Uninterruptible Power Supply (UPS)
BX35F/BX50F/BX50FW/BX75SW
Instruction Manual
• This manual gives you important information to use the this unit safely and therefore be sure to
read it before installation and use.
• Keep this manual handy at the place where you install the this unit so that you can read it
whenever necessary.
Introduction
Introduction
Thank you for purchasing the POWLI BX35F/BX50F/BX50FW/BX75SW Uninterruptible Power
Supply (UPS).
This unit is a UPS designed specifically for personal computers.
The UPS protects (backs up) personal computers, displays, peripherals, and so on up to a
power consumption of 350VA/210W (BX35F), 500VA/300W (BX50F, BX50FW), 750 VA/450W
(BX75SW) from failures in the power supply, such as power failures and voltage variations.
It protects connected devices from surge coming from power line.
You can easily replace batteries by yourself.
By using the UPS monitoring software, the system can be shut down automatically when a
power failure occurs.
Read this manual thoroughly to make the most of the unit.
Notes on the use of the Unit
The unit is designed and manufactured for use for OA equipment such as personal computers.
Do not use it when very high reliability and safety are required as listed below.
% Medical equipment that may cause death directly
% Applications that may cause injury (applications that directly affect the operation and control
of planes, ships, railroads, elevators, and so on)
% Applications that are always subjected to vibration such as cars and ships
% Applications in which a failure of this product may cause significant damage or effect to
the society and public
(essential computer systems, main communication equipment, public transportation
systems, and so on)
% Equipment with the same level of importance
For equipment that greatly affects the safety of people and maintaining public functions,
special considerations must be taken for operation, maintenance, and management, such as
duplication of the system and emergency power generation facilities.
Observe the contents of this manual such as the use conditions and environments.
If you want to use the unit for an important system that requires very high reliability, contact
the shop of purchase.
Do not modify/alter the unit.
This unit is designed for use inside Japan only. Do not use overseas countries (outside
Japan).
% If the voltage or frequency of the power supply differs, a failure or fire may occur.
% The unit does not comply with overseas safety standards and the EMI standards/regulations.
Disclaimers
We are not liable to all damage including malfunction and failure of equipment, connected devices,
and software and other secondary damage even if it is caused by the use of our product.
Make sure to read the safety precautions before using the unit.
©OMRON Corporation. 2002 All Rights Reserved.
IMPORTANT SAFETY INSTRUCTION
1.SAVE THESE INSTRUCTIONS.
This manual contains important instruction for Model BX35F, BX50F,
BX50FW, BX75SW.
That should be followed during instruction of the UPS and batteries.
2.SYMBOL
This symbol indicates earth ground.
This symbol indicates turning on UPS.
This symbol indicates turning off UPS.
3.INTERNAL BATTERY
Internal battery is Lead-acid type.
For BX35FW, BX50F, BX50FW model, the internal battery voltage is 6V
7.2AH. Each UPS used 2pcs batteries. And the total battery voltage is 12Vdc.
For BX75SW model, the internal battery voltage is 12V 7AH or 7.2AH.
The UPS used 2pcs batteries. And the total battery voltage is 24Vdc.
4.TEMPERATURE RATING
Maximun ambit temperature of UPS 40°C.
5.ENVIRONMENT
The unit is intended for installation in a temperature controlled, indoor
area free of conductive contaminants.
This pluggable type A equipment with battery already installed by the
supplier is operator installable and may be operated by laymen.
During the installation of this equipment it should be assured that the
sum of the leakage currents of the UPS and the connected loads does
not exceed 3.5mA.
The mains socket outlet that supplies the UPS shall be installed near the
UPS and shall be easily accessible.
For battery information, see users manual.
-1-
Procedure from installation to operation
Read “Safety precautions”
Pages 4 – 10
Start
Remove the product from
the package and check
the contents Page 11
Installation/connection
Perform installation and
connection Page 15
Check the operation
Page 23
Preparation for operation
Charge the battery
Page 25
Measure the backup time
Page 25
It is possible to omit the backup time measurement step.
Recharge the battery again
Page 25
* Preparation is complete.
Operate Page 26
No
Maintenance/inspection
Perform maintenance and
inspection Page 37
Deteriorated battery?
Yes
Replace the battery
Page 38
-2-
Table of Contents
Table of Contents
Introduction ....................................................................................................................................................... 1
IMPORTANT SAFETY INSTRUCTION ............................................................................................................. 1
Safety precautions ............................................................................................................................................ 4
1. Preparation ................................................................................................................................................. 11
1-1 Checking the contents ....................................................................................................................... 11
1-2 Part names ....................................................................................................................................... 12
1-3 Explanation of symbol used on unit .................................................................................................. 14
2. Installation and connection ........................................................................................................................
2-1 Precautions and notes on installation and connection .....................................................................
2-2 Installation and connection(BX35F/BX50F/BX50FW) ......................................................................
2-3 Installation and connection (BX75SW) .............................................................................................
2-4 Checking the operation ....................................................................................................................
15
15
18
20
23
3. Preparation for operation ...........................................................................................................................
3-1 Charging the battery .........................................................................................................................
3-2 Measuring the initial value of backup time .......................................................................................
3-3 Recharging the battery .....................................................................................................................
25
25
25
25
4. Operation ...................................................................................................................................................
4-1 Precautions and notes on operation .................................................................................................
4-2 Start and stop procedures and basic operation ................................................................................
4-3 Interpreting beeps and displays .......................................................................................................
4-4 Suspending a beep ..........................................................................................................................
4-5 Description of the self-diagnostic test function .................................................................................
4-6 Description of the auto battery test function .....................................................................................
4-7 Changing the setting of the functions ...............................................................................................
26
26
27
29
32
32
32
33
5. Maintenance and Inspection .....................................................................................................................
5-1 Checking the battery ........................................................................................................................
5-2 Replacing the battery .......................................................................................................................
5-3 Cleaning ...........................................................................................................................................
37
37
38
43
6. Using the Contact Signal (only for BX50FW, BX75SW) ............................................................................ 44
7. Measuring the backup time (Checking the discharge time of the battery) ................................................ 47
7-1 Measuring method of the backup time ............................................................................................. 47
7-2 Estimated backup time ..................................................................................................................... 47
8. Troubleshooting ......................................................................................................................................... 49
9. Description of related products ..................................................................................................................
9-1 Using the Network Line Surge Protection Function (BX75SW Only) ...............................................
9-2 Using the UPS monitoring software .................................................................................................
9-3 Connecting the UPS .........................................................................................................................
9-4 About the included UPS monitoring software ...................................................................................
50
50
51
52
53
References ......................................................................................................................................................
A. Specifications .......................................................................................................................................
B. Related products ..................................................................................................................................
C. Dimensional outline drawing (unit: mm) ...............................................................................................
D. Circuit block diagram ...........................................................................................................................
54
54
54
55
57
-3-
Safety precautions
Safety precautions
Important information for safe operation is described.
Be sure to read it before installation and start of use.
The safety symbols and their meaning used in this manual are as follows:
Warning
Misuse may cause death or serious injury.
Caution
Misuse may cause injury or property damage.
* Property damage means damage to houses/household effects, livestock, and pets.
: Indicates prohibition. For example,
indicates that disassembly is prohibited.
: Indicates obligation. For example,
indicates that grounding is necessary.
Note that events categorized as a caution required matter also may cause more serious results under certain
conditions.
Warning
Do not use this unit when very high reliability and safety are required as
listed below. This unit is designed and manufactured for use with OA
equipment such as personal computers.
Medical equipment or system that may cause death directly.
Applications that directly affect the safety of people (For example, the operation and control
of cars and elevators).
Applications in which a failure of the unit may cause significant damage to the society and
public (For example, essential computer systems and main communication equipment.)
Applications with the same level of importance.
Caution (for installation and connection)
Carry the unit considering its weight and balance, and place it on a stable
and robust base.
Dropping or toppling the unit may cause injury.
The weight of this unit is approximately: 5 kg (BX35F/BX50F/BX50FW)/ 9 kg (BX75SW).
If you drop the unit, stop using it and have an inspection and repair be done.
For repair, contact the shop of purchase.
Keep plastic package bags out of reach of children.
They may put their heads into it, and may be suffocated.
Make sure to connect the AC input plug of the unit into a wall outlet
(commercial power) with rated input voltage.
Connecting to a wall outlet (commercial power) of a different rated input voltage may result in
fire.
The unit may fail.
-4-
Safety precautions
Caution (for installation and connection)
Do not connect devices such as dryers, which have a half-wave rectifier
where only half-cycles of the AC power flows.
Overcurrent may damage the UPS.
Connect the unit to a wall outlet (commercial power) with a current capacity
of 8A or more (BX35F) or 12A or more (BX50F, BX50FW, and BX75SW).
Otherwise, the power cord may be heated.
When equipment with the maximum output capacity is connected, a maximum current of 8A
or (BX35F) or 12A (BX50F, BX50FW, and BX75SW) flows.
Provide secure grounding.
For a 3P wall outlet, directly connect the AC input plug of the unit to it. Not doing so may cause
an electric shock in the case of unit failure or electric leakage.
When you use a 3P-2P conversion plug for AC input plug, be sure to perform grounding
before connecting the AC input plug into a wall outlet (commercial power).
Do not disconnect the grounding before disconnecting the AC input plug from a wall outlet
(commercial power).
Grounding is necessary to enable its surge protection function.
Do not disassemble, repair, or modify the unit.
Doing so may cause an electric shock or a fire.
Do not install the unit in other than specified orientations.
Dropping or toppling the unit may cause injury.
If you install the unit in an orientation other than specified, the unit cannot be protected from a
battery fluid leakage.
Do not put any object on the unit whenever installing it vertically or
horizontally.
Doing so may cause distortion of/damage to the case, which may cause a fire.
Do not use the unit where the maximum temperature exceeds 40$C.
The battery becomes week rapidly, which may cause a fire.
Doing so may cause a failure or malfunction of the unit.
Do not install or store the unit in the places listed below.
The humidity is lower than 25%. The humidity is higher than 85%. A closed place such as in a
cabinet without clearance. There is flammable gas or corrosive gas. A place subject to vibration or shock. Outdoors.
Installation or storing the unit in such a place may cause a fire.
Do not use the unit in a closed place or do not cover the unit.
Doing so may cause abnormal heating or a fire.
Do not connect equipment that exceeds the output capacity of the unit.
The current protection of the unit may operate, which may stop the output.
The wiring of the plug strip heats up, which may cause a fire.
-5-
Safety precautions
Caution (for installation and connection)
Do not pinch or tie the cable of the unit.
Doing so may cause the cable to be damaged or heated, which may cause an electric shock
or a fire.
If the cable is damaged, stop using the unit and the cable must be repaired.
For repair, contact the shop of purchase.
Do not connect devices that use power supply with an improved power
factor.
Overcurrent may damage the UPS.
All of the included accessories are designed to be used exclusively with
the unit. Do not use the accessories with other devices.
Doing so may compromise the safety of devices.
