5127522-BTG-A-0715
TECHNICAL
GUIDE
DESCRIPTION
These packaged cooling/heating air conditioners are designed
for outdoor installation. Only utility and duct connections are
required at the point of installation.
FEATURES
• Operating Efficiency - All PCE4 air conditioner models are
rated at 14.0 SEER and 11.0 EER for cooling operation.
SINGLE PACKAGE
AIR CONDITIONER/ELECTRIC HEAT
14 SEER – R-410A
2 THRU 5 NOMINAL TONS
MODELS: PCE4*24 THRU 60
• On Site Flexibility - All model sizes use a compact design
cabinet in one of two footprints. This provides installer flexibility for placing the proper capacity unit on curbs or pads
with the smallest footprint after the internal load has been
determined. Field convertible duct connections from side
shot to down shot allows the installer to have greater flexibility with less inventory.
• Lower Installation Cost - Installation time and costs are
reduced by easy power and control wiring connections. The
small base dimension means less space is required on the
ground or roof. All units are completely wired, charged with
R-410A and tested prior to shipment. Test stations using a
state-of-the-art computerized process system are used to
insure product quality. Refrigerant charge and component
part numbers are verified via computers during assembly.
Vital run test statistics such as system pressure, motor currents, air velocity and temperature, unit vibration, and gas
system safeties are monitored and recorded by the system to
insure unit performance. Equal size side supply and return
duct connections allow easy connection of ducts to match
low crawl spaces without transition pieces.
• Utility Connections Made Easy - Electric utility access provided through the bottom or the side of the unit. Utility connections can be made quickly and with a minimum amount of
field labor. A field supplied and field installed electrical disconnect switch must be installed.
®
Due to continuous product improvement, specifications
are subject to change without notice.
Visit us on the web at
www.upgnet.com
Additional rating information can be found at:
www.ahridirectory.org
WARRANTY SUMMARY*
Extended 10-Years limited parts and compressor warranty
* Extended warranty requires online registration within 90 days of purchase for
replacement or closing for new home purchase. See limited warranty certificate
in User’s Information Manual for details.
• Convertible Airflow Design - The bottom duct openings are
covered when they leave the factory, ready to be used for a
side supply/side return application. If a bottom supply/bottom
return application is desired, simply remove the two panels
from the bottom of the unit and place them in the side supply/
side return duct openings. No panel cutting is required and
no accessory panel is necessary. Convertible airflow design
allows maximum field flexibility and minimum inventory.
• Condensate Pan - A corrosion-resistant, long-lasting, watertight pan is positioned below the evaporator coil to collect
and drain all condensate, preventing build-up of stagnant
condensate. The condensate pan conforms to ASHRAE 6289 standards (Ventilation for Acceptable Indoor Air Quality).
• Condensate Drain - The 3/4 inch NPT female connection is
rigidly mounted to assure proper fit and leak tight seal.
• Durable Finish - The cabinet is made of G90 galvanized
steel with a powder paint coating for appearance and protection. The pre-treated galvanized steel provides a better paintto-steel bond, which resists corrosion and rust creep. Powder
paint finish ensures less fading when exposed to sunlight,
and provides superior corrosion resistance (1000 hour salt
spray tested).
Continued on next page.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
5127522-BTG-A-0715
• Full Perimeter Base Rails - The easily removable base rails
provide a solid foundation for the entire unit and protects the
unit during shipment. The rails provide fork lift access from all
sides, and rigging holes are also provided so that an overhead crane can be used to place the units on a roof. On
applications where the unit is placed on a pad, the base will
keep the unit off the pad to deter corrosion. On applications
where height is limited, the base rails may be removed by
removing 2 screws in each corner.
• Simple Control Circuit - Field thermostat wiring connects to
color coded leads using twist on wire connections. Cooling
controls use contactor and relays for simple application and
troubleshooting. Mate-n-lock plug connectors are used. The
electrical control box is not located in the compressor compartment. The controls are mounted to allow the separate
access panel to be removed for trouble shooting and maintenance without affecting the normal system operating pressures. All wiring internal to the unit is color/number coded.
• Attractive Appearance - A single-piece top cover containing
a top-discharge condenser fan arrangement requires less
square footage on installation and provides a wider variety of
installations. The one-piece design adds greater water integrity. Rounded corners with water drip edges add to the attractive appearance.
• Protected Compressor - The compressor is internally protected against high pressure and temperature. This is
accomplished by the simultaneous operation of high pressure relief valve and a temperature sensor which protect the
compressor if undesirable operating conditions occur.
• Top Discharge - The top-discharge outdoor fan does not
disrupt neighboring areas or dry out vegetation surrounding
the unit. The warm air from the top mounted fan is blown up
and away from the structure and any landscaping.
• Outdoor Coil Grille - All models utilize a stamped slotted
design which provides superior impact protection against
small objects during transit and after installation.
• Low Operating Sound Level - The upward air flow carries
the normal operating noise up and away from the living area.
The rigid top panel effectively isolates noise. Isolator
mounted compressor and the rippled fins of the outdoor coil
muffle the normal fan motor and compressor operating
sounds. The unique formed base pan also aids in sound
attenuation with its structural design.
• Fan System - All models operate over a wide range of
design conditions with a standard ECM indoor fan motor.
These units easily match all types of applications and provide greater on-site flexibility to match comfort requirements.
The cooling speed is factory-set and can be field-adjusted to
a second speed. The heating speed is factory set to maintain
mid point rise at the units heating input, but can be field
adjusted. This allows maximum comfort conditions.
• Pressure Switches - A high pressure switch is standard in
all units. It is an automatic reset switch. When discharge
pressure reaches 650 psi, the compressor will de-energize
until pressure reaches 450 psi.
• Exclusive Coil Design - Grooved copper tubes and
enhanced aluminum fin construction improves heat transfer
for maximum efficiency and durability for long-lasting durability and efficient operation. Indoor coils will use tin-coated
copper tubing with aluminum fins for effective heat transfer.
• Electric Heat - All electric heat models use 6HK electric
heat, which are available in 230v/1/60 from 2 kW to 25 kW,
230v/3/60 10kW to 25kW, and 460v/3/60 10kW to 25kW.
Most kits stageable above 10 kW. Single phase single point
field wiring kits are available for all applications except 25kW.
• Low Maintenance - Long life, permanently lubricated condenser and evaporator fan motor bearings need no annual
maintenance, adding greater reliability to the unit. Slide-out
blower assembly and evaporator coil assembly can be easily
removed for cleaning.
• Easy Service Access - Individual access panels are provided in access to all major components - compressors,
evaporator coils, blower, controls/electric heat kits, filters,
etc. that makes servicing easy. Removing these panels allow
easy removal of the components such as the blower assembly for maintenance and ease of troubleshooting.
• Replacement Parts - The installer requires no special training to replace any of the components of these units and the
number of new components have been reduced to minimize
the inventory of unique parts.
2
Johnson Controls Unitary Products
5127522-BTG-A-0715
NOMENCLATURE
PCE
4
A
24
1
2
3
4
50
2
X
6
1
A
8
9
1. Model Family
PCE - packaged A/C with electric heat,
PHE - packaged heat pump with electric heat,
PCG - packaged A/C with gas heat,
PHG - packaged heat pump with gas heat,
5. Gas Heating Input BTU/Hr x 1000
050 = 50,000 BTU/Hr. input, blank = electric heat
2. Nominal Cooling Efficiency
4 = 14 SEER, 6 = 16 SEER, etc.
7. NOx Approval
X = low-NOx, blank = not low-Nox
3. Cabinet Size
A = small 35 x 51, B = large 45 x 51
8. Generation Level
1 = first generation
4. Nominal Air Conditioning Cooling Capacity BTUx1000
24 = 24,000 BTU, etc.
9. Revision Level
A = original release, B = second release
6. Voltage-Phase-Frequency
2 = 208/230-1-60, 3=208/230-3-60, 4 = 460-3-60
Examples:
PCE4B4221A is a packaged air conditioner, 14 SEER, 3-1/2 ton, large cabinet, 230 volt, single phase model, (first generation, first release)
COMPONENT LOCATION
OUTDOOR FAN MOTOR
OUTDOOR FAN
OUTDOOR COIL
(Behind Panel)
COIL GUARD PANEL
CONTACTOR
TXV
CAPACITOR
TRANSFORMER
COMPRESSOR
BLOWER MOTOR
OPTIONAL
ELECTRIC HEAT KIT
INDOOR COIL
INDOOR BLOWER
REMOVABLE
BASE RAILS
A0411-001
Unit Limitations
Unit Limitations
Model
Unit Voltage
Applied Voltage
Outdoor DB Temp
Min
Max
Max (°F)
A24
208/230-1-60
187
252
125
A30
208/230-1-60
187
252
125
A36
208/230-1-60
187
252
125
A42
208/230-1-60
187
252
125
B48
208/230-1-60
187
252
125
B60
208/230-1-60
187
252
125
Johnson Controls Unitary Products
3
5127522-BTG-A-0715
ACCESSORIES
• Economizer for Downflow Applications
(S1-2EE04708424, S1-2EE04708524) - Modulating integrated economizer provides simultaneous operation
between mechanical cooling and economizer operation.
Independent blade design insures proper control and less
than 1% leak rate. Includes hood and mesh bird screen filter
integrated into the hood, dry bulb sensor and relief damper.
Separate field accessories of single/dual enthalpy kits are
also available.
• Economizer for Horizontal Applications
(S1-2EE04708624, S1-2EE04708724) - Modulating integrated economizer provides simultaneous operation
between the mechanical cooling and economizer operation.
Independent blade design insures proper control and less
than 1% leak rate. Includes hood and mesh bird screen filter
integrated into hood, dry bulb sensor and relief damper. Separate field accessories of single enthalpy and dual enthalpy
are available.
• Single/Dual Enthalpy Sensor (S1-2EC04700624) - Sensor
replaces dry bulb sensor standard in economizer kit. Provides improved economizer operation by sensing the dry
bulb temperature from outdoors plus the enthalpy content of
the outdoor air.
• CO2 Sensor Kit (S1-2AQ04700824) - Sensor kit detects
CO2 levels automatically and overrides the economizer
when CO2 levels rise above the preset limits.
• Outdoor Temperature Sensor Kit
(S1-2EC04700724S1-2EC04700724v) - Additional outdoor
air temperature sensor kit used with economizers.
• Filter/Frame Kit (Single Phase Only)
(S1-1FF0602, S1-1FF0601) - Kit contains the necessary
hardware to field install return air filters into the base unit.
The filter rack is suitable for either 1" or 2" filters. (filters not
supplied) This kit is available for single phase horizontal or
vertical duct applications.
• Motorized Fresh Air Damper
(S1-2MD04705224, S1-2MD04705124) - Designed for duct
mounted side supply/return and unit mounted down supply/
return applications. Damper capable of providing 0% through
50% of outdoor air (field supplied). Closes on power loss,
includes hood and screen assembly.
• Low Ambient Kit (S1-2LA04700824) - Kit provides necessary hardware to convert unit to operate in cooling cycle
down to 0º F. Standard unit operation 45º F.
