Product Data - Jenkins Heating and Air

25HNB6**C
Infinityr 16 2---Stage Heat Pump
with Puronr Refrigerant for Coastal Applications
2 to 5 Nominal Tons
Product Data
INDUSTRY LEADING
FEATURES / BENEFITS
Energy Efficiency
S
S
13.7 -- 17.2 SEER/11.2 -- 13.3 EER/8.0 -- 9.5 HSPF
Microtube Technologyt refrigeration system
S
S
S
S
S
Sound level as low as 67 dBA
Quiet mount split post compressor grommets
Compressor sound hood
Laminated steel compressor mounting plate
8 pole PSC ball bearing outdoor condenser fan motor
S
System supports Infinity Controlt or standard 2--stage
thermostat controls
Sound
Comfort
Reliability
S
S
S
S
S
S
S
S
S
S
Puronr refrigerant -- environmentally sound, won’t deplete
the ozone layer and low lifetime service cost.
Front--seating service valves
2--stage scroll compressor
Internal pressure relief valve
Internal thermal overload
High pressure switch
Loss of charge switch
Filter drier
Balanced refrigeration system for maximum reliability
Crankcase heater standard
Controls and Diagnostics
S
S
Carrier’s heat pumps with Puronr refrigerant provide a collection
of features unmatched by any other family of equipment. The
25HNB6 has been designed utilizing Carrier’s Puron refrigerant.
The environmentally sound refrigerant allows consumers to make a
responsible decision in the protection of the earth’s ozone layer.
This product has been designed and manufactured to meet Energy
Starr criteria for energy efficiency when matched with appropriate
coil components. Refer to the combination ratings in the Product
Data for system combinations that meet Energy Starr guidelines.
NOTE: Ratings contained in this document are subject to
change at any time. Always refer to the AHRI directory
(www.ahridirectory.org) for the most up--to--date ratings
information.
S
S
Infinityt Control or 2--Stage Thermostat
2 control wires to outdoor unit with Infinity Control (serial
numbers 3112E and newer)
Utility Interface Connection
Enhanced diagnostics capability with Infinityt Control
Durability
WeatherArmor Ultrat protection package:
S Solid, Durable sheet metal construction
S Steel louver coil guard
S 2--Sided, baked--on, complete coverage, powder paint
ArmorPlatet Condenser Coil
S Aluminum fin material is pre--coated on both sides with a
corrosion protective epoxy phenolic thermoset coating.
S Industry leading standard coastal warranty coverage
Applications
S
S
Long--line -- up to 250 feet (76.2 m) total equivalent length.
Low ambient cooling (down to 0_F / --17.8_C ) with
approved low ambient accessory kits or complete Infinity
system.
MODEL NUMBER NOMENCLATURE
1
N
2
N
3
A
4
A
5
A/N
6
N
7
N
8
N
9
A/N
10
A/N
11
A/N
12
N
13
N
2
5
H
N
B
6
3
6
C
0
0
3
0
Product
Series
Product
Family
Tier
Major
Series
SEER
Variations
Open
Open
Voltage
25 = HP
H = RES HP
0=Not
Defined
0=Not
Defined
Minor
Series
3=208/230--- 1
0, 1, 2...
25HNB6C
the environmentally sound refrigerant
N=
Infinity Series
B = Puron
6=16 SEER
Cooling
Capacity
1,000 Btuh
(nominal)
C = Coastal
Use of the AHRI Certified
TM Mark indicates a
manufacturer’s
participation in the
program For verification
of certification for individual
products, go to
www.ahridirectory.org.
This product has been designed and manufactured to
meet Energy Star criteria for energy efficiency when
matched with appropriate coil components. However,
proper refrigerant charge and proper air flow are critical
to achieve rated capacity and efficiency. Installation of
this product should follow all manufacturing refrigerant
charging and air flow instructions. Failure to confirm
proper charge and air flow may reduce energy
efficiency and shorten equipment life.
STANDARD FEATURES
FEATURES
Unit Size --- Voltage, Series
24---32
36---31
48---31
60---31
ArmorPlate™ Fins
X
X
X
X
Inner and Outer Sheet Metal Surfaces Coated with Baked
on Powder Paint
X
X
X
X
Puron Refrigerant
X
X
X
X
2 control wires to outdoor unit with Infinity Control
(serial numbers 3112E and newer)
X
X
X
X
Maximum SEER Rating*
17.2
17.0
16.5
16.0
2--- Stage Scroll Compressor
X
X
X
X
Louvered Coil Guard
X
X
X
X
Field Installed Filter Drier
X
X
X
X
Front Seating Service Valves
X
X
X
X
Internal Pressure Relief Valve
X
X
X
X
Long Line capability
X
X
X
X
Loss of Charge Switch
X
X
X
X
High Pressure Switch
X
X
X
X
Crankcase Heater
X
X
X
X
Low ambient cooling down to 0_F capability
with Infinity Control or Approved Kit
X
X
X
X
Utility Interface Connections
X
X
X
X
Enhanced Diagnostics with Infinity Control
X
X
X
X
Sound Blanket
X
X
X
X
X = Standard
* With approved combinations
2
PHYSICAL DATA
UNIT SIZE SERIES
Operating Weight lb (kg)
24--- 32
275 (125)
36--- 31
296 (134)
Shipping Weight lb (kg)
Compressor Type
318 (144)
339 (154)
48--- 31
328 (149)
60--- 31
350 (159)
371 (168)
395 (179)
Ultratechr Scroll
REFRIGERANT
Control
Puronr (R---410A)
TXV (Puron Hard Shutoff)
Charge lb (kg)
Outdoor Htg Piston #
13.07 (5.93)
46
13.70 (6.21)
55
COND FAN
Air Discharge
13.73 (6.23)
61
14.78 (6.70)
67
Air Qty (CFM)
Motor HP
Motor RPM
COND COIL
Face Area (Sq ft)
Fins per In.
Rows
Circuits
VALVE CONNECT. (In. ID)
Vapor
3200
1/12
3200
1/12
4350
1/4
5000
1/4
800
800
825
825
25.2
20
25.2
20
25.2
20
30.18
20
2
8
2
8
2
8
2
10
3/4
7/8
7/8
7/8
1 ---1/8
1 ---1/8
Liquid
REFRIGERANT TUBES (In. OD)
25HNB6C
Propeller Type, Direct Drive
Vertical
3/8
Rated Vapor*
Max Liquid Line
3/4
7/8
3/8
* Units are rated with 25 ft (7.6 m) of lineset length. See Vapor Line Sizing and Cooling Capacity Loss table when using other sizes and lengths of lineset.
Note: See unit Installation Instruction for proper installation.
VAPOR LINE SIZING AND COOLING CAPACITY LOSS
Acceptable vapor line diameters provide adequate oil return to the compressor while avoiding excessive capacity loss. The suction line
diameters shown in the chart below are acceptable for AC systems with Puron refrigerant:
Unit
Nominal
Size
(Btuh)
24,000
2 ---Stage
HP with
Puron
36,000
2 ---Stage
HP with
Puron
48,000
2 ---Stage
HP with
Puron
60,000
2 ---Stage
HP with
Puron
Maximum
Liquid Line
Diameters
(In. OD)
3/8
3/8
3/8
3/8
Vapor Line
Diameters
(In.) OD
Cooling Capacity Loss (%)
Total Equivalent Line Length ft. (m)
Standard
Application
26--- 50
51--- 80
Long Line Application Requires Accessories
81--- 100
101--- 125
126--- 150
151--- 175
176--- 200
201--- 225
226--- 250
(7.9--- 15.2)
(15.5--- 24.4)
(24.7--- 30.5)
(30.8--- 38.1)
(38.4--- 45.7)
(46.0--- 50.3)
(53.6--- 60.0)
(61.3--- 68.6)
(68.9--- 76.2)
5/8
0
1
1
2
3
3
4
4
5
3/4
0
1
1
1
1
1
1
1
1
5/8
1
2
4
5
6
7
9
10
11
3/4
0
0
1
1
2
2
3
3
4
7/8
0
0
—
—
—
—
—
—
—
3/4
1
2
2
3
4
5
6
7
7
7/8
0
1
1
2
2
2
3
3
4
1 ---1/8
0
0
—
—
—
—
—
—
—
3/4
1
2
4
5
6
8
9
10
11
7/8
0
1
2
2
3
4
4
5
5
1 ---1/8
0
0
—
—
—
—
—
—
—
Standard Length = 80 ft. (24.4 m) or less total equivalent length
Applications in this area are long line. Accessories are required as shown recommended on Long Line Application Guidelines
Applications in this area may have height restrictions that limit allowable total equivalent length, when outdoor unit is below indoor unit.
— Applications in this area are not recommended due to insufficient oil return.
3
REFRIGERANT PIPING LENGTH LIMITATIONS
Maximum Line Lengths:
The maximum allowable total equivalent length for heat pumps varies depending on the vertical separation. See the tables below for
allowable lengths depending on whether the outdoor unit is on the same level, above or below the outdoor unit.
Maximum Line Lengths for Heat Pump Applications
Units on equal level
MAXIMUM ACTUAL LENGTH
ft (m)
200 (61)
MAXIMUM EQUIVALENT LENGTH{
ft (m)
250 (76.2)
MAXIMUM VERTICAL SEPARATION ft (m)
N/A
200 (61)
250 (76.2)
200 (61)
Outdoor unit ABOVE
indoor unit
Outdoor unit BELOW
indoor unit
See Table ’Maximum Total Equivalent Length: Outdoor Unit BELOW Indoor Unit’
{ Total equivalent length accounts for losses due to elbows or fitting. See the Long Line Guideline for details.
25HNB6C
Maximum Total Equivalent Length{ -- Outdoor Unit BELOW Indoor Unit
Size
Liquid Line
Diameter
w/ TXV
024
HP with
Puron
036
HP with
Puron
048
HP with
Puron
060
HP with
Puron
0--- 20
(0 --- 6.1)
HP with Puronr Refrigerant --- Maximum Total Equivalent Length{
Vertical Separation ft (m) Outdoor unit BELOW indoor unit;
21--- 30
31--- 40
41--- 50
51--- 60
61--- 70
(6.4 --- 9.1)
(9.4 --- 12.2)
(12.5 --- 15.2)
(15.5 --- 18.3)
(18.6 --- 21.3)
71--- 80
(21.6 --- 24.4)
3/8
250*
250*
250*
250*
250*
250*
250*
3/8
250*
250*
250*
250*
250*
250*
250*
3/8
250*
250*
250*
250*
230
160
--- ---
3/8
250*
225*
190
150
110
--- ---
--- ---
* Maximum actual length not to exceed 200 ft (61 m)
{ Total equivalent length accounts for losses due to elbows or fitting. See the Long Line Guideline for details.
--- --- = outside acceptable range
LONG LINE APPLICATIONS
An application is considered Long Line when the refrigerant level in the system requires the use of accessories to maintain acceptable
refrigerant management for systems reliability. Defining a system as long line depends on the liquid line diameter, actual length of the tubing,
and vertical separation between the indoor and outdoor units.
For Heat Pump systems, the chart below shows when an application is considered Long Line. Beyond these lengths, long line accessories
are required:
HP WITH PURONr REFRIGERANT LONG LINE DESCRIPTION ft (m)
Beyond these lengths, long line accessories are required
Liquid Line Size
Units On Same Level
Outdoor Below Indoor
Outdoor Above Indoor
3/8
80 (24.4)
20 (6.1) vertical or 80 (24.4) total
80 (24.4)
Note: See Long Line Guideline for details
4
ACCESSORIES
KIT NUMBER
KHALS0401LLS
KIT NAME
SOLENOID VALVE
24--- 32
X
36--- 31
X
48--- 31
X
60--- 31
X
KHASS0606MPK*
KSAHS2501AAA{
SNOW STAND
X
X
X
X
HARD START KIT
X
X
KSAHS2801AAA{
HARD START KIT
KSASF0101AAA
X
X
SUPPORT FEET
X
X
X
X
KAAFT0101AAA
FREEZE THERMOSTAT
X
X
X
X
KSALA0301410
LOW AMBIENT PRESSURE SWITCH
X
X
X
X
X
X
X
X
KHAIR0201AAA
ISOLATION RELAY
x = Accessory S = Standard
* Available from RCD
{ Not backward compatible to previous series.
ACCESSORY CONTROLS
DESCRIPTION
Infinity Touch Control (non ---Wi---Fi)
SYSTXCCITW01
Infinity Touch Control with Wi---Fi & Wireless Access Point
SYSTXCCUID01-V
Infinity Control Deluxe 7-Day Programmable (Wall-mounted system control.)
SYSTXCCUIZ01-V
Infinity Control Deluxe Zoning 7-Day Programmable (Wall-mounted control for a multi-zone system.)
SYSTXCC4ZC01
Infinity 4-Zone Damper Control Module (Wall-mounted control for a four-zone system.)
SYSTXCCSMS01
Infinity Smart Sensor (Optional wall control used to monitor temperature and/or fan control in an individual zone.)
SYSTXCCRRS01
Infinity Remote Room Sensor (Monitors temperature in an individual zone.)
SYSTXCCRCT01
or
SYSTXCCRWF01
Infinity System Access Module (Hardware for wireless access and control via internet.)
SYSTXCCNIM01
Infinity Network Interface Module (Connects Heat Recovery and Energy Recovery Ventilators on Non-zoning applications.)
SYSTXXXBPU01
Decorative Back Plate for Infinity Control (Decorative wall plate.)
5
25HNB6C
PART NO.
SYSTXCCITN01
ACCESSORY USAGE GUIDELINE
Accessory
Compressor Start Assist Capacitor
and Relay
Crankcase Heater
No
No
No
Yes
(standard on some units)
No
No
No
No
No
No
No
See Residential Piping
and Long Line Guideline
No
Yes
(standard w/factory
approved indoor unit)
No
Yes
(standard w/factory
approved indoor unit)
Recommended
Yes (kit required)
Support Feet
Required for Sea
Coast
Applications
(within 2 miles/3.2 km)
Yes
(standard on some units)
Standard with
Infinity Control
(no kit required)
Standard with
Infinity Control
(no kit required)
No
Standard with Infinity
Control
(no kit required)
Yes
(standard w/factory
approved indoor unit)
Recommended
Isolation Relay
Puron Refrigerant Balance Port
Hard Shutoff TXV
Required for Long Line
Applications*
No
Yes (kit required)
Low---Ambient Pressure Switch
Required for
Low Ambient
Cooling Applications
Utilizing UI
(Below 55° F / 12.8° C)
Yes
(standard on some units)
Evaporator Freeze Thermostat
Liquid Line Solenoid Valve
25HNB6C
Required for
Low Ambient
Cooling Applications
Utilizing 2--- Stage
Thermostat on 16 SEER
Models Only
(Below 55° F / 12.8° C)
No
Yes (kit required)
Yes
(standard w/factory
approved indoor unit)
Recommended
* For tubing set lengths between 80 and 200 ft. (24.38 and 60.96 m) horizontal or 20 ft. (6.10 m) vertical differential (total equivalent length), refer to the
Residential Piping and Long Line Guideline
Accessory Description and Usage (Listed Alphabetically)
1. Compressor Start Assist -- Capacitor and Relay
Start capacitor and relay gives a “hard” boost to compressor motor
at each start up.
Usage Guideline:
Not required on this unit since compressor always starts
unloaded.
Available if required by local codes.
2. Crankcase Heater
An electric resistance heater which mounts to the base of the
compressor to keep the lubricant warm during off cycles. Improves
compressor lubrication on restart and minimizes the chance of
liquid slugging.
Usage Guideline:
Required in low ambient cooling applications.
Required in long line applications.
3. Evaporator Freeze Thermostat
An SPST temperature--actuated switch that stops unit operation
when evaporator reaches freeze--up conditions.
Usage Guideline:
Required when low ambient kit has been added.
4. Isolation Relay
An SPDT relay which switches the low ambient controller out of
the outdoor fan motor circuit when the heat pump switches to
heating mode.
Usage Guideline:
Required in all heat pumps where low ambient kit has
been added.
5. Low--Ambient Pressure Switch
A long life pressure switch which is mounted to outdoor unit
service valve. It is designed to cycle the outdoor fan motor in order
to maintain head pressure within normal operating limits. The
control will maintain working head pressure at low--ambient
temperatures down to 0_F (--17.8_C) when properly installed.
Usage Guideline:
A Low--Ambient Pressure Switch must be used when
cooling operation is used at outdoor temperatures
below 55_F (12.8_C).
Suggested in all commercial applications.
6. Liquid--Line Solenoid Valve (LLS)
An electrically operated shutoff valve which stops and starts
refrigerant liquid flow in response to compressor operation. It is to
be installed at the outdoor unit to control refrigerant off cycle
migration in the heating mode.
Usage Guideline:
An LLS is required in all long line heat pump
applications to control refrigerant off cycle migration in
the heating mode. See Long Line Guideline.
Suggested for all commercial applications.
7. Outdoor Air Temperature Sensor
Designed for use with Carrier Thermostats listed in this
publication. This device enables the thermostat to display the
outdoor temperature. This device also is required to enable special
thermostat features such as auxiliary heat lock out.
Usage Guideline:
Suggested for all Carrier thermostats listed in this
publication.
8. Snow Stand
Coated wire rack which supports unit 18 in. (457.2 mm) above
mounting pad to allow for drainage from unit base.
Usage Guideline:
Suggested in the following applications:
Heat pump installations in heavy snowfall areas.
Heat pump installations in snow drift locations.
Heat pump installations in areas of prolonged
subfreezing temperatures.
All commercial installations.
9. Thermostatic Expansion Valve (TXV) Bi--Flow
A modulating flow--control valve which meters refrigerant liquid
flow rate into the evaporator in response to the superheat of the
refrigerant gas leaving the evaporator.
Usage Guideline:
Accessory required to meet AHRI rating and system
reliability, where indoor not equipped.
Required in all heat pump applications designed with
Puron refrigerant.
6
ELECTRICAL DATA
V/PH
OPER VOLTS*
MAX
MIN
COMPR
LRA
FAN
RLA
MCA
FLA
MIN
WIRE
SIZE{
MIN
WIRE
SIZE{
MAX
LENGTH
ft (m)}
MAX
LENGTH
ft (m)}
60C
75C
60C
75C
MAX
FUSE**
or CKT
BRK
AMPS
25
40
50
60
24--- 32
58.3
12.5
0.6
16.2
14
14
48 (14.8)
46 (14.1)
36--- 31
83.0
18.5
0.6
23.7
12
12
52 (16.0)
50 (15.3)
208 ---230/1
253
197
48--- 31
104.0
22.8
1.3
29.8
10
10
67 (20.4)
63 (19.4)
60--- 31
152.9
28.8
1.5
37.5
8
8
82 (25.2)
78 (24.0)
* Permissible limits of the voltage range at which the unit will operate satisfactorily
{ If wire is applied at ambient greater than 30_C, consult table 310 ---16 of the NEC (NFPA 70). The ampacity of non ---metallic---sheathed cable (NM),
trade name ROMEX, shall be that of 60_C conditions, per the NEC (NFPA 70) Article 336 ---26. If other than uncoated (no ---plated), 60 or 75_C
insulation, copper wire (solid wire for 10 AWG or smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the NEC (NFPA 70).
} Length shown is as measured 1 way along wire path between unit and service panel for voltage drop not to exceed 2%.
** Time ---Delay fuse.
FLA --- Full Load Amps
LRA --- Locked Rotor Amps
MCA --- Minimum Circuit Amps
RLA --- Rated Load Amps
NOTE: Control circuit is 24 ---V on all units and requires external power source. Copper wire must be used from service disconnect to unit.
All motors/compressors contain internal overload protection.
Complies with 2010 requirements of ASHRAE Standards 90.1
SOUND POWER LEVEL (dBA)
Unit Size
--- Voltage,
Series
Standard Rating dBA
TYPICAL OCTAVE BAND SPECTRUM (dBA, without tone adjustment)
125
250
500
1000
2000
4000
8000
68 --- High Stage
50.5
56.0
24--- 32
67 --- Low Stage
50.0
56.5
70 --- High Stage
50.5
56.0
36--- 31
68 --- Low Stage
51.5
56.5
70 --- High Stage
52.0
59.5
48--- 31
69 --- Low Stage
53.0
60.5
71 --- High Stage
49.5
59.0
60--- 31
71 --- Low Stage
51.5
60.0
NOTE: Tested in compliance with AHRI 270 ---2008 but not listed with AHRI.
60.0
61.0
60.0
59.5
63.5
63.5
63.0
63.5
62.5
61.5
66.0
63.0
65.0
63.5
63.5
65.5
60.0
60.0
60.0
59.5
59.5
59.0
59.5
59.5
58.0
58.5
56.5
57.0
56.5
56.5
58.0
59.5
51.0
49.0
50.0
49.0
49.5
50.0
54.5
55.0
CHARGING SUBCOOLING (TXV--TYPE EXPANSION DEVICE)
UNIT SIZE --- VOLTAGE, SERIES
24--- 32
36--- 31
48--- 31
60--- 31
REQUIRED SUBCOOLING _F (_C)
10 (5.6)
13 (7.2)
12 (6.7)
11 (6.1)
7
25HNB6C
UNIT
SIZE --VOLTAGE,
SERIES
8
2
DIMENSIONS -- ENGLISH
25HNB6C
9
2
DIMENSIONS -- SI
25HNB6C
10
10 (-23.3)
10
20
30
40
50
60
70
80
0 (-17.8)
10 (-12.2)
30 (-1.1)
40 (4.4)
OUTDOOR TEMPERATURE, ºF( ºC)
20 (-6.7)
25HNB6C BALANCE POINT WORKSHEET - HIGH STAGE
BUILDING HEAT LOSS, UNIT INTEGRATED
HEATING CAPACITY, MBTUH
50 (10.0)
25HNB6C
60 (15.6)
70 (21.1)
80 (26.7)
BASED ON INDOOR ENT. AIR AT
70ºF 21.1ºC AND AT RATED CFM
25HNB624
FV4CNF002
25HNB636
FV4CNB006
25HNB648
FV4CN(B,F)005
25HNB660
FV4CNB006
11
10 (-23.3)
10
20
30
40
50
60
0 (-17.8)
10 (-12.2)
30 (-1.1)
40 (4.4)
OUTDOOR TEMPERATURE, ºF( ºC)
20 (-6.7)
25HNB6C BALANCE POINT WORKSHEET -- LOW STAGE
BUILDING HEAT LOSS, UNIT INTEGRATED
HEATING CAPACITY, MBTUH
25HNB6C
50 (10.0)
60 (15.6)
70 (21.1)
BASED ON INDOOR ENT. AIR AT
70ºF 21.1ºC AND AT RATED CFM
25HNB624
FV4CNF002
25HNB636
FV4CNB006
80 (26.7)
25HNB648
FV4CN(B,F)005
25HNB660
FV4CNB006
12
24”
(609.6)
Service
12”
(304.8)
12”
(304.8)
24”
(609.6)
Note: Numbers in ( ) = mm
24”
(609.6)
24”
(609.6)
Service
Wall
6”
(152.4 mm)
24”
(609.6)
Service
Wall
24”
(609.6)
12”
(304.8)
Clearances (various examples)
24”
(609.6)
Service
12”
(304.8)
24”
Service
Wall
6”
(152.4)
IMPORTANT: When installing multiple units in an alcove, roof well, or partially enclosed area, ensure there is adequate ventilation to prevent re--circulation of discharge air.
CLEARANCES
25HNB6C
Wall
A07833
13
FV4CNF002
FV4CNB006
FV4CN(B,F)005
FV4CNB006
25HNB624C**32
25HNB636C**31
25HNB648C**31
25HNB660C**31
Furnace Model Number
24,000
36,400
47,000
56,500
Cooling
Capacity
13.0
13.3
12.5
12.5
EER
17.0
17.0
16.0
16.0
SEER
Cooling
700
1050
1400
1750
High
ID CFM
560
840
1120
1400
Low
* Ratings are net values reflecting the effects of circulating fan heat. Supplemental electric heat is not included. Ratings are based on:
Cooling Standard: 80_F (27_C) db 67_F (19_C) wb indoor entering air temperature and 95_F (35_C) db air entering outdoor unit.