This UPS utilizes voltages that may be hazardous. Do not attempt to disassemble the unit The
unit contains no user serviceable parts.Only factory service personnel may perform repairs.
Connection to any other type of receptacle other than a two-pole,three-wire grounded receptacle may result in shock hazard as well as violate local electical codes.
Do not allow liquids or any foreign object to enter the UPS.DO not place beverages or any
other liquid-containing vessels on or near the unit.
This unit intended for installation in a controlled environment (temperature controlled, indoor
area free of conductive contaminants).Avoid installing the UPS in locations where there is
standing or running water,or excessive humidity.
Do not attach a power strip or surge suppressor to the UPS.
Do not attach non-computer-related items,such as medical equipment,life-support
equipment,microwave ovens,or vacuum cleaners to UPS.
With the installation of the equipment it should be prevented, that the sum of the leakage
current of the UPS and the connected consumer does not exceed 3.5mA.
Caution (for use)
Do not wet or pour water onto the unit.
Doing so may cause an electric shock or a fire.
If you wet the unit, stop using it and the unit must be inspected and/or repaired.
For repair, contact the shop of purchase.
When the battery is dead, replace it immediately or stop using the unit.
Continuing the use of it may cause a fi re or electric shock due to liquid leaks.
Ambient temperature
20°C
30°C
Expected life
4 to 5 years * The values in the table are the expected life under standard
2 to 2.5 years
use conditions and are not guaranteed.
Wipe the 100-VAC input plug clean of dirt with a dry cloth occasionally.
Settled dust may cause a fire.
-6-
Safety precautions
Caution (for use)
If you notice abnormal sound or smell, smoke, or leakage from the inside,
immediately turn off the power switch and disconnect the AC input plug
from a wall outlet (commercial power).
Using the unit under such conditions may cause a fire.
If you notice such a condition, stop using the unit and contact the shop of purchase. for inspection
and repairs.
Use the unit under the conditions in which you can immediately disconnect the AC input plug
from a wall outlet (commercial power) in the case of an abnormal event.
If fluid leaks from the unit, do not touch the fluid.
Doing so may cause blindness or burns.
If the fluid contacts your eyes or skin, wash it out with lots of clean water and consult your doctor.
Caution (for maintenance)
When maintaining the connected equipment, turn OFF the power switch
and disconnect the AC input plug.
Even if you disconnect the AC input plug while the UPS is operating, the power output of this
unit does not stop and power is supplied from the outlet during a power failure.
Do not disassemble, repair, or modify the unit.
Doing so may cause an electric shock or a fire.
If fluid leaks from the unit, do not touch the fluid.
Doing so may cause blindness or burns.
If the fluid contacts your eyes or skin, wash it out with lots of clean water and consult your doctor.
Do not throw the unit into fire.
The lead battery in the unit may explode, or leak dilute sulfuric acid.
Caution (for battery replacement)
Perform replacement on a stable and flat place.
Handle the battery carefully not to drop it.
Not doing so could cause injury or burns due to liquid (acid) leakage.
Use a specified battery for replacement.
Not doing so may cause a fire.
Product model: BXB50F (battery pack for BX35F/BX50F/BX50FW)
BXB75S (battery pack for BX75SW)
Do not replace the battery in a place where there is flammable gas.
Spark may occur when connecting the battery, which may cause an explosion or fire.
If fluid (dilute sulfuric acid) leaks from the battery, do not touch the fluid.
Doing so may cause blindness or burns.
If it contacts your eyes or skin, wash it out with lots of clean water and consult your doctor.
Do not disassemble or modify the battery.
Doing so could cause dilute sulfuric acid leak, which could cause blindness and burns.
Do not drop the battery or do not give strong impact on it.
Dilute sulfuric acid may leak.
-7-
Safety precautions
Caution (for battery replacement)
Do not short the battery with metal objects.
● Doing so could cause an electric shock, fire or burn.
● Some electrical energy still remains inside the spent battery.
Do not put the battery into fire or do not break it.
● The battery may explode or leak dilute sulfuric acid.
● A battery can present a risk of electrical shock and high short circuit current.The following
precautions should be observed when working on batteries:
1) Remove watches, rings, or other metal objects from the hands.
2) Use tools with insulated handles.
3) Wear rubber gloves and boots.
4) Do not lay tools or metal parts on top of batteries.
5) Disconnect charging source prior to connecting or disconnecting batteries terminals.
● Servicing of batteries should be performed or supervised by personnel knowledgeable of
batteries and the required precautions. Keep unauthorized personnel away from batteries.
Notes
When moving the unit from a cold place to a warm place, leave it for several hours
before using it.
● If the unit is moved to a warmer place and the power is turned on soon, the unit failure may occur due to
condensation to the unit.
Charge the battery for at least 12 hours soon after purchasing the unit.
● If you do not use the unit for a long time after the purchase, the property of the battery may deteriorate and
the battery may become unusable.
● To charge a battery, connect the AC input plug of the unit to a wall outlet (commercial power).
When storing the unit, charge the battery for at least 12 hours and turn off the power switch.
● Even if the unit is not used, the battery gradually discharges, and if it is left for a long time, it goes into an
over discharge state.
The backup time may become shorter or the battery may become unusable.
● The storable period of the built-in battery of the unit is 6 months after complete charging.
● If you want to store the battery longer than 6 months, connect the AC input plug of the unit to a commercial
power wall outlet for at least 12 hours within 6 months.
● Turn off the power switch of the unit during storage.
Do not short the output lines of the unit each other and the output lines to the ground.
● The unit may fail.
Do not connect the AC input plug of the unit to its Power Supply Output Receptacle
during the Battery Mode.
● The unit may fail.
Do not install or store the unit in a place exposed to direct sunlight.
● The rise of temperature may cause the built-in battery to deteriorate rapidly and become unusable.
Do not perform a withstand voltage test.
● The input circuit has a built-in surge absorption device. A withstand voltage test may break it.
● When performing an insulation resistance test, use the 250VDC range.
-8-
Safety precautions
Notes
Before stopping the commercial power to the unit, turn OFF the power switch of the unit.
The unit enters Battery Mode when commercial power is stopped. If you frequently use the unit in Battery
Mode, the battery life may be significantly shortened.
Do not connect a page printer (laser printer, etc.) to the unit.
The Commercial Power Mode and Battery Mode are repeated frequently, which may shorten the life of the battery.
As the peak current of a page printer is large, an excess of the connection capacity or a power failure due
to instantaneous voltage drop may be detected.
Do not use the unit for devices that malfunction due to an instantaneous power failure
of 10msec (0.01 second) or less.
The connected device may stop due to switching time of 10msec or less.
Do not use the unit for inductive devices such as fluorescent lamps.
Connected devices may stop due to a rectangular wave output.
Inductive devices include devices incorporating transformers, coils, motors, and so on for their input.
Do not fail to confirm the system operation beforehand if the unit is used combined
with devices which power supply frequency fluctuate widely, such as private electric
generator.
This unit automatically recognizes the input power frequency when input power is supplied.
If the unit is connected when the input power frequency is not stable at the rated level, the unit may misidentify
the power supply frequency and may fail to operate normally.
(If the unit is in operation, changing from commercial power supply to another power supply
source, such as generating equipment, will cause no problem.)
Do not fail to confirm the system operation beforehand if the unit is used
other than “Output 100V mode”. (for BX50FW/BX75SW only)
At the time of battery operation, the maximum voltage (peak voltage) of output (rectangular
wave) may be lower than the maximum voltage at the time of usual operation (commercial
power supply). For this reason, some connected devices may fail to operate normally.
Battery recycling
This unit uses lead acid batteries.
The lead acid batteries are precious recyclable resources. Please cooperate recycling.
For information on recycling, please contact the shop of purchase.
-9-
Pb
Safety precautions
Explanation
Usual operation
● You may either leave the power switch of the unit on (operation status) or turn it off each time when stopping
the connected system. You can choose either of the operation methods for your convenience. We recommend turning off the power switch when you do not use connected devices for a long time.
● The battery is charged when the AC input plug of the unit is connected to a wall outlet (commercial power).
End of Battery Mode
● If a power failure lasts long, the battery discharges and power output from the unit stops. Shut down your
computer after performing appropriate procedure (for example, saving data) while the unit supplies power.
Reboot
● If the battery discharges completely during a power failure, the unit stops. After the recovery from the power
failure, the unit automatically restarts and supplies power. If you do not want to restart connected devices,
turn off the power switch of either the unit or the connected devices.
- 10 -
1. Preparation
1. Preparation
1-1 Checking the contents
Check whether all the package contents are included and there is no damage found on their appearance.
If you should notice defects or anything wrong, contact the shop of purchase.
(1) Accessories related to the main unit
User’s manual
Warranty
User registration card
3P-2P conversion adaptor
Label (How to determine operating status)
Rubber feet
Vertical stand
BX35F
1
1
1
1
1
None
BX50F
1
1
1
1
1
None
BX50FW
1
1
1
1
1
None
BX75SW
1
1
1
1
1
4
1 set (2 pieces)
1 set (2 pieces)
1 set (2 pieces)
None
BX35F
1
1
1 (USB)
BX50F
1
1
1 (USB)
BX50FW
1
1
1 (RS-232C)
BX75SW
1
1
1 (RS-232C)
(2) UPS monitoring software
User’s manual
CD-ROM
Communication cable
- 11 -
1. Preparation
1-2 Part names
BX35F/BX50F
Digital Status Indicator
Front view
Beep Stop/Test Switch
Battery Replacement Indication Lamp
Power Switch
Battery Replacement Cover
Grounding Terminal
AC Input Cord/Plug
Rear view
Power Supply Output Receptacle
AC Input Overcurrent Protection
USB Communication Connector
DIP Switch
BX50FW
Digital Status Indicator
Beep Stop/Test Switch
Front view
Battery Replacement Indication Lamp
Power Switch
Battery Replacement Cover
Communication Method Selection Switch
Power Supply Output Receptacle
AC Input Cord/Plug
Rear view
AC Input Overcurrent Protection
Serial/Contact Communication Connector
DIP Switch
- 12 -
1. Preparation
BX75SW
Digital Status Indicator
Front view
Beep Stop/Test Switch
Battery Replacement Indication Lamp
Power Switch
Battery Replacement Cover
Rear view
DIP Switch
Communication Method Selection Switch
Serial/Contact Communication Connector
Grounding Terminal
Network Surge Protection (Optional)
Power Supply Output Receptacle
AC Input Overcurrent Protection
AC Input Cord/Plug
- 13 -
1. Preparation
1-3 Explanation of symbol used on unit
Symbol
Description
Start the UPS.
Stop the UPS.
Suspend a beep.
UPS output power enable, supplied by operating on line mode, battery mode.
UPS has Error.
- 14 -
2. Installation and connection
2. Installation and connection
2-1 Precautions and notes on installation and connection
Caution (for installation and connection)
Carry the unit considering its weight and balance, and place it on a stable
and robust base.
Dropping or toppling the unit may cause injury.
The weight of this unit is approximately: 5 kg (BX35F/BX50F/BX50FW)/ 9 kg (BX75SW).
