2/45.45/93.75/187.5/500/1500/3000/6000/12000 kbps
(can be set manually and automatically)
Transmission length
≤ 1200 m (Depends on transmission speed and cable type)
Transmission medium
2-wire twisted pair, shielded
Relay output
Number of outputs
1
Maximum switching voltage
30 V DC (1 A)
65 V DC (0.46 A)
150 V AC (0.46 A)
102986_en_08
PHOENIX CONTACT 5 / 19
PSI-REP-PROFIBUS/12MB
General data
Degree of protection
IP20
Dimensions (W/H/D)
35 mm x 99 mm x 105 mm
Housing material
PA 6.6-FR green
Free fall in acc. with IEC 60068-2-32
1m
Vibration resistance in acc. with EN 60068-2-6/
IEC 60068-2-6
5g, 10...150 Hz, 2.5 h, in XYZ direction
Shock in acc. with EN 60068-2-27/IEC 60068-2-27
15g, 11 ms period, half-sine shock pulse
MTTF (mean time to failure) SN 29500 standard,
temperature 25 °C, operating cycle 21 %
(5 days a week, 8 hours a day)
1638 Years
MTTF (mean time to failure) SN 29500 standard,
temperature 40 °C, operating cycle 34.25 %
(5 days a week, 12 hours a day)
812 Years
MTTF (mean time to failure) SN 29500 standard,
temperature 40 °C, operating cycle 100 %
(7 days a week, 24 hours a day)
340 Years
Bit distortion, input
max. ± 35 %
Bit distortion, output
< 6.25 %
Bit delay in standard operation
≤ 11 bit (Filter mode)
Bit delay
1 bit (Direct mode)
Noise emission according to
EN 55011
Noise immunity according to
EN 61000-4-2
Electromagnetic compatibility
Conformance with EMC Directive 2014/30/EU
Transmission channels
2 (1/1), TD, RD, half duplex
Ambient conditions
Ambient temperature (operation)
-20 °C ... 60 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Permissible humidity (operation)
30 % ... 95 % (non-condensing)
Altitude
≤ 5000 m (for restrictions see manufacturer's declaration)
≤ 2000 m (when used in Ex zone 2)
Approvals / Certificates
Conformance
CE-compliant
EAC
Free from substances that could impair the application of according to P-VW 3.10.7 57 65 0 VW-AUDI-Seat central
coating
standard
ATEX
Please follow the special installation instructions in the
documentation!
 II 3 G Ex nA nC IIC T4 Gc X
UL, USA/Canada
cULus listed UL 508
Class I, Zone 2, AEx nA nC IIC T6
Class I, Zone 2, Ex nA nC IIC T6 Gc X
Class I, Div. 2, Groups A, B, C, D
Standards/regulations
DIN EN 50178, DIN EN 60950
102986_en_08
PHOENIX CONTACT 6 / 19
PSI-REP-PROFIBUS/12MB
Conformance with EMC Directive 2014/30/EU
Noise immunity according to EN 61000-6-2
Electrostatic discharge
Electromagnetic HF field
Fast transients (burst)
Surge current loads (surge)
Conducted interference
EN 61000-4-2
Contact discharge
± 6 kV
Discharge in air
± 8 kV
Comments
Criterion B
EN 61000-4-3
Frequency range
80 MHz ... 3 GHz
Field intensity
10 V/m
Comments
Criterion A
EN 61000-4-4
Input
± 2 kV
Signal
± 2 kV
Comments
Criterion B
EN 61000-4-5
Input
± 0.5 kV
Signal
± 1 kV
Comments
Criterion B
EN 61000-4-6
Voltage
10 V
Comments
Criterion A
Emitted interference in acc. with EN 61000-6-4
Interference emission
Criterion A
Criterion B
EN 55011
Class A, industrial applications
Normal operating behavior within the specified limits
Temporary impairment of operating behavior that is corrected by the device itself
102986_en_08
PHOENIX CONTACT 7 / 19
PSI-REP-PROFIBUS/12MB
5
Safety regulations and installation notes
5.1
Installation and operation
5.2
WARNING: Explosion hazard when used
in potentially explosive areas
WARNING:
Observe the following safety notes when
using the repeater.
•
•
•
•
•
•
•
The category 3 device is designed for installation in
zone 2 potentially explosive areas. It meets the
requirements of EN 60079-0:2012+A11:2013 and
EN 60079-15:2010.
