254596-YTG-A-0306
®
DESCRIPTION
YORK Sunline Magnum™ units are convertible single package air conditioners with a common cabinet and a common
roof curb for the 3, 4 and 5 ton sizes. The units were
designed for light commercial and commercial applications.
They can easily be installed on a roof curb, slab, roof jack or
frame.
TECHNICAL GUIDE
SINGLE PACKAGE GAS/ELECTRIC UNITS
All units include:
AND SINGLE PACKAGE
•
Powder Paint finish that meets ASTM-B-117 1000 hour
salt spray standards
•
Permanently lubricated motors
•
Bottom or side air discharge configuration capability
(field convertible)
•
Manufactured under the quality standards of ISO9001
•
Simplicity® Control Board
•
Copper tube/aluminum fin coils
•
Easy access to all components
•
Rigging holes in base rails for lifting
•
Fork lift slots on three sides
•
Single point power connection
•
Complete factory package - tested, charged and wired
•
Belt Drive Indoor Blower
•
CSA agency listing on all units
AIR CONDITIONERS
DJ 036, 048 & 060
3, 4 & 5 NOMINAL TONS
13.40 to 13.50 SEER
WARRANTY
•
Factory Limited Parts Warranty
•
One-year parts warranty
•
A Five-year parts warranty on the compressor and
electric heat elements.
•
Ten-year parts warranty on the gas-fired heat
exchangers.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
254596-YTG-A-0306
TABLE OF CONTENTS
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Tbl. #
PRODUCT NOMENCLATURE . . . . . . . . . . . . . . . . . 3
11 DJ048 INDOOR SOUND POWER LEVELS (VERTICAL
DUCTED DISCHARGE) . . . . . . . . . . . . . . . . . . . . . . . 11
FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
FACTORY-INSTALLED OPTIONS . . . . . . . . . . . . . . 5
FIELD-INSTALLED ACCESSORIES . . . . . . . . . . . . 6
Pg. #
12 DJ060 INDOOR SOUND POWER LEVELS
(HORIZONTAL DUCTED INLET) . . . . . . . . . . . . . . . . 12
GUIDE SPECIFICATIONS . . . . . . . . . . . . . . . . . . . 36
13 DJ060 INDOOR SOUND POWER LEVELS
(HORIZONTAL DUCTED DISCHARGE) . . . . . . . . . . . 12
LIST OF FIGURES
14 DJ060 INDOOR SOUND POWER LEVELS (VERTICAL
DUCTED INLET) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Fig. #
Pg. #
1
UNIT CUTAWAY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2
TYPICAL FIELD POWER & CONTROL WIRING . . . . 29
3
UNIT DIMENSIONS (3 - 5 TON COOLING ONLY/
ELECTRIC HEAT) FRONT VIEW . . . . . . . . . . . . . . . . 30
4
UNIT DIMENSIONS (3 - 5 TON COOLING/GAS HEAT)
FRONT VIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
5
UNIT WITH ECONOMIZER RAINHOOD . . . . . . . . . . . 31
6
UNIT WITH FIXED OUTDOOR AIR/MOTORIZED
DAMPER RAINHOOD . . . . . . . . . . . . . . . . . . . . . . . . . 31
7
UNIT DIMENSIONS (REAR VIEW) . . . . . . . . . . . . . . . 32
8
DISCONNECT/BLOWER ACCESS LOCATION . . . . . 32
9
TYPICAL APPLICATIONS . . . . . . . . . . . . . . . . . . . . . . 33
10 FOUR AND SIX POINT LOADING . . . . . . . . . . . . . . . . 34
11 ROOF CURB DIMENSIONS . . . . . . . . . . . . . . . . . . . . 35
15 DJ060 INDOOR SOUND POWER LEVELS (VERTICAL
DUCTED DISCHARGE) . . . . . . . . . . . . . . . . . . . . . . . 13
16 DJ036 COOLING CAPACITIES (3 TON) . . . . . . . . . . . 14
17 DJ048 COOLING CAPACITIES (4 TON) . . . . . . . . . . . 15
18 DJ060 COOLING CAPACITIES (5 TON) . . . . . . . . . . . 16
19 SUPPLY AIR BLOWER PERFORMANCE (DJ036 BELT
DRIVE) - SIDE DUCT APPLICATION . . . . . . . . . . . . . 17
20 SUPPLY AIR BLOWER PERFORMANCE (DJ036 BELT
DRIVE) - BOTTOM DUCT APPLICATION . . . . . . . . . 18
21 SUPPLY AIR BLOWER PERFORMANCE (DJ048 BELT
DRIVE) - SIDE DUCT APPLICATION . . . . . . . . . . . . . 19
22 SUPPLY AIR BLOWER PERFORMANCE (DJ048 BELT
DRIVE) - BOTTOM DUCT APPLICATION . . . . . . . . . 20
23 SUPPLY AIR BLOWER PERFORMANCE (DJ060 BELT
DRIVE) - SIDE DUCT APPLICATION . . . . . . . . . . . . . 21
24 SUPPLY AIR BLOWER PERFORMANCE (DJ060 BELT
DRIVE) - BOTTOM DUCT APPLICATION . . . . . . . . . 22
LIST OF TABLES
Pg. #
25 BELT DRIVE BLOWER MOTOR AND DRIVE DATA . 23
1
CAPACITY RATINGS - (ARI 210/240) . . . . . . . . . . . . . . 7
26 STATIC RESISTANCES . . . . . . . . . . . . . . . . . . . . . . . 23
2
GAS HEAT RATINGS . . . . . . . . . . . . . . . . . . . . . . . . . . 7
27 ELECTRIC HEATER CFM LIMITATIONS . . . . . . . . . . 23
3
2 STAGE GAS HEAT RATINGS . . . . . . . . . . . . . . . . . . 7
4
DJ036 INDOOR SOUND POWER LEVELS
(HORIZONTAL DUCTED INLET) . . . . . . . . . . . . . . . . . . 8
28 ELECTRICAL DATA - DJ036, 048 & 060 BELT DRIVE
W/O POWERED CONVENIENCE OUTLET . . . . . . . . 24
Tbl. #
5
DJ036 INDOOR SOUND POWER LEVELS
(HORIZONTAL DUCTED DISCHARGE) . . . . . . . . . . . . 8
29 ELECTRICAL DATA - DJ036, 048 & 060 BELT DRIVE
WITH POWERED CONVENIENCE OUTLET . . . . . . . 26
30 PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
6
DJ036 INDOOR SOUND POWER LEVELS (VERTICAL
DUCTED INLET) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
31 ELECTRIC HEAT CORRECTION FACTORS . . . . . . 28
7
DJ036 INDOOR SOUND POWER LEVELS (VERTICAL
DUCTED DISCHARGE) . . . . . . . . . . . . . . . . . . . . . . . . . 9
33 UTILITIES ENTRY . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
8
DJ048 INDOOR SOUND POWER LEVELS
(HORIZONTAL DUCTED INLET) . . . . . . . . . . . . . . . . . 10
9
DJ048 INDOOR SOUND POWER LEVELS
(HORIZONTAL DUCTED DISCHARGE) . . . . . . . . . . . 10
10 DJ048 INDOOR SOUND POWER LEVELS (VERTICAL
DUCTED INLET) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2
32 VOLTAGE LIMITATIONS . . . . . . . . . . . . . . . . . . . . . . 28
34 MINIMUM CLEARANCES . . . . . . . . . . . . . . . . . . . . . . 32
35 DJ 4 AND 6 POINT LOADS WEIGHT
DISTRIBUTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
36 CENTER OF GRAVITY . . . . . . . . . . . . . . . . . . . . . . . . 34
37 OPERATING WEIGHTS (LBS.) . . . . . . . . . . . . . . . . . . 35
Unitary Products Group
254596-YTG-A-0306
PRODUCT NOMENCLATURE
3-5 Ton Sunline Magnum™ Model Number Nomenclature
D J 048 N04 A 2 A AA 2 0 1 2 4 A
Product Category
Product Style
D = A/C, Single Pkg., R-22
A = Style A
Product Identifier
Configuration Options (not required for all units)
These four digits will not be assigned until a quote is requested, or an order placed.
J = 13.0 SEER A/C
SS Drain Pan
CPC Controller, DFS, APS
Johnson Controller, DFS, APS
Nominal Cooling Capacity
Honeywell Controller, DFS, APS
036 = 3.0 Ton
048 = 4.0 Ton
060 = 5.0 Ton
Novar Controller, DFS, APS
Simplicity IntelliComfort Controller
Simplicity IntelliComfort Controller w/ModLinc
2" Pleated filters
Heat Type and Nominal Heat Capacity
BAS Ready Unit with Belimo Economizer
Any Combination of Additional Options that Don’t Have an Option Code Pre-assigned
C00 = Cooling Only. Suitable for Field
Installed Electric Heat
Product Generation
Gas Heat Options
2 = Second Generation
N04 = 40 MBH Output Aluminized Steel, 1 Stage (036)
N06 = 60 MBH Output Aluminized Steel, 1 Stage (048)
N08 = 80 MBH Output Aluminized Steel, 1 Stage
(036, 060, 072)
N10 = 100 MBH Output Aluminized Steel, 1 Stage
(048, 060, 072)
D06 = 60 MBH Output Aluminized Steel, 2 Stage
(036, 048, 060, 072)
D10 = 100 MBH Output Aluminized Steel, 2 Stage
(036*, 048, 060, 072)
S04 = 40 MBH Output Stainless Steel, 1 Stage (036)
S06 = 60 MBH Output Stainless Steel, 1 Stage (048)
S08 = 80 MBH Output Stainless Steel, 1 Stage
(036, 060, 072)
S10 = 100 MBH Output Stainless Steel, 1 Stage
(048, 060, 072)
T06 = 60 MBH Output Stainless Steel, 2 Stage
(036, 048, 060, 072)
T10 = 100 MBH Output Stainless Steel, 2 Stage
(036*, 048, 060, 072)
Additional Options
Standard Cabinet
Hinged Filter Door & Toolless Access Cabinet
AA = None
AB = Phase Monitor
AC = Coil Guard
AD = Dirty Filter Switch
AE = Phase Monitor & Coil Guard
AF = Phase Monitor & Dirty Filter Switch
AG = Coil Guard & Dirty Filter Switch
AH = Phase Monitor, Coil Guard & Dirty Filter Switch
AS = Bottom Drain Connection
RC = Coil Guard & American Flag
TA = Technicoat Condenser Coil
TJ = Technicoat Evaporator Coil
TS = Technicoat Evaporator and Condenser Coil
BA = Hinged Filter Door & Toolless Access Panels
BA = Hinged Filter Door & Toolless Access Panels
BB = Phase Monitor, Hinged Filter Door & Toolless
Access Panels
BC = Coil Guard, Hinged Filter Door & Toolless
Access Panels
BD = Dirty Filter Switch, Hinged Filter Door &
Toolless Access Panels
BE = Phase Monitor & Coil Guard, Hinged Filter
Door & Toolless Access Panels
BF = Phase Monitor & Dirty Filter Switch, Hinged
Filter Door & Toolless Access Panels
BG = Coil Guard & Dirty Filter Switch, Hinged Filter
Door & Toolless Access Panels
BH = Phase Monitor, Coil Guard & Dirty Filter Switch,
Hinged Filter Door & Toolless Access Panels
Electric Heat Options
E05 = 5 KW
E07 = 7 KW
E10 = 10 KW
E15 = 15 KW
E20 = 20 KW
E30 = 30 KW
ZZ = If desired option combination is not listed above, ZZ will be assigned and configuration options will be
located in digits 15-18.
Installation Options
*(D, T)10 = 92 MBH Output on 036 Models
Airflow
N = Belt Drive
P = Belt Drive/Single Input Economizer
R = Belt Drive/Motorized Damper
Voltage
1 = 208/230-1-60
2 = 208/230-3-60
4 = 460-3-60
5 = 575-3-60
A = No Options Installed
B = Option 1
C = Option 2
D = Options 1 & 2
E = Option 3
F = Option 4
G = Options 1 & 3
H = Options 1 & 4
J = Options 1, 2 & 3
K = Options 1, 2, & 4
L = Options 1,3 & 4
M = Options 1, 2, 3, & 4
N = Options 2 & 3
P = Options 2 & 4
Q = Options 2, 3, & 4
R = Options 3 & 4
S = Option 5
T = Options 1 & 5
U = Options 1, 3, & 5
V = Options 1, 4, & 5
W = Options 1, 3, 4, & 5
X = Options 3 & 5
Y = Options 4 & 5
Z = Options 3, 4 & 5
Options
1 = Disconnect
2 = Non-Pwr'd Conv. Outlet
3 = Smoke Detector S.A.
4 = Smoke Detector R.A.
5 = Pwr'd Conv. Outlet
Unitary Products Group
3
254596-YTG-A-0306
FEATURES
gas valve, if applicable, and the temperature limit
switch on gas heat units. The unit control board will
alarm on ignition failures, compressor lockouts and
repeated limit switch trips.
All models are available with a wide variety of factorymounted options such as stainless steel heat exchangers,
electric heaters, phase monitor, convenience outlet, dirty filter
switch, disconnect switch, smoke detectors, and coil guard to
make them suitable for almost every application.
All units are self-contained and assembled on full perimeter
base rails with forklift holes on three sides and holes for overhead rigging. Every unit is completely piped, wired, charged
and tested at the factory to simplify the field installation and to
provide years of dependable operation.
All models (including those with an economizer) are suitable
for either bottom or horizontal duct connections. For bottom
duct, remove the sheet metal panels from the supply and
return air openings through the base of the unit. For horizontal duct, remove the supply and return air panels on the rear
of the unit.
•
Nuisance Trip Protection- To prevent nuisance
trouble calls, the control board uses a “three strikes,
you’re out” philosophy. The high and low-pressure
switches and the freezestats must trip three times
within two hours before the unit control board will
lock out the compressor.
•
On Board Diagnostics - Each alarm will energize a
trouble light on the thermostat, if so equipped, and
flash an alarm code on the control board LED. Each
high and low-pressure switch alarm as well as each
freezestat alarm has its own flash code. The control
board saves the five most recent alarms in memory,
and these alarms can be reviewed at any time.
Alarms and programmed values are retained
through the loss of power.
All models are available with these “factory mounted” outdoor
air damper options:
All units have long lasting powder paint cabinets with 1000
hour salt spray test approval under ASTM-B117 procedures.
•
Single enthalpy economizer
All models are CSA listed.
•
Motorized outdoor air damper
•
Warranty - All models include a one-year limited parts
warranty on the complete unit. Compressors and electric
heater elements carry a five-year warranty. Gas heat
exchangers carry a 10-year parts warranty.
•
Gas Heat Operation - All single phase models with gas
heat have minimum annual fuel utilization efficiency
(AFUE) of 80%. All three phase models with gas heat
have minimum steady state efficiency of 80%. Each section includes a durable heat exchanger with aluminized
steel or optional stainless steel tubes, a redundant gas
valve, spark ignition, power venting, an ignition module
for 100% shut-off and all of the safety controls required
to meet the latest ANSI standards.
Supply air blowers are equipped with a belt drive that can be
adjusted to meet the exact requirements of the job.
All compressors are equipped with internal pressure relief.
Every refrigerant circuit includes a liquid line filter-drier, a high
pressure switch and a suction line with a freezestat and low
pressure/loss of charge switch to protect all system components.
•
Simplicity® Controls - Simplicity® control boards have
standardized a number of features previously available
only as options or by utilizing additional controls.
•
4
Low Ambient - An integrated low-ambient control
allows all units to operate in the cooling mode down
to 0ºF outdoor ambient without additional assistance. Optionally, the control board can be programmed to lockout the compressors when the
outdoor air temperature is low or when free cooling
is available.
•
Anti-Short Cycle Protection - To aid compressor
life, an anti-short cycle delay is incorporated into the
standard controls. Compressor reliability is further
ensured by programmable minimum run times. For
testing, the anti short cycle delay can be temporarily
overridden with the push of a button.