If you drop the unit, stop using it and have an inspection and repair be done.
For repair, contact the shop of purchase.
Keep plastic package bags out of reach of children.
They may put their heads into it, and may be suffocated.
Make sure to connect the AC input plug of the unit into a wall outlet
(commercial power) with rated input voltage.
Connecting to a wall outlet (commercial power) of a different rated input voltage may result in fire.
The unit may fail.
Do not connect devices such as dryers, which have a half-wave rectifier
where only half-cycles of the AC power flows.
Overcurrent may damage the UPS.
Connect the unit to a wall outlet (commercial power) with a current capacity
of 8A or more (BX35F) or 12A or more (BX50F, BX50FW, and BX75SW).
Otherwise, the power cord may be heated.
When equipment with the maximum output capacity is connected, a maximum current of 8A
or (BX35F) or 12A (BX50F, BX50FW, and BX75SW) flows.
Provide secure grounding.
For a 3P wall outlet, directly connect the AC input plug of the unit to it. Not doing so may cause
an electric shock in the case of unit failure or electric leakage.
When you use a 3P-2P conversion plug for AC input plug, be sure to perform grounding
before connecting the AC input plug into a wall outlet (commercial power).
Do not disconnect the grounding before disconnecting the AC input plug from a wall outlet
(commercial power).
Grounding is necessary to enable its surge protection function.
Do not disassemble, repair, or modify the unit.
Doing so may cause an electric shock or a fire.
Do not install the unit in other than specified orientations.
Dropping or toppling the unit may cause injury.
If you install the unit in an orientation other than specified, the unit cannot be protected from a
battery fluid leakage.
Do not put any object on the unit whenever installing it vertically or
horizontally.
Doing so may cause distortion of/damage to the case, which may cause a fire.
The life of the battery and electronic components may shorten due to a decrease in the heat
dissipation performance. This may lead to a failure of the device.
- 15 -
2. Installation and connection
Caution (for installation and connection)
Do not use the unit where the maximum temperature exceeds 40$C.
The battery becomes week rapidly, which may cause a fire.
Doing so may cause a failure or malfunction of the unit. Do not install or store the product in
the places listed below.
Do not install or store the unit in the places listed below.
The humidity is lower than 25%. The humidity is higher than 85%. A closed place such as in a
cabinet without clearance. There is flammable gas or corrosive gas. A place subject to vibration or shock. Outdoors.
Installation or storing the unit in such a place may cause a fire.
Do not use the unit in a closed place or do not cover the unit.
Doing so may cause abnormal heating or a fire.
Do not connect equipment that exceeds the output capacity of the unit.
The current protection of the unit may operate, which may stop the output.
The wiring of the plug strip heats up, which may cause a fire.
Do not pinch or tie the cable of the unit.
Doing so may cause the cable to be damaged or heated, which may cause an electric shock or a fire.
If the cable is damaged, stop using the unit and the cable must be repaired.
For repair, contact the shop of purchase.
Do not connect devices that use power supply with an improved power factor.
Overcurrent may damage the UPS.
All of the included accessories are designed to be used exclusively with
the unit. Do not use the accessories with other devices.
Doing so may compromise the safety of devices.
Notes
When moving the unit from a cold place to a warm place, leave it for several hours
before using it.
If the unit is moved to a warmer place and the power is turned on soon, the unit failure may occur due to
condensation to the unit.
Charge the battery for at least 12 hours soon after purchasing the unit.
If you do not use the unit for a long time after the purchase, the property of the battery may deteriorate and
the battery may become unusable.
To charge a battery, connect the 100 VAC input plug of the unit to a wall outlet (commercial power).
When storing the unit, charge the battery for at least 12 hours and turn off the power switch.
Even if the unit is not used, the battery gradually discharges, and the battery is left for a log time, it goes into
an over discharge state.
The backup time may become shorter or the battery may become unusable.
The storable period of the built-in battery of the unit is 6 months after complete charging.
If you want to store the battery longer than 6 months, connect the AC input plug of the unit to a commercial
power wall outlet for at least 12 hours within 6 months.
Turn off the power switch of the unit during storage.
- 16 -
2. Installation and connection
Notes
Do not short the output lines of the unit each other and the output lines to the ground.
● The unit may fail.
Do not connect the AC input plug of the unit to its Power Supply Output Receptacle
during the Battery Mode.
● The unit may fail.
Do not connect a page printer (laser printer etc.) to the unit.
● The Commercial Power Mode and Battery Mode are repeated frequently, which may shorten the life of the battery.
● As the peak current of a page printer is large, an excess of the connection capacity or a power failure due
to instantaneous voltage drop may be detected.
Do not use the unit for devices that malfunction due to an instantaneous power
failure of 10msec (0.01 second) or less.
● The connected device may stop due to the switching time of 10msec or less.
Do not use the unit for inductive devices such as fluorescent lamps.
● Connected devices may stop due to a rectangular wave output.
● Inductive devices include devices incorporating transformers, coils, motors, and so on for their input.
Do not fail to confirm the system operation beforehand if the unit is used combined
with devices which power supply frequency fluctuate widely, such as private electric
generator.
● This unit automatically recognizes the input power frequency when input power is supplied.
If the unit is connected when the input power frequency is not stable at the rated level, the unit may misidentify
the power supply frequency and may fail to operate normally.
(If the unit is in operation, changing from commercial power supply to another power supply source, such as
generating equipment, will cause no problem.)
Do not install or store the unit in a place exposed to direct sunlight.
● The rise of temperature may cause the built-in battery to deteriorate rapidly and become unusable.
Do not perform a withstand voltage test.
● The input circuit has a built-in surge absorption device. A withstand voltage test may break it.
● When performing an insulation resistance test, use the 250 VDC range.
Before stopping the commercial power to the unit, turn OFF the power switch of the unit.
● The unit enters Battery Mode when commercial power is stopped. If you frequently use the unit in Battery
Mode, the battery life may be significantly shortened.
Do not fail to confirm the system operation beforehand if the unit is used other than
"Output 100V mode". (for BX50FW/BX75SW only)
● At the time of battery operation, the maximum voltage (peak voltage) of output (rectangular wave) may be
lower than the maximum voltage at the time of usual operation (commercial power supply). For this reason,
some connected devices may fail to operate normally.
- 17 -
2. Installation and connection
2-2 Installation and connection(BX35F/BX50F/BX50FW)
Connection to back up your computer and peripherals
Note
Before installing this device, make a record of the serial number of this device.
The serial number is required when contacting the shop of purchase.
The serial number is written in the label on the unit.
(1) Disconnect all AC input plugs of your computer and peripherals from a wall outlet (commercial power).
Wall outlet
(commercial power)
Computer
Modem or other
peripheral
(2) Install the unit.
Write the usage start date on the label on the top side. Also, by using the included UPS
monitoring software, possible to keep a record of usage start date by the software.
Do not install the unit in any position other than those indicated below.
Vertical BX35F/BX50F/BX50FW
(Attach the included stand so
that the left side is the bottom.)
Horizontal BX35F/BX50F/BX50FW
• Detach the rubber feet from the
bottom surface when positioning
vertically.
• Once the rubber feet are removed,
protrusions on the bottom surface will
become visible.
Align the stand with these protrusions
to attach it.
Do not position the unit in the ways shown below.
Front panel facing upward
Front panel facing
downward
Front panel
Vertical
(Right side at bottom)
Front panel
Upside down
- 18 -
2. Installation and connection
(3) Connect devices that require backup to the unit’s power supply output receptacle.
When the unit’s 3 output receptacles (the BX35F/50F has 3, the BX50FW has 2) are insufficient, increase
the number of output receptacles by attaching a separately purchased power strip.
<Connection example 1>
<Connection example 2>
Modem or other peripheral
External HD
Separately purchased
power strip
PC
PC
• Even when the connected device has a 2P AC input plug, it can be connected to the power supply
output receptacle.
However, when a 2P AC input plug has a ground wire, attach the ground wire to the grounding terminal
(
) on the back of the unit.
<When connected device has 3P plug>
Connect directly
Plug of connected
device
<When connected device has 2P plug>
Connect directly
Plug of connected
device
<When connected device has 2P plug + ground>
Connect the plug directly
Plug of connected
device
The unit’s power
supply output
receptacle
Connect the ground wire to the
grounding terminal (
) on the unit
- 19 -
2. Installation and connection
(4) When the installation and connection are complete, connect the AC input plug of this unit to a wall outlet
(commercial power).
When you connect the AC input plug of this unit to a wall outlet (commercial power), battery charging
automatically starts regardless of the on/off state of the Power Switch and charging completes within 12
hours.
< 3P wall outlet >
< 2P wall outlet >
Wall outlet
(commercial power) Connect it directly.
AC input plug
of the unit
Wall outlet
(commercial power)
Connect the
grounding wire to
the grounding
terminal equipped to
the building. (If no
grounding terminal
is available, a
means of grounding
must be
constructed.)
Use the attached 3P-2P
Conversion Plug.
Plug of connected
device
Attached 3P-2P
Conversion Plug
• This unit was charged before shipment, but if it is being used for the first time, the backup time may be
reduced due to natural discharge. We recommend charging the unit before use.
2-3 Installation and connection (BX75SW)
Connection to back up your computer and peripherals
(1) Disconnect all computer and peripheral AC input plugs from the wall outlet (commercial power).
Wall outlet
(commercial power)
Computer
Modem or other
peripheral
- 20 -
2. Installation and connection
(2) Install the unit.
Write the usage start date on the label on the side. Also, by using the included UPS monitoring
software, possible to keep a record of usage start date by the software.
● Do not use this unit in any position other than the “proper positions” indicated in the illustration below.
Vertical
Proper positions
Horizontal
* Attach the rubber feet to each of the four corners on the bottom surface of the unit.
Improper positions
✕
✕
✕
The front surface in
on the bottom.
The back surface in
on the bottom.
- 21 -
The left surface in on the
bottom.
2. Installation and connection
(3) Connect devices that require backup to the unit’s power supply output receptacle.
A total of up to 750VA (7.5A) or 450W can be connected.
<Connection example 1>
<Connection example 2>
Modem or other peripheral
External HD
PC
Separately purchased
power strip
PC
• Even when the connected device has a 2P AC input plug, it can be connected to the power supply
output receptacle.
However, when a 2P AC input plug has a ground wire, attach the ground wire to the grounding terminal
(
) on the back of the unit.
(4) When installation and connection are complete, connect the unit’s AC input plug to a wall outlet (commercial power).
When the AC input plug is connected to a wall outlet (commercial power), the battery automatically starts
charging, taking up to 12 hours to complete.
< 3P wall outlet >
Wall outlet
(commercial power)
< 2P wall outlet >
Wall outlet
(commercial power)
Connect it directly.
AC input plug
of the unit
Connect the
grounding wire to
the grounding
terminal equipped to
the building. (If no
grounding terminal
is available, a
means of grounding
must be
constructed.)
Use the attached 3P-2P
Conversion Plug.
