Bryant 558J Legacy Rooftop Electric Heating/Electric Cooling Service manual
Add to my manuals80 Pages
advertisement
▼
Scroll to page 2
of 80
558J 17-30 Nominal 15 to 27.5 Tons With Puron ® (R-410A) Refrigerant Service and Maintenance Instructions TABLE OF CONTENTS SAFETY CONSIDERATIONS TABLE OF CONTENTS . . . . . . . . . . . . . . . . . . . . . . . . . 1 Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment. Untrained personnel can perform the basic maintenance functions of replacing filters. Trained service personnel should perform all other operations. SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . 1 UNIT ARRANGEMENT AND ACCESS . . . . . . . . 3 SUPPLY FAN (BLOWER) SECTION . . . . . . . . . . 4 2−SPEED FAN WITH VARIABLE FREQUENCY DRIVE (VFD) . . . . . . . . . . . . . . . . 6 ADDITIONAL VFD INSTALLATION AND TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . 7 COOLING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 EVAPORATOR COILS . . . . . . . . . . . . . . . . . . . . . . 11 PERFECT HUMIDITY™ DEHUMIDIFICATION SYSTEM . . . . . . . . . . . . . 13 THERMOSTATIC EXPANSION VALVE (TXV) . . 18 PURON (R−410A) REFRIGERANT . . . . . . . . . . 20 COOLING CHARGING CHARTS . . . . . . . . . . . . . 21 COMPRESSORS . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 TROUBLESHOOTING THE COOLING SYSTEM 27 CONVENIENCE OUTLETS . . . . . . . . . . . . . . . . . 28 SMOKE DETECTORS . . . . . . . . . . . . . . . . . . . . . . 29 INDICATORS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 PROTECTIVE DEVICES . . . . . . . . . . . . . . . . . . . . 36 RTU−OPEN CONTROL SYSTEM . . . . . . . . . . . . . . . . 38 ECONOMI$ER SYSTEMS . . . . . . . . . . . . . . . . . . . . . . 39 PRE−START−UP/START−UP . . . . . . . . . . . . . . . . . . . . 47 START−UP, GENERAL . . . . . . . . . . . . . . . . . . . . . . . . 48 START−UP, RTU−OPEN CONTROLS . . . . . . . . . . . . . 49 FASTENER TORQUE VALUES . . . . . . . . . . . . . . . . . 49 APPENDIX I. MODEL NUMBER NOMENCLATURE . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 APPENDIX II. PHYSICAL DATA . . . . . . . . . . . . . . . . 51 APPENDIX III. FAN PERFORMANCE . . . . . . . . . . . . 59 APPENDIX IV. WIRING DIAGRAMS . . . . . . . . . . . . 65 UNIT START-UP CHECKLIST . . . . . . . . . . . . . . . . . . 79 When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply. Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguishers available for all brazing operations. Follow all safety codes. Consult local building codes and National Electrical Code (NEC) for special requirements. Recognize safety information. This is the safety−alert . When you see this symbol on the unit and in symbol instructions or manuals, be aware of the potential for physical injury hazards. Understand the signal words DANGER, WARNING, and CAUTION. These words are used with the safety−alert symbol. DANGER identifies a hazardous situation which, if not avoided, will result in death or severe personal injury. WARNING indicates a hazardous situation which, if not avoided, could result in death or personal injury. CAUTION indicates a hazardous situation which, if not avoided, could result in minor to moderate injury or product and property damage. NOTICE is used to address practices not related to physical injury. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation. ! CAUTION CUT HAZARD Failure to follow this caution may result in personal injury. Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts and servicing air conditioning equipment. WARNING ! NOTICE FIRE, EXPLOSION HAZARD Failure to follow this warning could result in death, personal personal injury and/or property damage. OPERATIONAL TEST ALERT Failure to follow this ALERT could result in an unnecessary evacuation of the facility. Pressing the controller’s test/reset switch for longer than seven seconds will put the duct detector into the alarm state and activate all automatic alarm responses. Never use air or gases containing oxygen for leak testing or for operating refrigerant compressors. Pressurized mixtures of air or gases containing oxygen can lead to an explosion. ! ELECTRICAL SHOCK HAZARD Failure to follow this warning could cause personal injury or death. Before performing service or maintenance operations on the fan system, shut off all unit power and Lockout/Tagout the unit disconnect switch. DO NOT reach into the fan section with power still applied to the unit. WARNING ! FIRE, EXPLOSION HAZARD Failure to follow this warning could result in death, personal personal injury and/or property damage. Never use non−certified refrigerants in this product. Non−certified refrigerant could contain contaminant that could lead to unsafe operating conditions. Use ONLY refrigerants that conform to AHRI Standard 700. ! UNIT OPERATION AND SAFETY HAZARD Failure to follow this warning could cause personal injury, death and/or equipment damage. This system uses Puron refrigerant which has higher pressures than R−22 and other refrigerants. No other refrigerant may be used in this system. Gauge set, hoses, and recovery system must be designed to handle Puron refrigerant. If unsure about equipment, consult the equipment manufacturer. ! WARNING ELECTRICAL OPERATION HAZARD Failure to follow this warning could result in personal injury or death. Units with convenience outlet circuits may use multiple disconnects. Check the convenience outlet for power status before opening the unit for service. Locate its disconnect switch, if appropriate, and open it. Lockout/Tagout this switch if necessary. WARNING ! WARNING IMPORTANT: Lockout/Tagout is a term used when electrical power switches are physically locked, preventing power to the unit. A placard is placed on the power switch, alerting personnel that the power is disconnected. CAUTION UNIT DAMAGE HAZARD Failure to follow this caution can result in reduced unit performance or unit shutdown. High velocity water from a pressure washer, garden hose, or compressed air should never be used to clean a coil. The force of the water or air jet will bend the fin edges and increase airside pressure drop. 2 UNIT ARRANGEMENT AND ACCESS Seasonal Maintenance These items should be checked at the beginning of each season (or more often if local conditions and usage patterns dictate): General Fig. 1 and Fig. 2 show general unit arrangement and access locations. SUPPLY FAN HEATING SECTION Air Conditioning Condenser fan motor mounting bolts tightness OUTDOOR FANS/MOTORS OUTDOOR AIR HOOD Compressor mounting bolts Condenser fan blade positioning Control box cleanliness and wiring condition Wire terminal tightness Refrigerant charge level DISCONNECT CONVENIENCE OUTLET CONTROL BOX ACCESS PANEL Evaporator coil cleaning CONDENSER COIL (CIRCUIT A) RETURN AIR FILTER AND INDOOR COIL ACCESS PANEL GAS SECTION ACCESS PANEL Evaporator blower motor amperage COMPRESSOR (CIRCUIT A) Heating C12560 Fig. 1 − Access Panels and Components, Front Heat exchanger flue passageways cleanliness Gas burner condition Gas manifold pressure Heating temperature rise Economizer or Outside Air Damper Inlet filters condition Check damper travel (economizer) Check gear and dampers for debris and dirt CONDENSER COIL CIRCUIT A CONDENSER COIL CIRCUIT B Air Filters and Screens COMPRESSOR CIRCUIT B Each unit is equipped with return air filters. If the unit has an economizer, it will also have an outside air screen. If a manual outside air damper is added, an inlet air screen will also be present. C09505 Fig. 2 − Typical Access Panel Locations, Rear Routine Maintenance Each of these filters and screens will need to be periodically replaced or cleaned. These items should be part of a routine maintenance program, to be checked every month or two, until a specific schedule for each can be identified for this installation: Return Air Filters Return air filters are disposable fiberglass media type. Access to the filters is through the small lift−out panel located on the rear side of the unit, above the evaporator/return air access panel. (See Fig. 1.) Quarterly Inspection (and 30 days after initial start) The 558J units should be inspected and serviced every three months. ! Return air filter replacement Outdoor hood inlet filters cleaned CAUTION EQUIPMENT DAMAGE HAZARD Failure to follow this CAUTION can result in premature wear and damage to equipment. DO NOT OPERATE THE UNIT WITHOUT THE RETURN AIR FILTERS IN PLACE. Dirt and debris on heat exchangers and coils can cause excessive current use, resulting in motor failure. Belt tension checked Belt condition checked Pulley alignment checked Fan shaft bearing locking collar tightness checked Condenser coil cleanliness checked Condensate drain checked 3 Removing the Return Air Filters 1. Remove the return air filter and indoor coil access panel. See Fig. 1. 2. Reach inside and remove filters from the filter rack. 3. Replace these filters as required with similar replacement filters of same size. 4. Re−install the return air filter and indoor coil access panel. Supply Fan Assembly Outdoor Air Hood Vertical Supply Models The supply fan system consists of two forward−curved centrifugal blower wheels mounted on a solid blower shaft that is supported by two greaseable pillow block concentric bearings. A fixed−pitch driven fan pulley is attached to the fan shaft and an adjustable−pitch driver pulley is mounted on the motor. The pulleys are connected using a V−belt. (See Fig. 4.) Outside air hood inlet screens are permanent aluminum−mesh type filters. See Fig. 2. Inspect these screens for cleanliness. Remove the screens when cleaning is required. Clean by washing with hot low−pressure water and soft detergent and replace all screens before restarting the unit. Observe the flow direction arrows on the side of each filter frame. The two fan wheels used on the vertical supply models are the same: 15″ diameter x 15″ width. This arrangement provides uniform airflow distribution across the width of the evaporator coil, electric heater, and into the supply duct. Horizontal Supply Models Economizer Inlet Air Screen This air screen is retained by spring clips under the top edge of the hood. (See Fig. 3.) The horizontal supply models have two different fan wheel sizes on a single shaft. The front side wheel is 18″ diameter x 15″ wide, while the rear side fan is 15″ diameter x 11″ wide. This arrangement promotes uniform airflow across the width of the evaporator coil and heater assembly while using a supply outlet on the rear side of the unit. 17 1/4 (438 mm) NOTE: This major difference in the fan system design makes it impossible to field−convert the 558J unit’s supply fan outlet configuration. DIVIDER 15” X 15” SUPPLY FANS OUTSIDE AIR HOOD CLEANABLE ALUMINUM SCREEN BAROMETRIC RELIEF FILTER CLIP C06027 Fig. 3 − Inlet Air Screen Installation VERTICAL SUPPLY FANS Remove screens be removing the screws in the horizontal clips on the leading edge of the hood. Slide the filters out. See Fig. 3. 15” X 11” SUPPLY FAN Install the filters by sliding clean or new filters into the hood side retainers. Once positioned, re−install the horizontal clips. 18” X 15” SUPPLY FAN SUPPLY FAN (BLOWER) SECTION ! WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could cause personal injury or death. Before performing service or maintenance operations on the fan system, shut off all unit power and Lockout/Tagout the unit disconnect switch. DO NOT reach into the fan section with power still applied to the unit. HORIZONTAL SUPPLY FANS C12683 Fig. 4 − Supply Fan Arrangements 4 Belt 5. Make sure the fan shaft and motor shaft are parallel before tightening the motor mount nuts. See Fig. 6. 6. Make adjustments as necessary. 7. Tighten the four motor mounting nuts. 8. Check the V−belt tension. Make adjustments as necessary. 9. Re−tighten the four motor mounting nuts. 10. Tighten both jack bolt locking nuts securely. Check the belt condition and tension quarterly. Inspect the belt for signs of cracking, fraying or glazing along the inside surfaces. Check belt tension by using a spring−force tool, such as Browning’s “Belt Tension Checker” (p/n 1302546 or equivalent tool); tension should be 6−lbs at a 5/8−in. (1.6 cm) deflection when measured at the center line of the belt span. This point is at the center of the belt when measuring the distance between the motor shaft and the blower shaft. Replacing the V−belt 1. Use a belt with same section type or similar size. Do not substitute a “FHP” or notched type V−belt. 2. Loosen (turn counterclockwise) the motor mounting plate front bolts and rear bolts. See Fig. 4. BLOWER 15” X 17” BLOWER SHAFT BLOWER 18” X 15” V-BELT ! MOTOR CAUTION EQUIPMENT DAMAGE HAZARD Failure to follow this CAUTION can result in premature wear and damage to equipment. Do not use a screwdriver or pry−bar to place the new V−belt in the pulley groove. This can cause stress on the V−belt and the pulley, resulting in premature wear on the V−belt and damage to the pulley. MOTOR ADJUSTMENT BOLTS (4) JACKBOLT LOCKING NUT (2) MOTOR MOUNTING PLATE JACKBOLT (2) C12260 Fig. 5 − Belt Drive Motor Mounting 3. Loosen (turn counterclockwise) the jack bolt lock nuts. Loosen (turn counterclockwise) the jack bolts, relieving the belt tension and allowing easy removal of the belt by hand. 4. Remove the belt by gently lifting the old belt over one of the pulleys. 5. Install the new belt by gently sliding the belt over both pulleys, then tighten (turn clockwise) the jack bolts, sliding the motor plate away from the fan housing until proper belt tension is achieved. 6. Check the alignment of the pulleys, adjust if necessary. See Fig. 6. 7. Tighten all bolts attaching the motor to the motor plate. 8. Tighten all jack bolt jam nuts by turning clockwise. 9. Check the tension after a few hours of runtime and re−adjust as required. See Fig. 5. NOTE: Without the spring−tension tool, place a straight edge across the belt surface at the pulleys, then push down on the belt at mid−span using one finger until a 1/2−in. (1.3 cm) deflection is reached. STRAIGHTEDGE BROWNING BELT TENSION CHECKER 1/2” (1.3 cm) BELT DEFLECTION Adjustable−Pitch Pulley on Motor C12093 Fig. 6 − Checking Blower Moter Belt Tension The motor pulley is an adjustable−pitch type that allows a servicer to implement changes in the fan wheel speed to match as−installed ductwork systems. The pulley consists of a fixed flange side that faces the motor (secured to the motor shaft) and a movable flange side that can be rotated around the fixed flange side that increases or reduces the pitch diameter of this driver pulley. (See Fig. 6.) Adjusting the Belt Tension Use the following steps to adjust the V−belt tension. See Fig. 4. 1. Loosen the four motor mounting nuts that attach the motor to the blower rail. 2. Loosen the two jack bolt locking nuts beneath the motor mounting plate. Turn the jack bolt locking nut counterclockwise to loosen. 3. Turn the jack bolts counterclockwise to loosen and clockwise to tighten. 4. Adjust the V−belt for proper tension. As the pitch diameter is changed by adjusting the position of the movable flange, the centerline on this pulley shifts laterally, along the motor shaft. This creates a requirement for a realignment of the pulleys after any adjustment of the movable flange. Also reset the belt tension after each realignment. The factory settings of the adjustable pulley is five turns open from full closed. 5 Check the condition of the motor pulley for signs of wear. Glazing of the belt contact surfaces and erosion on these surfaces are signs of improper belt tension and/or belt slippage. Pulley replacement may be necessary. LOCKING COLLAR Changing Fan Speed 1. Shut off the main unit power supply, and use the approved Lockout/Tagout procedures. 2. Loosen the belt by loosening the motor adjustment bolts as described in the Belt Adjustment section above. 3. Loosen the movable pulley flange setscrew. (See Fig. 6.) 4. Screw the movable flange toward fixed flange to increase speed and away from fixed flange to decrease speed. Increasing fan speed increases load on the motor. Do not exceed maximum speed specified in the Product Data or motor amperage listed on the unit rating plate.. 5. Set the movable flange at the nearest keyway or flat of the pulley hub and tighten the setscrew to torque of 72 ± 5 in−lbs (8.14 ± 0.56 Nm). T-25 TORX SOCKET HEAD CAP SCREW C11505 Fig. 8 − Tightening Locking Collar 2−SPEED FAN WITH VARIABLE FREQUENCY DRIVE (VFD) 2−Speed Indoor Fan Speed System The 2-speed fan utilizes a Fan Speed control board and Variable Frequency Drive (VFD) to automatically adjust the indoor fan motor speed in sequence with the unit’s ventilation, cooling and heating operation. Conforming to ASHRAE 90.1 2010 Standard Section 6.4.3.10.b, during the first stage of cooling operation the SAV system will adjust the fan motor to provide two- thirds (2/3) of the design airflow rate for the unit. Aligning the Fan and Motor Pulleys 1. Loosen the fan pulley setscrews. 2. Slide the fan pulley along the fan shaft. Make angular alignment by loosening the motor from its mounting. See Fig. 7. 3. Tighten the fan pulley setscrews and motor mounting bolts to torque specifications. 4. Recheck the belt tension. See Fig. 6. When the call for the second stage of cooling is required, the 2-speed fan will allow the design airflow rate for the unit established (100%). During the heating mode, the SAV system will allow total design airflow rate (100%) operation. During ventilation mode, the 2-speed fan will operate the fan motor at 2/3 speed. Identifying Factory Option This supplement only applies to units that meet the criteria detailed in Table 1. If the unit does not meet that criteria, discard this document. Table 1 – Model−Size / VFD Option Indicator Model / Sizes Position in Model Number VDP FIOP Indicator 558J 17 − 30 17 G, J See Appendix I for the Model Number Nomenclature breakdown. Unit Installation with 2−Speed Fan Option C07075 Fig. 7 − Supply−Fan Pulley Adjustment 558J Rooftop—Refer to the base unit installation instructions for standard required operating and service clearances. Bearings This fan system uses bearings featuring concentric split locking collars. The collars are tightened through a cap screw bridging the split portion of the collar. The cap screw has a Torx T25 socket head. To tighten the locking collar: Hold the locking collar tightly against the inner race of the bearing and torque the cap screw to 65−70 in−lb (7.4−7.9 Nm). See Fig. 8. NOTE: The Remote VFD Keypad is a field-installed op tion. It is not included as part of the Factory installed VFD option. See “Variable Frequency Drive (VFD) Installa tion, Setup and Troubleshooting Supplement” for wiring schematics and performance charts and configuration. See Fig. 9 for location of the (VFD) as mounted on the various 558J models. 6 ! Variable Frequency Drive (VFD) CAUTION EQUIPMENT DAMAGE HAZARD Failure to follow this CAUTION can result in premature wear and damage to equipment. Do not use a screwdriver or pry−bar to place the new V−belt in the pulley groove. This can cause stress on the V−belt and the pulley, resulting in premature wear on the V−belt and damage to the pulley. 7. Loosen the four mounting bracket bolts and lock washers. 8. Remove four bolts, four flat washers, four lock wash ers and four nuts attaching the motor mounting plate to the unit. Discard all lock washers. 9. Remove the motor and motor mounting bracket from the unit. 10. Remove four bolts, flat washers, lock washers and single external-tooth lock washer attaching the motor to the motor mounting plate. Discard all lock washers and external-tooth lock washer. 11. Lift the motor from the motor mounting plate and set aside. 12. Slide the motor mounting band from the old motor. 13. Slide the motor mounting band onto the new motor and set the motor onto the motor mounting plate. 14. Remove the variable pitch pulley from the old motor and attach it to the new motor. 15. Inspect the variable pitch pulley for cracks and wear. Replace the pulley if necessary. 16. Secure the pulley to the motor by tightening the pul ley setscrew to the motor shaft. 17. Insert four bolts and flat washers through the mount ing holes on the motor and into holes on the motor mounting plate. 18. On one bolt, place a new external-tooth lock washer between the motor and motor mounting band. 19. Make sure the teeth of the external-tooth lock washer make contact with the painted base of the motor. This washer is essential for properly grounding the motor. 20. Install four new lock washers and four nuts on the bolts on the bottom of the motor mounting plate, but do not tighten the mounting bolts at this time. 21. Set the new motor and motor mounting bracket back onto the unit. See Fig. 10. 22. Install four bolts, four flat washers, four new lock washers and four nuts attaching the motor assembly to the unit, but do not tighten the mounting bolts at this time. 23. Install the motor drive V-belt to the motor pulley and blower wheel pulley. See CAUTION. 24. Align the motor pulley and blower wheel pulley using a straight edge. See Fig. 7. 25. Adjust the V-belt tension using the adjustment tool. 26. Turn the two jack bolts clockwise, moving the motor assembly away from the blower pulley, increasing the V-belt tension. C11531 Fig. 9 − VFD Location for 50HC 15–27.5 Units ADDITIONAL VFD INSTALLATION AND TROUBLESHOOTING Additional installation, wiring and troubleshooting infor mation for the VFD can be found in the following manu als: “Variable Frequency Drive (VFD) Installation, Setup and Troubleshooting Supplement.” Motor When replacing the motor, use the following steps. See Fig. 10. BLOWER PULLEY V-BELT MOTOR PULLEY MOTOR MOTOR MOUNTING BOLTS (4) JACK BOLT JAM NUT (2) JACK BOLT (2) C12034 Fig. 10 − Replacing Belt Driven Motor Replacing the Motor 1. Turn off all electrical power to the unit. Use approved lockout/tagout procedures on all electrical power sources. 2. Remove the cover on the motor connection box. 3. Disconnect all electrical leads to the motor. 4. Loosen the two jack bolt jamnuts on the motor mounting bracket. 5. Turn the two jack bolts counterclockwise until the motor assembly moves closer to the blower pulley. 6. Remove the V-belt from the blower pulley and motor pulley. 7 27. Tighten the four bolts securing the motor mounting brackets to the unit. Torque bolts to 120 ± 12 in-lbs (14 ± 1.4 Nm). 28. Remove the cover on the motor connection box. 29. Re-connect all electrical leads to the motor and re place the connection box cover. 30. Re-connect all electrical power to the unit. Remove lockout tags on all electrical power sources. 31. Start the unit and allow to run for a designated period. 32. Shut off the unit and make any necessary adjustments to the V-belt tension or the motor and blower wheel pulley alignment. To reduce vibration, replace the motor’s adjustable pitch pulley with a fixed pitch pulley (after the final airflow balance adjustment). This will reduce the amount of vibration generated by the motor/belt-drive system. To determine variable pitch pulley diameter, perform the following calculation: 1. Determine full open and full closed pulley diameter. 