Installation, operation, and maintenance may only be
carried out by qualified electricians. Follow the
installation instructions as described. When installing
and operating the device, the applicable regulations
and safety directives (including national safety
directives), as well as generally approved technical
regulations, must be observed. The safety data is
provided in this package slip and on the certificates
(conformity assessment, additional approvals where
applicable).
The device must not be opened or modified. Do not
repair the device yourself, replace it with an equivalent
device. Repairs may only be carried out by the
manufacturer. The manufacturer is not liable for
damage resulting from violation.
The IP20 protection (IEC 60529/EN 60529) of the
device is intended for use in a clean and dry
environment. The device must not be subject to
mechanical strain and/or thermal loads, which exceed
the limits described.
The device is not designed for use in atmospheres with
a danger of dust explosions.
The device must be stopped and immediately removed
from the Ex area if it is damaged, was subject to an
impermissible load, stored incorrectly or if it
malfunctions.
The device is designed exclusively for SELV operation
according to IEC 60950/EN 60950/VDE 0805. The
device may only be connected to devices, which meet
the requirements of EN 60950.
102986_en_08
Installation in Zone 2
Please make sure that the following notes and
instructions are observed.
•
•
•
•
•
•
•
Observe the specified conditions for use in potentially
explosive areas.
The device should be installed so that a degree of
protection of at least IP54 is achieved in accordance
with EN 60529. To this end, a suitable, approved
housing that meets the requirements of EN 60079-15
should be used.
Only devices that are designed for operation in
Ex Zone 2 and the conditions at the installation location
may be connected to the circuits in Zone 2.
In potentially explosive areas, terminals may only be
snapped onto or off the DIN rail connector and wires
may only be connected or disconnected when the
power is switched off.
The switches of the device that can be accessed may
only be actuated when the power supply to the device is
disconnected or when it has been ensured that there is
no potentially explosive atmosphere present.
For safe operation, lockable plug connections must
have a functional interlock (e. g. locking clip, screw
connection etc.). Insert the interlock. Repair any
damaged connectors immediately.
The application height in zone 2 is limited to 2000 m
(80 kPa).
PHOENIX CONTACT 8 / 19
PSI-REP-PROFIBUS/12MB
5.3
UL Notes
PROCESS CONTROL EQUIPMENT FOR HAZARDOUS LOCATIONS 31ZN
A) This equipment is suitable for use in Class I, Zone 2, AEx nA nC IIC T6;
Class I, Zone 2, Ex nA nC IIC T6 Gc X and Class I, Division 2, Groups A, B, C, D
or non-hazardous locations only.
B) WARNING - EXPLOSION HAZARD - Substitution of components may impair suitability
for Class I, Zone 2/Division 2.
C) WARNING - EXPLOSION HAZARD - Do not disconnect equipment unless power has been
switched off or the area is known to be non-hazardous.
D) Conductor temperature rating must be 65°C or higher.
E) Product must be installed in Class I, Zone 2 certified and at least an IP54 enclosure.
F) The product has to be installed in an enclosure with tool removable cover or door.
G) Product must be used in no more than a pollution degree 2 environment as defined
by IEC 60664-1.
H) Provisions must be made to provide transient protection to the product so that voltage levels
do not exceed 40 % of the rated voltage at the power supply terminals.
I) The relay contacts are directly connected to connections 3 and 4 ()
Wire Range: 30-12 AWG
Torque: 5-7 (Lbs-Ins)
102986_en_08
24 Vdc, 90 mA
Tamb = 60°C
30-12 AWG, Copper Solid and Stranded, Field and Factory
Torque: 5-7 Lbs-Ins
PHOENIX CONTACT 9 / 19
PSI-REP-PROFIBUS/12MB
6
Application examples
Linear structure
The repeater can be used to create network structures that
are tailored to the relevant application.
The limits set by the PROFIBUS standard are therefore
extended. The standard defines the following basic
specifications:
– Up to 32 devices per potential segment
– Only line structures
– Maximum bus cable length: 1200 m
– Bus cable termination at the start and end of the bus
cable
Please note that in each potential segment,
the port of the repeater must be considered as
an electrical device.
Max. of 30 devices
= Switch on bus terminating resistor
Figure 2
Branch
PROFIBUS 12 mbps
100m
Max. of 30 devices
Line structure
Bus segmentation with repeaters makes it possible to
multiply the permissible coverage of the network and to
extend the number of devices.
