NA11538C_ Dynaciat LG.indd

dynaciat lg
Water-cooled chillers
High energy efficiency
Compact and quiet
Scroll compressors
N TA L LY F R
IEN
D
T
EN
CT
IO N
D E L'E N VI RO
NN
N TA L LY F R
IE
35 to 350 kW
Heating capacity : 40 to 210 kW
Cooling capacity :
ND
HFC R410A
EM
TE
O
O
TE
NME
PR
PR
Cooling or heating
RO
LY
HFC R407C
VI
T
NME
CT
EN
RO
EN
VI
LY
EN
Brazed plate heat exchangers
Self-adjusting electronic control
IO N
D E L'E N VI RO
NN
EM
Use
The water-cooled packaged LG DYNACIAT series of
chillers-heaters are especially designed to supply chilled
or hot water with a middle capacity for air conditioning
application systems encountered in collective and
commercial buildings, as well as industrial premises and
processes. These packaged units are designed to be
implanted as standard indoors in a technical plant, sheltered
against adverse weather and frost.
To operate in COOLING mode, these units must be cooled
by a water circulation coming from an external source, such
as underground water or city water if using a water flow
control valve, or connected to an external water drycooler or
a cooling tower.
On a water supply, the LGP series can be used as a heat
pump during winter time.
Connected to a underfloor heating or cooling system, fan coil
units or an air handling unit, a LGP series heat pump provides
heating and air conditioning of buildings thanks to a set of
valves located on the water circuit (not supplied).
Each unit is assembled, internally wired (logic and starting
box), charged with refrigerant, and is subject to a operation
test in the factory.
The installation work is simple, and the only operations
required on site are electrical wiring and water piping
connections.
Range
DYNACIAT LG - LGP series
DYNACIAT LGN series
Water-cooled chillers or heat pump models
Chiller models without condenser (for split system)
DYNACIAT ILG series
Water-to-water reversible heat pumps models
Description
DYNACIAT LG series units are supplied as standard with the
following components:
- water cooled condenser,
- chiller evaporator,
- capacity control system on outlet chilled or hot water,
- logic, control and starting electric box :
. Power supply : 3~50Hz 400V (+6%/-10%) + earth
. Logic circuit : 1~50Hz 230V (+6%/-10%)
(transformers are mounted on the unit as standard feature),
- casing for indoor installation.
n Conformity with the EC European directives
‘‘LOW VOLTAGE’’ directive (LVD),
Machines 98 / 37 EEC
Electromagnetic EMC 89 / 336 EEC
Pressure vessels PED 97 / 23 EEC
category 2 (LG-LGP-ILG)
PED is not applicable (LGN) unit not complete
n Conforms to standards
- EN 60-204 and EN 378-2
heat pumps - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - nA 12.538 B
1
Water-cooled chillers
Technical
Efficiency
DynaCiat LG - LGP
120V
150V
200V
240V
300V
350V
400V
500V
540V
600V
Net cooling capacity (1)
kW
34,50
45,30
61,10
68,60
90,90
104,70
118,90
146,50
158,90
181,90
Net power input (1)
kW
8,00
10,30
13,90
16,20
20,30
23,60
26,90
33,80
36,10
40,10
4,29
4,40
4,40
4,23
4,48
4,43
4,42
4,33
4,40
4,53
4,63
4,69
5,23
4,99
4,97
4,98
5,02
4,80
4,99
5,06
net EER (3)
net EER ESEER (3)
u
Net heating capacity (2)
kW
40,46
53,45
71,45
80,63
106,91
122,44
139,91
172,46
186,57
213,28
Net power input (2)
kW
9,75
12,50
17,16
19,68
24,88
28,56
32,63
40,66
44,10
49,25
4,15
4,28
4,16
4,10
4,30
4,29
4,29
4,24
4,23
4,33
67,0
70,0
69,0
70,0
73,0
74,0
75,0
76,0
75,0
76,0
COP (3)
Sound power level (3)
dB(A)
Refrigerant
circuit
Compressor
Type
Electric supply
Hermetic SCROLL 2900 rpm
Starting mode
Direct in line in series
Quantity
1
2
Oil quality
Oil volume
l (cir1)
3.25
4.14
6.50
6.50
8.28
8.84
9.76
11.24
8.28
8.28
l (cir2)
-
-
-
-
-
-
-
-
6.50
8.28
N°
Refrigerant weight
1
2
R410A (1720)
kg (cir1)
3.3
3.8
6.8
7.1
9.9
11
13.7
16.1
7.3
9.9
kg (cir2)
-
-
-
-
-
-
-
-
9.5
9.9
ph/Hz/V
3~50Hz 400V (+6%/-10%) + Earth
Maxi rated current
A
23.2
30.2
42.2
46.2
60.2
66.2
76.0
91.8
106.2
120.2
Starting current
Starting current
Soft Start option
Breaking capacity
A
137.0
174.0
139.0
160.0
204.0
255.0
302.0
317.0
250
264.0
A
70
60
76
93.0
90
167.0
194.0
210.0
136.0
150.0
95
95
95
95
95
kA
50
Electrics box protection
Maxi wires section
IP22
mm2
50
50
50
50
50
Control voltage
ph/Hz/V
1~50Hz 230V (+6%/-10%) transformer mounted
Capacity control
%
100-0
100-0
100-50-0
100-50-0
100-50-0
l
2.7
3.6
4.8
5.3
9.9
100
100
57-43-0
63-37-0
Brazed plate heat exchanger type
Type
Evaporator
4
POE 3MAF (32 cst).
Refrigerant type (GWP)
Type
Water content
Outlet water mini Maxi
°C
Minimum water flow
m3/h
3.5
Maximum water flow
m /h
11.2
3
Water connections
Ø
Design pressure
bar
Water content
Outlet water mini Maxi
11.3
100-50-0
100-72-50- 100-75-5022-0
25-0
12.8
15.7
15.2
19.8
10.9
12.4
15.2
16.4
19.1
34.0
38.4
47.5
51.1
58.4
-10°C / +18°C
4.8
6.2
14.6
19.8
G 1’’1/4
7.0
9.5
22.2
29.2
G 1’’1/2
G 2’’
G 2’’1/2
DN80 PN16
10 bars WATER side
Type
Condenser
dynaciat lg
and electrical characteristics
Brazed plate heat exchanger type
l
3.0
4.1
5.1
5.8
°C
8.0
9.4
11.1
15.2
13.8
16.0
+30°C / +55°C
Minimum water flow
m3/h
3.1
4.1
5.4
6.1
8.2
9.4
10.7
13.1
14.3
16.3
Maximum water flow
m3/h
8.5
11.1
15.1
17.0
22.3
26.0
29.4
35.0
39.1
44.6
Water connections
Ø
Design pressure
bar
10 bars WATER side
Storage mini Maxi
°C
-20°C / +50°C
G 2’’
G 2’’1/2
DN80 PN16
226
299
197
222
292
286
279
454
217
274
mm
1201
1201
1201
1201
1201
1201
1201
1201
1201
1201
Length
mm
798
798
1492
1492
1492
1492
1492
1492
2380
2380
Width
mm
883
883
883
883
883
883
883
883
883
883
Weight empty
kg
230
300
385
390
590
620
665
735
930
1125
Weight in operation
kg
240
Capacities based on: -EN14511 EUROVENT conditions
(1) / COOLING mode : +12°C/+7°C and +30°C/+35°C
(2)/ HEATING mode : +40°C/+45°C and +12°C/+7°C
312
400
406
617
650
703
780
(3) EER or COP as net values
(3) LW: Overall sound power level as per ISO3744
990
1190
Weight Dimensions
l
Operating height
2
Mini water pipe content
G 1’’1/2
heat pumps - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - nA 12.538 B
Technical
and electrical characteristics
Efficiency
DynaCiat® ILG
Compressor
Refrigerant
circuit
Electric supply
240V
300V
28,90
37,60
50,30
58,80
76,60
Net power input (1)
kW
8,50
10,90
14,70
16,40
20,90
3,39
3,45
3,41
3,59
3,65
net EER (3)
net EER ESEER (3)
3,53
3,61
4,31
4,38
4,34
Net heating capacity (2)
kW
38,1
49,9
66,6
76,8
100
Net power input (2)
kW
9,6
12,4
16,9
18,8
24,1
3,96
4,02
3,95
4,08
4,15
67
70
69
70
73
dB(A)
Type
Hermetic SCROLL 2900 rpm
Starting mode
Direct in line in series
Quantity
1
2
Oil quality
Oil volume
POE 3MAF (32 cst).