High--- Temp Heating Standard: 70_F (21_C) db indoor entering air temperature and 47_F (8_C) db 43° F (6_C) wb air entering outdoor unit.
Low--- Temp Heating Standard: 70_F (21_C) db indoor entering air temperature and 17_F ( ---8_C) db 15° F ( ---9_C) wb air entering outdoor unit.
EER — Energy Efficiency Ratio
SEER — Seasonal Energy Efficiency Ratio
COP — Coefficient of Performance
HSPF — Heating Seasonal Performance Factor
Coil Model Number
Model Number
25HNB6C
High Temp
Capacity
47_F (8_C)
25,000
35,800
47,000
58,000
3.90
4.06
3.68
3.72
COP
9.0
9.5
9.0
9.0
HSPF
Heating
Low Temp
Capacity
17_F ( --- 8_C)
15,300
22,600
29,200
36,000
2.74
3.00
2.72
2.76
COP
NOTE: Ratings contained in this document are subject to change at any time.
For AHRI ratings certificates, please refer to the AHRI directory www.ahridirectory.org
Additional ratings and system combinations can be accessed via the Carrier database at: www.MyCarrierRatings.com
For performance data at specific application &/or design conditions with various indoor unit combinations, the equipment performance calculator can be accessed at :
http://rpmob.wrightsoft.com/
TESTED AHRI COMBINATION RATINGS*
14
72 (22.2)
67 (19.4)
63 (17.2)††
62 (16.7)
57 (13.9)
72 (22.2)
67 (19.4)
63 (17.2)††
62 (16.7)
57 (13.9)
72 (22.2)
67 (19.4)
63 (17.2)††
62 (16.7)
57 (13.9)
72 (22.2)
67 (19.4)
63 (17.2)††
62 (16.7)
57 (13.9)
72 (22.2)
67 (19.4)
63 (17.2)††
62 (16.7)
57 (13.9)
72 (22.2)
67 (19.4)
63 (17.2)††
62 (16.7)
57 (13.9)
72 (22.2)
67 (19.4)
63 (17.2)††
62 (16.7)
57 (13.9)
72 (22.2)
67 (19.4)
63 (17.2)††
62 (16.7)
57 (13.9)
EWB
° F (° C)
See notes on pg. 17
640
560
520
480
800
700
650
600
CFM
EVAPORATOR AIR
Sens‡
22.47
20.32
16.88
17.58
14.67
23.20
21.24
17.53
18.28
15.16
23.87
22.13
18.16
18.95
15.64
25.06
23.81
19.37
20.24
16.52
17.39
16.18
13.33
13.92
11.55
17.96
16.93
13.88
14.50
11.95
18.48
17.65
14.39
15.06
12.34
19.39
18.98
15.39
16.13
13.05
Total
22.47
24.03
24.52
26.60
29.44
23.20
24.52
25.01
27.11
30.01
23.87
24.95
25.44
27.57
30.50
25.06
25.69
26.15
28.31
31.29
17.39
18.31
18.68
20.33
22.57
17.96
18.68
19.05
20.72
22.98
18.48
19.01
19.37
21.05
23.34
19.39
19.60
19.88
21.59
23.93
Capacity MBtuh†
75 (23.9)
1.02
1.02
1.01
1.00
0.98
1.02
1.02
1.01
1.00
0.98
1.02
1.02
1.02
1.00
0.98
1.03
1.03
1.03
1.01
0.99
1.43
1.44
1.44
1.46
1.47
1.44
1.45
1.45
1.47
1.48
1.45
1.46
1.46
1.47
1.49
1.47
1.48
1.48
1.49
1.51
Total
System
KW**
85 (29.4)
16.21
16.89
17.23
18.75
20.81
16.73
17.22
17.55
19.09
21.18
17.20
17.52
17.82
19.38
21.48
18.02
18.06
18.27
19.85
22.00
21.26
22.54
22.99
24.94
27.61
21.94
22.98
23.43
25.41
28.12
22.56
23.37
23.82
25.81
28.55
23.65
24.06
24.45
26.48
29.26
Total
16.21
15.08
12.36
12.93
10.67
16.73
15.78
12.87
13.47
11.05
17.20
16.44
13.36
13.99
11.41
18.02
18.06
14.30
15.01
12.06
21.26
19.39
16.03
16.71
13.88
21.94
20.28
16.66
17.38
14.35
22.56
21.13
17.27
18.03
14.80
23.65
22.73
18.43
19.28
15.64
Sens‡
Capacity MBtuh†
DETAILED COOLING CAPACITIES#
95 (35)
Total
Sens‡
Capacity MBtuh†
Total
System
KW**
105 (40.6)
Total
Sens‡
Capacity MBtuh†
25HNB624C**32 Outdoor Section With FV4CNF002 Indoor Section --- High
1.60
20.00
20.00
1.78
18.69
18.69
1.60
20.99
18.43
1.79
19.40
17.45
1.61
21.40
15.16
1.79
19.77
14.27
1.62
23.23
15.82
1.80
21.47
14.92
1.63
25.73
13.07
1.82
23.80
12.26
1.61
20.62
20.62
1.79
19.26
19.26
1.61
21.39
19.28
1.80
19.75
18.25
1.61
21.79
15.76
1.80
20.11
14.85
1.63
23.64
16.47
1.81
21.83
15.54
1.64
26.17
13.52
1.82
24.19
12.70
1.62
21.19
21.19
1.80
19.78
19.78
1.62
21.74
20.09
1.81
20.08
19.01
1.62
22.14
16.35
1.81
20.41
15.41
1.63
24.00
17.09
1.82
22.15
16.14
1.65
26.55
13.96
1.83
24.52
13.11
1.64
22.20
22.20
1.82
20.69
20.69
1.64
22.38
21.57
1.82
20.73
20.73
1.64
22.69
17.47
1.82
20.90
16.49
1.65
24.59
18.30
1.83
22.66
17.30
1.66
27.18
14.75
1.85
25.08
13.85
25HNB624C**32 Outdoor Section With FV4CNF002 Indoor Section --- Low
1.19
14.97
14.97
1.39
13.72
13.72
1.19
15.42
13.96
1.39
13.94
12.83
1.18
15.71
11.39
1.38
14.18
10.42
1.17
17.12
11.92
1.37
15.48
10.93
1.15
19.02
9.79
1.35
17.22
8.92
1.19
15.44
15.44
1.39
14.13
14.13
1.19
15.72
14.60
1.39
14.23
13.39
1.19
15.99
11.86
1.39
14.42
10.87
1.17
17.41
12.43
1.37
15.73
11.41
1.15
19.32
10.15
1.35
17.48
9.24
1.19
15.86
15.86
1.39
14.51
14.51
1.19
16.00
15.20
1.39
14.54
14.54
1.19
16.23
12.32
1.39
14.62
11.29
1.17
17.66
12.93
1.37
15.94
11.88
1.15
19.59
10.47
1.35
17.72
9.54
1.20
16.60
16.60
1.40
15.17
15.17
1.20
16.63
16.63
1.40
15.19
15.19
1.20
16.62
13.20
1.40
14.95
12.11
1.18
18.07
13.88
1.38
16.29
12.77
1.16
20.04
11.07
1.36
18.09
10.10
Total
System
KW**
CONDENSER ENTERING AIR TEMPERATURES ° F (° C)
1.62
1.62
1.62
1.60
1.59
1.62
1.62
1.62
1.61
1.59
1.62
1.62
1.62
1.61
1.59
1.63
1.63
1.63
1.62
1.60
2.00
2.01
2.01
2.02
2.03
2.01
2.02
2.02
2.03
2.04
2.02
2.03
2.03
2.04
2.05
2.04
2.04
2.04
2.05
2.07
Total
System
KW**
115 (46.1)
12.46
12.50
12.66
13.86
15.45
12.83
12.85
12.86
14.07
15.68
13.16
13.19
13.04
14.25
15.88
13.74
13.76
13.32
14.54
16.19
17.34
17.78
18.10
19.68
21.84
17.86
18.11
18.40
20.00
22.17
18.33
18.43
18.66
20.27
22.46
19.15
19.18
19.08
20.71
22.95
Total
12.46
12.48
9.48
9.97
8.08
12.83
12.85
9.89
10.42
8.37
13.16
13.19
10.29
10.85
8.64
13.74
13.76
11.05
11.68
9.17
17.34
16.44
13.37
14.01
11.45
17.86
17.19
13.93
14.61
11.86
18.33
18.26
14.47
15.19
12.24
19.15
19.18
15.51
16.31
12.95
Sens‡
Capacity MBtuh†
25HNB6C
1.89
1.89
1.89
1.88
1.87
1.89
1.89
1.89
1.88
1.87
1.89
1.89
1.90
1.89
1.87
1.90
1.90
1.91
1.90
1.88
2.27
2.27
2.28
2.29
2.30
2.28
2.28
2.28
2.29
2.30
2.29
2.29
2.29
2.30
2.31
2.31
2.31
2.31
2.32
2.33
Total
System
KW**
125 (51.7)
11.22
11.24
11.18
12.28
13.74
11.55
11.57
11.35
12.46
13.93
11.84
11.86
11.50
12.61
14.10
12.34
12.36
11.74
12.86
14.36
15.96
16.14
16.40
17.86
19.84
16.42
16.46
16.65
18.13
20.13
16.84
16.87
16.87
18.36
20.39
17.57
17.60
17.24
18.74
20.80
Total
11.22
11.24
8.57
9.05
7.27
11.55
11.57
8.95
9.46
7.53
11.84
11.86
9.32
9.86
7.79
12.34
12.36
10.01
10.62
8.27
15.96
15.39
12.47
13.10
10.63
16.42
16.46
13.00
13.67
11.01
16.84
16.87
13.52
14.23
11.37
17.57
17.60
14.51
15.30
12.05
Sens‡
Capacity MBtuh†
2.20
2.20
2.20
2.20
2.19
2.21
2.20
2.21
2.20
2.20
2.21
2.21
2.21
2.21
2.20
2.22
2.22
2.23
2.22
2.21
2.59
2.60
2.60
2.61
2.61
2.60
2.60
2.61
2.61
2.62
2.61
2.61
2.61
2.62
2.63
2.63
2.63
2.63
2.63
2.64
Total
System
KW**
15
72 (22.2)
67 (19.4)
63 (17.2)††
62 (16.7)
57 (13.9)
72 (22.2)
67 (19.4)
63 (17.2)††
62 (16.7)
57 (13.9)
72 (22.2)
67 (19.4)
63 (17.2)††
62 (16.7)
57 (13.9)
72 (22.2)
67 (19.4)
63 (17.2)††
62 (16.7)
57 (13.9)
72 (22.2)
67 (19.4)
63 (17.2)††
62 (16.7)
57 (13.9)
72 (22.2)
67 (19.4)
63 (17.2)††
62 (16.7)
57 (13.9)
72 (22.2)
67 (19.4)
63 (17.2)††
62 (16.7)
57 (13.9)
72 (22.2)
67 (19.4)
63 (17.2)††
62 (16.7)
57 (13.9)
EWB
° F (° C)
See notes on pg. 17
960
840
780
720
1200
1050
975
900
CFM
EVAPORATOR AIR
Sens‡
33.59
30.52
25.27
26.24
21.83
34.66
31.93
26.25
27.28
22.51
35.64
33.31
27.21
28.30
23.16
37.35
35.95
29.06
30.27
24.41
25.97
24.32
19.90
20.80
17.17
26.78
25.51
20.73
21.66
17.75
27.53
26.67
21.54
22.53
18.31
28.86
28.91
23.11
24.22
19.40
Total
33.59
35.79
36.56
39.56
43.66
34.66
36.45
37.23
40.24
44.40
35.64
37.04
37.80
40.84
45.03
37.35
38.04
38.75
41.80
46.06
25.97
27.04
27.62
30.03
33.45
26.78
27.53
28.09
30.55
34.02
27.53
27.98
28.51