•
Fan Delays - Fan on and fan off delays are fully programmable and are independent of one another. All
units are programmed with default values based
upon their configuration of cooling and heat.
•
Safety Monitoring - The control board monitors the
high and low-pressure switches, the freezestats, the
The gas supply piping can be routed into the heating
compartment through a hole in the base pan of the unit
or through a knockout in the piping panel on the front of
the unit.
•
Electric Heat Operation - All electric heat models are
wired for a single power source and include a bank of
nickel chromium elements mounted at the discharge of
the supply air blower to provide a high velocity and uniform distribution of air across the heating elements.
Every element is fully protected against excessive temperature by thermal limit switches.
The power supply wiring can be routed into the control
box through a threaded pipe connection (field supplied)
in the base pan of the unit or through a knockout in the
wiring panel on the side of the unit.
•
BAS Controls - York’s Sunline™ series units offer factory
mounted BAS controls such as Simplicity® INTELLI-Comfort™, Novar, Honeywell, Johnson, and CPC.
Unitary Products Group
254596-YTG-A-0306
FIGURE 1 -
UNIT CUTAWAY
FACTORY-INSTALLED OPTIONS
•
•
SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZERS - Includes a slide-in / plug-in damper assembly
with fully modulating spring-return motor actuator capable of introducing up to 100% outdoor air with nominal
1% leakage type dampers.
FILTER OPTIONS - Standard units are shipped with 1”
throw-away filters installed. 2” pleated filters are offered
as a factory installed option.
•
The enthalpy system contains one sensor that monitors
the outdoor air and determines when the air is cool
enough and dry enough to provide free cooling.
CONVENIENCE OUTLET - This 110 volt outlet can be
“powered” by the unit with a stepdown transformer or the
unit may be ordered with a “non-powered” convenience
outlet that can be wired in the field.
•
DISCONNECT SWITCH - For gas heat units and cooling
units with electric heat, a HACR breaker sized to the unit
is provided. For cooling only units, a switch sized to the
largest electric heat available for the particular unit is
provided. Factory installed option only.
•
BAS - Building Automation System Controls
Simplicity® INTELLI-Comfort™ CONTROL - The York®
Simplicity® INTELLI-Comfort™ control is factory installed.
It includes a supply air sensor, a return air sensor, and an
outside air sensor. There are provisions for a field installed
dirty filter indicator switch, an air-proving switch, an Outside Air Humidity sensor, a Return Air Humidity sensor, an
Inside IAQ sensor, and an Outside Air IAQ sensor. Construction mode operation, 365-day real time clock with 7
day programming plus holiday scheduling is built-in. Two
different modes of demand ventilation are achieved
through the INTELLI-Comfort™ using CO2 sensors. It
uses an inside CO2 sensor to perform Demand Ventilation. It can also use an Outside CO2 sensor to perform
Differential Demand Ventilation. It uses a Patented Comfort Ventilation algorithm to provide comfortable ventilation
The rainhood is painted to match the basic unit and must
be field-assembled before installing.
•
MOTORIZED OUTDOOR AIR INTAKE DAMPER Includes a slide-in / plug-in damper assembly with a 2-position, spring return motor actuator which opens to a pre-set
position whenever the supply air blower is operating and
will drive fully closed when the blower unit shuts down.
The rain hood is painted to match the basic unit and
must be field assembled before installing.
•
PHENOLIC COATED EVAPORATOR AND CONDENSER COILS - Special coating process that utilizes
Technicoat 10-1TM processes. Coating is applied by total
immersion of the complete coil for maximum protection.
•
ELECTRIC HEATERS - Wired for single point power
supply. These nickel chromium heater elements are provided with limit and automatic reset capability to prevent
operation at excessive temperatures.
Unitary Products Group
5
254596-YTG-A-0306
air temperature. The patented economizer-loading algorithm will protect the equipment when harsh operating
conditions exist. Humidity in the occupied space or return
duct can be monitored and controlled via humidity sensors
and the on-board connection for hot gas re-heat system. It
uses the INTELLI-Start™ algorithm to maximize energy
savings by recovering the building from the Unoccupied
Setpoints to the Occupied Setpoints just in time for the
Occupied Time Period to begin. The Simplicity® INTELLIComfort™ balances space temperature, ventilation air
temperature, CO2 and humidity for ultimate comfort.
•
Simplicity® INTELLI-Comfort™ with MOD LINK CONTROL - The York® Simplicity® INTELLI-Comfort™ with
Mod Link control is factory installed. It includes all the
features of the INTELLI-Comfort™ control with an additional control to translate communications from MODBUS to the BACnet MSTP protocol.
•
Novar® BAS CONTROL - The Novar® ETC-3 building
automation system controller is factory installed.
Includes supply air sensor, return air sensor, dirty filter
indicator switch, and air proving switch.
•
JOHNSON CONTROLS BAS CONTROL - The Johnson
Control YK-UNT-1126 building automation system controller is factory installed. Includes supply air sensor,
return air sensor, dirty filter indicator switch, and air proving switch.
•
•
•
•
CPC BAS CONTROL - The Computer Process Controls
Model 810-3060 ARTC Advanced Rooftop building automation system controller is factory installed. Includes
supply air sensor, return air sensor, dirty filter indicator
switch and air proving switch.
STAINLESS STEEL HEAT EXCHANGER - For applications in corrosive environments, this option provides a
full stainless steel heat exchanger assembly.
•
STAINLESS STEEL DRAIN PAN - An optional rustproof stainless steel drain pan is available to provide
years of trouble-free operation in corrosive environments.
•
BOTTOM DRAIN CONNECTION - An optional bottom
drain connection is available for inside the curb connections for applications in cold environments to reduce
freezing drain lines.
•
PHASE MONITORS - Designed to prevent unit damage.
The phase monitor will shut the unit down in an out-ofphase condition.
•
DIRTY FILTER SWITCH - This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally high
pressure drop across the filters. Factory installed option
or field installed accessory.
•
HINGED FILTER DOOR/“TOOLLESS” BLOWER AND
ACCESS PANELS (not hinged) - This option allows for
easy access and maintenance.
NOTE:Knobs are shipped inside the unit to prevent shipping damage. These must be field installed for
tool-less operation.
FIELD-INSTALLED ACCESSORIES
•
HONEYWELL BAS CONTROL - The Honeywell
W7750C building automation system controller is factory
installed. Includes air supply sensor, return air sensor,
dirty filter indicator switch, and air proving switch.
COIL GUARD - Customers can purchase a coil guard kit
to protect the condenser coil from damage. This is not a
hail guard kit.
SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZERS - Includes a slide-in / plug-in damper assembly
with fully modulating spring-return motor actuator capable of introducing up to 100% outdoor air with nominal
1% leakage type dampers.
The enthalpy system contains one sensor that monitors
the outdoor air and determines when the air is cool
enough and dry enough to provide free cooling.
SMOKE DETECTORS - (supply air & return air) The
smoke detectors stop operation of the unit by interrupting
power to the control board if smoke is detected within the
air compartment.
Factory installed Smoke Detectors in the Return
Air, may be subjected to freezing temperatures
during "off" times due to Out Side Air infiltration.
These Smoke Detectors have an operational limit
of 32°F to 131°F. Smoke Detectors installed in
areas that could be out side those limitations will
have to be moved to prevent having false alarms.
6
•
The rainhood is painted to match the basic unit and must
be field-assembled before installing.
•
MOTORIZED OUTDOOR AIR INTAKE DAMPER Includes a slide-in / plug-in damper assembly with a 2position, spring return motor actuator which opens to
some pre-set position whenever the supply air blower is
operating and will drive fully closed when the blower unit
shuts down.
The rain hood is painted to match the basic unit and
must be field assembled before installing.
•
ELECTRIC HEATERS wired for single point power supply. These nickel chromium heater elements are provided with limit and automatic reset capability to prevent
operation at excessive temperatures.
Unitary Products Group
254596-YTG-A-0306
•
ROOF CURBS - Eight and fourteen-inch high roof curbs
provide a water-tight seal between the unit and the finished
roof. These full perimeter curbs meet the requirements of
the National Roofing Contractors Association (NRCA) and
are shipped knocked-down for field assembly.
•
BAROMETRIC RELIEF DAMPER - This damper accessory can be used to relieve internal building air pressure
on units with an economizer without power exhaust. This
accessory includes a rain hood, a bird screen and a fully
assembled damper. With bottom duct connections, the
damper should be mounted over the opening in the
return air panel. With horizontal ductwork, the accessory
should be mounted on the return air duct.
•
ENTHALPY ACCESSORY CONTROL KIT - This kit
contains the required components to convert a single
enthalpy economizer to dual enthalpy.
•
BURGLAR BARS - Mount in the supply and return
openings to prevent entry into the duct work.
•
FLUE EXHAUST EXTENSION KIT - In locations with
wind or weather conditions which may interfere with
proper exhausting of furnace combustion products, this
kit can be installed to prevent the flue exhaust from
entering nearby fresh air intakes.
•
CO2 SENSOR - Senses CO2 levels and automatically
overrides the economizer when levels rise above the
present limits.
•
COIL GUARD - Customers can purchase a coil guard kit
to protect the condenser coil from damage. This is not a
hail guard kit.
•
HAIL GUARD - Hail Guard kit is available to prevent unit
from hail damage. This is a sloped hood that fits above
the coil.
•
GAS PIPING KIT - This kit supplies all necessary fittings
and shut off valve.
Roof curbs are designed to fit inside the base rails of the
unit and include both a wood nailing strip and duct
hanger supports.
•
HIGH ALTITUDE NATURAL GAS - Burner orifices and
pilot orifices are provided for proper furnace operation at
altitudes up to 6,000 feet.
•
PROPANE - Burner orifices, pilot orifices and gas valve
parts are provided to convert a natural gas furnace to
propane.
•
HIGH ALTITUDE PROPANE - Burner orifices and pilot
orifices are provided for proper furnace operation at altitudes up to 6,000 feet. This accessory supplements the
basic propane conversion kit.
•
LOW NOX KIT - Required to reduce the emission of
nitrogen oxides below 40 nano grams per joule.
•
POWER EXHAUST - Our single input economizer
options are available with power exhaust. Whenever the
outdoor air intake dampers are opened for free cooling,
the exhaust fan will be energized to prevent the conditioned space from being over-pressurized during economizer operation.
The power exhaust option can only be used on bottom duct configurations.
TABLE 1: CAPACITY RATINGS - (ARI 210/240)1
MODEL
MBH
EER2
SEER3
CFM
SOUND
RATING
(Db)4
DJ036
DJ048
DJ060
35.8
46.5
56.5
11.65
11.75
11.15
13.50
13.45
13.40
1200
1600
1800
84
83
81
1. 80/67°F Indoor and 95°F outdoor.
2. EER = Energy Efficiency Ratio at full load - the cooling
capacity in Btu’s per hour (Btuh) divided by the power
input in watts, expressed in Btuh per watt (Btuh/watt).
3. SEER = Seasonal Energy Efficiency Ratio.
4. Rated in accordance with ARI 270 Standard.
TABLE 2: GAS HEAT RATINGS1
MODEL
MBH
INPUT
MBH
OUTPUT
AFUE
(%)
TEMP
RISE ºF
50
100
40
80
80.9
80.5
15 - 45
40 - 70
75
125
60
100
80.9
80.3
25 - 55
45 - 75
100
125
80
100
80.5
80.3
25 - 55
35 - 65
DJ036N04
DJ036N08
DJ048N06
DJ048N10
DJ060N08
DJ060N10
1. All units are single-stage heating.
TABLE 3: 2 STAGE GAS HEAT RATINGS
MODEL1
MBH INPUT
MBH OUTPUT
STEADY STATE EFFICIENCY
2ND STAGE
1ST STAGE 2ND STAGE 1ST STAGE 2ND STAGE 1ST STAGE
DJ036D06
DJ036D10
DJ048D06
DJ048D10
DJ060D06
DJ060D10
45
69
45
75
45
75
75
115
75
125
75
125
35.8
55.2
35.7
60.4
35.8
60.4
60.8
92
60.8
100.6
60.8
100.6
79.4
80.0
79.4
80.5
79.4
80.5
81.1
80.2
81.1
80.5
81.1
80.5
RISE
MIN. MAX.
35
55
25
45
35
45
70
90
70
75
70
75
MINIMUM HEATING
AIRFLOW (CFM)
790
950
790
1230
1010
1230
1. Models are 3Ø only.
Unitary Products Group
7
254596-YTG-A-0306
TABLE 4: DJ036 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET)
UNIT DESCRIPTION / MODEL
CONFIGURATION
Indoor Blower Speed (RPM)
Blower Static Pressure (IWG)
Airflow (CFM)
Blower Motor BHP
Octave Center Freq.
63
125
250
500
1000
2000
4000
8000
630
0.2
1116
0.41
Cooling
ID Blower
Operation2
Only (dB)
(dB)
80
82
76
77
56
59
50
50
40
43
41
42
41
41
45
45
DJ036 / 3 Ton / Belt Drive
Horizontal Ducted Inlet
631
879
885
0.3
0.2
0.7
928
1979
1020
0.37
0.76
0.53
Cooling
Cooling
Cooling
ID Blower
ID Blower
ID Blower
Operation2
Operation2
Operation2
Only (dB)
Only (dB)
Only (dB)
(dB)
(dB)
(dB)
80
82
78
83
81
85
76
77
82
83
81
82
56
60
60
61
58
60
49
50
54
54
51
52
39
42
49
50
44
45
40
42
49
49
43
44
41
41
49
49
41
41
45
45
47
47
45
45
1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .
2. Cooling Operation – ID blower, compressor and outdoor fan operating.
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
4. Test duct termination is flush with reverberation room wall.
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.
TABLE 5: DJ036 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED DISCHARGE)
UNIT DESCRIPTION / MODEL
CONFIGURATION
Indoor Blower Speed (RPM)
Blower Static Pressure (IWG)
Airflow (CFM)
Blower Motor BHP
Octave Center Freq.
63
125
250
500
1000
2000
4000
8000
630
0.2
1116
0.41
Cooling
ID Blower
Operation2
Only (dB)
(dB)
80
84
74
77
58
61
48
51
41
45
39
41
41
41
45
45
DJ036 / 3 Ton / Belt Drive
Horizontal Ducted Discharge
631
879
885
0.3
0.2
0.7
928
1979
1020
0.37
0.76
0.53
Cooling
Cooling
Cooling
ID Blower
ID Blower
ID Blower
Operation2
Operation2
Operation2
Only (dB)
Only (dB)
Only (dB)
(dB)
(dB)
(dB)
80
83
85
87
84
87
74
76
80
82
80
83
58
61
68
68
63
65
47
50
58
58
53
54
39
43
55
55
49
50
37
39
53
53
46
47
38
38
55
55
49
49
44
44
52
53
47
47
1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .
2. Cooling Operation – ID blower, compressor and outdoor fan operating.
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
4. Test duct termination is flush with reverberation room wall.
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.
8
Unitary Products Group
254596-YTG-A-0306
TABLE 6: DJ036 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET)
UNIT DESCRIPTION / MODEL
CONFIGURATION
Indoor Blower Speed (RPM)
Blower Static Pressure (IWG)
Airflow (CFM)
Blower Motor BHP
Octave Center Freq.
63
125
250
500
1000
2000
4000
8000
632
0.2
1069
0.36
Cooling
ID Blower
Operation2
Only (dB)
(dB)
78
82
70
75
55
60
47
50
40
43
37
40
36
37
44
44
DJ036 / 3 Ton / Belt Drive
Vertical Ducted Inlet
632
881
883
0.3
0.2
0.7
870
1903
917
0.33
0.71
0.49
Cooling
Cooling
Cooling
ID Blower
ID Blower
ID Blower
Operation2
Operation2
Operation2
Only (dB)
Only (dB)
Only (dB)
(dB)
(dB)
(dB)
78
82
80
85
80
84
70
74
71
80
71
79
55
60
59
61
58
62
47
50
52
53
49
52
39
43
50
51
45
46
37
39
45
46
41
43
36
37
45
46
40
40
44
44
45
47
44
44
1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .
2. Cooling Operation – ID blower, compressor and outdoor fan operating.
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
4. Test duct termination is flush with reverberation room wall.
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.
TABLE 7: DJ036 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED DISCHARGE)
UNIT DESCRIPTION / MODEL
CONFIGURATION
Indoor Blower Speed (RPM)
Blower Static Pressure (IWG)
Airflow (CFM)
Blower Motor BHP
Octave Center Freq.
63
125
250
500
1000
2000
4000
8000
632
0.2
1069
0.36
Cooling
ID Blower
Operation2
Only (dB)
(dB)
80
83
78
79
55
60
48
51
41
44
37
40
38
39
44
45
DJ036 / 3 Ton / Belt Drive
Vertical Ducted Discharge
632
881
883
0.3
0.2
0.7
870
1903
917
0.33
0.71
0.49
Cooling
Cooling
Cooling
ID Blower
ID Blower
ID Blower
Operation2
Operation2
Operation2
Only (dB)
Only (dB)
Only (dB)
(dB)
(dB)
(dB)
80
83
83
86
82
85
77
78
80
83
79
82
54
59
63
63
58
62
46
50
58
59
52
53
39
43
54
55
48
49
35
38
50
50
42
44
36
37
52
53
44
44
44
44
49
50
45
45
1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .
2. Cooling Operation – ID blower, compressor and outdoor fan operating.
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
4. Test duct termination is flush with reverberation room wall.
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.
Unitary Products Group
9
254596-YTG-A-0306
TABLE 8: DJ048 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET)
UNIT DESCRIPTION / MODEL
CONFIGURATION
Indoor Blower Speed (RPM)
Blower Static Pressure (IWG)
Airflow (CFM)
Blower Motor BHP
Octave Center Freq.
63
125
250
500
1000
2000
4000
8000
766
0.2
1484
0.67
Cooling
ID Blower
Operation2
Only (dB)
(dB)
74
97
70
86
53
58
49
55
42
42
40
44
38
44
42
43
DJ048 / 4 Ton / Belt Drive
Horizontal Ducted Inlet
769
1077
1087
0.5
0.4
1.0
993
2270
1406
1.24
0.90
0.54
Cooling
Cooling
Cooling
ID Blower
ID Blower
ID Blower
Operation2
Operation2
Operation2
Only (dB)
Only (dB)
Only (dB)
(dB)
(dB)
(dB)
74
95
77
90
77
90
69
86
73
78
72
77
52
57
60
61
58
61
47
54
54
56
51
53
38
39
50
55
45
45
38
43
48
51
45
46
36
41
48
52
43
45
42
44
45
48
44
45
1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .
2. Cooling Operation – ID blower, compressor and outdoor fan operating.
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
4. Test duct termination is flush with reverberation room wall.
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.
TABLE 9: DJ048 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED DISCHARGE)
UNIT DESCRIPTION / MODEL
CONFIGURATION
Indoor Blower Speed (RPM)
Blower Static Pressure (IWG)
Airflow (CFM)
Blower Motor BHP
Octave Center Freq.
63
125
250
500
1000
2000
4000
8000
766
0.2
1484
0.67
Cooling
ID Blower
Operation2
Only (dB)
(dB)
77
97
72
86
60
62
53
56
47
47
45
46
46
47
47
47
DJ048 / 4 Ton / Belt Drive
Horizontal Ducted Discharge
769
1077
1087
0.5
0.4
1.0
993
2270
1406
0.54
1.24
0.90
Cooling
Cooling
Cooling
ID Blower
ID Blower
ID Blower
Operation2
Operation2
Operation2
Only (dB)
Only (dB)
Only (dB)
(dB)
(dB)
(dB)
75
95
84
91
82
91
69
85
81
83
78
80
57
59
71
71
66
67
49
54
60
61
55
56
42
43
58
59
52
52
40
43
54
55
50
50
40
42
57
58
52
52
45
45
54
54
48
49
1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .
2. Cooling Operation – ID blower, compressor and outdoor fan operating.
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
4. Test duct termination is flush with reverberation room wall.
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.
10
Unitary Products Group
254596-YTG-A-0306
TABLE 10: DJ048 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET)
UNIT DESCRIPTION / MODEL
CONFIGURATION
Indoor Blower Speed (RPM)
Blower Static Pressure (IWG)
Airflow (CFM)
Blower Motor BHP
Octave Center Freq.
63
125
250
500
1000
2000
4000
8000
791
0.2
1408
0.54
Cooling
ID Blower
Operation2
Only (dB)
(dB)
76
95
68
84
54
57
48
53
43
44
40
43
38
43
43
43
DJ048 / 4 Ton / Belt Drive
Vertical Ducted Inlet
794
1084
1095
0.5
0.2
1.0
1000
2336
1275
0.42
1.12
0.73
Cooling
Cooling
Cooling
ID Blower
ID Blower
ID Blower
Operation2
Operation2
Operation2
Only (dB)
Only (dB)
Only (dB)
(dB)
(dB)
(dB)
77
93
80
91
79
91
67
82
76
84
73
80
52
56
63
61
57
59
46
53
54
57
50
53
40
41
52
52
47
47
38
42
49
51
44
46
36
40
49
54
43
45
43
43
45
47
44
44
1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .
2. Cooling Operation – ID blower, compressor and outdoor fan operating.
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
4. Test duct termination is flush with reverberation room wall.
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.
TABLE 11: DJ048 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED DISCHARGE)
UNIT DESCRIPTION / MODEL
CONFIGURATION
Indoor Blower Speed (RPM)
Blower Static Pressure (IWG)
Airflow (CFM)
Blower Motor BHP
Octave Center Freq.
63
125
250
500
1000
2000
4000
8000
791
0.2
1408
0.54
Cooling
ID Blower
Operation2
Only (dB)
(dB)
78
95
73
84
56
58
51
54
46
46
42
44
43
45
44
44
DJ048 / 4 Ton / Belt Drive
Vertical Ducted Discharge
794
1084
1095
0.5
0.2
1.0
1000
2336
1275
0.42
1.12
0.73
Cooling
Cooling
Cooling
ID Blower
ID Blower
ID Blower
Operation2
Operation2
Operation2
Only (dB)
Only (dB)
Only (dB)
(dB)
(dB)
(dB)
77
93
85
92
82
91
72
82
84
87
78
82
53
56
68
68
60
61
48
53
61
62
54
55
43
44
57
57
50
50
38
42
53
54
46
48
39
41
55
57
49
50
43
43
52
52
46
47
1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .
2. Cooling Operation – ID blower, compressor and outdoor fan operating.
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
4. Test duct termination is flush with reverberation room wall.
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.
Unitary Products Group
11
254596-YTG-A-0306
TABLE 12: DJ060 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET)
81,7'(6&5,37,2102'(/
&21),*85$7,21
,QGRRU%ORZHU6SHHG530
%ORZHU6WDWLF3UHVVXUH,:*
$LUIORZ&)0
%ORZHU0RWRU%+3
2FWDYH&HQWHU)UHT
&RROLQJ
,'%ORZHU
2SHUDWLRQ
2QO\G%
G%
'-7RQ%HOW'ULYH
+RUL]RQWDO'XFWHG,QOHW
&RROLQJ
&RROLQJ
&RROLQJ
,'%ORZHU
,'%ORZHU
,'%ORZHU
2SHUDWLRQ
2SHUDWLRQ
2SHUDWLRQ
2QO\G%
2QO\G%
2QO\G%
G%
G%
G%
5
60
5
53
50
4
4
7HVWHGLQDFFRUGDQFHZLWK$5,6WDQGDUG5HIHUWR6WDQGDUGIRU6RXQG5DWLQJRI'XFWHG$LU0RYLQJDQG&RQGLWLRQLQJ(TXLSPHQW &RROLQJ2SHUDWLRQ±,'EORZHUFRPSUHVVRUDQGRXWGRRUIDQRSHUDWLQJ
7HVW'XFW'LPHQVLRQLQZLGH[LQKLJK[IWORQJP[P[P
7HVWGXFWWHUPLQDWLRQLVIOXVKZLWKUHYHUEHUDWLRQURRPZDOO
'XFWHQGVRXQGUHIOHFWLRQFRUUHFWLRQG%DWNNN+]
TABLE 13: DJ060 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED DISCHARGE)
81,7'(6&5,37,2102'(/
&21),*85$7,21
,QGRRU%ORZHU6SHHG530
%ORZHU6WDWLF3UHVVXUH,:*
$LUIORZ&)0
%ORZHU0RWRU%+3
2FWDYH&HQWHU)UHT
&RROLQJ
,'%ORZHU
2SHUDWLRQ
2QO\G%
G%
'-7RQ%HOW'ULYH
+RUL]RQWDO'XFWHG'LVFKDUJH
&RROLQJ
&RROLQJ
&RROLQJ
,'%ORZHU
,'%ORZHU
,'%ORZHU
2SHUDWLRQ
2SHUDWLRQ
2SHUDWLRQ
2QO\G%
2QO\G%
2QO\G%
G%
G%
G%
7HVWHGLQDFFRUGDQFHZLWK$5,6WDQGDUG5HIHUWR6WDQGDUGIRU6RXQG5DWLQJRI'XFWHG$LU0RYLQJDQG&RQGLWLRQLQJ(TXLSPHQW &RROLQJ2SHUDWLRQ±,'EORZHUFRPSUHVVRUDQGRXWGRRUIDQRSHUDWLQJ
7HVW'XFW'LPHQVLRQLQZLGH[LQKLJK[IWORQJP[P[P
7HVWGXFWWHUPLQDWLRQLVIOXVKZLWKUHYHUEHUDWLRQURRPZDOO
'XFWHQGVRXQGUHIOHFWLRQFRUUHFWLRQG%DWNNN+]
12
Unitary Products Group
254596-YTG-A-0306
TABLE 14: DJ060 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET)
81,7'(6&5,37,2102'(/
&21),*85$7,21
,QGRRU%ORZHU6SHHG530
%ORZHU6WDWLF3UHVVXUH,:*
$LUIORZ&)0
%ORZHU0RWRU%+3
2FWDYH&HQWHU)UHT
&RROLQJ
,'%ORZHU
2SHUDWLRQ
2QO\G%
G%
'-7RQ%HOW'ULYH
9HUWLFDO'XFWHG,QOHW
&RROLQJ
&RROLQJ
&RROLQJ
,'%ORZHU
,'%ORZHU
,'%ORZHU
2SHUDWLRQ
2SHUDWLRQ
2SHUDWLRQ
2QO\G%
2QO\G%
2QO\G%
G%
G%
G%
7HVWHGLQDFFRUGDQFHZLWK$5,6WDQGDUG5HIHUWR6WDQGDUGIRU6RXQG5DWLQJRI'XFWHG$LU0RYLQJDQG&RQGLWLRQLQJ(TXLSPHQW &RROLQJ2SHUDWLRQ±,'EORZHUFRPSUHVVRUDQGRXWGRRUIDQRSHUDWLQJ
7HVW'XFW'LPHQVLRQLQZLGH[LQKLJK[IWORQJP[P[P
7HVWGXFWWHUPLQDWLRQLVIOXVKZLWKUHYHUEHUDWLRQURRPZDOO
'XFWHQGVRXQGUHIOHFWLRQFRUUHFWLRQG%DWNNN+]
TABLE 15: DJ060 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED DISCHARGE)
81,7'(6&5,37,2102'(/
&21),*85$7,21
,QGRRU%ORZHU6SHHG530
%ORZHU6WDWLF3UHVVXUH,:*
$LUIORZ&)0
%ORZHU0RWRU%+3
2FWDYH&HQWHU)UHT
&RROLQJ
,'%ORZHU
2SHUDWLRQ
2QO\G%
G%
'-7RQ%HOW'ULYH
9HUWLFDO'XFWHG'LVFKDUJH
&RROLQJ
&RROLQJ
&RROLQJ
,'%ORZHU
,'%ORZHU
,'%ORZHU
2SHUDWLRQ
2SHUDWLRQ
2SHUDWLRQ
2QO\G%
2QO\G%
2QO\G%
G%
G%
G%
7HVWHGLQDFFRUGDQFHZLWK$5,6WDQGDUG5HIHUWR6WDQGDUGIRU6RXQG5DWLQJRI'XFWHG$LU0RYLQJDQG&RQGLWLRQLQJ(TXLSPHQW &RROLQJ2SHUDWLRQ±,'EORZHUFRPSUHVVRUDQGRXWGRRUIDQRSHUDWLQJ
7HVW'XFW'LPHQVLRQLQZLGH[LQKLJK[IWORQJP[P[P
7HVWGXFWWHUPLQDWLRQLVIOXVKZLWKUHYHUEHUDWLRQURRPZDOO
'XFWHQGVRXQGUHIOHFWLRQFRUUHFWLRQG%DWNNN+]
Unitary Products Group
13
254596-YTG-A-0306
TABLE 16: DJ036 COOLING CAPACITIES (3 TON)
Temperature of Air on Condenser Coil
Air on Evaporator Coil
CFM
900
1050
1200
1350
1500
900
1050
1200
1350
1500
900
1050
1200
1350
1500
75°F
85°F
(MBH)1
Sensible Capacity (MBH)1
Return Dry Bulb (°F)
WB
(°F)
Total
Cap.1
(MBH)
Total2
Total2
Input
(kW)
86
83
80
77
74
71
68
86
83
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
44
42
40
39
44
42
40
39
44
43
40
39
45
43
41
40
46
44
42
41
2.3
2.3
2.3
2.3
2.2
2.3
2.3
2.3
2.2
2.3
2.3
2.3
2.2
2.3
2.3
2.3
2.3
2.3
2.3
2.3
24
30
40
39
26
33
40
39
28
35
40
39
30
37
41
40
32
40
42
41
21
28
35
37
23
30
38
38
25
32
40
39
26
33
41
40
27
35
42
41
16
23
30
32
17
24
32
34
18
25
33
36
18
25
35
36
18
26
37
36
14
20
28
30
14
21
29
31
14
21
30
32
14
21
31
32
14
22
33
32
18
25
27
18
26
28
18
26
29
18
27
28
17
28
27
15
23
25
15
23
25
14
23
25
14
23
24
13
24
23
41
38
35
35
42
39
35
35
43
40
36
36
43
40
37
36
44
41
37
37
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
23
29
35
35
25
31
35
35
27
34
36
36
29
36
37
36
31
39
37
37
20
26
32
34
22
28
34
35
24
31
36
36
25
32
37
36
27
34
37
37
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
38
35
30
30
39
36
31
31
41
37
32
32
41
37
32
33
42
38
33
33
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
21
27
30
30
24
30
31
31
26
33
32
32
28
35
32
33
30
38
33
33
19
24
29
30
21
27
31
31
23
30
32
32
24
31
32
33
26
33
33
33
14
19
24
25
15
21
26
27
16
23
29
29
16
23
28
29
17
24
28
29
11
17
22
22
12
18
23
24
12
19
25
25
12
19
24
25
12
20
24
24
14
19
19
15
20
21
16
22
22
15
20
21
15
19
20
12
17
17
12
17
18
12
18
18
11
16
17
11
15
15
35
31
27
27
36
32
28
28
37
33
29
29
37
33
29
29
37
33
29
29
3.0
2.9
3.0
3.0
3.0
2.9
2.9
2.9
2.9
2.8
2.9
2.9
3.0
2.9
2.9
2.9
3.1
2.9
3.0
3.0
20
25
27
27
22
28
28
28
25
31
29
29
27
32
29
29
28
33
29
29
17
23
26
27
19
25
28
28
21
28
29
29
23
29
29
29
24
31
29
29
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
32
27
24
25
32
28
25
25
33
29
25
26
33
29
25
26
33
28
25
25
3.3
3.1
3.2
3.2
3.3
3.0
3.1
3.1
3.2
3.0
3.1
3.1
3.3
3.1
3.2
3.2
3.4
3.2
3.3
3.3
18
23
24
25
21
26
25
25
23
29
25
26
25
29
25
26
27
28
25
25
16
21
23
25
18
23
24
25
20
26
25
26
21
27
25
26
22
28
25
25
19
25
33
35
20
27
35
37
21
28
37
39
22
29
39
40
23
31
42
41
95°F
16
22
27
27
18
24
30
30
19
26
32
32
20
27
32
33
21
29
33
33
115°F
13
18
21
23
15
20
23
25
16
22
25
27
17
23
25
26
18
25
25
25
11
16
18
20
12
17
20
22
13
19
22
24
13
19
21
22
13
20
20
21
8
13
16
17
9
14
17
19
9
15
18
20
9
15
17
18
9
16
16
16
11
13
15
11
14
16
12
15
17
11
13
14
11
11
12
8
11
12
8
11
13
8
11
13
8
9
10
7
7
8
28
24
21
22
29
24
21
22
29
25
22
22
29
24
21
22
28
24
21
22
3.7
3.3
3.5
3.5
3.5
3.2
3.4
3.4
3.4
3.1
3.3
3.3
3.6
3.2
3.4
3.4
3.8
3.4
3.6
3.6
17
22
21
22
19
24
21
22
21
25
22
22
23
24
21
22
25
24
21
22
14
19
20
22
16
22
21
22
18
24
22
22
19
24
21
22
20
24
21
22
Sensible Capacity
Return Dry Bulb (°F)
Total
Cap.1 Input
(MBH) (kW)
80
18
24
30
31
19
25
32
33
20
27
34
36
21
28
36
36
22
30
37
37
105°F
15
20
24
25
16
22
26
27
18
24
29
30
19
25
29
30
20
27
29
29
125°F
12
17
18
20
13
18
20
22
14
20
22
22
15
21
21
22
16
23
21
22
77
74
71
68
15
21
27
28
16
22
29
30
17
24
31
32
17
24
32
32
18
25
33
32
12
18
25
26
13
19
26
27
13
20
27
29
13
20
28
28
13
21
28
28
16
22
23
16
23
24
17
24
25
16
24
24
16
24
23
13
20
21
13
20
21
13
20
22
12
20
20
12
19
19
12
18
21
22
13
19
23
24
14
21
25
26
15
21
25
26
15
22
24
25
10
15
19
20
10
16
20
21
11
17
22
23
11
17
21
22
11
18
20
20
12
16
17
13
17
18
14
18
19
13
17
18
13
15
16
10
14
15
10
14
15
10
15
16
9
13
14
9
11
11
9
14
15
18
10
15
17
19
11
17
18
21
11
17
17
19
11
18
16
17
7
11
13
15
7
12
14
16
7
13
15
18
7
13
13
15
7
14
12
13
9
10
13
9
11
13
10
11
14
10
9
11
9
7
8
6
8
10
6
8
10
6
8
11
6
5
7
5
3
4
1. The capacities are gross ratings. For net capacity, deduct indoor blower motor, MBH=3.415 x kW. Refer to the appropriate Blower Performance table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
14
Unitary Products Group
254596-YTG-A-0306
TABLE 17: DJ048 COOLING CAPACITIES (4 TON)
Temperature of Air on Condenser Coil
Air on Evaporator Coil
CFM
1200
1400
1600
1800
2000
1200
1400
1600
1800
2000
1200
1400
1600
1800
2000
75°F
85°F
(MBH)1
Sensible Capacity (MBH)1
Return Dry Bulb (°F)
WB
(°F)
Total
Cap.1
(MBH)
Total2
Total2
Input
(kW)
86
83
80
77
74
71
68
86
83
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
58
57
53
51
58
56
53
51
57
56
53
51
57
56
53
51
57
55
52
50
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
32
43
53
51
34
45
53
51
36
48
53
51
39
52
53
51
41
55
52
50
28
39
47
51
30
41
50
51
32
43
53
51
33
46
53
51
35
48
52
50
22
32
40
45
22
33
41
47
22
34
43
48
23
35
45
46
23
36
46
44
18
29
37
42
18
29
37
43
18
29
38
43
17
30
39
41
17
30
40
38
26
33
38
25
33
39
25
33
39
24
34
36
24
34
32
22
30
35
21
29
34
20
29
34
19
29
30
18
28
26
54
51
47
46
55
52
48
46
55
52
48
47
55
52
48
47
55
52
48
46
3.1
3.1
3.0
3.0
3.1
3.1
3.0
3.0
3.1
3.1
3.1
3.0
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
30
40
47
46
33
43
48
46
36
46
48
47
38
49
48
47
41
52
48
46
27
36
44
46
29
39
46
46
31
42
48
47
33
44
48
47
35
47
48
46
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
50
45
41
40
52
47
42
42
54
49
44
43
53
48
44
43
53
48
43
42
3.3
3.4
3.3
3.3
3.4
3.4
3.3
3.3
3.4
3.4
3.3
3.3
3.4
3.4
3.3
3.3
3.4
3.4
3.3
3.3
29
37
41
40
32
41
42
42
35
45
44
43
38
46
44
43
41
48
43
42
25
33
41
40
28
37
42
42
30
40
44
43
33
43
44
43
35
46
43
42
18
27
34
33
20
29
37
36
21
31
39
39
22
32
38
38
23
34
37
37
15
23
31
30
16
25
33
32
16
26
35
34
17
27
33
32
17
28
31
31
20
27
26
20
29
28
21
30
29
22
28
27
22
25
25
16
24
23
16
24
24
17
25
25
16
22
22
16
19
19
45
39
36
35
47
41
37
37
49
43
39
39
49
43
39
38
48
42
38
38
3.7
3.7
3.6
3.6
3.7
3.7
3.6
3.6
3.7
3.7
3.6
3.6
3.7
3.7
3.6
3.7
3.7
3.7
3.7
3.7
27
34
36
35
30
38
37
37
33
41
39
39
36
42
39
38
39
42
38
38
23
31
36
35
26
34
37
37
28
37
39
39
31
39
39
38
33
41
38
38
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
40
34
31
30
42
36
32
32
45
38
34
34
44
37
34
33
43
36
33
33
4.0
3.9
3.9
3.9
4.0
4.0
3.9
3.9
4.0
4.0
3.9
4.0
4.0
4.0
4.0
4.0
4.1
4.0
4.0
4.0
25
32
31
30
28
35
32
32
31
38
34
34
34
37
34
33
37
36
33
33
21
28
31
30
24
32
32
32
27
35
34
34
29
36
34
33
31
36
33
33
25
36
44
49
26
37
46
51
27
39
47
53
28
40
50
52
29
42
52
50
95°F
22
30
37
37
24
33
41
40
26
35
44
43
27
38
44
43
29
40
43
42
115°F
18
25
28
28
20
28
31
31
22
30
34
34
24
33
34
33
25
35
33
33
14
21
25
24
16
24
27
27
17
26
30
29
18
27
28
28
19
29
27
27
11
18
21
21
12
20
23
23
13
21
25
25
13
22
23
23
13
23
21
21
15
18
17
16
19
19
16
20
20
17
18
17
17
15
15
11
14
14
11
15
15
12
16
15
11
12
12
11
9
9
35
28
26
25
38
30
28
27
40
32
29
29
39
31
29
29
39
31
28
28
4.3
4.2
4.2
4.2
4.3
4.3
4.2
4.3
4.3
4.3
4.2
4.3
4.4
4.3
4.3
4.3
4.4
4.3
4.3
4.3
23
28
26
25
26
30
28
27
29
32
29
29
32
31
29
29
35
31
28
28
19
26
26
25
22
29
28
27
25
32
29
29
27
31
29
29
29
31
28
28
Sensible Capacity
Return Dry Bulb (°F)
Total
Cap.1 Input
(MBH) (kW)
80
23
33
41
43
25
35
43
45
26
37
46
48
28
39
47
47
29
41
48
46
105°F
20
27
33
32
22
30
36
35
24
33
39
39
25
35
39
38
27
37
38
38
125°F
16
22
23
23
18
25
26
26
20
28
29
29
22
30
29
29
23
31
28
28
77
74
71
68
20
29
37
39
21
31
39
41
22
32
41
43
22
34
41
42
23
35
42
40
17
26
34
36
17
27
35
37
17
28
36
39
17
28
36
37
17
29
36
34
23
30
32
23
31
33
23
32
34
23
31
31
23
30
28
19
27
29
19
27
29
18
27
29
18
25
26
17
24
23
16
24
29
29
18
26
32
31
19
28
34
34
20
30
33
33
21
31
32
32
13
21
26
25
14
22
28
27
14
24
30
29
15
24
28
27
15
25
26
26
17
22
22
18
24
23
19
25
25
19
23
22
19
20
20
14
19
19
14
20
19
14
20
20
14
17
17
14
14
14
13
19
20
20
14
21
22
22
15
23
25
24
16
25
23
23
17
27
22
22
9
15
16
16
10
17
18
18
11
19
20
20
11
20
18
18
11
21
16
16
12
13
13
13
14
14
14
15
15
14
13
13
15
10
10
9
10
9
9
10
10
9
11
10
9
8
7
9
4
4
1. The capacities are gross ratings. For net capacity, deduct indoor blower motor, MBH=3.415 x kW. Refer to the appropriate Blower
Performance table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Unitary Products Group
15
254596-YTG-A-0306
TABLE 18: DJ060 COOLING CAPACITIES (5 TON)
Temperature of Air on Condenser Coil
Air on Evaporator Coil
CFM
1600
1800
2000
2250
2500
1600
1800
2000
2250
2500
1600
1800
2000
2250
2500
75°F
85°F
(MBH)1
Sensible Capacity (MBH)1
Return Dry Bulb (°F)
WB
(°F)
Total
Cap.1
(MBH)
Total2
Total2
Input
(kW)
86
83
80
77
74
71
68
86
83
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
73
65
58
55
76
67
60
57
79
70
63
60
80
70
63
60
80
70
63
60
3.4
3.4
3.4
3.4
3.4
3.5
3.4
3.4
3.4
3.5
3.4
3.4
3.4
3.5
3.4
3.4
3.4
3.5
3.4
3.4
41
50
58
55
45
54
60
57
48
58
63
60
53
64
63
60
57
70
63
60
37
45
56
56
40
48
59
58
43
52
63
60
46
56
63
60
50
60
63
60
29
37
47
49
30
38
50
51
31
40
52
54
33
43
54
53
35
45
56
52
24
32
43
45
25
33
45
46
25
34
46
48
26
36
47
46
27
38
48
45
28
39
40
28
39
41
28
40
42
29
41
40
30
41
37
24
34
36
23
34
36
23
34
36
23
34
33
23
33
30
67
60
54
52
69
62
56
54
72
64
58
56
72
65
58
56
73
65
59
57
3.9
3.9
3.8
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
39
47
54
52
42
52
56
54
46
56
58
56
50
61
58
56
54
65
59
57
34
43
52
52
37
47
55
54
40
50
58
56
43
54
58
56
46
58
59
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
61
56
51
50
62
57
52
51
64
59
53
52
65
59
54
53
66
60
55
54
4.4
4.4
4.3
4.4
4.4
4.4
4.3
4.4
4.4
4.4
4.3
4.4
4.5
4.4
4.3
4.4
4.5
4.4
4.4
4.4
36
45
51
50
40
50
52
51
44
55
53
52
47
57
54
53
51
60
55
54
31
41
49
48
35
45
51
50
38
49
53
52
41
52
54
53
43
55
55
54
23
32
40
40
25
35
44
43
26
37
47
46
27
39
47
46
28
40
47
46
19
28
36
36
20
30
38
38
21
31
41
41
21
32
40
40
21
33
40
39
24
32
31
25
33
33
26
35
35
26
34
33
26
32
31
19
27
27
20
28
28
20
29
29
19
27
26
18
25
24
57
51
47
47
58
52
48
48
59
53
48
48
60
54
49
49
60
54
49
49
5.0
4.9
4.9
4.9
5.0
4.9
4.9
4.9
5.0
4.9
4.9
4.9
5.0
4.9
4.9
5.0
5.1
5.0
4.9
5.0
33
43
47
47
37
47
48
48
41
51
48
48
44
53
49
49
47
54
49
49
29
38
45
45
32
42
47
47
35
46
48
48
37
49
49
49
39
52
49
49
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
53
47
43
44
53
47
43
44
54
48
44
45
54
48
44
45
55
48
44
45
5.6
5.5
5.4
5.5
5.6
5.5
5.4
5.5
5.5
5.5
5.4
5.5
5.6
5.5
5.4
5.5
5.6
5.5
5.5
5.6
30
40
43
44
34
44
43
44
37
48
44
45
40
48
44
45
43
48
44
45
26
36
41
41
29
40
42
43
32
44
44
45
34
46
44
45
36
48
44
45
33
41
52
53
35
43
55
56
37
46
58
60
39
49
60
60
42
53
63
60
95°F
27
36
44
44
30
40
49
48
32
43
53
52
34
46
54
53
36
48
55
54
115°F
21
32
36
37
24
35
40
41
26
38
44
45
27
40
44
45
28
42
44
45
17
28
32
33
19
30
35
36
20
32
38
39
20
33
37
38
21
34
37
38
13
23
28
29
14
25
30
31
14
26
32
33
14
27
31
32
13
27
29
30
19
24
24
20
25
26
21
26
27
20
24
25
20
22
23
15
19
20
15
20
21
15
20
21
13
17
18
12
14
15
49
42
39
41
49
42
39
41
49
42
39
41
49
42
39
41
49
42
39
41
6.1
6.0
6.0
6.1
6.1
6.0
6.0
6.1
6.1
6.0
5.9
6.1
6.1
6.0
6.0
6.1
6.2
6.1
6.0
6.2
27
38
39
41
31
41
39
41
34
42
39
41
37
42
39
41
39
42
39
41
23
34
37
38
26
38
38
39
28
41
39
41
30
42
39
41
32
42
39
41
Sensible Capacity
Return Dry Bulb (°F)
Total
Cap.1 Input
(MBH) (kW)
80
30
39
48
49
32
42
52
52
34
45
55
56
37
47
57
56
39
50
59
57
105°F
24
34
40
41
27
37
44
44
29
41
48
48
30
43
49
49
32
45
49
49
125°F
19
29
32
34
21
33
36
37
23
36
39
41
24
37
39
41
25
39
39
41
77
74
71
68
26
34
44
44
27
37
47
47
29
39
49
50
30
41
50
50
31
43
51
49
21
30
39
40
22
32
41
42
23
33
44
44
23
34
44
43
24
35
44
42
26
35
36
26
36
37
27
38
38
27
37
36
28
36
34
22
31
31
21
31
32
21
32
33
21
30
30
20
29
27
20
30
36
36
22
32
39
39
23
35
42
43
24
36
42
42
25
37
42
42
16
26
32
32
17
27
34
34
17
29
36
37
17
29
35
36
17
30
34
34
21
28
28
22
29
29
23
31
31
23
29
29
23
27
27
17
23
24
17
24
24
17
25
25
16
22
22
15
20
20
14
25
28
29
16
27
31
32
17
30
33
35
17
31
32
34
17
31
32
33
10
21
24
25
10
22
26
27
11
24
27
29
10
24
26
27
10
24
24
26
17
20
21
17
21
22
18
22
23
17
19
21
16
17
18
12
15
17
12
16
17
12
16
17
11
13
14
9
9
11
1. The capacities are gross ratings. For net capacity, deduct indoor blower motor, MBH=3.415 x kW. Refer to the appropriate Blower Performance table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
16
Unitary Products Group
254596-YTG-A-0306
TABLE 19: SUPPLY AIR BLOWER PERFORMANCE (DJ036 BELT DRIVE) - SIDE DUCT APPLICATION
AVAILABLE EXTERNAL STATIC PRESSURE - IWG1
AIR
FLOW
CFM
RPM
WATTS
BHP
RPM
WATTS
BHP
RPM
WATTS
BHP
RPM
WATTS
BHP
RPM
WATTS
800
----
----
----
----
----
----
696
357
0.38
743
389
0.42
786
422
0.45
900
----
----
----
656
353
0.38
706
385
0.41
753
417
0.45
797
450
0.48
0.51
0.2
0.3
0.4
0.5
0.6
BHP
1000
----
----
----
671
376
0.40
722
408
0.44
768
440
0.47
812
473
1100
634
364
0.39
690
398
0.43
741
431
0.46
787
463
0.50
831
496
0.53
1200
656
389
0.42
712
423
0.45
763
455
0.49
809
488
0.52
853
520
0.56
1300
681
418
0.45
737
452
0.49
787
485
0.52
834
517
0.55
877
550
0.59
1400
707
454
0.49
763
488
0.52
813
520
0.56
860
552
0.59
903
585
0.63
1500
735
496
0.53
791
530
0.57
841
562
0.60
887
594
0.64
931
627
0.67
1600
763
545
0.58
819
579
0.62
870
612
0.66
916
644
0.69
960
677
0.73
1700
793
602
0.65
849
636
0.68
900
669
0.72
946
701
0.75
990
734
0.79
1800
824
667
0.72
880
701
0.75
930
733
0.79
977
765
0.82
1021
798
0.86
1900
855
739
0.79
911
773
0.83
962
806
0.86
1008
838
0.90
1052
871
0.93
2000
887
819
0.88
943
853
0.92
994
886
0.95
1040
918
0.98
1084
951
1.02
AVAILABLE EXTERNAL STATIC PRESSURE - IWG1
AIR
FLOW
CFM
RPM
WATTS
BHP
RPM
WATTS
BHP
RPM
WATTS
BHP
RPM
WATTS
BHP
RPM
WATTS
BHP
800
829
457
0.49
872
495
0.53
916
538
0.58
964
586
0.63
1017
642
0.69
0.7
0.8
0.9
1.0
1.1
900
839
485
0.52
882
524
0.56
927
566
0.61
975
615
0.66
1027
670
0.72
1000
854
508
0.55
897
547
0.59
942
589
0.63
990
638
0.68
1043
693
0.74
1100
874
531
0.57
916
569
0.61
961
612
0.66
1009
660
0.71
1062
715
0.77
1200
896
555
0.60
938
594
0.64
983
636
0.68
1031
685
0.73
1084
740
0.79
1300
920
585
0.63
963
623
0.67
1007
666
0.71
1055
714
0.77
1108
770
0.83
1400
946
620
0.67
989
659
0.71
1034
701
0.75
1082
750
0.80
----
----
----
1500
974
662
0.71
1017
701
0.75
1061
743
0.80
1109
792
0.85
----
----
----
1600
1003
712
0.76
1045
750
0.80
1090
793
0.85
----
----
----
----
----
----
1700
1032
769
0.82
1075
807
0.87
----
----
----
----
----
----
----
----
----
1800
1063
833
0.89
1106
872
0.94
----
----
----
----
----
----
----
----
----
1900
1094
906
0.97
----
----
----
----
----
----
----
----
----
----
----
----
2000
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
1. Blower performance includes gas heat exchangers and 1” filters. See STATIC RESISTANCE table for additional applications.
Factory Installed AK74 blower sheave and A39 belt.
AK61 blower sheave and A36 belt - Field installation required.
Unitary Products Group
17
254596-YTG-A-0306
TABLE 20: SUPPLY AIR BLOWER PERFORMANCE (DJ036 BELT DRIVE) - BOTTOM DUCT APPLICATION
AVAILABLE EXTERNAL STATIC PRESSURE - IWG1
AIR
FLOW
CFM
RPM
WATTS
BHP
RPM
WATTS
BHP
RPM
WATTS
BHP
RPM
WATTS
BHP
RPM
WATTS
BHP
800
----
----
----
----
----
----
----
----
----
749
384
0.41
791
422
0.45
900
----
----
----
----
----
----
720
364
0.39
764
404
0.43
806
443
0.47
0.2
0.3
0.4
0.5
0.6
1000
----
----
----
690
346
0.37
739
388
0.42
783
429
0.46
824
467
0.50
1100
657
334
0.36
711
376
0.40
760
417
0.45
804
458
0.49
845
497
0.53
1200
681
369
0.40
735
410
0.44
784
452
0.49
828
493
0.53
869
532
0.57
1300
707
409
0.44
761
451
0.48
809
493
0.53
854
534
0.57
895
572
0.61
1400
735
456
0.49
789
498
0.53
837
540
0.58
882
581
0.62
923
619
0.66
1500
765
509
0.55
819
550
0.59
867
592
0.64
911
633
0.68
953
672
0.72
1600
796
567
0.61
850
609
0.65
899
651
0.70
943
692
0.74
984
730
0.78
1700
829
631
0.68
883
673
0.72
932
715
0.77
976
756
0.81
1017
794
0.85
1800
863
701
0.75
918
743
0.80
966
785
0.84
1010
826
0.89
1051
864
0.93
1900
899
776
0.83
953
818
0.88
1001
860
0.92
1045
901
0.97
1087
939
1.01
2000
936
857
0.92
990
899
0.96
1038
941
1.01
1082
981
1.05
----
----
----
AVAILABLE EXTERNAL STATIC PRESSURE - IWG1
AIR
FLOW
CFM
RPM
WATTS
BHP
RPM
WATTS
BHP
RPM
WATTS
BHP
RPM
WATTS
BHP
RPM
WATTS
BHP
800
831
456
0.49
871
486
0.52
914
509
0.55
961
525
0.56
1012
532
0.57
0.7
0.8
0.9
1.0
1.1
900
846
477
0.51
886
507
0.54
929
530
0.57
976
546
0.59
1027
553
0.59
1000
864
502
0.54
905
531
0.57
947
555
0.60
994
571
0.61
1046
578
0.62
1100
885
531
0.57
926
561
0.60
969
584
0.63
1015
600
0.64
1067
607
0.65
1200
909
566
0.61
950
596
0.64
992
619
0.66
1039
635
0.68
1091
642
0.69
1300
935
607
0.65
976
636
0.68
1018
660
0.71
1065
676
0.72
----
----
----
1400
963
654
0.70
1004
683
0.73
1046
707
0.76
1093
722
0.77
----
----
----
1500
993
706
0.76
1033
736
0.79
1076
759
0.81
----
----
----
----
----
----
1600
1024
765
0.82
1065
794
0.85
1108
818
0.88
----
----
----
----
----
-------
1700
1057
829
0.89
1098
859
0.92
----
----
----
----
----
----
----
----
1800
1091
899
0.96
----
----
----
----
----
----
----
----
----
----
----
----
1900
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
2000
1. Blower performance includes gas heat exchangers and 1” filters. See STATIC RESISTANCE table for additional applications.
Factory Installed AK74 blower sheave and A39 belt.
AK61 blower sheave and A36 belt - Field installation required.
18
Unitary Products Group
254596-YTG-A-0306
TABLE 21: SUPPLY AIR BLOWER PERFORMANCE (DJ048 BELT DRIVE) - SIDE DUCT APPLICATION
AVAILABLE EXTERNAL STATIC PRESSURE - IWG1
AIR
0.2
0.3
0.4
0.5
0.6
0.7
FLOW
CFM RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP
1000
----
----
----
----
----
----
----
----
----
789
527
0.57
831
567
0.61
874
602
0.65
1100
----
----
----
----
----
----
----
----
----
811
559
0.60
854
599
0.64
896
634
0.68
1200
----
----
----
----
----
----
791
548
0.59
833
592
0.63
876
632
0.68
918
667
0.72
1300
----
----
----
772
539
0.58
813
584
0.63
855
628
0.67
898
668
0.72
940
703
0.75
1400
----
----
----
795
579
0.62
836
624
0.67
878
668
0.72
920
708
0.76
963
744
0.80
1500
779
578
0.62
819
624
0.67
860
669
0.72
902
713
0.77
944
753
0.81
987
789
0.85
1600
804
629
0.67
844
675
0.72
885
720
0.77
927
764
0.82
970
804
0.86 1013
839
0.90
1700
831
685
0.74
871
731
0.78
913
777
0.83
955
820
0.88
997
861
0.92 1040
896
0.96
1800
860
748
0.80
901
794
0.85
942
839
0.90
984
883
0.95 1026
923
0.99 1069
958
1.03
1900
891
817
0.88
931
862
0.92
973
908
0.97 1015
951
1.02 1057
992
1.06 1100
1027
1.10
2000
924
891
0.96
964
937
1.01 1005
982
1.05 1047
1026
1.10 1090
1066
1.14 1133
1102
1.18
2100
959
972
1.04
999
1018
1.09 1040
1063
1.14 1082
1107
1.19 1125
1147
1.23 1167
1182
1.27
2200
996
1059
1.14 1036
1104
1.18 1077
1150
1.23 1119
1194
1.28 1162
1234
1.32
----
----
----
2300
1034
1151
1.24 1075
1197
1.28 1116
1243
1.33 1158
1286
1.38
----
----
----
----
----
2400
1075
1250
1.34 1115
1296
1.39 1156
1341
1.44
----
----
----
----
----
----
----
----
----
2500
1118
1354
1.45 1158
1400
1.50
----
----
----
----
----
----
----
----
----
----
----
----
----
AVAILABLE EXTERNAL STATIC PRESSURE - IWG1
AIR
0.8
0.9
1.0
1.1
1.2
1.3
FLOW
CFM RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP
1000
917
631
0.68
959
651
0.70 1001
660
0.71 1041
658
0.71 1081
642
0.69 1119
611
0.66
1100
939
663
0.71
981
683
0.73 1023
692
0.74 1064
690
0.74 1103
674
0.72 1141
643
0.69
1200
961
696
0.75 1003
716
0.77 1045
725
0.78 1086
723
0.78 1125
707
0.76 1163
676
0.73
1300
983
732
0.79 1025
752
0.81 1067
761
0.82 1108
759
0.81 1147
743
0.80 1185
712
0.76
1400
1006
772
0.83 1048
792
0.85 1090
801
0.86 1130
799
0.86 1170
783
0.84
----
----
----
1500
1030
817
0.88 1072
837
0.90 1114
847
0.91 1154
844
0.91 1194
829
0.89
----
----
----
1600
1055
868
0.93 1098
888
0.95 1139
897
0.96 1180
895
0.96
----
----
----
----
----
----
1700
1083
924
0.99 1125
944
1.01 1166
954
1.02
----
----
----
----
----
----
----
----
----
1800
1112
987
1.06 1154
1007
1.08
----
----
----
----
----
----
----
----
----
----
----
----
1900
1142
1055
1.13 1185
1075
1.15
----
----
----
----
----
----
----
----
----
----
----
----
2000
1175
1130
1.21
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
2100
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
2200
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
2300
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
2400
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
2500
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
1. Blower performance includes gas heat exchangers and 1” filters. See STATIC RESISTANCE table for additional applications.
Factory Installed AK61 blower sheave and A36 belt.
AK56 blower sheave and A36 belt - Field installation required.
Unitary Products Group
19
254596-YTG-A-0306
TABLE 22: SUPPLY AIR BLOWER PERFORMANCE (DJ048 BELT DRIVE) - BOTTOM DUCT APPLICATION
AVAILABLE EXTERNAL STATIC PRESSURE - IWG1
AIR
0.2
0.3
0.4
0.5
0.6
0.7
FLOW
CFM RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP
1000
----
----
----
----
----
----
----
----
----
----
----
----
833
564
0.61
879
605
0.65
1100
----
----
----
----
----
----
----
----
----
809
549
0.59
854
592
0.63
900
633
0.68
1200
----
----
----
----
----
----
786
538
0.58
830
581
0.62
875
623
0.67
920
664
0.71
1300
----
----
----
766
535
0.57
808
574
0.62
851
617
0.66
896
659
0.71
942
700
0.75
1400
749
541
0.58
789
576
0.62
830
616
0.66
874
658
0.71
918
701
0.75
964
742
0.80
1500
774
587
0.63
813
622
0.67
855
662
0.71
898
705
0.76
943
747
0.80
989
788
0.85
1600
801
639
0.69
840
674
0.72
881
714
0.77
925
757
0.81
970
799
0.86 1015
840
0.90
1700
830
697
0.75
869
732
0.79
911
772
0.83
954
814
0.87
999
857
0.92 1045
898
0.96
1800
862
760
0.81
901
795
0.85
943
835
0.90
986
877
0.94 1031
920
0.99 1077
960
1.03
1900
897
828
0.89
936
863
0.93
977
903
0.97 1021
945
1.01 1066
988
1.06 1111
1029
1.10
2000
934
901
0.97
973
936
1.00 1015
976
1.05 1058
1018
1.09 1103
1061
1.14 1149
1102
1.18
2100
974
979
1.05 1013
1014
1.09 1055
1054
1.13 1098
1097
1.18 1143
1139
1.22 1189
1180
1.27
2200
1017
1063
1.14 1056
1098
1.18 1098
1138
1.22 1141
1180
1.27 1186
1223
1.31
----
----
----
2300
1063
1151
1.23 1102
1186
1.27 1144
1226
1.31 1187
1268
1.36
----
----
----
----
----
2400
1111
1243
1.33 1151
1278
1.37 1192
1318
1.41
----
----
----
----
----
----
----
----
----
2500
1163
1340
1.44 1202
1376
1.48
----
----
----
----
----
----
----
----
----
----
----
----
----
AVAILABLE EXTERNAL STATIC PRESSURE - IWG1
AIR
0.8
0.9
1.0
1.1
1.2
1.3
FLOW
CFM RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP
1000
925
642
0.69
971
673
0.72 1017
696
0.75 1061
708
0.76 1103
708
0.76 1144
693
0.74
1100
946
670
0.72
992
701
0.75 1037
723
0.78 1082
736
0.79 1124
735
0.79 1165
721
0.77
1200
967
701
0.75 1013
732
0.79 1058
755
0.81 1102
767
0.82 1145
767
0.82 1185
752
0.81
1300
988
737
0.79 1034
768
0.82 1079
791
0.85 1123
803
0.86 1166
803
0.86
----
----
----
1400
1010
779
0.84 1056
809
0.87 1102
832
0.89 1146
844
0.91 1188
844
0.91
----
----
----
1500
1035
825
0.89 1081
856
0.92 1126
879
0.94 1170
891
0.96
----
----
----
----
----
----
1600
1062
877
0.94 1108
908
0.97 1153
931
1.00 1197
943
1.01
----
----
----
----
----
----
1700
1091
935
1.00 1137
966
1.04 1182
988
1.06
----
----
----
----
----
----
----
----
----
1028
1.10
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
1800
1123
997
1.07 1169
1900
1157
1066
1.14
2000
1195
1139
1.22
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
2100
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
2200
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
2300
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
2400
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
2500
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
1. Blower performance includes gas heat exchangers and 1” filters. See STATIC RESISTANCE table for additional applications.
Factory Installed AK61 blower sheave and A36 belt.
AK56 blower sheave and A36 belt - Field installation required.
20
Unitary Products Group
254596-YTG-A-0306
TABLE 23: SUPPLY AIR BLOWER PERFORMANCE (DJ060 BELT DRIVE) - SIDE DUCT APPLICATION
AVAILABLE EXTERNAL STATIC PRESSURE - IWG1
AIR
0.2
0.3
0.4
0.5
0.6
0.7
FLOW
CFM RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP
1200
----
----
----
----
----
----
----
----
----
----
----
----
876
632
0.68
918
667
0.72
1300
----
----
----
----
----
----
----
----
----
855
628
0.67
898
668
0.72
940
703
0.75
1400
----
----
----
----
----
----
836
624
0.67
878
668
0.72
920
708
0.76
963
744
0.80
1500
----
----
----
819
624
0.67
860
669
0.72
902
713
0.77
944
753
0.81
987
789
0.85
1600
----
----
----
844
675
0.72
885
720
0.77
927
764
0.82
970
804
0.86 1013
839
0.90
1700
831
685
0.74
871
731
0.78
913
777
0.83
955
820
0.88
997
861
0.92 1040
896
0.96
1800
860
748
0.80
901
794
0.85
942
839
0.90
984
883
0.95 1026
923
0.99 1069
958
1.03
1900
891
817
0.88
931
862
0.92
973
908
0.97 1015
951
1.02 1057
992
1.06 1100
1027
1.10
2000
924
891
0.96
964
937
1.01 1005
982
1.05 1047
1026
1.10 1090
1066
1.14 1133
1102
1.18
2100
959
972
1.04
999
1018
1.09 1040
1063
1.14 1082
1107
1.19 1125
1147
1.23 1167
1182
1.27
2200
996
1059
1.14 1036
1104
1.18 1077
1150
1.23 1119
1194
1.28 1162
1234
1.32
----
----
----
2300
1034
1151
1.24 1075
1197
1.28 1116
1243
1.33 1158
1286
1.38
----
----
----
----
----
----
2400
1075
1250
1.34 1115
1296
1.39 1156
1341
1.44
----
----
----
----
----
----
----
----
----
2500
1118
1354
1.45 1158
1400
1.50
----
----
----
----
----
----
----
----
----
----
----
----
AVAILABLE EXTERNAL STATIC PRESSURE - IWG1
AIR
0.8
0.9
1.0
1.1
1.2
1.3
FLOW
CFM RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP
1200
961
696
0.75 1003
716
0.77 1045
725
0.78 1086
723
0.78 1125
707
0.76 1163
676
0.73
1300
983
732
0.79 1025
752
0.81 1067
761
0.82 1108
759
0.81 1147
743
0.80 1185
712
0.76
1400
1006
772
0.83 1048
792
0.85 1090
801
0.86 1130
799
0.86 1170
783
0.84
----
----
----
1500
1030
817
0.88 1072
837
0.90 1114
847
0.91 1154
844
0.91 1194
829
0.89
----
----
----
1600
1055
868
0.93 1098
888
0.95 1139
897
0.96 1180
895
0.96
----
----
----
----
----
----
1700
1083
924
0.99 1125
944
1.01 1166
954
1.02
----
----
----
----
----
----
----
----
----
1800
1112
987
1.06 1154
1007
1.08
----
----
----
----
----
----
----
----
----
----
----
----
1900
1142
1055
1.13 1185
1075
1.15
----
----
----
----
----
----
----
----
----
----
----
----
2000
1175
1130
1.21
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
2100
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
2200
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
2300
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
2400
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
2500
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
1. Blower performance includes gas heat exchangers and 1” filters. See STATIC RESISTANCE table for additional applications.
Factory Installed AK56 blower sheave and A36 belt.
Unitary Products Group
21
254596-YTG-A-0306
TABLE 24: SUPPLY AIR BLOWER PERFORMANCE (DJ060 BELT DRIVE) - BOTTOM DUCT APPLICATION
AVAILABLE EXTERNAL STATIC PRESSURE - IWG1
AIR
0.2
0.3
0.4
0.5
0.6
0.7
FLOW
CFM RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP
1000
----
----
----
----
----
----
----
----
----
----
----
----
862
453
0.49
901
498
0.53
1100
----
----
----
----
----
----
----
----
----
----
----
----
883
494
0.53
922
539
0.58
1200
----
----
----
----
----
----
----
----
----
866
489
0.53
904
536
0.58
943
581
0.62
1300
----
----
----
----
----
----
850
488
0.52
889
535
0.57
928
581
0.62
967
627
0.67
1400
----
----
----
836
491
0.53
875
537
0.58
913
584
0.63
952
631
0.68
991
676
0.73
1500
----
----
----
862
545
0.58
901
591
0.63
940
638
0.68
978
685
0.73 1017
730
0.78
1600
851
559
0.60
890
604
0.65
928
650
0.70
967
697
0.75 1006
744
0.80 1045
789
0.85
1700
880
624
0.67
919
668
0.72
958
714
0.77
996
761
0.82 1035
808
0.87 1074
853
0.92
1800
911
694
0.74
949
738
0.79
988
785
0.84 1027
832
0.89 1066
878
0.94 1105
923
0.99
1900
942
770
0.83
981
814
0.87 1020
860
0.92 1059
907
0.97 1097
954
1.02 1136
999
1.07
2000
976
851
0.91 1014
895
0.96 1053
941
1.01 1092
989
1.06 1130
1035
1.11 1169
1080
1.16
2100
1010
938
1.01 1049
982
1.05 1087
1028
1.10 1126
1075
1.15 1165
1122
1.20 1204
1167
1.25
2200
1046
1030
1.11 1084
1075
1.15 1123
1121
1.20 1162
1168
1.25 1200
1215
1.30
----
----
----
2300
1082
1128
1.21 1121
1172
1.26 1160
1219
1.31 1198
1266
1.36
----
----
----
----
----
----
1322
1.42
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
2400
1120
1231
1.32 1159
1276
1.37 1198
2500
1159
1340
1.44 1198
1384
1.48
----
AVAILABLE EXTERNAL STATIC PRESSURE - IWG1
AIR
0.8
0.9
1.0
1.1
1.2
1.3
FLOW
CFM RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP
1000
940
541
0.58
980
579
0.62 1019
613
0.66 1059
641
0.69 1099
662
0.71 1140
674
0.72
1100
961
582
0.62 1000
621
0.67 1040
654
0.70 1080
682
0.73 1120
703
0.75 1161
715
0.77
1200
983
624
0.67 1022
663
0.71 1062
697
0.75 1101
725
0.78 1142
745
0.80 1182
758
0.81
1300
1006
669
0.72 1045
708
0.76 1085
742
0.80 1125
770
0.83 1165
791
0.85
----
----
----
1400
1030
718
0.77 1070
757
0.81 1109
791
0.85 1149
819
0.88 1190
840
0.90
----
----
----
1500
1057
772
0.83 1096
811
0.87 1136
845
0.91 1176
873
0.94
----
----
----
----
----
----
1600
1084
831
0.89 1124
870
0.93 1163
904
0.97 1203
932
1.00
----
----
----
----
----
----
1700
1113
896
0.96 1153
935
1.00 1192
969
1.04
----
----
----
----
----
----
----
----
----
1800
1144
966
1.04 1183
1005
1.08
----
----
----
----
----
----
----
----
----
----
----
----
1900
1175
1042
1.12
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
2000
1209
1123
1.20
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
2100
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
2200
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
2300
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
2400
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
2500
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
1. Blower performance includes gas heat exchangers and 1” filters. See STATIC RESISTANCE table for additional applications.
Factory Installed AK56 blower sheave and A36 belt.
22
Unitary Products Group
254596-YTG-A-0306
TABLE 25: BELT DRIVE BLOWER MOTOR AND DRIVE DATA
MODEL
SIZE
BLOWER
RANGE
(RPM)
MOTOR1
HP
FRAME
ADJUSTABLE MOTOR PULLEY
OUTSIDE
DIA.
(IN.)
DESIGNATION
PITCH
DIA.
(IN.)
BELT
(NOTCHED)
FIXED BLOWER PULLEY
BORE
(IN.)
DESIGNATION
OUTSIDE
DIA.
(IN.)
PITCH
DIA.
(IN.)
BORE
(IN.)
DESIGNATION
PITCH
LENGTH
(IN.)
QTY.
DJ036
600/920
1-1/2
56
1VL40
2.7-3.7
2.4-3.4
5/8
AK74
7.2
7.0
1
A39
40.3
1
DJ048
790/1120
1-1/2
56
1VL40
2.7-3.7
2.4-3.4
5/8
AK61
5.9
5.7
1
A36
37.3
1
DJ060
850/1220
1-1/2
56
1VL40
2.7-3.7
2.4-3.4
5/8
AK56
5.4
5.2
1
A36
37.3
1
1. All motors have solid bases and are inherently protected. These motors can be selected to operate into their service factor because they are located
in the moving air, upstream of any heating device.
TABLE 26: STATIC RESISTANCES
RESISTANCE, IWG
DESCRIPTION
CFM
1000
1200
1400
1600
1800
2000
2200
2400
2600
2800
3000
0.07
0.08
0.09
0.11
0.13
0.15
0.17
0.20
0.23
0.26
0.30
7-15KW
0.04
0.05
0.06
0.07
0.08
0.10
0.12
0.14
0.16
0.19
0.22
20-30KW
0.06
0.07
0.08
0.09
0.11
0.13
0.15
0.17
0.20
0.23
0.26
0.08
0.10
0.12
0.14
0.16
0.18
0.20
0.23
0.26
0.29
0.32
ECONOMIZER1,3
ELECTRIC
HEATERS1
COOLING
ONLY2
1. Deduct these resistance values from the available external static pressure shown in SUPPLY AIR BLOWER PERFORMANCE Tables.
2. Add these resistance values to the available static resistance values on SUPPLY AIR BLOWER PERFORMANCE Tables.
3. The pressure through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct system is less than
0.25 IWG, the unit will deliver less CFM during full economizer operation.
TABLE 27: ELECTRIC HEATER CFM LIMITATIONS
MINIMUM SUPPLY AIR CFM
UNIT MODEL SIZE
NOMINAL TONS
VOLTAGE
HEATER SIZE NOMINAL KW
5
7
10
15
20
30
208/230-1-60
1100
1100
1200
1200
1300
-
208/230-3-60
1100
1100
1200
1200
1300
-
460-3-60
-
1100
1200
1200
1300
-
575-3-60
-
-
1200
1200
1300
-
208/230-1-60
1300
1300
1300
1300
1300
-
208/230-3-60
1300
1300
1300
1300
1300
-
460-3-60
-
1300
1300
1300
1300
-
575-3-60
-
-
1300
1300
1400
-
208/230-1-60
1600
1600
1600
1600
1600
1600
208/230-3-60
1600
1600
1600
1600
1600
1600
460-3-60
1600
1600
1600
1600
1600
1600
575-3-60
-
1600
1600
1600
1600
1800
3
4
5
Unitary Products Group
23
254596-YTG-A-0306
TABLE 28: ELECTRICAL DATA - DJ036, 048 & 060 BELT DRIVE W/O POWERED CONVENIENCE OUTLET
COMPRESSORS
MODEL
TONNAGE
VOLTAGE
RLA
EACH
LRA
EACH
OD FAN
MOTOR
FLA
ID
BLOWER
MOTOR
FLA
CONV
OUTLET
FLA
208-1-60
11.3
68.0
2.3
7.6
0.0
230-1-60
11.3
68.0
2.3
7.6
0.0
208-3-60
8.3
68.0
2.3
5.2
0.0
230-3-60
8.3
68.0
2.3
5.2
0.0
460-3-60
5.1
34.0
1.3
2.6
0.0
575-3-60
3.2
26.0
1.3
2.0
0.0
208-1-60
15.4
86.0
2.3
7.6
0.0
230-1-60
15.4
86.0
2.3
7.6
0.0
208-3-60
11.5
84.0
2.3
5.2
0.0
230-3-60
11.5
84.0
2.3
5.2
0.0
460-3-60
5.8
42.0
1.3
2.6
0.0
575-3-60
5.1
34.0
1.3
2.0
0.0
DJ036
DJ048
24
ELECTRIC HEATER HEATER HEATER
MODEL NO.
KW
AMPS
None
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
None
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
None
2CE045105252
2CE045107252
2CE04511025
2CE04511525
2CE04512025
None
2CE045105252
2CE045107252
2CE04511025
2CE04511525
2CE04512025
None
2CE045107462
2CE045110462
2CE045115462
2CE045120462
None
2CE04511058
2CE04511558
2CE04512058
None
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
None
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
None
2CE045105252
2CE045107252
2CE04511025
2CE04511525
2CE04512025
None
2CE045105252
2CE045107252
2CE04511025
2CE04511525
2CE04512025
None
2CE045107462
2CE045110462
2CE045115462
2CE045120462
None
2CE04511058
2CE04511558
2CE04512058
-4.0
5.6
8.0
11.9
15.9
-5.3
7.5
10.6
15.9
21.2
-4.0
5.6
8.0
11.9
15.9
-5.3
7.5
10.6
15.9
21.2
-6.8
10.1
13.6
19.5
-10.6
15.9
21.2
-4.0
5.6
8.0
11.9
15.9
-5.3
7.5
10.6
15.9
21.2
-4.0
5.6
8.0
11.9
15.9
-5.3
7.5
10.6
15.9
21.2
-6.8
10.1
13.6
19.5
-10.6
15.9
21.2
-19.2
26.9
38.5
57.2
76.4
-22.1
31.3
44.2
66.3
88.3
-11.1
15.5
22.2
33.0
44.1
-12.7
18.0
25.5
38.2
51.0
-8.2
12.1
16.4
23.5
-10.2
15.3
20.4
-19.2
26.9
38.5
57.2
76.4
-22.1
31.3
44.2
66.3
88.3
-11.1
15.5
22.2
33.0
44.1
-12.7
18.0
25.5
38.2
51.0
-8.2
12.1
16.4
23.5
-10.2
15.3
20.4
MIN.
MAX. FUSE/
CIRCUIT
BRKR1
SIZE
AMPACITY
(AMPS)
(AMPS)
24.0
30
33.5
35
43.2
45
57.6
60
81.0
90
105.1
110
24.0
30
37.1
40
48.6
50
64.7
70
92.3
100
119.9
125
17.9
25
20.4
25
25.9
30
34.3
35
47.8
50
61.7
70
17.9
25
22.4
25
29.1
30
38.4
40
54.3
60
70.2
80
10.3
15
13.5
15
18.4
20
23.7
25
32.6
35
7.0
15
15.2
20
21.6
25
28.0
30
29.1
35
33.5
40
43.2
45
57.6
60
81.0
90
105.1
110
29.1
35
37.1
40
48.6
50
64.7
70
92.3
100
119.9
125
21.9
30
21.9
30
25.9
30
34.3
35
47.8
50
61.7
70
21.9
30
22.4
30
29.1
30
38.4
40
54.3
60
70.2
80
11.1
15
13.5
15
18.4
20
23.7
25
32.6
35
9.4
15
15.2
20
21.6
25
28.0
30
Unitary Products Group
254596-YTG-A-0306
TABLE 28: ELECTRICAL DATA - DJ036, 048 & 060 BELT DRIVE W/O POWERED CONVENIENCE OUTLET (CONT)
COMPRESSORS
MODEL
TONNAGE
VOLTAGE
RLA
EACH
LRA
EACH
OD FAN
MOTOR
FLA
ID
BLOWER
MOTOR
FLA
CONV
OUTLET
FLA
208-1-60
25.0
150.0
2.3
7.6
0.0
230-1-60
25.0
150.0
2.3
7.6
0.0
208-3-60
17.3
123.0
2.3
5.2
0.0
230-3-60
17.3
123.0
2.3
5.2
0.0
460-3-60
8.4
70.0
1.3
2.6
0.0
575-3-60
7.0
53.0
1.3
2.0
0.0
DJ060
ELECTRIC HEATER HEATER HEATER
MODEL NO.
KW
AMPS
None
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
2CE04513006
None
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
2CE04513006
None
2CE045105252
2CE045107252
2CE04511025
2CE04511525
2CE04512025
2CE04513025
None
2CE045105252
2CE045107252
2CE04511025
2CE04511525
2CE04512025
2CE04513025
None
2CE045107462
2CE045110462
2CE045115462
2CE045120462
2CE045130462
None
2CE04511058
2CE04511558
2CE04512058
2CE04513058
-4.0
5.6
8.0
11.9
15.9
22.2
-5.3
7.5
10.6
15.9
21.2
29.6
-4.0
5.6
8.0
11.9
15.9
22.2
-5.3
7.5
10.6
15.9
21.2
29.6
-6.8
10.1
13.6
19.5
28.8
-10.6
15.9
21.2
30.4
-19.2
26.9
38.5
57.2
76.4
106.7
-22.1
31.3
44.2
66.3
88.3
123.3
-11.1
15.5
22.2
33.0
44.1
61.6
-12.7
18.0
25.5
38.2
51.0
71.2
-8.2
12.1
16.4
23.5
34.6
-10.2
15.3
20.4
29.3
MIN.
MAX. FUSE/
CIRCUIT
BRKR1
SIZE
AMPACITY
(AMPS)
(AMPS)
41.2
45
41.2
45
43.2
60
57.6
60
81.0
90
105.1
110
142.9
150
41.2
45
41.2
45
48.6
60
64.7
70
92.3
100
119.9
125
163.7
175
29.1
35
29.1
35
29.1
35
34.3
45
47.8
50
61.7
70
83.5
90
29.1
35
29.1
35
29.1
35
38.4
45
54.3
60
70.2
80
95.5
100
14.4
20
14.4
20
18.4
20
23.7
25
32.6
35
46.6
50
11.8
15
15.2
20
21.6
25
28.0
30
39.1
40
1. HACR Type per NEC.
2. These electric heaters do not include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block
accessories 2FB04700825 and 2FB04700846 are available for field installation.
Unitary Products Group
25
254596-YTG-A-0306
TABLE 29: ELECTRICAL DATA - DJ036, 048 & 060 BELT DRIVE WITH POWERED CONVENIENCE OUTLET
COMPRESSORS
MODEL
TONNAGE
VOLTAGE
RLA
EACH
LRA
EACH
OD FAN
MOTOR
FLA
ID
BLOWER
MOTOR
FLA
CONV
OUTLET
FLA
208-1-60
11.3
68.0
2.3
7.6
10.0
230-1-60
11.3
68.0
2.3
7.6
10.0
208-3-60
8.3
68.0
2.3
5.2
10.0
230-3-60
8.3
68.0
2.3
5.2
10.0
460-3-60
5.1
34.0
1.3
2.6
5.0
575-3-60
3.2
26.0
1.3
2.0
4.0
208-1-60
15.4
86.0
2.3
7.6
10.0
230-1-60
15.4
86.0
2.3
7.6
10.0
208-3-60
11.5
84.0
2.3
5.2
10.0
230-3-60
11.5
84.0
2.3
5.2
10.0
460-3-60
5.8
42.0
1.3
2.6
5.0
575-3-60
5.1
34.0
1.3
2.0
4.0
DJ036
DJ048
26
ELECTRIC HEATER HEATER HEATER
MODEL NO.
KW
AMPS
None
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
None
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
None
2CE045105252
2CE045107252
2CE04511025
2CE04511525
2CE04512025
None
2CE045105252
2CE045107252
2CE04511025
2CE04511525
2CE04512025
None
2CE045107462
2CE045110462
2CE045115462
2CE045120462
None
2CE04511058
2CE04511558
2CE04512058
None
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
None
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
None
2CE045105252
2CE045107252
2CE04511025
2CE04511525
2CE04512025
None
2CE045105252
2CE045107252
2CE04511025
2CE04511525
2CE04512025
None
2CE045107462
2CE045110462
2CE045115462
2CE045120462
None
2CE04511058
2CE04511558
2CE04512058
-4.0
5.6
8.0
11.9
15.9
-5.3
7.5
10.6
15.9
21.2
-4.0
5.6
8.0
11.9
15.9
-5.3
7.5
10.6
15.9
21.2
-6.8
10.1
13.6
19.5
-10.6
15.9
21.2
-4.0
5.6
8.0
11.9
15.9
-5.3
7.5
10.6
15.9
21.2
-4.0
5.6
8.0
11.9
15.9
-5.3
7.5
10.6
15.9
21.2
-6.8
10.1
13.6
19.5
-10.6
15.9
21.2
-19.2
26.9
38.5
57.2
76.4
-22.1
31.3
44.2
66.3
88.3
-11.1
15.5
22.2
33.0
44.1
-12.7
18.0
25.5
38.2
51.0
-8.2
12.1
16.4
23.5
-10.2
15.3
20.4
-19.2
26.9
38.5
57.2
76.4
-22.1
31.3
44.2
66.3
88.3
-11.1
15.5
22.2
33.0
44.1
-12.7
18.0
25.5
38.2
51.0
-8.2
12.1
16.4
23.5
-10.2
15.3
20.4
MIN.
MAX. FUSE/
CIRCUIT
BRKR1
SIZE
AMPACITY
(AMPS)
(AMPS)
34.0
45
46.0
50
55.7
60
70.1
80
93.5
100
117.6
125
34.0
45
49.6
50
61.1
70
77.2
80
104.8
110
132.4
150
28.3
35
32.9
35
38.4
40
46.8
50
60.3
70
74.2
80
28.3
35
34.9
40
41.6
45
50.9
60
66.8
70
82.7
90
15.3
20
19.7
20
24.7
25
29.9
30
38.8
40
11.2
15
20.2
25
26.6
30
33.0
35
39.1
50
46.0
50
55.7
60
70.1
80
93.5
100
117.6
125
39.1
50
49.6
50
61.1
70
77.2
80
104.8
110
132.4
150
31.9
40
32.9
40
38.4
40
46.8
50
60.3
70
74.2
80
31.9
40
34.9
40
41.6
45
50.9
60
66.8
70
82.7
90
16.1
20
19.7
20
24.7
25
29.9
30
38.8
40
13.4
15
20.2
25
26.6
30
33.0
35
Unitary Products Group
254596-YTG-A-0306
TABLE 29: ELECTRICAL DATA - DJ036, 048 & 060 BELT DRIVE WITH POWERED CONVENIENCE OUTLET (CONT)
COMPRESSORS
MODEL
TONNAGE
VOLTAGE
RLA
EACH
LRA
EACH
OD FAN
MOTOR
FLA
ID
BLOWER
MOTOR
FLA
CONV
OUTLET
FLA
208-1-60
25.0
150.0
2.3
7.6
10.0
230-1-60
25.0
150.0
2.3
7.6
10.0
208-3-60
17.3
123.0
2.3
5.2
10.0
230-3-60
17.3
123.0
2.3
5.2
10.0
460-3-60
8.4
70.0
1.3
2.6
5.0
575-3-60
7.0
53.0
1.3
2.0
4.0
DJ060
ELECTRIC HEATER HEATER HEATER
MODEL NO.
KW
AMPS
None
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
2CE04513006
None
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
2CE04513006
None
2CE045105252
2CE045107252
2CE04511025
2CE04511525
2CE04512025
2CE04513025
None
2CE045105252
2CE045107252
2CE04511025
2CE04511525
2CE04512025
2CE04513025
None
2CE045107462
2CE045110462
2CE045115462
2CE045120462
2CE045130462
None
2CE04511058
2CE04511558
2CE04512058
2CE04513058
-4.0
5.6
8.0
11.9
15.9
22.2
-5.3
7.5
10.6
15.9
21.2
29.6
-4.0
5.6
8.0
11.9
15.9
22.2
-5.3
7.5
10.6
15.9
21.2
29.6
-6.8
10.1
13.6
19.5
28.8
-10.6
15.9
21.2
30.4
-19.2
26.9
38.5
57.2
76.4
106.7
-22.1
31.3
44.2
66.3
88.3
123.3
-11.1
15.5
22.2
33.0
44.1
61.6
-12.7
18.0
25.5
38.2
51.0
71.2
-8.2
12.1
16.4
23.5
34.6
-10.2
15.3
20.4
29.3
MIN.
MAX. FUSE/
CIRCUIT
BRKR1
SIZE
AMPACITY
(AMPS)
(AMPS)
51.2
70
51.2
70
55.7
70
70.1
80
93.5
100
117.6
125
155.4
175
51.2
70
51.2
70
61.1
70
77.2
80
104.8
110
132.4
150
176.2
200
39.1
50
39.1
50
39.1
50
46.8
50
60.3
70
74.2
80
96.0
100
39.1
50
39.1
50
41.6
50
50.9
60
66.8
70
82.7
90
108.0
110
19.4
25
19.7
25
24.7
25
29.9
30
38.8
40
52.8
60
15.8
20
20.2
25
26.6
30
33.0
35
44.1
45
1. HACR Type per NEC.
2. These electric heaters do not include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block
accessories 2FB04700825 and 2FB04700846 are available for field installation.
Unitary Products Group
27
254596-YTG-A-0306
TABLE 30: PHYSICAL DATA
DJ
MODELS
EVAPORATOR
BLOWER
036
048
060
Centrifugal Blower (Dia. x Wd. in.)
12 X 10
12 X 10
12 X 10
Fan Motor HP (Belt Drive)
1-1/2
1-1/2
1-1/2
Rows Deep
3
4
4
Fins Per Inch
13
13
13
Face Area (Sq. Ft.)
5.1
5.1
5.1
Propeller Dia. (in.)
24
24
24
Fan Motor Hp
1/2
1/2
1/2
4200
EVAPORATOR
COIL
CONDENSER
FANS
Nom. CFM
4200
4200
Rows Deep
2
2
2
Fins Per Inch
18
18
18
Face Area (Sq. Ft.)
17.1
17.1
17.1
Quantity
1
1
1
Type
Recip.
Recip.
Scroll
Quantity Per Unit (15” X 20” X 1” or 2“)
2
2
2
Quantity Per Unit (14” X 25” X 1” or 2“)
1
1
1
Total Face Area (sq. ft.)
6.3
6.3
6.3
Refrigerant 22 (lbs./oz.)
9/4
9/8
11/0
CONDENSER
COILS
COMPRESSOR
(Qty. Per Unit)
AIR
FILTERS
CHARGE
TABLE 31: ELECTRIC HEAT CORRECTION
FACTORS
NOMINAL VOLTAGE
VOLTAGE
kW CAP. MULTIPLIER
TABLE 32: VOLTAGE LIMITATIONS1
VOLTAGE
POWER SUPPLY
MIN.
MAX.
208/230-1-60
187
252
208
208
1.00
240
230
0.92
208/230-3-60
187
252
480
460
0.92
460-3-60
432
504
600
575
0.92
575-3-60
540
630
1. Utilization Range “A” in accordance with ARI Standard
110.
28
Unitary Products Group
254596-YTG-A-0306
TYPICAL POWER WIRING
REFER TO THE ELECTRICAL DATA
TABLES TO SIZE THE DISCONNECT
SWITCH, OVERCURRENT PROTECTION AND WIRING.
TYPICAL CONTROL WIRING
COOLING ONLY (24 VOLT THERMOSTAT)
THERMOSTAT
TERMINALS
1
COOLING / HEATING (24 VOLT THERMOSTAT)
THERMOSTAT 1
TERMINALS
UNIT TERMINAL
STRIP TB1
R
RV
24 VOLT
TRANSFORMER
Y1
YC
ADD
JUMPER
Y2
UNIT TERMINAL
STRIP TB1
RC
R
Y
Y1
24 VOLT
TRANSFORMER
Y2
G
GF
W
C
1
RH
W1
W2
24 VOLT THERMOSTAT 2TH07701024. TO CONTROL THE ECONOMIZER
ON SECOND STAGE COOLING, USE THE THERMOSTAT 2TH0401224.
G
G
C
COOLING / HEATING (ELECTRONIC THERMOSTAT)
MULTI STAGE
THERMOSTAT1
TERMINALS
ADD
JUMPER
RC
UNIT TERMINAL
STRIP TB1
RH
R
Y1
Y1
2
Y2
3
W2
G
B
COM
ADD
JUMPER
THERMOSTAT1
TERMINALS
W2
RH
C
X
NOT
USED
OCC
ADD
JUMPER
4
A1
T
UNIT TERMINAL
STRIP TB1
RC
R
Y
Y1
W
W1
G
G
C
A2
T
24 VOLT
TRANSFORMER
TO REMOTE SENSOR
2TH040702224 IF USED
1
ELECTRONIC PROGRAMMABLE THERMOSTAT 2ET04700224 (INCLUDES SUBBASE).
2
SECOND STAGE COOLING IS NOT REQUIRED ON UNITS LESS ECONOMIZER.
3
SECOND STAGE HEATING IS ONLY REQUIRED ON UNITS WITH A TWO STAGE
ELECTRIC HEATER OR 2 STAGE GAS HEAT.
4
COOLING / HEATING (ELECTRONIC THERMOSTAT)
SINGLE STAGE
G
LED 1
LED 2
Y2
24 VOLT THERMOSTAT 2ET07701024. TO CONTROL THE ECONOMIZER ON THE SECOND
STAGE COOLING OR TO HAVE AN ELECTRIC HEAT ACCESSORY WITH TWO STAGES OF
HEAT, USE THERMOSTAT 2TH0471024.
W1
W1
4
24 VOLT
TRANSFORMER
1
1 ELECTRONIC
PROGRAMMABLE THERMOSTAT 2ET07701024 (INCLUDES SUBBASE).
TO CONTROL THE ECONOMIZER ON SECOND STAGE COOLING, USE THERMOSTAT
2TH04700224.
REMOVE JUMPER J2 FROM TERMINALS 4 AND 9 ON JUMPER PLUG CONNECTOR
P6 ON UNITS WITH ECONOMIZER. TERMINALS A1 AND A2 PROVIDE A RELAY
OUT-PUT TO CLOSE THE OUTDOOR ECONOMIZER DAMPERS WHEN THE
THERMOSTAT SWITCHES TO THE SET-BACK POSITION.
FIGURE 2 -
TYPICAL FIELD POWER & CONTROL WIRING
Unitary Products Group
29
254596-YTG-A-0306
FIGURE 3 -
UNIT DIMENSIONS (3 - 5 TON COOLING ONLY/ELECTRIC HEAT) FRONT VIEW
FIGURE 4 -
UNIT DIMENSIONS (3 - 5 TON COOLING/GAS HEAT) FRONT VIEW
30
Unitary Products Group
254596-YTG-A-0306
DETAIL “A”
FIGURE 5 -
UNIT WITH ECONOMIZER RAINHOOD
DETAIL “B”
FIGURE 6 -
UNIT WITH FIXED OUTDOOR AIR/MOTORIZED DAMPER RAINHOOD
Unitary Products Group
31
254596-YTG-A-0306
FIGURE 7 -
UNIT DIMENSIONS (REAR VIEW)
TABLE 34: MINIMUM CLEARANCES
FILTER
ACCESS
BLOWER MOTOR
ACCESS
LOCATION
CLEARANCE
Front
24” (Cooling/Electric Heat)
32” (Gas Heat)
Rear
12” (Less Economizer)
36” (With Economizer or Fixed
Air/Motorized Damper)
Left Side (Filter Access)
24” (Less Economizer)
36” (With Economizer)
Right Side (Cond. Coil)
24”
DOT PLUGS
FIELD-SUPPLIED
DISCONNECT SWITCH
LOCATION
MOUNTING BRACKET
FOR DICONNECT SWITCH
(Shipped attached to the
blower housing inside
the blower compartment)
A,B
WIRING ENTRY
(See Detail “B”)
DISCONNECT SWITCH LOCATION
AND MOTOR ACCESS PANEL FOR
UNIT WITH “BELT-DRIVE” OPTION
FIGURE 8 -
CONTROL BOX
ACCESS
DISCONNECT/BLOWER ACCESS
LOCATION
TABLE 33: UTILITIES ENTRY
HOLE
OPENING SIZE (DIA.)
A
7/8” KO1
Control Wiring2
B
2” KO1
Power Wiring
C
1-5/8” KO
Gas Piping (Front)
D
1-1/2” KO
Gas Piping (Bottom)
Below
Unit1
0”
Above
Unit2
72” (For
Condenser Air Discharge)
1. Units may be installed on combustible floors made
from wood or class A, B, or C roof covering material.
2. Units must be installed outdoors. Overhanging structures or shrubs should not obstruct condenser air discharge outlet.
USED FOR
Side
Bottom
Side
Bottom
1. Opening in the bottom to the unit can be located by the
side in the insulation.