• Rectangle to Round (Horizontal) Adapter
(S1-1AK0110, S1-1AK0111) - Kit includes one supply and
one return air rectangle to round duct adapter. Adapters are
preformed and designed to fit over current horizontal duct
openings on the base unit. Transition is from rectangle to 12"
round for the 1AK0110 kit and from rectangle to 14" round for
the 1AK0111 kit.
4
• Rectangle to Round (Downflow) Adapter
(S1-1AK0108, S1-1AK0109) - Kit includes one supply and
one return air rectangle to round duct adapter. Adapters are
preformed and designed to fit into current downflow duct
openings on the roof curb. Transition is from rectangle to 16"
round for the 1AK0108 kit and from rectangle to 18" round for
the 1AK0109 kit.
• Roof Curbs (S1-1RC0503, S1-1RC0501) - NRCA approved
curbs provide proper fit to base unit for rooftop installations.
Curbs are designed to be assembled through hinge pins in
each corner. Kit also provides seal strip to assure an air tight
seal. These are 8 inch high roof curbs.
• Roof Curbs (S1-1RC0504, S1-1RC0502) - NRCA approved
curbs provide proper fit to base unit for rooftop installations.
Curbs are designed for assembly through hinge pins in each
corner. Kit also provides seal strip to assure air tight seal.
These are 14 inch high roof curbs.
• Manual Outdoor Damper (S1-1FA0502, S1-1FA0501) Provides 0% through 50% outdoor air capability (field adjustable). Designed for duct mounted side supply/return applications and unit mounted down supply/return applications.
Includes hood and screen assembly.
• Transformer Kit (S1-2EC06700124) - Kit provides necessary hardware to provide single phase models from factory
furnished 40 VA transformer capability to 75 VA transformer
capability. (Required on installations with economizer or
motorized damper).
• Base Rail Hole Cover Kit (S1-1HC0101) - Kit provides necessary hardware to close off openings in base rails to block
off openings, i.e. prevent animal entrance.
• Loss of Charge Sensor (S1-2LC00024) - Kit provides Loss
of Charge sensor and wiring to provide safe shutdown of
compressor.
• Single Point Wiring Accessory Kits for 6HK Electric Heat
Applications (S1-SPWK*) - Kits provide field option for connecting electrical power supplies to the field installed 6HK
kits to allow single point connections for single phase electric
heat applications with the exception of 25kW kits.
• Transition Curb Kits (S1-1TC01*) - Adapter kits to allow
field use of pre-existing installed roof curbs to match PHE4
footprint to Affinity roof curbs, Carrier, Trane, or Goodman
curb footprints. Curb adapters are optional for current generation Carrier replacements but are recommended for previous generation applications. Refer to the PCE4 price pages
for more details.
• Wall Thermostat - The units are designed to operate with
standard, 24-volt electronic non power stealing and electromechanical thermostats. All units can operate with single
stage heat/single stage cool thermostats - with or without the
economizer.
* For additional kit numbers refer to the price pages.
Johnson Controls Unitary Products
5127522-BTG-A-0715
GUIDE SPECIFICATIONS
GENERAL
Units shall be manufactured by Unitary Products in an ISO
9001 certified facility. These packaged cooling and heating air
conditioners are designed for outdoor installation. Only utility
and duct connections are required at the point of installation. Air
Conditioning units provide electric cooling and electric heating,
with field installed electric heat kits from 2 kW to 25 kW for
heating operation.
DESCRIPTION
Units shall be factory-assembled, single packaged, Air
Conditioners with Electric Cooling/Electric Heating units,
designed for outdoor installation. They shall have built in, equal
size, field convertible duct connections for supply/return or
horizontal supply/return. The units shall be factory wired, piped,
charged with R-410A Refrigerant and factory tested prior to
shipment. All models shall be rated in accordance with DOE
and AHRI test procedures for both heating and cooling
operation. Units shall be CSA listed to the UL 1995/CAN/CSA
No. 236-M90 standards.
• Operating Efficiency - All models shall be rated at a minimum of 14.0 SEER and 11.0 EER for cooling and heating
operation rated in accordance with DOE requirements.
• Low Operating Sound Level - The upward air flow carries
the normal operating noise up and away from the living area.
The rigid top panel effectively isolates noise. Isolator
mounted compressor and the rippled fins of the condenser
coil muffle the normal fan motor and compressor operating
sounds. The unique formed base pan also aids in sound
attenuation with its structural design. Sound ratings as tested
under AHRI test procedures shall be less than 77 dbA for all
models.
UNIT CABINET
Unit cabinet shall be a single piece design, with drip edges and
no-seam corners to provide optimum water integrity. Unit shall
have a rigidly mounted condenser coil guard to provide
protection from objects and personnel after installation. Indoor
blower section shall be insulated with foil-faced or foam
insulation, fastened to prevent insulation from entering the air
stream. Cabinet panels shall be separate, easily removable for
servicing and maintenance. Unit shall be built on a formed,
design base pan, with embossments at critical points to add
strength and rigidity and to aid in minimizing sound. Full
perimeter base rails shall be provided to assure reliable transit
of equipment, overhead rigging, for truck access and proper
sealing on roof curb applications. Base rails shall be easily
removable, when required to lower unit height. Filters shall be
field installed, furnished and be accessible through a removable
access door, sealed airtight. Units vertical discharge and return
duct configuration shall be designed to fit between standard 24”
O.C. beams without modification to building structure, duct work
and base unit.
• Durable Finish - The cabinet shall be is made of G90 galvanized steel with a powder paint coating for appearance and
protection. The pre-treated galvanized steel shall provide a
better paint-to-steel bond, which resists corrosion and rust
creep. Powder paint finish shall provide superior corrosion
resistance (1000 hour salt spray tested).
Johnson Controls Unitary Products
• On Site Flexibility - All model sizes shall use a compact
design cabinet in one of two footprints. This provides installer
flexibility for placing the proper capacity unit on curbs or pads
with the smallest footprint after the internal load has been
determined. Field convertible duct connections from side
shot to down shot allows the installer to have greater flexibility with less inventory.
• Attractive Appearance - A single-piece top cover containing
a top-discharge condenser fan arrangement shall be used
which requires less square footage on installation and provides a wider variety of installations. The one-piece design
adds greater water integrity. Rounded corners with water drip
edges add to the attractive appearance and prevent water
penetration.
• Convertible Airflow Design - The bottom duct openings are
covered when they leave the factory, ready to be used for a
side supply/side return application. If a bottom supply/bottom
return application is desired, simply remove the two panels
from the bottom of the unit and place them in the side supply/
side return duct openings. No panel cutting is required and
no accessory panel is necessary. Convertible airflow design
allows maximum field flexibility and minimum inventory.
• Utility Connections Made Easy - Electric utility access shall
be provided through the bottom or the side of the unit. Utility
connections should be made quickly and with a minimum
amount of field labor. A field supplied and field installed electrical disconnect switch must be installed.
• Easy Service Access - Individual access panels are provided in access to all major components - compressors,
indoor coils, blower, controls/electric heat kits, filters, etc. that
makes servicing easy. Removing these panels allow easy
removal of the components such as the blower assembly for
maintenance and ease of troubleshooting.
• Top Discharge - The top-discharge outdoor fan does not
disrupt neighboring areas or dry out vegetation surrounding
the unit. The warm air from the top mounted fan is blown up
and away from the structure and any landscaping.
• Outdoor Coil Grille - All models utilize a stamped slotted
design which provides superior impact protection against
small objects during transit and after installation.
Indoor Blower Assembly - Fan shall be direct drive design.
Fan wheel shall be double-inlet type with forward-curved
blades, dynamically balanced to operate smoothly throughout
the entire range of operation. Airflow design shall be constant
air volume. Bearings shall be sealed and permanently
lubricated for longer life and no maintenance. Fan assembly
shall be a slide-out design for easy removal and cleaning.
Indoor blower motors shall be equipped with a standard high
efficiency brushless DC motor (constant torque) also known as
a standard ECM motor.
Outdoor Fan Assembly - The outdoor fan shall be of the
direct-driven propeller type, discharge air vertically, have
aluminum blades riveted to corrosion resistant steel spider
bracket and shall be statically balanced for smooth operation.
The outdoor fan motor shall be totally enclosed with
permanently lubricated bearings and internally protected
against overload conditions.
5
5127522-BTG-A-0715
REFRIGERANT COMPONENTS
CONTROLS
• Protected Compressor - The compressor shall be a fully
hermetic type, direct drive compressor, that is internally protected against high pressure and temperature. This is
accomplished by the simultaneous operation of high pressure relief valve and a temperature sensor which protect the
compressor if undesirable operating conditions occur. The
hermetic motor shall be suction gas cooled and have a voltage range of +/- 10% of the unit nameplate voltage. Compressors shall have internal isolation and sound muffling to
minimize vibration and noise, and be externally isolated on a
dedicated, independent mounting.
• Simple Control Circuit - Field thermostat wiring connects to
color coded leads using twist on wire connections. Cooling
controls use contactor and relays for simple application and
troubleshooting. Mate-n-lock plug connectors are used. The
electrical control box is not located in the compressor compartment. The controls are mounted to allow the separate
access panel to be removed for trouble shooting and maintenance without affecting the normal system operating pressures. All wiring internal to the unit is color/number coded.
• Indoor Coils - Indoor coils shall be of the direct expansion,
draw through design and have aluminum plate fins mechanically bonded to seamless internally enhanced tin-coated
copper tubes with all joints brazed.
• Condensate Pan - A corrosion-resistant, long-lasting, watertight pan is positioned below the indoor coil to collect and
drain all condensate, preventing build-up of stagnant condensate. The condensate pan conforms to ASHRAE 62-89
standards (Ventilation for Acceptable Indoor Air Quality).
• Condensate Drain - The 3/4 inch NPT female connection is
rigidly mounted to assure proper fit and leak tight seal.
• Outdoor Coils - Outdoor coils shall have aluminum plate fins
mechanically bonded to seamless internally enhanced copper tubes with all joints brazed, and be a draw through
design.
Refrigerant Circuit and Refrigerant Safety Components
shall include: Thermal expansion devices (TXV's) shall be
factory mounted and provided, Filter/strainer to eliminate any
foreign matter, reversing valves to control refrigerant flow.
6
• Pressure Switches - A high pressure switch is standard in
all units. It is an automatic reset switch. When discharge
pressure reaches 650 psi, the compressor will de-energize
until pressure reaches 450 psi.
• Factory Testing - Installation time and costs are reduced by
easy power and control wiring connections. All units are
completely wired, charged with R-410A and tested prior to
shipment. Test stations using a state-of-the-art computerized
process system shall be used to insure product quality.
Refrigerant charge and component part numbers are verified
via computer bar code scans during assembly. Vital run test
statistics such as system pressure, motor currents, air velocity and temperature, unit vibration, and gas system safeties
are monitored and recorded by the system to insure unit performance. This data could be provided by serial number
tracking if requested.
• Electric Heat - All electric heat models use 6HK electric
heat, which are available in 230v/1/60 from 2 kW to 25 kW,
230v/3/60 10kW to 25kW, and 460v/3/60 10kW to 25kW.