2. Subtract the full open diameter from the full closed diameter. 3. Divide that number by the number of pulley turns open from full closed This number is the change in pitch datum per turn open. STRAIGHTEDGE EXAMPLE: – Pulley dimensions 2.9 to 3.9 (full close to full open) – 3.9 - 2.9 = 1 – 1 divided by 5 (turns from full close to full open) – 0.2 change in pulley diameter per turn open – 2.9 + 0.2 = 3.1″ pulley diameter when pulley closed one turn from full open BROWNING BELT TENSION CHECKER 1/2” (1.3 cm) COOLING BELT DEFLECTION UNIT OPERATION AND SAFETY HAZARD Failure to follow this warning could cause personal injury, death and/or equipment damage. This system uses Puron refrigerant which has higher pressures than R−22 and other refrigerants. No other refrigerant can be used in this system. Gauge set, hoses, and recovery system must be designed to handle Puron refrigerant. If unsure about equipment, consult the equipment manufacturer. C12093 Fig. 11 − Adjusting V−belt Tension Changing Fan Wheel Speed by Changing Pulleys The horsepower rating of the belt is primarily dictated by the pitch diameter of the smaller pulley in the drive system (typically the motor pulley in these units). Do not install a replacement motor pulley with a smaller pitch diameter than provided on the original factory pulley. Change fan wheel speed by changing the fixed fan pulley (larger pitch diameter to reduce wheel speed, smaller pitch diameter to increase wheel speed) or select a new system with both pulleys and matching belt(s). ! WARNING FIRE, EXPLOSION HAZARD Failure to follow this warning could result in death, serious personal injury and/or property damage. Never use non−certified refrigerants in this product. Non−certified refrigerants could contain contaminates that could lead to unsafe operating conditions. Use ONLY refrigerants that conform to AHRI Standard 700. Before changing pulleys to increase fan wheel speed, check the fan performance at the target speed and airflow rate to determine new motor loading (bhp). Use the fan performance tables or use the Packaged Rooftop Builder software program. Confirm that the motor in this unit is capable of operating at the new operating condition. Fan shaft loading increases dramatically as wheel speed is increased. ! WARNING ! ROUND TUBE PLATE FIN (RTPF) CONDENSER COIL CAUTION EQUIPMENT DAMAGE HAZARD Failure to follow this CAUTION can result in equipment damage. Drive packages cannot be changed in the field. For example: a standard drive cannot be changed to a high static drive. This type of change will alter the unit’s certification and could require heavier wiring to support the higher amperage draw of the drive package. The condenser coil is fabricated with round tube copper hairpins and plate fins of various materials and/or coatings, and are also available with optional all−aluminum NOVATION coil construction. Check position 11 on the unit’s informative data plate for coil construction code, then refer to the Model Number Nomenclature in Appendix 1 to identify the materials provided in this unit. The coil may be one−row or 8 composite−type two−row. Composite two−row coils are two single−row coils fabricated with a single return bend end tubesheet. ! EQUIPMENT DAMAGE HAZARD Failure to follow this caution can result in equipment damage. DO NOT use Totaline® environmentally sound coil cleaner on the aluminum NOVATION condenser. Damage to the coil can occur. Only clean potable water is authorized for cleaning. NOVATION (MCHX) Condenser Coil The condenser coil uses new NOVATION® Heat Exchanger Technology or Microchannel Heat Exchanger. Coil (MCHX). This is an all−aluminum construction with louvered fins over single−depth crosstubes. The crosstubes have multiple small passages (microchannels) through which the refrigerant passes from header to header on each end. Tubes and fins are made of aluminum. Connection tube joints are made of copper. The coil can be one−row or two−row. Two−row coils are spaced apart to assist in cleaning. See Fig. 12. ! WARNING UNIT OPERATION AND SAFETY HAZARD Failure to follow this warning could cause personal injury, death. Using a high pressure washer (900 psig − 6205 kPa) to clean coils can cause severe injury or death if spray is aimed at service personnel. Do not use a high pressure washer to clean hands and do not direct spray in direction of eyes or other tissue. Routine Cleaning of NOVATION Condenser Coil Surfaces DO NOT clean the NOVATION condenser coil with chemicals. ONLY water is approved as the cleaning solution. Only clean potable water is authorized for cleaning NOVATION condensers. Carefully remove any foreign objects or debris attached to the coil face or trapped within the mounting frame and brackets. Using a high pressure water sprayer, purge any soap or industrial cleaners from hose and/or dilution tank prior to wetting the coil. ! CAUTION Recommended Condenser Coil Maintenance and Cleaning Routine cleaning of coil surfaces is essential to maintain proper operation of the unit. Elimination of contamination and removal of harmful residues will greatly increase the life of the coil and extend the life of the unit. The following maintenance and cleaning procedures are recommended as part of the routine maintenance activities to extend the life of the coil. WARNING EXPLOSION HAZARD Failure to follow this warning could result in death, serious personal injury, and/or property damage. Never use air or gases containing oxygen for leak testing or operating refrigerant compressors. Pressurized mixtures of air or gases containing oxygen can lead to an explosion. Remove Surface Loaded Fibers Surface loaded fibers or dirt should be removed with a vacuum cleaner. If a vacuum cleaner is not available, a soft non−metallic bristle brush may be used. In either case, the tool should be applied in the direction of the fins. Coil surfaces can be easily damaged (fin edges can be easily bent over and damage to the coating of a protected coil) if the tool is applied across the fins. FINS NOTE: Use of a water stream, such as a garden hose, against a surface loaded coil will drive the fibers and dirt into the coil. This will make cleaning efforts more difficult. Surface loaded fibers must be completely removed prior to using low−velocity clean water rinse. Periodic Clean Water Rinse A periodic clean water rinse is very beneficial for coils that are applied in coastal or industrial environments. However, it is very important that the water rinse is made with a very low−velocity water stream to avoid damaging the fin edges. Monthly cleaning as described below is recommended. TUBES MANIFOLD MICROCHANNELS C07273B Fig. 12 − Novation (Microchannel) Coil 9 CAUTION UNIT DAMAGE HAZARD Failure to follow this CAUTION can result in reduced unit performance or unit shutdown. Use only the recommended approved cleaning procedures for proper system performance. Routine Cleaning of Coil Surfaces Periodic cleaning with Totaline environmentally sound coil cleaner is essential to extend the life of coils. This cleaner is available from the Replacement Components Division as p/n: P902- 0301 for one-gallon (3.8L) container, and P902- 0305 for a 5-gallon (18.9L) container. It is recommended that all coils, including standard aluminum, pre−coated, copper/copper or E−coated coils be cleaned with the Totaline environmentally sound coil cleaner as described below. Coil cleaning should be part of the unit’s regularly scheduled maintenance procedures to ensure long life of the coil. Failure to clean the coils may result in reduced durability in the environment. C08205 Fig. 13 − Cleaning Condenser Coil Avoid use of: coil brighteners C08206 Fig. 14 − Propping Up Top Panel acid cleaning prior to painting high pressure washers 6. Remove the screws securing the coil to the compressor plate and compressor access panel. 7. Remove the fasteners holding the coil sections together at the return end of the condenser coil. Carefully separate the outer coil section 3 to 4 in. from the inner coil section. See Fig. 15. poor quality water for cleaning Totaline environmentally sound coil cleaner is a nonflammable, hypo allergenic, non bacterial, USDA accepted biodegradable agent that will not harm the coil or surrounding components such as electrical wiring, painted metal surfaces, or insulation. Use of non−recommended coil cleaners is strongly discouraged since coil and unit durability could be affected. Two−Row Coils Clean coil as follows: 1. Turn off unit power and tag the disconnect. 2. Remove the top panel screws on the condenser end of the unit. 3. Remove the condenser coil corner post. See Fig. 13. 4. Lift and hold the top cover open. 5. Hold the top pan open by placing the coil corner post between the top panel and center post. See Fig. 14. C08207 Fig. 15 − Separating Coil Sections 8. Clean the outer surfaces with a stiff brush in the normal manner. Use a water hose or other suitable equipment to flush down between the 2 coil sections to remove dirt and debris. 9. Secure the inner and outer coil rows together with a field−supplied fastener. 10. Reposition the outer coil section and remove the coil corner post from between the top panel and center post. Reinstall the coil corner post and access panel. 11. Replace all screws. 10 EVAPORATOR COILS Totaline environmentally sound coil cleaner is a nonflammable, hypo allergenic, non bacterial, USDA accepted biodegradable agent that will not harm the coil or surrounding components such as electrical wiring, painted metal surfaces, or insulation. Use of non−recommended coil cleaners is strongly discouraged since coil and unit durability could be affected. The evaporator coil uses the traditional round-tube, plate-fin (RTPF) technology. Tube and fin construction consists of various optional materials and coatings (see APPENDIX I). Coils are multiple-row. On two-compressor units, the evaporator coil is a face split design, meaning the two refrigerant circuits are independent in the coil. The bottom portion of the coil will always be circuit A, with the top of the coil being circuit B. TotalineR Environmentally Sound Coil Cleaner Application Equipment 2−1/2 gallon garden sprayer Coil Maintenance and Cleaning Recommendation Water rinse with low velocity spray nozzle Routine cleaning of coil surfaces is essential to maintain proper operation of the unit. Elimination of contamination and removal of harmful residues will greatly increase the life of the coil and extend the life of the unit. The following maintenance and cleaning procedures are recommended as part of the routine maintenance activities to extend the life of the coil. ! WARNING PERSONAL INJURY HAZARD Failure to follow this WARNING can result in severe personal injury and reduced unit performance. High−velocity water from a pressure washer, garden hose, or compressed air should never be used to clean a coil. The force of the water or air jet will bend the fin edges and increase airside pressure drop. High−velocity water from a pressure washer can cause severe injury upon contact with exposed body tissue. Always direct the water stream away from the body. Removing Surface Loaded Fibers Surface loaded fibers or dirt should be removed with a vacuum cleaner. If a vacuum cleaner is not available, a soft non- metallic bristle brush can be used. In either case, the tool should be applied in the direction of the fins. Coil surfaces can be easily damaged. Applying the tool across the fin edges can cause the edges to be easily bent over, damaging the coating of a protected coil. NOTE: Use of a water stream, such as a garden hose, against a surface-loaded coil will drive the fibers and dirt into the coil. This will make cleaning efforts more difficult. Surface-loaded fibers must be completely removed prior to using a low-velocity clean water rinse. A vacuum cleaner or a soft- bristled brush should be used to remove surface-loaded fibers and dirt. Totaline Environmentally Sound Coil Cleaner Application Instructions 1. Proper protection such as safety glasses, gloves and protective clothing are recommended during mixing and application. CAUTION Periodic Clean Water Rinse EQUIPMENT HAZARD Failure to follow this CAUTION can result in corrosion and damage to the unit. Harsh chemicals, household bleach or acid or basic cleaners should not be used to clean outdoor or indoor coils of any kind. These cleaners can be very difficult to rinse out of the coil and can accelerate corrosion at the fin/tube interface where dissimilar materials are in contact. If there is dirt below the surface of the coil, use the Totaline environmentally sound coil cleaner. A periodic clean-water rinse is very beneficial for coils that are used in coastal or industrial environments. However, it is very important that the water rinse is made with a very low-velocity water stream to avoid damage to the fin edges. Monthly cleaning, as described below, is recommended. Routine Cleaning of Evaporator Coil Surfaces Monthly cleaning with Totaline environmentally sound coil cleaner is essential to extend the life of the coils. This cleaner is available from the Replacement Parts Division (p/n: P902- 0301 for one-gallon (3.8L) container, and p/n: P902- 0305 for a 5-gallon (18.9L) container). It is recommended that all round tube coils be cleaned as described below. Coil cleaning should be part of the unit’s regularly scheduled maintenance procedures to ensure a long life for the coil. Failure to clean the coils can result in reduced durability in the environment. When cleaning the coils, avoid use of the following: 2. Remove all surface loaded fibers and dirt with a vacuum cleaner as described above. 3. Thoroughly wet finned surfaces with clean water and a low velocity garden hose, being careful not to bend fins. 4. Mix Totaline environmentally sound coil cleaner in a 2−1/2 gallon (9.6 L) garden sprayer according to the instructions included with the cleaner. The optimum solution temperature is 100F (38C). NOTE: Do NOT USE water in excess of 130F (54C), as the enzymatic activity will be destroyed. coil brighteners acid cleaning prior to painting high pressure washers poor quality water for cleaning 11 5. Thoroughly apply Totaline environmentally sound coil cleaner solution to all coil surfaces, including finned area, tube sheets and coil headers. 6. Hold the garden sprayer nozzle close to finned areas and apply cleaner with a vertical, up−and−down motion. 7. Avoid spraying in a horizontal pattern to minimize potential for fin damage. 8. Make sure the cleaner thoroughly penetrates deep into the finned areas. 9. Interior and exterior finned areas must be thoroughly cleaned. 10. Finned surfaces should remain wet with cleaning solution for 10 minutes. 11. Make sure surfaces are not allowed to dry before rinsing. Reapply cleaner as needed to ensure 10−minute saturation is achieved. 12. Thoroughly rinse all surfaces with low−velocity clean water using a downward rinsing motion of the spray nozzle. Protect fins from damage from the spray nozzle. Evaporator Coil Metering Devices The metering devices are multiple fixed−bore devices (Acutrol) swedged into the horizontal outlet tubes from the liquid header, located at the entrance to each evaporator coil circuit path. These are non−adjustable. Service requires replacing the entire liquid header assembly. (IFC) coil, then start the compressor and observe the frosting pattern on the face of the evaporator coil. A frost pattern should develop uniformly across the face of the coil starting at each horizontal header tube. Failure to develop frost at an outlet tube can indicate a plugged or a missing orifice. Refrigerant System Pressure Access Ports There are two access ports in the system − on the suction tube near the compressor and on the discharge tube near the compressor. These are brass fittings with black plastic caps. The hose connection fittings are standard 1/4 SAE male flare couplings. The brass fittings are two−piece High Flow valves, with a receptacle base brazed to the tubing and an integral spring−closed check valve core screwed into the base (See Fig. 16). This schrader valve is permanently assembled into this core body and cannot be serviced separately; replace the entire core body if necessary. Service tools are available from RCD (p/n P920−0010) that allow the replacement of the schrader valve core without having to recover the entire system refrigerant charge. Apply compressor refrigerant oil to the schrader valve core’s bottom o−ring. Install the fitting body with 96 ± 10 in−lbs (10.85 ± 1.13 Nm) of torque; do not over−tighten. NOTE: The High−Flow valve has a black plastic cap with a rubber o−ring located inside the cap. This rubber o−ring must be in place in the cap to prevent refrigerant leaks. To check for possible blockage of one or more of these metering devices, disconnect the supply fan contactor o o C08453 Fig. 16 − CoreMax Access Port Assembly EXAMPLE: Model 558J*D28 Circuit A (from Fig. 15) Circuit B (from Fig. 15) Outdoor Temperature . . . . . . . . . . . . . . . . . . 85F (29C) Outdoor Temperature . . . . . . . . . . . . . . . . . . 85F (29C) Suction Pressure . . . . . . . . . . . . . . . . . 125 psig (860 kPa) Suction Pressure . . . . . . . . . . . . . . . . . 120 psig (830 kPa) Suction Temperature should be . . . . . . . . . . 63F (17C) Suction Temperature should be . . . . . . . . . . 58F (14C) 12 PERFECT HUMIDITY] DEHUMIDIFICATION SYSTEM During the Reheat1 or Subcooling mode, the liquid refrigerant flows from the outdoor compressor through the condenser coil to the Reheat1 (RH1.x) 3−way valve and on to the Perfect Humidity™ coil. The Reheat2 (RH2.x) valve is closed. The liquid refrigerant then passes through the Perfect Humidity™ coil and then a metering device or Thermostatic Expansion Valve (TXV). From the TXV, the liquid refrigerant passes through the evaporator coil and back to the outdoor compressor. See Fig 18. Units with the factory−equipped Perfect Humidity™ option are capable of providing multiple modes of improved dehumidification as a variation of the normal cooling cycle. See Fig 17. The design of the Perfect Humidity™ system allows for two humidity control modes of operation of the rooftop unit, utilizing a common subcooling/reheat dehumidification coil located downstream of the standard evaporator coil. This allows the rooftop unit to operate in both a dehumidification (Subcooling) mode and a hot gas (Reheat) mode for maximum system flexibility. The Perfect Humidity™ package is factory−installed and will operate whenever there is a dehumidification requirement present. Reheat2 (Hot Gas Reheat Mode) for A17 − A30 This Reheat2 or Hot Gas Reheat mode is used when dehumidification is required without a need for cooling, such as when the outside air is at a neutral temperature, but high humidity exists. This situation requires the equipment to operate at a low SHR of 0.0 to 0.2. With no cooling requirement calling for dehumidification, the Perfect Humidity™ dehumidification system will energize both compressors, opening the two hot gas bypass valves, allowing refrigerant flow to the Perfect Humidity™ coil to reheat the unit’s supply air to a neutral temperature. The Perfect Humidity™ system is initiated based on an input from a discrete input from a mechanical space or return air humidistat. Perfect Humidity] Modes The hot bypassed refrigerant liquid (gas or two−phase mixture) exits the outdoor compressor and passes through the open Reheat1 (RH1.x) at the same time it passes through the condenser coil to the open Reheat2 (Rh2.x) to the Perfect Humidity™ coil. After the refrigerant passes through the Perfect Humidity™ coil, it enters a TXV metering device, decreasing the air pressure, and on to the evaporator coil. The refrigerant is subcooled in this coil to a temperature approaching the evaporator leaving air temperature. The liquid refrigerant then returns to the outdoor compressor. See Fig. 19. Normal Cooling for Units A17 − A30 During the Normal Cooling mode, the liquid refrigerant flows from the outdoor condenser through the normally open (NO) Cooling System Valve (CSV) to the expansion device. Both the Reheat1 (RH1.x) and Reheat2 (RH2) valves are closed during the normal cooling mode. During the Normal Cooling mode, the refrigerant flows from the outdoor compressor through the condenser coil. The Reheat2 (RH2.x) is closed, preventing the refrigerant from bypassing the condenser coil. The refrigerant then flows through the open Reheat2 (RH1.x) 3−way valve to the TXV Metering Device, bypassing the Perfect Humidity™ coil, and finally passing through the evaporator coil before returning to the outdoor compressor. See Fig 17. The refrigerant enters the TXV and evaporator coil at a temperature lower than the temperature in the standard cooling operation. This lower temperature increases the latent capacity of the evaporator. The refrigerant passes through the evaporator turning it into a superheated vapor. The air passing over the evaporator coil becomes colder than it would during normal operation. As this same air passes over the Perfect Humidity™ Reheat Coil, it will be warmed to the neutral supply air temperature. Reheat1 (Subcooling Mode) for Units A17 − A30 Th Reheat1 or Subcooling mode will be engaged to satisfy part−load−type conditions when there is a space call for cooling and dehumidification. Although the temperature could have dropped and decreased the sensible load in the space, the outdoor and/or space humidity levels could have risen. A typical scenario could be when the outside air is 85F (29C) with 70% to 80% relative humidity (RH). Desired Sensible Heat Ratio (SHR) for equipment in this scenario is typically from 0.4 to 0.7. The Perfect Humidity™ unit will initiate the Dehumidification mode when both the space temperature and humidity are above the temperature and humidity setpoints while attempting to meet both setpoint requirements. Perfect Humidity] System Components The Perfect Humidity™ System uses the standard unit compressor(s), evaporator coil and Round Tube−Plate Fin (RTPF) condenser coil. Additional refrigeration system hardware includes a subcooler/reheat coil and control solenoid valves. On some models, the evaporator coil includes a TXV as a standard feature. Units with Perfect Humidity™ FIOP also include a factory−installed head pressure control system (Motormaster I) to provide proper liquid pressure during reheat modes. Unique system controls include a reheat relay mode, and evaporator coil freezestat, and secondary low pressure switch. Once the humidity requirement is met, the unit can continue to operate in normal cooling mode to meet any remaining sensible capacity load. Alternatively, if the sensible load is met and humidity levels remain high the unit can switch to Hot Gas Reheat mode or Reheat2 mode to provide neutral, dehumidified air. 13 Operating Sequences The Perfect Humidity™ system provides three sub−modes of operation: Normal Cooling, Reheat1 