MASIBUS Energy Meter 2130

Add to my manuals
3 Pages

advertisement

MASIBUS Energy Meter 2130 | Manualzz

MASIBUS Energy Meter 2130

Three Phase

Description

MASIBUS Model 2130 Energy Meter is a solid state design, which is a complete LT/HT line measurement solution for the monitoring of three phase AC supply including all types of energies. The 2130 Power Meter is based on ASIC and Micro controller, with a high degree of programmability.

The meter meets the accuracy requirements of IS 13779/IEC

61036, and has been certified by the ERDA. This model is available for class 1.

The meter can be programmed to operate as an intelligent electronic device (IED) for measurement and storage device with serial communication making it an ideal data source for EMS,

SCADA, PLCs and BMS system.

The meter is supplied pre-programmed for operation and ready for use. Model 2130 power meter stores all its energy data and programming parameter into non-volatile memory using EEPROM. This power meter measures electrical parameters of 3 phase AC line and displays which is selectable from front keys. Battery backup is not required for Power Meter 2130.

Model 2130 has auto scaling facility while measuring energy from Kilo to Mega to Giga. Instrument can be self or auxiliary powered with very low burden. Calibration can be done using front keys or through PC software.

Model 2130 has digital input and output facility. Programmable pulse output can be used for KWH (importexport), KVARH (lag-lead) and KVAH. Programmable pulse input can be used to totalize 3 rd

party energy device.

The CT & PT ratio (primary) can be programmed at site using front membrane key. Model 2130 is supplied in panel mount version.

Features

 Accuracy class 1.0 as per IS13779/IEC 61036.

 True four quadrant measurements.

 Self/Aux powered

 4 X 16 back-lit LCD display

 51 Parameters of 3Ø AC Line using 19 display screens

 AUTO-SCALING from Kilo to Mega to Giga watt

 Programmable pulse input & output

 Calibration using front keys/ PC

 Isolated RS 485 (MODBUS RTU protocol)

MASIBUS Energy Meter 2130 Three Phase

Technical Specification

Input

Nominal Voltage Input

Direct connection Between 57.8V and 275V voltage

Standard Voltage offered

Accuracy Range

Burden

Overload

PT Ratio

230/400V for 3Ø 4 wire

50-115% of nominal voltage

< 2.5VA per phase

1.2x nominal (continuous)

1 to 9999.999 programmable

(primary)

Wire gauge 12 AWG

Nominal Input Current

Nominal Current 1 Amp or 5 Amp (Factory

Settable)

Accuracy Range

Burden

Overload

5-120% nominal

< 0.5VA per phase

4.0x nominal continuous

20.0x nominal for 1 sec.

CT Ratio

Wire gauge

Starting Current

1 to 9999.999 programmable

(primary)

12 AWG

0.4% of nominal current (Class 1.0)

Frequency

50Hz/60Hz range ± 5.0Hz

Accuracy (Class 1)

[Given Accuracy is for PF: 0.5 Lag - 1.0 - 0.8 Lead]

Volt

Current

Frequency

Power Factor

Active Power

Reactive Power

Apparent Power

1% rdg ± 1 digit

1% rdg ± 2 digit

0.1Hz ± 1 digit

1% rdg ± 2 digits (0.5 Lag –

1.0 – 0.8 Lead)

1% rdg ± 2 digits

2% rgd ± 2 digits

1% rgd ± 2 digits

Active Energy

Reactive Energy

Class 1.0 (IS 13779/IEC 1036)

Class 2.0 (IEC 1268)

Apparent Energy Class 1.0

System

Single Phase

3Ø 3 wire unbalanced load

3Ø 4 wire unbalanced load

Output Relay

Type

Rating

Watt/VAR/VA – SPNO

250V, 2A (AC)

±30V, 2A (DC)

Pulse Output

Type

Rating

Pulse Rate

Pulse duration

Wh/VARh/Vah – SPNO

200V, 100mA, Resistive (AC)

±200V, 100mA, Resistive (DC)

1 to 9999 pulse per selected type

80mSec ± 10%

Communication Output

Serial Port

Baud Rate

Start Bit

Stop Bit

Protocol

Isolation

RS485, Multidrop

Selectable: 4800/9600/19200

1

1

MODBUS-RTU

2KV

Environmental

Operating

Temperature

Storage

Temperature

Temperature

Coeff

Humidity

Warm up time

0 to 55 °C

-10 to 70 °C

IS-13779

30 to 95% RH non-condensing

5 min

Physical

Dimensions

Cut out

Mounting

96(W) x 96(H) x 74.4(D) mm

90 (W) x 90 (H) mm

Panel mounting

Weight 300gms approx.

Enclosure Material ABS

Miscellaneous

Display

Update Rate

Sensing Method

2x16 Backlight LCD module with 5.56mm character height

320ms

True RMS

Sampling at 320k sample on all channel measurement reading simultaneously.

Weight 500gms approx.

Enclosure Material ABS

MASIBUS Energy Meter 2130 Three Phase

Figure 1: Physical Dimensions (mm)

Head Office:

Techno Instrumentation (India) Pvt. Ltd.

An ISO 9001:2008 Certified Company

Plot# 67, Street# 1-B ,

Friends Colony Industrial Area,

G.T Road, Shahdara, Delhi – 110095,

India

M2MLogger is a division of Techno Instrumentation (India) Pvt. Ltd.

Telefax : +91-11-22112232

Mobile : +91 98105 54547

E-mail : [email protected]

Web : www.m2mlogger.com

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement