K-Series™ Rooftop Units 3 to 7.5 Tons Net Cooling Capacity

PA C KA G E D G A S / e l e c t r i c
KGA
K-Series™ Rooftop Units
Standard Efficiency - 60 HZ
Bulletin No. KGA/KGB-024-090 (10/2016)
P R O D U C T S P E C I F I C AT I O N S
ASHRAE 90.1
COMPLIANT
3 to 7.5 Tons
Net Cooling Capacity − 36,000 to 90,000 Btuh
Gas Input Heat Capacity − 65,000 to 150,000 Btuh
MODEL NUMBER IDENTIFICATION
K G A 060 S 4 B S 1 Y
Brand/Family
K = K-Series™ Product Line
Voltage
Y = 208/230V-3 phase-60hz
G = 460V-3 phase-60hz
J = 575V-3 phase-60hz
Unit Type
G = Packaged Gas Heat w/ Electric Cooling
Minor Design Sequence
1 = 1st Revision
2 = 2nd Revision
3 = 3rd Revision
Major Design Sequence
A = 1st Generation
Nominal Cooling Capacity - Tons
036 = 3 Tons
048 = 4 Tons
060 = 5 Tons
072 = 6 Tons
090 = 7.5 Tons
Cooling Efficiency
S = Standard Efficiency
Refrigerant Type
4 = R-410A
Heating Type
S = Standard Gas Heat, 1 stage
M = Medium Gas Heat, 1 stage
U = Medium Gas Heat, 2 Stage
T = High Gas Heat, 1 Stage
H = High Gas Heat, 2 Stage
W = Standard Gas Heat, 1 Stage, Low NOx
B = Standard Gas Heat, 2 Stage Low NOx
Y = Medium Gas Heat, 1 Stage, Low NOx
Q = Medium Gas Heat, 2 Stage, Low NOx
Z = High Gas Heat, 1 Stage, Low NOx
X = High Gas Heat, 2 Stage, Low NOx
Blower Type
D = Direct Drive
B = Belt Drive
FEATURES AND BENEFITS
H
K
M
G
O
E
C
F
N
J
D
L
B
I
KGA090S
(Cooling & Gas Heat)
Shown With Optional Economizer, Power Exhaust and
Hinged Access Panels
K-Series™ rooftop units from Allied are the new standard for reliable, efficient rooftop units built for long-lasting
performance that can significantly improve indoor environments. K-Series™ rooftop units feature:
•
•
•
•
•
•
•
•
•
•
•
R-410A Refrigerant - Environmentally friendly.
Single Speed Scroll Compressor - Furnished on all models.
Eco-Last™ Coil System (KGA072 and 090 Models) - Smaller, lighter condenser coil with improved heat transfer.
High Pressure Switches - Protect compressor.
Isolated Compressor Compartment - Allows performance check during normal compressor operation without
disrupting airflow.
Direct or Belt Drive Blower Motors - Direct drive (036, 048 and 060 models). Belt drive motors
(036, 048, 060, 072 and 090 models) to maximize air performance.
Independent Motor Mounts - Allows for easy and efficient service access without removing the top panel.
Downflow or Horizontal Airflow - Easy field conversion.
Two Fork Lift Slots on Three Sides - Easy to pick up and transport units from almost any angle.
Corrosion-Resistant Removable, Reversible Drain Pan - Provides application flexibility, durability and improved
serviceability.
Common Components - Many maintenance items are standard throughout the entire product line, reducing the
need to carry different parts to the job or maintain in inventory.
K-Series™ KGA Packaged Gas / Electric 3 to 7.5 Tons / Page 2
FEATURES AND BENEFITS
CONTENTS
Blower Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Dimensions - Accessories . . . . . . . . . . . . . . . . . . . . . . . . . 36
Dimensions - Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Features And Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
High Altitude Derate . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Model Number Identification . . . . . . . . . . . . . . . . . . . . . . . . .1
Options / Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Outdoor Sound Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Specifications - Belt Drive Blower . . . . . . . . . . . . . . . . . . . . . 14
Specifications - Direct Drive Blower . . . . . . . . . . . . . . . . . . . . 13
Specifications - Standard Gas Heat . . . . . . . . . . . . . . . . . . . . 15
Unit Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Weight Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
APPROVALS
AHRI Certified to AHRI Standard
210/240-2008 (2 thru 5 ton models)
and AHRI Standard 340/360-2007
(6 and 7.5 ton models).
ETL and CSA listed.
Units are Certified by CSA.
Components bonded for grounding
to meet safety standards for
servicing required by UL, ULC and
National and Canadian Electrical
Codes.
All models are ASHRAE 90.1
compliant.
ISO 9001 Registered
Manufacturing Quality System.
Models equipped with low NOx gas
heat meet the California Nitrogen
Oxides (NOx) Standards that apply
in the South Coast Air Quality
Management District and the San
Francisco Bay Area Air Quality
Management District.
WARRANTY
Limited ten years aluminized
heat exchanger, limited fifteen
years optional stainless steel heat
exchanger.
Limited five years on compressors.
Limited three years on the EcoLast™ Coil System.
Limited five years Optional High
Performance Economizers.
Limited one year all other covered
components.
HEATING SYSTEM
B Aluminized steel inshot burners,
direct spark ignition, electronic
flame sensor, combustion air
inducer, redundant automatic
single or dual stage gas valve with
manual shut-off.
Heat Exchanger
Tubular construction, aluminized
steel, life cycle tested.
Stainless Steel Heat Exchanger is
required if mixed air temperature is
below 45°F.
C Electronic Pilot Ignition
Electronic spark igniter provides
positive direct ignition of burners
on each operating cycle. The
system permits main gas valve to
stay open only when the burners
are proven to be lit. Should a
loss of flame occur, the gas valve
closes, shutting off the gas to
the burners. Ignition module has
LED to indicate status and aid in
troubleshooting.
Watchguard circuit on module
automatically resets ignition
controls after one hour of
continuous thermostat demand
after unit lockout, eliminating
nuisance service calls. Ignition
control is factory installed in the
controls section.
Limit Controls
Factory installed, redundant limit
controls with fixed temperature
setting.
Heat limit controls protect heat
exchanger and other components
from overheating.
Safety Switches
Flame roll-out switch, flame sensor
and combustion air inducer proving
switch protect system operation.
Low NOx Models
All single phase models are
available in low NOx versions.
Required Selections
Gas Input Choice - Order one:
• S tandard Gas Heat (1 Stage)
65,000 Btuh
(Not available for 090 models)
• S tandard Gas Heat (2 Stage)
70,000/53,000 Btuh
(Not available for 090 models)
• M edium Gas Heat (1 Stage)
108,000 Btuh
• M edium Gas Heat (2 Stage)
81,000/108,000 Btuh
• High Gas Heat (1 Stage)
150,000 Btuh
• High Gas Heat (2 Stage)
113,000/150,000 Btuh
Standard or Low NOx
Specify standard gas heat or Low
NOx option (three phase models
only).
NOTE - Standard Gas Heat
(2 Stage) is only available with Low
NOx models.
Options/Accessories
Factory Installed
Stainless Steel Heat Exchanger
Required if mixed air temperature
is below 45°F.
Field Installed
Combustion Air Intake
Extensions
Recommended for use with
existing flue extension kits in areas
where high snow areas can block
intake air.
K-Series™ KGA Packaged Gas / Electric 3 to 7.5 Tons/ Page 3
FEATURES AND BENEFITS
HEATING SYSTEM
(continued)
Low Temperature Vestibule
Heater
Electric heater automatically
controls minimum temperature in
gas burner compartment when
temperature is below -40°F. C.S.A.
certified to allow operation of unit
down to -60°F.
LPG/Propane Kits
Conversion kit to field change over
units from Natural Gas to LPG/
Propane.
Vertical Vent Extension Kit
Use to exhaust flue gases
vertically above unit. Required
when unit vent is too close to fresh
air intakes per building codes. The
vent kit also prevents ice formation
on intake louvers.
COOLING SYSTEM
Designed to maximize sensible
and latent cooling performance at
design conditions.
System can operate from 30°F
to 125°F without any additional
controls.
R-410A Refrigerant
Non-chlorine, ozone friendly,
R-410A.
Unit is factory pre-charged with
refrigerant. See Specifications
Tables.
D Single Speed Scroll Compressor
Scroll compressors for high
performance, reliability and quiet
operation.
Resiliently mounted on rubber
grommets for quiet operation.
Compressor Crankcase Heater
(Furnished on all KGA072 and
090 Models)
Protects against refrigerant
migration that can occur during low
ambient operation.
E Refrigerant Metering Orifice
Accurately meters refrigerant in
system.
Refrigerant control is accomplished
by exact sizing of refrigerant
metering orifice.
Filter/Drier
High capacity filter/drier protects
the system from dirt and moisture.
High Pressure Switch
Protects the compressor from
overload conditions such as
dirty condenser coils, blocked
refrigerant flow, or loss of outdoor
fan operation.
Freezestat
Protects the evaporator coil from
damaging ice build-up due to
conditions such as low/no air flow,
or low refrigerant charge.
F Eco-Last™ Coil System
(All KGA072 and 090 Models)
Condenser coil features
lightweight,
all aluminum
brazed fin
construction.
Constructed
of three
components:
a flat
extrusion
tube, fins in-between the flat
extrusion tubes and two refrigerant
manifolds.
Eco-Last™ Coil System Features:
• I mproved heat transfer
performance due to high
primary surface area (flat
tubes) versus secondary
surface (fins).
• S maller internal volume
(reduced refrigerant charge).
• H igh durability (all aluminum
construction).
• Fewer brazed joints.
• C ompact design (reduces unit
weight).
• Easy maintenance/cleaning.
Mounting brackets with rubber
inserts secure coil to unit providing
vibration dampening and corrosion
protection.
K-Series™ KGA Packaged Gas / Electric 3 to 7.5 Tons / Page 4
Conventional Fin/Tube Coil
(Condenser Coil for KGA036
thru 060 Models) and Evaporator
Coil (all models)
Copper tube construction,
enhanced rippled-edge aluminum
fins, flared shoulder tubing
connections, silver soldered
construction for improved heat
transfer. Factory leak tested
Evaporator coil cross row circuiting
with rifled tubing optimizes both
sensible and latent cooling
capacity.
Condensate Drain Pan
Plastic pan, sloped to meet
drainage requirements of ASHRAE
62.1.
Side or bottom drain connections.
Reversible to allow connection at
back of unit.
G Outdoor Coil Fan Motor
Thermal overload protected, totally
enclosed, permanently lubricated
sleeve (036 and 048 models) or
ball bearings (060, 072, 074 and
090 models), shaft up, wire basket
mount.
Outdoor Coil Fan
PVC coated fan guard furnished.
Required Selections
Cooling Capacity
Specify nominal cooling capacity of
the unit.
Options/Accessories
Field Installed
Condensate Drain Trap
Field installed only.
Available in copper or PVC.
Compressor Crankcase Heater
(Optional for KGA036 thru 060
Models Only)
Protects against refrigerant
migration that can occur during low
ambient operation.
Drain Pan Overflow Switch
Monitors condensate level in
drain pan, shuts down unit if drain
becomes clogged.
FEATURES AND BENEFITS
COOLING SYSTEM
(continued)
Options/Accessories (continued)
Low Ambient Kit
Cycles the outdoor fan while
allowing compressor operation in
the cooling cycle. This intermittent
fan operation allows the system
to operate without icing the
evaporator coil and losing capacity.
Designed for use in ambient
temperatures no lower than 0°F. A
crankcase heater must be installed
on the compressor.
CABINET
H Construction
Heavy-gauge steel panels and full
perimeter heavy-gauge galvanized
steel base rail provides structural
integrity for transportation,
handling, and installation.
Base rails have rigging holes.
Three sides of the base rail have
fork slots.
Raised edges around duct and
power entry openings in the bottom
of the unit provide additional
protection against water entering
the building.
Airflow Choice
Units are shipped in downflow
(vertical) configuration, can be
field converted to horizontal air
flow configuration without the
need of a kit.
I Power/Gas Entry
Electrical and gas lines can be
brought through the unit base or
through horizontal access knockouts.
Optional Bottom Gas Entry Kit is
available.
J Exterior Panels
Constructed of heavy-gauge,
galvanized steel with a two-layer
enamel paint finish.
Access Panels
Access panels are provided for
the economizer/filter section,
heating/blower section, and the
compressor/controls section.
NOTE - KGA072/090 models
include a filler panel for proper
cabinet fit for optional accessories
(Economizers, Power Exhaust,
Outdoor Air Dampers and
Barometric Relief Dampers).
Options/Accessories
Factory Installed
Corrosion Protection
A completely flexible immersed
coating with an electrodeposited dry film process (AST
ElectroFin E-Coat). Meets Mil
Spec MIL-P-53084, ASTM B117
Standard Method Salt Spray
Testing.
Indoor Corrosion Protection:
- Coated coil
- Painted blower housing
- Painted base
Outdoor Corrosion Protection:
- Coated coil
- Painted base
L Hinged Access Panels
CONTROLS
Unit Control
All control voltage is provided via a
24V (secondary) transformer with
built-in circuit breaker protection.
Heat/Cool Staging - Capable of
up to 2 heat / 2 cool staging with a
third party DDC control system or
thermostat.
Low Voltage Terminal Block Provides screw terminal
connections for thermostat or
controller wiring.
Night Setback Mode - Saves
energy by closing outdoor air
dampers and operating supply fan
on thermostat demand only.
Options / Accessories
Field Installed
Smoke Detector
Photoelectric type, installed in
supply air section, return air
section or both sections. Available
with power board and single
sensor (supply or return) or power
board and two sensors (supply and
return). Power board located in unit
control compartment.
Large access panels are hinged
and have quarter-turn latches
for quick and easy access to
maintenance areas (economizer
/ filter, compressor / controls,
heating / blower).
Field Installed
Combination Coil/Hail Guards
Heavy gauge steel frame painted
to match cabinet with expanded
metal mesh to protect the outdoor
coil from damage.
Bottom Gas Entry Kit
Field installed piping kit to facilitate
bottom gas entry.
K Insulation
All panels adjacent to conditioned
air are fully insulated with nonhygroscopic fiberglass insulation.
Unit base is fully insulated. The
insulation also serves as an air
seal to the roof curb, eliminating
the need to add a seal during
installation.
K-Series™ KGA Packaged Gas / Electric 3 to 7.5 Tons/ Page 5
FEATURES AND BENEFITS
M BLOWER
A wide selection of supply air
blower options are available
to meet a variety of air flow
requirements.
Motor
Overload protected, equipped with
ball bearings (belt drive) or sleeve
bearings (direct drive).
Direct drive motors are offered on
036, 048 and 060 models.
Single Speed belt drive motors are
offered on 036, 048, 060, 072 and
090 models and are available in
several different sizes to maximize
air performance.
Supply Air Blower
Forward curved blades, blower
wheel is statically and dynamically
balanced.
All belt drive motors have
adjustable pulley for speed
change.
Ordering Information
Specify direct drive or belt drive
motor.
For belt drive, specify motor
horsepower and drive kit number
when base unit is ordered.
INDOOR AIR QUALITY
Air Filters
Disposable 2 inch filters furnished
as standard.
Options/Accessories
Field Installed
High Performance Air Filters
Disposable MERV 8 or MERV 13
(Minimum Efficiency Reporting
Value based on ASHRAE 52.2)
efficiency 2 inch pleated filters.
UVC Germicidal Lamps
ELECTRICAL
Marked & Color-Coded Wiring
All electrical wiring is color-coded
and marked to identify which
components it is connecting.
Electrical Plugs
Positive connection electrical plugs
are used to connect common
accessories or maintenance parts
for easy removal or installation.
Required Selections
Voltage Choice
Specify when ordering base unit.
Options/Accessories
Factory or Field Installed
Helps eliminate mold and bacterial
growth on the evaporator and drain
pans. Improves indoor air quality
and maintains efficiency of system
by reducing fouling of evaporator
coil.
Indoor Air Quality (CO2) Sensor
Monitors CO2 levels adjusts
economizer dampers as needed
for Demand Control Ventilation.
Required Selections
Supply Air Blower
Order one, belt drive or direct
drive (See Blower Data Table for
specifications).
Order one drive kit, belt drive only,
see Drive Kit Specifications Table.
K-Series™ KGA Packaged Gas / Electric 3 to 7.5 Tons / Page 6
Disconnect Switch (80 Amp)
Accessible from outside of unit,
spring loaded weatherproof cover
furnished. Main power to the unit is
field connected to the disconnect
which allows all power to be shut
off for service. See Electrical Data
tables for ordering information, .
GFI Service Outlets (2)
115V ground fault circuit interrupter
(GFCI) type, non-powered, fieldwired.
Field Installed
GFI Weatherproof Cover
Single-gang cover.
Heavy-duty UV-resistant
polycarbonate case construction.
Hinged base cover with gasket.
OPTIONS / ACCESSORIES
ECONOMIZER OPTIONS
Factory or Field Installed
N Economizer
(Standard and High Performance
Common Features)
Outdoor Air Hood is furnished.
Factory installed Economizer
can be ordered with two exhaust
options:
• Barometric Relief Dampers
and Exhaust Hood.
• No Exhaust.
Field installed Economizer includes
Barometric Relief Dampers with
Exhaust Hood.
Barometric Relief Dampers allow
relief of excess air, aluminum blade
dampers prevent blow back and
outdoor air infiltration during off
cycle, bird screen furnished.
Occupied/Unoccupied mode with
field furnished setback thermostat.
Demand Control Ventilation (DCV)
ready using optional CO2 sensors.
Mixed Air Sensor is furnished for
field installation in the rooftop unit.
Sensor is factory installed when
Economizers are factory installed.
Single sensible sensor is furnished
with Economizer and enables
economizer operation if the
outdoor temperature is less than
the setpoint of the control.
Horizontal Economizer Conversion
kit is available for field installation.
Standard Economizer Features
(Not for Title 24)
Gear-driven action, return air
and outdoor air dampers, plugin connections to unit, neoprene
seals, 24-volt, fully-modulating
spring return motor.
Standard Economizer
Control Module
The Standard
Economizer
Control Module
can be adjusted
to operate based
on outdoor air
temperatures.
Economizer Controls:
• D
amper Minimum Position
- Can be set lower than
traditional minimum air
requirements resulting in cost
savings.
• IAQ Sensor - Signals
dampers to modulate and
maintain 55°F when CO2 is
higher than the CO2 setpoint.
• Demand Control Ventilation
(DCV) LED - A steady green
Demand Control Ventilation
LED indicates the IAQ reading
is higher than setpoint and
requires more fresh air.
• Free Cool LED - A steady
green LED indicates outdoor
air is suitable for free cooling.
Free Cooling runs when outdoor
air temperature is lower than
the set temperature on the
economizer control.
NOTE: The Free Cooling
default setting for outdoor air
temperature sensor is 55°F.
High Performance
Economizer Features
Approved for California Title 24
building standards.
ASHRAE 90.1-2010 compliant.
Gear-driven action, high torque
24-volt fully-modulating spring
return damper motor, return air
and outdoor air dampers, plug-in
connections to unit, nylon bearings,
enhanced neoprene blade edge
seals and flexible stainless steel
jamb seals to minimize air leakage.
NOTE - High Performance
Economizers are not approved for
use with enthalpy controls in Title
24 applications.
Module automatically detects
sensors by polling to determine
which sensors are installed in
system.
Module displays any alarm
messages (fault detection
and diagnostics) as an aid in
troubleshooting.
Non-volatile memory retains
parameter settings in case of
power failure.
Keypad with four navigation
buttons and LCD screen is
furnished for setting economizer
parameters.
• Menu Up/Exit
button
returns to the main menu.
• Arrow Up button moves
to the previous or next
parameter within the selected
menu.
• Arrow Down button moves
to the next parameter within
the selected menu.
• Select (enter) button
confirms parameter selection.
Main Menu Structure:
• STATUS (economizer and
system operation status)
• SETPOINTS (settings for
various setpoint parameters)
• SYSTEM SETUP (settings/
information about the system)
• ADVANCED SETUP (freeze
protection, CO2 settings,
stage 3 delay and additional
calibration settings)
• CHECKOUT (damper
positions)
• ALARMS (output signal that
can be configured for remote
alarm monitoring)
High Performance
Economizer Control Module
Module provides inputs and
outputs
to control
economizer
based on
parameter
settings.
K-Series™ KGA Packaged Gas / Electric 3 to 7.5 Tons/ Page 7
OPTIONS / ACCESSORIES
ECONOMIZER OPTIONS
(continued)
NOTE - The Free Cooling
setpoint for Title 24 applications
must be set based on the
Climate Zone where the system
is installed. See Section 140.4
“Prescriptive Requirements for
Space Conditioning Systems”
of the California Energy
Commission’s 2013 Building
Energy Efficiency Standards.
Refer to Installation Instructions
for complete setup information
and menu parameters available.
Factory or Field Installed
Single Enthalpy Temperature
Control
(Not for Title 24)
Outdoor air enthalpy sensor
enables Economizer if the outdoor
enthalpy is less than the setpoint of
the control.
Field Installed
Differential Enthalpy Control
(Not for Title 24)
Order two Single Enthalpy
Controls. One is field installed in
the return air section, the other in
the outdoor air section. Allows the
economizer control board to select
between outdoor air or return air,
whichever has lower enthalpy.
Horizontal Economizer
Conversion Kit
Insulated panel covers the bottom
return air opening on the unit base
to convert downflow Economizer to
horizontal airflow.
EXHAUST OPTIONS
Field Installed
O Power Exhaust Fan
Installs internal to unit for downflow
applications only with Economizer
option. Provides exhaust air
pressure relief. Interlocked to
run when supply air blower is
operating, fan runs when outdoor
air dampers are 50% open
(adjustable), motor is overload
protected.
Fan is 16 in. diameter with 4 fan
blades and a 1/3 hp motor.
NOTE - If Power Exhaust is field
installed with a factory installed
Economizer, the Economizer must
be ordered with the “No Exhaust”
option and the Barometric Relief
Dampers with Exhaust Hood must
also be ordered separately for field
installation.
OUTDOOR AIR OPTIONS
Factory or Field Installed
Outdoor Air Dampers Downflow or Horizontal
Linked mechanical dampers, 0 to
35% (fixed) outdoor air adjustable,
installs in unit.
Automatic model features fully
modulating spring return damper
motor with plug-in connection.
Manual model features a slide
damper. Maximum mixed air
temperature in cooling mode:
100°F.
Outdoor Air Hood is furnished.
ROOF CURBS
Nailer strip furnished, mates
to unit, US National Roofing
Contractors Approved, shipped
knocked down.
Hybrid Roof Curbs, Downflow
Roof curb can be assembled using
interlocking tabs to fasten corners
together. No tools required.
Curb can also be fastened together
with furnished hardware.
Available in 8, 14, 18, and 24 inch
heights.
Full Perimeter Curbs, Downflow
(090 Models Only)
Hybrid roof curbs can be
assembled using interlocking tabs
to fasten corners together. No tools
required.
Hybrid roof curbs can also be
fastened together with furnished
hardware.
Available in 8, 14, 18, and 24 inch
heights.
NOTE - 090 models can be used
on smaller 79-3/4 in. Hybrid Roof
Curbs (not full perimeter) with 153/4 in. overhang at condenser end
of unit. See dimension drawing on
page 40.
K-Series™ KGA Packaged Gas / Electric 3 to 7.5 Tons / Page 8
Adjustable Pitch Curb
Fully adjustable pitch curb provides
a level platform for rooftop units
allowing flexible installations
on roofs with uneven or sloped
angles.
Maximum slope is 3/4 in. per foot
in any direction.
Uses interlocking tabs to fasten
corners together. No tools required.
Hardware is furnished to connect
upper curb with lower curb.
Available in 14 inch height.
Adaptor Curbs (not shown)
Curbs are regionally sourced.
Dimensions will vary based
upon the source. Contact your
local sales representative for a
detailed cut sheet with applicable
dimensions.
CEILING DIFFUSERS
Ceiling Diffusers (Flush and
Step-Down)
Diffuser face and grilles with white
powder coat finish, insulated (UL
listed duct liner), diffuser box
with collars for duct connection,
fixed blades (flush diffusers) and
double deflection blades (stepdown diffusers), provisions for
suspending, internally sealed
(prevents recirculation), removable
return air grille, adapts to T-bar
ceiling grids or plaster ceilings.
Transitions (Supply and Return)
Used with diffusers, installs
in roof curb, galvanized steel
construction, flanges furnished for
duct connection to diffusers, fully
insulated.
OPTIONS / ACCESSORIES
Unit Model No.
Item
Model Catalog KGA KGA KGA KGA KGA
No.
No.
036 048 060 072 090
COOLING SYSTEM
Compressor Crankcase Heater
Condensate Drain Trap
208/230V-3ph - K1CCHT02A-2P
14D86
208/230V-3ph - T1CCHT01AN2P
14D83
460V-3ph - K1CCHT012A-2G
14D87
460V-3ph - T1CCHT01AN2G
14D84
575V-3ph - K1CCHT02A-2J
14D88
575V-3ph - T1CCHT01AN2J
14D85
PVC - C1TRAP20AD2
76W26
Copper - C1TRAP10AD2
76W27
Corrosion Protection
Drain Pan Overflow Switch
K1SNSR71AB1-
Low Ambient Kit
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
O
O
O
O
O
X
X
X
X
X
74W42
14D89
X
X
X
X
X
Standard
O
O
O
O
O
R-410A
O
O
O
O
O
T1GPKT01AN1
19W50
X
X
X
X
X
208/230V-3 ph - T1CWKT01AN1Y
19W53
X
X
X
X
X
460V-3ph - T1CWKT01AN1G
19W54
X
X
X
X
X
575V-3ph - T1CWKT01AN1J
19W62
X
X
X
X
X
T1EXTN10AN1
19W51
X
X
X
X
X
K1SNSR33AN2
Efficiency
Refrigerant Type
HEATING SYSTEM
Bottom Gas Piping Kit
Low Temperature Vestibule Heater
Combustion Air Intake Extensions
Gas Heat Input
Standard One-Stage - 65 kBtuh input
Factory
Standard Two-Stage - 53/70 kBtuh input
Factory
LPG/Propane
Conversion Kits
1
O
O
1
O
O
1
O
O
1
O
1
O
Medium One-Stage - 108 kBtuh input
Factory
O
O
O
O
O
Medium Two Stage - 81/108 kBtuh input
Factory
O
O
O
O
O
High One-Stage - 150 kBtuh input
Factory
O
O
O
O
High Two-Stage - 113/150 kBtuh input
Factory
O
O
O
O
For one-stage models - C1PROP10AP2
14N20
X
X
X
X
X
For two-stage models - C1PROP20AP2
14N21
X
X
X
X
X
Factory
O
O
O
O
O
31W62
X
X
X
X
X
Stainless Steel Heat Exchanger
Vertical Vent Extension
O
1
C1EXTN20FF1
Standard Two-Stage Heat is only available with Low NOx Models.
NOTE - The catalog and model numbers that appear here are for ordering field installed accessories only.
OX - Field Installed or Configure to Order (factory installed)
O - Configure to Order (Factory Installed)
X - Field Installed.
K-Series™ KGA Packaged Gas / Electric 3 to 7.5 Tons/ Page 9
OPTIONS / ACCESSORIES
Unit Model No.
Item
Model Catalog KGA KGA KGA KGA KGA
No.
No.
036 048 060 072 090
BLOWER - SUPPLY AIR
Motors
Direct Drive - 0.5 hp (208/230V-3ph, 460V-3ph, 575V-3ph)
Factory
Direct Drive - 0.75 hp (208/230V-3ph, 460V-3ph, 575V-3ph)
Factory
Belt Drive - 1 hp (208/230V, 460V, 575V-3ph) Standard Efficiency
Factory
O
O
O
1
O
O
Belt Drive - 2 hp (208/230V, 460V, 575V-3ph) Standard Efficiency
Factory
O
O
O
1
O
O
Belt Drive - 3 hp (208/230V, 460V, 575V-3ph) Standard Efficiency
Factory
Belt Drive - 1 hp (208/230V, 460V, 575V-3ph) ( 2 Speed)
Factory
O
Belt Drive - 2 hp (208/230V, 460V, 575V-3ph) (2 Speed)
Factory
O
Kit A01 - T1DRKT001-1 - 673-1010 rpm
Factory
Kit A02 - T1DRKT002-1 - 745-1117 rpm
Factory
Kit A03 - T1DRKT003-1 - 833-1250 rpm
Factory
Kit A04 - T1DRKT004-1 - 968-1340 rpm
Factory
Kit A05 - T1DRKT005-1 - 897-1346 rpm
Factory
Kit A06 - T1DRKT006-1 - 1071-1429 rpm
Factory
Kit A07 - T1DRKT007-1 - 1212-1548 rpm
Factory
Kit A08 - T1DRKT008-1 - 1193-1591 rpm
Factory
Kit AA01 - T1DRKT001AP1 - 522-784 rpm
Factory
O
O
Kit AA02 - T1DRKT002AP1 - 632-875 rpm
Factory
O
O
Kit AA03 - T1DRKT003AP1 - 798-1105 rpm
Factory
O
O
Kit AA04 - T1DRKT004AP1 - 921-1228 rpm
Factory
C1GARD51A-1
13R98
C1GARD51AT1
13T03
K1GARD50AP1
13T17
Drive Kits
See Blower Data Tables
for selection
O
O
O
O
O
O
O
1
O
1
O
O
O
O
O
CABINET
Combination Coil/Hail Guards
Hinged Access Panels
X
X
X
X
X
O
O
O
OX
OX
OX
O
O
CONTROLS
Commercial Controls
BACnet®
K0CTRL31A-1
96W14
K0CTRL31AP1
12B99
OX
OX
BACnet® Thermostat with Display
K0SNSR01FF1
97W23
X
X
X
X
X
BACnet Thermostat without Display
K0SNSR00FF1
97W24
X
X
X
X
X
OX
OX
OX
OX
OX
®
K0CTRL30A-1
96W14
K0CTRL30AP1
12B99
K0MISC00FF1
97W25
X
X
X
X
X
Smoke Detector - Supply or Return
(Power board and one sensor)
C1SNSR44AP1
53W78
X
X
X
X
X
Smoke Detector - Supply and Return
(Power board and two sensors)
C1SNSR43AP1
53W79
X
X
X
X
X
Novar 2051
®
Plenum Cable (75 ft.)
1
072 Single Speed Belt Drive models only.
NOTE - The catalog and model numbers that appear here are for ordering field installed accessories only.
OX - Field Installed or Configure to Order (factory installed)
O - Configure to Order (Factory Installed)
X - Field Installed.
K-Series™ KGA Packaged Gas / Electric 3 to 7.5 Tons / Page 10
OPTIONS / ACCESSORIES
Unit Model No.
Item
Model Catalog KGA KGA KGA KGA KGA
No.
No.
036 048 060 072 090
ECONOMIZER
Standard Economizer With Outdoor Air Hood (Sensible Control) (Not for Title 24)
Standard Economizer - Includes Barometric Relief Dampers and
Exhaust Hood
K1ECON30A-3-
Standard Economizer - No Exhaust
14D90
OX
OX
OX
OX
OX
Factory
O
O
O
O
O
Standard Economizer Controls (Not for Title 24)
Single Enthalpy Control
C1SNSR64FF1
53W64
OX
OX
OX
OX
OX
Differential Enthalpy Control (order 2)
C1SNSR64FF1
53W64
X
X
X
X
X
K1ECON32A-2
14D91
OX
OX
OX
OX
OX
Single Enthalpy Control
C1SNSR60FF1
10Z75
OX
OX
OX
OX
OX
Differential Enthalpy Control (order 2)
C1SNSR60FF1
10Z75
X
X
X
X
X
T1HECK00AN1
17W45
X
X
X
X
X
Motorized
K1DAMP21A-1
79W95
OX
OX
OX
OX
OX
Manual
C1DAMP11A-1
53W34
OX
OX
OX
OX
OX
208/230V-1 or 3ph - C1PWRE10A-1P
79W87
X
X
X
X
X
460V-3ph - C1PWRE10A-1G
79W88
X
X
X
X
X
575V-3ph - C1PWRE10A-1J
79W89
X
X
X
X
X
C1DAMP50A-1-
74W38
X
X
X
X
X
208/230V - 1 phase
Factory
O
O
O
208/230V - 3 phase
Factory
O
O
O
O
O
460V - 3 phase
Factory
O
O
O
O
O
575V - 3 phase
Factory
O
O
O
O
O
OX
OX
OX
OX
OX
15 amp non-powered, field-wired (208/230V, 460V only) LTAGFIK10/15
74M70
OX
OX
OX
OX
OX
20 amp non-powered, field-wired (575V only) C1GFCI20FF1
67E01
X
X
X
X
X
C1GFCI99FF1
10C89
X
X
X
X
X
High Performance Economizer With Outdoor Air Hood (Sensible Control)
(Approved for California Title 24 Building Standards)
High Performance Economizer - Includes Barometric Relief Dampers
and Exhaust Hood
High Performance Economizer Controls (Not for Title 24)
Economizer Accessories
Horizontal Economizer Conversion Kit
OUTDOOR AIR
Outdoor Air Dampers With Outdoor Air Hood
Power EXhaust FAN
Standard Static
NOTE - Order Barometric Relief Dampers
with Exhaust Hood below if unit is ordered
with factory installed Standard Economizer
with “No Exhaust” option
1
BAROMETRIC RELIEF
Barometric Relief Dampers with Exhaust Hood
ELECTRICAL
Voltage
60 hz
Disconnect (See Electrical Data Tables for selection)
GFI Service
Outlets
Weatherproof Cover for GFI
1
Required when Economizer is factory installed (no exhaust option) with field installed Power Exhaust Fan option.
NOTE - The catalog and model numbers that appear here are for ordering field installed accessories only.
OX - Field Installed or Configure to Order (factory installed)
O - Configure to Order (Factory Installed)
X - Field Installed.
K-Series™ KGA Packaged Gas / Electric 3 to 7.5 Tons/ Page 11
OPTIONS / ACCESSORIES
Unit Model No.
Item
Model Catalog KGA KGA KGA KGA KGA
No.
No.
036 048 060 072 090
Indoor Air Quality
Air Filters
High Efficiency Air Filters
Order 4 per unit
MERV 8 (16 x 20 x 2) - C1FLTR15A-1-
54W20
X
X
X
MERV 13 (16 x 20 x 2) - T1FLTR40A-1-
52W37
X
X
X
MERV 8 (20 x 20 x 2) - C1FLTR15D-1-
54W21
MERV 13 (20 x 20 x 2) - C1FLTR40D-1-
52W39
X
X
Indoor Air Quality (Co2) Sensors
Sensor - Wall-mount, off-white plastic cover with LCD display
C0SNSR50AE1L
77N39
X
X
X
X
X
Sensor - Wall-mount, black plastic case, no display, rated for plenum
mounting
C0SNSR53AE1L
87N54
X
X
X
X
X
CO2 Sensor Duct Mounting Kit - for downflow applications
C0MISC19AE1-
85L43
X
X
X
X
X
Aspiration Box - for duct mounting non-plenum rated CO2 sensor
(77N39)
C0MISC16AE1-
90N43
X
X
X
X
X
E1UVCL10AN1-
50W90
X
X
X
X
X
X
X
X
X
X
X
X
X
X
UVC Germicidal Lamps
1
UVC Light Kit (208/230v-1ph)
CEILING DIFFUSERS
Step-Down - Order one
RTD9-65S
13K60
RTD11-95S
13K61
FD9-65S
13K55
Flush - Order one
X
X
X
X
X
X
FD11-95S
13K56
T1TRAN10AN1
17W53
T1TRAN20N-1
17W54
8 in. height
C1CURB70A-1
11F50
X
X
X
X
2
X
14 in. height
C1CURB71A-1
11F51
X
X
X
X
2
X
18 in. height
C1CURB72A-1
11F52
X
X
X
X
2
X
24 in. height
C1CURB73A-1
11F53
X
X
X
X
2
X
8 in. height
K1CURB70AP1
11S47
X
14 in. height
K1CURB71AP1
11S48
X
18 in. height
K1CURB72AP1
11T01
X
24 in. height
K1CURB73AP1
11T06
X
C1CURB55AT1
43W27
Transitions (Supply and Return) - Order one
ROOF CURBS
Hybrid Roof Curbs, Downflow
Hybrid Roof Curbs, Full Perimeter, Downflow
Adjustable Pitch Curb
14 in. height
X
X
X
X
2
Lamps operate on 110-230V single-phase power supply. Step-down transformer may be ordered separately for 460V and 575V units. Alternately, 110V power supply
may be used to directly power the UVC ballast(s).
2
090 models will fit smaller roof curbs with overhang. See dimension drawing.
1
NOTE - The catalog and model numbers that appear here are for ordering field installed accessories only.
OX - Field Installed or Configure to Order (factory installed)
O - Configure to Order (Factory Installed)
X - Field Installed.
K-Series™ KGA Packaged Gas / Electric 3 to 7.5 Tons / Page 12
X
SPECIFICATIONS - DIRECT DRIVE BLOWER
General Data
Nominal Tonnage
Model No.
Efficiency Type
Blower Type
Cooling
Performance
3 Ton
4 Ton
5 Ton
KGA036S4D
KGA048S4D
KGA060S4D
Standard
Standard
Standard
Multi-Speed Direct Drive Multi-Speed Direct Drive Multi-Speed Direct Drive
Gross Cooling Capacity - Btuh
37,500
50,000
61,800
Net Cooling Capacity - Btuh
36,000
48,000
59,000
1200
1600
1800
75
75
82
1
AHRI Rated Air Flow - cfm
2
3 - 5 TON
Sound Rating Number (SRN)((dBA)
Total Unit Power - kW
3.4
4.4
5.3
SEER (Btuh/Watt)
13.0
13.0
13.0
EER (Btuh/Watt)
10.7
11
11.2
1
1
Refrigerant
Type
Charge Furnished
Gas Heating Options - See page 15
R-410A
R-410A
R-410A
7 lbs. 12 oz.
8 lbs. 12 oz.
12 lbs. 8 oz.
Standard (1 or 2 Stage)
or
Medium (1 or 2 Stage)
Standard (1 or 2 Stage),
Medium (1 or 2 Stage) or
High (1 or 2 Stage)
Compressor Type (one per unit)
Scroll
Scroll
Scroll
Outdoor Coil
Net face area - sq. ft.
15.6
15.6
15.6
Tube diameter - in.
3/8
3/8
3/8
Number of rows
1
1.5
2
Fins per inch
20
20
20
(1) 1/4
(1) 1/4
(1) 1/3
Outdoor
Coil Fan
Motor - (No.) HP
Motor rpm
825
825
1075
Total Motor Input - watts
250
250
370
(1) 24 - 3
(1) 24 - 3
(1) 24 - 3
Total air volume - cfm
3700
3500
4300
Net face area - sq. ft.
7.8
7.8
7.8
Tube diameter - in.
3/8
3/8
3/8
Diameter - (No.) in. / No. of blades
Indoor Coil
Number of rows
3
3
4
Fins per inch
14
14
14
(1) 1 NPT
(1) 1 NPT
Drain Connection (no.) and size - in.
Indoor
Blower
(1) 1 NPT
Expansion device type
Nominal Motor HP
Wheel nominal diameter x width - in.
Filters
Refrigerant Metering Orifice (RFC)
0.5 hp
(1) 10 x 10
Type
0.75 hp
(1) 10 x 10
(1) 11 x 10
Disposable
Number and size - in.
Electrical Characteristics - 60 Hz
0.5 hp
(4) 16 x 20 x 2
208/230V,
460V & 575V
3 phase
208/230V,
460V & 575V
3 phase
208/230V,
460V & 575V
3 phase
NOTE - Net capacity includes evaporator blower motor heat deduction. Gross capacity does not include evaporator blower motor heat deduction.
1
AHRI Certified to AHRI Standard 210/240: 95°F outdoor air temperature and 80°F db/67°F wb entering evaporator air; minimum external duct static pressure.
2
Sound Rating Number (SRN) rated in accordance with test conditions included in ARI Standard 270-95.
K-Series™ KGA Packaged Gas / Electric 3 to 7.5 Tons/ Page 13
SPECIFICATIONS - BELT DRIVE BLOWER
General Data
Nominal Tonnage
Model No.
Efficiency Type
Blower Type
Cooling
Performance
Gross Cooling Capacity - Btuh
Net Cooling Capacity - Btuh
AHRI Rated Air Flow - cfm
3
Sound Rating Number (SRN) (dBA)
Total Unit Power - kW
SEER (Btuh/Watt)
IEER (Btuh/Watt)
EER (Btuh/Watt)
Refrigerant
Type
Charge Furnished
Gas Heating Options - See page 15
Compressor Type (one per unit)
Outdoor Coil
Net face area - sq. ft.
Tube diameter - in.
Number of rows
Fins / inch
Outdoor
Motor - (No.) HP
Coil Fan
Motor rpm
Total Motor Input - watts
Diameter - (No.) in. / No. of blades
Total air volume - cfm
Indoor Coil
Net face area - sq. ft.
Tube diameter - in.
Number of rows
Fins per inch
Drain Connection (no.) and size - in.
Expansion device type
4
Indoor
Nominal Motor HP
Blower
Maximum Usable Motor HP
& Drive
Available Drive Kits
Selection
Nominal Motor HP
Maximum Usable Motor HP
Available Drive Kits
Wheel nominal diameter x width - in.
Type
Number and size - in.
Electrical Characteristics - 60 Hz
Filters
3 - 7.5 TON
3 Ton
4 Ton
5 Ton
6 Ton
KGA036S4B KGA048S4B KGA060S4B KGA072S4B
Standard
Standard
Standard
Standard
Single Speed Single Speed Single Speed Single Speed
Belt Drive
Belt Drive
Belt Drive
Belt Drive
37,500
50,000
61,800
72,500
1
1
1
2
36,000
48,000
59,000
69,000
1200
1600
1800
2450
75
75
82
79
3.4
4.4
5.3
6.1
1
1
1
13.0
13.0
13.0
--2
------12.3
1
1
1
2
10.7
11.0
11.2
11.2
R-410A
R-410A
R-410A
R-410A
7 lbs. 12 oz.
8 lbs. 12 oz.
12 lbs. 8 oz.
7 lbs. 1 oz.
Standard
(1 or 2 Stage)
Standard (1 or 2 Stage),
or
Medium (1 or 2 Stage) or
Medium
High (1 or 2 Stage)
(1 or 2 Stage)
Scroll
Scroll
Scroll
Scroll
15.6
15.6
15.6
17.8
3/8
3/8
3/8
--1
1.5
2
1
20
20
20
23
(1) 1/4
(1) 1/4
(1) 1/3
(1) 1/3
825
825
1075
1075
250
250
370
370
(1) 24 - 3
(1) 24 - 3
(1) 24 - 3
(1) 24 - 3
3700
3500
4300
4700
7.8
7.8
7.8
9.7
3/8
3/8
3/8
3/8
3
3
4
4
14
14
14
14
(1) 1 NPT
(1) 1 NPT
(1) 1 NPT
(1) 1 NPT
Refrigerant Metering Orifice (RFC)
1 hp, 2 hp
1 hp, 2 hp
1 hp, 2 hp
1 hp, 2 hp
1.15 hp, 2.3 hp 1.15 hp, 2.3 hp 1.15 hp, 2.3 hp 1.15 hp, 2.3 hp
A01
A02
A03
A04
673 - 1010 rpm 745 - 1117 rpm 833 - 1250 rpm 968 - 1340 rpm
A05
A06
A07
A08
897 - 1346 rpm 1071 - 1429 rpm 1212 - 1548 rpm 1193 - 1591 rpm
-------------------------
-----
-----
-----
---
---
---
(1) 10 x 10
(1) 10 x 10
(1) 10 x 10
Disposable
(4) 16 x 20 x 2
208/230V,
208/230V,
208/230V,
460V & 575V 460V & 575V 460V & 575V
3 phase
3 phase
3 phase
7.5 Ton
KGA090S4B
Standard
Single Speed
Belt Drive
92,000
2
90,000
2430
79
8.2
--2
11.2
2
11.0
R-410A
8 lbs. 8 oz.
Medium
(1 or 2 Stage)
or High
(1 or 2 Stage)
Scroll
24.2
--1
23
(1) 1/2
1075
520
(1) 24 - 4
5300
9.7
3/8
4
14
(1) 1 NPT
1 hp
1.15 hp
AA01
522 - 784 rpm
2 hp
2.3 hp
AA02
632 - 875 rpm
AA03
798 - 1105 rpm
--3 hp
--3.45 hp
AA04
--921 - 1228 rpm
(1) 10 x 10
(1) 15 x 9
Disposable
(4) 20 x 20 x 2
208/230V,
208/230V,
460V & 575V 460V & 575V
3 phase
3 phase
NOTE - Net capacity includes evaporator blower motor heat deduction. Gross capacity does not include evaporator blower motor heat deduction.
1, 2
AHRI Certified to AHRI Standard 1 210/240 or 2 340/360: 95°F outdoor air temperature and 80°F db/67°F wb entering evaporator air; minimum external duct static
pressure.
3
Sound Rating Number (SRN) rated in accordance with test conditions included in ARI Standard 270-95.
4
Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor hp required. Maximum usable hp of motors
furnished are shown. In Canada, nominal motor hp is also maximum usable motor hp output. If motors of comparable hp are used, be sure to keep within the service
factor limitations outlined on the motor nameplate.
K-Series™ KGA Packaged Gas / Electric 3 to 7.5 Tons / Page 14
SPECIFICATIONS - STANDARD GAS HEAT
Model No.
Heat Input Type
Input
Btuh
Output
Btuh
Temperature
Rise Range - °F
1st Stage
2nd Stage
1st Stage
2nd Stage
1st stage
2nd Stage
Standard
Thermal
Efficiency
Gas Supply Connections
Rec. Gas Supply Pressure Nat./ LPG
1
1
036,
048,
060,
072
Standard
(1 Stage)
036,
036,
090
036,
090
048,
048,
048,
060,
060,
060,
072
072
072
Standard
Medium
Medium
(2 Stage)
(1 Stage)
(2 Stage)
Low NOx Only
65,000
53,000
108,000
81,000
--70,000
--108,000
52,000
43,000
86,000
65,000
--57,000
--86,000
15 - 45 5-35 5-35
5-35 30 - 70 15 - 45 25 - 55 10 - 40
--15-45 10-40
----30 - 70 15 - 45
80%
81%
81%
80%
80%
80%
80%
048,
060,
072
090
High
(1 Stage)
048,
060,
072
090
High
(2 Stage)
150,000
113,000
--150,000
120,000
90,000
--120,000
45 - 75 25 - 55 30 - 60 15 - 45
----45 - 75 25 - 55
80%
80%
80%
80%
1/2 in. NPT
7 in.w.g. / 11 in.w.g.
Thermal Efficiency at full input.
HIGH ALTITUDE DERATE
Heat Input Type
NOTE - Units may be installed at altitudes
up to 2000 ft. above sea level without any
modifications. At altitudes above 2000 ft.
Standard (1 stage)
units must be derated to match information
in the table shown. At altitudes above 4500 Standard (2 stage)
ft. unit must be derated 2% for each 1000 ft. Medium (1 stage)
above sea level.
Medium (2 stage)
NOTE - This is the only permissible derate
for these units.
High (1 stage)
High (2 stage)
Altitude Feet
Gas Manifold Pressure
in. w.g.
Input Rate (Btuh)
Natural Gas LPG/ Propane
2001 - 4500
3.0
9.0
60,000
2001 - 4500
3.0/1.7
9.0/5.1
65,000 / 49,000
2001 - 4500
3.0
9.0
100,000
2001 - 4500
3.0/1.7
9.0/5.1
100,000 / 75,000
2001 - 4500
3.0
9.0
139,000
2001 - 4500
3.0/1.7
9.0/5.1
139,000 / 104,000
K-Series™ KGA Packaged Gas / Electric 3 to 7.5 Tons/ Page 15
RATINGS
NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.
3 TON - KGA036S4
Outdoor Air Temperature Entering Outdoor Coil
Entering
85°F
95°F
105°F
115°F
Total
Wet
Air
Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total
Bulb
Volume Cool Motor
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Cool Motor
Cool Motor
Cool Motor
TemperCap. Input
Cap. Input
Cap. Input
Cap. Input
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
ature
cfm
kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F
960
35.6
2.35 0.75 0.87 0.98 33.4
2.67
0.75 0.89
1
31.1
3.04 0.77 0.91
1
28.5
3.48
0.79 0.93
1
63°F
1200
37.7
2.36
0.8 0.93
1
35.3
2.68
0.81 0.95
1
32.9
3.06 0.82 0.98
1
30.2
3.49
0.84
1
1
1440
39.3
2.37 0.84 0.98
1
36.8
2.69
0.85
1
1
34.5
3.07 0.87
1
1
32
3.5
0.9
1
1
960
37.6
2.36 0.59 0.72 0.84 35.4
2.68
0.59 0.73 0.86 33.1
3.05 0.59 0.74 0.88 30.4
3.5
0.59 0.76
0.9
67°F
1200
39.8
2.38 0.62 0.78 0.91 37.5
2.7
0.62 0.79 0.92 34.9
3.07 0.63 0.8 0.94 32.1
3.5
0.64 0.82 0.97
1440
41.4
2.39 0.65 0.82 0.96 38.9
2.71
0.66 0.84 0.98 36.2
3.08 0.66 0.86
1
33.3
3.51
0.68 0.88
1
960
39.9
2.38 0.45 0.58 0.7
37.5
2.7
0.44 0.58 0.71 34.9
3.07 0.42 0.58 0.72 32.2
3.5
0.43 0.58 0.74
71°F
1200
42
2.39 0.45 0.61 0.75 39.5
2.71
0.46 0.61 0.77 36.9
3.09 0.45 0.62 0.79
34
3.52
0.45 0.63 0.81
1440
43.6
2.41 0.47 0.65 0.8
41
2.73
0.46 0.65 0.82 38.2
3.1
0.47 0.66 0.83 35.2
3.53
0.47 0.68 0.87
4 TON - KGA048S4
Outdoor Air Temperature Entering Outdoor Coil
Entering
85°F
95°F
105°F
115°F
Total
Wet
Air
Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total
Bulb
Volume Cool Motor
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Cool Motor
Cool Motor
Cool Motor
TemperCap. Input
Cap. Input
Cap. Input
Cap. Input
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
ature
cfm
kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F
1280
47.6
3.02 0.74 0.87 0.98 44.5
3.44
0.74 0.88
1
41.2
3.89 0.75 0.9
1
37.8
4.41
0.77 0.93
1
63°F
1600
50.4
3.04 0.79 0.93
1
47.1
3.46
0.8
0.95
1
43.7
3.91 0.81 0.97
1
40
4.42
0.83
1
1
1920
52.6
3.05 0.83 0.99
1
49.1
3.47
0.85
1
1
45.7
3.93 0.87
1
1
42.3
4.45
0.89
1
1
1280
50.6
3.04 0.58 0.72 0.84 47.2
3.45
0.58 0.72 0.85 43.9
3.91 0.57 0.73 0.87 40.3
4.44
0.57 0.74
0.9
67°F
1600
53.5
3.06 0.61 0.77 0.9
50
3.48
0.61 0.78 0.92 46.4
3.94 0.62 0.8 0.95 42.5
4.45
0.62 0.81 0.98
1920
55.6
3.07 0.64 0.82 0.96 51.9
3.5
0.65 0.83 0.98 47.9
3.95 0.66 0.85
1
44
4.47
0.67 0.88
1
1280
53.7
3.06 0.43 0.57 0.69 50.2
3.48
0.43 0.57
0.7
46.6
3.93 0.42 0.57 0.71 42.8
4.46
0.41 0.57 0.72
71°F
1600
56.4
3.07 0.45 0.6 0.75 52.6
3.5
0.45
0.6
0.76
49
3.96 0.44 0.61 0.78
45
4.48
0.43 0.62
0.8
1920
58.6
3.08 0.47 0.64 0.8
54.8
3.52
0.47 0.64 0.81 50.8
3.98 0.46 0.65 0.83 46.7
4.5
0.45 0.66 0.86
5 TON - KGA060S4
Outdoor Air Temperature Entering Outdoor Coil
Entering
85°F
95°F
105°F
115°F
Total
Wet
Air
Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total
Bulb
Volume Cool Motor
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Cool Motor
Cool Motor
Cool Motor
TemperCap. Input
Cap. Input
Cap. Input
Cap. Input
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
ature
cfm
kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F
1600
60.1
3.48 0.68 0.84
1
57
3.93
0.69 0.86
1
53.5
4.44 0.71 0.89
1
50
5.04
0.73 0.93
1
63°F
2000
63.1
3.51 0.74 0.94
1
59.8
3.96
0.76 0.97
1
56
4.47 0.78
1
1
52.6
5.06
0.81
1
1
2400
65.6
3.54
0.8
1
1
62.3
3.99
0.83
1
1
59.1
4.51 0.86
1
1
55.6
5.1
0.91
1
1
1600
63.9
3.52 0.54 0.66 0.79 60.5
3.97
0.54 0.67 0.82 57.1
4.48 0.55 0.69 0.85 53.2
5.07
0.56 0.71 0.89
67°F
2000
66.8
3.55 0.57 0.72 0.9
63.1
4
0.58 0.73 0.93 59.2
4.51 0.58 0.75 0.97 55.1
5.1
0.59 0.79
1
2400
68.9
3.58
0.6 0.78 0.99
65
4.02
0.61
0.8
1
61.1
4.54 0.63 0.84
1
56.8
5.12
0.64 0.88
1
1600
67.7
3.56
0.4 0.52 0.64 64.2
4.01
0.41 0.53 0.65 60.4
4.53
0.4 0.54 0.67 56.4
5.12
0.4
0.54 0.69
71°F
2000
70.7
3.6
0.42 0.56 0.7
67
4.05
0.42 0.57 0.71 62.8
4.56 0.42 0.57 0.73 58.5
5.15
0.42 0.59 0.76
2400
72.7
3.62 0.43 0.59 0.75 68.7
4.07
0.43
0.6
0.78 64.6
4.58 0.44 0.62 0.81
60
5.17
0.44 0.64 0.85
6 TON - KGA072S4
Outdoor Air Temperature Entering Outdoor Coil
Entering
85°F
95°F
105°F
115°F
Total
Wet
Air
Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total
Bulb
Volume Cool Motor
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Cool Motor
Cool Motor
Cool Motor
TemperCap. Input
Cap. Input
Cap. Input
Cap. Input
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
ature
cfm
kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F
1920
69.7
4.27 0.74 0.89
1
64.1
4.8
0.75 0.92
1
58.7
5.43 0.77 0.95
1
53
6.14
0.79 0.99
1
63°F
2400
73.5
4.32
0.8 0.98
1
67.7
4.84
0.82
1
1
62.6
5.47 0.85
1
1
57.5
6.2
0.88
1
1
2880
77.2
4.37 0.86
1
1
71.8
4.9
0.89
1
1
66.4
5.52 0.92
1
1
60.8
6.24
0.97
1
1
1920
74.6
4.33 0.56 0.71 0.86 68.8
4.85
0.57 0.73 0.88 63.1
5.48 0.58 0.75 0.92 57.3
6.2
0.58 0.77 0.95
67°F
2400
78.3
4.39 0.61 0.78 0.95 72.2
4.9
0.62
0.8
0.98
66
5.51 0.62 0.82
1
60
6.23
0.64 0.86
1
2880
80.9
4.42 0.64 0.84
1
74.6
4.93
0.66 0.87
1
68
5.54 0.67 0.9
1
62
6.26
0.69 0.95
1
1920
79.5
4.4
0.42 0.55 0.69 73.6
4.91
0.42 0.56 0.71 67.5
5.53
0.4 0.57 0.73 61.4
6.25
0.4
0.57 0.75
71°F
2400
83.3
4.45 0.45 0.6 0.76 76.9
4.96
0.44 0.61 0.78 70.5
5.57 0.43 0.62 0.8
64.3
6.29
0.41 0.63 0.84
2880
85.8
4.5
0.46 0.64 0.82 79.4
5.01
0.45 0.66 0.86 72.5
5.6
0.45 0.67 0.88 66.1
6.32
0.45 0.68 0.93
K-Series™ KGA Packaged Gas / Electric 3 to 7.5 Tons / Page 16
RATINGS
NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.
7.5 TON - KGA090S4
Entering
Total
Wet
Air
Bulb
Volume
Temperature
cfm
2400
63°F
3000
3600
2400
67°F
3000
3600
2400
71°F
3000
3600
Total
Cool
Cap.
kBtuh
92.4
97.7
101.9
99.4
104.5
108.5
106.2
111.7
115.6
Outdoor Air Temperature Entering Outdoor Coil
85°F
95°F
105°F
115°F
Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total Total Comp. Sensible To Total
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Ratio (S/T)
Motor
Cool Motor
Cool Motor
Cool Motor
Input
Cap. Input
Cap. Input
Cap. Input
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F kBtuh
kW
75°F 80°F 85°F
5.97 0.69 0.84 0.98 85.3
6.6
0.7
0.86
1
77.8
7.32
0.7 0.88
1
69.9
8.15
0.71 0.91
1
6.04 0.75 0.92
1
90.2
6.68
0.76 0.95
1
82.5
7.4
0.78 0.98
1
74.5
8.23
0.81
1
1
6.11 0.81
1
1
94.6
6.75
0.83
1
1
87.2
7.48 0.85
1
1
79.5
8.33
0.89
1
1
6.07 0.54 0.67 0.81 91.8
6.7
0.53 0.68 0.83 84.2
7.43 0.53 0.68 0.85 75.9
8.26
0.52
0.7
0.88
6.15 0.57 0.73 0.89 96.8
6.78
0.58 0.74 0.91 88.7
7.51 0.57 0.76 0.95 79.9
8.34
0.58 0.79 0.99
6.21 0.61 0.79 0.97 100.2 6.84
0.62 0.81 0.99
92
7.57 0.62 0.84
1
82.7
8.39
0.62 0.87
1
6.17
0.4 0.53 0.65 98.5
6.81
0.38 0.52 0.66 90.6
7.54 0.37 0.52 0.67 82.2
8.38
0.36 0.52 0.68
6.26 0.41 0.57 0.71 103.8
6.9
0.4
0.57 0.72 95.1
7.63
0.4 0.57 0.74 86.3
8.46
0.38 0.58 0.77
6.33 0.44 0.6 0.77 107.2 6.96
0.43 0.61 0.79 98.6
7.69 0.42 0.62 0.82
89
8.51
0.41 0.63 0.85
K-Series™ KGA Packaged Gas / Electric 3 to 7.5 Tons/ Page 17
BLOWER DATA - DIRECT DRIVE - KGA036, KGA048
BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE.
FOR ALL UNITS ADD:
1 - Any factory installed options air resistance (larger gas heat section, economizer, wet coil, etc.) See page 27.
2 - Any field installed accessories air resistance (duct resistance, diffuser, etc.) See page 27.
External Static
Pressure (in. w.g.)
Air Volume (cfm) at Various Blower Speeds
208 VOLTS
High
Medium
230 VOLTS
460/575 VOLTS
Low
High
Medium
Low
High
3 and 4 Ton Standard Efficiency (Downflow)
Medium
Low
KGA036S and KGA048S
0.0
1873
1561
1123
2094
1783
1321
2064
1727
1216
0.1
1993
1601
1148
2168
1797
1338
2105
1744
1229
0.2
1913
1601
1137
2098
1803
1308
2050
1694
1198
0.3
1858
1527
1078
2036
1725
1261
1987
1638
1167
0.4
1801
1496
1046
1973
1679
1219
1905
1598
1148
0.5
1763
1467
987
1910
1647
1177
1862
1559
1108
0.6
1709
1414
897
1830
1560
1080
1781
1509
1057
0.7
1617
1368
806
1727
1519
986
1698
1449
982
0.8
1472
1269
730
1604
1419
918
1614
1389
920
0.9
1359
1162
487
1478
1363
706
1488
1346
792
1.0
961
922
370
1093
1083
590
1167
1099
703
3 and 4 Ton Standard Efficiency (Horizontal)
KGA036S and KGA048S
0.0
1799
1530
1073
2012
1747
1263
2015
1756
1251
0.1
1868
1544
1088
2032
1733
1268
2071
1760
1279
0.2
1802
1494
1068
1976
1682
1228
2014
1700
1226
0.3
1735
1432
1014
1900
1618
1185
1937
1634
1187
0.4
1666
1397
980
1825
1568
1142
1878
1597
1174
0.5
1615
1350
904
1750
1516
1078
1801
1558
1124
0.6
1564
1305
842
1675
1440
1014
1743
1479
1060
0.7
1462
1228
758
1562
1364
928
1664
1415
982
0.8
1330
1151
670
1449
1287
842
1512
1335
865
0.9
1194
1011
464
1298
1185
671
1393
1297
733
1.0
878
878
355
998
1032
565
1060
1063
618
K-Series™ KGA Packaged Gas / Electric 3 to 7.5 Tons / Page 18
BLOWER DATA - DIRECT DRIVE - KGA060
BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE.
FOR ALL UNITS ADD:
1 - Any factory installed options air resistance (larger gas heat section, economizer, wet coil, etc.) See page 27.
2 - Any field installed accessories air resistance (duct resistance, diffuser, etc.) See page 27.
External Static
Pressure (in. w.g.)
Air Volume (cfm) at Various Blower Speeds
208 VOLTS
High
230 VOLTS
460/575 VOLTS
Low
High
Low
High
Low
5 Ton Standard Efficiency (Downflow)
KGA060S
0.0
2200
1649
2411
1957
2241
1755
0.1
2256
1669
2417
2002
2221
1742
0.2
2202
1739
2396
1985
2193
1747
0.3
2170
1705
2328
1972
2144
1725
0.4
2158
1689
2293
1959
2104
1695
0.5
2130
1676
2279
1930
2086
1678
0.6
2056
1662
2158
1900
2008
1652
0.7
2032
1657
2089
1857
1975
1610
0.8
1963
1591
2077
1796
1941
1586
0.9
1887
1597
1876
1746
1855
1555
1.0
1695
1400
1746
1601
1778
1486
5 Ton Standard Efficiency (Horizontal)
0.0
KGA060S
2114
1615
2305
1880
2308
1890
0.1
2115
1610
2290
1876
2334
1906
0.2
2074
1622
2249
1870
2292
1890
0.3
2025
1599
2188
1841
2230
1859
0.4
1996
1577
2148
1812
2210
1846
0.5
1952
1542
2087
1768
2148
1817
0.6
1882
1534
2026
1739
2108
1786
0.7
1838
1488
1966
1680
2094
1743
0.8
1773
1443
1905
1622
1988
1682
0.9
1657
1389
1784
1534
1915
1679
1.0
1548
1335
1672
1462
1853
1506
K-Series™ KGA Packaged Gas / Electric 3 to 7.5 Tons/ Page 19
BLOWER DATA - BELT DRIVE - KGA036
BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE.
FOR ALL UNITS ADD:
1 - Any factory installed options air resistance (heat section, economizer, wet coil, etc.).
2 - Any field installed accessories air resistance (duct resistance, diffuser, etc.).
See page 27 for blower motors and drives and wet coil and options/accessory air resistance data.
DOWNFLOW
External Static - in. w.g.
Air
Volume
cfm
RPM
900
493
0.11
564
0.15
637
0.19
711
0.22
783
0.24
851
1000
517
0.14
588
0.18
660
0.22
733
0.24
804
0.26
1100
544
0.17
614
0.21
685
0.25
757
0.27
826
0.29
1200
574
0.2
643
0.24
712
0.28
782
0.31
849
1300
613
0.23
679
0.28
745
0.31
811
0.34
873
1400
662
0.26
722
0.30
781
0.34
841
0.37
1500
710
0.29
763
0.33
816
0.38
869
0.41
0.10
0.20
BHP
RPM
BHP
0.30
RPM
BHP
0.40
RPM
BHP
0.50
RPM
BHP
0.60
0.70
BHP
0.80
RPM
BHP
RPM
BHP
0.26
910
0.29
961
0.32
868
0.29
924
0.32
974
0.35
887
0.32
940
0.36
987
0.38
0.33
906
0.36
956
0.39
1001
0.42
0.36
926
0.40
973
0.43
1016
0.46
897
0.41
944
0.44
989
0.48
1032
0.51
919
0.45
963
0.49
1006
0.53
1049
0.56
Field Furnished
RPM
Kit A01
External Static - in. w.g.