The full number of devices from the PROFIBUS
specification (n x 32) applies in each potential segment.
Higher transmission speeds can also be supported by
subdividing into shorter segment lengths.
100m
Example: normally, a PROFIBUS segment with a length of
200 m could only be operated at a data rate of 1.5 Mbps. If
you use a repeater after 100 m, the possible data rate is
12 Mbps.
Max. of 31 devices
Star structure
= Switch on bus terminating resistor
Figure 1
Branch line
R R R
A segment can be created as an active branch, which can
comprise the full bus cable length and a maximum of
31 devices.
= Switch on bus termination resistor
Figure 3
102986_en_08
Star structure
PHOENIX CONTACT 10 / 19
PSI-REP-PROFIBUS/12MB
Tree structure
= Switch on bus terminating resistor
Figure 4
Tree structure
Mixed/network structures, star, and tree structures can be
created using the repeaters. The repeaters can be extended
using PSI-MOS-PROFIB/FO... fiber optic converters.
In addition, the repeaters can be combined and therefore
configured to form a modular PROFIBUS hub.
6.1
Bit retiming
PROFIBUS signals with a bit distortion of up to 35 % can be
reliably detected using the bit retiming function and are
converted to their original bit form before being transferred
to the next segment.
This data processing function means that a virtually
unlimited number of repeaters can be connected without an
impermissible level of bit distortion.
6.2
Bit oversampling
The bit oversampling function can be used to detect and
filter disturbances. This means that these disturbances are
not transferred to the next segment.
102986_en_08
PHOENIX CONTACT 11 / 19
PSI-REP-PROFIBUS/12MB
7
Product description
7.1
Dimensions
105
35
PSI-REP-PROFIB/12MB
Ord.-No. 27 08 863
99
VCC
TD
RD
ERR A
Port A
PORT B
ERR B
Figure 5
7.2
Housing dimensions
Block diagram
DC
24V (1)
DC
DC
0V (2)
DC
gn
11 (3)
Alarm
DIP switch
DIN rail connector
12 (4)
Bus
management
Port A
VP
6
GND
5
DATA (P)
3
DATA (N)
8
Port B
6 VP
5 GND
3 DATA (P)
Retiming
8 DATA (N)
Retiming
Retiming
gn
ye
24V
0V
GND D(N) D(P)
DIN rail connector
Figure 6
102986_en_08
Block diagram
PHOENIX CONTACT 12 / 19
PSI-REP-PROFIBUS/12MB
7.3
Function elements
1
2
3
Status and diagnostics indicators
LED
VCC
4
0,6 ... 0,8 Nm
5 ... 7 lb In
ON
Flashing
OFF
Meaning
Supply voltage OK
Supply voltage present but no valid
data rate detected (“Autobaud”
setting only)
No supply voltage
PSI-REP-PROFIB/12MB
Ord.-No. 27 08 863
5
7
VCC
TD
RD
9
ERR A
6
8
Port A
ERR B
PORT B
10
Figure 7
11
Function elements
1
2
3
4
5
6
24 V DC supply voltage
0 V DC supply voltage
Switch contact
Connection 11
Switch contact
Connection 12
LED VCC
Green Supply voltage
LED TD
Yellow Transmit data, Dynamic,
port A
7 LED RD
Green Receive data, Dynamic,
port A
8 D-SUB 9
PROFIBUS interface, port A
9 LED ERR A Red
Transmission error, port A
10 LED ERR B Red
Transmission error, port B
11 D-SUB 9
PROFIBUS interface, port B
The relay contacts are connected directly to connections
3 and 4.
102986_en_08
PHOENIX CONTACT 13 / 19
PSI-REP-PROFIBUS/12MB
8
Configuration via DIP switches
8.1
•
Set the data rate (DIP switches 1 - 4)
Set the transmission speed using the DIP switches.
NOTE: electrostatic discharge!
The device contains components that can be
damaged or destroyed by electrostatic
discharge. When handling the device,
observe the necessary safety precautions
against electrostatic discharge (ESD)
according to EN 61340-5-1 and
IEC 61340-5-1.
Only select the mode of operation when the
power is disconnected! The change is
activated after renewed power up.
The DIP switches for configuration are located under the
cover on the port B interface.
•
Insert a small screwdriver into the slot on the bottom of
the cap and remove the cap.