Plug of connected
device
Attached 3P-2P
Conversion Plug
• This unit was charged before shipment, but if it is being used for the first time, the backup time may be
reduced due to natural discharge. We recommend charging the unit before use.
- 22 -
2. Installation and connection
2-4 Checking the operation
When you are complete with connecting devices to the unit, the backup function must be confirmed.
Check that the Battery Mode is performed normally according to the following procedure.
This operation check simulates a power failure by disconnecting the AC input plug from a wall outlet.)
(1) Turn on the Power Switch of this unit.
The beeper sounds and the current settings are displayed on the LED.
After 5 secounds, the self-diagnostic test is performed in Battery Mode for approximately 10 seconds.
When the self-diagnostic test finishes successfully, switching to AC output from commercial power is performed and the following display is obtained.
(If the battery voltage is low, the self-diagnostic test is not performed and the operation starts immediately,
using output from commercial power.)
Status indicator
Description
Power switch “ON”
Operating normally
(2) Bring all the connected devices into operation.
(Including devices connected to the AC outlet of your PC.)
Operate the devices in a way in which abrupt power stop does not damage the connected devices, data,
etc.
(3) Under this condition, check the LED display and a beep of this unit.
Are they in the same status as shown below?
Status indicator
Beep
Power supply output receptacles
None
Outputs power (connected devices are powered)
Are the same as shown above.
➜ The operation is normal. Proceed to (4).
Are not the same as shown above. ➜ The operation is abnormal. One of the description in "4. Display
and beeps when there is an equipment failure" of "4-3 Interpreting
a beep and display" on page 29 must apply.
Take necessary measures and then proceed to (4).
(4) Disconnect the AC input plug of this unit from a wall outlet (commercial power).
The UPS enters Battery Mode.
- 23 -
2. Installation and connection
(5) In Battery Mode, check the LED display and a beep of the unit.
Are the LED display in the same status as A or B below?
Status indicator
(
indicates blinking)
Beep
Intermittent
4-second
intervals
Intermittent
1-second
intervals
Output
Charging
Description
ON
OFF
Discharging
Backup is operating due to power failure or AC input error.
The battery will be depleted if backup operation continues.
ON
OFF
Discharging
(Same as above.)
Battery level is low, so output will stop soon.
None
OFF
OFF
Discharging
Battery is dead, so output stopped. (This is displayed only
for a few seconds.)
Are not the same as shown above.
Operation is abnormal. Check the status of lamps and beep and
turn off the Power Switch.
• If the display is one of those shown in “4. Displays and beeps
when there is an equipment failure” in “4-3 Interpreting beeps
and displays” on page 29, take the necessary measures and
then go back to (1) on page 23.
• If no Battery Mode is performed and the UPS and the connected
devices stop, insufficient charging of the battery is suspected.
Connect the AC input plug of the UPS to a wall outlet (commercial power), charge the battery for approximately 6 hours, and
then go back to (4) on page 23.
• If the problem persists after checking the 2 points above,
contact the shop of purchase.
(6) Connect the AC input plug to a wall outlet (commercial power) again.
The Status indicator stops blinking and turns on without intervals, and the beeper stops.
(The status is as shown below.)
Status indicator
Description
Power switch “ON”
Operating normally
Checking the operation is now complete.
Installation and connection is now complete.
- 24 -
3. Preparation for operation
3. Preparation for operation
3-1 Charging the battery
When you connect the AC input plug of this unit to a wall outlet (commercial power), the battery charging automatically starts regardless of the on/off state of the Power Switch, and it is fully charged within
12 hours.
This unit has been charged prior to shipment. However, the backup time becomes shorter when using it for
the first time due to spontaneous discharge. We recommend charging this unit before using it.
If you do not perform the initial backup time measurement described below in “3-2 Measuring the initial
value of backup time”, proceed to “4. Operation”. Page 26
3-2 Measuring the initial value of backup time
When you measure the backup time initial value of the unit in your environment, this value can be used as
a guide when checking the battery and deciding the UPS monitoring software setting values.
See also
"7. Measuring the backup time"
Page 47
3-3 Recharging the battery
The battery is discharged completely when the backup time is measured, so you need to recharge it before
using the UPS.
You can use connected devices while recharging the battery, but the backup time when a power failure
occurs is shorter until the battery is fully charged.
(If a power failure occurs immediately after the start of charging, backup stops immediately.)
See also
Charge the battery as described in "3-1 Charging the battery."
Preparation for starting operation is now complete.
- 25 -
4. Operation
4. Operation
4-1 Precautions and notes on operation
Caution (for use)
Do not wet or pour water onto the unit.
Doing so may cause an electric shock or a fire.
If you wet the unit, stop using it and the unit must be inspected and/or repaired.
For repair, contact the shop of purchase.
When the battery is dead, replace it immediately or stop using the unit.
Continuing the use of it may cause a fire or electric shock due to liquid leaks.
For more on how to check the battery, see “5. Maintenance and inspection” on page 37.
For more on how to replace the battery, see“5-2 Replacing the battery” on page 38.
Ambient temperature
20°C
30°C
Expected life
4 to 5 years * The values in the table are the expected life under standard
2 to 2.5 years
use conditions and are not guaranteed.
Wipe the AC input plug clean of dirt with a dry cloth occasionally.
Settled dust may cause a fire.
If you notice abnormal sound or smell, smoke, or leakage from the inside,
immediately turn off the power switch and disconnect the AC input plug
from a wall outlet (commercial power).
Using the unit under such conditions may cause a fire.
If you notice such a condition, stop using the unit and contact the shop of purchase for inspection
and repairs.
Use the unit under the conditions in which you can immediately disconnect the AC input plug
from a wall outlet (commercial power) in the case of an abnormal event.
If fluid leaks from the unit, do not touch the fluid.
Doing so may cause blindness or burns.
If the fluid contacts your eyes or skin, wash it out with lots of clean water and consult your doctor.
Notes
Before stopping the commercial power to the unit, turn OFF the power switch of the unit.
The unit enters Battery Mode when commercial power is stopped. If you frequently use the unit in Battery
Mode, the battery life may be significantly shortened.
- 26 -
4. Operation
Explanation
Usual operation
● You may either leave the power switch of the unit on (operation status) or turn it off each time when stopping
the connected system. You can choose either of the operation methods for your convenience. We recommend turning off the power switch when you do not use connected devices for a long time.
● The battery is charged when the AC input plug of the unit is connected to a wall outlet (commercial power).
End of Battery Mode
● If a power failure lasts long, the battery discharges and power output from the unit stops. Shut down your
computer after performing appropriate procedure (for example, saving data) while the unit supplies power.
Reboot
● If the battery discharges completely during a power failure, the unit stops. After the recovery from the power
failure, the unit automatically restarts and supplies power. If you do not want to restart connected devices,
turn off the power switch of either the unit or the connected devices.
4-2 Start and stop procedures and basic operation
● When the AC input plug is connected to a wall outlet and the power switch is in the
OFF position:
• The status indicator displays "
".
• Power output is stopped.
• The battery is charged automatically.
● Start procedure
Operation Turn on the power switch of the UPS.
• The details of the most recent error are displayed. (item 4 on page 29)
• The beeper sounds and the current setting is displayed on the status indicator.
Cold start ON/OFF setting ➛ Output voltage setting.
• The status indicator displays “
”, and the self-diagnostic test is performed in Battery Mode for about
10 seconds.
(If the battery voltage is low, the self-diagnostic test is not performed. It is automatically executed after
the battery is charged.)
• When the self-diagnostic test finishes successfully, switching to AC output from commercial power is
performed and normal operation starts.
• If the self-diagnostic test is not executed, the UPS immediately starts outputting AC from commercial
power.
Status indicator
None
Beep
Power supply output receptacles
Outputs power (connected devices are powered)
• During operation, the battery is charged automatically.
- 27 -
4. Operation
Operation during a power failure
• If a power failure or abnormal input power supply occurs, the UPS automatically switches to Battery
Mode, continuing power output from the Power Supply Output Receptacles supplied from the battery.
• The status is displayed and the beeper sounds intermittently to alert the user.
See also
Setting switch 1 can be used to turn the beeper ON/OFF.
Page 33
(
Status
Battery
indicator replacement
Beep
Output Charging
Description
indicates blinking)
Solution
Intermittent
4-second
intervals
ON
Perform shutdown
Backup is operating due to power failure or operations for the
OFF
Discharging AC input error. The battery will be depleted connected devices
if backup operation continues.
and stop them.
Intermittent
1-second
intervals
ON
OFF
(Same as above.)
(Same as above.)
Discharging Battery level is low, so output will stop soon.
None
OFF
Battery is dead, so output stopped.
OFF
Charge the battery.
Discharging (This is displayed only for a few seconds.)
Operation during recovery from a power failure
• If a power failure or abnormal power input is resolved while the UPS supplies power, it returns to the
commercial power output status automatically. Charging the consumed battery starts.
• If a power failure or abnormal power input is resolved after the battery is discharged completely and
power output is stopped, the UPS restarts automatically and resumes power output. Charging the consumed battery starts.
Stop procedure
Operation
Turn on the power switch of the UPS.
• The power output from the UPS stops.
Status
Battery
indicator replacement
Beep
None
Output Charging
OFF
ON
Description
There is AC input
Power switch “OFF”
• Even if you turn off the power switch, if 1AC is supplied from commercial power, the battery is automatically charged.
- 28 -
4. Operation
4-3 Interpreting beeps and displays
1. Displays and beeps during normal operation
No.
Status
Battery
indicator replacement
Beep
Output Charging
indicates blinking
Description
Solution
1
None
OFF
OFF
No AC input
Operation stopped
—
2
None
OFF
ON
There is AC input
Power switch “OFF”
—
3
None
ON
ON
Power switch “ON”
Operating normally
—
2. Displays and beeps while testing
4
None
ON
OFF
Self-diagnostic test in progress
Discharging
—
5
None
ON
OFF
Auto battery test in progress
Discharging
—
3. Displays and beeps during power failure or AC input error
6
Intermittent
4-second
intervals
ON
Backup is operating due to power failure or Perform shutdown
OFF
AC input error. The battery will be depleted operations for the
Discharging if backup operation continues.
connected devices
and stop them.
7
Intermittent
1-second
intervals
ON
(Same as above.)
OFF
(Same as above.)
Discharging Battery level is low, so output will stop soon.
8
None
OFF
Battery is dead, so output stopped.
OFF
Discharging (This is displayed only for a few seconds.)
Charge the battery.
9
None
OFF
(ON)
AC input voltage or frequency is
too high (over)
Power switch “OFF”
Use within the input
voltage/frequency
range described in
the specifications.
10
None
OFF
(ON)
AC input voltage or frequency is
too low (under)
Power switch “OFF”
(Same as above.)
4. Displays and beeps when there is an equipment failure
11
Intermittent
0.5-second
intervals
12
Continuous
Reduce the number
of connected
devices until the
ON
display appears as
in status No. 3.