l (cir1)
3.25
4.14
6.50
N°
6.50
8.28
8.1
9.2
1
Refrigerant type (GWP)
R410A (1720)
Refrigerant weight
kg (cir1)
Type
ph/Hz/V
3.25
3.6
5.5
3~50Hz 400V (+6%/-10%) + Earth
Maxi rated current
A
23.2
30.2
42.2
46.2
60.2
Starting current
A
137.0
174.0
139.0
160.0
204.0
Starting current
Soft Start option
A
70.0
60.0
76.0
93.0
90.0
Breaking capacity
kA
50
50
50
50
Electrics box protection
Maxi wires section
Internal circuit
200V
kW
Sound power level (4)
External circuit
150V
Net cooling capacity (1)
COP (3)
Weight Dimensions
120V
IP22
mm2
Control voltage
ph/Hz/V
Capacity control
%
50
50
1~50Hz 230V (+6%/-10%) transformer mounted
100-0
Type
Water content
100-0
100-50-0
100-50-0
100-50-0
Brazed plate heat exchanger type
l
2.7
3.6
4.8
5.3
9.9
Minimum water flow
m3/h
5
6.5
9
10
13.5
Maximum water flow
m3/h
14
18
25
28
36
Water connections
Ø
Design pressure
bar
G 1’’1/2
Type
Water content
G 2’’
10 bars WATER side
Brazed plate heat exchanger type
l
2.7
3.6
4.8
5.8
9.9
Minimum water flow
3
m /h
5
6.5
9
10
13.5
Maximum water flow
m /h
14
18
25
28
3
Water connections
Ø
Design pressure
bar
Storage temperature
°C
Mini water pipe content
G 1’’1/2
36
G 2’’
10 bars WATER side
-20°C / +50°C
l
226
299
197
222
292
Operating height ¯
Length
Width
mm
mm
mm
1201
798
883
1201
798
883
1201
1492
883
1201
1492
883
1201
1492
883
Weight empty
kg
226
289
379
452
595
Weight in operation
kg
237
301
394
468
622
Capacities based on: -EN14511 EUROVENT conditions
(1) / COOLING mode : +12°C/+7°C and +30°C/+35°C
(2) / HEATING mode : +40°C/+45°C and +12°C/+7°C
(3) EER or COP as net values
(3) LW: Overall sound power level as per ISO3744
heat pumps - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - nA 12.538 B
3
dynaciat lg
Water-cooled chillers
Water-cooled chillers
dynaciat lg
Technical
and electrical characteristics
Efficiency
DynaCiat® LGN
120Z 150Z 200Z 240Z 300Z 350Z 400Z 500Z 540Z 600Z 753Z 900Z 1000Z 1100Z 1200Z
Net cooling capacity (1)
kW
27,65
40,30
54,25
66,89
80,62
94,86 109,86 133,22 149,81 161,20 203,20 244,11 266,94 294,73 325,83
Net power input
kW
7,54
11,40
15,15
19,11
22,67
26,94
30,93
37,58
41,39
45,20
55,80
67,89
74,06
82,95
91,34
Net discharge output (1)
kW
35,0
52,0
70,0
86,0
103,0
122,0
140,0
171,0
191,0
207,0
259,0
312,0
341,0
377,7
417,2
3,66
3,53
3,58
3,50
3,55
3,52
3,55
3,55
3,62
3,57
3,64
3,60
3,60
3,55
3,57
67
70
69
70
73
74
75
76
75
76
78
79
79
81
82
Efficiency EER (2)
Sound power level (3)
dB(A)
Compressor
Type
Starting mode
Refrigerant
circuit
Direct in line in series
Quantity
1
2
Oil quality
Oil volume
l (cir1)
3.8
6.2
7.6
10.0
l (cir2)
-
-
-
-
12.4
14.2
16.0
16.0
12.4
12.4
16.0
16.0
16.0
16.4
16.8
-
-
-
-
10.0
12.4
8.0
16.0
16.0
16.4
16.8
2
R407C (1520)
Refrigerant load
Refrigerant not supplied (nitrogen charge)
ph/Hz/V
3~50Hz 400V (+6%/-10%) + Earth
Maxi rated current
A
19.5
30.0
39.0
49.0
59.0
68.0
77.0
95.0
108.0
118.0
142.6
172.4
190.0
208.0
224.0
Starting current
Starting current
Soft Start option
Breaking capacity
A
120.0
175.0
140.0
195.0
205.0
245.0
254.0
318.0
254.0
264.0
366.0
395.0
413.0
473.0
489.0
A
72.0
104.0
84.0
118.0
124.0
148.0
161.0
208.0
160.0
166.0
254.0
284.0
300.0
339.0
357.0
kA
50
50
50
50
50
50
50
50
50
50
100
100
100
100
100
mm2
50
50
50
50
50
95
95
95
95
95
185
185
185
185
185
IP22
Control voltage
ph/Hz/V
1~50Hz 230V (+6%/-10%) - transformer mounted
Capacity control
%
100-0
100-0
10050-0
10040-0
l
2.3
2.3
4.5
5.7
100- 100- 100- 100- 100-72- 100-75- 100-66- 100-72- 100-75- 100-78- 100-7550-0 57-43-0 50-0 50-0 45-18-0 50-25-0 33-0 50-22-0 50-25-0 50-22-0 50-25-0
Brazed plate heat exchanger type
Water content
Outlet water mini Maxi
5.7
°C
6.8
Minimum water flow
m3/h
3.5
4.8
6.2
7.0
9.5
Maximum water flow
m /h
11.2
14.6
19.8
22.2
29.2
3
Water connections
Ø
Design pressure maxi
bar
Balance circuit 1 / circuit 2
Gas discharge
Liquid return
G 1’’1/4
G 1’’1/2
7.9
11.3
11.3
15.8
15.8
15.8
10.9
12.4
15.2
16.4
19.1
23.1
27.5
30.1
34.0
38.4
47.5
51.1
58.4
45.0
54.6
60.0
G 2’’
18.0
20.3
35.0
39.0
68.0
77.0
-8°C / +12°C
G 2’’1/2
DN80 PN16
DN100 PN16
DN125 PN16
10 bars WATER side
Without condenser
%
100
Ø (cir1) 1’’1/8
54/46
50/50
67/33
56/44
50/50
50/50
50/50
1’’1/8
1’’3/8
1’’3/8
1’’5/8
1’’5/8
2’’1/8
2’’1/8
1’’3/8
1’’5/8
2’’1/8
2’’1/8
2’’1/8
2’’1/8
2’’1/8
Ø (cir2)
-
-
-
-
-
-
-
-
1’’5/8
1’’5/8
1’’3/8
2’’1/8
2’’1/8
2’’1/8
2’’1/8
Ø (cir1)
7/8”
7/8”
7/8”
1’’1/8
1’’1/8
1’’1/8
1’’3/8
1’’3/8
1’’1/8
1’’1/8
1’’3/8
1’’3/8
1’’3/8
1’’5/8
1’’5/8
Ø (cir2)
-
-
-
-
-
-
-
-
1’’1/8
1’’1/8
1’’1/8
1’’3/8
1’’3/8
1’’5/8
1’’5/8
Design pressure maxi
bar
Storage temperature
°C
Mini water pipe content
6.8
-10°C / +12°C
High pressure circuit
Condenser
4
1
Type
Weight Dimensions
3
POE ISO32-160SZ
Refrigerant type (GWP)
Maxi wires section
Electrics box protection
Evaporator
4
POE ISO32-160SZ
Refrig. circuit no.
Type
Electric supply
Hermetic SCROLL 2900 rpm
29.5 bar HP
-20°C / +50°C
l
158
233
153
148
227
227
309
376
144
221
370
293
368
353
442
Operating height
mm
1201
1201
1201
1201
1201
1201
1201
1202
1201
1201
1681
1681
1681
1681
1681
Length
mm
788
788
1482
1482
1482
1482
1482
1482
2370
2370
2200
2200
2200
2200
2200
Width
mm
873
873
873
873
873
873
873
873
873
873
880
880
880
880
880
Weight empty
kg
223
284
375
436
518
548
586
591
835
954
975
1135
1135
1161
1229
Weight in operation
kg
232
296
390
452
543
577
621
636
883
1008
1017
1177
1177
1203
1273
(1) Capacities based on : COOLING mode: +12°C/+7°C and condensing
+45°C
(2) EER as net values
4
(3) LW: Overall sound power level as per ISO3744
heat pumps - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - nA 12.538 B
Main
components
n Framework
- casing with removable sheets in galvanised steel,
- enamelled paint colors RAL 7024 and RAL 7035
n Hermetic SCROLL compressors
- Integral motor cooled by suction gas
- Motor protection by a winding internal thermostat
- Mounting on antivibration mounts
n Evaporator
-
Brazed plate heat exchanger(s)
End plates and internal plates in AISI 316 stainless steel
High efficiency optimised plates profile
Thermal insulation
n Condenser
LG - LGP - ILG Series
- Brazed plate heat exchanger(s)
- End plates and internal plates in AISI 316 stainless steel
- High efficiency optimised plate profile
- Thermal insulation
LGN Series
- Chiller without condenser
- Possibility of connection on a removed air-cooled condenser
OPERA or AIRIAL series
- Refrigeration sleeves for LGN (without condenser).
n Control and safety devices
-
Thermostatic expansion valve
High and low refrigerant pressure switch
Safety relief valves on refrigerant circuit
Temperature sensors and pressure transducers
Chilled water flow switch
Unit starting sequence
n Electrics box
Entirely assembled, the electrics box, containing all the
electric components and control process unit (CPU), allows
control over all the machine’s functions, operation monitoring,
adjustment of the water temperature settings, or interface with
an external managing system.
The electrics box includes:
- Power circuit and remote control circuit
- Wiring numbering
- Main safety switch breaker on front panel with handle
- Control circuit transformer
- Circuit breaker protections on power and control circuits
- Compressor(s) motor(s) contactor(s)
- General earth connection
- Microprocessor electronic system
Micro Connect ILG
Connect 2 for LG - LGP - LGN
- Free contacts for field wiring signals report.
Connect 2 electronic control system
A CIAT microprocessor electronic control system, with CPU,
with centralisation of controls and monitoring of internal operating.
Including:
- Selector for Run, Stop, Reset or Remote,
- Running mode selector, COOLING or HEATING,
- Output. RS485 output for BMS control (ModBus-JBus),
. Output adapter for additional potential-free contact board,
. Output adapter for remote control (optional).
- LCD screen for output or internal operation and LED sight glasses
Functions:
- Monitoring of operating information by :
. direct display of clear text messages in different languages
. direct display of temperatures and pressures
- Complete control of compressors with starting sequence,
counting and equalisation of compressors’ running times
- Master Slave Management allows two machines to be
controlled on a single water loop, by alternating the Master and
Slave according to the running time.
- Anti-short cycle protection
- Auto-adaptative functions with adjustment of the control
system on the running parameters deviation
- Capacity stage control system on each compressor (multi
compressors) in accordance with the cooling or heating
requirements controlled by the water temperatures
- Control of the internal operating parameters
- Second setting point control
- Direct display of water temperatures
- Diagnosis of operating status and faults :
HP/LP, water flow, compressor(s) motor(s), anti-frost
- Remote management and remote control
Microconnect
electronic control
module
n Composition
- a control terminal with display for viewing and
selecting the different modes (on/off, heating/
cooling mode, clock, weekly programming)
- an electronic control board
- an outdoor temperature sensor
n Functions
- controls the water or air temperature in each mode
- continuously monitors the operating settings
- diagnoses and displays faults
- adjusts the setpoint based on the outdoor temperature (in cooling
mode and in heating mode)
- manages auxiliaries
- manages and automatically equalises the compressor running
time (multi-compressors)
- dialogue with the remote control terminal
Optional equipment (kit to be mounted on-site)
n Optional equipment (delivered separately)
- Remote control box, (Except ILG)
- Additional potential-free contact board, (Except ILG)
- Evaporator and condenser flexible connectors,
- 800 microns water filter, evaporator and condenser,
- For city water use (LG 120 - 500), condenser 2-way control valve,
- For starting with low water temperature (LG 120 - 500) condenser
3-way control valve,
- Phase rotation detecter (rotation, phase failure, over voltage,
under voltage),
- Soft starter
heat pumps - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - nA 12.538 B
5
dynaciat lg
Water-cooled chillers
Water-cooled chillers
dynaciat lg
Operating
range
LGN 120Z - 1200Z
Condensation temperature °C
Condenser water outlet °C
LG-LGP 120V - 600V
Necessary Glycol
7
Necessary Glycol
-4
-3
Chilled water outlet °C
Evaporator
Chilled water outlet °C
limits
The curves represent the minimum and maximun allowable
temperature difference of chilled water (or glycol) in accordance
with the outlet temperature.
