Commercial Thermostat Submittal Data English Language/I-P Units SUBMITTAL DATA Unit Designation: Job Name: Architect: Engineer: Contractor: Rev.: 02/23/06D ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at www.climatemaster.com. *LC204* LC204 Rev.: 02/23/06D Thermostat Submittal Data Eng/I-P ATM11C01 One Heat / One Cool Manual Changeover Non-Programmable 3.00 in [76mm] Application: Temperature increase & decrease The ATM11C01 thermostat provides single-stage, nonprogrammable temperature control for 24V water-source heat pump systems. Features: • • • • Color: White Integral switches control system and fan mode. Vented cover for improved temperature sensing. Mount directly on wall or vertical outlet box using mounting plate. • Electronic sensing (no mercury bulb or bi-metal switching). 4.70 in [119mm] Fan: turns continuous fan OFF or ON Specifications: Electrical Rating: • Voltage 20 to 30 VAC • Heating: 0.18 to 1.0A at 30VAC maximum. • Cooling: 1.5A running, 7.5A inrush at 25 VAC. Temperature Settings: • Scale Range: 50°F to 90°F (10°C to 32°C). Switching Action: • Accurate electronic sensing/switching. • 4-wire control of heating/cooling/reversing valve. 1.25 in Depth (32mm) Mode: Selects system mode - OFF, HEAT, or COOL Wiring: Connection to CXM Control ATM11C01 Thermostat Compressor Y CXM Y W Reversing Valve Fan O O G G 24Vac Hot R R Connection to DXM Control ATM11C01 Thermostat Compressor Y DXM Y1 W Reversing Valve O Fan 24Vac Hot G O/W2 G R R ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at www.climatemaster.com. LC204 Rev.: 02/23/06D Page ______ of ______ Thermostat Submittal Data Eng/I-P ATM11C03 One Heat / One Cool Manual Changeover Non-Programmable With Remote Sensor & Two-Speed Fan Control 4.6 in [116.8mm] Mode: Selects system mode OFF, HEAT, or COOL Two-Speed Fan Specifications: Electrical Rating: • Input Power: 18 to 30 Vac, 50/60 Hz. 2.7 in [68.6mm] Temperature Settings: • Setpoint Range: 50°F to 90°F [10°C to 32°C]. • The default setpoint for heating is 70°F [21°C] and for cooling is 74°F [23°C]. Press the ▲ or ▼ keys to change the setting. To change between heat and cool settings, press the mode key until the setting to be changed appears. Fault Light Temperature decrease Temperature increase 1.1 in Depth (27.9mm) Fan: turns continuous fan OFF or ON Display Range: • Display Updates: Updated every 12 seconds. • Differential (autochangeover model): 3°F [1.5°C] minimum. Output Ratings: • Maximum current for each output is 1 Amp. Mounting: Wiring: 4.9in [124.5mm] Connection to CXM Control CXM ATM11C03 Thermostat 1.5in [38.1mm] 3.1in [78.7mm] Compressor Reversing Valve Fan 24Vac Hot 24Vac Common Fault LED 3.9in [99.1mm] 2.4in [60.9mm] O G1 Note 1 O G R R C C L AL1 S1 Note 2 S2 Remote Sensor Connection to DXM Control Application: ATM11C03 Thermostat The ATM11C03 electronic thermostat provides single-stage, non-programmable temperature control for 24V water-source heat pump systems. Remote sensor is included. Features: • • • • • • • • • Y Y Heat-Off-Cool System selections. Fan-On-Auto selections. High / Low fan speed switch. Remote temperature sensor included. °F or °C temperature display. Light emitting diode (LED) for alarm status. Installer setup options allow for customized applications. Zero temperature droop performance. Setpoints are permanently held in memory (no batteries used) and retained during power outages. • Wall mounting plate. Compressor Y Hi Speed Fan G2 Reversing Valve Lo Speed Fan 24Vac Hot 24Vac Common Fault LED O DXM Y1 Note 1 G1 R C L S1 Note 2 S2 Remote Sensor H O/W2 G R C AL1 Note 1: Two speed fan selection switch is only operable with DXM board and units with PSC fan motor. DXM board must be configured (DIP 2.7 in "OFF" position) for high speed fan. This feature is typically used for console and vertical stack units. This thermostat will work with the CXM board, but the two-speed feature will not control the fan. Note 2: Remote sensor is shipped with thermostat. When remote sensor is not used, internal jumper must be reinstalled. ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at www.climatemaster.com. LC204 Rev.: 02/23/06D Page ______ of ______ Thermostat Submittal Data Eng/I-P ATA11U01 One Heat / One Cool Auto / Manual Changeover Non-Programmable 4.55 in [115.6mm] Fan: turns continuous fan OFF or ON Features (cont.): Fault Light Temperature increase 3.30 in [83.8mm] Temperature decrease • Extended fan operation feature can be used to operate fan for 90 seconds after “Y” turns off. • Setup feature allows either “current room temp” or the “current setpoint” to be displayed. • Optional safety setpoints ensure that heating and cooling will occur even if thermostat is in “Off” mode. • Backplate wiring for easy installation. Specifications: Electrical Rating: • Input Power: 18 to 30 Vac, 50/60 Hz. 0.8 in Depth (20.3mm) Mode: Selects system mode - OFF, HEAT, COOL, or AUTO Mounting: Temperature Settings: • Setpoint Range: 50°F to 90°F [10°C to 32°C]. • The default setpoint for heating is 70°F [21°C] and for cooling is 74°F [23°C]. Press the ▲ or ▼ keys to change the setting. To change between heat and cool settings, press the mode key until the setting to be changed appears. Display Range: 1.587in (40.3mm) • Display Updates: Updated every 12 seconds. • Differential (autochangeover model): 3°F [1.5°C] minimum. 2.375in (60.3mm) Output Ratings: UP • Maximum current for each output is 1 Amp. Wiring: Connection to CXM Control 2.625in (66.7mm) ATA11U01 Thermostat 3.275in (83.2mm) Application: The ATA11U01 electronic thermostat provides single-stage, non-programmable temperature control for 24V water-source heat pump systems. CXM Compressor Y Y Reversing Valve Fan O O G G 24Vac Hot 24Vac Common Fault LED R R C C L AL1 Connection to DXM Control Features: • • • • • • • • ATA11U01 Thermostat Heat-Off-Cool-Auto System selections. Fan-On-Auto selections. °F or °C temperature display. Configurable automatic or manual changeover operation. Light emitting diode (LED) for alarm status. Installer setup options allow for customized applications. Zero temperature droop performance. Temperature display adjustment feature provides display offset for custom applications. • Setpoints are permanently held in memory (no batteries used) and retained during power outages. DXM Compressor Y Y1 Reversing Valve Fan 24Vac Hot 24Vac Common O O/W2 G R C Fault LED G R C L AL1 ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at www.climatemaster.com. LC204 Rev.: 02/23/06D Page ______ of ______ Thermostat Submittal Data Eng/I-P ATA11C04 One Heat / One Cool Auto / Manual Changeover Non-Programmable With Remote Sensor & Two-Speed Fan Control 4.6 in [116.8mm] Mode: Selects system mode OFF, HEAT, COOL, or AUTO Two-Speed Fan Features (cont.): • Wall mounting plate. 2.7 in [68.6mm] Specifications: Electrical Rating: • Input Power: 18 to 30 Vac, 50/60 Hz. Fault Light Temperature decrease Temperature Settings: Temperature increase 1.1 in Depth (27.9mm) Fan: turns continuous fan OFF or ON • Setpoint Range: 50°F to 90°F [10°C to 32°C]. • The default setpoint for heating is 70°F [21°C] and for cooling is 74°F [23°C]. Press the ▲ or ▼ keys to change the setting. To change between heat and cool settings, press the mode key until the setting to be changed appears. Display Range: • Display Updates: Updated every 12 seconds. • Differential (autochangeover model): 3°F [1.5°C] minimum. Mounting: 4.9in [124.5mm] Output Ratings: • Maximum current for each output is 1 Amp. 1.5in [38.1mm] Wiring: Connection to CXM Control 3.1in [78.7mm] 3.9in [99.1mm] ATM11C04 Thermostat Compressor 2.4in [60.9mm] Reversing Valve Fan 24Vac Hot 24Vac Common Fault LED Application: The ATA11C04 electronic thermostat provides single-stage, non-programmable temperature control for 24V water-source heat pump systems. Remote sensor is included. • • • • • • • • • • Heat-Off-Cool-Auto System selections. Fan-On-Auto selections. High / Low fan speed switch. Remote temperature sensor included. °F or °C temperature display. Configurable automatic or manual changeover