TD
1
2
4
5
ON = 
Data rate [kbps]
Autobaud
12000
6000
3000
1500
500
187.5
93.75
45.45
19.2
9.6
DIP 1



DIP 2




DIP 3





DIP 4





B
R
ER
3
Set all connected PROFIBUS devices to the
same data rate!
rt
Po
6
A
8.2
Set the operating mode (DIP switch 5)
A
R
ER
Operating mode
FILTER
DIRECT
ON
ON
1
2
3
S1...S6
DIP 5
OFF
ON
4
5
6
O
P
R
T
B
In FILTER operating mode (DIP 5 = OFF), the repeater filters
out destroyed telegrams. This avoids unnecessary network
load and improves resistance to interference. The bit delay
resulting from the repeater is 11 bits. Take this into account
when configuring the lines.
Figure 8
DIP switches
At delivery, all DIP switches are in the "OFF" position.
DIP switch 6 has no function.
102986_en_08
In DIRECT operating mode (DIP 5 = ON), the filter function
is switched off. The bit delay is only 1 bit. You don't need to
take this bit delay into account when configuring the lines.
If several repeaters are connected to form a star structure,
there is no additional bit delay when distributing the data
signal via the DIN rail connector.
The corresponding bit delay must only be taken into
consideration when the telegram is received at port A or
port B. The direction (master or slave) from which the
telegram is received at the repeater is therefore not
important.
PHOENIX CONTACT 14 / 19
PSI-REP-PROFIBUS/12MB
9
9.1
Cable configuration
•
The cable configuration is only necessary if
the repeater is operated in FILTER mode
(DIP 5 = OFF). In this case, the bit delay of
11 bits must be taken into consideration in the
cable configuration of the control system.
•
•
•
Configuring the network parameters in STEP 7
Open the “Properties-DP” dialog box and click on
“Properties”.
Select a subnetwork and click on “Properties”.
Switch to the “Network Settings” tab and click on
“Options”.
Switch to the “Cables” tab.
Data transmission cables and network components lead to
signal delays. The following section provides support when
calculating the necessary network parameters.
The configuration of network parameters is described using
a practical example with STEP 7® software.
The following data is required for configuration:
– Number of repeaters
– Total length of all copper cables
Tslot_Init = a + b x L + 22 x N
Tslot_Init = Minimum slot time in bit periods
a, b
= Length parameter (see table)
L
= Network coverage in km
N
= Number of repeaters
Data rate [kbps]
12000
6000
3000
1500
500
187.5
93.75
45.45
19.2
9.6
102986_en_08
a
DP
811
461
261
161
111
71
71
411
71
71
DP/FMS
811
461
261
991
371
371
211
411
76
71
b
120
60
30
15
5
1.875
0.9375
0.4545
0.192
0.096
Figure 9
•
•
•
•
Options
Activate the “Take into account the following cable
configuration” checkbox.
Enter the total number of repeaters used and the total
length of all copper cables. If fiber optic paths are used,
enter them separately.
Close all dialog boxes with “OK”.
Switch to the “Network Settings” tab and activate the
“User-Defined” profile.
PHOENIX CONTACT 15 / 19
PSI-REP-PROFIBUS/12MB
Figure 10
•
Click on “Bus Parameters”.
Figure 11
•
•
•
Properties - PROFIBUS
PROFIBUS
Enter the calculated value “Tslot_init” and click on
“Recalculate”.
Change the “Gap Factor” to “1” and the “Retry Limit” to
“3”.
Confirm all dialog boxes with “OK” and load the
parameterization to the controller.
102986_en_08
PHOENIX CONTACT 16 / 19
PSI-REP-PROFIBUS/12MB
10
10.2
Assembly
Combined assembly
Observe the snap-in direction of the device
and DIN rail connector: snap-on foot below
and plug on the left.
CAUTION: Electric shock
The device is designed exclusively for SELV
operation according to IEC 60950/EN 60950/
VDE 0805. The device may only be
connected to devices, which meet the
requirements of EN 60950.
A connection station must not consist of more
than ten devices.
A
NOTE: Malfunction
Use a grounding terminal block to connect the
DIN rail to protective earth ground. The
devices are grounded when they are snapped
onto the DIN rail (installation according to
PELV).
This ensures that the shielding is effective.
Connect protective earth ground with low
impedance.