Air
Volume
cfm
RPM
900
1008
0.34
1056
0.36
1000
1020
0.37
1067
1100
1032
0.41
1078
1200
1045
0.45
1300
1060
0.49
1400
1075
1500
1093
0.90
BHP
1.00
RPM
BHP
1.10
RPM
BHP
1.20
RPM
BHP
Kit A01
1.30
RPM
BHP
1.40
1.50
1.60
RPM
BHP
RPM
BHP
RPM
BHP
Kit A05
1104
0.39
1149
0.41
1190
0.44
1229
0.46
1267
0.49
1305
0.52
0.40
1115
0.42
1159
0.45
1200
0.48
1239
0.51
1277
0.54
1314
0.57
0.43
1124
0.46
1168
0.49
1210
0.52
1249
0.55
1286
0.58
1323
0.62
1090
0.47
1135
0.50
1178
0.53
1220
0.57
1259
0.60
1296
0.64
1332
0.67
1104
0.51
1148
0.55
1190
0.58
1230
0.62
1269
0.65
1306
0.69
1342
0.72
0.53
1119
0.56
1162
0.60
1203
0.63
1242
0.67
1280
0.71
1317
0.75
1352
0.78
0.58
1136
0.61
1177
0.65
1217
0.69
1255
0.73
1292
0.77
1328
0.80
1364
0.84
HORIZONTAL
External Static - in. w.g.
Air
Volume
cfm
RPM
0.10
BHP
0.20
RPM
BHP
0.30
RPM
BHP
0.40
RPM
BHP
0.50
RPM
BHP
0.60
RPM
0.70
BHP
Field Furnished
RPM
0.80
BHP
RPM
BHP
Kit A01
900
465
0.09
531
0.14
600
0.17
670
0.20
740
0.22
808
0.24
869
0.27
925
0.30
1000
483
0.12
549
0.16
617
0.20
687
0.22
756
0.24
822
0.26
881
0.29
935
0.33
1100
504
0.14
570
0.19
637
0.22
706
0.25
773
0.27
837
0.29
894
0.32
946
0.36
1200
527
0.17
592
0.22
658
0.25
726
0.28
792
0.30
854
0.32
908
0.36
957
0.39
1300
552
0.20
617
0.25
682
0.29
748
0.31
812
0.33
871
0.36
923
0.40
970
0.43
1400
580
0.24
644
0.28
708
0.32
773
0.35
834
0.37
890
0.40
938
0.44
984
0.48
1500
611
0.28
674
0.32
736
0.35
799
0.38
857
0.41
908
0.44
954
0.49
998
0.52
External Static - in. w.g.
Air
Volume
cfm
RPM
0.90
BHP
1.00
RPM
BHP
1.10
RPM
BHP
1.20
RPM
BHP
Kit A01
1.30
RPM
BHP
1.40
1.50
1.60
RPM
BHP
RPM
BHP
RPM
BHP
Kit A05
900
977
0.33
1028
0.36
1079
0.39
1127
0.42
1169
0.45
1208
0.48
1246
0.51
1282
0.54
1000
985
0.36
1036
0.39
1087
0.42
1135
0.45
1177
0.48
1216
0.52
1253
0.55
1290
0.58
1100
995
0.39
1044
0.42
1093
0.45
1140
0.49
1183
0.52
1223
0.56
1261
0.59
1297
0.62
1200
1005
0.43
1053
0.46
1100
0.49
1146
0.53
1190
0.56
1230
0.60
1268
0.63
1304
0.67
1300
1016
0.47
1063
0.50
1109
0.53
1154
0.57
1197
0.61
1237
0.64
1275
0.68
1311
0.72
1400
1029
0.51
1074
0.54
1120
0.58
1164
0.61
1205
0.65
1245
0.69
1282
0.73
1318
0.77
1500
1042
0.56
1087
0.59
1132
0.62
1174
0.66
1215
0.71
1253
0.75
1290
0.78
1326
0.82
K-Series™ KGA Packaged Gas / Electric 3 to 7.5 Tons / Page 20
BLOWER DATA - BELT DRIVE - KGA048
BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE.
FOR ALL UNITS ADD:
1 - Any factory installed options air resistance (heat section, economizer, wet coil, etc.).
2 - Any field installed accessories air resistance (duct resistance, diffuser, etc.).
See page 27 for blower motors and drives and wet coil and options/accessory air resistance data.
DOWNFLOW
Air
Volume
cfm
1200
1300
1400
1500
1600
1700
1800
1900
2000
0.10
RPM BHP
574
608
645
684
723
761
798
834
869
0.20
0.24
0.28
0.31
0.35
0.40
0.45
0.51
0.57
0.20
0.30
RPM BHP RPM BHP
Field Furnished
644
0.24
713
0.28
677
0.28
744
0.31
712
0.31
778
0.35
749
0.35
811
0.38
785
0.39
844
0.43
819
0.44
875
0.48
853
0.49
905
0.54
885
0.55
934
0.60
917
0.62
962
0.67
Air
Volume
cfm
0.90
1.00
RPM BHP RPM BHP
Kit A02
1200
1043 0.44 1090 0.47
1300
1058 0.49 1104 0.51
1400
1074 0.53 1119 0.56
1500
1092 0.58 1136 0.61
1600
1112 0.63 1154 0.67
1700
1132 0.69 1173 0.73
1800
1154 0.76 1194 0.80
1900
1178 0.83 1215 0.88
2000
1201 0.91 1237 0.97
HORIZONTAL
Air
Volume
cfm
1200
1300
1400
1500
1600
1700
1800
1900
2000
Air
Volume
cfm
1200
1300
1400
1500
1600
1700
1800
1900
2000
0.10
RPM BHP
540
568
599
632
667
702
737
771
805
0.18
0.21
0.25
0.29
0.33
0.36
0.41
0.46
0.51
0.90
RPM BHP
1010
1024
1038
1054
1071
1089
1108
1128
1148
0.43
0.47
0.52
0.57
0.62
0.67
0.73
0.79
0.86
1.10
RPM BHP
1135
1148
1162
1177
1193
1211
1230
1250
1271
0.50
0.55
0.59
0.65
0.71
0.77
0.85
0.93
1.02
0.20
0.30
RPM BHP RPM BHP
Field Furnished
606
0.22
673
0.26
634
0.26
699
0.29
664
0.29
728
0.33
696
0.33
758
0.36
729
0.36
789
0.40
761
0.40
819
0.44
794
0.45
848
0.49
825
0.50
877
0.54
857
0.56
905
0.61
1.00
RPM BHP
Kit A02
1061 0.46
1073 0.50
1086 0.55
1100 0.60
1116 0.65
1132 0.71
1149 0.77
1167 0.84
1186 0.91
External Static - in. w.g.
0.40
0.50
RPM BHP RPM BHP
784
0.31
850
0.33
813
0.34
874
0.37
842
0.38
898
0.41
871
0.42
921
0.45
898
0.46
943
0.50
924
0.52
965
0.56
950
0.58
990
0.62
977
0.64 1015 0.68
1004 0.71 1042 0.75
External Static - in. w.g.
1.20
1.30
1.40
RPM BHP RPM BHP RPM BHP
Kit A06
1179 0.53 1220 0.57 1259 0.60
1190 0.58 1231 0.62 1269 0.65
1203 0.63 1242 0.67 1280 0.71
1217 0.69 1255 0.73 1292 0.76
1232 0.75 1269 0.79 1306 0.83
1248 0.81 1285 0.86 1321 0.90
1266 0.89 1302 0.93 1338 0.98
1286 0.98 1321 1.02 1356 1.06
1307 1.07 1342 1.11 1376 1.15
External Static - in. w.g.
0.40
0.50
RPM BHP RPM BHP
1.10
RPM BHP
748
0.29
816
0.30
771
0.32
835
0.34
795
0.35
855
0.38
821
0.39
877
0.42
848
0.43
898
0.46
873
0.48
920
0.52
898
0.53
941
0.58
923
0.59
964
0.64
948
0.66
987
0.71
External Static - in. w.g.
1.20
1.30
RPM BHP RPM BHP
1110
1120
1131
1144
1158
1172
1188
1204
1221
1156
1165
1175
1186
1198
1211
1225
1241
1257
0.50
0.54
0.59
0.64
0.69
0.75
0.81
0.88
0.96
0.60
RPM BHP
Kit A02
906
0.36
925
0.40
944
0.44
963
0.49
983
0.54
1004 0.60
1028 0.66
1054 0.72
1081 0.78
0.53
0.58
0.62
0.68
0.73
0.79
0.85
0.92
1.00
1199
1207
1216
1226
1237
1249
1262
1276
1292
0.57
0.62
0.66
0.72
0.77
0.83
0.90
0.97
1.05
0.60
RPM BHP
Kit A02
870
0.33
886
0.37
903
0.41
922
0.46
941
0.51
960
0.56
981
0.62
1002 0.68
1025 0.75
1.40
RPM BHP
Kit A06
1239 0.61
1246 0.65
1255 0.70
1264 0.75
1274 0.81
1285 0.87
1298 0.94
1311 1.01
1326 1.09
0.70
RPM BHP
0.80
RPM BHP
953
969
986
1004
1024
1045
1069
1095
1121
998
1014
1030
1048
1067
1089
1112
1137
1162
0.39
0.43
0.48
0.53
0.58
0.63
0.69
0.75
0.82
0.42
0.46
0.51
0.56
0.61
0.66
0.72
0.79
0.86
1.50
RPM BHP
1.60
RPM BHP
1297
1306
1317
1328
1341
1356
1373
1391
1411
1333
1342
1352
1364
1377
1391
1408
1426
1446
0.64
0.69
0.74
0.80
0.87
0.94
1.02
1.10
1.19
0.67
0.72
0.78
0.84
0.91
0.98
1.06
1.14
1.23
0.70
RPM BHP
0.80
RPM BHP
914
929
946
963
982
1001
1021
1043
1065
961
975
991
1008
1026
1044
1064
1085
1107
0.37
0.41
0.45
0.50
0.55
0.61
0.66
0.72
0.79
0.40
0.44
0.49
0.54
0.59
0.64
0.70
0.76
0.82
1.50
RPM BHP
1.60
RPM BHP
1276
1284
1292
1301
1310
1321
1332
1345
1359
1312
1320
1328
1336
1345
1355
1366
1379
1393
0.64
0.69
0.74
0.79
0.85
0.91
0.98
1.05
1.13
0.68
0.73
0.78
0.83
0.89
0.95
1.01
1.09
1.17
K-Series™ KGA Packaged Gas / Electric 3 to 7.5 Tons/ Page 21
BLOWER DATA - BELT DRIVE - KGA060
BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE.
FOR ALL UNITS ADD:
1 - Any factory installed options air resistance (heat section, economizer, wet coil, etc.).
2 - Any field installed accessories air resistance (duct resistance, diffuser, etc.).
See page 27 for blower motors and drives and wet coil and options/accessory air resistance data.
DOWNFLOW
Air
Volume
cfm
1600
1700
1800
1900
2000
2100
2200
2300
2400
Air
Volume
cfm
0.10
0.20
RPM BHP RPM BHP
Field Furnished
745
0.36
805
0.40
783
0.41
840
0.45
820
0.47
873
0.51
856
0.52
906
0.57
891
0.59
937
0.64
924
0.66
968
0.71
956
0.74
999
0.78
990
0.81 1032 0.86
1025 0.90 1066 0.95
0.90
RPM BHP
1600
1125
1700
1147
1800
1170
1900
1194
2000
1218
2100
1243
2200
1268
2300
1295
2400
1324
HORIZONTAL
Air
Volume
cfm
1600
1700
1800
1900
2000
2100
2200
2300
2400
Air
Volume
cfm
1600
1700
1800
1900
2000
2100
2200
2300
2400
0.64
0.70
0.77
0.85
0.94
1.03
1.14
1.25
1.36
0.10
RPM BHP
690
725
761
795
830
863
895
926
957
0.33
0.38
0.42
0.48
0.53
0.60
0.67
0.75
0.84
862
893
923
953
982
1011
1041
1072
1105
0.44
0.49
0.55
0.62
0.69
0.75
0.83
0.91
1.00
1.00
1.10
RPM BHP RPM BHP
Kit A03
1167 0.68 1206 0.72
1187 0.75 1224 0.79
1208 0.82 1244 0.87
1230 0.90 1265 0.95
1253 1.00 1287 1.05
1277 1.09 1311 1.15
1302 1.20 1336 1.25
1328 1.30 1362 1.35
1356 1.41 1390 1.46
0.20
0.30
RPM BHP RPM BHP
Field Furnished
751
0.37
810
0.40
784
0.41
839
0.45
816
0.46
868
0.50
848
0.52
897
0.56
879
0.58
926
0.63
910
0.65
954
0.70
939
0.73
982
0.78
969
0.81 1009 0.86
998
0.89 1038 0.94
0.90
RPM BHP
1.00
RPM BHP
1086
1104
1124
1145
1167
1188
1210
1232
1254
1129
1147
1165
1183
1203
1222
1243
1263
1284
0.63
0.68
0.74
0.81
0.88
0.96
1.05
1.16
1.26
0.30
RPM BHP
0.66
0.72
0.79
0.85
0.93
1.02
1.11
1.22
1.32
1.10
RPM BHP
Kit A03
1171 0.70
1186 0.76
1202 0.83
1220 0.90
1237 0.98
1256 1.07
1275 1.17
1295 1.27
1317 1.37
External Static - in. w.g.
0.40
0.50
0.60
0.70
RPM BHP RPM BHP RPM BHP RPM BHP
Kit A03
913
0.48
956
0.52
996
0.55 1037 0.59
940
0.53
980
0.57 1019 0.61 1061 0.64
967
0.60 1006 0.63 1045 0.67 1086 0.70
994
0.66 1032 0.70 1071 0.73 1112 0.76
1022 0.73 1060 0.76 1099 0.80 1140 0.84
1051 0.79 1089 0.83 1128 0.87 1167 0.92
1080 0.87 1119 0.91 1157 0.96 1196 1.02
1111 0.95 1149 1.00 1187 1.06 1225 1.13
1143 1.05 1181 1.11 1218 1.17 1255 1.24
External Static - in. w.g.
1.20
1.30
1.40
1.50
RPM BHP RPM BHP RPM BHP RPM BHP
Kit A07
1244 0.76 1281 0.80 1317 0.84 1353 0.88
1261 0.83 1298 0.87 1333 0.91 1369 0.95
1280 0.91 1316 0.95 1351 0.99 1386 1.03
1301 1.00 1336 1.04 1371 1.08 1406 1.12
1323 1.09 1358 1.14 1392 1.17 1427 1.21
1346 1.19 1381 1.23 1415 1.27 1450 1.31
1371 1.29 1405 1.33 1439 1.37 1474 1.40
1397 1.39 1431 1.43 1465 1.47 1500 1.50
1424 1.50 1458 1.53 1492 1.57 1527 1.61
External Static - in. w.g.
0.40
0.50
RPM BHP RPM BHP
865
0.44
912
0.48
891
0.49
935
0.53
916
0.55
957
0.59
942
0.61
981
0.66
968
0.68 1006 0.73
994
0.75 1032 0.80
1021 0.83 1058 0.87
1048 0.90 1085 0.94
1076 0.98 1112 1.03
External Static - in. w.g.
1.20
1.30
RPM BHP RPM BHP
1211
1225
1240
1256
1273
1291
1309
1329
1350
K-Series™ KGA Packaged Gas / Electric 3 to 7.5 Tons / Page 22
0.74
0.80
0.87
0.94
1.03
1.12
1.21
1.31
1.41
1249
1262
1276
1291
1307
1324
1343
1362
1383
0.78
0.84
0.91
0.99
1.07
1.16
1.25
1.35
1.45
0.60
RPM BHP
Kit A03
955
0.52
975
0.58
997
0.64
1020 0.70
1044 0.77
1070 0.83
1096 0.91
1122 0.99
1149 1.08
1.40
RPM BHP
1286
1298
1311
1326
1341
1358
1376
1395
1415
0.82
0.88
0.95
1.03
1.11
1.20
1.29
1.39
1.48
0.80
RPM BHP
1081
1104
1129
1154
1180
1206
1233
1261
1290
0.62
0.67
0.73
0.80
0.88
0.97
1.08
1.19
1.30
1.60
RPM BHP
1388
1404
1422
1441
1463
1486
1511
1537
1563
0.92
0.99
1.07
1.16
1.25
1.34
1.44
1.54
1.64
0.70
RPM BHP
0.80
RPM BHP
997
1017
1038
1060
1084
1110
1135
1160
1185
1041
1060
1081
1103
1126
1150
1174
1197
1221
0.56
0.62
0.68
0.74
0.80
0.87
0.95
1.04
1.14
1.50
RPM BHP
Kit A07
1321 0.86
1333 0.92
1345 0.99
1360 1.07
1375 1.15
1391 1.23
1409 1.33
1428 1.42
1448 1.52
0.60
0.65
0.71
0.77
0.84
0.91
1.00
1.09
1.20
1.60
RPM BHP
1356
1367
1380
1393
1408
1424
1442
1462
1483
0.90
0.96
1.03
1.10
1.18
1.27
1.36
1.45
1.55
BLOWER DATA - BELT DRIVE - KGA072 - DOWNFLOW
BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE.