31.00
34.49
28.86
28.91
29.20
31.73
35.28
Capacity MBtuh†
75 (23.9)
1.44
1.44
1.43
1.41
1.38
1.44
1.44
1.43
1.41
1.39
1.44
1.44
1.43
1.41
1.39
1.44
1.44
1.44
1.42
1.39
2.10
2.13
2.13
2.16
2.21
2.12
2.14
2.15
2.18
2.22
2.14
2.16
2.16
2.20
2.24
2.18
2.19
2.19
2.23
2.27
Total
System
KW**
24.13
24.89
25.41
27.65
30.80
24.87
25.33
25.83
28.10
31.29
25.56
25.76
26.20
28.48
31.71
26.76
26.80
26.80
29.12
32.39
32.13
33.92
34.65
37.50
41.43
33.12
34.52
35.26
38.13
42.08
34.03
35.06
35.78
38.66
42.65
35.63
36.01
36.63
39.53
43.58
Total
24.13
22.65
18.43
19.26
15.82
24.87
23.77
19.21
20.10
16.36
25.56
24.84
19.98
20.92
16.89
26.76
26.80
21.46
22.52
17.92
32.13
29.55
24.34
25.30
20.94
33.12
30.93
25.31
26.33
21.60
34.03
32.28
26.24
27.32
22.24
35.63
34.85
28.06
29.26
23.47
Sens‡
Capacity MBtuh†
85 (29.4)
Total
Sens‡
Capacity MBtuh†
95 (35)
Total
System
KW**
Total
Sens‡
Capacity MBtuh†
105 (40.6)
CONDENSER ENTERING AIR TEMPERATURES ° F (° C)
25HNB636C**31 Outdoor Section With FV4CNB006 Indoor Section --- High
2.36
30.60
30.60
2.67
28.98
28.98
2.38
31.98
28.55
2.68
29.95
27.51
2.39
32.68
23.39
2.69
30.59
22.40
2.41
35.38
24.34
2.71
33.12
23.34
2.45
39.09
20.03
2.74
36.62
19.09
2.38
31.53
31.53
2.69
29.83
29.83
2.39
32.54
29.91
2.69
30.44
28.83
2.40
33.22
24.33
2.70
31.07
23.32
2.43
35.92
25.34
2.72
33.61
24.32
2.46
39.68
20.67
2.76
37.15
19.70
2.40
32.38
32.38
2.70
30.61
30.61
2.41
33.03
31.22
2.71
30.91
30.11
2.41
33.69
25.26
2.71
31.48
24.22
2.44
36.40
26.32
2.74
34.03
25.28
2.48
40.20
21.29
2.77
37.60
20.30
2.43
33.86
33.86
2.74
31.97
31.97
2.44
33.95
33.86
2.74
32.02
32.02
2.44
34.43
27.03
2.74
32.13
25.96
2.47
37.17
28.23
2.76
34.71
27.15
2.51
41.01
22.49
2.80
38.32
21.48
25HNB636C**31 Outdoor Section With FV4CNB006 Indoor Section --- Low
1.73
22.32
22.32
2.06
20.47
20.47
1.72
22.77
21.00
2.06
20.65
19.36
1.72
23.23
17.00
2.05
21.04
15.58
1.70
25.29
17.79
2.04
22.92
16.32
1.67
28.18
14.50
2.01
25.56
13.21
1.72
22.98
22.98
2.06
21.07
21.07
1.72
23.18
22.04
2.06
21.11
21.11
1.72
23.59
17.73
2.06
21.34
16.26
1.70
25.67
18.57
2.04
23.25
17.06
1.68
28.60
15.01
2.02
25.92
13.69
1.72
23.60
23.60
2.06
21.61
21.61
1.72
23.64
23.64
2.06
21.65
21.65
1.72
23.91
18.45
2.06
21.61
16.93
1.70
26.01
19.34
2.04
23.53
17.78
1.68
28.96
15.51
2.02
26.22
14.15
1.73
24.68
24.68
2.06
22.57
22.57
1.73
24.72
24.72
2.06
22.61
22.61
1.73
24.44
19.85
2.07
22.06
18.24
1.71
26.56
20.85
2.05
23.99
19.19
1.68
29.55
16.47
2.02
26.71
15.05
Total
System
KW**
DETAILED COOLING CAPACITIES# CONTINUED
115 (46.1)
18.58
18.62
18.80
20.50
22.91
19.11
19.14
19.06
20.78
23.21
19.59
19.63
19.29
21.02
23.45
20.43
20.47
19.67
21.42
23.87
27.24
27.78
28.37
30.72
34.00
28.02
28.25
28.78
31.14
34.44
28.73
28.77
29.13
31.49
34.83
29.94
29.98
29.69
32.08
35.44
Total
18.58
18.62
14.16
14.87
11.93
19.11
19.14
14.80
15.56
12.37
19.59
19.63
15.43
16.24
12.81
20.43
20.47
16.65
17.56
13.65
27.24
26.41
21.35
22.28
18.05
28.02
27.68
22.25
23.24
18.66
28.73
28.77
23.13
24.18
19.26
29.94
29.98
24.84
26.02
20.41
Sens‡
Capacity MBtuh†
25HNB6C
2.46
2.46
2.46
2.44
2.41
2.46
2.46
2.46
2.44
2.42
2.46
2.46
2.46
2.44
2.42
2.46
2.46
2.47
2.45
2.42
3.03
3.03
3.04
3.06
3.09
3.04
3.05
3.05
3.07
3.10
3.06
3.06
3.07
3.09
3.12
3.09
3.09
3.09
3.11
3.15
Total
System
KW**
2.93
2.93
2.93
2.91
2.88
2.93
2.93
2.94
2.91
2.89
2.93
2.93
2.94
2.92
2.89
2.94
2.94
2.95
2.92
2.90
3.44
3.44
3.44
3.47
3.50
3.45
3.45
3.46
3.48
3.51
3.47
3.47
3.47
3.49
3.52
3.50
3.50
3.50
3.52
3.55
Total
System
KW**
125 (51.7)
16.64
16.67
16.53
18.05
20.21
17.10
17.13
16.73
18.28
20.45
17.51
17.54
16.92
18.47
20.65
18.24
18.27
17.25
18.80
20.98
25.34
25.47
25.95
28.13
31.17
26.04
26.08
26.30
28.48
31.56
26.66
26.70
26.60
28.79
31.88
27.74
27.78
27.07
29.28
32.39
Total
16.64
16.67
12.76
13.43
10.66
17.10
17.13
13.35
14.07
11.08
17.51
17.54
13.93
14.70
11.48
18.24
18.27
15.06
15.93
12.26
25.34
25.23
20.24
21.16
16.98
26.04
26.08
21.12
22.10
17.58
26.66
26.70
21.97
23.03
18.16
27.74
27.78
23.64
24.82
19.28
Sens‡
Capacity MBtuh†
3.49
3.49
3.49
3.47
3.44
3.49
3.49
3.50
3.47
3.44
3.49
3.49
3.50
3.47
3.44
3.49
3.49
3.51
3.48
3.45
3.90
3.91
3.91
3.93
3.96
3.92
3.92
3.92
3.95
3.98
3.94
3.94
3.94
3.96
3.99
3.97
3.97
3.96
3.99
4.02
Total
System
KW**
16
72 (22.2)
67 (19.4)
63 (17.2)††
62 (16.7)
57 (13.9)
72 (22.2)
67 (19.4)
63 (17.2)††
62 (16.7)
57 (13.9)
72 (22.2)
67 (19.4)
63 (17.2)††
62 (16.7)
57 (13.9)
72 (22.2)
67 (19.4)
63 (17.2)††
62 (16.7)
57 (13.9)
72 (22.2)
67 (19.4)
63 (17.2)††
62 (16.7)
57 (13.9)
72 (22.2)
67 (19.4)
63 (17.2)††
62 (16.7)
57 (13.9)
72 (22.2)
67 (19.4)
63 (17.2)††
62 (16.7)
57 (13.9)
72 (22.2)
67 (19.4)
63 (17.2)††
62 (16.7)
57 (13.9)
EWB
° F (° C)
See notes on pg. 17
1280
1120
1040
960
1600
1400
1300
1200
CFM
EVAPORATOR AIR
Sens‡
42.70
39.41
32.56
33.77
27.96
43.94
41.13
33.75
35.03
28.74
45.06
42.78
34.89
36.24
29.50
47.01
45.88
37.08
38.58
30.93
33.65
31.64
25.87
27.02
22.27
34.67
33.12
26.91
28.13
22.98
35.59
34.53
27.91
29.21
23.67
37.21
37.28
29.85
31.28
24.98
Total
42.70
45.46
46.41
50.09
55.10
43.94
46.21
47.15
50.86
55.89
45.06
46.88
47.79
51.52
56.57
47.01
48.00
48.82
52.57
57.65
33.65
35.08
35.83
38.99
43.33
34.67
35.69
36.41
39.61
44.00
35.59
36.25
36.91
40.13
44.57
37.21
37.28
37.74
40.98
45.50
Capacity MBtuh†
75 (23.9)
1.99
1.98
1.98
1.95
1.92
2.00
1.99
1.98
1.96
1.93
2.00
2.00
1.99
1.97
1.93
2.01
2.01
2.01
1.98
1.95
2.91
2.92
2.93
2.95
2.98
2.94
2.95
2.96
2.98
3.00
2.97
2.98
2.98
3.00
3.03
3.02
3.03
3.03
3.05
3.08
Total
System
KW**
30.83
31.83
32.50
35.42
39.42
31.75
32.38
33.00
35.95
40.00
32.58
32.90
33.44
36.41
40.50
34.04
34.09
34.16
37.14
41.30
41.39
43.68
44.59
48.12
52.90
42.57
44.38
45.26
48.81
53.62
43.63
44.98
45.84
49.40
54.24
45.45
46.04
46.76
50.34
55.20
Total
30.83
29.19
23.75
24.85
20.37
31.75
30.56
24.72
25.88
21.03
32.58
31.86
25.66
26.89
21.67
34.04
34.09
27.47
28.84
22.90
41.39
38.56
31.70
32.90
27.06
42.57
40.25
32.87
34.14
27.84
43.63
41.87
34.00
35.35
28.58
45.45
44.90
36.17
37.67
30.01
Sens‡
Capacity MBtuh†
85 (29.4)
Total
Sens‡
Capacity MBtuh†
95 (35)
Total
System
KW**
Total
Sens‡
Capacity MBtuh†
105 (40.6)
CONDENSER ENTERING AIR TEMPERATURES ° F (° C)
25HNB648C**31 Outdoor Section With FV4CN(B,F)005 Indoor Section --- High
3.26
39.86
39.86
3.66
38.17
38.17
3.27
41.63
37.58
3.67
39.40
36.53
3.28
42.48
30.72
3.68
40.18
29.67
3.30
45.85
31.92
3.70
43.40
30.88
3.33
50.43
26.08
3.74
47.76
25.04
3.29
40.96
40.96
3.69
39.18
39.18
3.30
42.26
39.25
3.70
39.98
38.15
3.31
43.09
31.87
3.71
40.71
30.81
3.33
46.48
33.15
3.73
43.94
32.10
3.36
51.07
26.84
3.77
48.32
25.79
3.32
41.94
41.94
3.72
40.09
40.09
3.33
42.83
40.84
3.73
40.51
39.67
3.33
43.60
32.99
3.73
41.16
31.92
3.35
47.00
34.35
3.76
44.39
33.28
3.38
51.61
27.58
3.79
48.79
26.52
3.38
43.64
43.64
3.78
41.65
41.65
3.38
43.86
43.45
3.78
41.71
41.71
3.38
44.42
35.15
3.79
41.88
34.05
3.41
47.82
36.66
3.81
45.12
35.57
3.43
52.47
28.99
3.85
49.53
27.91
25HNB648C**31 Outdoor Section With FV4CN(B,F)005 Indoor Section --- Low
2.34
27.95
27.95
2.75
25.05
25.05
2.33
28.52
26.72
2.74
25.24
24.22
2.33
29.09
21.61
2.74
25.67
19.49
2.30
31.77
22.66
2.71
28.12
20.50
2.27
35.44
18.46
2.68
31.46
16.57
2.35
28.77
28.77
2.75
25.77
25.77
2.34
29.03
27.96
2.75
25.82
25.82
2.34
29.53
22.52
2.74
26.04
20.33
2.31
32.23
23.63
2.72
28.49
21.39
2.28
35.94
19.08