Most kits stageable above 10 kW. Single point accessory kits
are available for single phase models. Single phase single
point field wiring kits are available for all applications except
25kW. Electric heat kits must be certified to UL 1995 standard requirements.
Johnson Controls Unitary Products
5127522-BTG-A-0715
Physical Data
MODELS
NOMINAL TONNAGE
PCE4A2421
PCE4A3021
PCE4A3621
PCE4A4221
PCE4B4821
PCE4B6021
2.0
2.5
3.0
3.5
4.0
5.0
AHRI Cooling Performance
Gross Capacity @ AHRI A point (MBH)
23.7
30.1
37.2
43.5
47.7
55.0
AHRI net capacity (MBH)
22.8
29.0
34.6
40.7
45.5
52.5
EER
11.0
11.0
11.0
11.0
11.0
11.0
SEER
14.0
14.0
14.0
14.0
14.0
14.0
Nominal CFM
800
1000
1200
1400
1600
2000
System power (KW)
2.1
2.6
3.2
3.8
4.2
4.8
R410A
R410A
R410A
R410A
R410A
R410A
5-4
9-2
8-3
9-4
14-4
14-2
Length
51-1/4
51-1/4
51-1/4
51-1/4
51-1/4
51-1/4
Width
35-3/4
35-3/4
35-3/4
35-3/4
45-3/4
45-3/4
Height
47
47
47
49
53
55
Operating WT. (lbs.)
343
389
395
466
483
500
Recip
Recip
Recip
Scroll
Scroll
Scroll
26.3
Refrigerant type
Refrigerant charge (lb-oz)
Dimensions (inches)
Compressors
Type
Outdoor Coil Data
Face area (Sq. Ft.)
15.3
15.3
15.3
17.3
24.1
Rows
1
2
2
2
2
2
Fins per inch
22
22
22
22
22
22
Tube diameter
3/8
3/8
3/8
3/8
3/8
3/8
Circuitry Type
Interlaced
Interlaced
Interlaced
Interlaced
Interlaced
Interlaced
4.4
Indoor Coil Data
Face area (Sq. Ft.)
3.4
3.4
3.4
3.4
4.4
Rows
2
3
3
3
3
3
Fins per inch
16
16
16
16
16
16
Tube diameter
3/8
3/8
3/8
3/8
3/8
3/8
Circuitry Type
Interlaced
Interlaced
Interlaced
Interlaced
Interlaced
Interlaced
TXV
TXV
TXV
TXV
TXV
TXV
Refrigerant control
Outdoor Fan Data
Fan diameter (Inch)
24
24
24
24
26
26
Type
Prop
Prop
Prop
Prop
Prop
Prop
Drive type
Direct
Direct
Direct
Direct
Direct
Direct
No. speeds
1
1
1
1
1
1
Motor HP each
1/4
1/4
1/4
1/4
1/3
1/3
RPM
850
850
850
850
850
850
Nominal total CFM
2400
2400
2400
2400
3200
3200
Direct Drive Indoor Blower Data
Fan Size (Inch)
Type
Motor HP each
RPM
Frame size
11 x 8
11 x 8
11 x 10
11 x 10
11 x 10
11 x 10
Centrifugal
Centrifugal
Centrifugal
Centrifugal
Centrifugal
Centrifugal
1/2
1/2
1/2
3/4
3/4
1
1200 Max
1200 Max
1200 Max
1200 Max
1200 Max
1200 Max
48
48
48
48
48
48
A
A
A
A
B
B
Filters
Filter Size
Quantity size
Johnson Controls Unitary Products
Field-supplied external filters must be sized so as not to exceed 300 fpm air velocity through disposable filters. For internal filter use, a filter rack kit is available. Consult the instructions supplied with that kit for
replacement filter sizes. Filter sizes: A=20x20, B=20x30.
7
5127522-BTG-A-0715
COOLING PERFORMANCE DATA
PACKAGED UNIT MODEL NO.
ID CFM
CONDENSER
IDDB
ENTERING AIR
TEMPERATURE
IDWB
T.C.
55 / 45
S.C.
K.W.
T.C.
65 / 55
S.C.
K.W.
T.C.
75 / 63
S.C.
K.W.
T.C.
85 / 69
S.C.
K.W.
T.C.
95 / 75
S.C.
K.W.
T.C.
105 / 83
S.C.
K.W.
T.C.
115 / 89
S.C.
K.W.
T.C.
125 / 95
S.C.
K.W.
PCE4A2421
80
57
30.0
30.0
1.48
25.9
25.6
1.57
26.9
26.9
1.77
22.0
21.7
1.86
22.1
22.1
2.07
19.3
19.3
2.21
16.6
16.6
2.36
13.9
13.9
2.50
80
62
33.4
28.6
1.47
29.1
23.6
1.58
28.4
25.8
1.78
23.8
20.6
1.87
22.8
22.7
2.07
19.9
19.8
2.21
17.0
17.0
2.35
14.1
14.1
2.49
1000
75
62
33.4
23.8
1.47
28.8
19.9
1.57
28.2
20.9
1.78
23.4
17.1
1.87
22.5
18.3
2.06
19.2
16.4
2.20
16.0
14.6
2.32
12.8
12.8
2.45
80
67
36.7
23.7
1.46
32.1
19.9
1.57
31.4
21.1
1.62
26.5
17.4
1.89
25.5
18.8
2.09
22.0
17.2
2.24
18.5
15.6
2.38
15.1
14.0
2.53
80
72
39.8
18.7
1.44
35.4
16.0
1.56
35.3
16.8
1.61
29.9
13.7
1.95
28.8
14.1
2.21
24.7
11.9
2.34
20.7
9.6
2.47
17.6
9.4
2.59
80
57
27.4
27.4
1.44
25.9
25.7
1.58
24.4
24.0
1.72
22.3
22.1
1.85
20.2
20.1
1.98
17.8
17.8
2.12
15.5
15.4
2.25
13.1
13.1
2.39
80
62
30.9
25.0
1.44
28.7
23.6
1.58
26.6
22.2
1.73
24.1
20.9
1.86
21.6
19.5
2.00
18.8
17.4
2.13
16.1
15.4
2.26
13.4
13.4
2.39
800
75
62
31.2
20.9
1.44
28.7
19.7
1.58
26.2
18.5
1.73
23.7
17.2
1.86
21.3
16.0
2.00
18.3
14.4
2.12
15.4
12.9
2.24
12.4
11.4
2.36
80
67
34.3
21.0
1.42
31.9
19.8
1.54
29.4
18.6
1.65
26.8
17.5
1.84
24.2
16.4
2.03
21.0
14.9
2.17
17.9
13.6
2.31
14.8
12.2
2.45
80
72
37.6
16.9
1.40
35.4
16.0
1.53
33.2
15.1
1.65
30.2
13.8
1.88
27.3
12.6
2.11
23.7
10.8
2.25
20.2
9.1
2.38
17.2
8.4
2.52
80
57
24.9
24.9
1.41
25.9
25.9
1.59
21.9
21.2
1.66
22.6
22.5
1.84
18.3
18.2
1.90
16.3
16.2
2.03
14.3
14.3
2.15
12.3
12.3
2.27
80
62
28.4
21.3
1.41
28.4
23.5
1.59
24.8
18.6
1.68
24.4
21.1
1.86
20.3
16.4
1.94
17.7
15.1
2.06
15.1
13.8
2.17
12.6
12.6
2.29
600
75
62
29.0
18.1
1.40
28.6
19.5
1.59
24.2
16.0
1.67
24.1
17.3
1.86
20.1
13.6
1.94
17.3
12.4
2.05
14.7
11.1
2.17
12.0
9.9
2.28
80
67
31.8
18.2
1.39
31.6
19.7
1.50
27.5
16.1
1.69
27.2
17.5
1.79
22.9
14.0
1.97
20.0
12.7
2.11
17.3
11.5
2.24
14.5
10.3
2.37
80
72
35.4
15.1
1.37
35.3
16.0
1.49
31.1
13.3
1.69
30.5
13.9
1.81
25.8
11.1
2.00
22.7
9.8
2.15
19.7
8.6
2.30
16.7
7.4
2.45
1200
75
62
43.2
32.6
1.71
38.8
30.5
1.89
34.3
28.4
2.08
29.8
26.1
2.24
25.3
23.7
2.41
20.6
19.5
2.56
16.0
15.5
2.71
11.4
11.4
2.86
80
67
44.9
31.1
1.68
41.6
29.8
1.88
38.3
28.5
2.08
34.2
26.7
2.27
30.1
24.8
2.45
25.9
22.4
2.61
21.8
20.1
2.77
17.7
17.7
2.92
80
72
48.3
24.5
1.66
45.6
23.4
1.86
42.9
22.3
2.06
38.6
20.6
2.27
34.3
18.9
2.47
28.7
16.9
2.67
23.3
14.9
2.86
17.8
13.0
3.06
80
57
37.8
36.9
1.67
34.4
34.0
1.83
31.1
31.1
1.99
27.8
27.8
2.15
24.4
24.4
2.32
20.3
20.3
2.49
16.3
16.3
2.66
12.3
12.3
2.83
80
62
41.0
34.5
1.66
37.6
32.5
1.83
34.1
30.5
2.00
30.3
28.1
2.16
26.4
25.7
2.31
22.8
22.3
2.49
19.3
19.0
2.65
15.7
15.7
2.82
1000
75
62
40.8
29.5
1.65
36.9
27.6
1.83
33.0
25.6
2.02
28.8
23.4
2.14
24.5
21.2
2.26
20.0
17.8
2.44
15.6
14.5
2.61
11.2
11.2
2.79
80
67
43.8
28.8
1.65
40.5
27.3
1.83
37.1
25.8
2.02
33.2
24.0
2.19
29.2
22.2
2.37
24.7
20.0
2.50
20.3
17.8
2.62
15.9
15.7
2.73
80
72
47.9
23.6
1.62
44.1
25.2
1.82
40.3
26.9
2.02
36.6
21.9
2.22
32.8
17.0
2.41
27.8
15.2
2.61
23.0
13.5
2.80
18.2
11.7
2.99
80
57
34.5
33.6
1.62
31.4
31.0
1.78
28.4
28.4
1.94
25.5
25.5
2.09
22.6
22.6
2.24
19.2
19.2
2.41
15.9
15.9
2.57
12.6
12.6
2.74
80
62
38.4
30.5
1.61
35.2
28.7
1.77
31.9
26.9
1.93
28.2
25.0
2.08
24.6
23.1
2.24
20.8
19.9
2.40
17.2
16.7
2.56
13.6
13.6
2.72
800
75
62
38.5
26.4
1.60
35.1
24.6
1.78
31.7
22.8
1.95
27.7
20.8
2.03
23.7
18.7
2.11
19.4
16.1
2.32
15.2
13.6
2.52
11.0
11.0
2.72
80
67
42.8
26.5
1.61
39.4
24.8
1.78
36.0
23.2
1.95
32.1
21.3
2.12
28.2
19.5
2.30
23.4
17.5
2.38
18.8
15.6
2.46
14.1
13.7
2.55
80
72
47.5
22.6
1.59
42.6
27.0
1.78
37.7
31.5
1.97
34.5
23.3
2.16
31.3
15.1
2.35
26.9
13.6
2.55
22.7
12.0
2.73
18.5
10.5
2.92
COOLING PERFORMANCE DATA
PACKAGED UNIT MODEL NO.