Water glycol
Example:
For a water outlet: + 5 °C
mini difference: 2,6 °C
Water temp.: 7,6 / 5 °C
Max. difference: 6 °C
Water temp.: 11 / 5 °C
For temperature differences not included between the 2 curves,
consult us.
Water
glycol coefficients
CORRECTION
n 30 % concentration of glycol weight
Cooling capacity
Evaporator
n Freezing point of the solution: -17,5 °C.
Reading valves in the brochure
Pf: Refrigeration power according to selection tables
Pa: Compressor absorbed power according to selection tables
0,98
Pfc = Pf x 0.98
1.00
see selection table
1,05
Pcf x 0.86
Qc =
1.10
Qc =
DPc: Corrected water pressure drop, evaporator or condenser.
Evaporator + condenser
Qc: Corrected chilled or hot water flow rate
1.05 DT
1,15
DPc = DP x 1.15
12 / 7 °C
Cooling capacity
0,97
Pfc = Pf x 0.97
Chilled water
flow
1,05
Pressure drop
1,10
Cooling capacity
Corrected values according to calculations above:
Pfc: Corrected cooling capacity
Pcf x 0.86
x
Pressure drop
Average temp.
Average temp.
DP: Water pressure drop according to curves for the
corresponding corrected flow rate value (Qc).
6
Condenser
K: Correction cœfficients
Chilled water
flow
POSITIVE TEMPERATURE NEGATIVE TEMPERATURE
K
Calculation
K
Calculation
Qc =
x 1.10
DT
1.30
DPc = DP x 1.30
see operating limits
(Pcf+Pa) x 0.86
x 1.05
DT
DPc = DP x 1.10
35 / 40 °C
0,95
Pfc = Pf x 0.95
0.97
Pfc = Pf x 0.97
Pcf x 0.86
Pcf x 0.86
Chilled water
flow
1,05
Pressure drop
1,15
DPc = DP x 1.15
1.30
Hot water flow
1,05
(Pcf+Pa) x 0.86
Qc =
x 1.05
1.05
Condenser
pressure drop
1,10
DPc = DP x 1.10
Qc =
x 1.05
DT
DT
1.10
1.10
Qc =
x 1.10
DT
DPc = DP x 1.30
Qc =
(Pcf+Pa) x 0.86
x 1.05
DT
DPc = DP x 1.10
heat pumps - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - nA 12.538 B
Minimum
water pipes volume
The Connect controller is equipped with an anticipation logic allowing high flexibility in adjusting the set points according to the
parameters drifting, in particular for low water volume hydraulic installations.
An adapted management of the compressors operating periods avoids therefore the start of anti-short cycle functions, and in
most cases, the requirement of a buffer tank.
The calculation of the minimum water volume is given for EUROVENT rated conditions, in cooling mode only.
This value is applicable for most air conditioning applications (assembly with fan coil units)
Note: for installations running with a low volume of water (assembly with air handling unit) or for industrial processes, the buffer
tank is a required component.
For heat pump applications, we recommend the use of a buffer tank to ensure a stable temperature is maintained during the defrosting cycles.
NOTES:
Industrial processes which require a high stability of water temperatures or installations with high thermal load variation can
privilege the installation of a water buffer tank.
Models LG - LGP - ILG
120V
150V
200V
240V
300V
350V
400V
500V
540V
600V
753Z
900Z
Minimum installation volume (liters)
226
299
197
222
292
286
279
454
217
274
457
364
Noise
1000Z 1100Z 1200Z
457
451
565
levels
The DYNACIAT LG - LGP - LGN - ILG range is a must by its design integrating the «noiseless» assembly process for attenuation
of vibrations and sound power sources :
n Scroll compressor(s) mounted on antivibration mounts
n Anti-vibratil assembly of several compressors on structure isolated from the frame (120 to 600)
n Piping dissociated from the unit structure
n Double skin paneling with mineral wool insulation 25 mm (753 to 1200)
n Antivibration mounts to be positioned between the ground and the unit as standard (753 to 1200)
n
Sound power levels ref 2x10-12 Pa ±3 dB (Lw)
Sizes
120
150
200
240
300
350
400
500
540
600
753
900
1000
1100
1200
n
63 Hz
77
78
78
78
81
82
83
84
83
84
89
89
89
90
90
125 Hz
65
74
60
68
77
75
76
74
78
80
68
69
69
71
73
POWER LEVEL SPECTRUM (dB)
250 Hz
500 Hz
1000 Hz
65
59
59
72
67
60
60
62
62
68
62
62
75
70
63
75
68
64
76
69
67
77
67
69
76
70
66
78
73
66
70
75
73
71
76
74
71
76
74
72
76
74
72
77
75
2000 Hz
61
64
64
64
67
69
70
72
69
70
69
70
70
74
76
4000 Hz
59
57
62
62
60
63
64
66
64
63
69
70
70
74
76
Sound pressure levels ref 2x10-5 Pa ±3 dB (Lp)
Measuring point:
Sizes
120
150
200
240
300
350
400
500
540
600
753
900
1000
1100
1200
n
in free field
63 Hz
46
47
47
47
50
51
52
53
51
52
57
57
57
58
58
n
125 Hz
34
43
28
37
46
43
44
43
46
48
36
37
37
39
41
10 meters from the unit, 1.50 meters from the ground
PRESSURE LEVEL SPECTRUM (dB)
250 Hz
500 Hz
1000 Hz
34
28
28
41
35
29
29
31
31
37
31
31
44
38
32
43
37
33
45
37
36
45
36
38
44
39
34
47
41
35
38
43
41
39
44
42
39
44
42
40
44
42
40
45
43
2000 Hz
29
33
33
32
36
38
39
40
37
39
37
38
38
42
44
n
Global level Lw
dB(A)
67
70
69
70
73
74
75
76
75
76
78
79
79
81
82
directivity 2
4000 Hz
28
25
30
31
28
31
32
34
33
31
37
38
38
42
44
Global level Lp
dB(A))
35
39
38
38
42
42
44
45
43
45
46
47
47
49
50
NOTES: Acoustic pressure levels depend on installation conditions, and consequently are only indicative. Reminder: only the
sound power levels are comparable and certified.
heat pumps - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - nA 12.538 B
7
dynaciat lg
Water-cooled chillers
Water-cooled chillers
EN
and heating capacities
R410A
200V
240V
300V
350V
400V
Pf
kW
19.0
24.0
30.1
34.2
36.4
42.8
46.1
50.2
25.5
31.6
39.3
44.6
47.5
55.9
60.5
65.9
33.5
42.5
53.2
60.5
64.4
76.0
81.8
89.0
37.8
47.9
59.7
67.7
72.2
84.9
91.9
99.7
50.1
62.8
78.1
89.1
95.1
112.
121.5
132.3
57.0
71.9
90.0
103.0
110.2
130.3
142.5
156.1
64.2
81.4
101.9
116.6
124.3
147.4
162.9
177.7
30
Pa
kW
6.7
6.7
6.7
6.8
6.8
6.9
6.9
7.0
8.4
8.5
8.6
8.7
8.7
9.0
9.0
9.3
11.4
11.4
11.5
11.6
11.7
11.8
11.9
12.1
13.4
13.4
13.5
13.6
13.7
13.9
14.0
14.2
16.8
16.9
17.1
17.3
17.4
17.9
18.1
18.6
19.3
19.5
19.8
20.1
20.3
20.8
21.0
21.6
22.0
22.3
22.6
22.9
23.1
23.7
23.6
24.1
Pc
kW
25.4
30.5
36.6
40.8
43.0
49.5
52.8
57.1
33.6
39.8
47.6
53.1
56.0
64.7
69.3
75.0
44.5
53.5
64.3
71.7
75.7
87.5
93.4
100.9
50.6
60.9
72.9
80.9
85.6
98.5
105.5
113.6
66.2
79.1
94.7
105.9
112.0
129.5
139.2
150.5
75.5
90.7
109.3
122.6
129.9
150.7
163.1
177.2
85.3
102.8
123.9
138.9
146.8
170.5
186.0
201.4
Pf
kW
17.9
22.6
28.6
32.6
34.7
41.0
44.3
48.2
24.2
30.2
37.7
42.9
45.6
53.8
58.3
63.6
31.4
40.1
50.5
57.7
61.5
73.0
78.5
85.5
35.6
45.3
56.8
64.6
69.0
81.4
87.7
96.0
47.6
59.9
74.9
85.5
91.3
107.