2. Do not remove the 2” knockout ring.
32
Unitary Products Group
254596-YTG-A-0306
FIGURE 9 -
TYPICAL APPLICATIONS
Unitary Products Group
33
254596-YTG-A-0306
BACK OF UNIT
A
447/8
821/4
D
BACK OF UNIT
A
447/8
X
821/4
B
F
X
B
APPROXIMATE
CENTER OF GRAVITY
C
FRONT OF UNIT
CONDENSER COIL
END OF UNIT
Y
APPROXIMATE
CENTER OF GRAVITY
C
E
D
FRONT OF UNIT
CONDENSER COIL
END OF UNIT
Y
FIGURE 10 - FOUR AND SIX POINT LOADING
TABLE 35: DJ 4 AND 6 POINT LOADS WEIGHT DISTRIBUTION
UNIT
TOTAL
4-Point Loading (lb)
6-Point Loading (lb)
A
B
C
D
A
B
C
D
E
F
DJ036 Cooling/ Electric
575
132
125
155
164
89
85
82
102
106
110
DJ036N04
615
141
133
166
175
95
91
88
110
114
118
DJ036D06
625
143
135
168
178
96
93
89
111
115
120
DJ036N08
635
145
138
171
181
98
94
91
113
117
122
DJ036D10
645
148
140
174
184
99
96
92
115
119
124
DJ048 Cooling/ Electric
585
134
127
158
167
90
87
84
104
108
112
DJ048(D,N)06
635
145
138
171
181
98
94
91
113
117
122
DJ048(D,N)10
655
150
142
177
187
101
97
94
117
121
125
DJ060 Cooling/ Electric
590
135
128
159
168
91
88
84
105
109
113
DJ060D06
640
147
139
173
182
99
95
92
114
118
123
DJ060N08
650
149
141
175
185
100
97
93
116
120
125
DJ060(D,N)10
660
151
143
178
188
102
98
95
118
122
126
TABLE 36: CENTER OF GRAVITY
DIMENSION
3 - 5 TON
X
40”
Y
20”
34
Unitary Products Group
254596-YTG-A-0306
TABLE 37: OPERATING WEIGHTS (LBS.)
MODEL SIZE
3 TON
4 TON
5 TON
575
585
590
N04
615
-
-
N06
-
635
-
N08
635
-
650
DJ (Cooling Only)
BASIC
UNIT
DJ
(Gas/Electric)
N10
-
655
660
D06
625
635
640
D10
645
655
660
Economizer
50
Motorized Damper
OPTIONS
Electric Heater
ACCY.
26
5 - 7 kW
18
10 - 15 kW
23
20 - 30 kW
28
Roof Curb
92
Barometric Relief / Fixed Air Damper
10
FIGURE 11 - ROOF CURB DIMENSIONS
Unitary Products Group
35
254596-YTG-A-0306
GUIDE SPECIFICATIONS
GENERAL
Units shall be manufactured by York International Unitary
Products Group in an ISO 9001 certified facility.
York's Sunline Magnum™ units are convertible single package units. Although the units are primarily designed for curb
mounting on a roof, they can also be slab-mounted at ground
level or set on steel beams above a finished roof. Cooling
only, cooling with gas heat and cooling with electric heat
models are available with a wide variety of factory-mounted
options and field-installed accessories to make them suitable
for almost every application. All units are self-contained and
assembled on full perimeter base rails with holes in the four
corners for overhead rigging. Every unit is completely piped,
wired, charged and tested at the factory to simplify the field
installation and to provide years of dependable operation. All
models (including those with an economizer) are suitable for
either bottom or horizontal duct connections. Models with
power exhaust are suitable for bottom duct connections only.
For bottom duct, remove the sheet metal panels from the
supply and return air openings through the base of the unit.
For horizontal duct, remove the supply and return air panels
on the rear of the unit.
All non-Scroll compressors include crankcase heaters and all
compressors have internal pressure relief. Every refrigerant
circuit includes a liquid line filter-drier, a discharge line high
pressure switch and a suction line with a freezestat and low
pressure/loss of charge switch.The unit control circuit
includes a 75 VA transformer, a 24-volt circuit breaker and a
relay board with a compressor lockout circuit, a terminal strip
for thermostat wiring, plus an additional set of pin connectors
to simplify the interface of additional field controls. All models
are CSA listed. All models include a 1-year limited warranty
on the complete unit. Compressors and electric heater elements carry a 5-year warranty. Aluminized steel and Stainless
steel tubular heat exchangers carry a 10-year warranty.
DESCRIPTION
Units shall be factory-assembled, single packaged, Electric
Cooling/Gas Heat, Electric Cooling/Optional Electric Heat
and designed for outdoor mounted installation.
The 3 ton, 4 ton and 5 ton units shall have minimum SEER
rating of 13. They shall have built-in field convertible duct
connections for down discharge supply/return or horizontal
discharge supply/return, and be available with factory
installed options or field installed accessories. The units shall
be factory wired, piped, charged with R-22 refrigerant and
factory tested prior to shipment. All unit wiring shall be both
numbered and color coded. All units the cooling performance
shall be rated in accordance with DOE and ARI test procedures. Units shall be CSA listed, classified to ANSI Z21.47,
UL 1995/CSA No. 236 standards.
36
UNIT CABINET
Unit cabinet shall be constructed of G90 galvanized steel,
with exterior surfaces coated with a non-chalking, powdered
paint finish, certified at 1000 hours salt spray test per
ASTMB117 standards. Indoor blower section shall be insulated with a minimum 1/2” thick insulation, coated on the airside. Aluminum foil faced insulation shall be used in the
furnace compartment and be fastened with ridged fasteners
to prevent insulation from entering the air stream. Cabinet
panels shall be “large” size, easily removable for servicing
and maintenance. Full perimeter base rails shall be provided
to assure reliable transit of equipment, overhead rigging and
proper sealing on roof curb applications. Disposable 1" filters
shall be furnished and be accessible through a removable
access door, sealed airtight. Units filter track shall be
designed to accommodate either 1" or 2" filters. Fan performance measuring ports shall be provided on the outside of
the cabinet to allow accurate air measurements of evaporator
fan performance without removing panels or creating air bypass of the coils. Condensate pan shall be internally sloped
and conform to ASHRAE 62-89 self-draining standards. Condensate connection shall be a minimum of 3/4” I.D. female
and be a ridged mount connection.
INDOOR (EVAPORATOR) FAN ASSEMBLY
The indoor fan shall be a factory installed belt drive assembly
that includes an adjustable pitch motor pulley. Job site
selected (B.H.P.) brake horsepower shall not exceed the
motors nameplate horsepower rating, plus the service factor.
Units shall be designed not to operate above service factor.
Fan wheel shall be double-inlet type with forward-curved
blades, dynamically balanced to operate smoothly throughout
the entire range of operation. Airflow design shall be constant
air volume. Bearings shall be sealed and permanently lubricated for longer life and no maintenance.
OUTDOOR (CONDENSER) FAN ASSEMBLY
The outdoor fan shall be of the direct-driven propeller type,
discharge air vertically, have aluminum blades riveted to a
corrosion resistant steel spider bracket and shall be dynamically balanced for smooth operation. The outdoor fan motor
shall be totally enclosed with permanently lubricated bearings, internally protected against overload conditions and
staged independently.
REFRIGERANT COMPONENTS
Compressor:
a.
Shall be internally protected with internal high-pressure relief and over temperature protection.
b.
Shall have internal spring isolation and sound muffling to minimize vibration and noise, and be externally isolated on a dedicated, independent mounting.
Unitary Products Group
254596-YTG-A-0306
Coils:
a.
Evaporator and condenser coils shall have aluminum plate fins mechanically bonded to seamless
internally enhanced copper tubes with all joints
brazed. Special Phenolic coating shall be available
as a factory option.
b.
Evaporator and Condenser coils shall be of the
direct expansion, draw-thru, design.
Refrigerant Circuit and Refrigerant Safety Components shall
include:
a.
Independent fixed-orifice or thermally operated
expansion devices.
b.
Filter drier/strainer to eliminate any moisture or foreign matter.
c.
Accessible service gage connections on both suction and liquid lines to charge, evacuate, and measure refrigerant pressure during any necessary
servicing or troubleshooting, without losing charge.
d.
The refrigeration system shall provide at least 15°F
of sub-cooling at design conditions.
UNIT CONTROLS
a.
Unit shall be complete with self-contained low-voltage control circuit protected by a resetable circuit
breaker on the 24-volt transformer side.
b.
Unit shall incorporate a lockout circuit which provides reset capability at the space thermostat or
base unit, should any of the following standard
safety devices trip and shut off compressor.
c.
Loss-of-charge/Low-pressure switch.
d.
High-pressure switch.
e.
Freeze-protection thermostat, evaporator coil.
f.
Unit shall incorporate “AUTO RESET” compressor
over temperature, over current protection.
g.
Unit shall operate with conventional thermostat
designs and have a low voltage terminal strip for
easy hook-up.
h.
Unit control board shall have on-board diagnostics
and fault code display.
i.
Standard controls shall include anti-short cycle and
low voltage protection, and permit cooling operation
down to 0°F.
j.
Control board shall monitor each refrigerant safety
switch independently.
k.
Control board shall retain last 5 fault codes in non
volatile memory which will not be lost in the event of
a power loss.
GAS HEATING SECTION (SINGLE OR 2 STAGE)
Shall be designed with induced draft combustion with post
purge logic, energy saving direct spark ignition, and redundant main gas valve. Venter wheel shall be constructed of
Unitary Products Group
stainless steel for corrosion resistance. The heat exchanger
shall be of the tubular type, constructed of T1-40 aluminized
steel for corrosion resistance and allowing minimum mixed
air entering temperature of 25°F. Burners shall be of the
inshot type, constructed of aluminum coated steel and contain air mixture adjustments. All gas piping shall enter the unit
cabinet at a single location through either the side or curb
without any field modifications. Integrated control boards
shall provide timed control of evaporator fan functioning and
burner ignition. Heating section shall be provided with the following minimum protection:
a.
Primary and auxiliary high-temperature limit switches.
b.
Induced draft motor speed sensor.
c.
Flame roll out switch.
d.
Flame proving controls.
e.
If any of the above safety devices trip, a LED (lightemitting diode) indicator shall flash a diagnostic
code that indicates which safety switch has tripped.
ELECTRIC HEATING SECTION
An electric heating section, with nickel chromium elements,
shall be provided in a range of 5 thru 30 KW, offering two
stages of capacity - 16 KW and above on 208/230 volt heaters
and 20 KW and above on 460 and 575 volt heaters. The heating section shall have a primary limit control(s) and automatic
reset to prevent the heating element system from operating at
an excessive temperature. The heating section assembly
shall slide out of the unit for easy maintenance and service.
Units with Electric Heating shall be wired for a single point
power supply with branch circuit fusing (where required).
UNIT OPERATING CHARACTERISTICS
a.
Unit shall be capable of starting and running at 125°F
outdoor temperature, exceeding maximum load criteria of ARI Standard 210/240. The compressor, with
standard controls, shall be capable of operation
down to 0°F outdoor temperature. Unit shall be provided with fan time delay to prevent cold air delivery
before heat exchanger warms up (Gas heat only).
ELECTRICAL REQUIREMENTS
All unit power wiring shall enter unit cabinet at a single factory
provided location and be capable of side or bottom entry, to
minimize roof penetrations and avoid unit field modifications.
Separate side and bottom openings shall be provided for the
control wiring.
STANDARD LIMITED WARRANTIES
•
Compressor 5 Years
•
Heat Exchanger 10 Years
•
Electric Heat Element 5 Years
•
Other Parts 1 Year
37
254596-YTG-A-0306
OPTIONAL OUTDOOR AIR (Shall be made available by
either/or):
•
LOW NOX - Required to reduce the emission of nitrogen
oxides below 40 nanograms per joule.
•
•
GAS PIPING - Contains 1/2” pipe nipples, fittings and
gas cock (including panel assess gaskets) required for
bottom gas supply connection with external shut off.
•
POWER EXHAUST OPTION - To work in conjunction
with economizers.
•
ELECTRIC HEATERS
•
ECONOMIZER/MOTORIZED DAMPER RAIN HOOD Contains all hood panels and the hardware for assembling.
•
MANUAL OUTDOOR AIR DAMPER
•
COIL GUARD KIT - Guard for cooling coil.
•
HAIL GUARD
•
FLUE EXHAUST EXTENSION
•
ELECTRONIC ENTHALPY AUTOMATIC ECONOMIZER- Outdoor and return air dampers that are interlocked and positioned by a fully-modulating, spring
return damper actuator. The maximum leakage rate for
the outdoor air intake dampers shall not exceed 2%
when dampers are fully closed and operating against a
pressure differential of 0.5 IWG. A unit-mounted potentiometer shall be provided to adjust the outdoor and return
air damper assembly to take in CFM of outdoor air to
meet the minimum ventilation requirement of the conditioned space during normal operation. During economizer operation, a mixed-air temperature control shall
modulate the outdoor and return air damper assembly to
prevent the supply air temperature from dropping below
55°F. Changeover from compressor to economizer operation shall be provided by an integral electronic enthalpy
control that feeds input into the basic module. The outdoor intake opening shall be covered with a rain hood
that matches the exterior of the unit. Water eliminator/filters shall be provided. Simultaneous economizer/compressor operation is also possible. Dampers shall fully
close on power loss.
MOTORIZED OUTDOOR AIR DAMPERS - Outdoor air
dampers are positioned by a 2-position, spring-return
damper actuator. The maximum leakage rate for the outdoor air intake dampers shall not exceed 2% when
dampers are fully closed and operating against a pressure differential of 0.5 IWG. A unit-mounted potentiometer shall be provided to adjust the outdoor damper
assembly to take in the design CFM of outdoor air to
meet the ventilation requirements of the conditioned
space during normal operation. Whenever the indoor fan
motor is energized, the dampers open up to one of two
pre-selected positions - regardless of the outdoor air
enthalpy. Dampers return to the fully closed position
when the indoor fan motor is de-energized. Dampers
shall fully close on power loss.
OTHER FACTORY INSTALLED OPTIONS
•
POWER EXHAUST OPTION - To work in conjunction
with economizers.
•
STAINLESS STEEL HEAT EXCHANGER
•
STAINLESS STEEL DRAIN PAN
•
BOTTOM DRAIN CONNECTION
•
TECHNICOAT PHENOLIC COATED CONDENSER
AND EVAPORATOR COIL
•
ELECTRONIC SINGLE ENTHALPY ECONOMIZER
•
DIRTY FILTER SWITCH
•
PHASE MONITOR
•
COIL GUARD
•
POWERED GFI CONVENIENCE OUTLET
•
NON-POWERED GFI CONVENIENCE OUTLET
•
BAS CONTROLS (Simplicity® INTELLI-Comfort™,
CPC, JOHNSON, HONEYWELL, NOVAR)
•
BAS READY ECONOMIZER (BELIMO ACTUATOR
WITHOUT A CONTROLLER)
OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE
•
ROOF CURB - 14"and 8” high, full perimeter curb with
wood nailer (shipped knocked-down).
•
HINGED FILTER DOOR ACCESS AND TOOLESS
ACCESS PANELS
•
BAROMETRIC RELIEF DAMPER - Contains a rain
hood, air inlet screen, exhaust damper and mounting
hardware. Used to relieve internal air pressure through
the unit.
•
2" PLEATED FILTERS
•
DISCONNECT SWITCH
•
SUPPLY AIR SMOKE DETECTOR
•
PROPANE CONVERSION KIT - Contains new orifices
and gas valve parts to convert from natural to L.P. gas.
One per unit required.
•
RETURN AIR SMOKE DETECTOR
•
HIGH ALTITUDE - NATURAL GAS - Contains orifices
required for applications between 2000 and 6000 feet
altitude.
•
HIGH ALTITUDE - PROPANE GAS - Contains orifices
required for applications between 2000 and 6000 feet
altitude. Must be used with propane conversion kit.
38
Unitary Products Group
254596-YTG-A-0306
Unitary Products Group
39
Subject to change without notice. Printed in U.S.A.