ID CFM
CONDENSER
ENTERING AIR
IDDB
TEMPERATURE
IDWB
T.C.
55 / 45
S.C.
K.W.
T.C.
65 / 55
S.C.
K.W.
T.C.
75 / 63
S.C.
K.W.
T.C.
85 / 69
S.C.
K.W.
T.C.
95 / 75
S.C.
K.W.
T.C.
105 / 83
S.C.
K.W.
T.C.
115 / 89
S.C.
K.W.
T.C.
125 / 95
S.C.
K.W.
8
PCE4A3021
80
57
41.0
40.2
1.71
37.4
37.0
1.88
33.8
33.8
2.04
30.1
30.1
2.22
26.3
26.3
2.39
21.4
21.4
2.57
16.7
16.7
2.74
12.0
12.0
2.91
80
62
43.6
38.5
1.71
40.0
36.3
1.89
36.4
34.2
2.06
32.3
31.2
2.23
28.3
28.3
2.39
24.8
24.8
2.57
21.3
21.3
2.74
17.9
17.9
2.91
Johnson Controls Unitary Products
5127522-BTG-A-0715
COOLING PERFORMANCE DATA
PACKAGED UNIT MODEL NO.
ID CFM
CONDENSER
IDDB
ENTERING AIR
TEMPERATURE
IDWB
T.C.
55 / 45
S.C.
K.W.
T.C.
65 / 55
S.C.
K.W.
T.C.
75 / 63
S.C.
K.W.
T.C.
85 / 69
S.C.
K.W.
T.C.
95 / 75
S.C.
K.W.
T.C.
105 / 83
S.C.
K.W.
T.C.
115 / 89
S.C.
K.W.
T.C.
125 / 95
S.C.
K.W.
PCE4A3621
80
57
45.3
45.3
2.15
42.0
42.0
2.39
38.7
38.7
2.63
35.3
35.3
2.87
31.9
31.9
3.11
26.5
26.5
3.43
21.4
21.4
3.74
16.2
16.2
4.05
80
62
48.1
43.2
2.16
43.7
40.3
2.41
39.3
37.4
2.66
35.4
34.4
2.90
31.5
31.5
3.14
26.8
26.8
3.39
22.3
22.3
3.65
17.7
17.7
3.90
1400
75
62
48.0
36.0
2.16
43.8
34.1
2.40
39.6
32.1
2.64
35.5
30.0
2.88
31.5
28.0
3.12
26.3
24.0
3.35
21.3
20.2
3.57
16.3
16.3
3.79
80
67
53.1
36.5
2.15
48.6
34.5
2.41
44.1
32.4
2.67
39.4
30.1
2.93
34.8
27.8
3.20
29.0
24.4
3.43
23.4
21.1
3.67
17.7
17.7
3.90
80
72
54.6
27.9
2.15
52.4
26.6
2.40
50.1
25.4
2.65
45.0
23.6
2.93
39.8
21.8
3.21
33.7
19.3
3.48
27.7
17.0
3.75
21.7
14.6
4.01
80
57
42.2
42.2
2.07
39.4
39.4
2.30
36.6
36.6
2.52
33.6
33.6
2.75
30.5
30.5
2.99
26.0
26.0
3.27
21.6
21.6
3.54
17.2
17.2
3.81
80
62
46.3
39.5
2.07
42.5
36.9
2.31
38.6
34.3
2.55
34.8
32.0
2.79
31.0
29.7
3.02
26.5
25.7
3.27
22.2
21.8
3.50
17.9
17.9
3.74
1200
75
62
46.2
33.3
2.07
42.4
31.3
2.31
38.5
29.3
2.54
34.8
27.5
2.77
31.0
25.7
3.00
26.2
22.6
3.23
21.4
19.7
3.44
16.7
16.7
3.66
80
67
51.3
33.4
2.06
47.1
31.5
2.32
42.9
29.5
2.57
38.7
27.5
2.83
34.6
25.5
3.08
29.1
22.8
3.32
23.8
20.2
3.54
18.5
17.6
3.77
80
72
53.5
26.1
2.05
51.0
24.9
2.31
48.4
23.6
2.56
43.8
21.9
2.83
39.2
20.2
3.10
33.5
18.0
3.37
28.0
15.9
3.63
22.5
13.8
3.88
80
57
39.2
39.2
1.99
36.8
36.8
2.20
34.5
34.5
2.41
31.9
31.9
2.64
29.2
29.2
2.87
25.5
25.5
3.11
21.8
21.8
3.34
18.2
18.2
3.57
80
62
44.6
35.8
1.99
41.2
33.5
2.22
37.9
31.1
2.45
34.2
29.5
2.68
30.5
27.9
2.91
26.3
24.5
3.14
22.2
21.3
3.36
18.0
18.0
3.58
1000
75
62
44.5
30.6
1.99
41.0
28.6
2.22
37.4
26.6
2.44
34.0
25.0
2.67
30.6
23.4
2.89
26.0
21.2
3.11
21.5
19.1
3.32
17.0
17.0
3.53
80
67
49.5
30.4
1.97
45.6
28.5
2.22
41.7
26.7
2.47
38.0
25.0
2.72
34.3
23.3
2.97
29.2
21.3
3.20
24.2
19.3
3.42
19.2
17.4
3.65
80
72
52.4
24.4
1.95
49.5
23.1
2.21
46.7
21.8
2.46
42.7
20.2
2.73
38.6
18.7
2.99
33.4
16.7
3.25
28.3
14.8
3.50
23.2
13.0
3.76
1600
75
62
50.2
38.5
2.51
47.0
36.4
2.74
43.7
34.3
2.97
40.1
32.8
3.28
36.5
31.3
3.59
31.8
28.4
4.01
27.3
25.6
4.42
22.8
22.8
4.83
80
67
55.5
39.6
2.53
52.1
37.7
2.77
48.7
35.9
3.01
44.9
33.9
3.31
41.1
32.0
3.60
36.1
29.5
4.03
31.1
27.2
4.45
26.2
24.8
4.87
80
72
61.9
32.6
2.56
58.0
30.8
2.80
54.1
29.0
3.04
50.0
27.3
3.36
46.0
25.5
3.67
40.6
23.3
4.09
35.3
21.2
4.50
30.1
19.1
4.91
80
57
46.5
45.5
2.42
44.4
43.7
2.55
42.2
41.9
2.67
39.3
39.2
2.98
36.5
36.5
3.29
32.5
32.5
3.72
28.7
28.7
4.14
24.9
24.9
4.57
80
62
48.6
42.1
2.44
45.6
40.5
2.68
42.6
38.8
2.93
40.0
36.1
3.24
37.4
33.3
3.54
33.0
30.3
3.97
28.8
27.4
4.38
24.5
24.5
4.79
1400
75
62
48.5
36.2
2.43
45.6
34.4
2.66
42.6
32.7
2.89
39.3
31.0
3.20
35.9
29.4
3.51
31.5
26.9
3.94
27.2
24.4
4.35
22.9
22.0
4.76
80
67
53.7
37.0
2.45
50.5
35.3
2.70
47.4
33.6
2.94
43.8
31.2
3.24
40.2
28.9
3.54
35.5
27.0
3.97
30.9
25.2
4.37
26.4
23.3
4.78
80
72
59.6
30.7
2.47
56.1
29.2
2.71
52.5
27.6
2.94
48.8
25.9
3.26
45.1
24.1
3.57
40.0
22.1
3.99
35.0
20.1
4.41
30.1
18.1
4.82
80
57
43.7
43.1
2.35
42.2
41.9
2.36
40.6
40.6
2.38
38.0
38.0
2.69
35.4
35.4
3.00
31.7
31.7
3.44
28.2
28.2
3.86
24.7
24.7
4.29
80
62
46.9
39.2
2.36
44.1
37.7
2.61
41.3
36.3
2.86
38.2
34.5
3.17
35.1
32.7
3.48
31.2
29.6
3.90
27.4
26.7
4.31
23.7
23.7
4.71
1200
75
62
46.8
33.9
2.36
44.1
32.5
2.59
41.4
31.0
2.82
38.4
29.3
3.13
35.4
27.6
3.44
31.2
25.4
3.86
27.1
23.3
4.28
23.0
21.2
4.69
80
67
51.8
34.4
2.38
48.9
32.8
2.62
46.0
31.3
2.87
42.7
28.5
3.18
39.3
25.8
3.48
34.9
24.5
3.90
30.7
23.1
4.30
26.5
21.8
4.70
80
72
57.3
28.7
2.38
54.1
27.5
2.61
51.0
26.2
2.84
47.6
24.5
3.15
44.1
22.8
3.47
39.4
20.9
3.90
34.7
19.0
4.31
30.1
17.2
4.73
COOLING PERFORMANCE DATA
PACKAGED UNIT MODEL NO. PCE4A4221
ID CFM
CONDENSER
ENTERING AIR
IDDB
80
80
TEMPERATURE
IDWB
57
62
T.C.
49.4 50.2
55 / 45
S.C.
47.8 45.0
K.W.
2.50 2.52
T.C.
46.6 47.0
65 / 55
S.C.
45.5 43.2
K.W.
2.73 2.76
T.C.
43.8 43.9
75 / 63
S.C.
43.3 41.4
K.W.
2.97 3.00
T.C.
40.7 41.8
85 / 69
S.C.
40.4 37.7
K.W.
3.28 3.30
T.C.
37.6 39.7
95 / 75
S.C.
37.6 33.9
K.W.
3.59 3.60
T.C.
33.3 34.8
105 / 83
S.C.
33.3 31.0
K.W.
4.01 4.03
T.C.
29.2 30.1
115 / 89
S.C.
29.2 28.2
K.W.
4.43 4.45
T.C.
25.1 25.4
125 / 95
S.C.
25.1 25.4
K.W.
4.84 4.86
Johnson Controls Unitary Products
9
5127522-BTG-A-0715
COOLING PERFORMANCE DATA
PACKAGED UNIT MODEL NO.
ID CFM
CONDENSER
ENTERING AIR
IDDB
TEMPERATURE
IDWB
T.C.
55 / 45
S.C.
K.W.
T.C.
65 / 55
S.C.
K.W.
T.C.
75 / 63
S.C.
K.W.
T.C.
85 / 69
S.C.
K.W.
T.C.
95 / 75
S.C.
K.W.
T.C.
105 / 83
S.C.
K.W.
T.C.
115 / 89
S.C.
K.W.
T.C.
125 / 95
S.C.
K.W.
