(LVT) on 6in Post-Tension Concrete Floor with Ceiling Assembly

F6860.01-113-11-R0
ACOUSTICAL PERFORMANCE TEST REPORT
ASTM E 90 AND ASTM E 492
Rendered to
UNITED
PLASTICS CORPORATION
COMMERCIAL
ACOUSTICS
Series/Model:
4mm
Novalis
Stainmaster
with United
PlasticsFloor
dB-4Blokker
Pro
Series/Model:
4mm
Novalis
Stainmaster
with Commercial
Acoustics
Specimen Type: 152 mm Concrete Slab with Drop Ceiling
Overall Size: 3023 mm by 3632 mm
STC
IIC
60
70
Test Specimen Identification:
Floor Topping: 4 mm Novalis Stainmaster Premier Luxury Vinyl Plank
Floor Underlayment: 3.89 mm United
Plastics
dB-4 Floor
Pro Underlayment
Commercial
Acoustics
Blokker
Floor Slab: 152 mm Concrete Slab
Main Beams: 43 mm Armstrong HD8906 Drywall Main Beam
Cross Tees: 37.3 mm Armstrong XL8945P Cross Tee
Insulation: 88.9 mm Johns Manville Kraft Faced R-13 Fiberglass Insulation
Ceiling: 15.9 mm National Gypsum Gold Bond® Fire-Shield® Type X Gypsum Panel
Reference should be made to Intertek-ATI Report F6860.01-113-11 for complete test specimen
description. This page alone is not a complete report.
130 Derry Courtaa
York, PA 17406aa
www.archtest.com · www.intertek.com/building
p. 717.764.7700
f. 717.764.4129
F6860.01-113-11-R0
Page 1 of 4
Acoustical Performance Test Report
COMMERCIAL
UNITED
PLASTICSACOUSTICS
CORPORATION
511 Hay Street
1519 W. Cypress Street
Mount Airy, North Carolina 27030
Tampa, FL 33606
Report
Test Date
Report Date
F6860.01-113-11
03/22/16
04/01/16
Project Scope
Architectural Testing, Inc., a subsidiary of Intertek (Intertek-ATI), was contracted to conduct
airborne sound transmission loss and impact sound transmission tests. The complete test data is
included as attachments to this report. The client provided the test specimen. The specimen was
constructed on the date of testing.
Test Methods
The acoustical tests were conducted in accordance with the following standards. The equipment
listed in the attachments meets the requirements of the following standards.
ASTM E 90-09, Standard Test Method for Laboratory Measurement of Airborne Sound
Transmission Loss of Building Partitions
ASTM E 413-10, Classification for Rating Sound Insulation
ASTM E 492-09, Standard Test Method for Laboratory Measurement of Impact Sound
Transmission Through Floor-Ceiling Assemblies Using the Tapping Machine
ASTM E 989-06 (2012), Classification for Determination of Impact Insulation Class (IIC)
ASTM E 2235-04 (2012) Standard Test Method for Determination of Decay Rates for Use in
Sound Insulation Test Methods
Test Procedure
All testing was conducted in the VT test chambers at Intertek-ATI located in York,
Pennsylvania. The microphones were calibrated before conducting the tests.
The airborne transmission loss test was conducted in accordance with the ASTM E 90 test
method using the single direction method. Two background noise sound pressure level and five
sound absorption measurements were conducted at each of five microphone positions. Four
sound pressure level measurements were made simultaneously in both rooms, at each of five
microphone positions.
130 Derry Courtaa
York, PA 17406aa
www.archtest.com · www.intertek.com/building
p. 717.764.7700
f. 717.764.4129
F6860.01-113-11-R0
Page 2 of 4
Test Procedure (Continued)
The impact sound transmission test was conducted in accordance with the ASTM E 492 test
method. Two background noise sound pressure level, two sound pressure level measurements
with the tapping machine operating at each position specified by ASTM E 492, and five sound
absorption measurements were conducted at each of five microphone positions.
The air temperature and relative humidity conditions were monitored and recorded during all
measurements.
Test Conditions
Source Room
Average Temperature
Receive Room
19.3°C
Average Relative Humidity
Average Temperature
56%
21.3°C
Average Relative Humidity
52%
Test Calculations
The STC (Sound Transmission Class) and IIC (Impact Insulation Class) ratings were calculated
in accordance with ASTM E 413 and ASTM E 989, respectively.