2.69
31.87
17.14
2.35
29.51
29.51
2.75
26.43
26.43
2.35
29.57
29.57
2.75
26.47
26.47
2.35
29.91
23.39
2.75
26.37
21.15
2.32
32.62
24.57
2.73
28.82
22.27
2.29
36.36
19.67
2.70
32.23
17.70
2.36
30.81
30.81
2.77
27.57
27.57
2.36
30.86
30.86
2.77
27.62
27.62
2.36
30.54
25.09
2.77
26.89
22.71
2.34
33.25
26.39
2.75
29.36
23.96
2.31
37.06
20.82
2.72
32.80
18.76
Total
System
KW**
DETAILED COOLING CAPACITIES# CONTINUED
3.21
3.21
3.20
3.18
3.15
3.21
3.21
3.21
3.19
3.16
3.22
3.22
3.22
3.20
3.17
3.23
3.23
3.24
3.22
3.19
4.13
4.14
4.15
4.18
4.22
4.16
4.17
4.18
4.21
4.25
4.19
4.20
4.20
4.23
4.27
4.26
4.26
4.26
4.29
4.33
Total
System
KW**
115 (46.1)
22.16
22.20
22.29
24.49
27.50
22.79
22.83
22.60
24.81
27.85
23.36
23.40
22.86
25.08
28.14
24.35
24.38
23.31
25.52
28.59
36.35
37.07
37.76
40.80
44.93
37.28
37.61
38.22
41.27
45.41
38.12
38.18
38.61
41.67
45.81
39.54
39.60
39.24
42.28
46.44
Total
22.16
22.20
17.41
18.37
14.72
22.79
22.83
18.19
19.20
15.25
23.36
23.40
18.93
20.01
15.76
24.35
24.38
20.37
21.56
16.75
36.35
35.41
28.58
29.80
23.95
37.28
36.96
29.71
31.01
24.70
38.12
38.18
30.81
32.19
25.41
39.54
39.60
32.91
34.45
26.80
Sens‡
Capacity MBtuh†
25HNB6C
3.75
3.74
3.74
3.72
3.69
3.75
3.75
3.75
3.73
3.70
3.76
3.76
3.76
3.74
3.71
3.77
3.77
3.78
3.76
3.73
4.69
4.69
4.70
4.74
4.78
4.72
4.72
4.73
4.77
4.81
4.75
4.75
4.76
4.79
4.84
4.82
4.82
4.81
4.85
4.90
Total
System
KW**
125 (51.7)
19.33
19.36
18.99
20.96
23.63
19.87
19.90
19.24
21.21
23.90
20.35
20.38
19.46
21.43
24.13
21.18
21.21
19.84
21.80
24.49
34.44
34.69
35.25
38.11
41.99
35.28
35.34
35.64
38.51
42.39
36.04
36.09
35.98
38.84
42.73
37.32
37.36
36.51
39.37
43.25
Total
19.33
19.36
15.39
16.30
12.93
19.87
19.90
16.10
17.07
13.41
20.35
20.38
16.78
17.81
13.88
21.18
21.21
18.07
19.22
14.79
34.44
34.21
27.48
28.70
22.85
35.28
35.34
28.59
29.90
23.58
36.04
36.09
29.67
31.06
24.30
37.32
37.36
31.74
33.30
25.67
Sens‡
Capacity MBtuh†
4.36
4.36
4.37
4.34
4.31
4.37
4.37
4.38
4.35
4.32
4.38
4.37
4.39
4.36
4.33
4.39
4.39
4.41
4.38
4.35
5.34
5.35
5.35
5.40
5.45
5.38
5.38
5.38
5.43
5.48
5.42
5.42
5.41
5.46
5.51
5.48
5.49
5.47
5.51
5.57
Total
System
KW**
17
72 (22.2)
67 (19.4)
63 (17.2)††
62 (16.7)
57 (13.9)
72 (22.2)
67 (19.4)
63 (17.2)††
62 (16.7)
57 (13.9)
72 (22.2)
67 (19.4)
63 (17.2)††
62 (16.7)
57 (13.9)
72 (22.2)
67 (19.4)
63 (17.2)††
62 (16.7)
57 (13.9)
72 (22.2)
67 (19.4)
63 (17.2)††
62 (16.7)
57 (13.9)
72 (22.2)
67 (19.4)
63 (17.2)††
62 (16.7)
57 (13.9)
72 (22.2)
67 (19.4)
63 (17.2)††
62 (16.7)
57 (13.9)
72 (22.2)
67 (19.4)
63 (17.2)††
62 (16.7)
57 (13.9)
EWB
° F (° C)
Sens‡
51.61
49.03
40.39
41.97
34.72
53.11
51.18
41.87
43.55
35.71
54.46
53.25
43.31
45.08
36.66
56.83
57.13
46.05
48.03
38.47
41.27
39.35
32.14
33.46
27.41
42.46
41.17
33.40
34.81
28.25
43.54
42.90
34.63
36.12
29.08
45.41
45.49
37.00
38.66
30.65
Total
51.61
54.77
55.96
60.55
66.85
53.11
55.69
56.85
61.48
67.83
54.46
56.48
57.62
62.27
68.68
56.83
57.84
58.85
63.55
70.02
41.27
42.97
43.88
47.49
52.45
42.46
43.67
44.54
48.17
53.17
43.54
44.29
45.11
48.75
53.79
45.41
45.49
46.03
49.70
54.77
Capacity MBtuh†
75 (23.9)
2.45
2.43
2.43
2.40
2.36
2.45
2.45
2.44
2.41
2.37
2.46
2.46
2.45
2.42
2.38
2.48
2.48
2.48
2.45
2.41
3.56
3.59
3.60
3.65
3.71
3.61
3.64
3.65
3.69
3.75
3.66
3.68
3.69
3.73
3.80
3.75
3.76
3.77
3.81
3.88
Total
System
KW**
36.79
37.92
38.70
41.89
46.29
37.83
38.51
39.25
42.46
46.90
38.76
39.07
39.72
42.95
47.41
40.37
40.43
40.48
43.72
48.21
49.90
52.50
53.60
57.92
63.83
51.30
53.31
54.40
58.74
64.70
52.57
54.04
55.08
59.45
65.44
54.75
55.30
56.15
60.55
66.60
Total
36.79
36.10
29.32
30.56
24.87
37.83
37.77
30.50
31.82
25.66
38.76
39.35
31.64
33.05
26.42
40.37
40.43
33.85
35.42
27.89
49.90
47.37
38.83
40.35
33.13
51.30
49.45
40.27
41.88
34.08
52.57
51.45
41.67
43.37
35.01
54.75
55.14
44.33
46.24
36.76
Sens‡
Capacity MBtuh†
85 (29.4)
95 (35)
Total
Sens‡
Capacity MBtuh†
Total
System
KW**
105 (40.6)
Total
Sens‡
Capacity MBtuh†
25HNB660C**31 Outdoor Section With FV4CNB006 Indoor Section --- High
3.94
48.10
48.10
4.37
46.09
46.09
3.96
50.12
45.69
4.39
47.51
43.92
3.97
51.15
37.26
4.40
48.45
35.61
4.01
55.18
38.71
4.44
52.18
37.01
4.07
60.69
31.53
4.49
57.28
29.87
3.98
49.40
49.40
4.41
47.27
47.27
4.00
50.86
47.70
4.43
48.17
45.86
4.01
51.85
38.66
4.44
49.04
36.96
4.05
55.90
40.20
4.48
52.79
38.46
4.11
61.44
32.45
4.54
57.91
30.76
4.03
50.56
50.56
4.46
48.32
48.32
4.04
51.52
49.63
4.47
48.77
47.65
4.05
52.43
40.01
4.48
49.55
38.28
4.10
56.50
41.65
4.52
53.30
39.87
4.16
62.06
33.34
4.58
58.44
31.62
4.12
52.55
52.55
4.55
50.11
50.11
4.12
52.69
52.60
4.55
50.18
50.18
4.13
53.37
42.61
4.56
50.34
40.81
4.18
57.45
44.45
4.60
54.09
42.59
4.24
63.06
35.04
4.66
59.25
33.26
25HNB660C**31 Outdoor Section With FV4CNB006 Indoor Section --- Low
2.83
32.29
32.29
3.27
27.87
27.87
2.82
32.87
32.82
3.27
28.01
27.79
2.82
33.52
26.49
3.26
28.48
23.70
2.79
36.33
27.67
3.24
30.92
24.82
2.75
40.20
22.34
3.20
34.27
19.86
2.84
33.17
33.17
3.28
28.61
28.61
2.84
33.41
34.32
3.28
28.66
28.66
2.83
33.97
27.58
3.28
28.84
24.71
2.80
36.79
28.84
3.25
31.28
25.89
2.76
40.68
23.07
3.21
34.65
20.53
2.85
33.97
33.97
3.29
29.28
29.28
2.85
34.02
34.02
3.29
29.32
29.32
2.84
34.35
28.64
3.29
29.15
25.69
2.81
37.18
29.97
3.26
31.59
26.94
2.77
41.08
23.77
3.22
34.97
21.18
2.87
35.34
35.34
3.31
30.42
30.42
2.87
35.39
35.39
3.31
30.46
30.46
2.87
34.98
30.69
3.32
29.64
27.56
2.84
37.82
32.17
3.29
32.09
28.97
2.80
41.73
25.13
3.25
35.47
22.44
Total
System
KW**
CONDENSER ENTERING AIR TEMPERATURES ° F (° C)
3.78
3.78
3.77
3.75
3.71
3.79
3.79
3.79
3.76
3.72
3.80
3.80
3.80
3.77
3.74
3.82
3.82
3.83
3.80
3.76
4.87
4.88
4.89
4.93
4.99
4.91
4.92
4.93
4.97
5.03
4.96
4.96
4.97
5.01
5.07
5.05
5.05
5.05
5.09
5.15
Total
System
KW**
115 (46.1)
23.62
23.66
23.68
25.76
28.63
24.22
24.26
23.96
26.04
28.91
24.76
24.80
24.19
26.28
29.15
25.69
25.72
24.58
26.67
29.52
43.74
44.55
45.37
48.79
53.46
44.79
45.16
45.87
49.30
53.98
45.73
45.80
46.29
49.72
54.40
47.32
47.37
46.95
50.35
55.05
Total
23.62
23.66
21.00
22.04
17.46
24.22
24.26
21.92
23.03
18.07
24.76
24.80
22.80
24.00
18.67
25.69
25.72
24.51
25.85
19.83
43.74
42.00
33.84
35.19
28.12
44.79
43.80
35.16
36.60
28.97
45.73
45.80
36.43
37.98
29.80
47.32
47.37
38.88
40.62
31.39
Sens‡
Capacity MBtuh†
4.35
4.35
4.35
4.33
4.29
4.36
4.36
4.37
4.34
4.30
4.38
4.38
4.38
4.36
4.32
4.40
4.40
4.42
4.39
4.35
5.44
5.45
5.46
5.50
5.55
5.49
5.49
5.50
5.54
5.59
5.53
5.53
5.54
5.58
5.63
5.62
5.62
5.62
5.66
5.71
Total
System
KW**
EWB — Entering Wet Bulb 1.
NOTE: When the required data falls between the published data, interpolation may be performed. Extrapolation is not an acceptable practice.
25HNB6C
125 (51.7)
19.59
19.62
19.20
20.94
23.33
20.06
20.09
19.40
21.15
23.53
20.49
20.52
19.59
21.33
23.71
21.22
21.24
19.90
21.63
23.96
40.97
41.19
41.83
44.94
49.17
41.89
41.95
42.23
45.33
49.57
42.70
42.76
42.57
45.66
49.90
44.06
44.11
43.11
46.16
50.39
Total
19.59
19.62
18.40
19.38
15.17
20.06
20.09
19.23
20.28
15.72
20.49
20.52
20.03
21.15
16.27
21.22
21.24
21.53
22.81
17.33
40.97
39.81
31.92
33.24
26.24
41.89
41.95
33.19
34.61
27.06
42.70
42.76
34.43
35.94
27.87
44.06
44.11
36.80
38.50
29.42
Sens‡
Capacity MBtuh†
# Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per AHRI standard 210/240--- 08. If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.