Turn OFF this unit
and all connected
Out put stopped due to excess connection
devices. Reduce the
ON, or capacity. When the connection capacity is
number of connected
OFF
Discharging 120% or more, the unit immediately enters
devices, and then turn
this status without first entering status No. 11. ON this unit and the
connected devices.
There are too many connected devices and
ON, or the rated capacity is exceeded. If this
Discharging status continues for 5 minutes or more, the
status No. 12 occurs and output stops.
- 29 -
4. Operation
4. Displays and beeps when there is an equipment failure (continued)
Status
Battery
No.
indicator replacement
13
14
Beep
Continuous
Continuous
Output Charging
OFF
OFF
Description
Output stopped due to exceeded
ON, or
Discharging connection capacity or a short-circuit
with the connected devices
—
Output stopped due to a failure.
When the beep stop switch is
pressed, the details of the error are
displayed.
(No.15 to No.19)
Continuous
OFF
—
16
Continuous
OFF
—
17
Continuous
OFF
—
Output stopped due to battery charge
voltage error (over)
18
Continuous
OFF
—
Output stopped due to battery charge
voltage error (under)
Continuous
OFF
—
Solution
Check that the AC
input of connected
devices is not
short-circuited.
Follow the
corresponding
solutions in boxes
No. 15 to 19.
Turn OFF this unit and
all connected devices.
Then, turn the power
Output stopped due to output voltage error switch back ON for this
(over)
unit only. If the display
does not change, there
is a problem with this
unit, so get it repaired.
If the display does
change, it is due to a
Output stopped due to output voltage error combination with a
connected device.
(under).
If anything is unclear,
contact the the shop of
purchase.
15
19
indicates blinking
Output stopped due to problem with
the internal temperature
There is a problem with
this unit, so get it
repaired.
The cause of this may
be that the ambient
temperature of the UPS
has increased. Check
the ambient temperature of the UPS. If it
exceeds 40°C, lower
the ambient temperature. Turn OFF this unit
and all connected
devices. Then, turn the
power switch back ON
for this unit only. If the
temperature is lower
than 40°C, there is a
problem with this unit,
so get it repaired.
5. Display and beep for battery replacement
20
Intermittent
2-second
intervals
ON
ON
The battery test detected a weak battery.
- 30 -
Charge the battery.
You can replace the
weak battery with a
separately purchased
replacement battery
as needed.
4. Operation
6. UPS operation mode setting display
21
—
—
—
—
Cold start ON setting
UPS can start up even when there is no AC input
—
22
—
—
—
—
Cold start OFF setting
UPS can start up only when there is AC input
—
23
—
—
—
—
Output 100V mode
Output voltage is 100V (effective value)
—
24
—
—
—
—
Output 110V mode
Output voltage is 110V (effective value)
—
25
—
—
—
—
Output 115V mode
Output voltage is 115V (effective value)
—
26
—
—
—
—
Output 120V mode
Output voltage is 120V (effective value)
—
- 31 -
4. Operation
4-4 Suspending a beep
You can suspend a beep by pressing and holding the Beep Stop/Test Switch while a beep is sounding for 0.5
second or longer.
4-5 Description of the self-diagnostic test function
You can use the following procedure to check whether a failure occurs inside the unit and whether replacing
the battery is required.
If the battery is not fully charged, the self-diagnostic test is not executed immediately.
After charging is complete, it is automatically executed.
(1) Connect your computer and other devices to the UPS and then turn on the power switch of the UPS.
(2) Press and hold the Beep Stop/Test Switch of the UPS for 0.5 second or longer.
Release the Beep Stop/Test Switch when a beep sounds. The Battery Mode starts for testing purpose. (No
beep sounds.) When the test is complete, the normal operation automatically starts.
(3) If the status indicator/battery replacement lamp blinks and the beeper sounds:
See also
"4-3 Interpreting a beep and display"
Page 29
Follow the directions for the solutions described in “4. Displays and beeps when there is an equipment
failure” and “5. Display and beep for battery replacement”.
4-6 Description of the auto battery test function
This UPS provides functions to automatically check whether replacing the battery is required and whether the
internal circuit is at fault. (You do not have to perform any operation.)
The test is performed at intervals of 4 weeks after the AC Input Plug is connected to a wall outlet (commercial
power).
The test is not performed if the power switch is OFF or if the battery is not fully charged.
(1) When the auto battery test starts, the Battery Mode automatically starts. (No beep sounds.) After the auto
battery test is complete, the normal operation automatically starts.
(2) If the status indicator/battery replacement lamp blinks and the beeper sounds:
See also
"4-3 Interpreting a beep and display"
Page 29
Follow the directions for the solutions described in “4. Displays and beeps when there is an equipment
failure” and “5. Display and beep for battery replacement”.
The setting switch on the rear of the UPS allows you to select the "disable the auto battery test" setting.
See also
"4-7 Changing the setting of the functions"
See " Auto battery test ON/OFF setting."
- 32 -
Page 33
4. Operation
4-7 Changing the setting of the functions
1. Selecting functions with the setting switches
Operation
After changing the setting switches, turn ON the power switch again while the AC input plug is
connected to a wall outlet (commercial power).
• Otherwise, the change will not take effect.
● Power output stop delay time setting (setting switch 1 ) … Factory-shipped
setting: OFF
ON
1
2
3
4
5
6
7
8
OFF: The beeper sounds when an alarm is necessary.
ON:
The beeper does not sound for backup operation or battery replacement. The beeper sounds for
other errors (connection capacity exceeded, operation error, etc.).
● Auto restart setting (setting switch 2 ) … Factory-shipped setting: OFF
ON
1
2
3
4
5
6
7
8
OFF: Automatically restarts when power is restored.
After a power failure occurs and the unit shuts down using the shutdown software or contact signal,
the unit automatically starts and begins to output when the commercial power is restored.
ON:
Does not automatically restart when power is restored.
After the unit shuts down using the shutdown software or contact signal, it does not start up when
commercial power is restored. Startup is performed manually by turning the power switch OFF
once, and then back ON again.
● Auto battery test ON/OFF setting (setting switch 3 ) … Factory-shipped setting:
OFF
ON
1
2
3
4
5
6
7
8
OFF: The battery test is automatically executed at intervals of 4 weeks.
ON:
The auto battery test is disabled.
Use this setting to disable Battery Mode in for the regularly performed auto battery test.
- 33 -
4. Operation
● Power output stop delay time setting (setting switches 5 and 6 ) … Factoryshipped setting: OFF and OFF (Only for BX50FW and BX75SW)
ON
1
2
3
4
5
Setting switch 5 Setting switch 6
6
7
8
Power output stop
delay time
OFF
OFF
0 second
ON
OFF
60 seconds
OFF
ON
120 seconds
ON
ON
Does not stop
power output
The UPS delays the shutdown timing.
If the user sets “switch 5: ON, switch 6: ON”, the UPS does not stop the output, even if the backup stop (BS) is
valid.
AC input
ON
OFF
BS signal
ON
OFF
UPS output ON
OFF
This timing is 10 ms or 10 sec.
Timing corresponds to the settings
for switch 7 .
Shutdown delay timing
This delay corresponds to the settings
for switch 5 and switch 6 .
<Note>
The remote ON/OFF signal is not related to this setting.
When the remote ON/OFF signal is “High”, the UPS stops the output immediately.
- 34 -
4. Operation
● UPS stop signal setting (setting switch 7 ) … Factory-shipped setting: OFF
(Only for BX50FW, BX75SW)
ON
1
2
3
4
5
6
7
8
OFF: The unit’s power output can be stopped by inputting a “High” backup power supply stop signal (BS)
that continues for 10 seconds or more. The power supply output is stopped with a voltage signal
input, even in commercial operation.
After stopping power output, a “Low” backup power supply stop signal (BS) restarts the unit once
the commercial power supply is normal. However, it does not restart if the automatic restart setting
(setting switch 2 ) is ON.
ON:
The unit’s power output can be stopped by inputting a “High” backup power supply stop signal (BS)
that continues for 0.01 (10 ms) seconds or more. Power supply output can be stopped when the
stop signal is received, only during backup operation (Battery Mode).
After stopping power output, a “Low” backup power supply stop signal (BS) restarts the unit once
the error that caused the power failure is eliminated.
Use this setting in commercial operation when you do not want to stop operations when a backup
power supply stop signal (BS) is received.
● Communication connector 9th-pin output signal switching setting (setting
switch 8 ) …Factory-shipped setting: OFF (Only for BX50FW, BX75SW)
* Valid only when using contact signal interface.
ON
1
2
3
4
5
6
7
8
OFF: Outputs a signal when a deteriorated battery needs to be replaced (WB signal)
ON:
Outputs the BU inversion signal
2. Switching switch (Only for BX50FW, BX75SW)
Caution
• Before operating the switching switch, turn OFF the power switch of the main unit and unplug the AC
input plug (turn OFF the AC input).
• If the switching switch is changed during operation, communication with peripherals (PC, etc.) will
cease to perform normally.
• If the AC input plug is not disconnected, the switching switch setting changes will not become valid.
Contact
Serial
Use when switching the communication interface (serial communication, contact communication).
- 35 -
4. Operation
3. UPS operation mode settings
The settings available for this operation are shown below.
• Cold start ON/OFF setting
When ON, it is possible to start up the unit even when there is no AC input plug.
(It is not possible, however, to start up the unit by the remote signals.)
• Output voltage setting (100V/110V/115V/120V)
Four types of output voltage can be set. (Applicable only for BX50FW and BX75SW)
3-1. The UPS operation mode can be set if the power switch is turned ON while the beeper stop switch is
pressed.
Note: While in setting mode, output from the output receptacles are OFF, even if the power switch is ON.
How to make settings:
There are 2 items to select.
1) Cold start ON/OFF setting
2) Output voltage setting (only for BX50FW, BX75SW)
(1) When the beeper stop switch is pressed (for less than 3 seconds), the next item is displayed.
Cold start ON/OFF setting
Output voltage setting
(2) Setting mode starts if the beeper stop switch is held (for more than 3 seconds).
(3) When the power switch is turned OFF, setting mode quits and it returns to normal status (Status
No.2).
Note: The output voltage setting is disabled for the BX35F and BX50F.
(Example: When making output power supply settings, selection between 110V/115V/120V
modes is not possible. Only 100V mode is possible.)
Normal status
(A)
(B)
“
” There is AC input
Power switch “OFF” (Status No. 2)
Setting mode
Cold start
ON/OFF setting
(C)
(C)
(D)
ON
Cold start ON:
The unit can start up even
when there is no AC input
OFF
Cold start OFF:
The unit can start up only
when there is AC input
100V
Output 100V mode
110V
Output 110V mode
(D)
(D)
Output voltage setting
(C)
(D)
Only for BX50FW,
BX75SW
(D)
(C)
115V
Output 115V mode
120V
Output 120V mode
(D)
(A) Turn ON the power switch while the beeper stop switch is pressed.
(B) Turn OFF the power switch.
(C) Press and hold the beeper stop switch (for more than 3 seconds).
(D) Press the beeper stop switch (for less than 3 seconds).