FOR ALL UNITS ADD:
1 - Any factory installed options air resistance (heat section, economizer, wet coil, etc.).
2 - Any field installed accessories air resistance (duct resistance, diffuser, etc.).
See page 27 for blower motors and drives and wet coil and options/accessory air resistance data.
External Static - in. w.g.
Air
Volume
cfm
RPM
BHP
RPM
1900
857
0.41
892
0.45
2000
879
0.47
913
2100
900
0.53
2200
922
0.60
2300
947
2400
974
2500
0.10
0.20
BHP
0.30
RPM
0.40
0.50
0.60
0.70
BHP
RPM
BHP
RPM
BHP
RPM
BHP
BHP
RPM
BHP
927
0.50
962
0.55
999
0.60
1036
0.65
1074
0.69
1112
0.73
0.52
948
0.56
984
0.61
1020
0.67
1058
0.72
1096
0.76
1134
0.80
935
0.58
970
0.63
1007
0.69
1044
0.74
1081
958
0.65
994
0.71
1031
0.76
1068
0.82
1106
0.79
1119
0.84
1157
0.88
0.87
1143
0.91
1180
0.95
0.67
983
0.73
1020
0.79
1057
0.85
1094
0.90
0.76
1010
0.82
1047
0.88
1084
0.94
1120
0.99
1131
0.95
1168
1.00
1205
1.03
1157
1.04
1193
1.08
1230
1.12
1002
0.85
1039
0.91
1075
0.97
1112
1.03
1148
1.08
1184
1.13
1220
1.17
1257
1.21
2600
1032
0.95
1068
1.01
1105
1.07
1141
1.13
2700
1062
1.05
1099
1.11
1136
1.17
1172
1.22
1177
1.17
1213
1.22
1248
1.26
1284
1.31
1207
1.27
1242
1.32
1277
1.37
1312
1.43
2800
1094
1.16
1131
1.22
1167
1.27
1202
1.32
1237
1.38
1271
1.43
1305
1.49
1339
1.56
2900
1127
1.26
1163
1.32
1198
1.38
1233
1.44
1267
1.50
1300
1.56
1334
1.64
1367
1.71
Field Furnished
RPM
0.80
Kit A04
External Static - in. w.g.
Air
Volume
cfm
RPM
1900
1150
0.77
1188
0.81
1227
0.85
1267
0.88
1303
0.92
1333
0.97
1360
1.02
1392
1.06
2000
1172
0.84
1210
0.88
1248
0.92
1286
0.96
1321
1.00
1350
1.05
1377
1.10
1409
1.14
2100
1195
0.91
1233
0.95
1269
1.00
1306
1.04
1339
1.09
1367
1.14
1395
1.19
1426
1.23
2200
1218
0.99
1255
1.03
1290
1.09
1324
1.14
1356
1.19
1385
1.24
1413
1.28
1444
1.32
2300
1242
1.07
1277
1.13
1310
1.20
1343
1.26
1374
1.30
1403
1.34
1432
1.38
1464
1.42
2400
1267
1.16
1300
1.23
1332
1.31
1364
1.37
1394
1.41
1423
1.45
1453
1.48
1484
1.53
2500
1292
1.26
1324
1.34
1355
1.42
1387
1.48
1417
1.52
1445
1.56
1475
1.59
1506
1.64
2600
1318
1.38
1350
1.46
1380
1.55
1411
1.60
1440
1.64
1469
1.68
1498
1.71
1529
1.76
2700
1345
1.51
1376
1.60
1406
1.68
1436
1.73
1465
1.77
1493
1.80
1523
1.84
1553
1.88
2800
1372
1.65
1403
1.74
1433
1.82
1462
1.86
1490
1.90
1519
1.93
1548
1.97
1578
2.01
2900
1399
1.80
1430
1.89
1460
1.96
1489
2.00
1516
2.03
1544
2.06
1573
2.10
1603
2.14
0.90
BHP
1.00
RPM
BHP
1.10
RPM
1.20
BHP
RPM
BHP
1.30
RPM
BHP
1.40
RPM
BHP
1.50
RPM
Kit A04
1.60
BHP
RPM
BHP
Kit A08
K-Series™ KGA Packaged Gas / Electric 3 to 7.5 Tons/ Page 23
BLOWER DATA - BELT DRIVE - KGA072 - HORIZONTAL
BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE.
FOR ALL UNITS ADD:
1 - Any factory installed options air resistance (heat section, economizer, wet coil, etc.).
2 - Any field installed accessories air resistance (duct resistance, diffuser, etc.).
See page 27 for blower motors and drives and wet coil and options/accessory air resistance data.
External Static - in. w.g.
Air
Volume
cfm
RPM
BHP
RPM
BHP
1900
796
0.38
837
0.43
878
2000
833
0.43
870
0.48
2100
864
0.50
897
2200
887
0.57
920
2300
909
0.64
2400
931
0.72
2500
955
2600
2700
2800
2900
Air
Volume
cfm
0.10
0.20
0.30
RPM
BHP
0.40
0.50
0.60
0.70
RPM
BHP
RPM
BHP
RPM
BHP
RPM
RPM
BHP
0.48
918
0.53
958
0.58
997
0.62
1036
0.67
1074
0.71
907
0.54
943
0.59
980
0.64
1018
0.69
1055
0.73
1093
0.77
0.55
931
0.60
966
0.65
1002
0.71
1038
0.62
953
0.67
988
0.73
1024
0.78
1060
0.76
1075
0.80
1113
0.83
0.83
1097
0.87
1135
0.90
942
0.70
976
0.75
1011
0.81
1046
0.86
965
0.78
999
0.83
1035
0.89
1071
0.94
1083
0.91
1120
0.95
1157
0.98
1108
0.99
1144
1.03
1181
1.07
0.80
989
0.86
1024
0.92
1061
0.98
1097
1.03
1133
1.08
1170
1.11
1205
1.15
981
0.90
1016
0.96
1052
1.01
1088
1.07
1009
0.99
1044
1.05
1080
1.11
1116
1.16
1124
1.12
1160
1.16
1195
1.20
1230
1.25
1152
1.21
1187
1.26
1221
1.30
1254
1.35
1038
1.10
1073
1.16
1109
1.21
1145
1.26
1180
1.31
1214
1.36
1247
1.40
1279
1.46
1068
1.20
1104
1.26
1139
1.31
1174
1.36
1208
1.41
1240
1.47
1273
1.52
1304
1.58
Field Furnished
BHP
0.80
Kit A04
External Static - in. w.g.
0.90
RPM
BHP
1.00
RPM
BHP
1.10
RPM
BHP
1.20
RPM
BHP
1.30
RPM
1.40
BHP
RPM
BHP
1.50
RPM
BHP
Kit A04
1.60
RPM
BHP
Kit A08
1900
1112
0.74
1151
0.77
1190
0.81
1228
0.84
1265
0.88
1301
0.92
1335
0.97
1367
1.01
2000
1131
0.80
1170
0.83
1208
0.87
1245
0.91
1281
0.96
1316
1.00
1349
1.04
1380
1.09
2100
1151
0.87
1189
0.90
1227
0.94
1263
0.99
1298
1.04
1331
1.08
1363
1.13
1394
1.17
2200
1173
0.94
1210
0.98
1246
1.02
1281
1.07
1315
1.12
1347
1.17
1379
1.22
1409
1.26
2300
1195
1.02
1231
1.06
1266
1.11
1300
1.16
1333
1.22
1364
1.27
1395
1.32
1424
1.36
2400
1217
1.10
1252
1.15
1286
1.20
1319
1.26
1351
1.32
1382
1.38
1411
1.43
1440
1.48
2500
1240
1.20
1274
1.25
1307
1.31
1339
1.37
1370
1.43
1400
1.49
1428
1.55
1457
1.59
2600
1264
1.30
1297
1.35
1329
1.42
1360
1.49
1389
1.55
1418
1.61
1446
1.67
1475
1.72
2700
1287
1.40
1319
1.47
1350
1.54
1380
1.61
1409
1.68
1437
1.74
1465
1.79
1493
1.84
2800
1311
1.52
1342
1.59
1373
1.66
1402
1.74
1430
1.8
1457
1.87
1485
1.92
1513
1.97
2900
1335
1.65
1366
1.72
1395
1.79
1424
1.87
1451
1.94
1478
2.00
1505
2.05
1533
2.09
K-Series™ KGA Packaged Gas / Electric 3 to 7.5 Tons / Page 24
BLOWER DATA - BELT DRIVE - KGA090 - DOWNFLOW
BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE.
FOR ALL UNITS ADD:
1 - Any factory installed options air resistance (heat section, economizer, wet coil, etc.).
2 - Any field installed accessories air resistance (duct resistance, diffuser, etc.).
See page 27 for blower motors and drives and wet coil and options/accessory air resistance data.
External Static - in. w.g.
Air
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
1.00
Volume
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
cfm
Drive Kit AA01
Drive Kit AA02
AA03
2400
621 0.71 652 0.76 684 0.81 716 0.86 746 0.92 776 0.97 805 1.02 830 1.08 855 1.14 879 1.19
2500
642 0.77 673 0.82 704 0.87 734 0.93 764 0.98 793 1.04 820 1.09 845 1.15 868 1.21 892 1.27
2600
665 0.82 694 0.88 724 0.93 753 0.99 782 1.05 810 1.11 835 1.17 859 1.23 883 1.29 907 1.34
2700
688 0.89 716 0.94 744 1.00 773 1.06 800 1.13 827 1.19 851 1.25 875 1.31 898 1.37 922 1.42
2800
710 0.95 738 1.02 765 1.08 792 1.15 818 1.21 844 1.28 868 1.34 891 1.40 914 1.45 938 1.51
2900
733 1.03 759 1.10 785 1.17 811 1.24 836 1.30 861 1.37 885 1.43 908 1.49 931 1.54 954 1.59
3000
754 1.12 779 1.19 805 1.26 830 1.33 855 1.40 879 1.46 902 1.52 925 1.58 948 1.63 970 1.69
3100
775 1.22 800 1.29 824 1.36 849 1.43 873 1.50 897 1.56 920 1.62 942 1.67 964 1.73 987 1.78
3200
796 1.32 820 1.39 844 1.47 868 1.53 892 1.60 915 1.66 937 1.72 959 1.77 981 1.83 1002 1.88
3300
816 1.43 840 1.50 863 1.57 887 1.64 910 1.70 933 1.76 955 1.82 976 1.88 997 1.93 1018 1.99
3400
837 1.54 860 1.61 883 1.68 906 1.75 929 1.81 951 1.87 972 1.93 993 1.98 1013 2.05 1033 2.11
3500
858 1.66 881 1.73 903 1.79 926 1.86 948 1.92 969 1.98 990 2.04 1009 2.10 1029 2.17 1048 2.24
3600
879 1.77 901 1.84 923 1.91 945 1.97 966 2.04 987 2.10 1006 2.16 1025 2.23 1044 2.30 1062 2.38
External Static - in. w.g.
Air
0.90
1.00
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
Volume
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
cfm
Drive Kit AA03
AA04
2400
904 1.25 929 1.29 956 1.34 982 1.39 1008 1.43 1032 1.49 1056 1.55 1078 1.62 1099 1.68 1121 1.75
2500
917 1.32 942 1.37 968 1.41 994 1.46 1020 1.51 1044 1.57 1066 1.64 1088 1.70 1108 1.77 1130 1.84
2600
931 1.39 957 1.44 982 1.49 1008 1.54 1032 1.60 1055 1.66 1077 1.73 1098 1.80 1118 1.87 1139 1.94
2700
946 1.47 971 1.52 996 1.57 1021 1.63 1045 1.69 1067 1.76 1088 1.83 1108 1.91 1127 1.98 1148 2.05
2800
962 1.56 986 1.61 1011 1.66 1034 1.72 1057 1.79 1079 1.86 1099 1.94 1118 2.02 1137 2.09 1158 2.16
2900
978 1.65 1001 1.70 1025 1.75 1048 1.82 1069 1.89 1090 1.98 1109 2.06 1128 2.14 1147 2.22 1167 2.28
3000
993 1.74 1016 1.79 1039 1.86 1061 1.93 1081 2.01 1101 2.10 1120 2.18 1138 2.27 1157 2.34 1177 2.41
3100
1009 1.84 1031 1.90 1052 1.97 1073 2.05 1093 2.13 1112 2.22 1130 2.31 1148 2.40 1167 2.47 1187 2.53
3200
1024 1.94 1045 2.01 1065 2.09 1085 2.17 1104 2.26 1123 2.36 1141 2.45 1159 2.53 1178 2.60 1198 2.66
3300
1038 2.06 1058 2.13 1078 2.22 1097 2.31 1116 2.40 1134 2.49 1152 2.58 1170 2.66 1189 2.73 1209 2.79
3400
1053 2.19 1072 2.27 1091 2.35 1109 2.45 1127 2.54 1145 2.63 1163 2.72 1181 2.79 1200 2.86 1220 2.92
3500
1067 2.32 1085 2.41 1103 2.50 1121 2.59 1138 2.69 1156 2.78 1174 2.85 1192 2.93 1212 2.99 1231 3.05
3600
1081 2.46 1098 2.55 1116 2.64 1133 2.74 1151 2.83 1168 2.91 1186 2.99 1205 3.06 1224 3.12 1243 3.17
K-Series™ KGA Packaged Gas / Electric 3 to 7.5 Tons/ Page 25
BLOWER DATA - BELT DRIVE - KGA090 - HORIZONTAL
BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE.
FOR ALL UNITS ADD:
1 - Any factory installed options air resistance (heat section, economizer, wet coil, etc.).
2 - Any field installed accessories air resistance (duct resistance, diffuser, etc.).
See page 27 for blower motors and drives and wet coil and options/accessory air resistance data.
External Static - in. w.g.
Air
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
1.00
Volume
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
cfm
Drive Kit AA01
Drive Kit AA02
2400
572 0.75 602 0.78 633 0.81 664 0.85 695 0.88 725 0.92 755 0.97 784 1.01 811 1.06 836 1.11
2500
591 0.80 620 0.83 650 0.87 680 0.90 711 0.94 740 0.98 769 1.03 797 1.08 823 1.13 847 1.18
2600
610 0.86 639 0.89 668 0.92 697 0.96 727 1.00 755 1.05 783 1.09 810 1.14 835 1.20 859 1.25
2700
630 0.91 658 0.95 686 0.98 715 1.02 743 1.07 771 1.11 798 1.16 824 1.22 848 1.27 872 1.32
2800
650 0.97 677 1.01 705 1.05 732 1.09 760 1.14 787 1.19 813 1.24 838 1.30 861 1.35 885 1.40
2900
670 1.03 697 1.07 724 1.11 750 1.16 777 1.21 803 1.27 828 1.32 852 1.38 876 1.44 898 1.49
3000
691 1.09 717 1.14 743 1.18 769 1.24 794 1.29 819 1.35 844 1.42 868 1.47 890 1.53 913 1.58
3100
712 1.16 737 1.21 762 1.27 787 1.32 812 1.39 836 1.45 860 1.51 883 1.57 906 1.63 928 1.68
3200
732 1.24 756 1.30 781 1.36 805 1.42 829 1.48 853 1.55 876 1.61 899 1.67 921 1.73 943 1.78
3300
752 1.33 776 1.39 799 1.46 823 1.52 847 1.59 870 1.65 893 1.71 916 1.77 937 1.83 959 1.88
3400
772 1.43 795 1.50 818 1.56 842 1.63 865 1.69 888 1.76 910 1.82 932 1.88 953 1.93 974 1.99
3500
792 1.54 815 1.61 838 1.67 861 1.74 883 1.80 906 1.87 928 1.93 949 1.98 970 2.04 990 2.10
3600
812 1.65 834 1.72 857 1.79 880 1.85 902 1.92 924 1.98 945 2.04 966 2.10 986 2.16 1005 2.22
External Static - in. w.g.