PCE4B4821
80
57
58.1
57.1
2.21
54.4
54.0
2.46
50.8
50.8
2.71
46.5
46.5
3.05
42.2
42.2
3.39
37.2
37.2
3.85
32.4
32.4
4.31
27.6
27.6
4.76
80
62
61.5
53.6
2.21
56.8
51.5
2.47
52.2
49.5
2.73
47.2
45.8
3.06
42.2
42.2
3.38
37.0
37.0
3.85
31.9
31.9
4.31
26.9
26.9
4.76
1800
75
62
60.2
44.4
2.20
55.7
42.4
2.46
51.2
40.4
2.72
46.2
37.7
3.05
41.2
35.0
3.38
35.3
31.2
3.85
29.6
27.5
4.30
23.9
23.9
4.76
80
67
66.8
44.1
2.23
62.2
42.4
2.49
57.6
40.6
2.75
52.4
38.1
3.08
47.2
35.6
3.41
40.9
33.3
3.88
34.9
31.0
4.33
28.8
28.8
4.79
80
72
70.0
33.9
2.25
66.3
32.4
2.50
62.5
30.9
2.76
57.6
28.7
3.09
52.7
26.5
3.42
46.8
24.7
3.89
41.1
23.0
4.35
35.5
21.2
4.80
80
57
55.6
54.5
2.20
52.1
51.6
2.44
48.7
48.7
2.69
44.6
44.6
3.04
40.6
40.6
3.38
36.1
36.1
3.85
31.7
31.7
4.30
27.3
27.3
4.76
80
62
59.5
49.9
2.21
55.1
48.0
2.46
50.7
46.0
2.72
46.0
42.9
3.05
41.3
39.8
3.38
36.2
35.2
3.85
31.2
30.7
4.31
26.2
26.2
4.77
1600
75
62
58.7
42.1
2.20
54.4
40.1
2.45
50.1
38.2
2.71
45.1
35.5
3.04
40.2
32.9
3.38
35.0
30.1
3.85
30.1
27.3
4.30
25.1
24.6
4.76
80
67
65.1
41.9
2.23
60.9
40.2
2.49
56.6
38.5
2.75
51.5
35.9
3.08
46.4
33.4
3.41
40.6
31.3
3.88
35.1
29.3
4.33
29.6
27.4
4.79
80
72
70.0
33.5
2.24
65.7
31.5
2.49
61.4
29.5
2.75
56.8
27.5
3.09
52.2
25.4
3.42
46.5
23.7
3.89
41.0
22.0
4.34
35.6
20.3
4.80
80
57
53.1
51.9
2.18
49.8
49.2
2.43
46.5
46.5
2.68
42.8
42.8
3.02
39.0
39.0
3.36
34.9
34.9
3.84
30.9
30.9
4.30
27.0
27.0
4.76
80
62
57.5
46.3
2.20
53.4
44.5
2.46
49.3
42.6
2.71
44.9
40.0
3.05
40.5
37.4
3.38
35.4
33.4
3.86
30.5
29.5
4.31
25.5
25.5
4.77
1400
75
62
57.2
39.7
2.19
53.1
37.9
2.45
49.0
36.0
2.70
44.1
33.3
3.03
39.2
30.7
3.37
34.8
28.9
3.84
30.6
27.1
4.30
26.4
25.4
4.76
80
67
63.4
39.6
2.22
59.5
38.0
2.48
55.6
36.3
2.74
50.6
33.8
3.07
45.5
31.2
3.40
40.3
29.4
3.87
35.3
27.6
4.33
30.3
25.9
4.79
80
72
69.9
33.0
2.23
65.1
30.6
2.49
60.3
28.2
2.74
56.0
26.3
3.08
51.7
24.3
3.42
46.2
22.7
3.88
41.0
21.0
4.34
35.7
19.4
4.79
2050
75
62
65.2
49.1
3.43
28.9
23.1
3.74
57.7
46.1
4.05
52.8
43.8
4.45
47.9
41.5
4.84
39.9
35.7
5.41
32.1
30.0
5.97
24.4
24.4
6.53
80
67
68.7
46.2
3.43
32.9
23.1
3.76
65.7
46.2
4.09
60.0
44.0
4.48
54.3
41.8
4.86
46.0
37.8
5.42
38.0
33.9
5.96
30.0
30.0
6.49
80
72
72.9
34.9
3.41
36.7
17.6
3.76
73.2
35.2
4.11
60.4
41.4
4.47
47.5
47.5
4.83
44.7
39.3
5.41
42.0
31.3
5.98
39.3
23.4
6.55
80
57
60.4
60.4
3.28
56.7
56.7
3.57
53.0
53.0
3.87
26.5
26.5
4.26
46.0
46.0
4.66
41.5
41.5
5.23
37.1
37.1
5.79
32.7
32.7
6.35
80
62
64.1
54.7
3.29
60.5
53.5
3.59
56.9
52.3
3.88
52.5
49.3
4.28
48.1
46.3
4.68
42.6
41.4
5.25
37.2
36.6
5.80
31.9
31.9
6.35
1800
75
62
64.4
46.3
3.33
28.4
21.5
3.61
56.7
43.0
3.89
52.2
40.9
4.29
47.8
38.8
4.69
40.0
34.1
5.26
32.5
29.5
5.82
25.0
25.0
6.38
80
67
68.0
44.2
3.34
32.2
21.6
3.63
64.4
43.1
3.92
59.2
41.1
4.31
54.0
39.0
4.71
46.1
35.6
5.26
38.5
32.2
5.81
31.0
28.8
6.35
80
72
71.8
33.9
3.32
36.0
16.8
3.64
72.0
33.6
3.96
63.2
35.7
4.33
54.3
37.9
4.70
49.5
32.5
5.27
44.8
27.4
5.83
40.1
22.2
6.38
80
57
57.6
57.6
3.12
54.3
54.3
3.41
51.0
51.0
3.70
25.5
25.5
4.11
44.4
44.4
4.51
40.0
40.0
5.10
35.6
35.6
5.66
31.2
31.2
6.23
80
62
62.7
51.4
3.14
59.1
49.7
3.43
55.5
48.1
3.72
51.5
46.0
4.12
47.5
43.9
4.52
41.1
38.7
5.09
34.9
33.7
5.64
28.7
28.7
6.19
1550
75
62
63.6
43.4
3.23
27.9
20.0
3.48
55.7
40.0
3.73
51.6
38.0
4.13
47.6
36.1
4.53
40.1
32.5
5.11
32.9
29.1
5.67
25.6
25.6
6.24
80
67
67.2
42.2
3.24
31.6
20.0
3.50
63.1
40.0
3.76
58.4
38.1
4.15
53.6
36.3
4.55
46.2
33.3
5.11
39.0
30.5
5.66
31.9
27.6
6.21
80
72
70.6
32.8
3.23
35.4
16.0
3.52
70.7
32.0
3.80
65.9
30.1
4.19
61.1
28.2
4.57
54.3
25.7
5.13
47.6
23.4
5.67
41.0
21.0
6.21
COOLING PERFORMANCE DATA
PACKAGED UNIT MODEL NO.
ID CFM
CONDENSER
IDDB
ENTERING AIR
TEMPERATURE
IDWB
T.C.
55 / 45
S.C.
K.W.
T.C.
65 / 55
S.C.
K.W.
T.C.
75 / 63
S.C.
K.W.
T.C.
85 / 69
S.C.
K.W.
T.C.
95 / 75
S.C.
K.W.
T.C.
105 / 83
S.C.
K.W.
T.C.
115 / 89
S.C.
K.W.
T.C.
125 / 95
S.C.
K.W.
10
PCE4B6021
80
57
63.1
63.1
3.44
59.1
59.1
3.74
55.1
55.1
4.03
27.6
27.6
4.42
47.5
47.5
4.80
43.0
43.0
5.37
38.6
38.6
5.92
34.2
34.2
6.47
80
62
65.4
58.0
3.44
61.9
57.3
3.75
58.3
56.5
4.05
53.5
52.6
4.44
48.7
48.7
4.84
44.0
44.0
5.40
39.6
39.6
5.96
35.1
35.1
6.51
Johnson Controls Unitary Products
5127522-BTG-A-0715
DIMENSIONS
COIL GUARD
HIGH VOLTAGE
CONNECTION 7/8”
C
HIGH VOLTAGE
CONNECTION 1-3/32”
HEAT EXCHANGER
ACCESS PANEL
COMPRESSOR
ACCESS PANEL
CONDENSATE
DRAIN
BLOWER
ACCESS
PANEL
B
A
LOW VOLTAGE CONNECTION
CONTROL ACCESS
PANEL
A0379-001
Unit Dimensions
Dimensions
Model
A
B
C
PCE4A2421
51-1/4
35-3/4
47
PCE4A3021
51-1/4
35-3/4
49
PCE4A3621
51-1/4
35-3/4
49
PCE4A4221
51-1/4
35-3/4
49
PCE4B4821
51-1/4
45-3/4
53
PCE4B6021
51-1/4
45-3/4
55
Unit Clearances1
Direction
Distance (in.)
Direction
Top2
36
Power Entry (Right Side)
Distance (in.)
36
Side Opposite Ducts
36
Left Side
24
Duct Panel
0
Bottom 3
1
1. A 1" clearance must be provided between any combustible material and the supply air duct work.
2. Units must be installed outdoors. Overhanging structures or shrubs must not obstruct condenser air discharge outlet.
3. Units may be installed on combustible materials made from wood or class A, B or C roof covering materials only if factory
base rails are left in place as shipped.
Electric Heat Minimum Supply Air
Minimum Blower Speed for Electric Heat
Model
Voltage
Heater kW
2
5
8
10
13
15
18
20
Med. #3
Med. Hi #4
--
--
--
--
High #5
--
--
--
High #5
--
PCE4A2421
208/230-1-60
Low #1 Low #1 Med. Low #2
PCE4A3021
208/230-1-60
Low #1 Low #1
Low #1
Med. Low #2
Med #3
PCE4A3621
208/230-1-60
Low #1 Low #1
Low #1
Low #1
Med. Low #2
PCE4A4221
208/230-1-60
--
Low #1
Low #1
Low #1
Low #1
PCE4B4821
208/230-1-60
--
Low #1
Low #1
Low #1
Low #1
Low #1
PCE4B6021
208/230-1-60
--
Low #1
Low #1
Low #1
Low #1
Low #1
Johnson Controls Unitary Products
Med. Low #2 Med. Hi #4
--
--
High #5
--
Med. Low #2 Med. High #4
Low #1
25
--
Med. Low #2 Med. High #4
11
5127522-BTG-A-0715
Indoor Blower Specifications
Motor
Model
HP
RPM
EFF.