operation. Light emitting diode (LED) for alarm status. Installer setup options allow for customized applications. Zero temperature droop performance. Setpoints are permanently held in memory (no batteries used) and retained during power outages. Y O G1 Note 1 O G R R C C L AL1 S1 Note 2 S2 Remote Sensor Connection to DXM Control ATM11C04 Thermostat Compressor Features: CXM Y Hi Speed Fan Reversing Valve G2 Lo Speed Fan 24Vac Hot 24Vac Common G1 Fault LED DXM Y Y1 Note 1 H R O/W2 G R C L AL1 O C S1 Note 2 S2 Remote Sensor Note 1: Two speed fan selection switch is only operable with DXM board and units with PSC fan motor. DXM board must be configured (DIP 2.7 in "OFF" position) for high speed fan. This feature is typically used for console and vertical stack units. This thermostat will work with the CXM board, but the two-speed feature will not control the fan. Note 2: Remote sensor is shipped with thermostat. When remote sensor is not used, internal jumper must be reinstalled. ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at www.climatemaster.com. LC204 Rev.: 02/23/06D Page ______ of ______ Thermostat Submittal Data Eng/I-P ATA22U01 Two Heat / Two Cool Auto / Manual Changeover Non-Programmable 4.55 in [115.6mm] Fan: turns continuous fan OFF or ON Features (cont.): Fault Light Temperature increase 3.30 in [83.8mm] Temperature decrease • Extended fan operation feature can be used to operate fan for 90 seconds after “Y” turns off. • Setup feature allows either “current room temp” or the “current setpoint” to be displayed. • Optional safety setpoints ensure that heating and cooling will occur even if thermostat is in “Off” mode. • Backplate wiring for easy installation. • Automatic fan staging (when used with DXM board and direct drive motor). Specifications: Electrical Rating: • Input Power: 18 to 30 Vac, 50/60 Hz. 0.8 in Depth [20.3mm] Mode: Selects system mode - OFF, HEAT, COOL, EMHEAT, or AUTO Mounting: 1.587in (40.3mm) Temperature Settings: • Setpoint Range: 50°F to 90°F [10°C to 32°C]. • The default setpoint for heating is 70°F [21°C] and for cooling is 74°F [23°C]. Press the ▲ or ▼ keys to change the setting. To change between heat and cool settings, press the mode key until the setting to be changed appears. Display Range: 2.375in (60.3mm) • Display Updates: Updated every 12 seconds. • Differential (autochangeover model): 3°F [1.5°C] minimum. UP Output Ratings: • Maximum current for each output is 1 Amp. Wiring: Connection to CXM Control CXM ATA22U01 Thermostat 2.625in (66.7mm) Y Y Compressor Heating Stage 2 Y2/W Reversing Valve O Fan G 24Vac Hot R 24Vac Common C 3.275in (83.2mm) Application: Fault LED The ATA22U01 electronic thermostat provides two-stage, nonprogrammable temperature control for 24V water-source heat pump systems. Note 1 R C AL1 L Connection to DXM Control Features: Heat-Off-Cool-Em Heat-Auto System selections. Fan-On-Auto selections. °F or °C temperature display. Configurable automatic or manual changeover operation. Light emitting diode (LED) for alarm status. Installer setup options allow for customized applications. Zero temperature droop performance. Temperature display adjustment feature provides display offset for custom applications. • Setpoints are permanently held in memory (no batteries used) and retained during power outages. O G ATA22U01 Thermostat • • • • • • • • W Y Compressor Compressor Stage 2 Y2/W or Heating Stage 2 Reversing Valve Fan 24Vac Hot 24Vac Common Fault LED O G R C L DXM Note 2 Y1 Y2 W1 O/W2 G R C AL1 Note 1: Optional Connection for Heating Stage 2 operation, Thermostat "Y2" option must be configured as "Y2 - Off". Note 2: Connect "W/Y2" thermostat output to "Y2" on the DXM if thermostat "Y2" option is configured as "Y2 - On" and the desired operation is for 2 stages of compressor with no electric heat. Connect "W/Y2" thermostat output to "W1" on the DXM if thermostat "Y2" option is configured as "Y2 - Off" and the desired operation is for 1 stage of compressor with electric heat for Heating Stage 2. ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at www.climatemaster.com. LC204 Rev.: 02/23/06D Page ______ of ______ Thermostat Submittal Data Eng/I-P ATP11N01 One Heat / One Cool Manual Changeover Programmable 4.9 in [124.5mm] Mode: Selects system mode OFF, HEAT, or COOL Fan: turns continuous fan OFF or ON Temperature increase 4.9 in [124.5mm] Features (cont.): • • • • • Individual heat and cool set points. Accurate digital performance. Manual changeover operation. Convenient override allows temporary set point change. Set points are permanently held in memory (no batteries used) and retained during power outages. • Backlit LCD display. Specifications: Electrical Rating: Temperature decrease • Input Power: 18 to 30 VAC, 50/60 Hz. Temperature Settings: 0.8 in Depth [20.3mm] Backlight Programming Keys • Set point range: 45ºF to 90ºF [7ºC to 32ºC]. • The default (Energy Star) set point ranges are as follows: 6:00 AM 78ºF cool / 68ºF heat 8:00 AM 85ºF cool / 60ºF heat 5:00 PM 78ºF cool / 68ºF heat 10:00 PM 82ºF cool / 60ºF heat • Press the ▲ or ▼ keys to change the temperature setting. The SELECT and SET keys allow changes to the program and schedule. Output Ratings: Mounting: • Maximum current for each output is 1 Amp (3 Amp total max.). TOP Wiring: Connection to CXM Control* CXM ATP11U01 Thermostat 3.30" [83.8mm] 1.60" [40.6mm] Compressor Y1 Y Reversing Valve Fan O O G G 24Vac Hot 24Vac Common R R C C Connection to DXM Control* Application: ATP11U01 Thermostat The ATP11N01 Thermostat provides 1 stage heating, 1 stage cooling, and programmable temperature control of 24V watersource heat pump equipment. Programming schedule includes one schedule for the five week days, one schedule for the two weekend days and four periods per day (5/2/4). Features: • 5-day/2-day programming. • Four periods per day. • ºF or ºC temperature display. DXM Compressor Y1 Y1 Reversing Valve Fan O O/W2 G 24Vac Hot 24Vac Common R G C R C *Note: Make sure the HP switch is in the HP postion. When switched to HP mode, W1 is connected internally to Y1. ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at www.climatemaster.com. LC204 Rev.: 02/23/06D Page ______ of ______ Thermostat Submittal Data Eng/I-P ATP21U01 Two Heat / One Cool Auto / Manual Changeover Programmable 4.55 in [115.6mm] Fan: turns continuous fan OFF or ON Features (cont.): Temperature increase 3.30 in [83.8mm] Temperature decrease • • • • Zero temperature droop performance. Automatic (program mode) or manual changeover. Convenient overrides allow temporary set point changes. Set points are permanently held in memory (no batteries used) and retained during power outages. • Room temperature offset adjustment. • Back-plate wiring connections for easy installation. Specifications: Electrical Rating: • Input Power: 18 to 30 VAC, 50/60 Hz 0.8 in Depth [20.3mm] Mode: Selects system mode - OFF, HEAT, COOL, EMHEAT, or AUTO Programming Keys Mounting: 1.20" [30.5mm] Temperature Settings: • Set point range: 50ºF to 90ºF [10ºC to 32ºC] • The default (Energy Star) set point ranges are as follows: 6:00 AM 78ºF cool / 68ºF heat 8:00 AM 85ºF cool / 60ºF heat 5:00 PM 78ºF cool / 68ºF heat 10:00 PM 82ºF cool / 60ºF heat • Press the ▲ or ▼ keys to change the temperature setting. The MODE, PROGRAM and HOLD keys allow changes to the program and schedule. Output Ratings: [5 2. 9. 35 7m " m ] • Maximum current for each output is 1 Amp. UP Wiring: Connection to CXM Control ATP21U01 Thermostat 0.65" [16.5mm] CXM Compressor Y1 Y Reversing Valve O O Fan 24Vac Hot 24Vac Common G G R R C C 3.30" [83.8mm] Connection to DXM Control Application: ATP21U01 Thermostat The ATP21U01 Thermostat provides 2 stages heating, 1 stage cooling, and programmable temperature control of 24V watersource heat pump equipment. Programming schedule includes one schedule for the five week days, one schedule for the two weekend days and four periods per day (5/2/4). Features: • • • • DXM Compressor Y1 Y1 Reversing Valve Fan O 24Vac Hot 24Vac Common R O/W2 G R C G C 5-day/2-day programming. Four periods per day. ºF or ºC temperature display. Individual heat and cool set points. ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at www.climatemaster.com. LC204 Rev.: 02/23/06D Page ______ of ______ Thermostat Submittal Data Eng/I-P ATP32U01 Three Heat / Two Cool Auto / Manual Changeover Programmable (7 Day) 6.25 in [158.8mm] Features (cont.): • Set points are permanently held in memory (no batteries used) and retained during power outages. • Room temperature offset adjustment. • Progressive Recovery anticipates the time required to bring the space temperature to the next programmed event, and brings on the heat pump accordingly. • Large backlit dot matrix display is activated whenever a key is pressed and remains on for 25 seconds. • Menu-driven programming with five navigation buttons (UP/ DOWN/LEFT/RIGHT/SELECT) for ease of use. • Fault indication with red backlight display. • Configurable service interval messages and servicing contractor contact information. • Keypad lockout. • Back-plate wiring connections for easy installation. • Exclusive fault identification (When used with CXM or DXM) displays fault from CXM/DXM board (e.g. condensate overflow) and suggests possible causes. • Compatible with AST008 sensor for use as remote and/or outdoor sensor. • Automatic fan staging (when used with DXM board and direct drive motor). 4.25 in [108.0mm] 1.1 in Depth [27.9mm] Mounting: UP Specifications: 0.72" [18.3mm] Electrical Rating: • Input Power: 18 to 30 VAC, 50/60 Hz. Operating Conditions: 2.90" [73.7mm] • 32ºF to 104ºF [0ºC to 40ºC]. • 10% to 95% non-condensing. 6.25" [158.8mm] Temperature Settings: • Set point range: 40ºF to 90ºF [4ºC to 32ºC], +/- 2ºF [1ºC]. Output Ratings: • Maximum current for each output is 1.0 Amp (2.0 max. output total). 0.62" [15.7mm] Application: The ATP32U01 Thermostat provides 3 stages heating, 2 stages of cooling, and programmable temperature control of 24V water-source heat pump equipment. Features: • • • • • • • • 7-day programming. Four periods per day. ºF or ºC temperature display 12 or 24 hour clock. Individual heat and cool set points. Zero temperature droop performance. Automatic (program mode) or manual (HOLD) operation. Convenient overrides allow temporary set point changes. ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at www.climatemaster.com. LC204 Rev.: 02/23/06D Page ______ of ______ Thermostat Submittal Data Eng/I-P ATP32U01 Three Heat / Two Cool Auto / Manual Changeover Programmable (7 Day) Wiring: Single Stage Units Units With ECM Fan Connection to CXM Control CXM ATP32U01 Thermostat Compressor Y1 Y Reversing Valve Fan 24Vac Hot O O G G R R 24Vac Common Fault LED Connection to ECM Control ATP32U01 Thermostat C C L AL1 ECM Compressor Y1 Y1 Compressor Stage 2 Reversing Valve Y2 Y2 O O Fan G G 24Vac Hot 24Vac Common R R C C Fault LED L AL1 Connection to DXM Control ATP32U01 Thermostat Compressor Y1 Y2 Reversing Valve Fan 24Vac Hot 24Vac Common Fault LED DXM Units with CXM or DXM board and ECM fan motor Y1 Note 1 O G R C L Y2 O/W2 G R C AL1 Single stage unit with PSC or belt drive fan motor Two Stage Units Connection to CXM Control ATP32U01 Thermostat Compressor Compressor Stage 2 Reversing Valve Fan 24Vac Hot 24Vac Common Fault LED Y1 CXM 1 Y Y2 CXM 2 Y O O G G O R R G C C R L AL1 C AL1 Two compressor unit with CXM boards Connection to DXM Control ATP32U01 Thermostat Compressor Compressor Stage 2 Y1 Reversing Valve Fan 24Vac Hot 24Vac Common Fault LED O Y2 G R C L DXM Y1 Y2 O/W2 G R C AL1 Two compressor unit with DXM boards ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at www.climatemaster.com. LC204 Rev.: 02/23/06D Page ______ of ______ Thermostat Submittal Data Eng/I-P ATP32U02 Three Heat / Two Cool Auto / Manual Changeover Programmable (7 Day) With Dehumidification 6.25 in [158.8mm] Features (cont.): • Thermostat can be programmed to use humidification output to control a humidifier. • Four periods per day. • ºF or ºC temperature display. • 12 or 24 hour clock. • Individual heat and cool set