116.9
127.6
53.7
68.1
85.7
98.4
105.1
124.6
135.9
149.0
60.9
77.6
97.5
111.6
119.3
141.3
156.1
171.1
35
Pa
kW
7.5
7.5
7.5
7.5
7.5
7.6
7.6
7.7
9.3
9.5
9.5
9.6
9.6
9.8
9.8
10.0
12.9
12.9
12.9
13.0
13.0
13.1
13.1
13.3
15.0
15.0
15.0
15.1
15.2
15.3
15.2
15.5
18.7
18.9
19.0
19.2
19.2
19.6
19.5
20.0
21.4
21.6
21.9
22.2
22.3
22.7
22.8
23.3
24.5
24.7
25.0
25.3
25.4
25.9
25.7
26.1
Pc
kW
25
29.9
35.8
39.9
42.0
48.4
51.7
55.7
33.1
39.3
46.9
52.1
55.0
63.3
67.8
73.4
43.7
52.5
62.9
70.2
74.1
85.7
91.3
98.6
49.8
59.7
71.3
79.2
83.7
96.4
102.5
111.1
65.4
78.0
93.3
104.0
109.9
126.7
136.0
147.2
74.1
88.9
106.6
119.9
126.8
146.8
158.2
171.7
84.3
101.3
121.7
136.1
144.0
166.5
181.2
196.7
Pf
kW
16.5
21.1
27.0
30.8
33.0
39.0
42.3
46.0
22.8
28.6
35.9
40.8
43.5
51.4
55.8
60.6
29.1
37.5
47.6
54.5
58.2
69.5
75.0
81.6
32.8
42.3
53.6
61.1
65.3
77.3
84.3
91.8
44.7
56.8
71.2
81.4
86.9
102.9
111.9
122.2
50.5
64.3
81.5
93.3
99.9
118.8
129.9
141.8
57.2
73.5
92.7
106.2
113.7
135.1
150.2
162.0
Cc: gross cooling capacity
Pi: Compressors gross power input
Cde: Gross heating capacity
8
IEN
D
T
CT
IO N
CONDENSER WATER OUTLET TEMPERATURE °C
Evaporator water
outlet temperature
°C
-10
Glycol water -4
2
5
7
Pure water 12
15
18
-10
Glycol water -4
2
5
7
Pure water 12
15
18
-10
Glycol water -4
2
5
7
Pure water 12
15
18
-10
Glycol water -4
2
5
7
Pure water 12
15
18
-10
Glycol water -4
2
5
7
Pure water 12
15
18
-10
Glycol water -4
2
5
7
Pure water 12
15
18
-10
Glycol water -4
2
5
7
Pure water 12
15
18
N TA L LY F R
EN
TE
O
150V
NME
PR
120V
RO
HFC R410A
DYNACIAT LG - LGP
LG
LGP
VI
LY
Cooling
dynaciat lg
40
Pa
kW
8.4
8.4
8.3
8.4
8.4
8.4
8.3
8.4
10.4
10.5
10.6
10.7
10.7
10.8
10.7
10.8
14.6
14.6
14.5
14.6
14.6
14.5
14.5
14.7
16.8
16.8
16.8
16.8
16.8
17.0
16.7
16.9
20.7
21.0
21.2
21.3
21.4
21.6
21.4
21.7
23.8
24.0
24.3
24.5
24.6
25.0
24.9
25.3
27.3
27.6
27.8
28.0
28.1
28.5
28.1
28.6
Pc
kW
24.5
29.1
35
38.8
41.1
47.1
50.4
54.2
32.7
38.7
46.1
51.1
53.8
61.9
66.2
71.2
42.9
51.4
61.6
68.6
72.3
83.6
89.2
96.0
48.8
58.3
69.7
77.4
81.6
93.8
100.6
108.2
64.4
76.9
91.7
102.0
107.6
123.9
132.7
143.3
73.1
87.3
104.9
117.0
123.7
143.1
154.2
166.5
83.0
99.8
119.5
133.3
141.0
162.7
177.6
189.9
Pf
kW
15.2
19.4
25.2
28.9
30.9
36.7
40.0
43.7
21.3
26.9
33.8
38.6
41.2
48.7
52.9
57.8
26.6
34.6
44.4
51.0
54.6
65.4
70.8
77.8
30.1
39.2
50.0
57.3
61.3
73.0
79.5
86.7
41.8
53.3
67.2
76.9
82.3
97.8
106.6
116.4
47.0
60.4
76.5
88.0
94.2
112.3
122.7
134.7
52.9
68.6
87.5
100.3
107.6
128.0
141.5
154.8
45
Pa
kW
9.4
9.4
9.3
9.3
9.3
9.4
9.2
9.2
11.5
11.7
11.8
11.9
11.9
12.0
11.8
11.9
16.5
16.5
16.4
16.4
16.4
16.3
16.1
16.2
18.9
18.9
18.8
18.8
18.8
18.8
18.5
18.7
22.9
23.4
23.7
23.8
23.9
24.0
23.6
23.8
26.4
26.8
27.1
27.3
27.4
27.7
27.4
27.8
30.2
30.7
31.0
31.2
31.3
31.5
30.8
31.2
Pc
kW
24.1
28.3
34.1
37.9
39.9
45.8
49.0
52.6
32.1
38.1
45.2
50.0
52.7
60.4
64.4
69.4
42.1
50.2
60.1
66.8
70.4
81.2
86.4
93.5
47.8
57.1
68.0
75.3
79.4
91.2
97.5
104.8
63.4
75.6
90.0
99.8
105.3
121.0
129.5
139.5
71.9
85.9
102.5
114.3
120.6
139.1
149.4
161.8
81.5
97.8
117.2
130.4
137.7
158.5
171.5
185.1
Pf
kW
50
D E L'E N VI RO
NN
EM
55
Pa
kW
Pc
kW
Pf
kW
Pa
kW
Pc
kW
17.8
23.2
26.8
28.6
34.3
37.4
40.9
10.6
10.5
10.5
10.5
10.4
10.2
10.3
27.8
33.2
36.8
38.7
44.4
47.3
50.9
21.1
24.5
26.3
31.6
34.6
37.9
11.8
11.7
11.7
11.7
11.5
11.4
32.3
35.7
37.5
42.8
45.6
48.9
24.8
31.5
36.0
38.6
45.8
49.6
54.4
13.1
13.2
13.3
13.3
13.4
13.2
13.2
37.2
44.2
48.8
51.4
58.7
62.4
67.2
29.0
33.3
35.7
42.6
46.3
50.9
14.8
14.8
14.9
15.0
14.7
14.6
43.0
47.5
49.9
56.9
60.5
65.1
31.5
41.0
47.2
50.6
61.1
66.4
72.5
18.7
18.5
18.5
18.5
18.3
18.0
18.2
49.2
58.6
64.9
68.4
78.7
83.7
90.1
37.2
43.1
46.4
56.4
60.9
67.0
21
20.9
20.9
20.5
20.4
20.3
57.1
63.0
66.3
76.2
80.5
86.6
35.7
46.1
53.1
56.9
68.1
74.4
81.3
21.2 55.8
21.1 66.2
21.0 73.2
21.0 77.1
21.0 88.3
20.5 94.2
20.6 101.3
41.9
48.6
52.2
62.8
68.3
75.3
23.7
23.6
23.5
23.5
23.0
23.0
64.4
71.0
74.6
85.4
90.4
97.5
49.3
62.7
72.0
77.1
91.7
100.4
109.1
26.0
26.5
26.6
26.6
26.8
26.2
26.4
74.0
88.0
97.5
102.7
117.6
125.7
134.7
57.6
66.6
71.4
85.3
92.6
102.5
29.5 85.7
29.7 94.9
29.8 99.8
29.9 114.1
29.5 121.0
29.3 130.8
56.0
71.4
82.3
88.2
105.3
115.4
126.3
29.9
30.3
30.4
30.5
30.8
30.4
30.8
84.3
100.3
111.5
117.5
135.1
144.8
156.1
65.6
76.1
81.7
98.1
107.2
116.8
33.9
34.1
34.2
34.5
34.2
34.3
97.8
108.6
114.4
131.3
140.1
150.0
63.3
81.4
93.8
100.6
120.2
132.4
145.5
34.2
34.6
34.8
34.8
35.1
34.2
34.4
95.7
114.4
127.1
134.0
154.1
165.5
178.9
74.8
86.6
93.0
111.4
122.2
134.2
38.5
38.8
38.9
39.1
38.3
38.3
111.4
123.6
130.1
149.0
159.1
171.2
Standard condition
Zone where use of water / glycol is compulsory
Calculation fouling 0.00005 m2 °C/W
heat pumps - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - nA 12.538 B
IO N
D E L'E N VI RO
NN
NME
CT
IO N
CONDENSER WATER OUTLET TEMPERATURE °C
Evaporator water
outlet temperature Pf
°C
kW
-10 78.8
Glycol water -4 99.6
35
40
45
50
Pa
Pc
Pf
kW
kW
kW
27.3 105.0 74.4
27.6 126.2 94.8
Pa
Pc
Pf
kW
kW
kW
30.3 103.4 69.9
30.7 124.3 89.6
Pa
Pc
Pf
kW
kW
kW
33.7 101.9 64.5
34.1 122.3 83.7
Pa
Pc
Pf
kW
kW
kW
37.5 99.9
38.0 119.9 77.0
Pa
kW
2
5
7
Pure water 12
15
18
-10
Glycol water -4
2
5
7
Pure water 12
15
18
125.2
143.6
153.3
182.1
203.3
222.8
87.5
110.4
28.1
28.5
28.7
29.4
29.2
29.7
30.2
30.4
152.4
171.3
181.3
210.8
231.9
252.0
116.5
139.6
119.8
137.2
147.0
174.5
195.2
212.7
82.6
104.9
31.1
31.4
31.6
32.3
31.9
32.3
33.7
33.8
149.8
167.6
177.7
205.9
226.3
244.4
114.7
137.4
113.8
130.9
139.9
166.5
186.8
203.4
77.3
98.7
34.5
34.8
35.0
35.5
35.0
35.3
37.5
37.8
147.0
164.5
173.7
201.0
220.9
237.9
112.9
134.9
107.3
123.5
132.2
157.5
175.5
192.2
71.7
92.2
38.4
38.6
38.7
39.2
38.3
38.7
41.8
42.3
144.1
160.7
169.6
195.4
212.7
229.9
111.1
132.4
99.9
115.4
123.8
148.1
164.1
179.9
84.8
47.2 129.5
137.4
156.2
166.6
196.0
212.4
230.5
30.6
30.9
31.1
31.9
32.1
32.9
167.1
186.3
196.8
227.1
243.8
262.7
131.2
149.5
159.6
188.1
203.5
223.4
34.0
34.3
34.4
35.0
34.8
35.6
164.1
182.7
192.9
222.2
237.5
258.2
124.3
142.1
151.6
179.4
194.9
212.6
38.0
38.1
38.2
38.6
38.2
38.7
160.9
179.0
188.6
216.8
232.0
249.9
116.8
133.7
143.0
170.2
184.2
201.6
42.5
42.6
42.6
42.8
42.2
42.5
157.5
174.7
184.1
211.6
225.1
242.9
108.5
124.5
133.4
159.1
173.5
189.5
47.5
47.6
47.7
47.7
46.8
47.2
-10
Glycol water -4
2
5
7
Pure water 12
15
18
100.1 33.6 132.3 95.1 37.3 130.7 89.5 41.4 128.8 83.5 45.8 126.8
125.6 33.9 158.3 119.8 37.7 156.1 113.5 42.1 153.7 106.4 46.8 151.0 98.7
52.0 148.0
156.3
177.9
190.1
223.9
242.8
264.6
52.9
53.2
53.3
53.5
52.7
53.0
189.4
211.6
224.0
258.9
278.4
301.1
149.8
170.9
182.4
215.4
234.0
254.0
38.0
38.3
38.4
39.2
39.2
40.1
Cc: gross cooling capacity
Pi: Compressors gross power input
Cde: Gross heating capacity
186.6
208.1
219.7
253.6
272.3
293.2
142.5
163.0
173.9
206.0
223.9
244.0
42.5
42.6
42.8
43.2
42.9
43.4
183.4
204.2
215.3
248.0
265.8
286.3
134.5
154.0
164.5
195.4
212.6
231.4
47.4
47.6
47.7
48.0
47.2
47.9
179.9
199.8
210.5
241.9
258.4
277.9
125.4
144.0
154.1
183.7
199.5
218.6
N TA L LY F R
IEN
Pc
kW
Pf
kW
D E L'E N VI RO
55
NN
EM
Pa
kW
Pc
kW
47.7
47.9
48.1
48.4
136.5
151.8
160.2
183.7
42.3 117.1
42.8
43.0
43.1
43.5
42.3
42.7
140.7
156.7
165.2
190.0
205.0
221.4
153.8
170.1
179.2
205.2
218.7
235.2
175.9
195.1
205.3
235.3
250.5
270.0
91.3
106.1
114.2
137.3
150.2 47.5 195.9
166.1 47.7 212.2
99.2
114.6
123.1
147.4
160.1
174.4
53.3
53.3
53.3
53.4
52.2
52.8
149.7
165.4
174.1
198.7
210.3
225.4
115.4
133.1
142.7
170.8
184.7
203.7
59.0
59.3
59.5
59.8
59.2
59.3
171.5
189.7
199.6
228.2
241.8
261.0
Standard condition
Zone where use of water / glycol is compulsory
Calculation fouling 0.00005 m2 °C/W
heat pumps - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - nA 12.538 B
D
T
TE
EM
30
34.2
34.6
34.8
35.8
36.3
37.2
RO
EN
EN
EN
T
EN
CT
VI
HFC R407C
O
R410A
D
PR
600V
TE
O
540V
IEN
PR
500V
N TA L LY F R
HFC R410A
DYNACIAT LG - LGP
LG
LGP
NME
LY
and heating capacities
RO
LY
Cooling
VI
9
dynaciat lg
Water-cooled chillers
Water-cooled chillers
- Cooling
mode
EN
capacities
VI
RO
NME
N TA L LY F R
IEN
D
LY
HFC R410A
O
TE
T
PR
DYNACIAT ILG
CT
EN
Cooling
dynaciat lg
IO N
D E L'E N VI RO
NN
EM
CONDENSER WATER OUTLET TEMPERATURE °C
ILG
120V
Pure water
Pure water
R410A
150V
30
Evaporator
water outlet
temperature °C
200V
240V
300V
Pure water
Pure water
Pure water
Cc: gross cooling capacity
Pi: Compressors gross power input
10
35
40
45
50
55
Pf
Pa
Pf
Pa
Pf
Pa
Pf
Pa
Pf
Pa
Pf
Pa
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
5
28.9
7.1
27.3
7.9
25.6
8.8
23.8
9.9
21.8
11.1
19.8
12.3
7
31.0
7.1
29.2
8.0
27.4
8.9
25.5
9.9
23.4
11.1
21.4
12.3
12
36.5
7.2
34.5
8.0
32.5
8.9
30.5
9.9
28.2
11.1
25.9
12.3
15
40.0
7.3
38.0
8.0
36.0
8.9
33.5
9.9
31.0
11.1
28.7
12.3
18
43.5
7.3
41.5
8.1
39.5
8.9
37.0
9.9
34.5
11.1
32.0
12.3
5
37.0
9.2
35.5
10.1
33.5
11.3
31.5
12.6
29.3
14.0
27.0
15.4
7
40.0
9.2
38.0
10.2
35.9
11.4
33.8
12.7
31.5
14.1
29.0
15.5
12
47.0
9.3
45.0
10.3
42.6
11.4
40.0
12.8
37.5
14.3
34.8
15.7
15
51.5
9.4
49.0
10.3
46.5
11.5
44.0
12.8
41.0
14.3
38.5
15.8
18
56.5
9.5
54.0
10.4
51.0
11.5
48.3
12.8
45.0
14.3
42.0
15.8
5
50.2
12.3
47.4
13.8
44.2
15.6
41.0
17.6
37.4
19.9
33.8
22.2
7
53.6
12.4
50.8
13.9
47.4
15.6
44.0
17.6
40.4
19.9
36.8
22.2
12
63.7
12.5
60.2
13.9
56.8
15.6
52.8
17.6
48.6
19.9
44.6
22.2
15
70.0
12.5
66.0
14.0
62.5
15.6
58.4
17.6
54.0
19.9
49.6
22.2
18
76.0
12.6
72.0
14.0
68.0
15.7
64.0
17.7
59.6
19.9
55.0
22.2
5
58.6
14.2
55.4
15.8
51.9
17.6
48.2
19.8
44.2
22.2
40.4
24.6
7
62.0
14.2
59.1
15.8
55.6
17.6
51.8
19.8
47.6
22.2
43.4
24.6
12
73.6
14.4
70.0
16.0
66.0
17.8
62.0
19.8
57.2
22.2
52.4
24.6
15
81.0
14.4
77.0
16.0
73.0
17.8
68.3
19.8
63.0
22.2
58.2
24.4
18
88.0
14.6
84.0
16.0
80.0
17.8
75.2
19.8
69.6
22.2
64.0
24.4
5
76.0
18.2
72.0
20.2
68.0
22.4
64.0
25.0
59.4
28.0
55.0
30.6
7
80.7
18.2
77.0
20.2
73.0
22.6
68.7
25.2
64.0
28.0
59.0
30.8
12
95.0
18.6
91.0
20.4
86.0
22.8
81.0
25.4
75.6
28.4
70.7
31.2
15
104.0
18.8
100.0
20.6
95.0
22.8
89.2
25.4
83.7
28.4
78.0
31.4
18
113.5
19.0
109.0
20.8
104.0
23.0
98.0
25.6
92.0
28.6
86.0
31.4
Standard condition
Zone where use of chilled water is compulsory.
Calculation fouling 0,00005 m2 °C/W
heat pumps - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - nA 12.538 B
mode
EN
- Heating
RO
NME
N TA L LY F R
IEN
D
LY
heating capacities
VI
HFC R410A
CT
EN
O
TE
T
PR
DYNACIAT ILG
IO N
D E L'E N VI RO
NN
EM
CONDENSER WATER OUTLET TEMPERATURE °C
ILG
Glycol water
120V
Pure water
Glycol water
150V
Pure water
R410A
30
Evaporator
water outlet
temperature °C
Glycol water
200V
Pure water
Glycol water
240V
Pure water
Glycol water
300V
Pure water
Cc: gross cooling capacity
Pi: Compressors gross power input
35
40
45
50
55
Pc
Pa
Pc
Pa
Pc
Pa
Pc
Pa
Pc
Pa
Pc
Pa
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
-8
-4
26.9
30.2
6.5
6.5
26.4
29.5
7.3
7.2
25.7
28.8
8.3
8.2
24.8
28.0
9.1
9.1
27.1
10.3
2
35.9
6.6
35.2
7.3
34.3
8.1
33.4
9.2
32.6
10.3
31.2
11.9
5
39.9
6.6
38.9
7.3
38.0
8.1
36.9
9.1
35.9
10.2
34.8
11.4
7
42.2
6.6
41.1
7.3
40.1
8.2
38.9
9.1
37.6
10.2
36.5
11.4
10
45.6
6.7
44.5
7.4
43.4
8.2
42.1
9.1
40.8
10.1
39.3
11.4
12
48.5
6.8
47.3
7.5
46.0
8.2
44.6
9.1
43.1
10.1
41.7
11.4
-8
-4
34.6
38.7
8.2
8.3
34.0
38.0
9.2
9.2
33.5
37.4
10.3
10.4
32.7
36.6
11.4
11.5
35.9
12.9
2
46.3
8.4
45.3
9.3
44.5
10.5
43.8
11.7
42.8
13.0
41.5
14.5
5
51.4
8.5
50.4
9.4
49.4
10.5
48.4
11.7
47.0
13.1
45.9
14.8
7
54.2
8.6
53.2
9.5
52.2
10.5
50.8
11.7
49.5
13.1
48.5
14.8
10
12
58.8
62.4
8.7
8.9
57.6
61.2
9.6
9.7
56.3
59.7
10.6
10.6
54.8
58.1
11.8
11.8
53.3
56.6
13.2
13.1
51.7
54.8
14.8
14.8
-8
-4
46.4
52.3
11.1
11.1
45.0
50.9
12.7
12.6
44.1
50.2
14.4
14.3
43.3
49.1
16.3
16.2
47.7
18.2
2
62.3
11.3
60.9
12.7
59.6
14.3
58.0
16.1
56.1
18.0
54.7
20.6
5
69.6
11.4
67.9
12.8
66.2
14.3
64.5
16.0
62.8
18.2
61.1
20.2
7
73.1
11.5
71.3
12.8
69.6
14.3
67.9
16.1
66.0
18.2
64.1
20.1
10
12
79.5
83.7
11.6
11.7
77.8
82.2
12.9
13.0
75.4
80.2
14.4
14.4
73.5
78.0
16.2
16.1
71.0
75.4
18.2
18.1
68.7
73.0
20.0
19.9
-8
-4
53.1
59.8
13.1
13.0
52.3
58.6
14.6
14.6
51.7
57.8
16.6
16.5
50.5
56.5
18.6
18.6
55.4
20.9
2
71.3
13.2
69.9
14.7
68.4
16.5
66.8
18.5
65.6
20.8
63.8
23.3
5
80.8
13.2
78.8
14.6
76.8
16.3
74.3
18.2
72.1
20.4
69.9
22.9
7
85.0
13.3
83.2
14.7
81.1
16.3
78.6
18.1
76.1
20.4
73.6
22.8
10
12
92.4
98.2
13.5
13.7
89.6
96.1
14.9
15.0
87.7
93.5
16.4
16.5
85.5
90.9
18.2
18.2
82.7
87.3
20.3
20.3
79.6
84.2
22.8
22.8
-8
-4
69.1
77.7
16.5
16.7
67.7
76.6
18.3
18.4
66.4
75.0
20.6
20.7
65.1
73.7
23.0
23.2
72.2
25.7
2
92.6
16.9
91.1
18.6
89.5
20.8
87.8
23.4
85.5
26.0
83.1
28.9
5
103.3
17.0
101.4
18.8
99.4
20.9
97.2
23.3
94.5
26.0
91.5
29.7
7
107.9
17.1
106.3
18.8
104.1
20.9
101.5
23.3
98.9
26.1
95.1
29.8
10
12
117.2
124.1
17.4
17.5
114.6
121.3
19.1
19.3
112.1
118.6
21.1
21.3
109.1
115.7
23.4
23.4
106.2
112.5
26.2
26.3
101.6
107.7
29.9
29.9
Standard condition
Zone where use of chilled water is compulsory.