{{ At TVA rating indoor condition (75_F edb/63_F ewb). All other indoor air temperatures are at 80_F edb.
** System kw is total of indoor and outdoor unit kilowatts.
} Sensible capacities shown are based on 80_F (27_C) entering air at the indoor coil. For sensible capacities at other than 80_F (27_C), deduct 835 Btuh
(245 kW) per 1000 CFM (480 L/S) of indoor coil air for each degree below 80_F (27_C), or add 835 Btuh (245 kW) per 1000 CFM (480 L/S) of indoor coil air per degree above 80_F (27_C).
{ Total and sensible capacities are net capacities. Blower motor heat has been subtracted.
1600
1400
1300
1200
2000
1750
1625
1500
CFM
EVAPORATOR AIR
DETAILED COOLING CAPACITIES# CONTINUED
5.01
5.01
5.02
4.99
4.95
5.02
5.02
5.03
5.00
4.97
5.03
5.03
5.05
5.02
4.98
5.06
5.06
5.08
5.05
5.01
6.09
6.09
6.10
6.14
6.19
6.14
6.14
6.14
6.18
6.23
6.18
6.19
6.18
6.22
6.27
6.27
6.27
6.26
6.30
6.35
Total
System
KW**
18
---3 ( ---19.4)
9.13
9.20
9.28
9.42
8.72
8.80
8.89
9.04
8.25
8.34
8.43
8.58
4.07
4.13
4.18
4.29
4.91
4.97
5.04
5.14
4.47
4.55
4.60
4.72
650
700
800
600
650
700
800
600
650
700
800
480
520
560
640
480
520
560
640
480
520
560
640
Total
4.34
4.23
4.18
4.11
4.73
4.64
4.57
4.52
3.95
3.84
3.80
3.75
7.90
7.76
7.67
7.59
8.31
8.18
8.10
8.03
8.67
8.54
8.47
8.40
Integ*
Capacity MBtuh
600
CFM
See notes on pg. 21
75
(23.9)
70
(21.1)
65
(18.3)
75
(23.9)
70
(21.1)
65
(18.3)
EDB
° F (° C)
INDOOR AIR
1.26
1.25
1.25
1.26
1.19
1.18
1.18
1.19
1.09
1.08
1.08
1.08
1.51
1.52
1.52
1.52
1.44
1.45
1.45
1.46
1.37
1.38
1.38
1.39
Total
Sys.
KW†
6.74
6.56
6.47
6.38
7.27
7.11
7.02
6.93
7.72
7.57
7.49
7.41
11.57
11.37
11.25
11.13
12.04
11.85
11.73
11.61
12.47
12.29
12.17
12.06
Total
6.19
6.03
5.94
5.86
6.68
6.53
6.45
6.37
7.09
6.96
6.88
6.81
10.63
10.45
10.34
10.23
11.07
10.89
10.78
10.67
11.46
11.29
11.19
11.08
Integ*
Capacity MBtuh
7 ( ---13.9)
1.29
1.29
1.29
1.30
1.22
1.22
1.23
1.23
1.15
1.16
1.16
1.17
1.60
1.61
1.61
1.62
1.53
1.54
1.54
1.55
1.46
1.47
1.47
1.48
Total
Sys.
KW†
HEAT PUMP HEATING PERFORMANCE
9.77
9.54
9.40
9.26
10.33
10.10
9.97
9.84
10.81
10.60
10.47
10.36
15.14
14.93
14.81
14.66
15.48
15.29
15.18
15.05
15.80
15.61
15.50
15.38
Total
Total
Sys.
KW†
Total
Integ*
Capacity MBtuh
27 ( ---2.8)
Total
Sys.
KW†
Total
Integ*
Capacity MBtuh
37 (2.8)
Total
Sys.
KW†
OUTDOOR COIL ENTERING AIR TEMPERATURES ° F (° C)
1.70
1.72
1.73
1.75
1.63
1.64
1.66
1.67
1.55
1.57
1.58
1.60
18.14
17.89
17.75
17.58
18.54
18.29
18.14
17.97
18.92
18.67
18.53
18.36
16.11
15.89
15.76
15.62
16.47
16.24
16.11
15.96
16.80
16.58
16.45
16.31
1.80
1.83
1.85
1.87
1.73
1.75
1.77
1.79
1.65
1.68
1.70
1.72
21.39
21.07
20.88
20.67
21.85
21.53
21.33
21.11
22.30
21.97
21.78
21.56
19.47
19.18
19.00
18.81
19.88
19.59
19.41
19.21
20.29
20.00
19.82
19.62
1.93
1.96
1.99
2.02
1.85
1.88
1.90
1.93
1.77
1.80
1.83
1.85
8.91
8.70
8.57
8.44
9.42
9.21
9.09
8.97
9.85
9.66
9.55
9.44
1.33
1.34
1.35
1.36
1.27
1.27
1.28
1.29
1.20
1.21
1.22
1.23
12.62
12.30
12.13
11.95
13.20
12.88
12.70
12.53
14.07
13.50
13.27
13.10
11.20
10.93
10.77
10.61
11.72
11.44
11.28
11.13
12.50
11.99
11.78
11.63
1.36
1.38
1.39
1.40
1.30
1.31
1.32
1.34
1.24
1.25
1.26
1.28
15.60
15.30
15.12
14.90
16.03
15.74
15.56
15.37
16.46
16.15
15.98
15.80
14.20
13.93
13.76
13.56
14.59
14.32
14.16
13.99
14.98
14.70
14.54
14.38
1.39
1.42
1.43
1.46
1.32
1.35
1.37
1.39
1.26
1.28
1.30
1.32
25HNB624C**32 Outdoor Section With FV4CNF002 Indoor Section --- Low
13.81
13.61
13.50
13.36
14.11
13.94
13.84
13.72
14.40
14.24
14.13
14.02
25HNB624C**32 Outdoor Section With FV4CNF002 Indoor Section --- High
Integ*
Capacity MBtuh
17 ( ---8.3)
17.79
17.44
17.24
17.02
18.26
17.90
17.69
17.46
18.73
18.36
18.13
17.89
24.89
24.50
24.27
24.00
25.40
25.00
24.76
24.49
25.92
25.50
25.25
24.98
Total
17.79
17.44
17.24
17.02
18.26
17.90
17.69
17.46
18.73
18.36
18.13
17.89
24.89
24.50
24.27
24.00
25.40
25.00
24.76
24.49
25.92
25.50
25.25
24.98
Integ*
Capacity MBtuh
47 (8.3)
25HNB6C
1.41
1.44
1.46
1.49
1.34
1.37
1.39
1.42
1.27
1.30
1.33
1.35
2.07
2.11
2.15
2.19
1.99
2.03
2.06
2.10
1.91
1.95
1.98
2.01
Total
System
KW†
57 (13.9)
19.96
19.54
19.30
19.03
20.46
20.02
19.77
19.49
20.95
20.51
20.24
19.96
28.65
28.18
27.90
27.58
29.21
28.74
28.44
28.12
29.78
29.29
28.99
28.65
Total
19.96
19.54
19.30
19.03
20.46
20.02
19.77
19.49
20.95
20.51
20.24
19.96
28.65
28.18
27.90
27.58
29.21
28.74
28.44
28.12
29.78
29.29
28.99
28.65
Integ*
Capacity MBtuh
1.43
1.47
1.50
1.54
1.36
1.40
1.43
1.47
1.29
1.33
1.36
1.39
2.24
2.30
2.34
2.39
2.15
2.21
2.24
2.29
2.07
2.12
2.16
2.20
Total
Sys.
KW†
67 (19.4)
22.12
21.63
21.35
21.05
22.63
22.13
21.84
23.94
23.15
22.62
22.32
21.98
32.54
32.02
31.70
31.33
33.14
32.62
32.27
31.90
33.75
33.21
32.86
32.45
Total
22.12
21.63
21.35
21.05
22.63
22.13
21.84
23.94
23.15
22.62
22.32
21.98
32.54
32.02
31.70
31.33
33.14
32.62
32.27
31.90
33.75
33.21
32.86
32.45
Integ*
Capacity MBtuh
1.47
1.52
1.55
1.60
1.39
1.45
1.48
1.83
1.32
1.37
1.41
1.45
2.46
2.53
2.58
2.64
2.36
2.43
2.47
2.54
2.27
2.33
2.38
2.43
Total
Sys.
KW†
19
---3 ( ---19.4)
13.75
13.88
13.99
14.18
13.21
13.33
13.44
13.63
12.66
12.77
12.88
13.05
9.56
9.69
9.80
9.97
8.75
8.86
8.96
9.14
7.89
7.99
8.09
8.25
975
1050
1200
900
975
1050
1200
900
975
1050
1200
720
780
840
960
720
780
840
960
720
780
840
960
Total
7.59
7.44
7.35
7.26
8.41
8.25
8.15
8.05
9.17
9.01
8.91
8.80
12.01
11.85
11.75
11.65
12.54
12.36
12.26
12.15
13.05
12.87
12.77
12.65
Integ*
Capacity MBtuh
900
CFM
See notes on pg. 21
75
(23.9)
70
(21.1)
65
(18.3)
75
(23.9)
70
(21.1)
65
(18.3)
EDB
° F (° C)
INDOOR AIR
1.82
1.82
1.82
1.82
1.75
1.75
1.75
1.75
1.68
1.68
1.68
1.68
2.09
2.09
2.09
2.10
1.99
1.99
1.99
2.00
1.89
1.90
1.90
1.90
Total
Sys.
KW†
11.44
11.29
11.17
11.03
12.26
12.05
11.92
11.78
13.00
12.78
12.65
12.50
17.31
17.11
16.98
16.83
17.89
17.66
17.52
17.38
18.44
18.20
18.06
17.91
Total
10.51
10.37
10.26
10.14
11.27
11.07
10.96
10.83
11.94
11.74
11.62
11.49
15.91
15.72
15.60
15.47
16.44
16.23
16.10
15.97
16.94
16.72
16.60
16.46
Integ*
Capacity MBtuh
7 ( ---13.9)
1.81
1.82
1.82
1.83
1.73
1.74
1.74
1.75
1.66
1.67
1.67
1.68
2.19
2.20
2.21
2.22
2.08
2.09
2.10
2.11
1.98
1.99
2.00
2.01
Total
Sys.
KW†
14.82
14.62
14.47
14.31
15.56
15.30
15.16
14.99
16.23
15.97
15.82
15.65
21.92
21.63
21.45
21.26
22.99
22.76
22.62
21.98
23.36
23.16
23.03
22.88
Total
Total
Sys.
KW†
Total
Integ*
Capacity MBtuh
27 ( ---2.8)
Total
Sys.
KW†
Total
Integ*
Capacity MBtuh
37 (2.8)
Total
Sys.