points. • Zero temperature droop performance. • Automatic (program mode) or manual (HOLD) operation. • Convenient overrides allow temporary set point changes. • Set points are permanently held in memory (no batteries used) and retained during power outages. • Room temperature offset adjustment. • Progressive Recovery anticipates the time required to bring the space temperature to the next programmed event, and brings on the heat pump accordingly. • Large backlit dot matrix display is activated whenever a key is pressed and remains on for 25 seconds. • Menu-driven programming with five navigation buttons (UP/ DOWN/LEFT/RIGHT/SELECT) for ease of use. • Fault indication with red backlight display. • Configurable service interval messages and servicing contractor contact information. • Keypad lockout. • Back-plate wiring connections for easy installation. • Exclusive fault identification (When used with CXM or DXM) displays fault from CXM/DXM board (e.g. condensate overflow) and suggests possible causes. • Compatible with AST008 sensor for use as remote and/or outdoor sensor. • Automatic fan staging (when used with DXM board and direct drive motor). 4.25 in [108.0mm] 1.1 in Depth [27.9mm] Mounting: UP 0.72" [18.3mm] 2.90" [73.7mm] 6.25" [158.8mm] Specifications: Electrical Rating: 0.62" [15.7mm] • Input Power: 18 to 30 VAC, 50/60 Hz. Operating Conditions: Application: • 32ºF to 104ºF [0ºC to 40ºC]. • 10% to 95% non-condensing. The ATP32U02 Thermostat provides 3 stages heating, 2 stages of cooling, and programmable temperature/humidity control of 24V water-source heat pump equipment. Temperature Settings: Features: • 7-day programming. • Dehumidification output is designed to work with ClimaDry Modulating Reheat option or with ECM fan motor dehumidification mode. • Integrated control of both temperature and relative humidity. • Integrated control eliminates separate thermostat and dehumidistat/humidistat. • Set point range: 40ºF to 90ºF [4ºC to 32ºC], +/- 2ºF [1ºC]. • Dehumidification set point range: 15% to 95% RH. • Humidification set point range: 10% to 45% RH. Output Ratings: • Maximum current for each output is 1.0 Amp (2.0 max. output total). ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at www.climatemaster.com. LC204 Rev.: 02/23/06D Page ______ of ______ Thermostat Submittal Data Eng/I-P ATP32U02 Three Heat / Two Cool Auto / Manual Changeover Programmable (7 Day) With Dehumidification Wiring: Units with ClimaDry™ Reheat Units with ECM Fan Connection to DXM Control ATP32U02 Thermostat DXM Connection to ECM Control Y1 Y1 DH H Reversing Valve Fan 24Vac Hot O O/W2 Y1 G Compressor Compressor Stage 2 Y1 G Y2 R R Dehumidification DH Y2 DH 24Vac Common Fault LED C C Reversing Valve O O L AL1 Fan G G 24Vac Hot 24Vac Common R R C Compressor Dehumidification Single stage unit with ClimaDry Modulating Reheat Option and DXM board (PSC or belt drive fan motor) ATP32U02 Thermostat Fault LED C L ECM AL1 Connection to DXM Control ATP32U02 Thermostat Compressor Compressor Stage 2 Dehumidification Reversing Valve Fan 24Vac Hot 24Vac Common Fault LED Y1 Y2 DH O G R C L DXM Units with CXM or DXM board and ECM fan motor, utilizing ECM dehumidification mode (w/o ClimaDry option) Y1 Y2 H O/W2 G R C AL1 Notes: 1) ECM dehumidification mode slows down fan speed in the cooling mode when dehumidification output from thermostat is active. Normal heating and cooling fan speeds are not affected. 2) ECM board DIP switch SW9 must be in dehumid. mode. Units with ClimaDry™ Reheat & ECM Fan Two compressor unit with ClimaDry Modulating Reheat Option and DXM board Connection to ECM & DXM Control ATP32U02 Thermostat ECM DXM Y1 Y2 Y1 Y2 Compressor Compressor Stage 2 Y1 Dehumidification DH Reversing Valve O O/W2 H O/W2 Fan 24Vac Hot G 24Vac Common Fault LED C L G R C AL1 G R C AL1 Y2 R Single or two-stage unit with ClimaDry Modulating Reheat Option and DXM board (ECM fan motor) ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at www.climatemaster.com. LC204 Rev.: 02/23/06D Page ______ of ______