Test Specimen Materials and Installation Details
Material
Premier Luxury
Vinyl Plank
Dimensions
(mm)
1219 by 152.4
4.0
Novalis Stainmaster
Quantity
10.98 m²
Average
Weight
7.96 kg/m²
Note: Adhered to the underlayment with XL Brands Stix Essential RES Aerosol Spray Adhesive per
manufacturer's specifications
7620 by 1219
Underlayment
Thickness
Manufacturer and Series
(mm)
3.9
United
Plastics
dB-4 Pro
Commercial
Acoustics
Floor Blokker 10.98 m²
4.14 kg/m²
Note: Loose laid with seams taped. The underlayment was composed of a 0.75 lb. mass-loaded EVA
with an attached polyester fiber layer.
3023 by 3632
152.0
N/A
10.98 m²
366.18 kg/m²
Concrete Slab
Note: The concrete slab was installed in a test frame flush to the source room.
38.1 by 2870
43.0
Armstrong HD8906
10.9 lin m
0.45 kg/m
Drywall Main Beam Note: Twelve gauge hanger wires were attached to the bottom side of the concrete at twelve locations
and then to the main beams. The hanger wire was twisted around itself a minimum of three times
within 76 mm creating a 305 mm plenum. The measured steel thickness is 0.5 mm.
38.3 by 1219
37.3
Armstrong XL8945P
27.2 lin m
0.45 kg/m
Cross Tee
Note: Inserted into the main beams on 607 mm centers. The measured steel thickness is 0.5 mm.
2962 by 584
88.9
Johns Manville Kraft Faced R-13
Fiberglass Insulation
Note: Loose laid onto the ceiling grid system
10.98 m²
1.33 kg/m²
F6860.01-113-11-R0
Page 3 of 4
Test Specimen Materials and Installation Details (Continued)
Material
Dimensions
(mm)
3023 by 1219
Gypsum Panel
Thickness
Manufacturer and Series
(mm)
National Gypsum Gold Bond®
15.9
Fire-Shield® Type X
Quantity
10.56 m²
Average
Weight
11.23 kg/m²
Note: Fastened with fine thread drywall screws on 305 mm centers
Comments
The total weight of the floor/ceiling assembly was 4303.9 kg. Intertek-ATI will store samples
of the test specimen for four years. Photographs of the test specimen are included in the
attachments. A drawing of the test specimen is included in the attachments.
Intertek-ATI will service this report for the entire test record retention period. Test records,
such as detailed drawings, datasheets, representative samples of test specimens, or other
pertinent project documentation, will be retained by Intertek-ATI for the entire test record
retention period. The test record retention period ends four years after the test date.
This report does not constitute certification of this product nor an opinion or endorsement by
this laboratory. It is the exclusive property of the client so named herein and relates only to the
specimen tested. This report is intended to help in the client’s quality assurance program, but it
does not represent a continuous or exhaustive evaluation of the specimen tested or of other
products or materials that were not evaluated. The statements and data provided herein do not
constitute approval, disapproval, certification, or acceptance of performance or materials.
This report may not be reproduced, except in full, without the written approval of
Intertek-ATI.
FOR INTERTEK-ATI:
David M. Dacheux
Technician II - Acoustical Testing
Jordan Strybos
Project Manager - Acoustical Testing
Attachments (7 Pages): This report is complete only when all attachments are included.
* Stated by Client/Manufacturer
N/A - Non Applicable
F6860.01-113-11-R0
Page 4 of 4
Revision Log
Revision
R0
Date
Page(s)
Description
04/01/16
N/A
Original Report Issue
This report produced from controlled document template ATI 00629(d), Revised 02/09/15.