- 36 -
(D)
(D)
5. Maintenance and inspection
5. Maintenance and Inspection
Caution (maintenance)
When maintaining the connected equipment, turn OFF the power switch
and disconnect the AC input plug.
Even if you disconnect the AC input plug while the UPS is operating, the power output of this
unit does not stop and power is supplied from the outlet during a power failure.
Do not disassemble, repair, or modify the unit.
Doing so may cause an electric shock or a fire.
If fluid leaks from the unit, do not touch the fluid.
Doing so may cause blindness or burns.
If the fluid contacts your eyes or skin, wash it out with lots of clean water and consult your doctor.
Do not throw the unit into fire.
The lead battery in the unit may explode, or leak dilute sulfuric acid.
5- 1 Checking the battery
The sealed lead battery used in the unit has a limited life.
(The life varies depending on your storage/use environment and backup frequency.)
The nearer the end of the life is, the more rapidly deterioration proceeds.
1. Life of battery (estimated replacement timing)
Ambient temperature
20°C
30°C
Life of battery Replacement estimation
4 to 5 years 4 to 5 years after staring use
2 to 2.5 years 2 years after staring use
2. Method to check the battery
There are 3 methods for checking the battery.
• Perform a self-diagnostic test. (See page 32.)
• Use the auto battery test function. (See page 32.)
• Measure the backup time. (See page 47.)
By measuring the backup time, the battery life can be determined more accurately.
See also
Measure the backup time according to "7-1 Measuring method of the backup time."
Page 47
If the measured value is equal to the "initial value of the backup time" or less than half the value obtained
from the graph of "Estimated backup time" on page 47, replace the battery.
• When you compare the "initial value of the backup time" you measured and the current backup time,
make the capacity of devices connected to the UPS same as when you measured the initial value to
make judgment accurately.
3. Guideline on the frequency of checking the battery (measuring the backup time)
Ambient temperature
20°C
30°C
Check at intervals of 6 months
Until 3 years from purchase
Until 1.5 years from purchase
Check at intervals of 1 month
From after 3 years
From after 1.5 years
* The battery deteriorates even if it is stored. The higher the temperature is, the shorter the life
becomes.
- 37 -
5. Maintenance and inspection
5-2 Replacing the battery
The battery can be replaced either while the unit is stopped (power supply output stopped) or while it is in
operation (outputting power supply).
Caution
When the unit is used in compliance with UL standards, do not replace the battery while in operation
(while power is being output). Replacing the battery while in operation does not comply with UL standards. Make sure to stop the operation of the unit before replacing the battery.
* When replacing the battery, stop the connected devices, turn OFF the power switch of the UPS, and
disconnect the AC input plug from the wall.
* If an input power supply error such as a power failure occurs when replacing the battery while in operation, backup cannot be performed and output stops.
* Do not replace the battery during backup operation. Output will stop.
Caution (for battery replacement)
Perform replacement on a stable and flat place.
● Handle the battery carefully not to drop it.
● Not doing so could cause injury or burns due to liquid (acid) leakage.
Use a specified battery for replacement.
● Not doing so may cause a fire.
● Product model: BXB50F (battery pack for BX35F/BX50F/BX50FW)
BXB75S (battery pack for BX75SW)
Do not replace the battery in a place where there is flammable gas.
● Spark may occur when connecting the battery, which may cause an explosion or fire.
If fluid (dilute sulfuric acid) leaks from the battery, do not touch the fluid.
● Doing so may cause blindness or burns.
● If it contacts your eyes or skin, wash it out with lots of clean water and consult your doctor.
Do not disassemble or modify the battery.
● Doing so could cause dilute sulfuric acid leak, which could cause blindness and burns.
Do not drop the battery or do not give strong impact on it.
● Dilute sulfuric acid may leak.
Do not short the battery with metal objects.
● Doing so could cause an electric shock, fire or burn.
● Some electrical energy still remains inside the spent battery.
Do not put the battery into fire or do not break it.
● The battery may explode or leak dilute sulfuric acid.
- 38 -
5. Maintenance and inspection
Caution (for battery replacement)
A battery can present a risk of electrical shock and high short circuit current.The following
precautions should be observed when working on batteries:
1) Remove watches, rings, or other metal objects from the hands.
2) Use tools with insulated handles.
3) Wear rubber gloves and boots.
4) Do not lay tools or metal parts on top of batteries.
5) Disconnect charging source prior to connecting or disconnecting batteries terminals.
Servicing of batteries should be performed or supervised by personnel knowledgeable of
batteries and the required precautions. Keep unauthorized personnel away from batteries.
Notes
Battery recycling
This unit uses lead acid batteries.
The lead acid batteries are precious recyclable resources. Please cooperate recycling.
For information on recycling, please contact the shop of purchase.
Pb
5-2-1 Battery replacement procedure (BX35F/BX50F/BX50FW)
Preparation
(1) Purchase a BXB50F spare battery pack (sold separately).
(2) Remove any objects that are on this device when replacing the battery.
Replacing the battery (BX35F/BX50F/BX50FW)
(1) Open the front panel.
Use a screwdriver to remove the screw (1).
Detach the front panel.
(2) Disconnect the battery connector and remove the metal cover.
(Disconnect the red and black connectors.
Hold one connector in each hand and pull
them apart.)
- 39 -
(1) Slide the front metal cover to the right, and
(2) Pull it toward you to remove it.
5. Maintenance and inspection
(3) Remove the old battery, and insert the new battery.
Caution
If liquid (dilute sulfuric acid) leaks from the battery do not touch the fluid.
Do not make the batter pack upside down.
• Doing so could cause burns and, if it is put into your eye, blindness.
• If the liquid touches your eyes or skin, wash it out with lots of clean water and consult your doctor.
• Just put the spare batter pack into the packaging plastic bag and seal it with tape.
Do not drop the battery pack.
• Hold the battery securely not to drop it.
Do not remove the battery by holding the cables.
Pull on the white label attached to the battery, and
then hold the battery with your hands to remove it.
Insert the new battery.
Be careful not to drop the battery.
(4) Reattach the metal cover and connect the connectors.
• You may hear a “pop” sound when you connect the battery if it is replaced after the unit’s operation is
stopped, but this is not abnormal.
Fit the metal cover into the grooves and slide it to the
left to secure it.
(The battery is secured inside the case.)
Connect the red and black connectors.
(Make sure that the connectors are securely
connected.)
(5) Reattach the front panel.
Fit the left side of the panel on the case, and then
attach it.
Battery replacement is complete.
- 40 -
Tighten the screw with a screwdriver to secure
the front panel.
5. Maintenance and inspection
<After replacing the battery during operation...>
If the battery replacement indicator is displayed and the beeper sounds before replacement,
press the beeper stop/test button once to stop the beeper, and hold it for 5 sec. to perform a
self-diagnostic test. The beeper stops and normal operation resumes after the 10-second test
is complete.
<After replacing the battery when operation was stopped...>
Connect the AC input plug to a wall outlet (commercial power) and turn ON the power switch of the
UPS. When operation starts, the self-diagnostic test is automatically performed. Normal operation
resumes after the 10-second test.
Write the usage start date on the label on the top side. Also, by using the included UPS
monitoring software, possible to keep a record of usage start date by the software.
5-2-2 Replacing the battery (BX75SW)
Preparation
(1) Purchase a BXB75S spare battery pack (sold separately).
(2) Remove any objects that are on this device when replacing the battery.
Replacing the battery (BX75SW)
(1) Open the front panel.
Loosen and remove the 2 screws.
Detach the front panel.
(2) Disconnect the battery connector and remove the metal cover.
(Hold one connector in each hand and pull them apart.)
(1) Slide the front metal cover upward, and
(2) Pull it toward you to remove it.
- 41 -
5. Maintenance and inspection
(3) Hold the label stuck to the battery pack and remove it.
Insert the new battery pack.
Caution
● If liquid (dilute sulfuric acid) leaks from the battery do not touch the fluid.
Do not make the batter pack upside down.
• Doing so could cause burns and, if it is put into your eye, blindness.
• If the liquid touches your eyes or skin, wash it out with lots of clean water and consult your doctor.
• Just put the spare batter pack into the packaging plastic bag and seal it with tape.
● Do not drop the battery pack.
• If you see red tape stuck on the top of the battery pack, you can remove the battery completely by
pulling it 10 cm further.
Hold the battery securely not to drop it.
● Do not remove the battery by holding the cables.
Pull on the white label attached to the battery,
and then hold the battery with your hands to
remove it.
Insert the new battery pack.
Be careful not to drop the battery.
(4) Reattach the metal cover and connect the connectors.
You may hear a “pop” sound when you connect the battery if it is replaced after the unit’s
operation is stopped, but this is not abnormal.
Fit the metal cover into the grooves and
slide it downward to secure it.
Connect the red and black connectors.
(Make sure that the connectors are securely connected.)
(The battery is secured inside the case.)
- 42 -
5. Maintenance and inspection
(5) Fit the front panel.
Turn the 2 screws to secure the font panel clockwise with a screwdriver.
Fit the front panel.
Tighten the 2 screws.
Battery replacement is now completed.
<After replacing the battery during operation...>
If the battery replacement indicator is displayed and the beeper sounds before replacement,
press the beeper stop/test button once to stop the beeper, and hold it for 5 sec. to perform a
self-diagnostic test. The beeper stops and normal operation resumes after the 10-second test
is complete.
<After replacing the battery when operation was stopped...>
Connect the AC input plug to a wall outlet (commercial power) and turn ON the power switch of the
UPS. When operation starts, the self-diagnostic test is automatically performed. Normal operation
resumes after the 10-second test.
Write the usage start date on the label on the side. Also, by using the included UPS monitoring software, possible to keep a record of usage start date by the software.
5-3 Cleaning
Cleaning the UPS
Wipe the UPS lightly by tight squeezed soft cloth soaked with water or detergent
Do not use chemicals such as thinner and benzene. (They cause deformation or discoloration.)
Removing dust from the Power Plug
• Turn off connected devices and the Power Switch of the UPS.
• Disconnect the AC Input Plug from a wall outlet (commercial power) and remove dust around the plug
with a dry cloth.
• Disconnect the AC Input plugs of the connected devices from the UPS and clean them also.
• Connect the AC Input plugs of the connected devices to the UPS again, and connect the AC Input Plug
of the UPS to a wall outlet (commercial power).
(For information on the connection procedure:)
See also
"2-2 Installation and connection"
Page 18
- 43 -
6. Using the Contact Signal
6. Using the Contact Signal
(only for BX50FW, BX75SW)
You can develop your unique system based on the following specifications to automate the process at the
power failure.
Your can perform power-failure or closing procedure of the system by detecting the Backup Signal and the
Battery Low Signal, or receive failure notification by detecting the Trouble Signal.
You can stop the UPS by inputting the UPS Stop Signal from the system, and remote control start and stop of
the UPS by using the Remote ON/OFF Signal.
Also, this function is valid only when “connection communication” is selected for the “switching switch”. (See
item 2 on page 35.)