and Reheat2. The Reheat1 and Reheat2 modes are available when the unit is not in a heating mode and when the Low Ambient Lockout Switch is closed. When there is both cooling demand (thermostat Y1 demand) and dehumidification demand, circuit 1 will operate in Subcooling (Reheat1) mode. See Fig. 18 Schematic for system refrigerant flow. When there is only a single cooling demand, one or both circuits will operate in Hot Gas (Reheat2) mode. The DSV solenoid valve is open and the CSV solenoid is closed. See Fig. 19 schematic for system refrigerant flow. Subcooler/Reheat Coil The Subcooler/Reheat Coil is mounted across the leaving face of the unit’s evaporator coil. The coil is a one−row design with two separate circuits. INDOOR LEAVING AIR RDV1 VALVE LDV1 VALVE CONDENSER COIL PERFECT HUMIDITY COIL CIR 1 RDV2 VALVE LDV2 VALVE CONDENSER COIL CIR 2 OUTDOOR AIR OUTDOOR AIR TXV METERING DEVICE TXV METERING DEVICE COMPRESSOR CIR 1 = CLOSED VALVE COMPRESSOR CIR 2 EVAPORATOR COIL = OPEN VALVE = 3-WAY VALVE INDOOR ENTERING AIR C13851 Fig. 17 − Normal Cooling Mode – Perfect Humidity] System INDOOR LEAVING AIR RDV1 VALVE LDV1 VALVE CONDENSER COIL PERFECT HUMIDITY COIL CIR 1 CIR 2 RDV2 VALVE LDV2 VALVE CONDENSER COIL OUTDOOR AIR OUTDOOR AIR TXV METERING DEVICE TXV METERING DEVICE COMPRESSOR CIR 1 = CLOSED VALVE COMPRESSOR CIR 2 EVAPORATOR COIL = OPEN VALVE = 3-WAY VALVE INDOOR ENTERING AIR C13852 Fig. 18 − Subcooling Mode (Reheat 1) – Perfect Humidity] System 14 INDOOR LEAVING AIR RDV1 VALVE LDV1 VALVE CONDENSER COIL PERFECT HUMIDITY COIL CIR 1 RDV2 VALVE LDV2 VALVE CONDENSER COIL CIR 2 OUTDOOR AIR OUTDOOR AIR TXV METERING DEVICE TXV METERING DEVICE COMPRESSOR CIR 1 = CLOSED VALVE COMPRESSOR CIR 2 EVAPORATOR COIL = OPEN VALVE = 3-WAY VALVE INDOOR ENTERING AIR C13853 Fig. 19 − Hot Gas Reheat Mode (Reheat 2) – Perfect Humidity] System Table 2 – Perfect Humidity] Reheat Control Board I/O Point Name Type Humidistat/LTLO Thermostat W1 Econ Y1 Thermostat G 24V Power (J1) 24V Power (J2) Econ Y2 COMP1 IFM COMP2 LSV DSV1 NOT LSV DSV2 DI, 24VAC DI, 24VAC DI, 24VAC DI, 24VAC 24VAC 24 VAC DI, 24VAC DO, 24VAC DO, 24VAC DO, 24VAC DO, 24VAC DO, 24VAC DO, 24VAC DO, 24VAC Connection Pin Number J1A - 1 (1) J1A - 2 (2) J1A - 6 (6) J1B - 1 (7) J1B - 3 (9) J2 - 1 J1B - 5 (11) J1A - 5 (5) J1B - 4 (8) J1B - 4 (10) J2 - 2 J2 - 3 J2 - 4 J2 - 5 LEGEND COMP — Compressor CTB — Control Terminal Board DI — Discrete Input (switch) DO — Discrete Output (switch) DSV — Discharge (gas) Solenoid Valve ECON — Economizer FPT — Freeze Protection Thermostat IFM — Indoor (supply) Fan Motor LSV — Liquid Solenoid Valve LTLO — Low Temperature Lockout REHEAT — Connection Strip REHEAT (on CTB) 15 Unit Connection LTLO CTB - REHEAT - 4 CTB - REHEAT - 5 CTB - REHEAT - 1 CTB - R CTB - R CTB - REHEAT - 7 CTB - HEAT - 6 CTB - REHEAT - 2 CTB - REHEAT - 8 FTP (BLK) DSV Note 2 - circ only 2 - circ only 2 - circ only Table 3 – Inputs/Modes/Outputs Summary OFF ON HUM / LT LO OFF OFF ON OFF OFF OFF On OFF ON OFF OFF ON ON OFF ON OFF ON X OFF OFF ON OFF OFF ON OFF OFF ON ON ON ON OFF ON ON OFF OFF ON X ON OFF OFF ON + W2 X ON Y1 Y2 W1 G COMP COMP 1 2 MODE Normal Normal Fan Cool1 Normal Normal Reheat Subcool Cir1/ Reheat Cir2 Subcool Cir1 and Cir2 Heat Override Heat Override Cool2 Heat 1 Dehumidify Cool1 and Cool2 / Subcool-Dehumidify IFM LSV LSV2 1 LSV NOT DSV1 DSV2 OFF ON=Y 1 0N=Y2 OFF ON ON OFF OFF ON=G OFF ON=G OFF OFF OFF ON=R ON=R OFF OFF OFF OFF ON OFF ON ON ON=G OFF ON=G OFF ON=G ON ON=G ON OFF OFF ON ON ON=R ON=R OFF OFF OFF OFF ON=R OFF OFF OFF ON=R ON=R Cool1 and Cool2 / Subcool-Dehumidify ON ON ON=G ON ON OFF OFF OFF Heat 1 OFF OFF ON=G OFF OFF ON=R OFF OFF Heat 1 and 2 OFF OFF ON=G OFF OFF ON=R OFF OFF 16 Table 4 – Perfect Humidity] Troubleshooting PROBLEM Subcooling Reheat Mode Will Not Activate Hot Gas Reheat Mode Will Not Activate No Dehumidification Demand CAUSE REMEDY General cooling mode problem See Cooling Service Troubleshooting. No dehumidification demand See No Dehumidification Demand, below. CRC relay operation See CRC Relay Operation, below. Circuit RLV, CLV or LDV valve problem See CLV, RLV or LDV Valve Operation, below. General cooling mode problem See Cooling Service Troubleshooting. No dehumidification demand See No Dehumidification Demand, below. CRC relay operation See CRC Relay Operation, below. Circuit RLV, CLV or LDV valve problem See CLV, RLV or LDV Valve Operation, below. Circuit RDV valve is not open See RDV Valve Operation, below. Outdoor temperature too low Check Reheat 2 Circuit Limit Temperatures (Configuration → HMZR → RA.LO and RB.LO) using ComfortLink Scrolling Marquee. Relative humidity setpoint too low — Humidistat Check/reduce setting on accessory humidistat. Relative humidity setpoint too low — RH sensor Check Space RH Setpoints (Setpoints → RH.SP and RH.UN) and occupancy using ComfortLink Scrolling Marquee. Software configuration error for accessory humidistat Check Space Humidity Switch (Configuration UNIT RH.SW) using ComfortLink Scrolling Marquee. Software configuration error for accessory humidity sensor Check RH Sensor on OAQ Input (Configuration → UNIT → RH.S) using ComfortLink Scrolling Marquee. No humidity signal Check wiring. Check humidistat or humidity sensor. Check using Cool→Reheat1 Valve Test (Service Test → HMZR → CRC) using ComfortLink Scrolling Marquee. Check MBB relay output. No 24V signal to input terminals Check wiring. CRC Relay Operation Check transformer and circuit breaker. No power to output terminals Check wiring. Relay outputs do not change state Replace faulty relay. Check using Cool→Reheat1 Valve Test (Service Test → HMZR → CRC) using ComfortLink Scrolling Marquee. Check CRC Relay Operation. No 24V signal to input terminals Check Wiring. Check transformer and circuit beaker or fuses. RLV, CLV or LDV Valve Operation Check continuous over-voltage is less than 10%. Check under-voltage is less than 15%. Solenoid coil burnout Check for missing coil assembly parts. Check for damaged valve enclosing tube. Stuck valve Replace valve. Replace filter drier. Check using Cool→Reheat1 Valve Test (Service Test → HMZR → RHV.A or RHV.B) using ComfortLink Scrolling Marquee. Check MBB relay output. No 24V signal to input terminals Check wiring. Check transformer and circuit breaker or fuses. RDV Valve Operation (NOTE: Normally Closed When De-energized) Check continuous over-voltage is less than 10%. Check under-voltage is less than 15%. Solenoid coil burnout Check for missing coil assembly parts. Check for damaged valve enclosing tube. Stuck valve Replace valve. Replace filter drier. Low Latent Capacity in Subcool ing or Hot Gas Reheat Modes CLV valve open or leaking See CLV Valve Operation, above. Low Sensible Capacity in Normal Cool or Subcooling Reheat Modes RDV valve open or leaking See RDV Valve Operation, above. Low Suction Pressure and High Superheat During Normal Cool Mode General cooling mode problem See Cooling Service Troubleshooting (Table 4). RDV valve open or leaking See RDV Valve Operation, above. Low Suction Pressure and High Discharge Pressure General cooling mode problem See Cooling Service Troubleshooting (Table 4). Both RLV and CLV valves closed See RLV and CLV Valve Operation, above. RDV Valve Cycling On/Off Hot Gas Reheat mode low suction pressure limit Normal Operation During Mixed Circuit Subcooling and Hot Gas Reheat Modes at Lower Outdoor Temperatures. Circuit B Will Not Operate With Circuit A Off Normal operation. Motormaster outdoor fan control requires operation of circuit A. None LEGEND CRC — Cooling/Reheat Control CLV — Cooling Liquid Valve RLV — Reheat Liquid Valve RH — Relative Humidity RDV — Reheat Discharge Valve 17 THERMOSTATIC EXPANSION VALVE (TXV) All two−stage 558J units with Perfect Humidity™ have a factory installed nonadjustable thermostatic expansion valve (TXV). The TXV will be a bi-flow, bleed port expansion valve with an external equalizer. TXVs are specifically designed to operate with Puron or R-22 refrigerant, use only factory authorized TXVs. See Fig. 21. TXV Operation The TXV is a metering device that is used in air conditioning and heat pump systems to adjust to changing load conditions by maintaining a preset superheat temperature at the outlet of the evaporator coil. The volume of refrigerant metered through the valve seat is dependent upon the following: 1. Superheat temperature is sensed by the cap tube sensing bulb on suction the tube at the outlet of evaporator coil. This temperature is converted into pressure by refrigerant in the bulb pushing downward on the diaphragm which opens the valve using the push rods. 2. The suction pressure at the outlet of the evaporator coil is transferred through the external equalizer tube to the underside of the diaphragm. 3. The needle valve on the pin carrier is spring loaded, exerting pressure on the underside of the diaphragm. Therefore, the bulb pressure equals the evaporator pressure (at the outlet of the coil) plus the spring pressure. If the evaporator load increases, the temperature increases at the bulb, which increases the pressure on the topside of the diaphragm, pushing the carrier away from the seat, opening the valve and increasing the flow of refrigerant. The increased refrigerant flow causes increased leaving evaporator pressure which is transferred through the equalizer tube to the underside of the diaphragm. This causes the pin carrier spring pressure to close the TXV valve. The refrigerant flow is effectively stabilized to the load demand with a negligible change in superheat. Replacing TXV CAUTION PERSONAL INJURY HAZARD Failure to follow this CAUTION can result in injury to personnel and damage to components. Always wear approved safety glasses, work gloves, and other recommended Personal Protective Equipment (PPE) when working with refrigerants. 2. Using the gauge set approved for use with Puron (R− 410A) refrigerant, recover all refrigerant from the system. 3. Remove the TXV support clamp. 4. Disconnect the liquid line at the TXV inlet. 5. Remove the liquid line connection at the TXV inlet. 6. Remove the equalizer tube from the suction line of the coil. Use a tubing cutter to cut the brazed equalizer line approximately 2 inches (50 mm) above the suction tube. 7. Remove the bulb from the vapor tube above the evaporator coil header outlet. 8. Install the new TXV; avoid damage to the tubing or the valve when attaching the TXV to the distributor. Protect the TXV against over−temperature conditions by using wet rags and directing the torch flame tip away from the TXV body. Connect the liquid line to the TXV inlet by repeating the above process. 9. Attach the equalizer tube to the suction line. If the replacement TXV has a flare nut on its equalizer line, use a tubing cutter to remove the mechanical flare nut from the equalizer. Then use a coupling to braze the equalizer line to the stub (previous equalizer line) in the suction line. 10. Attach the TXV bulb in the same location as the original (in the sensing bulb indent), wrap the bulb in protective insulation and secure using the supplied bulb clamp. See Figs. 20 and 22. CAPILLARY TUBE TO TXV EQUALIZER TUBE FROM TXV VALVE TXV SENSOR BULB SENSOR BULB INDENT 15.9 mm (REF) DIRECTION OF REFRIGERANT FLOW SENSOR BULB INSULATION C10372 Fig. 20 − TXV Sensor Valve Insulation 11. Route the equalizer tube through the suction connection opening (large hole) in the fitting panel and install the fitting panel in place. 12. Sweat the inlet of the TXV marked “IN” to the liquid line. Avoid excessive heat which could damage the valve. 13. Check for leaks. 14. Evacuate the system completely and then recharge. 15. Remove the lockout/tagout on the main power switch and restore power to the unit. 16. Complete the charging procedure. 1. Disconnect all AC power to the unit. Use approved lockout/tagout procedures. 18 Refrigerant System Pressure Access Ports spring-closed check valve core screwed into the base. This check valve is permanently assembled into this core body and cannot be serviced separately; replace the entire core body if necessary. Service tools are available from RCD that allow the replacement of the check valve core without having to recover the entire system refrigerant charge. Apply compressor refrigerant oil to the check valve core’s bottom o-ring. Install the fitting body with 96 ±10 in-lbs of torque; do not over- tighten. There are two access ports in the system: on the suction tube near the compressor, and on the discharge tube near the compressor. These are brass fittings with black plastic caps. The hose connection fittings are standard 1/4 SAE male flare couplings. See Fig. 16. The brass fittings are two-piece High Flow valves, with a receptacle base brazed to the tubing and an integral CAPILLARY TUBE DIAPHRAGM PUSHRODS FEEDER TUBES INLET COIL OUTLET NEEDLE VALVE SPRING DISTRIBUTOR BULB EXTERNAL EQUALIZER TUBE C150325 Fig. 21 − Thermostatic Expansion Valve (TXV) Operation CLAMP TXV SENSOR BULBS TXV SENSOR BULB CIRCUIT 2 TXV SENSOR BULBS TXV (CIRCUIT 2) TXV (CIRCUIT 1) CIRCUIT 1 C12557 Fig. 22 − TXV Sensor Bulb Locations 19 PURONR (R−410A) REFRIGERANT This unit is designed for use with Puron (R−410A) refrigerant. Do not use any other refrigerant in this system. CAUTION UNIT DAMAGE HAZARD Failure to follow this CAUTION can result in damage to components. The compressor is in a Puron (R−410A) refrigerant system and uses a polyester (POE) oil. This oil is extremely hygroscopic, meaning it absorbs water readily. POE oils can absorb 15 times as much water as other oils designed for HCFC and CFC refrigerants. Avoid exposure of POE oil to the atmosphere. Exposure to the atmosphere can cause contaminants that are harmful to R−410A components to form. Keep POE oil containers closed until ready for use. Puron (R−410A) refrigerant is provided in pink (rose) colored cylinders. These cylinders are available with and without dip tubes; cylinders with dip tubes will have a label indicating this feature. For a cylinder with a dip tube, place the cylinder in the upright position (access valve at the top) when removing liquid refrigerant for charging. For a cylinder without a dip tube, invert the cylinder, with the access valve located on the bottom, when adding liquid refrigerant. Because Puron (R−410A) refrigerant is a blend, it is strongly recommended that refrigerant always be removed from the cylinder as a liquid. Admit liquid refrigerant into the system in the discharge line when breaking the refrigerant system vacuum while the compressor is OFF. Only add refrigerant (liquid) into the suction line while the compressor is operating. If adding refrigerant into the suction line, use a commercial metering/expansion device at the gauge manifold; remove liquid from the cylinder, pass it through the metering device at the gauge set, and then pass it into the suction line as a vapor. Do not remove Puron (R−410A) refrigerant from the cylinder as a vapor. Refrigerant Charge Unit panels must be in place when the unit is operating during the charging procedure. To prepare the unit for charge adjustment: No Charge Use standard evacuating techniques. Evacuate the system down to 500 microns and let set for 10 minutes to determine if the system has a refrigerant leak. If the evacuation level raises to 1100 microns and stabilizes, then the system has moisture in it and should be dehydrated as GTAC2-5 recommends. If the system continues to rise above 1100 microns, then the system has a leak and should be pressurized and leak tested using appropriate techniques as explained in GTAC2-5. After evacuating the system, weigh in the specified amount of refrigerant as listed on the unit's rating plate. Low−Charge Cooling Using the Cooling Charging Charts (Figs. 23 thru 30), vary the refrigerant until the conditions of the appropriate chart are met. Note the charging charts are different from the type normally used. These charts are based on charging the units to the correct superheat for the various operating conditions. Accurate pressure gauge and temperature sensing devices are required. Connect the pressure gauge to the service port on the suction line. Mount the temperature sensing device on the suction line and insulate it so the outdoor ambient temperature does not affect the reading. Indoor-air cfm must be within the normal operating range of the unit. SIZE DESIGNATION NOMINAL TON REFERENCE 17 20 24 28 15 17.5 20 25 EXAMPLE: Model 558J*D28 Circuit A Outdoor Temperature . . . . . . . . . . . . . . . . . . 85F (29C) Suction Pressure . . . . . . . . . . . . . . . . . 125 psig (860 kPa) Suction Temperature should be . . . . . . . . . . 63F (17C) Circuit B Outdoor Temperature . . . . . . . . . . . . . . . . . . 85F (29C) Suction Pressure . . . . . . . . . . . . . . . . . 120 psig (830 kPa) Suction Temperature should be . . . . . . . . . . 58F (14C) Using the Cooling Charging Charts Take the outdoor ambient temperature and read the suction pressure gauge. Refer to the chart to determine what the suction temperature should be. If the suction temperature is high, add refrigerant. If the suction temperature is low, carefully recover some of the charge. Recheck the suction pressure as the charge is adjusted. Select the appropriate unit charging chart from Figs. 23 thru 30. Note the outdoor ambient temperature and read the suction pressure gauge. Refer to the chart to determine what the suction temperature should be. If the suction temperature is high, add refrigerant. If the suction temperature is low, carefully recover some of the charge. Recheck the suction pressure as the charge is adjusted. For 17–28 sizes, perform this procedure once for Circuit A (using the Circuit A chart) and once for Circuit B (using the Circuit B chart). 20 COOLING CHARGING CHARTS COOLING CHARGING CHART 17.5 Ton - Circuit A 115F / 46.1C 105F / 40.6C 185.0 175.0 95F / 35.0C 85F / 29.4C 75F / 23.9C 65F / 18.3C 55F / 12.8C 45F / 7.2C Suction Pressure (psig) 165.0 155.0 145.0 135.0 125.0 115.0 105.0 95.0 85.0 75.0 °F °C 35 1.7 40 4.4 45 7.2 50 55 60 65 70 75 80 85 90 95 100 10.0 12.8 15.6 18.3 21.1 23.9 26.7 29.4 32.2 35.0 37.8 Suction Temperature 50HE501045-C C12227 Fig. 23 − Cooling Charging Chart − 15 Ton (Circuit A) COOLING CHARGING CHART 17.5 Ton - Circuit B 115F / 46.1C 105F / 40.6C 185.0 175.0 95F / 35.0C 85F / 29.4C 75F / 23.9C 65F / 18.3C 55F / 12.8C 45F / 7.2C Suction Pressure (psig) 165.0 155.0 145.0 135.0 125.0 115.0 105.0 95.0 85.0 75.0 °F °C 35 1.7 40 4.4 45 7.2 50 55 60 65 70 75 80 85 90 95 100 10.0 12.8 15.6 18.3 21.1 23.9 26.7 29.4 32.2 35.0 37.8 Suction Temperature 50HE501046-C 12228 Fig. 24 − Cooling Charging Chart − 15 Ton (Circuit B) 21 COOLING CHARGING CHARTS (cont.) COOLING CHARGING CHART 20 Ton - Circuit A 115F / 46.1C 105F / 40.6C 185.0 175.0 95F / 35.0C 85F / 29.4C 75F / 23.9C 65F / 18.3C 55F / 12.8C 45F / 7.2C Suction Pressure (psig) 165.0 155.0 145.0 135.0 125.0 115.0 105.0 95.0 85.0 75.0 °F °C 35 1.7 40 4.4 45 7.2 50 55 60 65 70 75 80 85 90 95 100 10.0 12.8 15.6 18.3 21.1 23.9 26.7 29.4 32.2 35.0 37.8 Suction Temperature 50HE501089-C C12229 Fig. 25 − Cooling Charging Chart − 17.5 Ton (Circuit A) C12230A Fig. 26 − Cooling Charging Chart − 17.5 Ton (Circuit B) 22 COOLING CHARGING CHARTS (cont.) C12231A Fig. 27 − Cooling Charging Chart − 20 Ton (Circuit A) C12232A Fig. 28 − Cooling Charging Chart − 20 Ton (Circuit B) 23 C12233A Fig. 29 − Cooling Charging Chart − 25 Ton (Circuit A) C12234A Fig. 30 − Cooling Charging Chart − 25 Ton (Circuit B) 24 COMPRESSORS ! Lubrication UNIT DAMAGE HAZARD Failure to follow this caution may result in damage to components. The compressor is in a Puron refrigerant system and uses a polyolester (POE) oil. This oil is extremely hygroscopic, meaning it absorbs water readily. POE oils can absorb 15 times as much water as other oils designed for HCFC and CFC refrigerants. Avoid exposure of the oil to the atmosphere. The compressor is charged with the correct amount of oil at the factory. ! WARNING FIRE, EXPLOSION HAZARD Failure to follow this warning could result in death, personal personal injury and/or property damage. NOTE: Only factory−trained service technicians should remove and replace compressor units. Never use air or gases containing oxygen for leak testing or for operating refrigerant compressors. Pressurized mixtures of air or gases containing oxygen can lead to an explosion. ! Compressor Mounting Bolts: Compressor mounting bolts should be periodically inspected for proper tightness. Bolts should be tightened and have the torque set at 65−75 in−lb (7.3 − 8.5 Nm). Compressor Rotation WARNING On 3−phase units with scroll compressors, it is important to be certain the compressor is rotating in the proper direction. To determine whether or not the compressor is rotating in the proper direction: PERSONAL INJURY AND ENVIRONMENTAL HAZARD Failure to follow this WARNING can result in personal injury or death. 1. Connect service gauges to suction and discharge pressure fittings. 2. Energize the compressor. 3. The suction pressure should drop and the discharge pressure should rise, as is normal on any start−up. NOTE: If the suction pressure does not drop and the discharge pressure does not rise to normal levels: 4. Note that the evaporator fan is probably also rotating in the wrong direction. 5. Turn off power to the unit. Use applicable lockout/ tagout procedures. 6. Reverse any two of the unit power leads. 7. Reapply power to the compressor. Use a gauge set certified for use with Puron (R−410A) refrigerant to relieve presure and recover all refrigerant before system repair or final unit disposal. Wear safety glasses and gloves when handling refrigerants. Keep torches and other ignition sources away from refrigerants and oils. ! CAUTION WARNING FIRE, EXPLOSION HAZARD Failure to follow this warning could result in death, personal personal injury and/or property damage. The suction and discharge pressure levels should now move to their normal start−up levels. NOTE: When the compressor is rotating in the wrong direction, the unit makes an elevated level of noise and does not provide cooling. Never use non−certified refrigerants in this product. Non−certified refrigerant could contain contaminant that could lead to unsafe operating conditions. Use ONLY refrigerants that conform to AHRI Standard 700. Filter Drier Replace the Filter Drier whenever the refrigerant system is exposed to atmosphere. Only use factory specified liquid−line filter driers with working pressures no less than 650 psig (4482 kPa). Do not install a suction−line filter drier in liquid line. A liquid−line filter drier designed for use with Puron refrigerant is required on every unit. Replacing the Compressor The compressor using Puron refrigerant contains a POE oil. This oil has a high affinity for moisture. Do not remove the compressor’s tube plugs until ready to insert the unit suction and discharge tube line ends. 25 Replacing the Filter Drier 3. 4. 5. 6. Use the following steps to replace the Filter Drier. 1. Using a Puron (R410) gauge set, recover all refrig erant from the system. 2. Use a tubing cutter to remove the filter drier from the line. NOTE: Do Not use a torch to remove the old filter drier. The heat from the torch will allow contaminants into the air and into the open refrigeration system. 3. Sweat a new replacement filter drier into the refriger ant line. 4. Re-charge the refrigerant system. Loosen the fan hub setscrews. Adjust the fan height as shown in Fig. 31. Tighten the setscrews. Replace the condenser−fan assembly. C10323 Fig. 31 − Condenser Fan Adjustment Adjusting the Condenser−Fan 1. Shut off the unit power supply. Apply the appropriate lockout/tagout procedures. 2. Remove the condenser−fan assembly (grille, motor, and fan). 26 TROUBLESHOOTING THE COOLING SYSTEM Refer to Table 5 for additional troubleshooting topics. Table 5 – Cooling Service Troubleshooting PROBLEM Compressor and Con denser Fan Will Not Start. Compressor Will Not Start But Condenser Fan Runs. CAUSE Power failure. Fuse blown or circuit breaker tripped. Defective thermostat, contactor, transformer, or control relay. Insufficient line voltage. Incorrect or faulty wiring. Thermostat setting too high. Faulty wiring or loose connections in compres sor circuit. Compressor motor burned out, seized, or internal overload open. Defective run/start capacitor, overload, start relay. One leg of three-phase power dead. Refrigerant overcharge or undercharge. Compressor Cycles (other than normally satisfying thermostat). Compressor Operates Continuously. Excessive Head Pressure. Head Pressure Too Low. Excessive Suction Pressure. Suction Pressure Too Low. Defective compressor. Insufficient line voltage. Blocked condenser. Defective run/start capacitor, overload, or start relay. Defective thermostat. Faulty condenser-fan motor or capacitor. Restriction in refrigerant system. Dirty air filter. Unit undersized for load. Thermostat set too low. Low refrigerant charge. Leaking valves in compressor. Air in system. Condenser coil dirty or restricted. Dirty air filter. Dirty condenser coil. Refrigerant overcharged. Faulty TXV valve. Air in system. Condenser air restricted or air short-cycling. Low refrigerant charge. Compressor valves leaking. Restriction in liquid tube. High head load. Compressor valves leaking. Refrigerant overcharged. Dirty air filter. Low refrigerant charge. Metering device or low side restricted. Faulty TXV valve. Replace defective component. Determine cause and correct. Check wiring diagram and rewire correctly. Lower thermostat setting below room temperature. Check wiring and repair or replace. Tighten loose connec tions. Determine cause. Replace compressor. Determine cause and replace defective component. Replace fuse or reset circuit breaker. Determine cause. Recover refrigerant, evacuate system, and recharge to values on nameplate. Replace defective compressor. Determine cause and correct. Determine cause and correct. Determine cause and replace. Replace thermostat. Replace. Defective fan motor or capacitor. Locate restriction and remove. Replace filter. Decrease load or replace with larger unit. Reset thermostat. Locate leak; repair and recharge. Replace compressor. Recover refrigerant, evacuate system, and recharge. Clean coil or remove restriction. Replace air filter. Clean condenser coil. Recover excess refrigerant. 1. Check TXV bulb mounting and secure tightly to suction line and insulate. 2. Replace TXV valve and filter drier if stuck open or closed. Recover refrigerant, evacuate system, and recharge. Determine cause and correct. Check for leaks; repair and recharge. Replace compressor. Remove restriction. Check for source and eliminate. Replace compressor. Recover excess refrigerant. Replace filter. Check for leaks; repair and recharge. Remove source of restriction. 1. Check TXV bulb mounting and secure tightly to suction line and insulate. 2. Replace TXV valve and filter drier if stuck open or closed. Temperature too low in conditioned area. Outdoor ambient below 25°F. Increase air quantity. Check filter and replace if necessary. Check belt tension on blower. Reset thermostat. Install low-ambient kit. Time off delay not finished. Wait for 30-second off delay. Compressor rotating in wrong direction. Reverse the 3-phase power leads. Insufficient evaporator airflow. Evaporator Fan Will Not Shut Off. Compressor Makes Excessive Noise. REMEDY Call power company. Replace fuse or reset circuit breaker. 27 CONVENIENCE OUTLETS ! WARNING ELECTRICAL OPERATION HAZARD Failure to follow this warning could result in personal injury or death. Units with convenience outlet circuits may use multiple disconnects. Check convenience outlet for power status before opening unit for service. Locate its disconnect switch, if appropriate, and open it. Tag−out this switch, if necessary. Two types of convenience outlets are offered on 50HC models: Non−powered and unit−powered. Both types provide a 125−volt Ground−Fault Circuit−Interrupter (GFCI) duplex receptacle rated at 15A behind a hinged waterproof access cover, located on the end panel of the unit. See Fig. 33. Non−Powered Type This type requires the field installation of a general−purpose 125−volt 15A circuit powered from a source elsewhere in the building. Observe national and local codes when selecting wire size, fuse or breaker requirements and disconnect switch size and location. Route 125V power supply conductors into the bottom of the utility box containing the duplex receptacle. C10324 Fig. 33 − Powered Convenience Outlet Wiring Pwd-CO Transformer Convenience Outlet GFCI Pwd-CO Fuse Switch UNIT VOLTAGE 208, 230 CONNECT AS 460 480 575 600 Control Box Access Panel C08128 Fig. 32 − Convenience Outlet Location Wet in Use Convenience Outlet Cover The unit has a “wet in use” convenience outlet cover that must be installed on the panel containing the convenience outlet. This cover provides protection against moisture entering the GFCI receptacle. This cover is placed in the unit control box during shipment. Unit−Powered Type A unit−mounted transformer is factory−installed to step down the main power supply voltage to the unit to 115−v at the duplex receptacle. This option also includes a manual switch with fuse, located in a utility box and mounted on a bracket behind the convenience outlet; access is through the unit’s control box access panel. See Fig. 33. 240 PRIMARY CONNECTIONS L1: RED +YEL L2: BLU + GRA L1: RED Splice BLU + YEL L2: GRA L1: RED L2: GRA TRANSFORMER TERMINALS H1 + H3 H2 + H4 H1 H2 + H3 H4 H1 H2 Duty Cycle The unit-powered convenience outlet has a duty cycle limitation. The transformer is intended to provide power on an intermittent basis for service tools, lamps, etc. It is not intended to provide 15-amps loading for continuous duty loads (such as electric heaters for overnight use). Observe a 50% limit on circuit loading above 8 amps (i.e., limit loads exceeding 8 amps to 30 minutes of operation every hour). The primary leads to the convenience outlet transformer are not factory−connected. Selection of primary power source is a customer−option. If local codes permit, the transformer primary leads can be connected at the line−side terminals on a unit−mounted non−fused disconnect or circuit breaker switch; this will provide service power to the unit when the unit disconnect switch or circuit breaker is open. Other connection methods will result in the convenience outlet circuit being de−energized 28 when the unit disconnect or circuit breaker is open. See Fig. 33. GFCI RECEPTACLE NOT INCLUDED COVER - WHILE-IN-USE WEATHERPROOF GFCI Maintenance P TO TOP 1. Press the TEST button on the face of the receptacle. This should cause the internal circuit of the receptacle to trip and open the receptacle. 2. Check for proper grounding and power line phasing should the GFCI receptacle fail to trip. 3. Repair ground wire connections as needed and correct the line phasing. 4. Press RESET button to clear the tripped condition. WET LO CATIO NS GASKET BASEPLATE FOR GFCI RECEPTACLE C09022 Fig. 34 − Weatherproof Cover Installation Fuse On Powered Type 1. Remove the blank cover plate at the convenience outlet. Discard the blank cover. 2. Loosen the two screws at the GFCI duplex outlet until approximately 1/2−in (13 mm) under the screw heads is exposed. 3. Press the gasket over the screw heads. Slip the backing plate over the screw heads at the keyhole slots and align with the gasket; tighten the two screws until snug. Do not over−tighten. 4. Mount the weatherproof cover to the backing plate as shown in Fig. 34. 5. Remove two slot fillers in the bottom of the cover to allow service tool cords to exit the cover. 6. Check the cover installation to confirm full closing and latching. The factory fuse is a Bussman “Fusetron” T−15, non−renewable screw−in (Edison base) type plug fuse. Using Unit−Mounted Convenience Outlets Units with unit−mounted convenience outlet circuits will often require that two disconnects be opened to de−energize all power to the unit. Treat all units as electrically energized until the convenience outlet power is also checked and de−energization is confirmed. Observe National Electrical Code Article 210, Branch Circuits, for use of convenience outlets. Always use a volt meter to verify no voltage is present at the GFCI receptacles before working on the unit. Installing a Weatherproof Cover A weatherproof while-in-use cover for the factory installed convenience outlets is now required by UL standards. This cover cannot be factory-mounted due to its depth. The cover must be installed at the unit installation. For shipment, the convenience outlet is covered with a blank cover plate. SMOKE DETECTORS Smoke detectors are available as factory−installed options on 558J models. Smoke detectors may be specified for Supply Air only or for Return Air without or with economizer or in combination of Supply Air and Return Air. Return Air smoke detectors are arranged for vertical return configurations only. All components necessary for operation are factory−provided and mounted. The unit is factory−configured for immediate smoke detector shutdown operation; additional wiring or modifications to unit terminal board may be necessary to complete the unit and smoke detector configuration to meet project requirements. The weatherproof cover kit is shipped in the unit’s control box. The kit includes the hinged cover, backing plate and gasket. ! TOP WET LOCAT IONS Periodically test the GFCI receptacle by pressing the TEST button on the face of the receptacle. WARNING ELECTRICAL OPERATION HAZARD Failure to follow this warning could result in personal injury or death. Before performing service or maintenance operations on the convenience outlets, Lockout/Tagout all electrical power to the unit. System The smoke detector system consists of a four−wire controller and one or two sensors. Its primary function is to shut down the rooftop unit in order to prevent smoke from circulating throughout the building. It is not to be used as a life saving device. Controller The controller (Fig. 35) includes a controller housing, a PC board, and clear plastic cover. The controller can be connected to one or two compatible duct smoke sensors. 29 The clear plastic cover is secured with a single captive screw for easy access to the wiring terminals. The controller has three LEDs: Power, Trouble and Alarm. A manual test/reset button is located on the cover face. from a fire, causes the sensor to signal an alarm state but dust and debris accumulated over time does not. Duct Smoke Sensor Duct Smoke Sensor Controller Exhaust Tube Exhaust Gasket Sensor Housing and Electronics See Detail A Conduit Nuts (supplied by installer) Intake Gasket Conduit Support Plate Controller Housing and Electronics Cover Gasket (ordering option) Terminal Block Cover TSD-CO2 (ordering option) Conduit Couplings (supplied by installer) Sensor Cover Plug Controller Cover Sampling Tube (ordered separately) Fastener (2X) Coupling Detail A Cover Gasket (ordering option) Alarm Trouble Power Magnetic Test/Reset Switch Test/Reset Switch Alarm Trouble Power Dirty C08208 Fig. 35 − Controller Assembly Sensor The sensor (see Fig. 36) includes a plastic housing, a printed circuit board, a clear plastic cover, a sampling tube inlet and an exhaust tube. The sampling tube, when used, and exhaust tube are attached during installation. The sampling tube varies in length depending on the size of the rooftop unit. The clear plastic cover permits visual inspections without having to disassemble the sensor. The cover attaches to the sensor housing using four captive screws and forms an airtight chamber around the sensing electronics. Each sensor includes a harness with an RJ45 terminal for connecting to the controller. Each sensor has four LEDs: Power, Trouble, Alarm and Dirty. A manual test/reset button is located on the left side of the housing. Air is introduced to the duct smoke detector sensor’s sensing chamber through a sampling tube that extends into the HVAC duct and is directed back into the ventilation system through a (shorter) exhaust tube. The difference in air pressure between the two tubes pulls the sampled air through the sensing chamber. When a sufficient amount of smoke is detected in the sensing chamber, the sensor signals an alarm state and the controller automatically takes the appropriate action to shut down fans and blowers, change over air handling systems, notify the fire alarm control panel, etc. C08209 Fig. 36 − Smoke Detector Sensor For installations using two sensors, the duct smoke detector does not differentiate which sensor signals an alarm or trouble condition. Smoke Detector Locations Supply Air The Supply Air smoke detector sensor is located to the left of the unit’s indoor (supply) fan. See Fig. 37. Access is through the fan access panel. There is no sampling tube used at this location. The sampling tube inlet extends through the side plate of the fan housing (into a high pressure area). The controller is located on a bracket to the right of the return filter, accessed through the lift−off filter panel. SUPPLY AIR SMOKE DETECTOR SENSOR The sensor uses a photoelectric (light scattering principle) process called differential sensing to prevent gradual environmental changes from triggering false alarms. A rapid change in environmental conditions, such as smoke C10325 Fig. 37 − Typical Supply Air Smoke Detector Sensor Location 30 Return Air without Economizer FIOP Smoke Detector Wiring and Response The sampling tube is located across the return air opening on the unit basepan. See Fig. 38. The holes in the sampling tube face downward, into the return air stream. The sampling tube is attached to the control module bushing that extends from the control box through the partition into the return air section of the unit. The sensor tube is shipped mounted to the Indoor Blower Housing and must be relocated to the return air section of the unit. Installation requires that this sensing tube be attached to the control module bushing. See installation steps. All units: The FIOP smoke detector is configured to automatically shut down all unit operations when a smoke condition is detected. See Fig. 40, Smoke Detector Wiring. Highlight A: The JMP 3 is factory−cut, transferring unit control to the smoke detector. Highlight B: The smoke detector NC contact set will open on a smoke alarm condition, de−energizing the ORN conductor. RETURN AIR DETECTOR MODULE (Shipping position shown)* Highlight C: 24V power signal using the ORN lead is removed at the Smoke Detector input on the Central Terminal board (CTB); all unit operations cease immediately. CONTROLLER MODULE RTU−−Open Controls: Unit operating functions (fan, cooling and heating) are terminated as described above. In addition: Highlight D: On smoke alarm condition, the smoke detector NO Alarm contact will close, supplying 24V power to the GRA conductor. RETURN AIR DETECTOR SAMPLING TUBE Highlight E: The GRA lead at the Smoke Alarm input on LCTB provides a 24V signal to the FIOP DDC control. *RA detector must be moved from shipping position to operating position by installer RTU−OPEN: The 24V signal is conveyed to the RTU−OPEN J1−10 input terminal. This signal initiates the FSD sequence by the RTU−OPEN control. FSD status is reported to the connected BAS network. C07307 Fig. 38 − Typical Return Air Detector Location Return Air with Economizer The sampling tube is inserted through the side plates of the economizer housing, placing it across the return air opening on the unit basepan. See Fig. 39. The holes in the sampling tube face downward, into the return air stream. The sampling tube is connected through tubing to the return air sensor that is mounted on a bracket high on the partition between return filter and controller location. The Return Air Sensor is shipped in a flat−mounting location. Installation requires that this sensor be relocated to its operating location and the tubing to the sampling tube be connected. See installation steps. Using Remote Logic: Five field−use conductors are provided for additional annunciation functions. Additional Application Data: Refer to Catalog number HKRNKA−1XA for discussions on additional control features of these smoke detectors, including multiple unit coordination. See Fig. 40. 31 RETURN AIR SENSOR (Operating Position Shown) CONTROLLER MODULE SCREWS (2) SAMPLE TUBE C12050 Fig. 39 − Return Air Sampling Tube Location in Unit with Economizer B D C F E 48TM502525 D A C12559 Fig. 40 − Typical Smoke Detector System Wiring 32 Sensor and Controller Tests NOTICE Sensor Alarm Test OPERATIONAL TEST NOTICE Failure to follow this NOTICE may result in an unnecessary evacuation of the facility. Pressing the controller’s test/reset switch for longer than seven seconds will put the duct detector into the alarm state and activate all automatic alarm responses. The sensor alarm test checks a sensor’s ability to signal an alarm state. This test requires that you use a field provided SD−MAG test magnet. NOTICE OPERATIONAL TEST NOTICE Failure to follow this NOTICE may result in an unnecessary evacuation of the facility. This test places the duct detector into the alarm state. Unless part of the test, disconnect all auxiliary equipment from the controller before performing the test. If the duct detector is connected to a fire alarm system, notify the proper authorities before performing the test. Dirty Controller Test Procedure 1. Press the controller’s test/reset switch for two seconds. 2. Verify that the controller’s Trouble LED flashes. Dirty Sensor Test The dirty sensor test provides an indication of the sensor’s ability to compensate for gradual environmental changes. A sensor that can no longer compensate for environmental changes is considered 100% dirty and requires cleaning or replacing. You must use a field provided SD−MAG test magnet to initiate a sensor dirty test. The sensor’s Dirty LED indicates the results of the dirty test as shown in Table 6. Sensor Alarm Test Procedure 1. Hold the test magnet where indicated on the side of the sensor housing for seven seconds. 2. Verify that the sensor’s Alarm LED turns on. 3. Reset the sensor by holding the test magnet against the sensor housing for two seconds. 4. Verify that the sensor’s Alarm LED turns off. NOTICE OPERATIONAL TEST NOTICE Failure to follow this NOTICE may result in an unnecessary evacuation of the facility. Holding the test magnet against the sensor housing for more than seven seconds will put the duct detector into the alarm state and activate all automatic alarm responses. Controller Alarm Test The controller alarm test checks the controller’s ability to initiate and indicate an alarm state. NOTICE OPERATIONAL TEST NOTICE Failure to follow this NOTICE may result in an unnecessary evacuation of the facility. This test places the duct detector into the alarm state. Unless part of the test, disconnect all auxiliary equipment from the controller before performing the test. If the duct detector is connected to a fire alarm system, notify the proper authorities before performing the test. Table 6 – Dirty LED Test FLASHES DESCRIPTION 1 0-25% dirty. (Typical of a newly installed detector) 2 25-50% dirty 3 51-75% dirty 4 76-99% dirty Dirty Sensor Test Procedure 1. Hold the test magnet where indicated on the side of the sensor housing for two seconds. 2. Verify that the sensor’s Dirty LED flashes. Controller Alarm Test Procedure 1. Press the controller’s test/reset switch for seven seconds. 2. Verify that the controller’s Alarm LED turns on. 3. Reset the sensor by pressing the test/reset switch for two seconds. 4. Verify that the controller’s Alarm LED turns off. NOTICE OPERATIONAL TEST NOTICE Failure to follow this NOTICE may result in an unnecessary evacuation of the facility. Changing the dirty sensor test operation will put the detector into the alarm state and activate all automatic alarm responses. Before changing dirty sensor test operation, disconnect all auxiliary equipment from the controller and notify the proper authorities if connected to a fire alarm system. Dirty Controller Test The dirty controller test checks the controller’s ability to initiate a dirty sensor test and indicate its results. 33 Changing the Dirt Sensor Test 12 By default, sensor dirty test results are indicated by: The sensor’s Dirty LED flashing. The controller’s Trouble LED flashing. The controller’s supervision relay contacts toggle. Smoke Detector Controller 1 TB3 The operation of a sensor’s dirty test can be changed so that the controller’s supervision relay is not used to indicate test results. When two detectors are connected to a controller, sensor dirty test operation on both sensors must be configured to operate in the same manner. 3 Auxiliary equipment 14 SD-TR14 Trouble 5 18 Vdc (+) Wire must be added by installer Power 19 4 15 1 2 3 Alarm Reset/Test 20 18 Vdc (−) 2 C08247 Fig. 41 − Remote Test/Reset Station Connections NOTICE Remote Station Test The remote station alarm test checks a test/reset station’s ability to initiate and indicate an alarm state. OPERATIONAL TEST NOTICE Failure to follow this NOTICE can result in an unnecessary evacuation of the facility. If the test/reset station’s key switch is left in the RESET/TEST position for longer than seven seconds, the detector will automatically go into the alarm state and activate all automatic alarm responses. NOTICE OPERATIONAL TEST NOTICE Failure to follow this NOTICE may result in an unnecessary evacuation of the facility. Changing the dirty sensor test operation will put the detector into the alarm state and activate all automatic alarm responses. Before changing the dirty sensor test operation, disconnect all auxiliary equipment from the controller and notify proper authorities if connected to a fire alarm system. NOTICE OPERATIONAL TEST NOTICE Failure to follow this NOTICE can result in an unnecessary evacuation of the facility. Holding the test magnet to the target area for longer than seven seconds will put the detector into the alarm state and activate all automatic alarm responses. SD−TRK4 Remote Alarm Test Procedure The test/reset station dirty sensor test checks the test/reset station’s ability to initiate a sensor dirty test and indicate the results. It must be wired to the controller as shown in Fig. 41 and configured to operate the controller’s supervision relay. For more information, see “Changing the Dirty Sensor Test.” + 13 1. Hold the test magnet where indicated on the side of the sensor housing for approximately 60 seconds until the sensor’s Alarm LED turns on and its Dirty LED flashes twice. 2. Reset the sensor by removing the test magnet and then holding it against the sensor housing again for approximately 2 seconds until the sensor’s Alarm LED turns off. Remote Test/Reset Station Dirty Sensor Test − 2 Supervision relay contacts [3] To Configure the Dirty Sensor Test Operation 1. Turn the key switch to the RESET/TEST position for seven seconds. 2. Verify that the test/reset station’s Alarm LED turns on. 3. Reset the sensor by turning the key switch to the RESET/TEST position for two seconds. 4. Verify that the test/reset station’s Alarm LED turns off. 1 Dirty Sensor Test Using an SD−TRK4 1. Turn the key switch to the RESET/TEST position for two seconds. 2. Verify that the test/reset station’s Trouble LED flashes. Detector Cleaning Cleaning the Smoke Detector Clean the duct smoke sensor when the Dirty LED is flashing continuously or sooner if conditions warrant. 34 Alarm State NOTICE The smoke detector enters the alarm state when the amount of smoke particulate in the sensor’s sensing chamber exceeds the alarm threshold value. (See Table 7.) Upon entering the alarm state: The sensor’s Alarm LED and the controller’s Alarm LED turn on. OPERATIONAL TEST NOTICE Failure to follow this NOTICE can result in an unnecessary evacuation of the facility. If the smoke detector is connected to a fire alarm system, first notify the proper authorities that the detector is undergoing maintenance then disable the relevant circuit to avoid generating a false alarm. The contacts on the controller’s two auxiliary relays switch positions. The contacts on the controller’s alarm initiation relay close. 1. Disconnect power from the duct detector then remove the sensor’s cover. (See Fig. 42.) The controller’s remote alarm LED output is activated (turned on). HVAC duct Sampling tube The controller’s high impedance multiple fan shutdown control line is pulled to ground Trouble state. Sensor housing The SuperDuct duct smoke detector enters the trouble state under the following conditions: A sensor’s cover is removed and 20 minutes pass before it is properly secured. Optic plate Airflow Retainer clip A sensor’s environmental compensation limit is reached (100% dirty). Optic housing A wiring fault between a sensor and the controller is detected. C07305 An internal sensor fault is detected upon entering the trouble state: The contacts on the controller’s supervisory relay switch positions. (See Fig. 43.) Fig. 42 − Sensor Cleaning Diagram 2. Using a vacuum cleaner, clean compressed air, or a soft bristle brush, remove loose dirt and debris from inside the sensor housing and cover. Use isopropyl alcohol and a lint−free cloth to remove dirt and other contaminants from the gasket on the sensor’s cover. 3. Squeeze the retainer clips on both sides of the optic housing then lift the housing away from the printed circuit board. 4. Gently remove dirt and debris from around the optic plate and inside the optic housing. 5. Replace the optic housing and sensor cover. 6. Connect power to the duct detector then perform a sensor alarm test. If a sensor trouble, the sensor’s Trouble LED the controller ’s Trouble LED turn on. If 100% dirty, the sensor’s Dirty LED turns on and the controller ’s Trouble LED flashes continuously. If a wiring fault between a sensor and the controller, the controller ’s Trouble LED turns on but not the sensor’s. Trouble Alarm Power INDICATORS Test/reset switch Normal State The smoke detector operates in the normal state in the absence of any trouble conditions and when its sensing chamber is free of smoke. In the normal state, the Power LED on both the sensor and the controller are on and all other LEDs are off. C07298 Fig. 43 − Controller Assembly NOTE: All troubles are latched by the duct smoke detector. The trouble condition must be cleared and then the duct smoke detector must be reset in order to restore it to the normal state. 35 Table 7 – Detector Indicators CONTROL OR INDICATOR Magnetic test/reset switch Alarm LED Trouble LED Dirty LED Power LED DESCRIPTION Resets the sensor when it is in the alarm or trouble state. Activates or tests the sensor when it is in the normal state. Indicates the sensor is in the alarm state. Indicates the sensor is in the trouble state. Indicates the amount of environmental compensation used by the sensor (flashing continuously = 100%) Indicates the sensor is energized. Resetting Alarm and Trouble Condition Trips: Manual reset is required to restore smoke detector systems to Normal operation. For installations using two sensors, the duct smoke detector does not differentiate which sensor signals an alarm or trouble condition. Check each sensor for Alarm or Trouble status. Clear the condition that has generated the trip at this sensor. Then reset the sensor by pressing and holding the reset button (on the side) for 2 seconds. Verify that the sensor’s Alarm and Trouble LEDs are now off. At the controller, clear its Alarm or Trouble state by pressing and holding the manual reset button (on the front cover) for 2 seconds. Verify that the controller’s Alarm and Trouble LEDs are now off. Replace all panels. Controller’s Power LED is Off 1. Make sure the circuit supplying power to the controller is operational. If not, make sure JP2 and JP3 are set correctly on the controller before applying power. 2. Verify that power is applied to the controller’s supply input terminals. If power is not present, replace or repair wiring as required. Remote Test/Reset Station’s Trouble LED Does Not flash When Performing a Dirty Test, but the Controller’s Trouble LED Does 1. Verify that the remote test/station is wired as shown in Fig. 41. Repair or replace loose or missing wiring. 2. Configure the sensor dirty test to activate the controller ’s supervision relay. See “Changing Sensor Dirty Test Operation.” Troubleshooting Controller’s Trouble LED is On 1. Check the Trouble LED on each sensor connected to the controller. If a sensor’s Trouble LED is on, determine the cause and make the necessary repairs. 2. Check the wiring between the sensor and the controller. If wiring is loose or missing, repair or replace as required. Controller’s Trouble LED is Flashing 1. One or both of the sensors is 100% dirty. 2. Determine which Dirty LED is flashing then clean that sensor assembly as described in the detector cleaning section. Sensor’s Trouble LED is On 1. Check the sensor’s Dirty LED. If it is flashing, the sensor is dirty and must be cleaned. 2. Check the sensor’s cover. If it is loose or missing, secure the cover to the sensor housing. 3. Replace sensor assembly. Sensor’s Power LED is Off 1. Check the controller’s Power LED. If it is off, determine why the controller does not have power and make the necessary repairs. 2. Check the wiring between the sensor and the controller. If wiring is loose or missing, repair or replace as required. Sensor’s Trouble LED is On, But the Controller’s Trouble LED is OFF Remove JP1 on the controller. PROTECTIVE DEVICES Compressor Protection Overcurrent The compressor has internal linebreak motor protection. Reset is automatic after compressor motor has cooled. Overtemperature Each compressor has an internal protector to protect it against excessively high discharge gas temperatures. Reset is automatic. High Pressure Switch The system is provided with a high pressure switch mounted on the discharge line. The switch is stem−mounted and brazed into the discharge tube. Trip setting is 630 psig ± 10 psig (4344 ± 69 kPa) when hot. Reset is automatic at 505 psig (3482 kPa). 36 Low Pressure Switch Troubleshooting Supply Fan Motor Overload Trips The system is protected against a loss of charge and low evaporator coil loading condition by a low pressure switch located on the suction line near the compressor. The switch is stem−mounted. Trip setting is 54 psig ± 5 psig (372 ± 34 kPa). Reset is automatic at 117 ± 5 psig (807 ± 34 kPa). The supply fan used in 558J units is a forward−curved centrifugal wheel. At a constant wheel speed, this wheel has a characteristic that causes the fan shaft load to DECREASE when the static pressure in the unit−duct system increases and to INCREASE when the static pressure in the unit−duct system decreases (and fan airflow rate increases). Motor overload conditions typically develop when the unit is operated with an access panel removed, with unfinished duct work, in an economizer−open mode, or a leak develops in the duct system that allows a bypass back to unit return opening. Supply (Indoor) Fan Motor Protection ! WARNING PERSONAL INJURY HAZARD Failure to follow this WARNING can result in personal injury. Disconnect all electrical power when servicing the fan motor. Apply appropriate lockout/tagout procedures. Table 8 – Overcurrent Device Type Motor Size (bhp) 1.7 2.4 2.9 3.7 4.7 Motors with 2.9 and 3.7 bhp are equipped with an internal overtemperature or protection device. The type of device depends on the motor size. See Table 8. Overload Device Internal Linebreak Internal Linebreak Thermik Thermik External (circuit breaker) Reset Automatic Automatic Automatic Automatic Manual Condenser Fan Motor Protection The High Static option supply fan motor is equipped with a pilot−circuit Thermix combination overtemperature/ overcurrent protection device. This device resets automatically. Do not bypass this switch to correct trouble. Determine the cause and correct it. The condenser fan motor is internally protected against overtemperature. Control Circuit, 24−V The control circuit is protected against overcurrent conditions by a circuit breaker mounted on the control transformer TRAN. Reset is manual. The Thermik device is a snap−action overtemperature protection device that is embedded in the motor windings. The Thermik can be identified by two blue wires extending out of the motor control box. It is a pilot−circuit device that is wired into the unit’s 24V control circuit. When this switch reaches its trip setpoint, it opens the 24V control circuit and causes all unit operation to cease. This device resets automatically when the motor windings cool. Do not bypass this switch to correct trouble. Determine the cause and correct it. The External Overload Breaker is an overcurrent device used on motors with a horsepower rating of 4.7 hp or greater. This is a specially−calibrated circuit breaker that is UL recognized as a motor overload controller. When the current to the motor exceeds the circuit breaker setpoint, the device opens all motor power leads to the motor, shutting the motor down. Reset requires a manual reset at the overload switch. This device (designated IFCB) is located on the side of the supply fan housing, behind the fan access panel. The Must Hold and Must Trip values are listed on the side of the External Overload Breaker. 37 RTU−OPEN CONTROL SYSTEM The RTU Open controller is an integrated component of the rooftop unit. Its internal application programming provides optimum performance and energy efficiency. RTU Open enables the unit to run in 100% stand−alone control mode or a Third Party Building Automation System (BAS). On−board DIP switches allow you to select your protocol (and baud rate) of choice among the four most popular protocols in use today: BACnet, Modbus, Johnson N2 and LonWorks. The RTU Open control is factory−mounted in the 558J unit’s main control box, to the left of the Light Commercial Terminal Board (LCTB). See Fig. 44. Factory wiring is completed through harnesses connected to the LCTB. Field connections for RTU Open sensors will be made at the Phoenix connectors on the RTU Open board. The factory−installed RTU Open control includes the supply−air temperature (SAT) sensor. The outdoor air temperature (OAT) sensor is included in the FIOP/accessory EconoMi$er2 package. Sensory/Accessory Installation There are a variety of sensors and accessories available for the RTU−OPEN. Some of these can be factory or field installed, while others are only field installable. The RTU−OPEN controller may also require connection to a building network system or building zoning system. All field control wiring that connects to the RTU−OPEN must be routed through the raceway built into the corner post of the unit or secured to the unit control box with electrical conduit. The unit raceway provides the UL required clearance between high and low−voltage wiring. Pass the control wires through the hole provided in the corner post, then feed the wires thorough the raceway to the RTU−OPEN. Connect the wires to the removable Phoenix connectors and then reconnect the connectors to the board. See Fig. 44. IMPORTANT: Refer to the specific sensor or accessory instructions for its proper installation and for rooftop unit installation refer to base unit installation instructions and the unit’s wiring diagrams. ! WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death, and/or equipment damage. Disconnect and lockout/tagout electrical power before wiring the RTU−OPEN controller. Additional RTU−OPEN Installation and Troubleshooting Additional installation, wiring and troubleshooting information for the RTU−OPEN Controller can be found in the following manuals: “Controls, Start−up, Operation and Troubleshooting Instructions,” and “RTU Open Installation and Start−up Guide.” C10818 Fig. 44 − RTU−OPEN Control Module 38 ECONOMI$ER SYSTEMS IMPORTANT: Any economizer that meets the economizer requirements as laid out in California’s Title 24 mandatory section 120.2 (fault detection and diagnostics) and/or prescriptive section 140.4 (life−cycle tests, damper leakage, 5 year warranty, sensor accuracy, etc), will have a label on the economizer. Any economizer without this label does not meet California’s Title 24. The five year limited parts warranty referred to in section 140.4 only applies to factory installed economizers. Please refer to your economizer on your unit. WIRING HARNESS ECONOMIER IV CONTROLLER OUTSIDE AIR TEMPERATURE SENSOR LOW AMBIENT SENSOR ACTUATOR The 558J units may be equipped with a factory−installed or accessory (field−installed) EconoMi$er system. Two types are available: with a logic control system (EconoMi$er IV) and without a control system (EconoMi$er2). See Fig. 45 for component locations on each type. See Figs. 46 and 47 for EconoMi$er section wiring diagrams. Both EconoMi$ers use direct−drive damper actuators. C06021 OUTDOOR AIR HOOD ECONOMI$ER2 PLUG BAROMETRIC RELIEF DAMPER HOOD SHIPPING BRACKET GEAR DRIVEN DAMPER C06022 Fig. 45 − EconoMi$er IV Component Locations FOR OCCUPANCY CONTROL REPLACE JUMPER WITH FIELD-SUPPLIED TIME CLOCK 8 7 LEGEND DCV— Demand Controlled Ventilation IAQ — Indoor Air Quality LA — Low Ambient Lockout Device OAT — Outdoor-Air Temperature POT — Potentiometer RAT — Return-Air Temperature Potentiometer Defaults Settings: Power Exhaust Middle Minimum Pos. Fully Closed DCV Max. Middle DCV Set Middle Enthalpy C Setting NOTES: 1. 620 ohm, 1 watt 5% resistor should be removed only when using differential enthalpy or dry bulb. 2. If a separate field-supplied 24 v transformer is used for the IAQ sensor power supply, it cannot have the secondary of the transformer grounded. 3. For field-installed remote minimum position POT, remove black wire jumper between P and P1 and set control minimum position POT to the minimum position. C06028 Fig. 46 − EconoMi$er IV Wiring 39 BLACK 4 TRANSFORMER GROUND 3 5 BLUE 500 OHM RESISTOR 2 8 VIOLET 6 NOTE 1 PINK 7 RUN OAT SENSOR RED NOTE 3 1 24 VAC 10 YELLOW 50HJ540573 ACTUATOR ASSEMBLY 11 9 DIRECT DRIVE ACTUATOR WHITE 4-20mA SIGNAL 12 4-20 mA TO J9 ON PremierLink BOARD ECONOMISER2 PLUG NOTES: 1. Switch on actuator must be in run position for economizer to operate. 2. PremierLink™ control requires that the standard 50HJ540569 outside-air sensor be replaced by either the CROASENR001A00 dry bulb sen sor or HH57A077 enthalpy sensor. 3. 50HJ540573 actuator consists of the 50HJ540567 actuator and a harness with 500-ohm resistor. C08310 Fig. 47 − EconoMi$er2 with 4 to 20 mA Control Wiring Table 9 – EconoMi$er IV Input/Output Logic INPUTS Demand Control Ventilation (DCV) OUTPUTS Enthalpy* Compressor Outdoor Return High (Free Cooling LED Off) Low Below set (DCV LED Off) Low (Free Cooling LED On) High (Free Cooling LED Off) High Low Above set (DCV LED On) Low (Free Cooling LED On) High Y1 Y2 Stage Stage 1 2 N Terminal† Occupied Unoccupied Damper On On On On On Off On Off Off Off Off Off On On On Off On Off Off Off Off Off Off Off Minimum position Closed On On On On On Off On Off Off Off Off Off Modulating†† (between min. position and DCV maximum) Modulating†† (between closed and DCV maximum) On On On Off On Off Off Off Modulating*** Modulating††† Off Off Off Off * † ** †† *** Minimum position Closed Modulating** (between min. position and full‐open) Modulating** (between closed and full‐open) For single enthalpy control, the module compares outdoor enthalpy to the ABCD setpoint. Power at N terminal determines Occupied/Unoccupied setting: 24 vac (Occupied), no power (Unoccupied). Modulation is based on the supply‐air sensor signal. Modulation is based on the DCV signal. Modulation is based on the greater of DCV and supply‐air sensor signals, between minimum position and either maximum position (DCV) or fully open (supply‐air signal). ††† Modulation is based on the greater of DCV and supply‐air sensor signals, between closed and either maximum position (DCV) or fully open (supply‐air signal). 40 C06053 Fig. 48 − EconoMi$er IV Functional View EconoMi$er IV Standard Sensors SUPPLY AIR TEMPERATURE SENSOR MOUNTING LOCATION Table 9 provides a summary of EconoMi$er IV I/O logic. A functional view of the EconoMi$er is shown in Fig. 48. Typical settings, sensor ranges, and jumper positions are also shown. An EconoMi$er IV simulator program is available to help with EconoMi$er IV training and troubleshooting. SUPPLY AIR TEMPERATURE SENSOR (SEALED INSIDE CRIMP END) Outdoor Air Temperature (OAT) Sensor The outdoor air temperature sensor (HH57AC074) is a 10 to 20 mA device used to measure the outdoor-air temperature. The outdoor-air temperature is used to determine when the EconoMi$er IV can be used for free cooling. The sensor is factory-installed on the EconoMi$er IV in the outdoor airstream. See Fig. 49. The operating range of temperature measurement is 40 to 100F (4 to 38C). See Fig. 67. C06033 Fig. 49 − Supply Air Sensor Location EconoMi$er IV Control Modes Supply Air Temperature (SAT) Sensor The supply air temperature sensor is a 3 K thermistor located at the inlet of the indoor fan. See Fig. 49. This sensor is factory installed. The operating range of temperature measurement is 0° to 158F (−18 to 70C). See Table 49 for sensor temperature/resistance values. The temperature sensor looks like an eyelet terminal with wires running to it. The sensor is located in the “crimp end” and is sealed from moisture. IMPORTANT: The optional EconoMi$er2 does not include a controller. The EconoMi$er2 is operated by a 4 to 20 mA signal from an existing field-supplied controller. See Fig. 62 for wiring information. Determine the EconoMi$er IV control mode before set up of the control. Some modes of operation may require different sensors. The EconoMi$er IV is supplied from the factory with a supply−air temperature sensor and an outdoor− air temperature sensor. This allows for operation of the EconoMi$er IV with outdoor air dry bulb changeover control. Additional accessories can be added to allow for different types of changeover control and operation of the EconoMi$er IV and unit. Outdoor Air Lockout Sensor The EconoMi$er IV is equipped with an ambient temperature lockout switch located in the outdoor airstream which is used to lock out the compressors below a 42F (6C) ambient temperature. See Fig. 61. 41 The standard controller is shipped from the factory configured for outdoor dry bulb changeover control. The outdoor air and supply air temperature sensors are included as standard. For this control mode, the outdoor temperature is compared to an adjustable setpoint selected on the control. If the outdoor-air temperature is above the setpoint, the EconoMi$er IV will adjust the outside air dampers to minimum position. If the outdoor-air temperature is below the setpoint, the position of the outside air dampers will be controlled to provided free cooling using outdoor air. When in this mode, the LED next to the free cooling setpoint potentiometer will be on. The changeover temperature setpoint is controlled by the free cooling setpoint potentiometer located on the control. See Fig. 50. The scale on the potentiometer is A, B, C, and D. See Fig. 51 for the corresponding temperature changeover values. FLOW IN CUBIC FEET PER MINUTE (cfm) Outdoor Dry Bulb Changeover 30 25 20 15 10 5 0 0.13 0.20 0.22 0.25 0.30 0.35 0.40 0.45 0.50 STATIC PRESSURE (in. wg) C06031 Fig. 52 − Outdoor−Air Damper Leakage Differential Dry Bulb Control For differential dry bulb control the standard outdoor dry bulb sensor is used in conjunction with an additional accessory dry bulb sensor (p/n: CRTEMPSN002A00). The accessory sensor must be mounted in the return airstream. See Fig. 53. Wiring is provided in the EconoMi$er IV wiring harness. ECONOMI$ER IV CONTROLLER ECONOMI$ER IV GROMMET C06034 Fig. 50 − EconoMi$er IV Controller Potentiometer and LED Locations RETURN AIR SENSOR 19 RETURN DUCT (FIELD-PROVIDED) LED ON 18 D 17 LED OFF 16 mA 15 14 C07085 LED ON C LED OFF 13 12 Fig. 53 − Return Air Temperature or Enthalpy Sensor Mounting Location LED ON In this mode of operation, the outdoor-air temperature is compared to the return-air temperature and the lower temperature airstream is used for cooling. When using this mode of changeover control, turn the enthalpy setpoint potentiometer fully clockwise to the D setting. See Fig. 50. B LED OFF LED ON A 11 10 LED OFF 9 40 45 50 55 60 65 70 75 80 DEGREES FAHRENHEIT 85 90 95 Outdoor Enthalpy Changeover 100 C06035 Fig. 51 − Outside Air Temperature Changeover Setpoints For enthalpy control, accessory enthalpy sensor (p/n: HH57AC078) is required. Replace the standard outdoor dry bulb temperature sensor with the accessory enthalpy sensor in the same mounting location. See Fig. 70. When the outdoor air enthalpy rises above the outdoor enthalpy changeover setpoint, the outdoor-air damper moves to its minimum position. The outdoor enthalpy changeover setpoint is set with the outdoor enthalpy setpoint potentiometer on the EconoMi$er IV controller. The setpoints are A, B, C, and D. See Fig. 51. The factory- installed 620-ohm jumper must be in place across terminals SR and SR+ on the EconoMi$er IV controller. 