SF
Frame
PCE4A2421
1/2
Variable
0.8
1.0
48
PCE4A3021
1/2
Variable
0.8
1.0
48
PCE4A3621
1/2
Variable
0.8
1.0
48
PCE4A4221
3/4
Variable
0.8
1.0
48
PCE4B4821
3/4
Variable
0.8
1.0
48
PCE4B6021
1
Variable
0.8
1.0
48
Sound Performance
Model
(Tons)
Sound Rating1
dB (A)
125
250
500
1000
2000
4000
8000
PCE4A2421
75
62.4
61.5
64.2
67.0
61.0
57.3
49.6
PCE4A3021
75
60.5
61.6
64.8
66.9
60.9
56.0
49.7
PCE4A3621
74
58.5
61.8
65.4
66.5
60.7
54.8
49.8
PCE4A4221
74
63.5
63.9
62.3
65.0
64.0
54.1
46.6
PCE4B4821
74
63.5
63.9
62.3
65.0
64.0
54.1
46.6
PCE4B6021
76
72.3
65.0
63.9
64.0
60.0
55.5
49.0
Octave Band Centerline Frequency (Hz)
1. Rated in accordance with AHRI Standard 270.
Electrical Data - 208/230-1-60 - Single Source Power
Single Point Connection Kit Required
Model
Compressor
RLA
LRA MCC
OD Fan
Motor
Blower
Motor
FLA
FLA
PCE4A24
9
45
14
1.3
3.8
PCE4A30
10
57
15
1.3
3.8
PCE4A36
13
78
23
1.3
3.8
PCE4A42
18
112
28
1.3
5.4
Electric Heat Option
Heater Kit
none
6HK16500206
6HK16500506
6HK16500806
6HK16501006
6HK16501306
none
6HK16500206
6HK16500506
6HK16500806
6HK16501006
6HK16501306
6HK16501506
none
6HK16500206
6HK16500506
6HK16500806
6HK16501006
6HK16501306
6HK16501506
none
6HK16500506
6HK16500806
6HK16501006
6HK16501306
6HK16501506
6HK16501806
6HK16502006
Heater kW
208
-1.8
3.6
5.8
7.2
9.4
-1.8
3.6
5.8
7.2
9.4
10.8
-1.8
3.6
5.8
7.2
9.4
10.8
-3.6
5.8
7.2
9.4
10.8
13.0
14.4
230
-2.2
4.4
7.1
8.8
11.5
-2.2
4.4
7.1
8.8
11.5
13.2
-2.2
4.4
7.1
8.8
11.5
13.2
-4.4
7.1
8.8
11.5
13.2
15.9
17.6
Stages
-1
1
1
1
2
-1
1
1
1
2
2
-1
1
1
1
2
2
-1
1
1
2
2
2
2
Heater Amps
208
-8.7
17.3
27.9
34.6
45.2
-8.7
17.3
27.9
34.6
45.2
51.9
-8.7
17.3
27.9
34.6
45.2
51.9
-17.3
27.9
34.6
45.2
51.9
62.5
69.2
230
-9.6
19.1
30.9
38.3
50.0
-9.6
19.1
30.9
38.3
50.0
57.4
-9.6
19.1
30.9
38.3
50.0
57.4
-19.1
30.9
38.3
50.0
57.4
69.1
76.5
MCA1
(Amps)
208
16.0
15.6
26.4
39.6
48.0
61.2
17.4
15.6
26.4
39.6
48.0
61.2
69.7
21.4
15.6
26.4
39.6
48.0
61.2
69.7
29.1
28.4
41.6
50.0
63.2
71.7
84.9
93.3
Max Fuse 2or
Breaker3 Size
230
208
230
16.0
20
20
16.7
20
20
28.7
30
30
43.3
40
45
52.6
50
60
67.3
70
70
17.4
25
25
16.7
25
25
28.7
30
30
43.3
40
45
52.6
50
60
67.3
70
70
76.5
70
80
21.4
30
30
16.7
30
30
28.7
30
30
43.3
40
45
52.6
50
60
67.3
70
70
76.5
70
80
29.1
45
45
30.7
45
45
45.3
45
50
54.6
50
60
69.3
70
70
78.5
80
80
93.2
90
100
102.4
100
110
For notes see Page 13.
12
Johnson Controls Unitary Products
5127522-BTG-A-0715
Electrical Data - 208/230-1-60 - Single Source Power
Single Point Connection Kit Required
Compressor
Model
RLA
LRA MCC
OD Fan
Motor
Blower
Motor
FLA
FLA
PCE4B48
22
117
34
1.7
5.4
PCE4B60
24
144
38
1.7
7.0
Electric Heat Option
Heater Kit
none
6HK16500506
6HK16500806
6HK16501006
6HK16501306
6HK16501506
6HK16501806
6HK16502006
none
6HK16500506
6HK16500806
6HK16501006
6HK16501306
6HK16501506
6HK16501806
6HK16502006
Heater kW
208
-3.6
5.8
7.2
9.4
10.8
13.0
14.4
-3.6
5.8
7.2
9.4
10.8
13.0
14.4
230
-4.4
7.1
8.8
11.5
13.2
15.9
17.6
-4.4
7.1
8.8
11.5
13.2
15.9
17.6
Stages
-1
1
1
2
2
2
2
-1
1
1
2
2
2
2
208
-17.3
27.9
34.6
45.2
51.9
62.5
69.2
-17.3
27.9
34.6
45.2
51.9
62.5
69.2
230
-19.1
30.9
38.3
50.0
57.4
69.1
76.5
-19.1
30.9
38.3
50.0
57.4
69.1
76.5
Max Fuse 2or
MCA1
(Amps)
Heater Amps
208
34.4
28.4
41.6
50.0
63.2
71.7
84.9
93.3
39.2
30.4
43.6
52.0
65.2
73.7
86.9
95.3
230
34.4
30.7
45.3
54.6
69.3
78.5
93.2
102.4
39.2
32.7
47.3
56.6
71.3
80.5
95.2
104.4
Breaker3 Size
208
230
50
50
50
50
50
50
50
60
70
70
80
80
90
100
100
110
60
60
60
60
60
60
60
60
70
80
80
90
90
100
100
110
1. Minimum Circuit Ampacity.
2. Maximum Over Current Protection per standard UL 1995.
3. Fuse or HACR circuit breaker size installed at factory or field installed.
Electrical Data for 208-1-60 Multi Source Power
Model
Compressor
RLA
LRA MCC
Electric Heat Option
OD Fan Blower
Motor Motor
FLA
FLA
Heater Kit
Heater kW
208
Stages
Multi Source
Heater Amps
208
208
208
208
208
208
208
208
208
Circuit #1 Compressor Circuit
Multi Source: Compressor
Circuit and Heat Circuits
MCA1
MCA1
MCA1
MCA1
MOP2
MOP2
MOP2
MOP2
Amps
Amps
Amps
Amps
Circuit #2 Heat
Multi Source:
Circuit #2 Heat
Circuit #3 Heat
A24
9
45
14
1.3
A30
10
57
15
1.3
none
6HK(0,1)6500206
6HK(0,1)6500506
3.8 6HK(0,1)6500806
6HK(0,1)6501006
6HK16501306
6HK26501306
none
6HK(0,1)6500206
6HK(0,1)6500506
6HK(0,1)6500806
3.8 6HK(0,1)6501006
6HK16501306
6HK16501506
6HK26501306
6HK26501506
-1.8
3.6
5.8
7.2
9.4
9.4
-1.8
3.6
5.8
7.2
9.4
10.8
9.4
10.8
-1
1
1
1
2
1
-1
1
1
1
2
2
1
1
Circuit #1
-8.7
17.3
27.9
34.6
45.2
45.2
-8.7
17.3
27.9
34.6
45.2
51.9
45.2
51.9
16.0
16.0
16.0
16.0
16.0
16.0
16.0
17.4
17.4
17.4
17.4
17.4
17.4
17.4
17.4
17.4
20
20
20
20
20
20
20
25
25
25
25
25
25
25
25
25
Circuit #2
-10.8
21.6
34.9
43.3
37.7
56.5
-10.8
21.6
34.9
43.3
37.7
43.3
56.5
64.9
-15
25
40
45
40
60
-15
25
40
45
40
50
60
70
Circuit #3
-----18.8
------18.8
21.6
---
-----20
------20
25
---
Circuit #4
-----------------
-----------------
For notes, see Page 14.
Johnson Controls Unitary Products
13
5127522-BTG-A-0715
Electrical Data for 208-1-60 Multi Source Power (Continued)
Model
Compressor
RLA
LRA MCC
Electric Heat Option
OD Fan Blower
Motor Motor
FLA
FLA
Heater Kit
Heater kW
208
Stages
Multi Source
Heater Amps
208
208
208
208
208
208
208
208
208
Circuit #1 Compressor Circuit
Multi Source: Compressor
Circuit and Heat Circuits
MCA1
MCA1
MCA1
MCA1
MOP2
MOP2
MOP2
MOP2
Amps
Amps
Amps
Amps
Circuit #2 Heat
Multi Source:
Circuit #2 Heat
Circuit #3 Heat
A36
13
78
23
1.3
3.8
A42
18
112
28
1.7
5.4
B48
22
117
34
1.7
5.4
B60
24
144
38
1.7
7.0
none
6HK(0,1)6500206
6HK(0,1)6500506
6HK(0,1)6500806
6HK(0,1)6501006
6HK16501306
6HK16501506
6HK26501306
6HK26501506
none
6HK(0,1)6500506
6HK(0,1)6500806
6HK(0,1)6501006
6HK16501306
6HK16501506
6HK16501806
6HK16502006
6HK26501306
6HK26501506
6HK26501806
6HK26502006
none
6HK(0,1)6500506
6HK(0,1)6500806
6HK(0,1)6501006
6HK16501306
6HK16501506
6HK16501806
6HK16502006
6HK26501306
6HK26501506
6HK26501806
6HK26502006
none
6HK(0,1)6500506
6HK(0,1)6500806
6HK(0,1)6501006
6HK16501306
6HK16501506
6HK16501806
6HK16502006
6HK26501306
6HK26501506
6HK26501806
6HK26502006
6HK16502506
6HK26502506
-1.8
3.6
5.8
7.2
9.4
10.8
9.4
10.8
-3.6
5.8
7.2
9.4
10.8
13.0
14.4
9.4
10.8
13.0
14.4
-3.6
5.8
7.2
9.4
10.8
13.0
14.4
9.4
10.8
13.0
14.4
-3.6
5.8
7.2
9.4
10.8
13.0
14.4
9.4
10.8
13.0
14.4
18.0
18.0
-1
1
1
1
2
2
1
2
1
1
1
1
2
2
2
2
1
1
1
1
-1
1
1
2
2
2
2
1
1
1
2
-1
1
1
2
2
2
2
1
1
1
1
3
1
Circuit #1
-8.7
17.3
27.9
34.6
45.2
51.9
45.2
51.9
-17.3
27.9
34.6
45.2
51.9
62.5
69.2
45.2
51.9
62.5
69.2
-17.3
27.9
34.6
45.2
51.9
62.5
69.2
45.2
51.9
62.5
69.2
-17.3
27.9
34.6
45.2
51.9
62.5
69.2
45.2
51.9
62.5
69.2
86.5
86.5
21.4
21.4
21.4
21.4
21.4
21.4
21.4
21.4
21.4
29.5
29.5
29.5
29.5
29.5
29.5
29.5
29.5
29.5
29.5
29.5
29.5
34.4
34.4
34.4
34.4
34.4
34.4
34.4
34.4
34.4
34.4
34.4
34.4
39.2
39.2
39.2
39.2
39.2
39.2
39.2
39.2
39.2
39.2
39.2
39.2
39.2
39.2
30
30
30
30
30
30
30
30
30
45
45
45
45
45
45
45
45
45
45
45
45
50
50
50
50
50
50
50
50
50
50
50
50
60
60
60
60
60
60
60
60
60
60
60
60
60
60
Circuit #2
-10.8
21.6
34.9
43.3
37.7
43.3
56.5
64.9
-21.6
34.9
43.3
56.5
43.3
52.1
43.3
56.5
64.9
78.1
86.5
-21.6
34.9
43.3
56.5
43.3
52.1
43.3
56.5
64.9
78.1
86.5
-21.6
34.9
43.3
56.5
43.3
52.1
43.3
56.5
64.9
78.1
86.5
43.3
108.2
-15
25
40
45
40
50
60
70
-25
40
45
40
50
40
45
60
70
80
90
-25
40
45
40
50
40
45
60
70
80
90
-25
40
45
40
50
40
45
60
70
80
90
45
110
Circuit #3
-----18.8
21.6
------21.6
21.6
26.0
43.3
--------21.6
21.6
26.0
43.3
--------21.6
21.6
26.0
43.3
----43.3
--
-----20
25
------20
25
40
45
--------20
25
40
45
--------20
25
40
45
----45
--
Circuit #4
---------------------------------------------21.6
--
---------------------------------------------25
--
1. MCA = Minimum Circuit Ampacity.
2. MOP = Maximum Over Current Protection device; must be HACR type circuit breaker or time delay fuse.
14
Johnson Controls Unitary Products
5127522-BTG-A-0715
Electrical Data for 230-1-60 Multi Source Power
Model
Compressor
RLA
LRA MCC
Electric Heat Option
OD Fan Blower
Motor Motor
FLA
FLA
Heater Kit
Heater kW
230
Stages
Multi Source
Heater Amps
230
230
230
230
230
230
230
230
230
Circuit #1 Compressor Circuit
Multi Source: Compressor
Circuit and Heat Circuits
MCA1
MCA1
MCA1
MCA1
MOP2
MOP2
MOP2
MOP2
Amps
Amps
Amps
Amps
Circuit #2 Heat
Multi Source:
Circuit #2 Heat
Circuit #3 Heat
A24
A30
A36
A42
9
10
13
18
45
57
78
112
14
15
23
28
1.3
1.3
1.3
1.7
Circuit #2
Circuit #3
none
--
--
--
16.0
Circuit #1
20
--
--
--
--
Circuit #4
--
--
6HK(0,1)6500206
2.2
1
9.6
16.0
20
12.0
15
--
--
--
--
6HK(0,1)6500506
4.4
1
19.1
16.0
20
23.9
25
--
--
--
--
3.8 6HK(0,1)6500806
7.1
1
30.9
16.0
20
38.6
40
--
--
--
--
6HK(0,1)6501006
8.8
1
38.3
16.0
20
47.8
50
--
--
--
--
6HK16501306
11.5
2
50.0
16.0
20
41.7
45
20.8
25
--
--
6HK26501306
11.5
1
50.0
16.0
20
62.5
70
--
--
--
--
none
--
--
--
17.4
25
--
--
--
--
--
--
6HK(0,1)6500206
2.2
1
9.6
17.4
25
12.0
15
--
--
--
--
6HK(0,1)6500506
4.4
1
19.1
17.4
25
23.9
25
--
--
--
--
6HK(0,1)6500806
7.1
1
30.9
17.4
25
38.6
40
--
--
--
--
3.8 6HK(0,1)6501006
8.8
1
38.3
17.4
25
47.8
50
--
--
--
--
6HK16501306
11.5
2
50.0
17.4
25
41.7
45
20.8
25
--
--
6HK16501506
13.2
2
57.4
17.4
25
47.8
50
23.9
25
--
--
6HK26501306
11.5
1
50.0
17.4
25
62.5
70
--
--
--
--
6HK26501506
13.2
1
57.4
17.4
25
71.7
80
--
--
--
--
none
--
--
--
21.4
30
--
--
--
--
--
--
6HK(0,1)6500206
2.2
1
9.6
21.4
30
12.0
15
--
--
--
--
6HK(0,1)6500506
4.4
1
19.1
21.4
30
23.9
25
--
--
--
--
6HK(0,1)6500806
7.1
1
30.9
21.4
30
38.6
40
--
--
--
--
3.8 6HK(0,1)6501006
8.8
1
38.3
21.4
30
47.8
50
--
--
--
--
6HK16501306
11.5
2
50.0
21.4
30
41.7
45
20.8
25
--
--
6HK16501506
13.2
2
57.4
21.4
30
47.8
50
23.9
25
--
--
6HK26501306
11.5
1
50.0
21.4
30
62.5
70
--
--
--
--
6HK26501506
13.2
2
57.4
21.4
30
71.7
80
--
--
--
--
none
--
1
--
29.5
45
--
--
--
--
--
--
6HK(0,1)6500506
4.4
1
19.1
29.5
45
23.9
25
--
--
--
--
6HK(0,1)6500806
7.1
1
30.9
29.5
45
38.6
40
--
--
--
--
6HK(0,1)6501006
8.8
1
38.3
29.5
45
47.8
50
--
--
--
--
6HK16501306
11.5
2
50.0
29.5
45
62.5
45
23.9
25
--
--
6HK16501506
13.2
2
57.4
29.5
45
47.8
50
23.9
25
--
--
6HK16501806
15.9
2
69.1
29.5
45
57.6
45
28.8
45
--
--
6HK16502006
17.6
2
76.5
29.5
45
47.8
50
47.8
50
--
--
6HK26501306
11.5
1
50.0
29.5
45
62.5
70
--
--
--
--
6HK26501506
13.2
1
57.4
29.5
45
71.7
80
--
--
--
--
6HK26501806
15.9
1
69.1
29.5
45
86.4
90
--
--
--
--
6HK26502006
17.6
1
76.5
29.5
45
95.7
100
--
--
--
--
5.4
For notes, see Page 16.
Johnson Controls Unitary Products
15
5127522-BTG-A-0715
Electrical Data for 230-1-60 Multi Source Power
Model
Compressor
RLA
LRA MCC
Electric Heat Option
OD Fan Blower
Motor Motor
FLA
FLA
Heater Kit
Heater kW
230
Stages
Multi Source
Heater Amps
230
230
230
230
230
230
230
230
230
Circuit #1 Compressor Circuit
Multi Source: Compressor
Circuit and Heat Circuits
MCA1
MCA1
MCA1
MCA1
MOP2
MOP2
MOP2
MOP2
Amps
Amps
Amps
Amps
Circuit #2 Heat
Multi Source:
Circuit #2 Heat
Circuit #3 Heat
B48
B60
22
24
117
144
34
38
1.7
1.7
5.4
7.0
Circuit #2
Circuit #3
none
--
--
--
34.4
Circuit #1
50
--
--
--
--
Circuit #4
--
--
6HK(0,1)6500506
4.4
1
19.1
34.4
50
23.9
25
--
--
--
--
6HK(0,1)6500806
7.1
1
30.9
34.4
50
38.6
40
--
--
--
--
6HK(0,1)6501006
8.8
1
38.3
34.4
50
47.8
50
--
--
--
--
6HK16501306
11.5
2
50.0
34.4
50
62.5
45
23.9
25
--
--
6HK16501506
13.2
2
57.4
34.4
50
47.8
50
23.9
25
--
--
6HK16501806
15.9
2
69.1
34.4
50
57.6
45
28.8
45
--
--
6HK16502006
17.6
2
76.5
34.4
50
47.8
50
47.8
50
--
--
6HK26501306
11.5
1
50.0
34.4
50
62.5
70
--
--
--
--
6HK26501506
13.2
1
57.4
34.4
50
71.7
80
--
--
--
--
6HK26501806
15.9
1
69.1
34.4
50
86.4
90
--
--
--
--
6HK26502006
17.6
2
76.5
34.4
50
95.7
100
--
--
--
--
none
--
--
--
39.2
60
--
--
--
--
--
--
6HK(0,1)6500506
4.4
1
19.1
39.2
60
23.9
25
--
--
--
--
6HK(0,1)6500806
7.1
1
30.9
39.2
60
38.6
40
--
--
--
--
6HK(0,1)6501006
8.8
1
38.3
39.2
60
47.8
50
--
--
--
--
6HK16501306
11.5
2
50.0
39.2
60
62.5
45
23.9
25
--
--
6HK16501506
13.2
2
57.4
39.2
60
47.8
50
23.9
25
--
--
6HK16501806
15.9
2
69.1
39.2
60
57.6
45
28.8
45
--
--
6HK16502006
17.6
2
76.5
39.2
60
47.8
50
47.8
50
--
--
6HK26501306
11.5
1
50.0
39.2
60
62.5
70
--
--
--
--
6HK26501506
13.2
1
57.4
39.2
60
71.7
80
--
--
--
--
6HK26501806
15.9
1
69.1
39.2
60
86.4
90
--
--
--
--
6HK26502006
17.6
1
76.5
39.2
60
95.7
100
--
--
--
--
6HK16502506
22.0
3
95.7
39.2
60
47.8
50
47.8
50
23.9
25
6HK26502506
22.0
1
95.7
39.2
60
119.6
125
--
--
--
--
1. MCA = Minimum Circuit Ampacity.
2. MOP = Maximum Over Current Protection device; must be HACR type circuit breaker or time delay fuse.
16
Johnson Controls Unitary Products
5127522-BTG-A-0715
Single Point Kit P/N
Unit Model Number
Breaker Size
Heat Kit
S1-2SPWK008
PCE4A24
20 Amp
up to 13 kW
S1-2SPWK006
PCE4A30
25 Amp
up to 15 kW
S1-2SPWK001
PCE4A36
30 Amp
up to 15 kW
S1-2SPWK006
PHE4A24
25 Amp
up to 13 kW
S1-2SPWK002
PHE4A30
35 Amp
up to 15 kW
S1-2SPWK007
PHE4B36
40 Amp
up to 15 kW
S1-2SPWK003
PCE4A42
45 Amp
up to 20 kW
S1-2SPWK003
PHE4B42
45 Amp
up to 20 kW
S1-2SPWK004
PCE4B48
50 Amp
up to 20 kW
S1-2SPWK004
PHE4B48
50 Amp
up to 20 kW
S1-2SPWK005
PCE4B60
60 Amp
up to 20 kW
S1-2SPWK005
PHE4B60
60 Amp
up to 20 kW
FOR USE WITH THE FOLLOWING HEARTER KITS
Heater Kit No.
kW 208/240
Volts
Amps 208/240
6HK16500206
6HK16500506
6HK16500806
6HK16501006
6HK16501306
6HK16501506
6HK16501806
6HK16502006
1.8/2.4
3.6/4.8
5.76/7.68
7.2/9.6
9.36/12.48
10.8/14.4
12.96/17.28
14.4/19.2
280/240
280/240
280/240
280/240
280/240
280/240
280/240
280/240
8.7/10.0
17.3/20.0
27.7/32.0
34.6/40.0
45.0/52.0
51.9/60.0
62.3/72.0
89.2/80.0
TO HEAT KIT GROUND LUG
TO L1 on HEAT KIT BREAKER(S)
TO L2 on HEAT KIT BREAKER(S)
NOTE:
For single circuit heater kits,
remove the wires for the second
circuit from the single-point block.
(Mount with 4 self tapping
screws as shown.)