10.1
C
B
Mounting on a DIN rail
A
Figure 13
B
Figure 12
Mounting on a DIN rail
The DIN rail connector is used to bridge the power supply
and communication.
• For one connection station, plug the DIN rail connectors
together (order no. 2709561, 2 per device).
• Push the connected DIN rail connectors into the DIN
rail.
• Place the device onto the DIN rail from above. Push the
module from the front toward the mounting surface until
it audibly engages.
10.3
•
•
•
•
•
To avoid contact resistance, only use clean, corrosionfree 35 mm DIN rails according to DIN EN 60715.
Install an end bracket next to the left-hand device to
prevent the devices from slipping.
Place the device onto the DIN rail from above. Push the
module from the front toward the mounting surface until
it audibly engages.
Snap the other devices that are to be contacted onto the
DIN rail next to one another.
102986_en_08
Combined assembly
•
•
Removal
Push down the locking tab with a screwdriver, needlenose pliers or similar.
Slightly pull the bottom edge of the device away from
the mounting surface.
Pull the device away from the DIN rail.
When you dismantle a connection station, also remove the
DIN connectors.
PHOENIX CONTACT 17 / 19
PSI-REP-PROFIBUS/12MB
11
11.2
Supply voltage
The device is operated using a 24 V DC SELV.
1
5
6
7
9
2
3
4
Operation in a topology
When the devices are operated in a topology, the supply
voltage must only be supplied to the first device in the
station.
The remaining devices are supplied via the DIN rail
connector. A second power supply unit can be used to
create a redundant supply concept.
PSI-REP-PROFIB/12MB
Ord.-No. 27 08 863
VCC
TD
RD
8
24 V
0V
24 V
0 V 24 V
0V
ERR A
Port A
Figure 14
Port B
10
ERR B
1
2
24 V DC supply voltage
0 V DC supply voltage
11.1
•
11
Operation as a single device
Supply voltage to the device via terminal blocks 1 (24 V)
and 2 (0 V).
102986_en_08
Individual/redundant supply
Using the system current supply
Alternatively, the connection station can be connected to a
system power supply.
• Connect a system power supply to two DIN rail
connectors on the left of the group.
– MINI-SYS-PS-100-240AC/24DC/1.5,
Order No. 2866983 or
– MINI-PS100-240AC/24DC/1.5/EX,
Order No.: 2866653
– Two DIN rail connectors, Order No. 2709561
PHOENIX CONTACT 18 / 19
PSI-REP-PROFIBUS/12MB
12
Connecting data cables
13
Switching output
NOTE: Malfunction
NOTE: device damage
Use shielded twisted pair data cables.
Connect the cable shielding at both ends of
the transmission path.
The maximum load capacity of the relay
contact is 30 V DC, 1 A, and 65 V DC/
150 V AC, 0.46 A.
The device is equipped with a floating switching output for
error diagnostics (terminals 3 (11) and 4 (12)).
2
IB/1
OF 63
-PR 8 8
EP 7 0
I-R . 2
PS .-No
Ord
The floating switch contact opens on the relevant device if
there is a transmission error on port A or port B.
MB
The switching output is an N/C contact. It can be connected
to a local digital input, e.g., on a PLC, for error detection.
C
VC
RD
TD
R
Port A
A
ER
rt
Po
R
A
B
Port B
ER
When mounted in a topology, the individual switching
outputs can be connected to separate input points or the
individual contacts can be looped through to generate a
group message.
24 V DC
P
O
R
T
B
24 V DC
24 V 0 V
Figure 16
Figure 15
•
•
24 V 0 V
24 V 0 V
24 V 0 V
24 V 0 V
Individual and group message
D-SUB connections for port A and port B
Connect the data lines for port A and Port B to the
corresponding D-SUB connections using a suitable
plug, for example a SUBCON-PLUS-PROFIB/SC2
plug, order number 2708232.
If the device is used at the beginning or the end of an
electrical PROFIBUS segment, activate the termination
in the connector plug.
Assignment of the D-SUB connection
Contact Signal
Meaning
3
RxD / TxD-P
Receive/transmit data positive, B cable
5
DGND
Data transmission potential
(reference potential to VP)
6
VP
5 V auxiliary voltage output
(P5V), max. 50 mA
8
RxD / TxD-N
Receive/transmit data –
negative A cable
102986_en_08
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany
phoenixcontact.com
19 / 19