F6860.01-113-11-R0
Attachments
Instrumentation
Instrument
Manufacturer
Model
ATI Number
Date of
Calibration
Data Acquisition Unit
National Instruments
PXI-1033
63763
06/14
Microphone Calibrator
Norsonic
1251
INT00127
01/16
Receive Room Microphone
Scantek
378B20
63748
05/15
Receive Room Microphone
PCB Piezotronics
378B20
63744
05/15
Receive Room Microphone
PCB Piezotronics
378B20
63745
05/15
Receive Room Microphone
PCB Piezotronics
378B20
63746
05/15
Receive Room Microphone
PCB Piezotronics
378B20
63747
05/15
Receive Room Environmental
Indicator
Comet
T7510
63810
63811
10/15
10/15
Source Room Microphone
PCB Piezotronics
378B20
63738
04/15
Source Room Microphone
PCB Piezotronics
378B20
63739
04/15
Source Room Microphone
PCB Piezotronics
378B20
63740
04/15
Source Room Microphone
PCB Piezotronics
378B20
63742
04/15
Source Room Microphone
Scantek
378B20
63741
04/15
Source Room Environmental
Indicator
Comet
T7510
63812
11/15
Tapping Machine
Look Line s.r.l.
EM50 (TM50) 65351
02/16
*
* The calibration frequency for this equipment is every two years per the manufacturer's recommendation.
Test Chambers
VT Receive Room Volume
155.77 m³
VT Source Room Volume
190 m³
Page 1 of 7
F6860.01-113-11-R0
AIRBORNE SOUND TRANSMISSION LOSS
ASTM E 90
Test Date
Data File No.
Client
Description
03/22/16
F6860.01
United Plastics
Corporation
Commercial
Acoustics
4 mm Novalis Stainmaster Premier Luxury Vinyl Plank, 3.89 mm Floor
UnitedBlokker
Plastics dB-4
Pro Underlayment, 152 mm Concrete Slab, 43 mm Armstrong HD8906 Drywall Main
Beam, 37.3 mm Armstrong XL8945P Cross Tee, 88.9 mm Johns Manville Kraft Faced R13 Fiberglass Insulation, 15.9 mm National Gypsum Gold Bond® Fire-Shield® Type X
Gypsum Panel
Specimen Area
Technician
10.98 m²
David M. Dacheux
Freq
(Hz)
80
100
125
160
200
250
315
400
500
630
800
1000
1250
1600
2000
2500
3150
4000
5000
6300
8000
10000
Background
Absorption
SPL
(dB)
(m²)
48.8
17.9
40.4
15.4
33.1
11.5
31.3
9.2
24.2
11.5
25.4
11.2
21.1
11.1
18.9
9.3
22.7
8.7
20.3
8.5
20.6
8.2
21.8
8.3
20.9
8.5
17.5
8.4
10.9
9.2
6.8
10.1
5.6
10.9
5.2
12.3
5.4
14.1
5.7
17.9
6.1
23.7
6.3
29.1
STC Rating
Deficiencies
Notes:
60
32
Source
SPL
(dB)
107
105
104
106
103
102
103
102
102
104
103
103
103
103
103
101
103
105
106
99
98
93
Receive
SPL
(dB)
69
66
66
66
60
56
54
50
43
42
38
40
38
38
36
35
32
31
28
18
13
7
Specimen
TL
(dB)
37
38
39
42
44
48
50
54
61
65
67
66
67
67
69
68
72
74
78
81
83
83
95%
Number
Confidence
of
Limit
Deficiencies
3.60
2.30
1.70
5
2.20
5
1.80
6
1.00
5
1.10
6
0.60
5
0.60
0
0.90
0
0.40
0
0.60
0
0.70
0
0.70
0
0.60
0
0.60
0
0.60
0
1.30
0
2.20
1.80
1.70
1.60
-
(Sound Transmission Class)
(Sum of Deficiencies)
1) Receive Room levels less than 5 dB above the Background levels are highlighted in yellow.
2) Specimen TL levels listed in red indicate the lower limit of the transmission loss.
3) Specimen TL levels listed in green indicate that there has been a filler wall correction applied
ATI 00614 Revised 02/09/15
Page 2 of 7
F6860.01-113-11-R0
AIRBORNE SOUND TRANSMISSION LOSS
ASTM E 90
Test Date
Data File No.