Air
0.90
1.00
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
Volume
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
cfm
AA02
Drive Kit AA03
2400
861 1.16 886 1.21 911 1.26 937 1.30 963 1.35 988 1.41 1012 1.47 1034 1.53 1055 1.59 1076 1.65
2500
872 1.23 896 1.27 921 1.32 947 1.37 972 1.43 997 1.48 1019 1.55 1041 1.61 1061 1.68 1081 1.74
2600
883 1.30 908 1.35 933 1.40 958 1.45 982 1.50 1006 1.57 1027 1.63 1048 1.70 1068 1.77 1087 1.83
2700
895 1.37 920 1.42 944 1.47 969 1.53 992 1.59 1015 1.65 1036 1.72 1056 1.79 1075 1.86 1094 1.92
2800
908 1.45 932 1.50 956 1.56 980 1.62 1003 1.68 1025 1.75 1045 1.82 1064 1.89 1083 1.96 1102 2.02
2900
922 1.54 945 1.59 969 1.65 992 1.71 1014 1.78 1035 1.85 1055 1.92 1074 2.00 1092 2.07 1111 2.13
3000
936 1.63 959 1.68 982 1.74 1004 1.81 1026 1.88 1046 1.96 1065 2.03 1084 2.11 1102 2.18 1120 2.25
3100
950 1.73 973 1.78 995 1.85 1017 1.91 1037 1.99 1057 2.07 1076 2.15 1094 2.23 1112 2.31 1130 2.38
3200
965 1.83 987 1.89 1008 1.95 1029 2.03 1049 2.11 1068 2.19 1087 2.28 1105 2.36 1123 2.44 1141 2.51
3300
980 1.94 1001 2.00 1022 2.07 1042 2.15 1061 2.23 1080 2.32 1098 2.41 1116 2.50 1134 2.58 1152 2.65
3400
995 2.05 1015 2.12 1035 2.19 1054 2.28 1073 2.37 1092 2.46 1110 2.55 1128 2.64 1145 2.72 1163 2.79
3500
1010 2.17 1029 2.24 1048 2.32 1067 2.41 1086 2.51 1104 2.60 1122 2.70 1139 2.78 1157 2.86 1174 2.93
3600
1024 2.30 1043 2.38 1062 2.46 1080 2.55 1098 2.65 1116 2.75 1133 2.84 1151 2.93 1168 3.01 1186 3.08
AA03
K-Series™ KGA Packaged Gas / Electric 3 to 7.5 Tons / Page 26
Drive Kit AA04
BLOWER DATA
BELT DRIVE KIT SPECIFICATIONS - 036-072
Model
Motor HP
No. of
No. Nominal Maximum Speeds
A01
036
0.75
0.86
1
673-1010
1
1.15
1
673-1010
1.5
1.7
1
673-1010
2
2.3
1
673-1010
048
0.75
0.86
1
--1
1.15
1
--1.5
1.7
1
--2
2.3
1
--060
0.75
0.86
1
--1
1.15
1
--1.5
1.7
1
--2
2.3
1
--072
1
1.5
1
--2
2.3
1
---
BELT DRIVE KIT SPECIFICATIONS - 090
Model
Motor HP
No. of
No. Nominal Maximum Speeds
090
1
2
3
1.15
2.3
3.45
1
1
1
A02
--------745-1117
745-1117
745-1117
745-1117
-------------
Drive Kits and RPM Range
A03
A04
A05
A06
A07
A08
----897-1346
----------897-1346
----------897-1346
----------897-1346
------------1071-1429
----------1071-1429
----------1071-1429
----------1071-1429
----833-1250
------1212-1548
--833-1250
------1212-1548
--833-1250
------1212-1548
--833-1250
------1212-1548
----968-1340
------1193-1591
--968-1340
------1193-1591
Drive Kits and RPM Range
AA02
AA03
----632-875
798-1105
-----
AA01
522-784
-----
AA04
----921-1228
NOTE - Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor hp required.
Maximum usable hp of motors furnished are shown. In Canada, nominal motor hp is also maximum usable motor hp. If motors of comparable hp
are used, be sure to keep within the service factor limitations outlined on the motor nameplate.
OPTIONS / ACCESSORIES AIR RESISTANCE FOR 036-072 MODELS - in. w.g.
Air Volume
cfm
800
1000
1200
1400
1600
1800
2000
2200
2400
2600
2800
3000
Wet Indoor Coil
036-048
060
0.01
0.01
0.02
0.02
0.03
0.04
0.04
0.05
0.05
0.06
0.06
0.07
0.08
0.09
0.09
0.10
0.10
0.12
0.11
0.13
0.13
0.15
0.14
0.16
072
0.01
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.10
0.12
Gas Heat
Medium Input
High Input
0.02
0.02
0.02
0.02
0.02
0.02
0.02
0.03
0.03
0.04
0.03
0.05
0.04
0.06
0.04
0.07
0.05
0.08
0.05
0.09
0.06
0.10
0.07
0.11
Economizer
0.04
0.04
0.04
0.04
0.04
0.05
0.05
0.05
0.05
0.06
0.06
0.06
Filters
MERV 8
MERV 13
0.04
0.05
0.04
0.07
0.04
0.07
0.04
0.07
0.04
0.07
0.05
0.07
0.05
0.08
0.05
0.08
0.05
0.08
0.05
0.08
0.05
0.08
0.05
0.08
OPTIONS / ACCESSORIES AIR RESISTANCE FOR 090 MODELS - in. w.g.
Air Volume
cfm
Wet Indoor Coil
2400
2600
2800
3000
3200
3400
3600
0.08
0.09
0.10
0.11
0.12
0.14
0.15
Gas Heat
High Input
0.03
0.04
0.04
0.04
0.04
0.05
0.05
Economizer
0.05
0.06
0.06
0.06
0.06
0.06
0.06
Filters
MERV 8
0.05
0.05
0.05
0.05
0.06
0.06
0.06
MERV 13
0.08
0.08
0.08
0.08
0.09
0.09
0.10
K-Series™ KGA Packaged Gas / Electric 3 to 7.5 Tons/ Page 27
BLOWER DATA
CEILING DIFFUSERS AIR RESISTANCE (in. w.g.)
RTD9-65S Step–Down Diffuser
Air Volume
2 Ends
1 Side &
All Ends &
cfm
Open
2 Ends Open
Sides Open
800
0.15
0.13
0.11
1000
0.19
0.16
0.14
1200
0.25
0.20
0.17
1400
0.33
0.26
0.20
1600
0.43
0.32
0.20
1800
0.56
0.40
0.30
2000
0.73
0.50
0.36
2200
0.95
0.63
0.44
2400
-------2600
-------2800
-------3000
-------3200
-------3400
-------3600
-------CEILING DIFFUSER AIR THROW DATA
1
Air Volume - cfm
Effective Throw - ft.
Model No.
RTD9-65S
FD9-65S
800
10 - 17
14 - 18
1000
10 - 17
15 - 20
1200
11 - 18
16 - 22
1400
12 - 19
17 - 24
1600
12 - 20
18 - 25
1800
13 - 21
20 - 28
2000
14 - 23
21 - 29
2200
16 - 25
22 - 30
Model No.
RTD11-95S
FD11-95S
2600
24 - 29
19 - 24
2800
25 - 30
20 - 28
3000
27 - 33
21 - 29
3200
28 - 35
22 - 29
3400
30 - 37
22 - 30
3600
25 - 33
22 - 24
1
Effective throw based on terminal velocities of 75 ft. per minute.
K-Series™ KGA Packaged Gas / Electric 3 to 7.5 Tons / Page 28
FD9-65S
Flush
Diffuser
0.11
0.14
0.17
0.20
0.24
0.30
0.36
0.44
---------------
RTD11-95S Step–Down Diffuser
2 Ends
1 Side &
All Ends &
Open
2 Ends Open
Sides Open
------------------------------0.13
0.11
0.09
0.15
0.13
0.11
0.18
0.15
0.12
0.21
0.18
0.15
0.24
0.21
0.18
0.27
0.24
0.21
0.32
0.29
0.25
0.41
0.37
0.32
0.50
0.45
0.39
0.61
0.54
0.48
FD11-95S
Flush
Diffuser
----------0.09
0.10
0.12
0.14
0.17
0.20
0.25
0.31
0.37
0.44
ELECTRICAL DATA
3 TON
KGA036 - DIRECT AND BELT DRIVE
1
Voltage - 60hz
Compressor
208/230V - 3 Ph
460V - 3 Ph
575V - 3 Ph
8.7
4
3.6
Rated Load Amps
Locked Rotor Amps
70
31
27
Outdoor Fan
Motor
Full Load Amps
1.7
1.1
0.7
Power Exhaust
(1) 0.33 HP
Full Load Amps
2.4
1.3
1
Service Outlet 115V GFI (amps)
Indoor Blower
Motor
2
3
aximum
M
Overcurrent
Protection
Minimum
Circuit
Ampacity
15
Horsepower
15
20
0.5
1
2
0.5
1
2
0.5
1
2
Direct
Belt
Belt
Direct
Belt
Belt
Direct
Belt
Belt
Full Load Amps
3.9
4.6
7.5
2
2.1
3.4
2
1.7
2.7
Unit Only
25
25
25
15
15
15
15
15
15
with (1) 0.33 HP
Power Exhaust
25
25
30
15
15
15
15
15
15
Unit Only
17
18
21
9
9
10
8
7
8
with (1) 0.33 HP
Power Exhaust
19
20
23
10
10
11
9
8
9
Type
ELECTRICAL ACCESSORIES
Disconnect
Standard Access
20W17
20W17
20W17
Hinged Access
20W23
20W23
20W23
NOTE - All units have a minimum Short Circuit Current Rating (SCCR) of 5000 amps.
1
Extremes of operating range are plus and minus 10% of line voltage.
2
HACR type breaker or fuse.
3
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
ELECTRICAL DATA
4 TON
KGA048 - DIRECT AND BELT DRIVE
1
Voltage - 60hz
Compressor
208/230V - 3 Ph
460V - 3 Ph
575V - 3 Ph
Rated Load Amps
11
5.5
4.7
Locked Rotor Amps
86
37
34
Outdoor Fan
Motor
Full Load Amps
1.7
1.1
0.7
Power Exhaust
(1) 0.33 HP
Full Load Amps
2.4
1.3
1
Service Outlet 115V GFI (amps)
Indoor Blower
Motor
2
3
aximum
M
Overcurrent
Protection
Minimum
Circuit
Ampacity
Horsepower
0.5
1
2
0.5
1
2
0.5
1
2
Direct
Belt
Belt
Direct
Belt
Belt
Direct
Belt
Belt
Full Load Amps
3.9
4.6
7.5
2
2.1
3.4
2
1.7
2.7
Unit Only
30
30
30
15
15
15
15
15
15
with (1) 0.33 HP
Power Exhaust
30
30
35
15
15
15
15
15
15
Unit Only
20
21
23
10
11
13
12
9
10
with (1) 0.33 HP
Power Exhaust
22
23
26
12
12
13
10
10
11
Type
ELECTRICAL ACCESSORIES
Disconnect
Standard Access
20W17
20W17
20W17
Hinged Access
20W23
20W23
20W23
NOTE - All units have a minimum Short Circuit Current Rating (SCCR) of 5000 amps.
1
Extremes of operating range are plus and minus 10% of line voltage.
2
HACR type breaker or fuse.
3
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
K-Series™ KGA Packaged Gas / Electric 3 to 7.5 Tons/ Page 29
ELECTRICAL DATA
5 TON
KGA060 - DIRECT AND BELT DRIVE
Voltage - 60hz
1
Compressor
208/230V - 3 Ph
460V - 3 Ph
575V - 3 Ph
Rated Load Amps
13.5
8
5
Locked Rotor Amps
109
59
40
Outdoor Fan
Motor
Full Load Amps
2.4
1.3
1
Power Exhaust
(1) 0.33 HP
Full Load Amps
2.4
1.3
1
Service Outlet 115V GFI (amps)
Indoor Blower
Motor
aximum
M
Overcurrent
Protection
2
Minimum
Circuit
Ampacity
3
15
Horsepower
15
20
0.75
1
2
0.75
1
2
0.75
1
2
Direct
Belt
Belt
Direct
Belt
Belt
Direct
Belt
Belt
Full Load Amps
4.9
4.6
7.5
2.5
2.1
3.4
2.5
1.7
2.7
Unit Only
35
35
40
20
20
20
15
15
15
with (1) 0.33 HP
Power Exhaust
40
35
40
20
20
20
15
15
15
Unit Only
25
24
27
14
14
15
10
9
10
with (1) 0.33 HP
Power Exhaust
27
27
30
16
15
16
11
10
11
Type
ELECTRICAL ACCESSORIES
Disconnect
Standard Access
20W17
20W17
20W17
Hinged Access
20W23
20W23
20W23
NOTE - All units have a minimum Short Circuit Current Rating (SCCR) of 5000 amps.
1
Extremes of operating range are plus and minus 10% of line voltage.
2
HACR type breaker or fuse.
3
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
ELECTRICAL DATA 6 TON
KGA072 - BELT DRIVE BLOWER
1
Voltage - 60hz
Compressor
208/230V - 3 Ph
460V - 3 Ph
575V - 3 Ph
Rated Load Amps
19.6
8.2
6.6
Locked Rotor Amps
136
66.1
55.3
Outdoor Fan
Motor
Full Load Amps
2.4
1.3
1
Power Exhaust
(1) 0.33 HP
Full Load Amps
2.4
1.3
1
Service Outlet 115V GFI (amps)
Indoor Blower
Motor
2
3
aximum
M
Overcurrent
Protection
Minimum
Circuit
Ampacity
15
Horsepower
15
20
1
2
1
2
1
2
Type
Belt
Belt
Belt
Belt
Belt
Belt
Full Load Amps
4.6
7.5
2.1
3.4
1.7
2.7
Unit Only
50
50
20
20
15
15
with (1) 0.33 HP
Power Exhaust
50
50
20
20
15
15
Unit Only
32
35
14
15
11
12
with (1) 0.33 HP
Power Exhaust
34
37
15
17
12
13
ELECTRICAL ACCESSORIES
Disconnect
Kit
Standard Access
20W20
20W20
20W20
Hinged Access
20W26
20W26
20W26
NOTE - All units have a minimum Short Circuit Current Rating (SCCR) of 5000 amps.
1
Extremes of operating range are plus and minus 10% of line voltage.
2
HACR type breaker or fuse.
3
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
K-Series™ KGA Packaged Gas / Electric 3 to 7.5 Tons / Page 30
ELECTRICAL DATA 7.5 TON
KGA090 - BELT DRIVE BLOWER
1
Voltage - 60hz
Compressor 1
208/230V - 3 Ph
460V - 3 Ph
575V - 3 Ph
Rated Load Amps
25
12.2
9
Locked Rotor Amps
164
100
78
Outdoor Fan
Motors (1)
Full Load Amps (total)
2.4
1.3
1
Power Exhaust
(1) 0.33 HP
Full Load Amps (total)
2.4
1.3
1
Service Outlet 115V GFI
Indoor Blower
Motor
2
3
aximum
M
Overcurrent
Protection
Minimum
Circuit
Ampacity
15
Horsepower
15
20
1
2
3
1
2
3
1
2
3
Type
Belt
Belt
Belt
Belt
Belt
Belt
Belt
Belt
Belt
Full Load Amps
4.6
7.5
10.6
2.1
3.4
4.8
1.7
2.7
3.9
Unit Only
60
60
60
30
30
30
20
20
25
with (1) 0.33 HP
Power Exhaust
60
60
70
30
30
30
20
20
25
Unit Only
39
42
45
19
20
22
14
15
17
with (1) 0.33 HP
Power Exhaust
41
44
47
20
22
23
15
16
18
ELECTRICAL ACCESSORIES
Disconnect
Kit
Standard Access
20W20
20W20
20W20
Hinged Access
20W26
20W26
20W26
NOTE - All units have a minimum Short Circuit Current Rating (SCCR) of 5000 amps.
1
Extremes of operating range are plus and minus 10% of line voltage.
2
HACR type breaker or fuse.
3
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
K-Series™ KGA Packaged Gas / Electric 3 to 7.5 Tons/ Page 31
UNIT CLEARANCES - INCHES (MM)
C
B
OUTDOOR AIR
HOOD
D
A
1
Unit Clearance
A
B
C
D
in.
mm
in.
mm
in.
mm
in.
mm
Service Clearance
48
1219
36
914
36
914
36
914
Clearance to Combustibles
36
914
1
25
1
25
1
25
Minimum Operation Clearance
36
914
36
914
36
914
36
914
NOTE - Entire perimeter of unit base requires support when elevated above the mounting surface.