Calculation fouling 0,00005 m2 °C/W
heat pumps - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - nA 12.538 B
11
dynaciat lg
Water-cooled chillers
Water-cooled chillers
dynaciat lg
Cooling and heating capacities rejected on remote condenser
VI
RO
NME
N TA L LY F R
IEN
D
LY
EN
DYNACIAT LGN
HFC R407C
O
CT
CONDENSING TEMPERATURE °C
LGN
Evaporator water
outlet temperature °C
Glycol water
120Z
Pure water
Glycol water
150Z
Pure water
Glycol water
R407C
200Z
Pure water
Glycol water
240Z
Pure water
Glycol water
300Z
Pure water
Glycol water
350Z
Pure water
Glycol water
400Z
Pure water
35
40
50
Pa
kW
Pc
kW
Pf
kW
Pa
kW
Pc
kW
Pf
kW
Pa
kW
Pc
kW
Pf
kW
Pa
kW
Pc
kW
-8
-4
15.2
18.2
5.9
5.9
20.8
23.9
14.3
17.2
6.6
6.6
20.6
23.6
13.3
16.1
7.4
7.4
20.3
23.2
12.3
14.9
8.3
8.3
20.1
22.8
2
5
7
12
24.3
28.7
30.8
38.2
5.9
5.9
5.9
5.9
30.0
34.5
36.6
44.0
23.1
27.3
29.4
36.5
6.6
6.6
6.6
6.6
29.4
33.7
35.8
42.9
21.7
25.7
27.8
34.5
7.4
7.4
7.4
7.4
28.8
32.9
34.9
41.7
20.2
24.0
26.0
32.3
8.3
8.3
8.3
8.3
28.2
32.0
34.0
40.4
-8
-4
22.6
27.1
8.7
8.8
31.0
35.5
21.4
25.7
9.7
9.8
30.7
35.1
20.1
24.2
10.8
10.9
30.4
34.6
18.7
22.6
12.1
12.2
30.2
34.2
2
5
7
12
35.4
41.6
44.8
54.7
8.9
8.9
8.9
9.0
44.0
50.3
53.5
63.5
33.7
39.7
42.9
52.4
9.9
9.9
9.9
10.0
43.3
49.3
52.5
62.1
31.9
37.6
40.6
49.7
11.0
11.1
11.1
11.1
42.5
48.3
51.3
60.5
30.0
35.4
38.4
47.1
12.3
12.4
12.4
12.4
41.8
47.3
50.3
59.1
-8
-4
30.0
35.7
11.8
11.8
41.3
47.0
28.0
33.7
13.2
13.2
40.6
46.4
26.0
31.6
14.8
14.8
40.1
45.7
24.0
29.3
16.7
16.7
39.7
45.1
2
5
7
12
47.3
56.1
60.5
75.0
11.9
12.0
12.0
12.1
58.8
67.7
72.2
86.8
45.2
53.3
57.8
71.5
13.3
13.3
13.4
13.4
58.0
66.2
70.8
84.6
42.5
50.2
54.5
67.6
14.9
14.9
14.9
15.0
56.8
64.6
69.0
82.2
39.6
47.0
51.0
63.5
16.7
16.7
16.7
16.8
55.6
63.1
67.1
79.8
-8
-4
36.5
44.0
14.7
14.8
50.5
58.3
34.5
41.7
16.4
16.5
50.1
57.6
32.3
39.3
18.3
18.4
49.7
56.8
30.0
36.6
20.5
20.6
49.4
56.2
2
5
7
12
58.5
68.8
74.4
91.9
15.0
15.1
15.2
15.4
73.1
83.5
89.2
106.9
55.6
65.6
71.1
87.6
16.7
16.8
16.9
17.1
71.7
81.9
87.5
104.2
52.5
62.1
67.2
83.2
18.6
18.7
18.8
18.9
70.4
80.1
85.4
101.6
49.3
58.3
63.2
78.4
20.8
20.9
21.0
21.1
69.2
78.4
83.4
98.9
-8
-4
45.0
53.3
17.5
17.6
61.7
70.3
42.0
50.7
19.5
19.6
60.5
69.5
39.5
47.7
21.7
21.9
60.1
68.6
36.8
44.8
24.3
24.5
59.7
68.0
2
5
7
12
70.4
82.4
89.3
109.8
17.8
18.0
18.0
18.2
87.7
99.9
106.8
127.6
67.1
79.3
85.5
104.8
19.8
20.0
20.0
20.2
86.3
98.7
105.0
124.5
63.5
75.0
81.0
99.8
22.1
22.2
22.3
22.4
84.8
96.5
102.6
121.6
59.7
70.5
76.5
94.2
24.7
24.8
24.9
25.0
83.3
94.4
100.4
118.4
-8
-4
51.8
62.5
20.7
20.9
71.6
82.6
48.9
59.2
22.9
23.1
70.7
81.4
46.0
55.8
25.4
25.7
70.1
80.3
43.0
52.3
28.3
28.5
69.7
79.4
2
5
7
12
82.7
97.8
105.3
129.5
21.3
21.5
21.7
22.0
103.3
118.8
126.4
151.1
78.6
93.0
100.5
123.8
23.5
23.8
23.9
24.3
101.3
116.1
123.7
147.5
74.4
88.0
95.3
117.5
26.1
26.3
26.5
26.9
99.5
113.4
120.9
143.6
70.1
82.8
89.8
111.0
29.0
29.2
29.4
29.8
97.8
111.0
118.1
139.9
-8
-4
60.1
72.5
23.8
24.0
82.8
95.6
56.9
68.8
26.2
26.5
81.9
94.2
53.5
64.8
29.1
29.3
81.1
92.7
50.0
60.6
32.2
32.5
80.4
91.5
2
5
7
12
95.9
113.4
122.3
151.3
24.5
24.8
24.9
25.4
119.6
137.5
146.6
176.1
91.2
107.6
116.9
143.9
27.0
27.3
27.5
28.0
117.3
134.1
143.6
171.2
86.2
101.9
110.4
136.4
29.8
30.2
30.4
30.9
114.9
131.0
139.8
166.4
81.0
96.0
104.1
128.7
33.0
33.4
33.6
34.2
112.7
128.2
136.5
161.8
Cc: gross cooling capacity
Pi: Compressors gross power input
Cde: Heating capacity to evacuate
12
45
Pf
kW
Pf
kW
EN
T
PR
TE
IO N
D E L'E N VI RO
55
NN
EM
Pa
kW
Pc
kW
13.7
18.7
22.2
24.1
30.1
9.4
9.4
9.4
9.3
9.3
22.5
27.6
31.2
33.1
39.1
20.9
28.0
33.1
35.8
44.1
13.7
13.8
13.8
13.8
13.9
33.8
41.1
46.4
49.1
57.5
26.8
36.6
43.5
47.3
59.2
18.9
18.8
18.8
18.8
18.8
44.6
54.5
61.6
65.4
77.3
33.8
45.8
54.3
59.0
73.3
23.2
23.3
23.4
23.5
23.6
55.6
68.0
76.7
81.5
96.1
41.5
55.7
65.9
71.5
88.5
27.4
27.6
27.7
27.8
27.9
67.3
82.0
92.5
98.2
115.5
48.6
65.4
77.4
84.0
104.1
31.8
32.2
32.5
32.7
33.1
78.6
96.2
108.6
115.4
136.1
46.4
35.9
80.1
56.4
75.8
89.8
97.5
120.9
36.2
36.7
37.1
37.3
38.0
90.6
110.8
125.4
133.4
157.5
Standard condition
Zone where use of water / glycol is compulsory
Calculation fouling 0.00005 m2 °C/W
heat pumps - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - nA 12.538 B
Cooling and heating capacities rejected on remote condenser
EN
RO
NME
N TA L LY F R
IE
ND
LY
DYNACIAT LGN
VI
HFC R407C
O
CT
CONDENSING TEMPERATURE °C
LGN
Evaporator water
outlet temperature °C
Glycol water
500Z
Pure water
Glycol water
540Z
Pure water
Glycol water
600Z
R407C
Pure water
Glycol water
753Z
Pure water
Glycol water
900Z
Pure water
Glycol water
1000Z
Pure water
Glycol water
1100Z
Pure water
Glycol water
1200Z
Pure water
35
40
45
EN
T
PR
TE
IO N
D E L'E N VI RO
NN
EM
55
50
Pf
Pa
Pc
Pf
Pa
Pc
Pf
Pa
Pc
Pf
Pa
Pc
-8
kW
73.75
kW
27.97
kW
100.6
kW
70.1
kW
31.2
kW
99.9
kW
67.1
kW
34.7
kW
100.1
kW
63.2
kW
38.5
kW
99.7
2
5
7
115.9
135.9
146.1
28.9
29.3
29.6
144
164.4
174.9
110.9
130.2
140.7
32.4
32.9
33.1
142.2
162.0
172.9
105.4
123.9
133.9
36.1
36.6
36.9
140.2
159.3
169.7
99.7
117.3
126.9
40.2
40.8
41.1
138.2
156.6
166.4
12
-8
178.9
80.3
30.2
32.0
208.4
110.9
172.1
76.1
33.8
35.7
205.1
110.1
164.3
71.7
37.7
40.0
200.9
109.6
155.9
67.4
41.9
44.8
196.5
109.6
2
5
7
129.2
154.3
167.0
32.6
32.8
32.9
160.8
186.3
199.1
123.3
146.9
158.7
36.3
36.5
36.6
158.4
182.3
194.2
116.5
139.2
150.4
40.5
40.7
40.8
155.6
178.5
190.0
110.0
130.9
142.0
45.3
45.5
45.6
153.5
174.8
186.0
12
-8
204.6
88.0
33.2
34.9
237.0
121.3
195.8
83.3
36.9
38.9
231.7
120.3
185.3
77.8
41.0
43.4
225.2
119.0
175.2
72.9
45.8
48.6
219.6
118.8
2
5
7
140.8
162.8
178.5
35.7
35.9
36.0
175.4
197.7
213.6
134.4
157.2
170.4
39.7
39.9
40.1
172.7
195.9
209.3
127.2
149.6
161.8
44.2
44.5
44.6
169.7
192.6
205.0
119.2
140.4
152.3
49.4
49.6
49.8
166.5
188.2
200.3
12
-8
220.1
116
36.3
42
255.6
156
210.5
111
40.3
47
249.8
155
200.1
105
44.9
52
243.8
155
189.1
99
50.1
58
237.6
154
2
5
7
178
206
222
43
44
44
220
248
265
171
197
214
48
49
49
218
245
261
163
188
204
54
55
55
215
241
257
154
178
193
60
61
61
212
237
252
12
-8
268
137
45
52
312
186
257
130
50
57
306
185
246
123
56
64
300
184
233
116
62
71
294
183
2
5
7
214
249
270
53
54
54
266
301
322
205
238
258
59
60
60
262
296
316
195
226
245
66
66
67
258
291
310
184
214
231
73
74
74
254
285
303
12
-8
325
151
55
56
379
205
312
145
61