Client
Description
03/22/16
F6860.01
United Plastics
Corporation
Commercial
Acoustics
4 mm Novalis Stainmaster Premier Luxury Vinyl Plank, 3.89 mm Floor
UnitedBlokker
Plastics dB-4
Pro Underlayment, 152 mm Concrete Slab, 43 mm Armstrong HD8906 Drywall Main
Beam, 37.3 mm Armstrong XL8945P Cross Tee, 88.9 mm Johns Manville Kraft Faced R13 Fiberglass Insulation, 15.9 mm National Gypsum Gold Bond® Fire-Shield® Type X
Gypsum Panel
Specimen Area
Technician
10.98 m²
David M. Dacheux
Airborne Sound Transmission Loss
100
90
Sound Transmission Loss (dB)
80
70
60
50
40
30
20
10
Specimen TL
Contour Curve
8000
4000
2000
1000
500
250
125
63
0
Frequency (Hz)
ATI 00614 Revised 02/09/15
Page 3 of 7
F6860.01-113-11-R0
IMPACT SOUND TRANSMISSION
ASTM E 492
Test Date
Data File No.
Client
Description
03/22/16
F6860.01
United Plastics
Corporation
Commercial
Acoustics
4 mm Novalis Stainmaster Premier Luxury Vinyl Plank, 3.89 mm Floor
UnitedBlokker
Plastics dB-4
Pro Underlayment, 152 mm Concrete Slab, 43 mm Armstrong HD8906 Drywall Main
Beam, 37.3 mm Armstrong XL8945P Cross Tee, 88.9 mm Johns Manville Kraft Faced R13 Fiberglass Insulation, 15.9 mm National Gypsum Gold Bond® Fire-Shield® Type X
Gypsum Panel
Specimen Area
Technician
10.98 m²
David M. Dacheux
Freq
Background SPL
Absorption
(Hz)
80
100
125
160
200
250
315
400
500
630
800
1000
1250
1600
2000
2500
3150
4000
5000
6300
8000
10000
(dB)
48.9
43.6
33.5
28.4
24.7
26.1
23.5
21.9
23.8
22.1
22.2
23.0
25.1
20.7
12.5
8.7
7.2
5.5
5.5
5.7
6.1
6.3
(m²)
17.6
14.4
11.5
9.4
11.2
10.9
11.2
9.2
8.5
8.6
8.3
8.4
8.5
8.4
9.2
10.2
11.0
12.4
14.1
18.0
23.6
29.6
IIC Rating
Deficiencies
Note:
70
28
95%
Number
Normalized Impact
SPL
Confidence
of
(dB)
Limit
Deficiencies
55
4.4
50
1.0
8
47
1.4
5
46
1.3
4
48
1.1
6
45
1.9
3
44
1.7
2
40
0.7
0
32
1.4
0
30
0.6
0
24
0.7
0
22
0.7
0
22
0.6
0
20
0.2
0
12
0.2
0
8
0.6
0
7
0.3
0
6
0.2
6
0.3
6
0.4
8
0.5
9
0.6
-
(Impact Insulation Class)
(Sum of Deficiencies)
Receive Room levels less than 5 dB above the Background levels are highlighted in yellow.
ATI 00615 Revised 02/09/15
Page 4 of 7
F6860.01-113-11-R0
IMPACT SOUND TRANSMISSION
ASTM E 492
Test Date
Data File No.
Client
Description
03/22/16
F6860.01
United Plastics
Corporation
Commercial
Acoustics
4 mm Novalis Stainmaster Premier Luxury Vinyl Plank, 3.89 mm United
Plastics dB-4
Floor Blokker
Pro Underlayment, 152 mm Concrete Slab, 43 mm Armstrong HD8906 Drywall Main
Beam, 37.3 mm Armstrong XL8945P Cross Tee, 88.9 mm Johns Manville Kraft Faced R13 Fiberglass Insulation, 15.9 mm National Gypsum Gold Bond® Fire-Shield® Type X
Gypsum Panel
Specimen Area
Technician
10.98 m²
David M. Dacheux
100
10
90
20
80
30
70
40
60
50
50
60
40
70
30
80
20
90
10
Impact Insulation Class (IIC)
Sound Pressure Level (dB)
Impact Sound Transmission
100
Normalized Impact SPL
Contour Curve
8000
4000
2000
1000
500
250
125
110
63
0
Frequency (Hz)
ATI 00615 Revised 02/09/15
Page 5 of 7
F6860.01-113-11-R0
Photographs
Source Room View of Test Specimen Installation
Source Room View of Test Specimen Installation
Receive Room View of Test Specimen Installation
Page 6 of 7
F6860.01-113-11-R0
Drawing
1-Floor Topping
2-Underlayment
3-Concrete Slab
4-Hanger Wire
5-Insulation
6-Ceiling Grid
7-Ceiling
Page 7 of 7