KW†
OUTDOOR COIL ENTERING AIR TEMPERATURES ° F (° C)
2.30
2.32
2.33
2.35
2.20
2.22
2.24
2.25
2.09
2.11
2.13
2.15
26.72
26.46
26.31
26.16
27.13
26.87
26.72
26.55
27.54
27.27
27.11
26.93
23.73
23.50
23.37
23.24
24.09
23.86
23.73
23.58
24.46
24.22
24.08
23.92
2.42
2.46
2.48
2.52
2.30
2.34
2.36
2.39
2.19
2.22
2.25
2.28
31.04
30.70
30.51
30.29
31.52
31.18
30.98
30.75
32.02
31.66
31.46
31.23
28.24
27.94
27.76
27.56
28.69
28.38
28.19
27.99
29.14
28.81
28.63
28.42
2.55
2.59
2.63
2.67
2.42
2.47
2.50
2.54
2.31
2.35
2.38
2.42
13.51
13.33
13.20
13.05
14.18
13.95
13.82
13.67
14.80
14.56
14.42
14.27
1.81
1.82
1.83
1.84
1.73
1.74
1.75
1.76
1.65
1.66
1.67
1.69
18.25
18.01
17.84
17.64
18.93
18.65
18.47
18.26
19.57
19.26
19.08
18.88
16.21
16.00
15.84
15.67
16.81
16.56
16.41
16.22
17.38
17.11
16.95
16.77
1.82
1.84
1.86
1.87
1.73
1.75
1.77
1.79
1.65
1.67
1.69
1.70
21.76
21.44
21.19
20.94
22.84
22.56
22.39
21.73
23.28
23.02
22.85
22.67
19.80
19.51
19.29
19.06
20.79
20.53
20.38
19.77
21.19
20.95
20.80
20.63
1.83
1.87
1.89
1.92
1.76
1.79
1.82
1.83
1.67
1.70
1.73
1.75
25HNB636C**31 Outdoor Section With FV4CNB006 Indoor Section --- Low
19.98
19.72
19.56
19.38
20.96
20.75
20.63
20.04
21.30
21.12
21.00
20.87
25HNB636C**31 Outdoor Section With FV4CNB006 Indoor Section --- High
Integ*
Capacity MBtuh
17 ( ---8.3)
HEAT PUMP HEATING PERFORMANCE CONTINUED
47 (8.3)
25.07
24.79
24.62
24.42
25.51
25.20
25.02
24.82
25.95
25.64
25.45
25.24
35.66
35.24
34.98
34.68
36.23
35.80
35.54
35.23
36.81
36.37
36.10
35.79
Integ*
25HNB6C
25.07
24.79
24.62
24.42
25.51
25.20
25.02
24.82
25.95
25.64
25.45
25.24
35.66
35.24
34.98
34.68
36.23
35.80
35.54
35.23
36.81
36.37
36.10
35.79
Total
Capacity MBtuh
1.86
1.92
1.95
1.99
1.77
1.81
1.85
1.88
1.67
1.72
1.75
1.79
2.70
2.76
2.80
2.85
2.57
2.63
2.67
2.72
2.46
2.51
2.55
2.60
Total
System
KW†
57 (13.9)
27.59
27.22
26.99
26.74
28.07
27.69
27.46
27.20
28.55
28.16
27.93
27.66
40.65
40.09
39.75
39.35
41.38
40.80
40.45
40.04
42.09
41.52
41.16
40.74
Total
27.59
27.22
26.99
26.74
28.07
27.69
27.46
27.20
28.55
28.16
27.93
27.66
40.65
40.09
39.75
39.35
41.38
40.80
40.45
40.04
42.09
41.52
41.16
40.74
Integ*
Capacity MBtuh
1.89
1.95
1.99
2.04
1.79
1.85
1.89
1.94
1.69
1.75
1.79
1.83
2.88
2.96
3.01
3.07
2.73
2.83
2.87
2.93
2.61
2.71
2.75
2.81
Total
Sys.
KW†
67 (19.4)
29.89
29.44
29.17
28.85
30.41
29.95
29.68
29.37
30.92
30.46
30.18
29.86
45.91
45.55
45.14
44.58
46.54
46.28
45.96
45.39
47.10
46.97
46.68
46.22
Total
29.89
29.44
29.17
28.85
30.41
29.95
29.68
29.37
30.92
30.46
30.18
29.86
45.91
45.55
45.14
44.58
46.54
46.28
45.96
45.39
47.10
46.97
46.68
46.22
Integ*
Capacity MBtuh
1.93
2.00
2.05
2.11
1.82
1.90
1.95
2.00
1.72
1.80
1.84
1.90
3.05
3.15
3.22
3.33
2.92
3.01
3.08
3.18
2.79
2.88
2.94
3.03
Total
Sys.
KW†
20
16.25
9.89
18.16
18.34
17.65
17.75
17.87
18.11
17.13
17.26
17.40
17.67
10.75
10.91
11.03
11.26
9.82
9.96
10.08
10.31
9.86
9.99
9.77
9.98
1400
1600
1200
1300
1400
1600
1200
1300
1400
1600
960
1040
1120
1280
960
1040
1120
1280
960
1040
1120
1280
9.18
8.99
9.19
9.07
9.48
9.28
9.16
9.03
10.36
10.15
10.03
16.01
15.88
15.76
16.66
16.44
16.33
16.24
16.88
16.70
16.61
18.06
16.53
17.97
Integ*
1300
Total
Capacity MBtuh
---3 ( ---19.4)
1200
CFM
See notes on pg. 21
75
(23.9)
70
(21.1)
65
(18.3)
75
(23.9)
70
(21.1)
65
(18.3)
EDB
° F (° C)
INDOOR AIR
2.45
2.44
2.44
2.43
2.33
2.32
2.31
2.31
2.23
2.22
2.22
2.21
3.00
2.99
2.99
2.99
2.83
2.82
2.82
2.82
2.66
2.65
2.65
2.66
Total
Sys.
KW†
14.24
13.94
13.77
13.59
15.26
14.97
14.79
14.61
16.19
15.89
15.72
15.52
22.71
22.38
22.20
22.03
23.27
22.97
22.80
22.65
23.67
23.41
23.28
23.15
Total
13.08
12.81
12.66
12.49
14.02
13.75
13.59
13.43
14.88
14.60
14.45
14.27
20.87
20.57
20.40
20.25
21.38
21.10
20.95
20.81
21.75
21.51
21.39
21.27
Integ*
Capacity MBtuh
7 ( ---13.9)
2.50
2.49
2.49
2.49
2.39
2.38
2.38
2.39
2.28
2.28
2.28
2.28
3.15
3.14
3.15
3.16
2.99
2.99
2.99
3.00
2.83
2.83
2.83
2.84
Total
Sys.
KW†
18.99
18.63
18.41
18.18
19.97
19.61
19.39
19.16
20.85
20.50
20.30
20.06
28.66
28.16
27.91
27.68
29.91
29.59
29.41
29.20
30.22
29.97
29.83
29.65
Total
Total
Sys.
KW†
Total
Integ*
Capacity MBtuh
27 ( ---2.8)
Total
Sys.
KW†
Total
Integ*
Capacity MBtuh
37 (2.8)
Total
Sys.
KW†
OUTDOOR COIL ENTERING AIR TEMPERATURES ° F (° C)
3.33
3.33
3.34
3.36
3.19
3.20
3.21
3.23
3.03
3.04
3.06
3.08
34.84
34.43
34.20
33.94
35.38
34.99
34.77
34.52
35.87
35.51
35.29
35.05
30.94
30.58
30.37
30.15
31.42
31.08
30.88
30.66
31.86
31.53
31.35
31.13
3.54
3.56
3.58
3.61
3.38
3.40
3.42
3.45
3.22
3.25
3.27
3.29
40.64
40.12
39.82
39.48
41.34
40.82
40.52
40.17
42.01
41.51
41.21
40.86
36.98
36.51
36.23
35.93
37.62
37.15
36.87
36.56
38.23
37.77
37.50
37.19
3.76
3.79
3.82
3.86
3.60
3.63
3.66
3.69
3.45
3.48
3.50
3.54
17.32
16.99
16.78
16.58
18.21
17.88
17.68
17.47
19.01
18.69
18.50
18.29
2.55
2.56
2.56
2.57
2.43
2.44
2.45
2.46
2.32
2.33
2.34
2.35
23.58
23.13
22.88
22.58
24.53
24.08
23.82
23.53
25.43
24.98
24.72
24.42
20.94
20.55
20.32
20.06
21.78
21.39
21.16
20.89
22.58
22.18
21.96
21.69
2.60
2.62
2.64
2.66
2.48
2.50
2.52
2.54
2.36
2.39
2.40
2.42
28.92
27.91
27.47
27.03
29.61
29.21
28.96
28.66
30.22
29.85
29.61
29.36
26.32
25.40
25.00
24.60
26.95
26.58
26.35
26.08
27.50
27.16
26.94
26.71
2.69
2.71
2.73
2.76
2.56
2.60
2.62
2.66
2.43
2.47
2.49
2.53
25HNB648C**31 Outdoor Section With FV4CN(B,F)005 Indoor Section --- Low
26.13
25.67
25.45
25.23
27.27
26.98
26.81
26.63
27.56
27.33
27.19
27.03
25HNB648C**31 Outdoor Section With FV4CN(B,F)005 Indoor Section --- High
Integ*
Capacity MBtuh
17 ( ---8.3)
HEAT PUMP HEATING PERFORMANCE CONTINUED
32.79
32.32
32.04
31.72
33.48
33.00
32.72
32.39
34.15
33.67
33.39
33.07
46.82
46.19
45.82
45.41
47.64
47.00
46.62
46.20
48.45
47.81
47.42
47.00
Total
32.79
32.32
32.04
31.72
33.48
33.00
32.72
32.39
34.15
33.67
33.39
33.07
46.82
46.19
45.82
45.41
47.64
47.00
46.62
46.20
48.45
47.81
47.42
47.00
Integ*
Capacity MBtuh
47 (8.3)
25HNB6C
2.76
2.81
2.85
2.89
2.61
2.67
2.71
2.75
2.48
2.53
2.57
2.61
4.01
4.07
4.11
4.16
3.85
3.90
3.93
3.98
3.69
3.74
3.77
3.82
Total
System
KW†
57 (13.9)
36.74
36.17
35.82
35.43
37.49
36.91
36.57
36.17
38.21
37.64
37.30
36.89
53.46
52.61
52.16
51.70
54.36
53.59
53.06
52.55
55.23
54.58
54.04
53.46
Total
36.74
36.17
35.82
35.43
37.49
36.91
36.57
36.17
38.21
37.64
37.30
36.89
53.46
52.61
52.16
51.70
54.36
53.59
53.06
52.55
55.23
54.58
54.04
53.46
Integ*
Capacity MBtuh
2.84
2.91
2.96
3.01
2.69
2.76
2.81
2.87
2.55
2.62
2.67
2.72
4.27
4.37
4.44
4.51
4.09
4.18
4.25
4.32
3.92
4.01
4.07
4.15
Total
Sys.
KW†
67 (19.4)
40.87
40.16
39.74
39.28
41.68
40.95
40.53
40.06
42.41
41.76
41.32
40.84
59.84
59.46
59.15
58.75
60.66
60.34
60.01
59.63
61.47
61.21
60.92
60.50
Total
40.87
40.16
39.74
39.28
41.68
40.95
40.53
40.06
42.41
41.76
41.32
40.84
59.84
59.46
59.15
58.75
60.66
60.34
60.01
59.63
61.47
61.21
60.92
60.50
Integ*
Capacity MBtuh
2.94
3.04
3.10
3.17
2.77
2.89
2.95
3.02
2.62
2.73
2.80
2.87
4.58
4.68
4.75
4.85
4.39
4.49
4.56
4.65
4.22
4.31
4.37
4.46
Total
Sys.
KW†
21
23.79
24.02
24.26
24.72
22.84
23.07
23.30
23.75
21.87
22.08
22.32
22.75
13.69
13.81
13.95
14.22
12.56
12.73
12.89
13.13
12.10
12.28
12.44
11.89
1625
1750
2000
1500
1625
1750
2000
1500
1625
1750
2000
1200
1300
1400
1600
1200
1300
1400
1600
1200
1300
1400
1600
Total
1500
CFM
10.94
11.44
11.30
11.14
12.08
11.86
11.72
11.56
13.08
12.83
12.71
12.59
20.93
20.53
20.32
20.12
21.85
21.44
21.22
21.01
22.74
22.32
22.09
21.88
Integ*
Capacity MBtuh
---3 ( ---19.4)
2.95
2.94
2.93
2.92
2.83
2.81
2.80
2.79
2.71
2.69
2.68
2.67
3.60
3.57
3.55
3.54
3.46
3.42
3.41
3.40
3.32
3.28
3.27
3.26
Total
Sys.