1. Signal output
The UPS has 5 kinds of output signals. The output circuit consists of an open collector circuit using a photo
coupler (a kind of electronic switch).
Backup Signal output: BU
Backup Signal reverse output: NBU
BU-COM ON when a power failure occurs
NBU-COM OFF when a power failure occurs
BU stays ON (NBU OFF) during a power failure.
NBU is output only when the”gcommunication connector 9th-pin output signal switching setting” (setting switch 8 ) is set to ON.
Battery Low Signal output: BL
BL-COM ON when the battery is low
Goes ON when the battery becomes weak during the
Battery Mode.
Trouble Signal output: TR
TR-COM ON when a power failure occurs
Goes ON when an internal failure of the UPS occurs.
Battery Replacement Signal output (WB)
WB-COM ON when battery deterioration is detected
Goes ON when the battery needs to be replaced due
to deterioration.
WB is output only when the “communication connector 9th-pin output signal switching setting” (setting
switch 8 ) is set to OFF.
2. Input of the UPS Stop Signal (BS)
BS-COM UPS stops
Stops the output of the UPS after the time period specified by the “power output stop delay time setting” (setting switches 5 and 6 ) has elapsed.
(1) When the "UPS Stop Signal setting" (setting switch 7 ) is set to OFF:
You can stop the output of the UPS by inputting the voltage signal (HIGH) that lasts at least 10 seconds
from the outside.
(2) When the "UPS Stop Signal setting" (setting switch 7 ) is set to ON:
You can stop power output by inputting the voltage signal (HIGH) that lasts at least 0.01 second (10
ms) from the outside that is accepted only during backup.
See also
"4-7 Changing the setting of the functions"
- 44 -
Pages 33
6. Using the Contact Signal
3. Remote ON/OFF Signal
External contact
Operate
Open
Start
Close
Stop
You can start and stop the UPS by the remote ON/OFF signals, by
the contact connected to the outside, or the ON/OFF status of the
open collector circuit. To use this function, turn on the Power Switch
of the UPS. (Note: When there is no AC power supply, it is not
possible to start up UPS by the remote ON/OFF signals even though
cold start is set ON.)
4. Connection to the system
Please make a cable to connect to the system by yourself.
See also
"8. Example of the use of the Contact Signal circuit"
Page 46
5. Contact Signal Connector (female DSUB9P)
Pin assignment
Pin number
1
2
3
4
5
6
7
8
9
Front view
Screw size: inch screw
#4-40 UNC
Signal name
BL
TR
BS
—
COM
Remote ON/OFF (–)
Remote ON/OFF (+)
BU
WB/NBU
6. Contact Signal ratings
Signal output (BL, TR, BU, WB/NBU)
UPS Stop Signal input (BS)
Photo coupler ratings:
35 VDC or less
Appliable voltage:
10mA
Input voltage HIGH
LOW
Maximum current
10 mA
5to 15 VDC
0.7 VDC or less
Remote ON/OFF
Voltage between terminals: 10 VDC
Current when closed:
max.10 mA
7. Contact Signal circuit inside the UPS
12V
2k 1
10V
BL
TR
BU
WB/NBU
2k 1
BS
Remote ON (+)
Remote OFF (-)
COM
- 45 -
6. Using the Contact Signal
8. Example of the use of the Contact Signal circuit
Example of the use of the BU, BL, WB/NBU signal
Nȍ
Example of the use of the TR signal
Example of the use of the BS signal
12V
12V
2kȍ
1kȍ
1.2kȍ
TLP521
From port on PC
TR
To system signal input
C2458
9. Precautions and notes on the use of the Contact Signal
Notes
When connecting a device that generates counter electromotive force to the signal output circuit
such as a relay, connect diodes to prevent counter electromotive force at the both end of the
relay.
Explanation
When power is restored after the unit stopped automatically during a power failure, the unit
automatically restarts and supplies power. If you do not want to start the connected devices, turn
OFF their switches or set the auto restart setting (setting switch 2) to ON. (See page 33.)
- 46 -
7. Measuring the backup time (checking the discharge time of the battery)
7. Measuring the backup time
(Checking the discharge time of the battery)
7-1 Measuring method of the backup time
(1) Connect the AC Input Plug of the UPS to a wall outlet (commercial power) and charge it for approximately
12 hours.
If you operate the UPS for 12 hours or more, it is charged. If a power failure occurred during this period,
charge it again.
(2) Turn ON all devices connected to the power output to be “backed up during a power failure”.
(Including devices connected to the AC outlet of your computer.)
Operate them in a way in which it is allowable that power supply to the connected devices stops.
● For Windows Server 2003/XP/Me/2000/Windows NT/Linux:
To be performed in case of hard drive stops.
● For Windows 98/95:
Choose Shut Down of Windows and follow the procedure below to shut down your OS.
Choose "Restart in MS-DOS mode" to exit from OS and display the MS-DOS mode screen.
(3) Disconnect the AC Input Plug of the UPS and measure the backup time.
Measure the time until the unit automatically stops and all displays disappear with the plug disconnected.
* The backup time you measure for the first time after purchase is the "initial value of the backup time."
7-2 Estimated backup time
The backup time varies depending on the capacity of connected devices.
After calculating the total capacity of connected devices, refer to the graph of the backup time to obtain an
estimation of the initial value of the backup time. (This is also applied to checking the battery.)
(1) Unify the total capacity (power consumption) of connected devices to W (Watt).
For the indication of connected devices, check your computer and the rear of the display.
There are 3 types of indication: VA (Volt·Ampare) indication, A (Ampare) indication, and W indication.
Example 1)
100 VAC, 50/60Hz, 145 W
Indication
Value
Example 2)
100 VAC, 50/60Hz, 1.8 A
VA
× power factor = W
Example 3)
100 VAC, 50/60Hz, 150 VA
A
× power factor × 100 = W
For devices that use the VA or A indication, convert the capacity into W. Multiply the value indicated on
devices by the value in the right table for conversion.
(When the power factor is unknown, enter “1”. The power factor usually ranges between 0.6 and 1.)
(2) Add the values converted into W to obtain the total capacity of the connected devices.
- 47 -
7. Measuring the backup time (checking the discharge time of the battery)
(3) Calculate the initial value of the backup time for the total capacity of the connected devices from the graph
below.
● Graph of backup time (initial value for product that has not been used)
● The smaller the capacity of connected devices becomes, the longer the backup time becomes.
<Reference diagram>
60
Backup time
50
40
BX35F
BX50F/BX50FW
BX75SW
30
20
10
5
3.5
0
42
60
90
84
120
180
126
180
270
168
240
360
Connection capacity (total capacity)
- 48 -
210
300
450
: BX35F
: BX50F/BX50FW
: BX75SW
8. Troubleshooting
8. Troubleshooting
Perform the checks shown below if the unit is operating abnormally.
If the unit continues to operate abnormally, please contact the shop of purchase.
Problem
Check and remedy
UPS does not operate.
The LED display does not
light up, even though the AC
input plug is connected to a
wall outlet (commercial
power) and the power switch
is ON.
1. Check that the AC Input Plug is connected to the commercial power securely.
2. The AC Input Overcurrent Protection worked and opened.
(If the black button is popped up, it is suspected that there are too many connected
devices or there is a short in connected devices.) Disconnect all of the connected
devices, push in the AC Input Overcurrent Protection Black Button, and turn on the
Power Switch of the UPS again. If the status indicator does not display normally, there is
a problem with the UPS. (See "Interpreting a beep and display" on page 29.)
3. Isn't the voltage of the wall outlet (commercial power) too low?
Stop devices that consume a lot of power such as an air conditioner. Check the UPS, for
example, by connect it to a wall outlet (commercial power) in another room or house.
(It does not operate when the voltage is less than 90V.)
Backup is not possible.
The computer stops when a
power failure occurs.
Isn't charging insufficient?
Perform the test after charging the battery for at least 12 hours.
You can charge the battery by connecting the AC input plug of the UPS to a wall outlet
(commercial power).)
Backup is performed too
frequently.
Frequent switching is
performed although a power
failure does not occur.
You hear the sound of
switching.
1. The input power supply may be at fault. Connect the UPS to a wall outlet (commercial
power) in another room or, if possible, another house and check it. Or, stop large devices
such as a cooler.
2. Isn't a page printer connected?
Because large current flows instantaneously in printers, normal backup is not possible.
The display is abnormal.
The display is unstable.
White lines occur.
Noise increases.
1. The UPS generates some noise when performing backup. For displays susceptible to
noise, distortion or white lines may occur, but the UPS is not at fault.
2. Grounding the UPS, computer, and display may improve this problem.
3. Noise during backup may become larger depending on connected devices, you can
continue to use the UPS because this occurs due to rectangular wave output.
The battery replacement
lamp blinks and the beeper
sounds at 2-second
intervals.
The battery is judged to be dead in the auto battery test or the self-diagnostic test.
Battery Mode cannot be performed and therefore replace the battery pack.
The status indicator shows
“ ”, and the beeper sounds
at 0.5-second intervals.
There are too many connected devices. There are too many connected devices. Reduce
the number of connected devices until “ ” is displayed on the status indicator.
The status indicator blinks
“ ”, and the beeper
sounds continuously.
The UPS stopped because too many devices were connected for 3 minutes or more, or
because 120% was exceeded.
Turn OFF all power to the unit and connected devices, and reduce the number of connected
devices. Then, turn the power to the unit and connected devices back ON and check
whether " " is displayed on the status indicator.
The output voltage is only
approximately 80 V when
measuring it with a tester.
The UPS outputs a special rectangular wave during the Batter Mode. Due to its
characteristics, simple testers indicates approximately 80 V. The UPS is not at fault. To
make correct measurement, you need a voltmeter that can measure "true rms value."
- 49 -
9. Description of related products
9. Description of related products
9-1 Using the Network Line Surge Protection Function
(BX75SW Only)
Using the optional BT75XSX, you can protect your modem, TA, and network card from damage due to surge by
absorbing surge voltage (abnormally high voltage) that may occur on the telephone line, ISDN line or network
cable due to thunder.
* If you do not use the Network Line Surge Protection Function, this section is not required.
The following 2 types of connectors are available for the Network Line Surge Protection Function.
- RJ45 (8 Pins)
- RJ11 (2 Pins, 4 Pins, or 6 Pins)
Notes
Do not reverse the connection of Line/Hub Side and Modem/TA/PC Side of the
Network Line Surge Protection.
● If a failure of the protection circuit occurs, the ISDN line and so on may be damaged.
1. When connecting to the telephone line
Connect the telephone line from the wall to the Line/Hub Side jack of the Network Line Surge Protection.
Use the telephone cable (modular cable) included with the BT75XSX to connect between the unit’s Modem/
TA/PC Side jack of the Network Line Surge Protection and your modem, FAX, etc.
2. When connecting to the ISDN line
Connect the ISDN line that comes out of the wall to the Line/Hub Side of the Network Line Surge Protection
of the UPS.
Use the telephone cable (modular cable) attached to the BT75XSX to connect between the Modem/TA/PC
Side Jack of the Network Line Surge Protection of the UPS and your DSU (or terminal adaptor with built-in
DSU).