62
371
204
297
138
68
69
363
204
281
130
75
77
354
203
2
5
7
234
271
293
57
58
58
290
327
349
224
260
281
64
65
66
287
323
345
214
248
268
72
73
73
283
318
339
202
235
254
80
81
82
279
313
333
12
-8
352
165
59
63
410
227
339
156
67
70
404
226
323
147
74
77
396
225
307
139
83
86
387
225
2
5
7
257
303
326
65
66
66
321
368
392
246
289
312
72
73
73
318
362
385
233
275
296
80
81
82
313
356
378
220
259
280
89
90
91
309
349
370
12
400
67
467
382
75
457
364
83
447
345
92
437
Pf
kW
Pa
kW
Pc
kW
58.9
42.7
99.1
93.5
110.1
119.1
146.7
44.6
45.2
45.6
46.5
136
153.5
162.9
191.6
102.5
122.2
132.3
163.7
50.8
51.0
51.0
51.2
150.9
171.0
181.3
213.2
111.1
131.5
143.0
177.6
55.2
55.5
55.6
55.9
163.7
184.7
196.4
231.5
92
64
153
144
167
181
220
67
68
68
69
208
232
247
287
108
79
182
172
200
217
269
81
82
83
84
250
279
297
350
121
86
202
190
220
239
289
89
90
91
92
275
307
326
378
129
95
224
206
242
263
323
99
100
101
102
305
342
364
426
-8
181
70
250
173
77
250
162
85
247
152
95
246
141
105
246
2
5
284
334
72
73
356
407
270
318
80
81
350
398
256
302
88
89
345
392
242
285
98
99
340
384
226
267
109
110
335
377
7
360
74
433
344
81
425
327
90
417
308
100
407
289
111
400
12
441
75
514
423
83
503
401
91
489
378
101
476
356
112
464
Cc: gross cooling capacity
Pi: Compressors gross power input
Cde: Heating capacity to evacuate
Standard condition
Zone where use of water / glycol is compulsory
Calculation fouling 0.00005 m2 °C/W
heat pumps - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - nA 12.538 B
13
dynaciat lg
Water-cooled chillers
Water-cooled chillers
dynaciat lg
Water pressure drop
LG - LGP 120 - 600
Condenser and evaporator
(prohibited use outside limit applications)
EVAPORATOR
160
Water pressure drop in kPa
100
80
60
50
40
30
20
10
8
3
4
5
6
7
8
9 10
15
20
30
40
50
60
70
80
Water flow m3/h
CONDENSER
160
Water pressure drop in kPa
100
80
60
50
40
30
20
10
8
3
4
5
6
7
8
9 10
15
20
30
40
50
60
70
80
Water flow m3/h
n Units conversion formulae
= bar x 100
Foot (ft)
= mm x 0.0032808
bar
= mH2O x 0.0981
Pounds (lb)
= kg x 2.205
kg/cm2
= bar x 1.0197
Cubic foot mn (cfm)
= m3/h x 0.5885
Pi (lbf/in2)
= bar x 14.504
US Gallons
= m3 x 264.2
Inches (in)
= mm x 0.0394
UK Gallons
= m3 x 220
kPa
14
heat pumps - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - nA 12.538 B
Water pressure
LGN 120 - 1200
dynaciat lg
Water-cooled chillers
drop
Condenser and evaporator
(prohibited use outside limit applications)
Water pressure drop in kPa
EVAPORATOR
Water flow m3/h
Filter - LG - LGP - LGN (compulsory)
8
Water pressure drop in mCE
6
0
4
AP
EV
12
0
50
50
-1
2
1
0.8
0.6
AP
EV
0.4
40
-2
0
0
ND
CO
0
35
0
024
0
3
0
20
AP
0V
5
E
1
012
ND
CO
0
35
00
3
AP
EV
2
D
0
50
00
4
N
CO
00
4
0
00
-1
0
90
0
30
20
5
0
7
-1
6
0
0
0
ND
54
11
D
CO
D
N
N
O
P
-C
CO
VA
P
E
A
AP
EV
EV
0.2
0.1
3
4
5
6
7
8
9 10
15
20
30
40
50
60
70
80
Water flow m3/h
heat pumps - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - nA 12.538 B
15
Water-cooled chillers
Water pressure
ILG 120 - 300
dynaciat lg
drop
Evaporator (prohibited use outside limit applications) INTERNAL CIRCUIT AND EXTERNAL CIRCUIT
Water pressure drop in kPa
250
200
100
90
80
0
15
0
12
70
60
0
20
50
0
24
40
0
30
30
20
15
3
4
5
6
7
8
9
10
15
20
25
30
40
50
60
70
Water flow
m3/h
Water pressure drop in mCE
Filter - ILG (compulsory)
Water flow m3/h
n Units conversion formulae
kPa
bar
kg/cm2
Pi (lbf/in2)
Inches (in)
16
=
=
=
=
=
bar x 100
mH2O x 0.0981
bar x 1.0197
bar x 14.504
mm x 0.0394
Foot (ft)
Pounds (lb)
Cubic foot mn (cfm)
US Gallons
UK Gallons
=
=
=
=
=
mm x 0.0032808
kg x 2.205
m3/h x 0.5885
m3 x 264.2
m3 x 220
heat pumps - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - nA 12.538 B
dynaciat lg
Water-cooled chillers
Dimensions
DYNACIAT LG - LGP 120 - 600
LG-LGP
120
Figure
150
200
240
300
1
350
400
500
540
2
Male connectors
a-b
G 1”1/2
c-d
G 1”1/4
A
127
G 1”1/2
600
3
Flange PN16
G 2”
G 2”1/2
DN 80
126
127
B
a : Condenser cooling water outlet (LG)
Condenser hot water outlet (LGP)
b : Condenser cooling water inlet (LG)
Condenser hot water inlet (LGP)
c : Evaporator chilled water outlet
C
d : Evaporator chilled water inlet
D
e : Electrical supply
E
Mass Kg
F
Empty
230
300
385
390
590
620
665
735
930
1125
In
operation
240
312
400
406
617
650
703
780
990
1190
heat pumps - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - nA 12.538 B
17
Water-cooled chillers
dynaciat lg
Dimensions
DYNACIAT LGN 120 - 1200
140 280 280
321
585 150 150 150
385
680
270
98
461
95
169 150 150 150 169
3xG
D
E
A
90
F
discharge pipe(s) connection
fluid return pipe(s) connection
1591
chilled water outlet
chilled water inlet
electrical supply
LGN
Circuit 2 Circuit 1
Anti-vibration mounts
Figure
Mass
Kg
240 300 350 400 500 540
1
2
600
1”3/8 1”3/8
1”5/8
2”1/8
1”5/8
b
7/8”
7/8” 1”1/8
1”1/8
1”1/8
1”1/8
a
1”3/8 1”5/8
b
1”1/8
G 1”1/2
Empty
223 284 375
In operation 232 296 390
G 2”
900 1000 1100 1200
4
1”1/8
G 1”1/4
127
753
3
a
c-d
A
B
C
D
E
F
G
18
120 150 200
4
Ø 2”1/8
1”3/8
1”1/8
1”5/8
Tube Ø
1”3/8
2”1/8
2”1/8
1”1/8
1”3/8
1”5/8
G 2”1/2 PN 16 DN 80
111
436 518 548 586 591 835
452 543 577 621 636 883
PN 16 DN 100
PN 16 DN 125
122
125.8
535 563 563 581
568
365 337 337 319
332
270 270 270 300
300
690 690 690 607
607
775 775 775 803
803
80
80
80
80
80
954 975 1135 1135 1161 1229
1008 1017 1117 1117 1203 1273
heat pumps - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - nA 12.538 B
dynaciat lg
Water-cooled chillers
Dimensions
DYNACIAT ILG 120 - 300
461
140 280 280
A
321
95
169 150 150 150 169
indooreau
circuit
water
outlet
a : Sortie
circuit
intérieur
indooreau
circuit
water
inlet
b : Entrée
circuit
intérieur
outdoor
outlet
c : Sortie
eaucircuit
circuitwater
extérieur
outdoor
circuit
inlet
d : Entrée
eau
circuitwater
extérieur
e : Alimentation
électrique
electrical supply
ILG
120
Figure
150
200
1
240
300
2
Male connectors
a-b
G 1”1/2
c-d
Mass Kg
A
G 2”
126
127
Empty
226
289
379
452
595
In operation
237
301
394
468
622
heat pumps - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - nA 12.538 B
19
Water-cooled chillers
Piping
installation example lg
-
dynaciat lg
lgp series
n COOLING or HEATING system with hydraulic changeover
cooling
WINTER
SUMMER
HEATING
WINTER
SUMMER
NOTE: the above piping diagram examples are indicative only and do not constitute installation details.