KW†
17.95
17.58
17.37
17.17
19.16
18.80
18.60
18.42
20.21
19.87
19.67
19.50
28.63
28.18
27.94
27.71
29.44
28.99
28.74
28.50
30.26
29.79
29.54
29.29
Total
16.50
16.15
15.96
15.78
17.61
17.28
17.09
16.93
18.57
18.26
18.08
17.92
26.31
25.90
25.67
25.46
27.06
26.64
26.41
26.19
27.80
27.38
27.14
26.92
Integ*
Capacity MBtuh
7 ( ---13.9)
3.02
3.00
3.00
3.00
2.89
2.88
2.87
2.87
2.77
2.75
2.75
2.75
3.80
3.77
3.77
3.76
3.64
3.62
3.61
3.61
3.49
3.47
3.46
3.46
Total
Sys.
KW†
23.79
23.32
23.05
22.80
24.93
24.50
24.24
23.98
25.94
25.53
25.29
25.04
36.40
35.20
34.84
34.56
36.85
36.48
36.27
36.04
37.26
36.89
36.69
36.45
Total
Total
Sys.
KW†
Total
Integ*
Capacity MBtuh
27 ( ---2.8)
Total
Sys.
KW†
Total
Integ*
Capacity MBtuh
37 (2.8)
Total
Sys.
KW†
OUTDOOR COIL ENTERING AIR TEMPERATURES ° F (° C)
4.05
4.02
4.02
4.03
3.88
3.87
3.87
3.88
3.71
3.70
3.71
3.72
42.82
42.39
42.15
41.89
43.28
42.85
42.61
42.34
43.75
43.31
43.07
42.81
38.03
37.65
37.43
37.21
38.44
38.06
37.84
37.61
38.86
38.47
38.25
38.02
4.29
4.30
4.31
4.34
4.11
4.11
4.13
4.15
3.93
3.94
3.95
3.97
50.01
49.50
49.21
48.89
50.57
50.06
49.77
49.45
51.14
50.62
50.33
50.01
45.51
45.05
44.78
44.49
46.02
45.55
45.29
45.00
46.53
46.07
45.80
45.51
4.57
4.60
4.62
4.66
4.38
4.40
4.43
4.46
4.20
4.22
4.24
4.27
21.69
21.26
21.02
20.79
22.73
22.33
22.10
21.87
23.65
23.27
23.05
22.83
3.09
3.09
3.09
3.10
2.95
2.96
2.96
2.97
2.82
2.83
2.83
2.84
29.27
28.73
28.41
28.07
30.41
29.87
29.55
29.23
31.45
30.92
30.62
30.30
25.99
25.51
25.23
24.93
27.01
26.53
26.25
25.96
27.93
27.46
27.19
26.91
3.16
3.18
3.19
3.21
3.02
3.04
3.05
3.07
2.89
2.90
2.92
2.94
35.34
34.38
33.69
33.24
36.13
35.67
35.36
35.00
36.86
36.39
36.10
35.80
32.16
31.28
30.66
30.25
32.88
32.46
32.17
31.85
33.54
33.11
32.85
32.58
3.28
3.30
3.31
3.34
3.12
3.16
3.19
3.22
2.97
3.01
3.04
3.07
25HNB660C**31 Outdoor Section With FV4CNB006 Indoor Section --- Low
33.19
32.09
31.76
31.51
33.60
33.26
33.07
32.86
33.97
33.63
33.45
33.23
25HNB660C**31 Outdoor Section With FV4CNB006 Indoor Section --- High
Integ*
Capacity MBtuh
17 ( ---8.3)
47 (8.3)
39.23
38.63
38.28
37.87
40.09
39.50
39.13
38.74
40.89
40.32
39.97
39.55
57.99
57.30
56.94
56.55
58.68
58.00
57.63
57.25
59.34
58.70
58.31
57.93
Total
39.23
38.63
38.28
37.87
40.09
39.50
39.13
38.74
40.89
40.32
39.97
39.55
57.99
57.30
56.94
56.55
58.68
58.00
57.63
57.25
59.34
58.70
58.31
57.93
Integ*
Capacity MBtuh
3.36
3.41
3.45
3.50
3.20
3.25
3.29
3.33
3.04
3.09
3.13
3.18
4.87
4.94
4.98
5.03
4.67
4.74
4.78
4.83
4.47
4.53
4.58
4.63
Total
System
KW†
57 (13.9)
42.79
42.08
41.66
41.18
43.75
43.01
42.58
42.09
44.64
43.89
43.47
42.98
66.19
65.85
65.56
65.16
66.90
66.64
66.38
66.02
67.57
67.40
67.16
66.85
Total
42.79
42.08
41.66
41.18
43.75
43.01
42.58
42.09
44.64
43.89
43.47
42.98
66.19
65.85
65.56
65.16
66.90
66.64
66.38
66.02
67.57
67.40
67.16
66.85
Integ*
Capacity MBtuh
3.45
3.52
3.57
3.63
3.27
3.35
3.40
3.46
3.10
3.19
3.24
3.30
5.20
5.27
5.33
5.40
4.99
5.06
5.11
5.19
4.79
4.86
4.91
4.98
Total
Sys.
KW†
67 (19.4)
45.96
45.31
44.86
44.31
46.81
46.18
45.78
45.24
47.64
47.03
46.62
46.15
72.85
73.83
73.74
73.45
72.84
74.68
74.67
74.43
72.61
75.47
75.53
75.37
Total
45.96
45.31
44.86
44.31
46.81
46.18
45.78
45.24
47.64
47.03
46.62
46.15
72.85
73.83
73.74
73.45
72.84
74.68
74.67
74.43
72.61
75.47
75.53
75.37
Integ*
Capacity MBtuh
25HNB6C
3.51
3.60
3.66
3.75
3.34
3.43
3.49
3.57
3.18
3.26
3.32
3.40
5.55
5.70
5.78
5.88
5.30
5.47
5.55
5.65
5.06
5.25
5.33
5.43
Total
Sys.
KW†
NOTE: When the required data falls between the published data, interpolation may be performed. Extrapolation is not an acceptable practice.
* Tested Combination
} The Btuh heating capacity values shown are net integrated values from which the defrost effect has been subtracted. The Btuh heating from supplement heaters should be added to those values to obtain total system capacity.
{ The kW values include the compressor, outdoor fan motor, and indoor blower motor. The kW from supplement heaters should be added to these values to obtain total system kilowatts.
EDB — Entering Dry Bulb 1.
75
(23.9)
70
(21.1)
65
(18.3)
75
(23.9)
70
(21.1)
65
(18.3)
EDB
° F (° C)
INDOOR AIR
HEAT PUMP HEATING PERFORMANCE CONTINUED
GUIDE SPECIFICATIONS
GENERAL
System Description
Outdoor--mounted, air--cooled, split--system heat pump unit
suitable for ground or rooftop installation. Unit consists of a
hermetic compressor, an air--cooled coil, forward--swept blade
propeller--type condenser fan, and a control box. Unit will
discharge supply air upward as shown on contract drawings. Unit
will be used in a refrigeration circuit to match up to a packaged fan
coil or coil unit.
—
—
—
—
Compressor
Quality Assurance
—
—
25HNB6C
—
—
—
—
—
Unit will be rated in accordance with the latest edition of
AHRI Standard 240.
Unit will be certified for capacity and efficiency, and
listed in the latest AHRI directory.
Unit construction will comply with latest edition of
ASHRAE and with NEC.
Unit will be constructed in accordance with UL
standards and will carry the UL label of approval. Unit
will have C--UL approval.
Unit cabinet will be capable of withstanding Federal Test
Method Standard No. 141 (Method 6061) 500--hr salt
spray test.
Air--cooled condenser coils are pressure tested and the
outdoor units are leak tested.
Unit constructed in ISO9001 approved facility.
Delivery, Storage, and Handling
—
—
—
—
—
—
—
—
U.S. and Canada only.
PRODUCTS
—
Factory--assembled, single--piece, air--cooled heat pump
unit. Contained within the unit enclosure is all factory
wiring, piping, controls, compressor, refrigerant charge
Puronr (R--410A) refrigerant, and special features
required prior to field start--up.
—
—
—
Unit cabinet, including louvered coil guard, will be
constructed of galvanized steel, bonderized, and coated
with a powder coat paint to both sides of the sheet metal
for enhanced sea coast corrosion resistance.
—
Fans
—
Condenser fan will be direct--drive propeller type,
forward swept blade, discharging air upward.
Refrigeration circuit components will include liquid--line
front--seating shutoff valve with sweat connections,
vapor--line back--seating shutoff valve with sweat
connections, system charge of Puronr (R--410A)
refrigerant, POE compressor oil, accumulator, and
reversing valve.
Unit will be equipped with high--pressure switch, loss-of--charge switch, and filter drier for Puronr refrigerant.
Operating Characteristics
Unit Cabinet
—
Condenser coil will be air cooled.
Coil will be constructed of aluminum fins with epoxy
phenolic thermoset coating specially designed to resist
coastal corrosion. Fins are mechanically bonded to
copper tubes which are then cleaned, dehydrated, and
sealed.
ArmorPlate coating -- Aluminum fin material is
pre--coated on both sides with a corrosion protective
epoxy phenolic coating.
Refrigeration Components
Unit will be shipped as single package only and is stored
and handled per unit manufacturer’s recommendations.
Equipment
Compressor will be hermetically sealed.
Compressor will be mounted on rubber vibration
isolators.
Compressor will be covered with a sound absorbing
blanket.
Condenser Coil
Warranty (for inclusion by specifying engineer)
—
AIR--COOLED, SPLIT--SYSTEM HEAT PUMP
25HNB6C
2 TO 5 NOMINAL TONS
Condenser fan motors will be totally enclosed, 1--phase
type with class B insulation and permanently lubricated.
Shafts will be corrosion resistant.
Fan blades will be statically and dynamically balanced.
Condenser fan openings will be equipped with coated
steel wire safety guards.
The capacity of the unit will meet or exceed _____ Btuh
at a suction temperature of _____ _F (_C). The power
consumption at full load will not exceed _____ kW.
Combination of the unit and the evaporator or fan coil
unit will have a total net cooling capacity of _____ Btuh
or greater at conditions of _____ CFM entering air
temperature at the evaporator at _____ _F (_C) wet bulb
and _____ _F (_C) dry bulb, and air entering the unit at
_____ _F (_C).
The system will have a SEER of _____ Btuh/watt or
greater at DOE conditions.
Electrical Requirements
—
—
—
Nominal unit electrical characteristics will be _____ v,
single phase, 60 hz. The unit will be capable of
satisfactory operation within voltage limits of _____ v to
_____ v.
Unit electrical power will be single point connection.
Control circuit will be 24v.
Special Features
—
22
Refer to section of this literature identifying accessories
and descriptions for specific features and available
enhancements.
1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than 0.01--in. wc.
2. Minimum outdoor operating air temperature without low--ambient operation accessory is 55_F (12.8_C).
3. The maximum outdoor operating ambient in cooling mode is 125_F (51.67_C) when operating voltage is 230v. For 208v
applications, the maximum outdoor ambient is 120_F (48.9_C).
4. Minimum outdoor operating air temperature for heating mode is –20_F (–28.9_C).
5. Maximum outdoor operating air temperature for heating mode is 66_F (18.9_C).
6. For reliable operation, unit should be level in all horizontal planes.
7. For interconnecting refrigerant tube lengths greater than 80 ft (23.4 m) and/or elevation differences between indoor and outdoor units
greater than 20 ft (6.1 m), consult Residential Piping and Longline Guideline and Service Manual available from equipment distributor.
8. If any refrigerant tubing is buried, provide a 6 in. (152.4 mm) vertical rise to the valve connections at the unit. Refrigerant tubing
lengths up to 36 in. (914.4 mm) may be buried without further consideration. Do not bury refrigerant lines longer than 36 in. (914.4
mm).
9. Use only copper wire for electric connection at unit. Aluminum and clad aluminum are not acceptable for the type of connector
provided.
10. Do not apply capillary tube indoor coils to these units.
11. Factory--supplied filter drier must be installed.
23
25HNB6C
SYSTEM DESIGN SUMMARY
25HNB6C
Copyright 2013 Carrier Corp. D 7310 W. Morris St. D Indianapolis, IN 46231
Edition Date: 04/13
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.