3. When connecting to LAN 10Base-T/100 Base-Tx
To protect your 10Base-T/100 Base-Tx (twisted pair cable without shielding) network interface, you need to
separately purchase a cable equivalent to your cable in use. Connect the 10Base-T/100Base-Tx cable from
the HUB to the unit’s Line/Hub Side jack of the Network Line Surge Protection. Connect between the Modem/TA/PC Side jack of the Network Line Surge Protection and the network interface of your computer with
a separately purchased cable.
- 50 -
9. Description of related products
4. Connection example
Connect to the
Line/HUB Side
Telephone line, ISDN line, or 10Base-T
Connect to the
Modem/TA/Network Card Side
Modem, FAX, or LAN card
9-2 Using the UPS monitoring software
* If you do not use the UPS monitoring software, you can disregard this section.
UPS monitoring software selection table
Model
BX35F
BX50F
OS
Windows Server2003
Communication
method
Serial (USB 1.1)
Windows XP/2000
Windows ME/98
UPS monitoring
software
PowerAct Pro
(included software)
Required options
(sold separately)
UPS service (OS standard) +
UPS service driver (included software)
Serial (USB 1.1)
Mac OS X (10.3 or later) Serial (USB 1.1)
Mac OS X Server (10.3 or later) (Note 1)
Serial (RS-232C)
BX50FW Windows Server2003
BX75SW Windows XP/2000
PowerAct Pro
(included software)
UPS Power Manager
(included software)
PowerAct Pro
(included software)
UPS service (OS standard) +
UPS service driver (included software)
Windows ME/98
Contact signal
(Note 1) (Note 3)
Contact signal
(Note 1) (Note 2)
Serial (RS-232C)
Linux(Note 5)
Serial (RS-232C)
Windows NT4.0
UPS service
(OS standard)
UPS service
(OS standard)
PowerAct Pro
(included software)
PowerAct Pro
(included software)
BUC16, BUC24
optional cable
BUC16 (Note 4), BUC24
optional cable
Note 1: Files cannot be automatically saved.
Note 2: To automatically stop the UPS, it may be necessary to change the PC’s BIOS settings.
Change the PC’S BIOS settings so that the PC’s power supply is not automatically cut after OS shutdown is performed.
Note 3: Even if the UPS does not stop when the OS is shut down, it stops automatically when the battery is depleted.
Note 4: If the connected PC is an NEC PC-9800 series or PC9821-series computer, use BUC19.
Note 5: For the latest information, check our website at http://www.omron.co.jp/ese/
1. Using the included monitoring software
To use the software, use the “PowerAct Pro” (Windows/Linux), “UPS Power Manager” (Mac) and connect
the PC to the unit using one of the following methods.
BX35F/BX50F (USB connection) ....................... Use the included USB cable to connect
BX50FW/BX75SW (RS-232C connection) ......... Use the included RS-232C cable to connect
- 51 -
9. Description of related products
2. Using the UPS service in Windows Server2003/XP/2000
Install the “UPS service driver” that is on the included CD-ROM, and connect to the unit using the method
shown below.
●BX35F/BX50F (USB connection) ....................... Use the included USB cable to connect
●BX50FW/BX75SW (RS-232C connection) ......... Use the included RS-232C cable to connect
When there is a problem with the power supply, files can be saved, applications can be quit, Windows can
be shut down, and the UPS can be stopped (shut down).
3. When using the UPS service in Windows NT 4.0
The OS standard UPS service can be used with a separately purchased cable.
●DOS/V machine (use a BUC16 or BUC24 optional cable to connect)
●NEC PC9801, 9821 machine (use a BUC19 or BUC24 optional cable to connect)
9-3 Connecting the UPS
1. USB connection
2. RS-232C connection
USB port
Connect to
RS-232C
terminal
Connect to
USB terminal
Connector
Connect to USB
port on PC
Connector
Connector
Connector
Connect to
RS-232C port
on UPS
Connect to
USB port on UPS
Connect to
RS-232C port on PC
Included USB cable
BX50FW
BX35F/BX50F
Included RS-232C cable
Connect to
RS-232C
terminal
Connector
Connector
Connect to
RS-232C port
on UPS
Connect to
RS-232C port on PC
BX75SW
Included RS-232C cable
- 52 -
9. Description of related products
9-4 About the included UPS monitoring software
Using the included UPS monitoring software allows you to automatically save data files and shut down your
computer when a power failure occurs. However, make settings so that the time from the occurrence of the
power failure until computer shutdown is less than the maximum backup time. For more details, refer to the
instruction manual and online help for the UPS monitoring software.
Using the included UPS monitoring software also enables you to change the unit’s operation mode settings,
use additional functions, perform scheduling operations, etc.
Explanation
Starting operation during a scheduled stop with UPS monitoring software
● If the unit starts operation during a scheduled stop period, turn the power switch OFF once, and then
turn it back ON.
You can start the unit manually.
In this case, the next scheduled ON operation is cancelled.
Auto restart after OS shutdown by UPS monitoring software
● In the event of a power failure, some PC models (see *1 below) automatically restart immediately after
the completion of the OS shutdown processing by the UPS monitoring software.
In this case, the unit stops during restart or after startup, possibly damaging files and/or the hard disk.
This problem can be avoided by disabling POWER MANAGEMENT in the BIOS settings.
*1) PC models: This problem has been reported with MICRON Millenia Mme.
● When the PC does not start up automatically, select the “System startup at power restoration” setting
(example: “Restore On AC/Power Loss) in the BIOS settings of your PC, and change to a “System
startup after power restoration” setting (example: “Power On). Individual BIOS setting methods and/or
displays may differ depending on the PC. For more information, refer to your PC instruction manual or the
technical support center for your PC.
● When considering a system with automatic startup at power restoration, choose a PC that satisfies the
condition shown below. For more information on PC operation when input power is supplied, consult
your PC instruction manual or contact the PC technical support center.
<Condition>
Without pressing the power switch, the PC starts up when input power is supplied.
● After shutdown processing in the event of a power failure, the unit restarts automatically and supplies
power once power is restored.
If you do not want the devices connected to the UPS to start up, turn OFF their switches.
● The automatic restart setting can be disabled in the included UPS monitoring software.
- 53 -
Reference
References
A. Specifications
BX35F
Method
Input
BX50F
BX50FW
BX75SW
Operation method
Full-time commercial power supply method
Connectable devices
PC, display, and peripherals
Input voltage
range
100V mode
100V mode
110V mode
110V mode
115V mode
115V mode
120V mode
120V mode
86 + 4 to 114 )2VAC 86 + 4 to 114 )2VAC
96 + 4 to 124 )2VAC 96 + 4 to 124 )2VAC
86 + 4 to 114 + 2VAC
101 + 4 to 129 )2VAC 101 + 4 to 129 )2VAC
106 + 4 to 134 )2VAC 106 + 4 to 134 )2VAC
Frequency
50/60Hz±4Hz
Maximum current
8A
12A
Waveform
Output
Batttery Mode)
350VA/210W
Voltage *2
90 to 110 VAC
(during backup
operation)
500VA/300W
100V mode
90 to 110 VAC
110V mode
100 to 120 VAC
90 to 110 VAC
(during backup 115V mode
105 to 120 VAC
operation)
120V mode
105 to 120 VAC
(During backup operation)
750VA/450W
100V mode
90 to 110 VAC
110V mode
100 to 120 VAC
115V mode
105 to 120 VAC
120V mode
105 to 120 VAC
(During backup operation)
10 msec. or less
Backup time*3
5 minutes or more 3.5 minutes or more 3.5 minutes or more 5 minutes or more
Compact sealed lead battery
Charging time
Environment
500VA/300W
Switching time
Type
Battery
12A
Sine wave / Rectangular wave
(In Commercial Power Mode/
Output capacity
(shared maximum)*1
12A
Battery fully charged and with no condensation / 12 hours
Operating ambient temperature
0 to 40°C (during operation)/ -15 to 40°C (during storage)
Operating ambient humidity
25 to 85%RH (during operation)/10 to 90%RH (during storage)
External dimensions
(W x D x H mm)
Weight of UPS
287 x 287 x 45
287 x 287 x 45
287 x 287 x 45
90 x 287 x 278
approx. 5kg
approx. 5kg
approx. 5kg
approx. 9kg
10W
10W
10W
10W
Internal power consumption
(Normal, Max.)
*1: Do not use the UPS exceeding allowable connection capacity either in VA or W values specified in the specifications.
*2: Do not fail to confirm the system operation beforehand if the unit is used other than "Output 100V mode".
At the time of battery operation, the maximum voltage may be lower than the voltage at the time of usual
operation (commercial power supply).
Rectangular waveforms during backup operation take the following values.
BX35F/BX50F/BX50FW
100V mode
110V mode
115V mode
120V mode
The minimum
voltage of the
effective value
90V
100V*
105V*
105V*
BX75SW
The minimum
voltage of the
peak voltage
103V
103V*
103V*
103V*
The minimum
voltage of the
effective value
90V
100V
105V
105V
The minimum
voltage of the
peak voltage
115V
115V
115V
115V
*: The figures at 110V/115V/120V modes are effective only to BX50FW.
*3: At the rated load connection, 20°C, initial characteristics
- 54 -
Peak voltage
Reference
B. Related products
Spare battery pack
Attachment fittings
Network line surge protection kit
Rack mounting bracket
BX35F
BXB50F
BXP50F
—
BYP50R
BX50F
BXB50F
BXP50F
—
BYP50R
BX50FW
BXB50F
BXP50F
—
BYP50R
BX75SW
BXB75S
—
BT75XSX
—
C. Dimensional outline drawing
BX35F/BX50F
Communication cable USB (approx. 2m)
2.5
45
11
287
Power cable (approx. 1.8m)
(unit : mm / Tolerance : +1mm)
287
- 55 -
Reference
BX50FW
Communication cable RS232C (approx. 2.2m)
2.5
45
11
287
Power cable (approx. 1.8m)
287
(unit : mm / Tolerance : +1mm)
90
BX75SW
278
Communication cable RS232C (approx. 2.2m)
287
Power cable (approx. 1.8m)
(unit : mm / Tolerance : +1mm)
- 56 -
Reference
D. Circuit block diagram
This UPS outputs power input from commercial power as it is and charges the battery at the same time. If a
power failure or voltage variation occurs, the UPS automatically switches to operation using the battery and
continues power output. At this time, the beeper sounds intermittently. When the power is recovered, normal
operation using commercial power is automatically recovered. (The beeper stops.) You do not have to perform
any operation.
BX35F/BX50F
AC input plug
Power Supply Output
Receptacle
Input Overcurrent
Protection
Inverter
circuit
Charging
circuit
Commercial Power Mode
Battery Mode
DC-DC
converter
Battery
BX50FW/BX75SW
Power Supply Output
Receptacle
AC input plug
Input Overcurrent
Protection
Inverter
circuit
Charging
circuit
Commercial Power Mode
Battery Mode
DC-DC
converter
Battery
- 57 -