20
heat pumps - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - nA 12.538 B
Piping
installation example lg
-
dynaciat lg
Water-cooled chillers
lgp series
n Well water COOLING-ONLY or HEATING-ONLY system
Hydraulic changeover valve
NOTE: the above piping diagram examples are indicative only and do not constitute installation details.
heat pumps - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - nA 12.538 B
21
Water-cooled chillers
Piping
installation example lg
-
dynaciat lg
lgp series
Hydraulic changeover valve
NOTE: the above piping diagram examples are indicative only and do not constitute installation details.
22
heat pumps - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - nA 12.538 B
Piping
installation example
-
dynaciat lg
Water-cooled chillers
ilg series
NOTE: the above piping diagram examples are indicative only and do not constitute installation details.
heat pumps - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - nA 12.538 B
23
Water-cooled chillers
Piping
installation example
-
dynaciat lg
ilg series
A
A
NOTE: the above piping diagram examples are indicative only and do not constitute installation details.
24
heat pumps - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - nA 12.538 B
DYNACIAT LG - LGP - ILG - LGN
series
Installation recommendations
n Instructions for water quality criteria
WARNING: A water filter (800 microns) must be mounted on the unit inlet by the installer.
Correct and specified operation along with the assurance of reasonable life expectancy from the chiller-heater is significantly
dependent on the water circuits, especially if the water quality is allowed to cause scaling, corrosion, the formation of algae
or the growth of micro-organisms.
The water quality must be thoroughly analyzed to ensure that it is suitable for use on the machine, and to establish that
chemical treatment will be sufficient to maintain water quality at acceptable levels and if it will be necessary to install a softening/
demineralisation process.
This water analysis must establish the compatibility of the water used on the site with the following schedule of the
different materials existing on the CIAT machine :
- copper tubes 99.9% brazed with copper and silver filler,
- depending on models, bronze threaded connexions or steal flange couplings,
- exchangers with plates and connexions in stainless steal AISI 316 - 1.4401 brazed with copper and silver filler.
Caution : if these instructions are not respected the warranty of the chiller will be voided.
n Lifting and handling operations
Work with the best safety conditions for people during the lifting and handling operations.
Follow the lifting instructions provided on the machine and the Installation, Operating, Commissioning and Maintenance
instructions manual to the letter.
Plan properly to ensure an accessible route to the place of installation before moving the machine.
Always lift the unit vertically, under no circumstances must the machine be bent or put in a horizontal position.
n Location of the machine
DYNACIAT units are designed to be positioned indoor in a technical plant.
Frost protection must be foreseen.
Great attention must be paid to leaving necessary space for maintenance access to the unit, including at the top.
The machine has to be mounted on a level, non combustible flat and horizontal floor with a foundation capable of supporting
the operation weight.
Counter measures against the noise level of the auxiliaries, such as pumps, are recommended.
Before installation, prevent, with the help of a sound specialist, the different possible sources of noise transmission, depending
on the machine room and its design.
It is NECESSARY to fit the pipework with rubber expansion joints (optional equipment).
n Venting of technical plant
In accordance with the regulations on the installation site, a fresh air supply system may be installed to avoid dangerous
situations or loss of comfort in the case of refrigerant leakage from the circuit of the machine.
n Installation of the accessories
Several optional accessories can be delivered separately, to be mounted on the machine on site.
Follow the instructions of the Installation, Operating, Commissioning and Maintenance manual to the letter.
n Field electrical wiring
Follow the Installation, Operating, Commissioning and Maintenance instructions manual to the letter.
All necessary instructions for electrical connections are detailed on the wiring diagrams attached to the unit.
(They must be followed strictly)
Connections must conform to good engineering practices and to norms and regulations in force.
Field electrical wiring on site:
. main electric power supply,
. remote control of the machine (if necessary)
. free contacts informations (optional).
It is important to note that the unit is not protected against lightning transients on the electrical supply.
Accordingly, the installation must be fitted with apparatus to give adequate transient protection, and such devices must be
incorporated in the field power electric box.
heat pumps - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - nA 12.538 B
25
dynaciat lg
Water-cooled chillers
Water-cooled chillers
dynaciat lg
n Piping connections:
Follow absolutely the Installation, Operating, Commissioning and Maintenance instructions manual to the letter.
All piping shall be properly aligned and graded to a drain valve to permit complete drainage of the system. All pipes must be
installed and connected to the machine ensuring that complete access for service is provided to all panels, then covered with a
thermal insulation.
Adequately support and brace the piping independently of the unit to avoid vibrations and strain on the piping connections.
Isolating valves and manual valves for water flow adjustment must also be installed.
- Field water connections required on site :
. water supply of the pipes installation check-pressure reducing valve,
. evaporator, condenser and water drain,
- Provide the accessories necessary for all hydraulic circuits, for example :
. a cooling water flow control valve, thermostatic type, mounted on the inlet side or outlet side of the condenser,
. water expansion tank,
. drain valves on pipes low points to extract all the water,
. exchangers stop valves and water filter,
. air purge valves on pipes top points,
. check that there is a sufficient water volume in the installation (if necessary provide a storage tank),
. rubber expansion joints on the exchangers inlet and outlet water side.
. thermowells at each inlet and outlet connection for measurement during commissioning and maintenance procedure.
Caution :
- Water circuit pressure do not exceed 4.0 bar,
- Expansion tank mounted before water pump,
- Do not install any valve on the expansion tank.
- Be sure to install the water circulating pumps immediately on the exchangers water inlet side.
- Be sure that the water pressure at the suction of each circulating pump is equal or higher than the minimum pressure NPSH
required, particularly in case of an «open» type circuit.
- Referring to the technical conditions, the water quality criteria must be analyzed.
- The frozen protection of the unit and the hydraulic piping is necessary, as is the possibility of a water drain of the circuit.
In case of use of glycol for protection against freezing, it is absolutely necessary to check the physical properties and
concentration before commissioning.
- Before making final connection to the chiller-heater, the piping must be flushed with clean water to remove debris in the circuit.
n Start up
The commissioning of DynaCiat machines must be made by CIAT or by a CIAT approved company.
Follow the Installation, Operating, Commissioning and Maintenance instructions manual to the letter.
Non exhaustive list of operations to be carried out during commissioning:
- Check the correct location of the machine
- Check the electrical supply protection. Check the phases and correct rotation direction
- Check the electrical connections on the unit
- Check the correct direction of water circulation on the unit
- Check cleanliness of the water circuit
- Adjust water flow to the specified value
- Check the refrigeration circuit pressures
- Check the correct direction of rotation of compressors
- Check the water pressure drop and water flow
- Complete running parameters check list
n Maintenance operations
The machine requires specific routine maintenance operations which must be provided by authorized service agents agreed by
CIAT.
A report of the running parameters must be completed on a special «CHECK LIST» form which may be sent to CIAT.
For this operation, refer to and follow the instructions of the Installation, Operating, Commissioning and Maintenance instructions
manual to the letter.
It is necessary to take out a maintenance contract of the unit with a specialist of refrigerating machines agreed by CIAT,
including the period of warranty.
DYNACIAT LGN
series
n Refrigeration connections
- Follow the installation, Operating, Commissioning and Maintenance instructions manual to the letter.
- The pipes must be in refrigerant quality copper and follow the state of the art.
- As these units have been designed for connection to a removed condenser not supplied by CIAT, neither refrigerant
connections nor commissioning will be carried out.
- The pipe runs should be designed carefully and the requirements taken into consideration to facilitate the oil return to the
compressor and pressure drops which can impair the performances.
26
heat pumps - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - nA 12.538 B
dynaciat lg
Water-cooled chillers
Drycoolers
Air
cooled condensers
The CIAT drycoolers and air cooled condensers
series OPERA - AIRIAL are compatible with the
DYNACIAT LG units with water cooled condensers or
DYNACIAT LGN units without condenser.
n
n Available in a large choice of sizes and 6 ventilation
speeds, OPERA and AIRIAL units are adapted to the
dimensional or acoustic constraints of the site.
heat pumps - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - nA 12.538 B
27
Water-cooled chillers
dynaciat lg
USER-FRIENDLY INTERFACE CONSOLE
-
Multilingual LCD (4 lines of 24 characters each)
Temperature and pressure readings
Diagnosis of operation and fault states
Master/Slave control of two machines in parallel
Fault memory management
Pump management
Programmable operation times
Voltage-free contact card:
Inputs: - Automatic operation control
- Selection of setpoints 1 and 2
- Setpoint adjustable via a 4-20 mA signal
- Heating/cooling mode selection
- Compressor load shedding
Output: - General fault signalling
- Pump control
RS-485 OUTPUT AS STANDARD
Open Modbus/Jbus protocol (standard)
LonWorks protocol (option)
Ethernet gateway (option)
RELAY BOARD (OPTION)
Available outputs:
-
Water flow rate fault
Frost protection fault
Pump fault
Fan fault (air-to-water unit)
Low and high pressure fault
Compressor safety fault
Discharge temperature fault
Compressor operation status
REMOTE CONTROL UNIT (OPTION)
Operation and design same as display
console in room
MULTICONNECT MULTI-UNIT MANAGEMENT
(OPTION)
Main functions available:
-M
anagement of up to eight units on a single
water loop
- Management in COOLING mode (water chiller)
or HEATING mode (heat pump)
-
Management of chilled-water or hot-water
pumps
- Centralised management of a backup unit
- Unit load shedding
- Programmable system operation times
- Energy storage mode management
- Unit running time balancing
- Modbus/Jbus protocol RS485 output for BMS
link
This document is non-contractual. As part of its policy of continual product improvement, CIAT reserves the right to make any technical modification it feels appropriate without prior notification.
Head office
Avenue Jean Falconnier - B.P. 14
01350 - Culoz - France
Tel.: +33 (0)4 79 42 42 42
Fax: +33 (0)4 79 42 42 10
info@ciat.fr - www.ciat.com
CIAT Service
Tel. : 08 11 65 98 98 (0,15 € / mn)
Fax : 08 26 10 13 63 (0,15 € / mn)
Compagnie Industrielle d’Applications Thermiques - S.A. with a registered capital of 26 728 480 € - R.C.S. Bourg-en-Bresse B 545 620 114
28