1
S
ervice Clearance - Required for removal of serviceable parts.
Clearance to Combustibles - Required clearance to combustible material.
Minimum Operation Clearance - Required clearance for proper unit operation.
Top
Clearance
Unobstructed
OUTDOOR SOUND DATA
Unit
Model No.
KGA036 and 048
KGA060
KGA072
KGA090
Octave Band Linear Sound Power Levels dBA, re 10-12 Watts - Center Frequency Hz
125
250
500
1000
2000
4000
8000
63
67
66
66
66
72
71
71
70
77
74
73
71
76
73
74
68
73
70
70
62
68
65
65
53
61
57
57
Sound Rating
Number (SRN)
(dBA)
1
75
82
79
79
Note - The octave sound power data does not include tonal corrections.
1
Sound Rating Number according to ARI Standard 270-95 (includes pure tone penalty). “SRN” is the overall A-Weighted Sound Power Level, (LWA), dBA (100 Hz to
10,000 Hz).
K-Series™ KGA Packaged Gas / Electric 3 to 7.5 Tons/ Page 33
WEIGHT DATA
Model Number
Net
Shipping
Base
Max.
Base
Max.
lbs.
kg
lbs.
kg
lbs.
kg
lbs.
kg
KGA036
534
242
634
288
594
269
703
319
KGA048
571
258
682
309
631
286
751
341
KGA060
601
273
712
323
661
300
781
354
KGA072
649
294
813
369
690
313
854
387
KGA090
783
355
883
401
843
382
953
432
Base Unit - The unit with standard heat exchanger NO OPTIONS.
Max. Unit - The unit with ALL OPTIONS Installed. (High Input Heat Exchanger, Economizer, etc.)
OPTIONS / ACCESSORIES
Shipping Weights
lbs.
kg
131
59
Motorized
25
12
Manual
18
8
35
16
Medium Heat (adder over standard heat)
8
4
High Heat (adder over standard heat)
19
9
8 in. height
50
23
14 in. height
70
32
18 in. height
80
36
24 in. height
100
45
8 in. height
57
26
14 in. height
60
27
18 in. height
91
41
24 in. height
114
52
113
51
ECONOMIZER / OUTDOOR AIR / EXHAUST
Economizer
Economizer - Includes Barometric Relief Dampers and Exhaust Hood
Outdoor Air Dampers
Power Exhaust
Standard Static
GAS HEAT
ROOF CURBS
Hybrid Roof Curbs, Downflow
Hybrid Curbs, Full Perimeter, Downflow
Adjustable Pitch Curb, Downflow
14 in. height
CEILING DIFFUSERS
Step-Down
Flush
Transitions (Supply and Return)
RTD9-65S
80
36
RTD11-95S
118
54
FD9-65S
80
36
FD11-95S
118
54
T1TRAN10AN1
22
10
T1TRAN20N-1
21
10
K-Series™ KGA Packaged Gas / Electric 3 to 7.5 Tons / Page 34
DIMENSIONS - UNIT - INCHES (MM)
Model
No.
036
048
060
072
090
AA
Base
lbs. kg
92 42
99 45
104 47
130 59
168 76
Max.
lbs. kg
114 52
123 56
128 58
162 74
195 88
CORNER WEIGHTS
BB
CC
Base
Max.
Base
Max.
lbs. kg lbs. kg lbs. kg lbs. kg
112 51 129 59 181 82 208 94
120 55 139 63 193 88 223 102
126 57 145 66 203 92 233 106
147 67 167 76 198 90 226 103
183 83 212 96 227 103 263 119
DD
Base
lbs. kg
149 68
159 72
167 76
175 79
203 95
EE
Max.
Base
lbs. kg in.
mm
184 83 38-1/2 978
197 90 38-1/2 978
206 94 38-1/2 978
257 117 40 1016
241 109 47 1194
CENTER OF GRAVITY
FF
Max.
Base
in. mm
in.
mm
40 1016 18
457
40 1016 18
457
40 1016 18
457
44 1118 20
508
47 1194 21
533
Max.
in.
mm
18
457
18
457
18
457
20
508
21
533
Base Unit - The unit with NO INTERNAL OPTIONS.
Max. Unit - The unit with ALL INTERNAL OPTIONS Installed. (Economizer, Standard Static Power Exhaust Fans, Controls, etc.). Does not include accessories external to
unit or high static power exhaust.
5-5/8
(143)
AA
16-1/4
(413)
11
(279)
18
(457)
BB
5 (127)
7 (178)
BOTTOM
RETURN
AIR
OPENING
29
(737)
BOTTOM
SUPPLY
AIR
OPENING
47 (1194)
BASE
20
(508) CENTER
OF
GRAVITY
25-3/4 (654)
KGA036 thru 072
38-3/4 (984) KGA090
FF
6-5/8
(168)
DD
26-1/2
(673)
9-1/2
(241)
CC
BOTTOM
CONDENSATE
OUTLET
EE
BOTTOM POWER ENTRY
3 X 8 (76 X 203)
TOP VIEW (Base)
83-1/4 (2115) KGA036 thru 072
96-1/4 (2445) KGA090
47 (1194)
BASE
END VIEW
35-3/8 (899) KGA036 thru 060
43-3/8 (1102) KGA072 / 090
1 (25)
38-7/8 (987) KGA036 thru 060
46-7/8 (1191) KGA072 / 090
45
(1143)
CONDENSATE
OUTLET
(EITHER SIDE)
3-1/2 (89)
LIFTING HOLES
(For rigging)
ELECTRICAL
INLET
FLUE/VENT
OUTLET
26-1/2
(673)
GAS
INLET
15
(381)
5-1/2
(140)
85-1/4 (2165) KGA036 thru 072 BASE
98-1/4 (2496) KGA090 BASE
1 (25)
27
(686)
SIDE VIEW
19-1/2
(495)
20
(508)
FORKLIFT SLOTS
(Front, Back and
Blower End)
18-3/8
(467)
11
(279)
2 (51)
29
(737)
5-1/2 HORIZONTAL HORIZONTAL 5-1/2
RETURN AIR (140)
(140) SUPPLY AIR
OPENING
OPENING
(Without Economizer)
BACK VIEW
K-Series™ KGA Packaged Gas / Electric 3 to 7.5 Tons/ Page 35
DIMENSIONS - ACCESSORIES - INCHES (MM)
OUTDOOR AIR HOOD DETAIL FOR OPTIONAL ECONOMIZER AND BAROMETRIC RELIEF DAMPERS
(Downflow Applications)
11-3/4
(298)
OPTIONAL OUTDOOR
AIR HOOD
(Furnished with Economizer)
17-3/8
(441)
OPTIONAL BAROMETRIC
RELIEF HOOD
(Furnished with Economizer )
OUTDOOR AIR HOOD FOR ECONOMIZER
(Furnished)
11-3/4
(298)
SIDE VIEW
BAROMETRIC RELIEF HOOD FOR ECONOMIZER
(Furnished)
17-3/8
(441)
35
(889)
35
(889)
19-7/8
(505)
13
(330)
OUTDOOR AIR DAMPER HOOD DETAIL FOR OPTIONAL MANUAL OR MOTORIZED OUTDOOR AIR DAMPERS
(Downflow or Horizontal Applications)
10-1/2
(267)
OPTIONAL
OUTDOOR
AIR DAMPERS
AND PANEL
OUTDOOR AIR
DAMPER HOOD
(Furnished)
OUTDOOR AIR
DAMPER HOOD
35
(889)
13-1/2
(343)
35
(889)
SIDE VIEW
16-1/2
(419)
K-Series™ KGA Packaged Gas / Electric 3 to 7.5 Tons / Page 36
10-1/2
(267)
DIMENSIONS - ACCESSORIES - INCHES (MM)
OUTDOOR AIR HOOD DETAIL WITH OPTIONAL ECONOMIZER AND BAROMETRIC RELIEF DAMPERS
(Horizontal Applications)
Barometric Relief Hood
and Dampers
ECONOMIZER DAMPERS
SUPPLY AIR DUCT
(Field Provided)
SUPPLY
AIR
OUTLET
RETURN AIR
DUCT TRANSITION
(Field fabricated and
installed on unit)
TOP VIEW
RETURN AIR DUCT
(Field Fabricated - Must be sized to
accommodate Barometric Relief
Hood and Return Air Requirements)
BAROMETRIC RELIEF HOOD DIMENSIONS
Width - 35-1/2 in. (902 mm)
Height -21 in. (533 mm)
RETURN
AIR
INLET
See previous page for details.
OUTDOOR AIR HOOD
(Furnished with Economizer)
19-1/2
(495)
HORIZONTAL
SUPPLY AIR
OPENING
31-3/8
(797)
11-3/4
(298)
This opening
not used in
Horizontal
Applications
with
20 Economizer
(508)
NOTE - Horizontal applications with Economizer require
Horizontal Economizer Conversion Kit.
See Options/Accessories table.
BAROMETRIC RELIEF HOOD
(Furnished with Economizer and
Field Installed on Field fabricated
Return Air Duct)
OUTDOOR
AIR
7/8
(22)
2-1/4
(57)
HORIZONTAL
RETURN AIR
OPENING
18-3/4
(476)
30-7/16
(773)
2-1/4
(57)
EXHAUST
AIR
BACK VIEW
5-1/2
RETURN AIR
(140) DUCT TRANSITION
(Field fabricated and
installed on unit)
RETURN AIR DUCT INLET
(Field Fabricated - Must be sized to
accommodate Barometric Relief
Hood and Return Air Requirements)
7/8
(22)
UNIT RETURN AIR DUCT
OPENING WITH ECONOMIZER
INSTALLED
END VIEW
NOTE - Return Air Duct and Transition must be supported.
K-Series™ KGA Packaged Gas / Electric 3 to 7.5 Tons/ Page 37
DIMENSIONS - ACCESSORIES - INCHES (MM)
HYBRID ROOF CURBS - DOUBLE DUCT OPENING - STANDARD AND FULL PERIMETER
A
38
(965)
B
19-1/8
(486)
41-1/2
(1054)
21-1/8
(537)
15-1/8
(384)
8 (203)
14 (356)
18 (457)
24 (610)
SUPPLY
OPENING
12-5/8
(321)
1-3/4
(44)
32
(813)
RETURN
OPENING
NOTE - Roof deck may be omitted within confines of curb.
DETAIL ROOF CURB
TYPICAL FLASHING DETAIL FOR ROOF CURB
BASE BOTTOM
PACKAGED
UNIT
1-3/4
(44)
1/2 (13)
FIBERGLASS
INSULATION
(Furnished)
COUNTER FLASHING
(Field Supplied)
FACTORY INSTALLED
PERIMETER WOOD
NAILER STRIP
NAILER STRIP
(Furnished)
ROOF CURB
(Extends around entire
perimeter of unit)
CANT STRIP
(Field Supplied)
8 (203)
14 (356)
18 (457)
24 (610)
ROOFING
MATERIAL
RIGID INSULATION
(Field Supplied)
1-3/4
(44)
Model No.
A
B
in.
mm
in.
mm
Standard - 036, 048, 060, 072, 090
79-3/4
2026
76-1/4
1937
Full Perimeter - 090
92-3/4
2356
89-1/4
2267
1
1
90 models can be used on smaller 79-3/4 in. (2026 mm) roof curbs (not full perimeter) with 15-3/4 in. (400
0
mm) overhang at condenser end of unit. See dimension drawing on page 40
K-Series™ KGA Packaged Gas / Electric 3 to 7.5 Tons / Page 38
DIMENSIONS - ACCESSORIES - INCHES (MM)
ADJUSTABLE PITCH CURBS - DOUBLE DUCT OPENING
76-1/4
(1937)
79-3/4
(2026)
38
(965)
21-1/8
(537)
19-1/8
(486)
15-1/8
(384)
41-1/2
(1054)
14
(356)
SUPPLY
OPENING
12-5/8
(321)
32
(813)
RETURN
OPENING
FACTORY INSTALLED
PERIMETER WOOD
NAILER STRIP
BOTTOM CURB
ASSEMBLY
NOTE - Maximum slope pitch is 3/4 in. per 1 foot (19 mm per 305 mm)
in any one direction.
TYPICAL FLASHING DETAIL FOR ROOF CURB
BASE BOTTOM
DETAIL ROOF CURB
PACKAGED
UNIT
1-3/4
(44)
1/2 (13)
FIBERGLASS
INSULATION
(Furnished)
COUNTER FLASHING
(Field Supplied)
FACTORY INSTALLED
PERIMETER WOOD
NAILER STRIP
NAILER STRIP
(Furnished)
ROOF CURB
(Extends around entire
perimeter of unit)
CANT STRIP
(Field Supplied)
ROOFING
MATERIAL
14
(356)
RIGID INSULATION
(Field Supplied)
1-3/4
(44)
K-Series™ KGA Packaged Gas / Electric 3 to 7.5 Tons/ Page 39
DIMENSIONS - ACCESSORIES - INCHES (MM)
090 MODELS - SHOWING OVERHANG ON SMALLER 79-3/4 INCH LENGTH ROOF CURBS
(Not Full Perimeter)
ROOF CURB
79-3/4
(2026)
2-3/4
(70)
15-3/4
(400)
SIDE VIEW
TRANSITIONS
T1TRAN10AN-1 - FOR 18 INCH (457 MM) DUCT
T1TRAN20N-1 - FOR 20 INCH (508 MM) DUCT
12
(305)
31-1/2
(800)
8 (203)
1-1/2 inch (38 mm) T1TRAN10AN-1
2 inch (51mm) T1TRAN20N-1
32
(813)
12-5/8
(321)
19-1/8
(486)
RETURN
OPENING
RETURN TRANSITION
SUPPLY
OPENING
21-1/8
(537)
T1TRAN10AN-1 - FOR 18 INCH (457 MM) DUCT
T1TRAN20N-1 - FOR 20 INCH (508 MM) DUCT
18-1/2
(470)
20-1/2
(521)
8 (203)
1-1/2 inch (38 mm) T1TRAN10AN-1
2 inch (51mm) T1TRAN20N-1
SUPPLY TRANSITION
K-Series™ KGA Packaged Gas / Electric 3 to 7.5 Tons / Page 40
DIMENSIONS - ACCESSORIES - INCHES (MM)
COMBINATION CEILING SUPPLY AND RETURN DIFFUSERS
STEP-DOWN CEILING DIFFUSER
E
FLUSH CEILING DIFFUSER
D
H
G
F
G
H
G
E
H
F
G
C
C
2 (51)
L
2 (51)
A
B
D
H
A
B
J
K
Model Number
A
in.
mm
B
in.
mm
C
in.
mm
D
in.
mm
E
in.
mm
F
in.
mm
G
in.
mm
H
in.
mm
J
in.
mm
K
in.
mm
L
in.
mm
Duct Size
RTD9-65S
RTD11-95S
47-5/8
47-5/8
1159
1159
23-5/8
29-5/8
600
752
11-3/8
14-3/8
289
365
21-1/2
27-1/2
546
699
45-1/2
45-1/2
1156
1158
22-1/2
22-1/2
572
572
11-1/2
11-1/2
292
292
10-3/4
13-3/4
273
349
45-1/2
45-1/2
1156
1156
21-1/2
27-1/2
546
699
7-1/8
8-1/8
181
206
in.
18 round
20 round
mm
457 round
508 round
Model Number
A
in.
mm
B
in.
mm
C
D
E
1159
23-5/8
29-5/8
752
mm
343
422
in.
21
27
mm
533
686
in.
in.
in.
in.
mm
Duct Size
47-5/8
1159
16-5/8
mm
H
47-5/8
600
mm
G
FD11-95S
13-1/2
in.
mm
F
FD9-65S
45
45
1143
1143
22-1/2
22-1/2
572
572
11-1/4
11-1/4
286
286
10-1/2
13-1/2
267
343
in.
18 round
20 round
mm
457 round
508 round
K-Series™ KGA Packaged Gas / Electric 3 to 7.5 Tons/ Page 41
Visit us at www.allied-commercial.com
For the latest technical information, visit us at www.allied-commercial.com
Contact us at 1-800-448-5872
NOTE - Due to Allied Commercial ongoing commitment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability.
Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury.
Installation and service must be performed by a qualified installer and servicing agency.
©2016 Allied Air Enterprises LLC, a Lennox International Inc. Company