A0352-003
Johnson Controls Unitary Products
17
5127522-BTG-A-0715
WEIGHTS & DIMENSIONS
"D"
CENTER OF
GRAVITY
COMPRESSOR
"C"
"A"
FRONT
OF UNIT
Y
"B"
X
A0295-001-TG
Weights and Dimensions
Model
PCE4A2421
Weight (lbs.)
Shipping
348
Operating
343
Center of Gravity
X
30
4 Point Load Location (lbs.)
Y
15
A
96
B
105
C
107
D
40
PCE4A3021
394
389
30
15
107
123
123
41
PCE4A3621
400
395
30
15
112
123
120
45
PCE4A4221
471
466
32
13
169
132
131
39
PCE4B4821
488
483
30
19
158
125
130
75
PCE4B6021
505
500
30
20
157
134
140
74
18
Johnson Controls Unitary Products
5127522-BTG-A-0715
AIRFLOW PERFORMANCE
Airflow - Side Duct Application
External Static Pressure (Inches WC)
Model
PCE4A2421
PCE4A3021
PCE4A3621
PCE4A4221
PCE4B4821
PCE4B6021
1.
2.
3.
4.
5.
Motor Speed
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
SCFM
SCFM
SCFM
SCFM
SCFM
SCFM
SCFM
SCFM
Low (1)
887
847
802
750
705
664
613
563
Low/Medium (2)
978
941
898
850
803
759
713
667
Medium (3)
1171
1114
1074
1039
993
949
906
864
Medium/High (4)
1349
1297
1265
1224
1185
1146
1107
1063
1201
High (5)
1487
1462
1392
1331
1318
1281
1241
Low (1)
1076
1020
984
943
903
859
819
779
Low/Medium (2)
1102
1048
1010
974
934
890
850
810
Medium (3)
1191
1140
1112
1076
1038
1000
958
919
Medium/High (4)
1201
1225
1187
1151
1118
1080
1041
1002
High (5)
1370
1329
1283
1271
1209
1176
1143
1109
Low (1)
1225
1174
1131
1090
1046
993
941
888
Low/Medium (2)
1259
1209
1166
1126
1084
1032
980
928
Medium (3)
1314
1271
1229
1186
1144
1097
1049
998
Medium/High (4)
1348
1306
1259
1222
1179
1133
1086
1036
1216
High (5)
1506
1471
1403
1389
1345
1305
1262
Low (1)
1436
1382
1342
1304
1262
1220
1179
1131
Low/Medium (2)
1544
1492
1455
1416
1376
1336
1294
1248
Medium (3)
1573
1523
1484
1445
1408
1367
1327
1279
Medium/High (4)
1681
1640
1599
1557
1517
1478
1436
1393
High (5)
1935
1887
1834
1788
1743
1701
1651
1591
Low (1)
1620
1564
1517
1466
1418
1360
1308
1206
Low/Medium (2)
1694
1630
1580
1530
1482
1430
1380
1292
Medium (3)
1798
1722
1669
1620
1572
1527
1480
1413
Medium/High (4)
1835
1758
1703
1653
1604
1558
1511
1442
High (5)
2146
2085
2025
1960
1872
1862
1798
1735
Low (1)
1730
1682
1628
1592
1552
1517
1479
1439
Low/Medium (2)
1858
1807
1749
1710
1667
1629
1589
1546
Medium (3)
2054
1998
1934
1890
1843
1801
1757
1710
Medium/High (4)
2195
2144
2098
2049
2003
1955
1883
1868
High (5)
2445
2388
2306
2293
2235
2178
2129
2077
Airflow tested with dry coil conditions, without air filters, at 230 volts.
Applications above 0.8" w.c. external static pressure are not recommended.
Brushless DC high efficiency standard ECM blower motor used for all indoor blower assemblies.
Minimal variations in airflow performance data results from operating at 208 volts. Data above may be used in those cases.
Heating applications tested at 0.50" w.c. esp, and cooling applications tested at 0.30" w.c.esp per standards.
Johnson Controls Unitary Products
19
5127522-BTG-A-0715
Airflow - Bottom Duct Application
External Static Pressure (Inches WC)
Model
PCE4A2421
PCE4A3021
PCE4A3621
PCE4A4221
PCE4B4821
PCE4B6021
1.
2.
3.
4.
5.
20
Motor Speed
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
SCFM
SCFM
SCFM
SCFM
SCFM
SCFM
SCFM
SCFM
Low (1)
899
869
827
782
734
685
630
575
Low/Medium (2)
1033
960
924
879
834
787
735
685
Medium (3)
1186
1133
1095
1056
1016
975
935
891
Medium/High (4)
1357
1322
1284
1248
1211
1174
1127
1087
High (5)
1480
1439
1404
1367
1369
1299
1264
1226
Low (1)
1076
1042
1009
969
930
890
849
808
Low/Medium (2)
1104
1063
1025
987
947
908
869
830
Medium (3)
1205
1170
1136
1098
1060
1025
985
943
Medium/High (4)
1285
1251
1213
1179
1141
1104
1065
1027
High (5)
1406
1375
1341
1306
1271
1236
1198
1163
Low (1)
1231
1186
1146
1103
1069
1030
977
912
Low/Medium (2)
1270
1225
1189
1140
1098
1046
1008
960
Medium (3)
1317
1286
1245
1198
1151
1110
1064
1024
Medium/High (4)
1358
1317
1275
1238
1197
1148
1105
1057
High (5)
1517
1475
1447
1400
1357
1318
1275
1232
Low (1)
1455
1414
1379
1335
1294
1254
1212
1160
Low/Medium (2)
1566
1532
1492
1455
1416
1372
1333
1280
Medium (3)
1565
1530
1491
1458
1419
1381
1336
1290
Medium/High (4)
1675
1641
1606
1578
1535
1495
1455
1412
High (5)
1946
1909
1863
1815
1771
1721
1654
1595
Low (1)
1598
1548
1502
1454
1410
1362
1307
1251
Low/Medium (2)
1663
1612
1568
1522
1476
1422
1370
1297
Medium (3)
1789
1733
1670
1650
1596
1578
1535
1483
Medium/High (4)
1931
1814
1808
1736
1673
1650
1597
1519
High (5)
2131
2058
1998
1949
1892
1840
1788
1728
Low (1)
1655
1612
1596
1531
1461
1462
1429
1391
Low/Medium (2)
1766
1720
1667
1629
1632
1539
1537
1498
Medium (3)
1987
1933
1861
1817
1820
1715
1725
1651
Medium/High (4)
2114
2050
2047
1974
1899
1889
1920
1866
High (5)
2369
2308
2249
2183
2126
2088
2034
1990
Airflow tested with dry coil conditions, without air filters, at 230 volts
Applications above 0.8" w.c. external static pressure are not recommended.
Brushless DC high efficiency standard ECM blower motor used for all indoor blower assemblies.
Minimal variations in airflow performance data results from operating at 208 volts. Data above may be used in those cases.
Heating applications tested at 0.50" w.c. esp, and cooling applications tested at 0.30" w.c.esp per standards.
Johnson Controls Unitary Products
5127522-BTG-A-0715
BOTTOM DUCT DIMENSIONS (Inches)
Additional Static Resistance
Size (Tons)
24 (2.0)
30 (2.5)
36 (3.0)
42 (3.5)
48 (4.0)
60 (5.0)
CFM
Wet Indoor Coil
Economizer1
500
600
700
800
900
1000
1100
1200
700
800
900
1000
1100
1200
1300
700
800
900
1000
1100
1200
1300
1400
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
0.01
0.01
0.01
0.02
0.03
0.04
0.05
0.06
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.02
0.03
0.04
0.05
0.06
0.07
0.07
0.08
0.09
0.09
0.02
0.03
0.04
0.05
0.06
0.07
0.07
0.08
0.09
0.09
0.02
0.03
0.04
0.05
0.06
0.07
0.07
0.08
0.09
0.09
0.00
0.00
0.00
0.01
0.01
0.01
0.01
0.02
0.00
0.01
0.01
0.01
0.01
0.02
0.03
0.00
0.01
0.01
0.01
0.01
0.02
0.03
0.04
0.02
0.02
0.02
0.03
0.04
0.04
0.04
0.04
0.05
0.05
0.02
0.02
0.02
0.03
0.04
0.04
0.04
0.04
0.05
0.05
0.02
0.02
0.02
0.03
0.04
0.04
0.04
0.04
0.05
0.05
Filter/Frame Kit
0.01
0.02
0.04
0.06
0.08
0.10
0.13
0.16
0.04
0.06
0.08
0.10
0.13
0.16
0.17
0.04
0.06
0.08
0.10
0.13
0.16
0.17
0.18
0.04
0.04
0.05
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.04
0.04
0.05
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.04
0.04
0.05
0.05
0.06
0.07
0.08
0.09
0.10
0.11
'
&
5(7851
$,5'8&7
$
(
%
6833/<
$,5'8&7
$
)
$
Model
A
B
C
D
E
F
24, 30, 36, 42
10
21.5
5
4.5
47.5
32
48, 60
14
13.5
5
3.5
47.5
42
REAR DUCT DIMENSIONS (Inches)
SUPPLY
AIR DUCT
15.6
RETURN
AIR DUCT
6
A
B
A
4.3
A0344-001
Model
A
B
24, 30, 36, 42
9.6
22
48, 60
13.6
14
1. The pressure drop through the economizer is greater for 100% outdoor air
than for 100% return air. If the resistance of the return air duct is less than
0.25 IWG, the unit will deliver less CFM during full economizer operation.
Filter pressure drop based on standard filter media tested at velocities not to
exceed 300 ft/min.
Johnson Controls Unitary Products
21
5127522-BTG-A-0715
UNIT TYPICAL DUCT APPLICATIONS
ROOF CURB
INSTALLATION
REAR DUCT
ROOF CURB
INSTALLATION
BOTTOM DUCT
SLAB ON
GROUND
INSTALLATION
A0324-001
UNIT TYPICAL SLAB ON GROUND INSTALLATION
TO POWER SUPPLY
RETURN
AIR DUCT
SUPPLY
AIR DUCT
FIELD-SUPPLIED
DISCONNECT
SWITCH
CONDENSATE
DRAIN
CONTROL WIRING TO
INDOOR THERMOSTAT
A0390-001
22
Johnson Controls Unitary Products
5127522-BTG-A-0715
UNIT TYPICAL ROOF CURB INSTALLATION
ROOF
CONDENSATE
DRAIN
ROOF CURB
FIELD-SUPPLIED
DISCONNECT
SWITCH
TO POWER SUPPLY
CONTROL WIRING TO
INDOOR THERMOSTAT
RETURN
AIR DUCT
SUPPLY
AIR DUCT
A0389-001
EXTERNAL STATIC PRESSURE SETUP
To measure external static pressure:
•
•
•
•
•
•
Measure the supply air static pressure
Record this positive number
Measure the return air static pressure
Record this negative number
Treat the negative number as a positive and add the two numbers together
This is total system static
Johnson Controls Unitary Products
23
NOTES
Subject to change without notice. Published in U.S.A.
Copyright © 2015 by Johnson Controls, Inc. All rights reserved.
York International Corp.
5005 York Drive
Norman, OK 73069
5127522-BTG-A-0715
Supersedes: Nothing
Download PDF