42 4 9 9 1 1 11 (29) (32) (3 ) (3 ) (41) (43) 44 CONTROL CONTROL POINT CURVE APPROX. deg. F (deg. C) 42 AT 50% RH (27) ITY MID HU 3 IVE 34 LA T U 22 24 (1 ) 7 2 1 9 RE 7 (21) 3 EN TH AL 2 PY BT 7 (24) 32 PE R PO UN D DR Y (% ) 4 AI R 73 (23) 7 (21) 7 (19) 3 (17) 3 A B C D 1 4 2 (1 ) 1 3 (13) 12 14 (1 ) 4 (4) 4 (7) 2 D 1 3 (2) D 35 (2) 40 (4) 4 (7) (1 ) 1 11 7 9 9 1 7 (13) (1 ) (1 ) (21) (24) (27) (29) (32) (3 ) (3 ) (41) (43) HIGH LIMIT CURVE APPROXIMATE DRY BULB TEMPERATURE--degrees F (degrees C) C06037 Fig. 54 − Enthalpy Changeover Setpoints the outdoor air enthalpy to the return air enthalpy to determine EconoMi$er IV use. The controller selects the lower enthalpy air (return or outdoor) for cooling. For example, when the outdoor air has a lower enthalpy than the return air, the EconoMi$er IV opens to bring in outdoor air for free cooling. Replace the standard outside air dry bulb temperature sensor with the accessory enthalpy sensor in the same mounting location. See Fig. 45. Mount the return air enthalpy sensor in the return air duct. See Fig. 53. Wiring is provided in the EconoMi$er IV wiring harness. See Fig. 46. The outdoor enthalpy changeover setpoint is set with the outdoor enthalpy setpoint potentiometer on the EconoMi$er IV controller. When using this mode of changeover control, turn the enthalpy setpoint potentiometer fully clockwise to the D setting. FACTORY JUMPER N1 N EXH Set 10V 2V EXH P1 P Min Pos T1 2V AQ1 SO+ SR 24 Vac HOT 24 Vac COM + _ DCV Max 10V 1 2 5 DCV AQ SR+ TR1 Open T SO TR 2V DCV Set 10V Free Cool B C A D 3 4 EF EF1 Indoor Air Quality (IAQ) Sensor Input The IAQ input can be used for demand control ventilation control based on the level of CO2 measured in the space or return air duct. Mount the accessory IAQ sensor according to manufacturer specifications. The IAQ sensor should be wired to the AQ and AQ1 terminals of the controller. Adjust the DCV potentiometers to correspond to the DCV voltage output of the indoor air quality sensor at the user-determined setpoint. See Fig. 56. C06038 Fig. 55 − EconoMi$er IV Control Differential Enthalpy Control For differential enthalpy control, the EconoMi$er IV controller uses two enthalpy sensors (HH57AC078 and CRENTDIF004A00), one in the outside air and one in the return air duct. The EconoMi$er IV controller compares 43 To determine the minimum position setting, perform the following procedure: 1. Calculate the appropriate mixed air temperature using the following formula: CO2 SENSOR MAX RANGE SETTING RANGE CONFIGURATION (ppm) 6000 5000 4000 800 ppm 900 ppm 1000 ppm 1100 ppm 3000 2000 1000 0 2 3 4 5 6 7 8 DAMPER VOLTAGE FOR MAX VENTILATION RATE C06039 Fig. 56 − CO2 Sensor Maximum Range Settings If a separate field-supplied transformer is used to power the IAQ sensor, the sensor must not be grounded or the EconoMi$er IV control board will be damaged. When using demand ventilation, the minimum damper position represents the minimum ventilation position for VOC (volatile organic compounds) ventilation requirements. The maximum demand ventilation position is used for fully occupied ventilation. When demand ventilation control is not being used, the minimum position potentiometer should be used to set the occupied ventilation position. The maximum demand ventilation position should be turned fully clockwise. Exhaust Setpoint Adjustment The exhaust setpoint will determine when the exhaust fan runs based on damper position (if accessory power exhaust is installed). The setpoint is modified with the Exhaust Fan Setpoint (EXH SET) potentiometer. See Fig. 50. The setpoint represents the damper position above which the exhaust fans will be turned on. When there is a call for exhaust, the EconoMi$er IV controller provides a 45 ± 15 second delay before exhaust fan activation to allow the dampers to open. This delay allows the damper to reach the appropriate position to avoid unnecessary fan overload. Minimum Position Control There is a minimum damper position potentiometer on the EconoMi$er IV controller. See Fig. 50. The minimum damper position maintains the minimum airflow into the building during the occupied period. When using demand ventilation, the minimum damper position represents the minimum ventilation position for Volatile Organic Compound (VOC) ventilation requirements. The maximum demand ventilation position is used for fully occupied ventilation. When demand ventilation control is not being used, the minimum position potentiometer should be used to set the occupied ventilation position. The maximum demand ventilation position should be turned fully clockwise. Adjust the minimum position potentiometer to allow the minimum amount of outdoor air, as required by local codes, to enter the building. Make minimum position adjustments with at least 10F temperature difference between the outdoor and return-air temperatures. (TO x OA + (TR ) 100 x RA ) =TM 100 TO = Outdoor-Air Temperature OA = Percent of Outdoor Air TR = Return-Air Temperature RA = Percent of Return Air TM = Mixed-Air Temperature As an example, if local codes require 10% outdoor air during occupied conditions, outdoor-air temperature is 60F, and return-air temperature is 75F. (60 x .10) + (75 x .90) = 73.5F 2. Disconnect the supply air sensor from terminals T and T1. 3. Ensure that the factory-installed jumper is in place across terminals P and P1. If remote damper positioning is being used, make sure that the terminals are wired according to Fig. 52 and that the minimum position potentiometer is turned fully clockwise. 4. Connect 24 vac across terminals TR and TR1. 5. Carefully adjust the minimum position potentiometer until the measured mixed air temperature matches the calculated value. 6. Reconnect the supply air sensor to terminals T and T1. Remote control of the EconoMi$er IV damper is desirable when requiring additional temporary ventilation. If a field-supplied remote potentiometer (Honeywell p/n: S963B1128) is wired to the EconoMi$er IV controller, the minimum position of the damper can be controlled from a remote location. To control the minimum damper position remotely, remove the factory-installed jumper on the P and P1 terminals on the EconoMi$er IV controller. Wire the field-supplied potentiometer to the P and P1 terminals on the EconoMi$er IV controller. (See Fig. 54.) Damper Movement Damper movement from full open to full closed (or vice versa) takes 21/2 minutes. Thermostats The EconoMi$er IV control works with conventional thermostats that have a Y1 (cool stage 1), Y2 (cool stage 2), W1 (heat stage 1), W2 (heat stage 2), and G (fan). The EconoMi$er IV control does not support space temperature sensors. Connections are made at the thermostat terminal connection board located in the main control box. 44 Occupancy Control the maximum ventilation rate of 20% (or base plus 15 cfm per person). Use Fig. 56 to determine the maximum setting of the CO2 sensor. For example, an 1100 ppm setpoint relates to a 15 cfm per person design. Use the 1100 ppm curve on Fig. 56 to find the point when the CO2 sensor output will be 6.7 volts. Line up the point on the graph with the left side of the chart to determine that the range configuration for the CO2 sensor should be 1800 ppm. The EconoMi$er IV controller will output the 6.7 volts from the CO2 sensor to the actuator when the CO2 concentration in the space is at 1100 ppm. The DCV setpoint may be left at 2 volts since the CO2 sensor voltage will be ignored by the EconoMi$er IV controller until it rises above the 3.6 volt setting of the minimum position potentiometer. Once the fully occupied damper position has been determined, set the maximum damper demand control ventilation potentiometer to this position. Do not set to the maximum position as this can result in over-ventilation to the space and potential high humidity levels. The factory default configuration for the EconoMi$er IV control is occupied mode. Occupied status is provided by the black jumper from terminal TR to terminal N. When unoccupied mode is desired, install a field−supplied timeclock function in place of the jumper between TR and N. When the timeclock contacts are closed, the EconoMi$er IV control will be in occupied mode. When the timeclock contacts are open (removing the 24V signal from terminal N), the EconoMi$er IV will be in unoccupied mode. Demand Control Ventilation (DCV) When using the EconoMi$er IV for demand controlled ventilation, there are some equipment selection criteria which should be considered. When selecting the heat capacity and cool capacity of the equipment, the maximum ventilation rate must be evaluated for design conditions. The maximum damper position must be calculated to provide the desired fresh air. Typically the maximum ventilation rate will be about 5 to 10% more than the typical cfm required per person, using normal outside air design criteria. A proportional anticipatory strategy should be taken with the following conditions: a zone with a large area, varied occupancy, and equipment that cannot exceed the required ventilation rate at design conditions. Exceeding the required ventilation rate means the equipment can condition air at a maximum ventilation rate that is greater than the required ventilation rate for maximum occupancy. A proportional-anticipatory strategy will cause the fresh air supplied to increase as the room CO2 level increases even though the CO2 setpoint has not been reached. By the time the CO2 level reaches the setpoint, the damper will be at maximum ventilation and should maintain the setpoint. In order to have the CO2 sensor control the economizer damper in this manner, first determine the damper voltage output for minimum or base ventilation. Base ventilation is the ventilation required to remove contaminants during unoccupied periods. The following equation may be used to determine the percent of outside air entering the building for a given damper position. For best results there should be at least a 10 degree difference in outside and return-air temperatures. (TO x OA + (TR ) 100 x CO2 Sensor Configuration The CO2 sensor has preset standard voltage settings that can be selected anytime after the sensor is powered up. See Table 10. Use setting 1 or 2 for Bryant equipment. See Table 10. 1. Press Clear and Mode buttons. Hold at least 5 seconds until the sensor enters the Edit mode. 2. Press Mode twice. The STDSET Menu will appear. Table 10 – EconoMi$er IV Sensor Usage APPLICATION Outdoor Air Dry Bulb Differential Dry Bulb Single Enthalpy Differential Enthalpy CO2 for DCV Control using a Wall‐Mounted CO2 Sensor CO2 for DCV Control using a Duct‐Mounted CO2 Sensor RA ) =TM 100 ECONOMI$ER IV WITH OUTDOOR AIR DRY BULB SENSOR Accessories Required None. The outdoor air dry bulb sensor is factory installed. CRTEMPSN002A00* HH57AC078 HH57AC078 and CRENTDIF004A00* 33ZCSENCO2 33ZCSENCO2† and O CRCBDIOX005A00†† 33ZCASPCO2** R * CRENTDIF004A00 and CRTEMPSN002A00 accessories are used on many different base units. As such, these kits may contain parts that will not be needed for installation. † 33ZCSENCO2 is an accessory CO2 sensor. ** 33ZCASPCO2 is an accessory aspirator box required for duct‐ mounted applications. †† CRCBDIOX005A00 is an accessory that contains both 33ZCSENCO2 and 33ZCASPCO2 accessories. TO = Outdoor-Air Temperature OA = Percent of Outdoor Air TR = Return-Air Temperature RA = Percent of Return Air TM = Mixed-Air Temperature Once base ventilation has been determined, set the minimum damper position potentiometer to the correct position. The same equation can be used to determine the occupied or maximum ventilation rate to the building. For example, an output of 3.6 volts to the actuator provides a base ventilation rate of 5% and an output of 6.7 volts provides 3. Use the Up/Down button to select the preset number. See Table 10. 4. Press Enter to lock in the selection. 5. Press Mode to exit and resume normal operation. 45 The custom settings of the CO2 sensor can be changed anytime after the sensor is energized. Follow the steps below to change the non-standard settings: 1. Press Clear and Mode buttons. Hold at least 5 seconds until the sensor enters the Edit mode. 2. Press Mode twice. The STDSET Menu will appear. 3. Use the Up/Down button to toggle to the NONSTD menu and press Enter. 4. Use the Up/Down button to toggle through each of the nine variables, starting with Altitude, until the desired setting is reached. 5. Press Mode to move through the variables. 6. Press Enter to lock in the selection, then press Mode to continue to the next variable. Dehumidification of Fresh Air with DCV (Demand Controlled Ventilation) Control If normal rooftop heating and cooling operation is not adequate for the outdoor humidity level, an energy recovery unit and/or a dehumidification option should be considered. 4. Remove 620−ohm resistor across SO and +. The Free Cool LED should turn off. 5. Return EconoMi$er IV settings and wiring to normal after completing troubleshooting. Single Enthalpy To check single enthalpy: 1. Make sure EconoMi$er IV preparation procedure has been performed. 2. Set the enthalpy potentiometer to A (fully CCW). The Free Cool LED should be lit. 3. Set the enthalpy potentiometer to D (fully CW). The Free Cool LED should turn off. 4. Return EconoMi$er IV settings and wiring to normal after completing troubleshooting. DCV (Demand Controlled Ventilation) and Power Exhaust To check DCV and Power Exhaust: 1. Make sure EconoMi$er IV preparation procedure has been performed. 2. Ensure terminals AQ and AQ1 are open. The LED for both DCV and Exhaust should be off. The actuator should be fully closed. 3. Connect a 9V battery to AQ (positive node) and AQ1 (negative node). The LED for both DCV and Exhaust should turn on. The actuator should drive to between 90 and 95% open. 4. Turn the Exhaust potentiometer CW until the Exhaust LED turns off. The LED should turn off when the potentiometer is approximately 90%. The actuator should remain in position. 5. Turn the DCV setpoint potentiometer CW until the DCV LED turns off. The DCV LED should turn off when the potentiometer is approximately 9−v. The actuator should drive fully closed. 6. Turn the DCV and Exhaust potentiometers CCW until the Exhaust LED turns on. The exhaust contacts will close 30 to 120 seconds after the LED turns on. 7. Return EconoMi$er IV settings and wiring to normal after completing troubleshooting. EconoMi$er IV Preparation This procedure is used to prepare the EconoMi$er IV for troubleshooting. No troubleshooting or testing is done by performing the following procedure. NOTE: This procedure requires a 9V battery, 1.2 kilo−ohm resistor, and a 5.6 kilo−ohm resistor which are not supplied with the EconoMi$er IV. IMPORTANT: Be sure to record the positions of all potentiometers before starting troubleshooting. 1. Disconnect power at TR and TR1. All LEDs should be off. Exhaust fan contacts should be open. 2. Disconnect device at P and P1. 3. Jumper P to P1. 4. Disconnect wires at T and T1. Place 5.6 kilo−ohm resistor across T and T1. 5. Jumper TR to 1. 6. Jumper TR to N. 7. If connected, remove sensor from terminals SO and +. Connect 1.2 kilo−ohm 4074EJM checkout resistor across terminals SO and +. 8. Put 620−ohm resistor across terminals SR and +. 9. Set minimum position, DCV setpoint, and exhaust potentiometers fully CCW (counterclockwise). 10. Set DCV maximum position potentiometer fully CW (clockwise). 11. Set enthalpy potentiometer to D. 12. Apply power (24 vac) to terminals TR and TR1. DCV Minimum and Maximum Position To check the DCV minimum and maximum position: 1. Make sure EconoMi$er IV preparation procedure has been performed. 2. Connect a 9v battery to AQ (positive node) and AQ1 (negative node). The DCV LED should turn on. The actuator should drive to between 90 and 95% open. 3. Turn the DCV Maximum Position potentiometer to midpoint. The actuator should drive to between 20 and 80% open. 4. Turn the DCV Maximum Position potentiometer to fully CCW. The actuator should drive fully closed. 5. Turn the Minimum Position potentiometer to midpoint. The actuator should drive to between 20 and 80% open. 6. Turn the Minimum Position Potentiometer fully CW. The actuator should drive fully open. Differential Enthalpy To check differential enthalpy: 1. Make sure EconoMi$er IV preparation procedure has been performed. 2. Place 620−ohm resistor across SO and +. 3. Place 1.2 kilo−ohm resistor across SR and +. The Free Cool LED should be lit. 46 PRE−START−UP/START−UP 7. Remove the jumper from TR and N. The actuator should drive fully closed. 8. Return EconoMi$er IV settings and wiring to normal after completing troubleshooting. ! WARNING PERSONAL INJURY HAZARD Failure to follow this warning could result in personal injury or death. Supply−Air Sensor Input To check supply−air sensor input: 1. Make sure EconoMi$er IV preparation procedure has been performed. 2. Set the Enthalpy potentiometer to A. The Free Cool LED turns on. The actuator should drive to between 20 and 80% open. 3. Remove the 5.6 kilo−ohm resistor and jumper T to T1. The actuator should drive fully open. 4. Remove the jumper across T and T1. The actuator should drive fully closed. 5. Return EconoMi$er IV settings and wiring to normal after completing troubleshooting. 1. Follow recognized safety practices and wear approved Personal Protective Equipment (PPE), including safety glasses and gloves when checking or servicing refrigerant system. 2. Do not use a torch to remove any component. System contains oil and refrigerant under pressure. To remove a component, wear PPE and proceed as follows: a. Shut off all electrical power to unit. Apply applicable Lock−out/Tagout procedures. b. Recover refrigerant to relieve all pressure from system using both high−pressure and low pressure ports. c. Do not use a torch. Cut component connection tubing with tubing cutter and remove component from unit. d. Carefully un−sweat remaining tubing stubs when necessary. Oil can ignite when exposed to torch flame. 3. Do not operate compressor or provide any electric power to unit unless compressor terminal cover is in place and secured. 4. Do not remove compressor terminal cover until all electrical power is disconnected and approved Lock−out/Tagout procedures are in place. 5. Relieve all pressure from system before touching or disturbing anything inside terminal box whenever refrigerant leak is suspected around compressor terminals. 6. Never attempt to repair a soldered connection while refrigerant system is under pressure. EconoMi$er IV Troubleshooting Completion This procedure is used to return the EconoMi$er IV to operation. No troubleshooting or testing is done by performing the following procedure. 1. Disconnect power at TR and TR1. 2. Set enthalpy potentiometer to previous setting. 3. Set DCV maximum position potentiometer to previous setting. 4. Set minimum position, DCV setpoint, and exhaust potentiometers to previous settings. 5. Remove 620−ohm resistor from terminals SR and +. 6. Remove 1.2 kilo−ohm checkout resistor from terminals SO and +. If used, reconnect sensor from terminals SO and +. 7. Remove jumper from TR to N. 8. Remove jumper from TR to 1. 9. Remove 5.6 kilo−ohm resistor from T and T1. Reconnect wires at T and T1. 10. Remove jumper from P to P1. Reconnect device at P and P1. 11. Apply power (24 vac) to terminals TR and TR1. ! WARNING ELECTRICAL OPERATION HAZARD Failure to follow this warning result in personal injury or death. The unit must be electrically grounded in accordance with local codes and NEC ANSI/NFPA 70 (American National Standards Institute/National fire Protection Association. Proceed as follows to inspect and prepare the unit for initial start−up: 1. Remove all access panels. 2. Read and follow instructions on all WARNING, CAUTION, and INFORMATION labels attached to, or shipped with, unit. 47 3. Make the following inspections: a. Inspect for shipping and handling damages such as broken lines, loose parts, or disconnected wires, etc. b. Inspect for oil at all refrigerant tubing connections and on unit base. Detecting oil generally indicates a refrigerant leak. Leak−test all refrigerant tubing connections using electronic leak detector, halide torch, or liquid−soap solution. c. Inspect all field−wiring and factory−wiring connections. Be sure that connections are completed and tight. Be sure that wires are not in contact with refrigerant tubing or sharp edges. d. Inspect coil fins. If damaged during shipping and handling, carefully straighten fins with a fin comb. 4. Verify the following conditions: a. Make sure that condenser−fan blade are correctly positioned in fan orifice. See Condenser−Fan Adjustment section for more details. b. Make sure that air filter(s) is in place. c. Make sure that condensate drain trap is filled with water to ensure proper drainage. d. Make sure that all tools and miscellaneous loose parts have been removed. Outdoor−Air Inlet Screens Outdoor−air inlet screen must be in place before operating unit. Compressor Mounting Compressors are internally spring mounted. Do not loosen or remove compressor hold down bolts. Internal Wiring Check all electrical connections in unit control boxes. Tighten as required. Refrigerant Service Ports Each unit system has two 1/4” SAE flare (with check valves) service ports: one on the suction line, and one on the compressor discharge line. Be sure that caps on the ports are tight. Compressor Rotation CAUTION EQUIPMENT DAMAGE HAZARD Failure to follow this CAUTION could result in equipment damage. Scroll compressors can only compress refrigerant if rotating in the right direction. Reverse rotation for extended times can result in internal damage to the compressor. Scroll compressors are sealed units and cannot be repaired on−site. START−UP, GENERAL Unit Preparation Make sure that unit has been installed in accordance with installation instructions and applicable codes. IMPORTANT: Follow the base unit’s start-up sequence as described in the unit’s installation instructions: In addition to the base unit start-up, there are a few steps needed to properly start-up the controls. RTU-OPEN’s Service Test function should be used to assist in the base unit start-up and also allows verification of output operation. Controller configuration is also part of start-up. This is especially important when field accessories have been added to the unit. The factory pre-configures options installed at the factory. There may also be additional installation steps or inspection required during the start-up process. Additional Installation/Inspection Inspect the field installed accessories for proper installation, making note of which ones do or do not require configuration changes. Inspect the RTU-OPEN’s Alarms for initial insight to any potential issues. Refer to the following manual: “Controls, Start−up, Operation and Troubleshooting Instructions.” Inspect the SAT sensor for relocation as intended during installation. Inspect special wiring as directed below. NOTE: When the compressor is rotating in the wrong direction, the unit will make an elevated level of noise and will not provide cooling. On 3−phase units with scroll compressors, it is important to be certain compressor is rotating in the proper direction. To determine whether or not compressor is rotating in the proper direction: 1. Connect service gauges to suction and discharge pressure fittings. 2. Energize the compressor. 3. The suction pressure should drop and the discharge pressure should rise, as is normal on any start−up. If the suction pressure does not drop and the discharge pressure does not rise to normal levels: 1. Note that the evaporator fan is probably also rotating in the wrong direction. 2. Turn off power to the unit and install lockout tag. 3. Reverse any two of the unit power leads. 4. Reapply electrical power to the compressor. 5. The suction pressure should drop, and the discharge pressure should rise, which is normal for scroll compressors on start−up. 6. Replace the compressor if suction/discharge pressures are not within specifications for the specific compressor. Return−Air Filters Ensure correct filters are installed in unit (see Appendix II − Physical Data). Do not operate unit without return−air filters. 48 Cooling LED is observed, the evaporator−fan on/off delay has been modified. Set space thermostat to OFF position. To start unit, turn on main power supply. Set system selector switch at COOL position and fan switch at AUTO. position. Adjust thermostat to a setting below room temperature. Compressor starts on closure of contactor. Ventilation (Continuous Fan) Set fan and system selector switches at ON and OFF positions, respectively. Evaporator fan operates continuously to provide constant air circulation. When the evaporator−fan selector switch is turned to the OFF position, there is a 30−second delay before the fan turns off. Check unit charge. Refer to Refrigerant Charge section. Reset thermostat at a position above room temperature. Compressor will shut off. Evaporator fan will shut off after a 30−second delay. START−UP, RTU−OPEN CONTROLS To shut off unit, set system selector switch at OFF position. Resetting thermostat at a position above room temperature shuts unit off temporarily until space temperature exceeds thermostat setting. NOTICE SET−UP INSTRUCTIONS Refer to the following manuals for additional installation, wiring and troubleshooting information for the RTU−OPEN Controller.: “Controls, Start−up, Operation and Troubleshooting Instructions,” “RTU Open Installation and Start−up Guide” and “RTU−Open Integration Guide”. Have a copy of these manuals available at unit start−up. NOTE: The default value for the evaporator−fan motor on/off delay is 45 seconds. The Integrated Gas Unit Controller (IGC) modifies this value when abnormal limit switch cycles occur. Based upon unit operating conditions, the on delay can be reduced to 0 seconds and the off delay can be extended to 180 seconds. When one flash of the FASTENER TORQUE VALUES Table 11 – Torque Values Supply fan motor mounting 120 in-lbs (13.6 Nm) ± 12 in-lbs (1.4Nm) Supply fan motor adjustment plate 120 in-lbs (13.6 Nm) ± 12 in-lbs (1.4Nm) Motor pulley setscrew 72 in-lbs (8.1 Nm) ± 5 in-lbs (0.6 Nm) Fan pulley setscrew 72 in-lbs (8.1 Nm) ± 5 in-lbs (0.6 Nm) Blower wheel hub setscrew 72 in-lbs (8.1 Nm) ± 5 in-lbs (0.6 Nm) Bearing locking collar setscrew 50 in-lbs (6.2 Nm) — 60 in-lbs (6.8 Nm) Compressor mounting bolts 65 in-lbs (7.3 Nm) — 75 in-lbs (8.5Nm) Condenser fan motor mounting bolts 20 in-lbs (2.3 Nm) ± 2 in-lbs 0.2 Nm) Condenser fan hub setscrew 84 in-lbs (9.5 Nm) ± 12 in-lbs (1.4 Nm) 49 APPENDIX I. MODEL NUMBER NOMENCLATURE Position: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 Example: 5 5 8 J E 1 7 D 0 0 0 A 1 A 0 A A Unit Type 558 -Cooling RTU with optional Electric Heat Packaging & 2-Speed Indoor Fan Motor A = Standard Packaging and electromechanical controls that require W7212 EconoMi$er IV C = Standard Packaging and electromechanical controls that require W7220 EconoMi$er X D = Standard Packaging and 2-speed indoor fan motor (VFD) Controller Model J - Puron® (R-410A) Refrigerant Voltage E = 460-3-60 P = 208/230-3-60 T = 575-3-60 Factory Installed Options 0A = None NOTE: See the 558J 15 to 27.5 ton Price Pages for a complete list of factory installed options. Cooling Tons (Vertical Air Flow Models Only) 17 = 15 tons 20 = 17.5 tons 24 = 20 tons 28 = 25 tons 30 = 27.5 tons Outdoor Air Options A = None B = Temp Econo, Baro Relief, Standard Leak (W7212 or W7220) D = Temp Econo, Cert Pwr Exhaust, Standard Leak (W7212 or W7220) E = Temp Econo, Baro Relief, Standard Leak w/CO2 (W7212 or W7220) G = Temp Econo, Cert Pwr Exhaust, Standard Leak w/CO2 (W7212 or W7220) H = Enthalpy Econo, Baro Relief, Standard Leak (W7212 or W7220) K = Enthalpy Econo, Cert Pwr Exhaust, Standard Leak (W7212 or W7220) L = Enthalpy Econo, Baro Relief, Standard Leak w/CO2 (W7212 or W7220) N = Enthalpy Econo, Cert Pwr Exhaust, Standard Leak w/CO2 (W7212 or W7220) P = Manual Outdoor Air Damper Q = 2 Position Damper U = Temp Econo, Baro Relief, Ultra Low Leak, (W7220) V = Temp Econo, Cent Pwr Exhaust, Ultra Low Leak Economizer (W7220) W = Enthalpy Econo, Baro Relief, Ultra Low Leak (W7220) X = Enthalpy Econo, Cent Pwr Exhaust, Ultra Low Leak (W7220) Refrig. System Options D = Two stage Cooling K = Two stage Cooling with Perfect Humidity™ (only available on 17-28 sizes with RTPF coil models) Heat Level (Field installed electric heaters available) 000 = No Heat Novation Coil Only (Outdoor - Indoor - Hail Guard) G = Al/Al - Al/Cu H = Al/Al - Cu/Cu J = Al/Al - E-coat Al/Cu K = E-coat Al/Al - Al/Cu L = E-coat Al/Al - E-coat Al/Cu T = Al/Al - Al/Cu — Louvered Hail Guards U = Al/Al - Cu/Cu — Louvered Hail Guards V = Al/Al - E-coat Al/Cu — Louvered Hail Guards W = E-coat Al/Al - Al/Cu — Louvered Hail Guards X = E-coat Al/Al - E-coat Al/Cu — Louvered Hail Guards Round Tube Plate Fin (RTPF) Coil Options (Outdoor - Indoor - Hail Guard) A = Al/Cu - Al/Cu B = Precoat Al/Cu - Al/Cu C = E-coat Al/Cu - Al/Cu D = E-coat Al/Cu - E-coat Al/Cu E = Cu/Cu - Al/Cu F = Cu/Cu - Cu/Cu M = Al/Cu - Al/Cu — Louvered Hail Guards N = Precoat Al/Cu - Al/Cu — Louvered Hail Guards P = E-coat Al/Cu - Al/Cu — Louvered Hail Guards Q = E-coat Al/Cu - E-coat Al/Cu — Louvered Hail Guards R = Cu/Cu - Al/Cu — Louvered Hail Guards S = Cu/Cu - Cu/Cu — Louvered Hail Guards Indoor Fan Options (Vertical Air Flow Models Only) 1 = Standard Static/Vertical Supply, Return Air Flow 2 = Medium Static/Vertical Supply, Return Air Flow 3 = High Static/Vertical Supply, Return Air Flow B = Medium Static High Efficiency Motor/Vertical Supply, Return Air Flow C = High Static High Efficiency Motor/Vertical Supply, Return Air Flow C13776B Serial Number Format POSITION NUMBER 1 2 3 4 5 6 7 8 9 10 TYPICAL 4 8 0 8 G 1 2 3 4 5 POSITION DESIGNATES 1−2 Week of manufacture (fiscal calendar) 3−4 Year of manufacture (“08” = 2008) 5 Manufacturing location (G = ETP, Texas, USA) 6−10 Sequential number 50 APPENDIX II. PHYSICAL DATA Table 12 – PHYSICAL DATA − VERTICAL RTPF (Round Tube/Plate Fin Coil Design) (COOLING) 15 − 27.5 TONS 558J-D17 558J-E17 558J-D20 RTPF RTPF RTPF RTPF 2 / 2 / Scroll 2 / 2 / Scroll 2 / 2 / Scroll 2 / 2 / Scroll 16.3/17.5 25.9/25.7 16.3/17.5 25.9/25.7 Acutrol TXV Acutrol TXV High-press. Trip / Reset (psig) 630 / 505 630 / 505 630 / 505 630 / 505 Low-press. Trip / Reset (psig) 54 / 117 27 / 44 54 / 117 27 / 44 Material Cu / Al Cu / Al Cu / Al Cu / Al 3/8" 3/8" 3/8" 3/8" Rows / FPI 4 / 15 4 / 15 4 / 15 4 / 15 total face area (ft2) 22.00 22.00 22.00 22.00 Condensate drain conn. size 3/4" 3/4" 3/4" 3/4" Cu / Al Refrigeration System # Circuits / # Comp. / Type R-410a charge A/B (lbs) Metering device 558J-E20 Evap. Coil Tube Diameter Perfect Humidity] Coil Material n/a Cu / Al n/a Tube Diameter n/a 3/8" n/a 3/8" Rows / FPI n/a 1 / 17 n/a 1 / 17 total face area (ft2) n/a 22.00 n/a 22.00 Evap. fan and motor — VERTICAL Motor Qty / Belt Qty / Driver Type Standard Static 1 / 1 / Belt 1 / 1 / Belt 1 / 1 / Belt 1 / 1 / Belt Nominal Nameplate HP 2.9 2.9 3.7 3.7 Max BHP 2.9 2.9 3.7 3.7 514-680 514-680 622-822 622-822 1200 1200 1200 1200 56 56 56 56 2 / Centrifugal 2 / Centrifugal 2 / Centrifugal 2 / Centrifugal 15 x 15 15 x 15 15 x 15 15 x 15 RPM range Max Blower/Shaft RPM motor frame size Fan Qty / Type Fan Diameter (in) Motor Qty / Belt Qty / Driver Type Medium Static 1 / 1 / Belt 1 / 1 / Belt 1 / 1 / Belt 1 / 1 / Belt Nominal Nameplate HP 3.7 3.7 4.9 4.9 Max BHP 3.7 3.7 4.9 4.9 679-863 679-863 713-879 713-879 1200 1200 1200 1200 56 56 56 56 2 / Centrifugal 2 / Centrifugal 2 / Centrifugal 2 / Centrifugal 15 x 15 15 x 15 15 x 15 15 x 15 n/a RPM range Max Blower/Shaft RPM motor frame size Fan Qty / Type Fan Diameter (in) Motor Qty / Belt Qty / Driver Type High Static 1 / 1 / Belt 1 / 1 / Belt n/a Nominal Nameplate HP 5.25 5.25 3.7 3.7 Max BHP 4.9 4.9 n/a n/a 826-1009 826-1009 n/a n/a 1200 1200 n/a n/a 56 56 n/a n/a 2 / Centrifugal 2 / Centrifugal n/a n/a 15 x 15 15 x 15 n/a n/a Motor Qty / Belt Qty / Driver Type n/a n/a 1 / 1 / Belt 1 / 1 / Belt Nominal Nameplate HP n/a n/a 5.0 5.0 Max BHP (208/230/460/575v) n/a n/a 6.5/ 6.9/ 7.0/ 8.3 6.5/ 6.9/ 7.0/ 8.3 713-879 RPM range Max Blower/Shaft RPM motor frame size Fan Qty / Type Fan Diameter (in) High Stat ic- Medi um Efficiency High Stat ic- High Efficiency RPM range n/a n/a 713-879 Max Blower/Shaft RPM n/a n/a 1200 1200 motor frame size n/a n/a 184T 184T Fan Qty / Type n/a n/a 2 / Centrifugal 2 / Centrifugal Fan Diameter (in) n/a n/a 15 x 15 15 x 15 Motor Qty / Belt Qty / Driver Type n/a n/a 1 / 1 / Belt 1 / 1 / Belt Nominal Nameplate HP 2.9 2.9 5.0 5.0 Max BHP (208/230/460/575v) n/a n/a 6.5/ 6.9/ 7.0/ 8.3 6.5/ 6.9/ 7.0/ 8.3 882-1078 RPM range n/a n/a 882-1078 Max Blower/Shaft RPM n/a n/a 1200 1200 motor frame size n/a n/a 184T 184T Fan Qty / Type n/a n/a 2 / Centrifugal 2 / Centrifugal Fan Diameter (in) n/a n/a 15 x 15 15 x 15 51 APPENDIX II. PHYSICAL DATA (CONT) Table 12 - PHYSICAL DATA − VERTICAL (cont) RTPF (Round Tube/Plate Fin Coil Design) (COOLING) 15 - 27.5 TONS 558J-D24 558J-E24 558J-D28 558J-E28 RTPF RTPF RTPF RTPF RTPF 2 / 2 / Scroll 2 / 2 / Scroll 2 / 2 / Scroll 2 / 2 / Scroll 2 / 2 / Scroll 20.6/14.7 27.9/20.5 19.8/ 20.4 27.9/ 28.9 27.0/ 28.5 Acutrol TXV Acutrol TXV Acutrol High-press. Trip / Reset (psig) 630 / 505 630 / 505 630 / 505 630 / 505 630 / 505 Low-press. Trip / Reset (psig) 54 / 117 27 / 44 54 / 117 27 / 44 54 / 117 Cu / Al Cu / Al Cu / Al Cu / Al Cu / Al 3/8" 3/8" 3/8" 3/8" 3/8" Rows / FPI 4 / 15 4 / 15 4 / 15 4 / 15 4 / 15 total face area (ft2) 22.00 22.00 23.11 23.11 26 Condensate drain conn. size 3/4" 3/4" 3/4" 3/4" 3/4" Refrigeration System # Circuits / # Comp. / Type R-410a charge A/B (lbs) Metering device 558J-D30 Evap. Coil Material Tube Diameter Humidimizer Coil Material n/a Cu / Al n/a Cu / Al n/a Tube Diameter n/a 3/8" n/a 3/8" n/a Rows / FPI n/a 1 / 17 n/a 1 / 17 n/a total face area (ft2) n/a 22.00 n/a 23.11 n/a 1 / 1 / Belt 1 / 1 / Belt 1 / 1 / Belt 1 / 1 / Belt n/a 5.25 4.9 690-863 1200 58 2 / Centrifugal 15 x 15 5.25 4.9 690-86 1200 58 2 / Centrifugal 15 x 15 5.25 4.9 717-911 1200 58 2 / Centrifugal 15 x 15 5.25 4.9 717-911 1200 58 2 / Centrifugal 15 x 15 n/a n/a n/a n/a n/a n/a n/a n/a n/a 5.0 n/a n/a n/a n/a n/a n/a6 n/a n/a 6.5/ 6.9/ 7.0/ 8.3 751-954 n/a n/a n/a n/a 1200 n/a n/a n/a n/a 184T n/a n/a n/a n/a n/a n/a n/a n/a 2 / Centrifugal 15 x 15 1 / 1 / Belt 1 / 1 / Belt 1 / 1 / Belt 1 / 1 / Belt 1 / 1 / Belt 5.0 5.0 5.0 5.0 7.5 6.5/ 6.9/ 7.0/ 8.3 6.5/ 6.9/ 7.0/ 8.3 6.5/ 6.9/ 7.0/ 8.3 6.5/ 6.9/ 7.0/ 8.3 10.5/11.9/11.9/11 835-1021 835-1021 913-1116 913-1116 973-1175 1200 1200 1200 1200 1200 184T 2 / Centrifugal 15 x 15 184T 2 / Centrifugal 15 x 15 184T 2 / Centrifugal 15 x 15 184T 2 / Centrifugal 15 x 15 213T 2 / Centrifugal 15 x 15 1 / 1 / Belt 1 / 1 / Belt 1 / 1 / Belt 1 / 1 / Belt 1 / 2 Belt 7.5 7.5 7.5 7.5 10.0 10.5/11.9/11.9/11 10.5/11.9/11.9/11 10.5/11.9/11.9/11 10.5/11.9/11.9/11 11.9/12.9/12.9/14.1 941-1176 941-1176 941-1176 941-1176 1015-1299 1200 1200 1200 1200 1300 213T 2 / Centrifugal 15 x 15 213T 2 / Centrifugal 15 x 15 213T 2 / Centrifugal 15 x 15 213T 2 / Centrifugal 15 x 15 213T 2 / Centrifugal 15 x 15 Evap. fan and motor — VERTICAL Standard Static Standard Static High Efficiency Medium Static High Efficiency High StaticHigh Efficiency Motor Qty / Belt Qty / Driver Type Nom Namplate HP Max BHP RPM range MaxBlwr/Shaft RPM motor frame size Fan Qty / Type Fan Diameter (in) Motor Qty / Belt Qty / Driver Type Nom Namplate HP Max BHP RPM range MaxBlwr/Shaft RPM motor frame size Fan Qty / Type Fan Diameter (in) Motor Qty / Belt Qty / Driver Type Nom Namplate HP Max BHP (208/230/460/575v) RPM range MaxBlwr/Shaft RPM motor frame size Fan Qty / Type Fan Diameter (in) Motor Qty / Belt Qty / Driver Type Nom Namplate HP Max BHP (208/230/460/575v) RPM range MaxBlwr/Shaft RPM motor frame size Fan Qty / Type Fan Diameter (in) 52 n/a n/a0 n/a n/a n/a n/a 1 / 1 / Belt APPENDIX II. PHYSICAL DATA (CONT) Table 12 - PHYSICAL DATA − VERTICAL (cont) RTPF (Round Tube/Plate Fin Coil Design) (COOLING) 15-27.5 TONS 558J-D17 558J-E17 558J-D20 558J-E20 558J-D24 558J-E24 558J-D28 558J-E28 558J-D30 Cond. Coil (Circuit A) RTPF RTPF RTPF RTPF RTPF RTPF RTPF RTPF RTPF Coil Length (in) Coil type 70 70 70 70 82 82 75 75 95 Coil Height (in) 44 44 44 44 44 44 52 52 52 Rows / FPI 2 /17 2 /17 2 /17 2 /17 2 /17 2 /17 2 /17 2 /17 2 /17 total face area (ft2) 21.4 21.4 21.4 21.4 25.1 25.1 27.1 27.1 34.3 Cond. Coil (Circuit B) RTPF RTPF RTPF RTPF RTPF RTPF RTPF RTPF RTPF Coil Length (in) Coil type 70 70 70 70 57 57 75 75 95 Coil Height (in) 44 44 44 44 44 52 52 52 52 Rows / FPI 2 /17 2 /17 2 /17 2 /17 2 /17 2 /17 2 /17 2 /17 2 /17 total face area (ft2) 21.4 21.4 21.4 21.4 17.4 17.4 27.1 27.1 34.3 3 / direct 3 / direct 3 / direct 3 / direct 4/ direct 4/ direct 4 / direct 4 / direct 6 / direct Motor HP / RPM 1/4 / 1100 1/4 / 1100 1/4 / 1100 1/4 / 1100 1/4 / 1100 1/4 / 1100 1/4 / 1100 1/4 / 1100 1/4 / 1100 Fan diameter (in) 22 22 22 22 22 22 22 22 22 RA Filter # / size (in) 6 / 20 x 25 x2 6 / 20 x 25 x2 6 / 20 x 25 x2 6 / 20 x 25 x2 9 / 16 x 25 x2 9 / 16 x 25 x2 9 / 16 x 25 x2 9 / 16 x 25 x2 9 / 16 x 25 x2 OA inlet screen # / size (in) 4 / 16 x 25 x1 4 / 16 x 25 x1 4 / 16 x 25 x1 4 / 16 x 25 x1 4 / 16 x 25 x1 4 / 16 x 25 x1 4 / 16 x 25 x1 4 / 16 x 25 x1 4 / 16 x 25 x1 Cond. fan / motor Qty / Motor drive type Filters 53 APPENDIX II. PHYSICAL DATA (CONT) Table 12 - PHYSICAL DATA − VERTICAL (cont) Novation - All Aluminum Coil Design Refrigeration System # Circuits / # Comp. / Type (COOLING) 15-27.5 TONS 558J*17 MCHX 558J*20 MCHX 558J*24 MCHX 558J*28 MCHX 2 / 2 / Scroll 2 / 2 / Scroll 2 / 2 / Scroll 2 / 2 / Scroll R-410a charge A/B (lbs) 9.5/12.0 9.5/12.0 14.4/12.5 12.5/13.0 Metering device Acutrol Acutrol Acutrol Acutrol High-press. Trip / Reset (psig) 630 / 505 630 / 505 630 / 505 630 / 505 Low-press. Trip / Reset (psig) 54 / 117 54 / 117 54 / 117 54 / 117 Material Cu / Al Cu / Al Cu / Al Cu / Al 3/8" 3/8" 3/8" 3/8" Rows / FPI 4 / 15 4 / 15 4 / 15 4 / 15 total face area (ft2) 19.56 19.56 22.00 23.11 Condensate drain conn. size 3/4" 3/4" 3/4" 3/4" Evap. Coil Tube Diameter Evap. fan and motor — VERTICAL Motor/Belt Qty / Drivr Type Standard Static 1 / 1 Belt 1 / 1 Belt 1 / 1 Belt 1 / 1 Belt Nominal Nameplate HP 2.9 3.7 5.25 5.25 Max BHP 2.9 3.7 4.9 4.9 514-680 622-822 690-863 717-911 1200 1200 1200 1200 56 56 56 56 2 / Centrifugal 2 / Centrifugal 2 / Centrifugal 2 / Centrifugal 15 x 15 15 x 15 15 x 15 15 x 15 RPM range Max Blower/Shaft RPM motor frame size Fan Qty / Type Fan Diameter (in) Motor/Belt Qty / Drivr Type Medium Static 1 / 1 Belt n/a n/a n/a Nominal Nameplate HP 3.7 n/a n/a n/a Max BHP 3.7 n/a n/a n/a 679-863 n/a n/a n/a 1200 n/a n/a n/a 56 n/a n/a n/a 2 / Centrifugal n/a n/a n/a 15 x 15 n/a n/a n/a RPM range Max Blower/Shaft RPM motor frame size Fan Qty / Type Fan Diameter (in) Motor/Belt Qty / Drivr Type High Static 1 / 1 Belt n/a n/a n/a Nominal Nameplate HP 5.25 n/a n/a n/a Max BHP 4.9 n/a n/a n/a 826-1009 n/a n/a n/a 1200 n/a n/a n/a 56 n/a n/a n/a 2 / Centrifugal n/a n/a n/a 15 x 15 n/a n/a n/a Motor/Belt Qty / Drivr Type n/a 1 / 1 Belt 1 / 1 Belt 1 / 1 Belt Nominal Nameplate HP n/a 5.0 5.0 5.0 Max BHP (208/230/460/575v) n/a 6.5/ 6.9/ 7.0/ 8.3 6.5/ 6.9/ 7.0/ 8.3 6.5/ 6.9/ 7.0/ 8.3 913-1116 RPM range Max Blower/Shaft RPM motor frame size Fan Qty / Type Fan Diameter (in) Medium Static High Efficiency High Stat ic- High Efficiency RPM range n/a 713-879 835-1021 Max Blower/Shaft RPM n/a 1200 1200 1200 motor frame size n/a 184T 184T 184T Fan Qty / Type n/a 2 / Centrifugal 2 / Centrifugal 2 / Centrifugal Fan Diameter (in) n/a 15 x 15 15 x 15 15 x 15 Motor/Belt Qty / Drivr Type n/a 1 / 1 Belt 1 / 1 Belt 1 / 1 Belt Nominal Nameplate HP n/a 5.0 7.5 7.5 Max BHP (208/230/460/575v) n/a 6.5/ 6.9/ 7.0/ 8.3 10.5/11.9/11.9/11 10.5/11.9/11.9/11 941-1176 RPM range n/a 882-1078 941-1176 Max Blower/Shaft RPM n/a 1200 1200 1200 motor frame size n/a 184T 213T 213T Fan Qty / Type n/a 2 / Centrifugal 2 / Centrifugal 2 / Centrifugal Fan Diameter (in) n/a 15 x 15 15 x 15 15 x 15 54 APPENDIX II. PHYSICAL DATA (CONT) Table 12 - PHYSICAL DATA − VERTICAL (cont) Novation - All Aluminum Coil Design (COOLING) 15-27.5 TONS 558J*17 558J*20 558J*24 558J*28 Cond. Coil (Circuit A) Novation Novation Novation Novation Coil Length (in) Coil type 70 70 82 75 Coil Height (in) 44 44 44 52 1 / 20.3 1 / 20.3 1 / 20.3 1 / 20.3 21.4 21.4 25.1 27.1 Rows / FPI total face area (ft2) Cond. Coil (Circuit B) Novation Novation Novation Novation Coil Length (in) Coil type 70 70 57 75 Coil Height (in) 44 44 44 52 1 / 20.3 1 / 20.3 1 / 20.3 1 / 20.3 21.4 21.4 17.4 27.1 Rows / FPI total face area (ft2) Cond. fan / motor Qty / Motor drive type 3 / direct 3 / direct 4 / direct 4 / direct Motor HP / RPM 1/4 / 1100 1/4 / 1100 1/4 / 1100 1/4 / 1100 Fan diameter (in) 22 22 22 22 RA Filter # / size (in) 6 / 20 x 25 x 2 6 / 20 x 25 x 2 6 / 20 x 25 x 2 9 / 16 x 25 x 2 OA inlet screen # / size (in) 4 / 16 x 25 x 1 4 / 16 x 25 x 1 4 / 16 x 25 x 1 4 / 16 x 25 x 1 Filters 55 APPENDIX II. PHYSICAL DATA (CONT) TABLE 13 – PHYSICAL DATA − HORIZONTAL (COOLING) RTPF (Round Tube/Plate Fin Coil Design) Refrigeration System # Circuits / # Comp. / Type R-410a charge A/B (lbs) Metering device High-press. Trip / Reset (psig) Low-press. Trip / Reset (psig) 15−25 TONS 558J-D18 558J-E18 558J-D21 558J-E21 2 / 2 / Scroll 17/16.4 TXV 630 / 505 54 / 117 2 / 2 / Scroll 24.5/25.7 TXV 630 / 505 27 / 44 2 / 2 / Scroll 17.5/16.8 TXV 630 / 505 54 / 117 2 / 2 / Scroll 25.5/25.5 TXV 630 / 505 27 / 44 Cu / Al 3/8" RTPF 4 / 15 22 3/4" Cu / Al 3/8" RTPF 4 / 15 22 3/4" Cu / Al 3/8" RTPF 4 / 15 22 3/4" Cu / Al 3/8" RTPF 4 / 15 22 3/4" Material Tube Diameter Rows / FPI total face area (ft2) Condensate drain conn. size Humidimizer Coil Material Tube Diameter Rows / FPI total face area (ft2) Evap. fan and motor — HORIZONTAL Motor Qty / Belt Qty / Driver Type Nominal Nameplate HP Max BHP RPM range Standard Static Max Blower/Shaft RPM motor frame size Fan Qty / Type Fan Diameter (in) n/a n/a n/a n/a Cu / Al 3/8" RTPF 1 / 17 22 n/a n/a n/a n/a Cu / Al 3/8" RTPF 1 / 17 22 1/1/ Belt 2.9 2.9 514-680 1100 56 2 / Centrifugal 18 x 15/15 X 11 1/1/ Belt 2.9 2.9 514-680 1100 56 2 / Centrifugal 18 x 15/15 X 11 1/1/ Belt 3.7 3.7 622-822 1100 56 2 / Centrifugal 18 x 15/15 X 11 1/1/ Belt 3.7 3.7 622-822 1100 56 2 / Centrifugal 18 x 15/15 X 11 Medium Static Motor Qty / Belt Qty / Driver Type Nominal Nameplate HP Max BHP RPM range Max Blower/Shaft RPM motor frame size Fan Qty / Type Fan Diameter (in) 1/1/ Belt 3.7 3.7 614-780 1100 56 2 / Centrifugal 18 x 15/15 X 11 1/1/ Belt 3.7 3.7 614-780 1100 56 2 / Centrifugal 18 x 15/15 X 11 1/1/ Belt 5.25 4.9 713-879 1100 56 2 / Centrifugal 18 x 15/15 X 11 1/1/ Belt 5.25 4.9 713-879 1100 56 2 / Centrifugal 18 x 15/15 X 11 High Static Motor Qty / Belt Qty / Driver Type Nominal Nameplate HP Max BHP RPM range Max Blower/Shaft RPM motor frame size Fan Qty / Type Fan Diameter (in) 1/1/ Belt 5.25 4.9 746-912 1100 56 2 / Centrifugal 18 x 15/15 X 11 1/1/ Belt 5.25 4.9 746-912 1100 56 2 / Centrifugal 18 x 15/15 X 11 n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a High StaticHigh Eff. Motor Qty / Belt Qty / Driver Type Nominal Nameplate HP Max BHP RPM range Max Blower/Shaft RPM motor frame size Fan Qty / Type Fan Diameter (in) n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a 1/1/ Belt 5.0 6.5/ 6.9/ 7.0/ 8.3 882-1078 1100 184T 2 / Centrifugal 18 x 15/15 X 11 1/1/ Belt 5.0 6.5/ 6.9/ 7.0/ 8.3 882-1078 1100 184T 2 / Centrifugal 18 x 15/15 X 11 56 APPENDIX II. PHYSICAL DATA (CONT) Table 13 PHYSICAL DATA − HORIZONTAL (cont) RTPF (Round Tube/Plate Fin Coil Design) (COOLING) 15−25 TONS 558J-D25 558J-E25 558J-D29 558J-E29 2 / 2 / Scroll 23.8/23.1 TXV 630 / 505 54 / 117 2 / 2 / Scroll 30.0/30.7 TXV 630 / 505 27 / 44 2 / 2 / Scroll 24.9/27.7 TXV 630 / 505 54 / 117 2 / 2 / Scroll 35.1/35.4 TXV 630 / 505 27 / 44 Cu / Al 3/8" RTPF 4 / 15 26 3/4" Cu / Al 3/8" RTPF 4 / 15 26 3/4" Cu / Al 3/8" RTPF 4 / 15 26 3/4" Cu / Al 3/8" RTPF 4 / 15 26 3/4" n/a n/a n/a n/a Cu / Al 3/8" RTPF 1 / 17 26 n/a n/a n/a n/a Cu / Al 3/8" RTPF 1 / 17 26 Evap. fan and motor HORIZONTAL Motor Qty / Belt Qty / Driver Type Nominal Nameplate HP Max BHP RPM range Standard Static Max Blower/Shaft RPM motor frame size Fan Qty / Type Fan Diameter (in) 1/1/ Belt 5.25 4.9 690-863 1100 56 2 / Centrifugal 18 x 15/15 X 11 1/1/ Belt 5.25 4.9 690-863 1100 56 2 / Centrifugal 18 x 15/15 X 11 1/1/ Belt 5.25 4.9 647-791 1100 56 2 / Centrifugal 18 x 15/15 X 11 1/1/ Belt 5.25 4.9 647-791 1100 56 2 / Centrifugal 18 x 15/15 X 11 Medium Static - High Eff. Motor Qty / Belt Qty / Driver Type Nominal Nameplate HP Max BHP RPM range Max Blower/Shaft RPM motor frame size Fan Qty / Type Fan Diameter (in) 1/1/ Belt 5.0 6.5/ 6.9/ 7.0/ 8.3 835-1021 1100 184T 2 / Centrifugal 18 x 15/15 X 11 1/1/ Belt 5.0 6.5/ 6.9/ 7.0/ 8.3 835-1021 1100 184T 2 / Centrifugal 18 x 15/15 X 11 1/1/ Belt 5.0 6.5/ 6.9/ 7.0/ 8.3 755-923 1100 184T 2 / Centrifugal 18 x 15/15 X 11 1/1/ Belt 5.0 6.5/ 6.9/ 7.0/ 8.3 755-923 1100 184T 2 / Centrifugal 18 x 15/15 X 11 High StaticHigh Eff. Motor Qty / Belt Qty / Driver Type Nominal Nameplate HP Max BHP RPM range Max Blower/Shaft RPM motor frame size Fan Qty / Type Fan Diameter (in) 1/1/ Belt 7.5 10.5/11.9/11.9/11 941-1100 1100 213T 2 / Centrifugal 18 x 15/15 X 11 1/1/ Belt 7.5 10.5/11.9/11.9/11 941-1100 1100 213T 2 / Centrifugal 18 x 15/15 X 11 1/1/ Belt 7.5 10.5/11.9/11.9/11 906-1100 1100 213T 2 / Centrifugal 18 x 15/15 X 11 1/1/ Belt 7.5 10.5/11.9/11.9/11 906-1100 1100 213T 2 / Centrifugal 18 x 15/15 X 11 Refrigeration System # Circuits / # Comp. / Type R-410a charge A/B (lbs) Metering device High-press. Trip / Reset (psig) Low-press. Trip / Reset (psig) Material Tube Diameter Rows / FPI total face area (ft2) Condensate drain conn. size Humidimizer Coil Material Tube Diameter Rows / FPI total face area (ft2) 57 APPENDIX II. PHYSICAL DATA (CONT) Table 13 PHYSICAL DATA − HORIZONTAL (cont) RTPF (Round Tube/Plate Fin Coil Design) (COOLING) 15−25 TONS 558J-D18 558J-E18 558J-D21 558J-E21 558J-D25 558J-E25 558J-D29 558J-E29 Cond. Coil (Circuit A) RTPF RTPF RTPF RTPF RTPF RTPF RTPF RTPF Coil Length (in) Coil type 70 70 72 72 82 82 95 95 Coil Height (in) 44 44 44 44 52 52 52 52 Rows / FPI 2 /17 2 /17 2 /17 2 /17 2 /17 2 /17 2 /17 2 /17 total face area (ft2) 21.4 21.4 22.0 22.0 29.6 29.6 34.3 34.3 Cond. Coil (Circuit B) RTPF RTPF RTPF RTPF RTPF RTPF RTPF RTPF Coil Length (in) Coil type 70 70 64 64 80 80 95 95 Coil Height (in) 44 44 44 44 52 52 52 52 Rows / FPI 2 /17 2 /17 2 /17 2 /17 2 /17 2 /17 2 /17 2 /17 total face area (ft2) 21.4 21.4 19.5 19.5 29.6 29.6 34.3 34.3 Cond. fan / motor Qty / Motor drive type 3 / direct 3 / direct 4 / direct 4 / direct 4/ direct 4/ direct 6 / direct 6 / direct Motor HP / RPM 1/4 / 1100 1/4 / 1100 1/4 / 1100 1/4 / 1100 1/4 / 1100 1/4 / 1100 1/4 / 1100 1/4 / 1100 Fan diameter (in) 22 22 22 22 22 22 22 22 RA Filter # / size (in) 6/20 x 25 x 2 6/20 x 25 x 2 6/20 x 25 x 2 6/20 x 25 x 2 9/16 x 25 x 2 9/16 x 25 x 2 9/16 x 25 x 2 9/16 x 25 x 2 OA inlet screen # / size (in) 4/16 x 25 x 1 4/16 x 25 x 1 4/16 x 25 x 1 4/16 x 25 x 1 4/16 x 25 x 1 4/16 x 25 x 1 4/16 x 25 x 1 4/16 x 25 x 1 Filters 58 APPENDIX III. FAN PERFORMANCE Table 14 – 558J*D17 CFM 4500 4900 5250 5650 6000 6400 6750 7150 7500 0.2 RPM 436 456 479 503 525 551 574 601 625 CFM 4500 4900 5250 5600 6000 6400 6750 7100 7500 VERTICAL SUPPLY / RETURN Available External Static Pressure (in. wg) 0.6 0.8 BHP RPM BHP RPM BHP 0.89 611 1.20 684 1.54 1.02 625 1.36 696 1.72 1.16 638 1.51 708 1.88 1.33 654 1.70 721 2.09 1.50 668 1.88 734 2.28 1.72 686 2.11 750 2.53 1.93 702 2.33 764 2.76 2.20 722 2.61 781 3.06 2.46 740 2.88 797 3.34 Available External Static Pressure (in. wg) 1.4 1.6 1.8 BHP RPM BHP RPM BHP 2.66 916 3.17 965 3.48 2.89 926 3.40 975 3.74 3.10 935 3.61 983 3.98 3.36 946 3.84 994 4.28 3.61 956 4.12 1003 4.56 3.91 968 4.42 1015 4.90 4.19 979 4.70 ------4.53 ------------4.86 ------------0.4 BHP 0.60 0.72 0.85 1.01 1.17 1.38 1.58 1.84 2.09 RPM 529 546 561 580 598 619 638 661 682 BHP 2.27 2.48 2.68 2.92 3.15 3.43 3.70 4.03 4.33 RPM 864 874 884 895 906 918 929 943 955 1.2 RPM 808 819 829 841 852 865 878 892 905 Std Static Motor and Drive - 514-680 RPM, Max BHP 2.29 High Static Motor and Drive - 826-1009 RPM, Max BHP 4.9 Bold - Requires alternate static drive package Table 15 – 558J*D20 CFM 5250 5700 6150 6550 7000 7450 7900 8300 8750 CFM 5250 5700 6150 6550 7000 7450 7900 8300 8750 BHP 0.85 1.03 1.25 1.46 1.74 2.05 2.40 2.75 3.18 RPM 561 582 605 627 652 679 706 731 760 BHP 2.68 2.95 3.26 3.54 3.90 4.29 4.71 5.11 5.61 RPM 884 897 910 923 938 953 970 985 1003 BHP 1.90 2.09 2.27 2.50 2.71 2.97 3.22 3.53 3.82 2.0 RPM 1012 1021 1029 1040 ---------------- BHP 3.92 4.19 4.44 4.76 ---------------- Medium Static Motor and Drive - 679-863 RPM, Max BHP 3.7 ---- Outside operating range ITALIC - Requires high static drive package with different motor pulley Available External Static Pressure (in. wg) 0.6 0.8 BHP RPM BHP RPM 1.16 638 1.51 708 1.35 656 1.72 723 1.58 675 1.96 740 1.81 693 2.20 756 2.10 714 2.50 775 2.42 737 2.84 795 2.78 761 3.21 816 3.14 783 3.58 836 3.58 809 4.03 859 Available External Static Pressure (in. wg) 1.4 1.6 1.8 BHP RPM BHP RPM 3.10 935 3.53 938 3.40 947 3.85 995 3.72 960 4.19 1008 4.03 972 4.52 1019 4.40 987 4.92 1033 4.81 1001 5.34 1047 5.25 1017 5.81 1062 5.67 1031 6.25 1076 6.19 1048 6.78 1092 17.5 TON 0.4 1.2 RPM 829 843 857 871 886 903 921 937 956 1.0 RPM 749 760 771 784 795 810 822 838 852 VERTICAL SUPPLY / RETURN 0.2 RPM 479 506 535 561 591 622 653 681 713 15 TON 1.0 BHP 1.88 2.11 2.37 2.63 2.94 3.30 3.68 4.06 4.53 RPM 771 785 801 815 832 850 869 887 908 BHP 3.98 4.32 4.68 5.03 5.45 5.89 6.38 6.83 7.39 RPM 1029 1041 1053 1064 1077 1091 1105 1119 1134 2.0 Std Static Motor and Drive - 622-822 RPM, Max BHP 3.7 ---- Outside operating range Medium Static Motor and Drive - 713-879 RPM, Max BHP 6.5 / 6.9 / 7.0 / 8.3; Voltage 208 / 230 / 460 / 575 High Static Motor and Drive - 882-1078 RPM, Max BHP 6.5 / 6.9 / 7.0 / 8.3; Voltage 208 / 230 / 460 / 575 ITALIC - Requires high static drive package with different Bold - Requires alternate static drive package motor pulley, all voltages BLACK Requires high static drive with different motor pulley; Confirm max BHP coverage based on unit voltage selected. UNDERSCORE — Operation point covered by factory package; Confirm max BHP coverage based on unit voltage selected. 59 BHP 2.27 2.53 2.81 3.08 3.41 3.78 4.18 4.57 5.05 BHP 4.44 4.80 5.18 5.55 5.98 6.45 6.96 7.43 8.01 APPENDIX III. FAN PERFORMANCE (CONT) Table 16 – 558J*D24 CFM 6000 6500 7000 7500 8000 8500 9000 9500 10000 0.2 RPM 519 545 571 597 624 650 677 703 730 CFM 6000 6500 7000 7500 8000 8500 9000 9500 10000 VERTICAL SUPPLY / RETURN 0.4 BHP 1.13 1.36 1.63 1.93 2.27 2.64 3.05 3.50 3.99 RPM 609 633 658 683 709 734 760 786 813 BHP 2.80 3.18 3.60 4.06 4.57 5.12 5.72 6.37 7.07 RPM 912 930 949 969 990 1012 1034 1057 1080 1.2 RPM 861 880 900 921 943 965 988 1011 1035 Available External Static Pressure (in. wg) 0.6 0.8 BHP RPM BHP RPM 1.48 682 1.80 747 1.75 705 2.11 768 2.06 728 2.45 791 2.40 753 2.83 814 2.78 777 3.25 837 3.20 802 3.71 861 3.67 827 4.21 886 4.17 853 4.76 910 4.73 878 5.36 935 Available External Static Pressure (in. wg) 1.4 1.6 1.8 BHP RPM BHP RPM 3.15 962 3.50 1008 3.55 978 3.92 1024 3.99 996 4.38 1041 4.47 1016 4.89 1060 5.00 1036 5.44 1079 5.58 1056 6.05 1099 6.21 1078 6.70 1120 6.89 1100 7.41 1141 7.62 1123 8.17 1163 20 TON 1.0 BHP 2.13 2.46 2.83 3.24 3.69 4.19 4.73 5.31 5.95 RPM 806 826 847 869 892 915 939 963 987 BHP 3.86 4.30 4.78 5.31 5.89 6.52 7.19 7.93 8.72 RPM 1053 1068 1085 1102 1121 1140 1160 1181 ---- BHP 2.46 2.82 3.21 3.65 4.13 4.66 5.23 5.85 6.52 2.0 BHP 4.23 4.69 5.19 5.74 6.34 6.99 7.69 8.45 ---- Std Static Motor and Drive - 690-863 RPM, Max BHP 4.9 ---- Outside operating range Medium Static Motor and Drive - 835-1021 RPM, Max BHP 6.5 / 6.9 / 7.0 / 8.3; Voltage 208 / 230 / 460 / 575 High Static Motor and Drive - 941-1176 RPM, Max BHP 10.5 / 11.9 / 11.9 / 11.0; Voltage 208 / 230 / 460 / 575 ITALIC - Requires high static drive package with different motor pulley, all voltages Bold - Requires alternate static drive package Table 17 – 558J*D28 CFM 7500 8150 8750 9400 10000 10650 11250 11900 12500 0.2 RPM 555 579 599 619 635 649 653 647 641 CFM 7500 8150 8750 9400 10000 10650 11250 11900 12500 VERTICAL SUPPLY / RETURN BHP 1.35 1.62 1.89 2.20 2.50 2.82 3.09 3.31 3.51 RPM 664 690 714 739 762 787 808 831 851 BHP 3.53 4.04 4.56 5.18 5.80 6.52 7.24 8.07 8.90 RPM 978 1003 1027 1053 1077 1104 1128 1155 1179 1.2 RPM 927 953 977 1003 1028 1054 1079 1105 1130 Available External Static Pressure (in. wg) 0.4 0.6 0.8 BHP RPM BHP RPM BHP 1.85 744 2.29 812 2.70 2.19 771 2.68 838 3.14 2.54 795 3.08 863 3.59 2.96 822 3.56 889 4.12 3.38 846 4.04 914 4.65 3.86 872 4.61 940 5.28 4.35 895 5.17 965 5.90 4.91 921 5.83 991 6.63 5.46 943 6.48 1015 7.34 Available External Static Pressure (in. wg) 1.4 1.6 1.8 BHP RPM BHP RPM BHP 3.94 1026 4.36 1071 4.79 4.49 1051 4.94 1096 5.39 5.04 1074 5.53 1119 6.01 5.70 1100 6.21 1144 6.73 6.35 1124 6.90 1168 7.45 7.12 1150 7.71 ------7.88 1174 8.51 ------8.76 ------------9.63 ------------- 25 TON 1.0 RPM 872 889 923 949 974 1000 1025 1051 1075 2.0 RPM 1114 1138 1161 1186 ---------------- Std Static Motor and Drive - 717-911 RPM, Max BHP 4.9 ---- Outside operating range Medium Static Motor and Drive - 913-1116 RPM, Max BHP 6.5 / 6.9 / 7.0 / 8.3; Voltage 208 / 230 / 460 / 575 High Static Motor and Drive - 941-1176 RPM, Max BHP 10.5 / 11.9 / 11.9 / 11.0; Voltage 208 / 230 / 460 / 575 ITALIC - Requires high static drive package with different Bold - Requires alternate static drive package motor pulley, all voltages UNDERSCORE — Operation point covered by factory package; Confirm max BHP coverage based on unit voltage selected. 60 BHP 3.12 3.60 4.08 4.65 5.23 5.91 6.58 7.37 8.14 BHP 5.21 5.85 6.49 7.25 ---------------- APPENDIX III. FAN PERFORMANCE (CONT) Table 18 – 558J−D30 CFM 8250 8950 9650 10300 11000 11700 12400 13050 13750 0.2 RPM 582 605 626 642 653 647 641 635 629 CFM 8250 8950 9650 10300 11000 11700 12400 13050 13750 VERTICAL SUPPLY / RETURN 0.4 BHP 1.66 1.98 2.32 2.65 2.99 3.22 3.47 3.70 3.96 RPM 694 722 749 774 800 824 848 868 888 BHP 4.13 4.75 5.43 6.12 6.93 7.81 8.76 9.71 10.79 RPM 1007 1035 1063 1089 1118 1147 1175 1202 1230 1.2 RPM 957 985 1013 1040 1068 1097 1126 1152 1180 Available External Static Pressure (in. wg) 0.6 0.8 BHP RPM BHP RPM BHP 2.25 775 2.75 842 3.22 2.67 803 3.23 871 3.75 3.13 832 3.76 900 4.34 3.60 858 4.30 926 4.93 4.14 886 4.93 955 5.64 4.73 913 5.62 983 6.40 5.36 940 6.37 1011 7.22 5.98 964 7.11 1036 8.04 6.67 989 7.95 1063 8.99 Available External Static Pressure (in. wg) 1.4 1.6 1.8 BHP RPM BHP RPM BHP 4.58 1055 5.04 1099 5.49 5.24 1082 5.73 1126 6.22 5.96 1110 6.49 1154 7.02 6.70 1136 7.27 1180 7.83 7.55 1164 8.17 1208 8.77 8.48 1193 9.14 1236 9.79 9.48 1221 10.19 1265 10.89 10.48 1248 11.24 1291 11.99 11.63 1277 12.45 ------- 27.5 TON Std Static Motor and Drive - 751-954 RPM, Max BHP 6.5 ---- Outside operating range Medium Static Motor and Drive - 973-1175 RPM, Max BHP 10.5 / 11.9 / 11.9 / 11.0; Voltage 208 / 230 / 460 / 575 High Static Motor and Drive - 1015-1300 RPM, Max BHP 11.9 / 12.9 / 12.9 / 14.1; Voltage 208 / 230 / 460 / 575 ITALIC - Requires high static drive package with different Bold - Requires alternate static drive package motor pulley, all voltages BLACK Operation point covered by factory package; Confirm max BHP coverage based on unit voltage selected. 61 1.0 RPM 902 931 959 986 1014 1043 1071 1097 1125 BHP 3.67 4.25 4.89 5.54 6.29 7.12 8.01 8.90 9.92 2.0 RPM 1142 1169 1196 1221 1249 1277 ---------- BHP 5.95 6.72 7.56 8.40 9.38 10.44 ---------- APPENDIX III. FAN PERFORMANCE (CONT) Table 19 – 558J*D18 CFM 4500 4900 5250 5650 6000 6400 6750 7150 7500 0.2 RPM 472 500 525 554 580 610 636 667 694 CFM 4500 4900 5250 5650 6000 6400 6750 7150 7500 HORIZONTAL SUPPLY / RETURN 0.4 BHP 1.04 1.29 1.48 1.76 2.04 2.39 2.74 3.18 3.60 RPM 549 573 595 620 643 670 695 723 748 BHP 3.81 4.16 4.49 ‐ ‐ ‐ ‐ ‐ ‐ RPM 828 845 ‐ ‐ ‐ ‐ ‐ ‐ ‐ 1.2 RPM 781 799 816 ‐ ‐ ‐ ‐ ‐ ‐ Available External Static Pressure (in. wg) 0.6 0.8 BHP RPM BHP RPM 1.51 616 2.03 676 1.76 638 2.30 696 2.00 658 2.57 715 2.30 681 2.90 736 2.61 702 3.22 756 2.99 727 3.64 779 3.36 749 4.03 800 3.83 775 4.52 ‐ 4.28 ‐ ‐ ‐ Available External Static Pressure (in. wg) 1.4 1.6 1.8 BHP RPM BHP RPM 4.46 ‐ ‐ ‐ 4.84 ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ 15 TON 1.0 BHP 2.59 2.89 3.18 3.54 3.88 4.32 4.74 ‐ ‐ RPM 731 750 767 787 806 ‐ ‐ ‐ ‐ BHP ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ RPM ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ 2.0 Standard Static Motor and Drive – 514 – 680 RPM, Max BHP 2.9 Medium Static Motor and Drive – 614 – 780 RPM, Max BHP 3.7 High Static Motor and Drive – 746 – 912 RPM, Max BHP 4.9 – Outside operating range Table 20 – 558J*D21 CFM 5250 5700 6150 6550 7000 7450 7900 8300 8750 CFM 5250 5700 6150 6550 7000 7450 7900 8300 8750 BHP 1.48 1.80 2.16 2.54 3.01 3.54 4.14 4.72 5.45 1.2 RPM 816 838 861 882 906 931 958 ‐ ‐ BHP ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ HORIZONTAL SUPPLY / RETURN 0.2 RPM 525 558 591 621 656 690 726 757 793 BHP 3.19 3.51 3.82 4.21 4.58 ‐ ‐ ‐ ‐ BHP 4.49 4.96 5.48 5.99 6.61 7.30 8.05 ‐ ‐ Available External Static Pressure (in. wg) 0.4 0.6 0.8 RPM BHP RPM BHP RPM 595 2.00 658 2.57 715 624 2.35 684 2.95 739 654 2.74 711 3.37 764 681 3.14 736 3.80 788 712 3.65 765 4.33 815 744 4.21 795 4.93 843 777 4.84 825 5.59 872 806 5.45 853 6.23 898 840 6.21 885 7.02 928 Available External Static Pressure (in. wg) 1.4 1.6 1.8 RPM BHP RPM BHP RPM 861 5.20 904 5.82 945 882 5.70 925 6.46 965 904 6.25 946 7.04 986 925 6.78 966 7.60 ‐ 948 7.43 988 8.28 ‐ 973 8.15 ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ Std Static Motor and Drive - 622 – 822 RPM, Max BHP 3.7 17.5 TON 1.0 BHP 3.18 3.58 4.04 4.50 5.06 5.68 6.37 7.04 7.86 RPM 767 790 814 836 862 888 916 940 ‐ BHP 6.68 7.24 7.85 ‐ ‐ ‐ ‐ ‐ ‐ RPM 984 1003 ‐ ‐ ‐ ‐ ‐ ‐ ‐ BHP 3.82 4.26 4.75 5.23 5.82 6.47 7.19 7.89 ‐ 2.0 Medium Static Motor and Drive - 713-879 RPM, Max BHP 4.9 High Static Motor and Drive - 835-1021 RPM, Max BHP 6.5 / 6.9 / 7.0 / 8.3; Voltage 208 / 230 / 460 / 575 - Outside operating range BLACK ITALIC - Requires high static drive package with different motor pulley Operation point covered by factory package; Confirm max BHP coverage based on unit voltage selected. 62 BHP 7.45 8.04 ‐ ‐ ‐ ‐ ‐ ‐ ‐ APPENDIX III. FAN PERFORMANCE (CONT) Table 21 – 558J*D25 CFM 6000 6500 7000 7500 8000 8500 9000 9500 10000 0.2 RPM 575 610 646 683 720 758 796 834 873 CFM 6000 6500 7000 7500 8000 8500 9000 9500 10000 HORIZONTAL SUPPLY / RETURN Available External Static Pressure (in. wg) 0.6 0.8 BHP RPM BHP RPM 2.01 708 2.51 764 2.37 738 2.90 792 2.79 768 3.35 821 3.25 800 3.85 851 3.78 832 4.41 882 4.36 865 5.02 913 5.01 899 5.71 946 5.73 933 6.46 978 6.52 968 7.28 1011 Available External Static Pressure (in. wg) 1.4 1.6 1.8 BHP RPM BHP RPM 4.68 949 5.26 989 5.20 974 5.82 1013 5.77 1000 6.42 1039 6.40 1026 7.08 1064 7.09 1053 7.79 1091 7.83 1081 8.57 ‐ 8.65 ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ 0.4 BHP 1.54 1.87 2.25 2.68 3.17 3.73 4.34 5.03 5.78 RPM 645 677 710 744 779 814 849 885 921 BHP 4.11 4.60 5.14 5.74 6.39 7.11 7.89 8.74 9.66 RPM 907 933 959 986 1014 1042 1071 ‐ ‐ 1.2 RPM 863 889 916 944 972 1002 1031 1062 1093 20 TON Std Static Motor and Drive - 690 – 680 RPM, Max BHP 4.9 - Outside operating range 1.0 BHP 3.02 3.45 3.93 4.46 5.05 5.70 6.42 7.20 8.06 RPM 815 842 870 899 929 959 990 1021 1053 BHP 5.86 6.44 7.08 7.77 8.51 ‐ ‐ ‐ ‐ RPM 1026 1051 1076 ‐ ‐ ‐ ‐ ‐ ‐ BHP 3.56 4.02 4.53 5.09 5.72 6.40 7.15 7.96 8.86 2.0 BHP 6.47 7.09 7.75 ‐ ‐ ‐ ‐ ‐ ‐ Bold - Requires alternate static drive package Medium Static Motor and Drive - 835 – 1021 RPM, Max BHP 6.5 / 6.9 / 7.0 / 8.3; Voltage 208 / 230 / 460 / 575 High Static Motor and Drive - 941-1100 RPM, Max BHP 10.5 / 11.9 / 11.9 / 11.0; Voltage 208 / 230 / 460 / 575 Underscore - Operation point covered by medium static drive; Confirm max BHP coverage based on unit voltage selected. Table 22 – 558J*D29 CFM 7500 8000 8500 9000 9500 10000 10500 11000 11500 0.2 RPM 683 720 758 796 834 873 911 950 989 CFM 7500 8000 8500 9000 9500 10000 10500 11000 11500 HORIZONTAL SUPPLY / RETURN BHP 2.68 3.17 3.73 4.34 5.03 5.78 6.62 7.53 8.53 RPM 744 779 814 849 885 921 958 995 1033 BHP 5.74 6.39 7.11 7.89 8.74 9.66 ‐ ‐ ‐ RPM 986 1014 1042 1071 ‐ ‐ ‐ ‐ ‐ 1.2 RPM 944 972 1002 1031 1062 1093 ‐ ‐ ‐ 25 TON Available External Static Pressure (in. wg) 0.4 0.6 0.8 BHP RPM BHP RPM BHP 3.25 800 3.85 851 4.46 3.78 832 4.41 882 5.05 4.36 865 5.02 913 5.70 5.01 899 5.71 946 6.42 5.73 933 6.46 978 7.20 6.25 968 7.28 1011 8.06 7.39 1003 8.18 1045 8.99 8.34 1038 9.16 1079 10.01 9.37 1074 10.23 ‐ ‐ Available External Static Pressure (in. wg) 1.4 1.6 1.8 BHP RPM BHP RPM BHP 6.40 1026 7.08 1064 7.77 7.09 1053 7.79 1091 8.51 7.83 1081 8.57 ‐ ‐ 8.65 ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ Std Static Motor and Drive - 647 – 791 RPM, Max BHP 4.9 - Outside operating range High Static Motor and Drive - 906-1100 RPM, Max BHP 10.5 / 11.9 / 11.9 / 11.0; Voltage 208 / 230 / 460 / 575 63 BHP 5.09 5.72 6.40 7.15 7.96 8.86 9.82 ‐ ‐ 2.0 RPM ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ BHP ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ Bold - Requires alternate static drive package Medium Static Motor and Drive - 755 – 923 RPM, Max BHP 6.5 / 6.9 / 7.0 / 8.3; Voltage 208 / 230 / 460 / 575 ITALIC - Requires high static drive package with different motor pulley 1.0 RPM 899 929 959 990 1021 1053 1086 ‐ ‐ APPENDIX III. FAN PERFORMANCE (CONT) Table 23 – Pulley Adjustment − Vertical − 3 Phase UNIT MOTOR/DRIVE COMBO 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 680 663 647 630 614 597 580 564 547 531 514 Medium Static 863 845 826 808 789 771 753 734 716 697 679 High Static 1009 991 972 954 936 918 899 881 863 844 826 Standard Static 822 802 782 762 742 722 702 682 662 642 622 Medium Static 879 862 846 829 813 796 779 763 746 730 713 High Static 1078 1058 1039 1019 1000 980 960 941 921 902 882 Standard Static 17 20 24 28 30 MOTOR PULLEY TURNS OPEN 0 Standard Static 863 846 828 811 794 777 759 742 725 707 690 Medium Static 1021 1002 984 965 947 928 909 891 872 854 835 High Static 1176 1153 1129 1106 1082 1059 1035 1012 988 965 941 Standard Static 911 892 872 853 833 814 795 775 756 736 717 Medium Static 1116 1096 1075 1055 1035 1015 994 974 954 933 913 High Static 1176 1153 1129 1106 1082 1059 1035 1012 988 965 941 Standard Static 954 934 913 893 873 853 832 812 792 771 751 Medium Static 1175 1155 1135 1114 1094 1074 1054 1034 1013 993 973 High Static 1299 1271 1242 1214 1185 1157 1129 1100 1072 1043 1015 NOTE: Do not adjust pulley further than 5 turns open. - Factory settings Table 24 – Pulley Adjustment − Horizontal − 3 Phase MOTOR PULLEY TURNS OPEN UNIT 18 21 25 29 MOTOR/DRIVE COMBO 0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 Standard Static 680 663 647 630 614 597 580 564 547 531 514 Medium Static 780 763 747 730 714 697 680 664 647 631 614 High Static 912 895 879 862 846 829 812 796 779 763 746 Standard Static 822 802 782 762 742 722 702 682 662 642 622 Medium Static 879 862 846 829 813 796 779 763 746 730 713 High Static 1078 1058 1039 1019 1000 980 960 941 921 902 882 Standard Static 863 846 828 811 794 777 759 742 725 707 690 Medium Static 1021 1002 984 965 947 928 909 891 872 854 835 High Static 1176 1153 1129 1106 1082 1059 1035 1012 988 965 941 *Standard Static 791 777 762 748 733 719 705 690 676 661 647 Medium Static 923 906 889 873 856 839 822 805 789 772 755 High Static 1107 1087 1067 1047 1027 1007 986 966 946 926 906 NOTE: Do not adjust pulley further than 5 turns open. * - Standard Static drive only for 50 series; 48 series used a field supplied drive - Factory settings 64 APPENDIX IV. WIRING DIAGRAMS Table 25 – Wiring Diagrams 558J−D17 / 558J−D30 UNITS DUAL CIRCUIT SIZE PERFECT HUMIDITY™ VOLTAGE CONTROL POWER CONTROL POWER 208/230-3-60 50HE500887-K 50HE500894-I 50HE502180-E 50HE502185-B 460-3-60 50HE500887-K 50HE500895-I 50HE502180-E 50HE502182-C 575-3-60 50HE500887-K 50HE500895-I 50HE502180-E 50HE501774-C 208/230-3-60 50HE500887-K 50HE500894-I 50HE502180-E 50HE502185-B 460-3-60 50HE500887-K 50HE500895-I 50HE502180-E 50HE502182-C 575-3-60 50HE500887-K 50HE500895-I 50HE502180-E 50HE501774-C 208/230-3-60 50HE500887-K 50HE500894-I 50HE502180-E 50HE502185-B 460-3-60 50HE500887-K 50HE500895-I 50HE502180-E 50HE502182-C 575-3-60 50HE500887-K 50HE500895-I 50HE502180-E 50HE501774-C 208/230-3-60 50HE500887-K 50HE500894-I 50HE502180-E 50HE502185-B 460-3-60 50HE500887-K 50HE500895-I 50HE502180-E 50HE502182-C 575-3-60 50HE500887-K 50HE500895-I 50HE502180-E 50HE501774-C 208/230-3-60 50HE502337-D 50HE500894-I 50HE502180-E 50HE502185-B D30 460-3-60 50HE502335-D 50HE500895-I 50HE502180-E 50HE502182-C 575-3-60 50HE502335-D 50HE500895-I 50HE502180-E 50HE501774-C ALL RTU-Open* 50HE501687-B 50HE501687-B ALL SAV/VFD 50HE502975-C 50HE502975-C D17 D20 D24 D28 NOTE: Component arrangement on Control; Legend on Power Schematic. * RTU-OPEN control labels overlay a portion of the base unit control label. The base unit label drawing and the control option drawing are required to provide a complete unit control diagram. 65 APPENDIX IV. WIRING DIAGRAMS (CONT) C150425 Fig. 57 − 558J D17 − D28 Control Diagram − 208/230−3−60; 460/575−3−60 66 APPENDIX IV. WIRING DIAGRAMS (CONT) C150370 Fig. 58 − 558J D30 Control Diagram − 208/230−3−60 67 APPENDIX IV. WIRING DIAGRAMS (CONT) 5 C150368 Fig. 59 − 558J D30 Control Diagram − 460/575−3−60 68 APPENDIX IV. WIRING DIAGRAMS (CONT) C150373 Fig. 60 − 558J D17 − D30 Power Diagram − 208/230−3−60 69 APPENDIX IV. WIRING DIAGRAMS (CONT) C12399 Fig. 61 − 558J D17 − D30 Power Diagram 460/575−3−60 70 APPENDIX IV. WIRING DIAGRAMS (CONT) C150375 Fig. 62 − 558J D17 − D30 Control Diagram 208/230−3−60; 460/575−3−60 with Perfect Humidity] 71 APPENDIX IV. WIRING DIAGRAMS (CONT) C150376 Fig. 63 − 558J D17 − D30 Power Diagram 208/230−3−60 with Perfect Humidity] 72 APPENDIX IV. WIRING DIAGRAMS (CONT) C150378 Fig. 64 − 558J D17 − D30 Power Diagram 460−3−60 with Perfect Humidity] 73 APPENDIX IV. WIRING DIAGRAMS (CONT) C150379 Fig. 65 − 558J D17 − D30 Power Diagram 575−3−60 with Perfect Humidity] 74 APPENDIX IV. WIRING DIAGRAMS (CONT) C12691 Fig. 66 − 558J − RTU−OPEN Wiring Diagram 75 APPENDIX IV. WIRING DIAGRAMS (CONT) C12689A Fig. 67 − 558J − SAV − VFD System Control Wiring Diagram 76 APPENDIX V. MOTORMASTER SENSOR LOCATIONS SENSOR LOCATION C12258 Fig. 68 − Motormaster Sensor Locations − D17, D20, and D24 SENSOR LOCATION C12259 Fig. 69 − Motormaster Sensor Location − D28 77 Copyright 2016 Bryant Heating and Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231 Edition Date: 03/16 Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 78 Catalog No: SM558J-17-30-01 Replaces: New UNIT START-UP CHECKLIST I. PRELIMINARY INFORMATION: MODEL NO.: DATE: SERIAL NO: _____________________________________ ______________ TECHNICIAN: ___________________________________ II. PRE-START-UP (insert check mark in box as each item is completed): VERIFY THAT JOBSITE VOLTAGE AGREES WITH VOLTAGE LISTED ON RATING PLATE VERIFY THAT ALL PACKAGING MATERIALS HAVE BEEN REMOVED FROM UNIT REMOVE ALL SHIPPING HOLD DOWN BOLTS AND BRACKETS PER INSTALLATION INSTRUCTIONS VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTALLATION INSTRUCTIONS VERIFY THAT FLUE HOOD IS INSTALLED CHECK REFRIGERANT PIPING FOR INDICATIONS OF LEAKS; INVESTIGATE AND REPAIR IF NECESSARY CHECK GAS PIPING FOR LEAKS CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS CHECK THAT RETURN (INDOOR) AIR FILTERS ARE CLEAN AND IN PLACE VERIFY THAT UNIT INSTALLATION IS LEVEL CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE AND SETSCREW TIGHTNESS CHECK TO ENSURE THAT ELECTRICAL WIRING IS NOT IN CONTACT WITH REFRIGERANT LINES OR SHARP METAL EDGES VERIFY PULLEY ALIGNMENT AND BELT TENSION PER INSTALLATION INSTRUCTIONS III. START-UP (REFER TO UNIT SERVICE/MAINTENANCE MANUAL FOR INSTRUCTIONS) ELECTRICAL SUPPLY VOLTAGE L1-L2 L2-L3 L3-L1 CIRCUIT 1 COMPRESSOR AMPS L1 L2 L2 CIRCUIT 2 COMPRESSOR AMPS L1 L2 L2 INDOOR FAN AMPS L1 L2 L2 OUTDOOR FAN AMPS NO. 1 NO. 2 TEMPERATURES OUTDOOR-AIR TEMPERATURE DB WB RETURN-AIR TEMPERATURE DB WB COOLING SUPPLY AIR DB WB GAS HEAT SUPPLY AIR DB PRESSURES GAS INLET PRESSURE IN. WG GAS MANIFOLD PRESSURE IN. WG (LOW FIRE) IN. WG (HI FIRE) REFRIGERANT SUCTION, CIRCUIT 1 PSIG F REFRIGERANT SUCTION, CIRCUIT 2 PSIG F REFRIGERANT DISCHARGE, CIRCUIT 1 PSIG F REFRIGERANT DISCHARGE, CIRCUIT 2 PSIG F VERIFY THAT 3−PHASE FAN MOTOR AND BLOWER ARE ROTATING IN CORRECT DIRECTION VERIFY THAT 3−PHASE SCROLL COMPRESSOR IS ROTATING IN CORRECT DIRECTION VERIFY REFRIGERANT CHARGE USING CHARGING CHARTS GENERAL SET ECONOMIZER MINIMUM VENT AND CHANGEOVER SETTINGS TO MATCH JOB REQUIREMENTS (IF EQUIPPED) 79 Copyright 2016 Bryant Heating and Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231 Edition Date: 03/16 Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 80 Catalog No: SM558J-17-30-01 Replaces: New
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project