DXair Pool Dehumidifiers The perfect balance of water and air.

DXair Pool Dehumidifiers
EC Series 6 to 30 Tons
G-60 Galvanized
The EC Model Series with dual compressors provides
the best combination of performance, comfort and
one-of-a-kind features that satisfy the high demands of
any residential or commercial natatorium.
The perfect balance of water and air.
EC SERIES POOL DEHUMIDIFIERS
Table of Contents
PERFORMANCE DATA.............................................................3
DXair POOL DEHUMIDIFICATION SYSTEMS.........................4
EC MODEL................................................................................4
Quality..............................................................................4
Advantages of DXair Technology..................................5
Flexible Installation.........................................................5
Quiet Operation .............................................................5
Serviceability....................................................................5
DXAIR EC MODELS 072-360...................................................6
UNIT CONFIGURATIONS.........................................................6
EC072-181 Vertical Single Blower .
Large Commercial Units..................................................6
EC210-360 Vertical Dual Blower .
Large Commercial Units..................................................6
EC072-150 Horizontal Large Commercial Units...........7
EC180-242 Horizontal Commercial Units......................7
FEATURES, FUNCTIONS AND BENEFITS................................8
Cabinet ............................................................................8
Filter Racks and Options.................................................8
Blower and Motor...........................................................8
Evaporator Coil and DuoGuard™ (Option)...................8
Refrigerant Circuit . ........................................................8
UNIT PROTECTION MODULE (UPM)....................................10
UPM Control Board Features.......................................10
Water Connections........................................................11
ADDITIONAL OPTIONS.........................................................11
Take-Apart Construction..............................................11
Energy Management Switch (EMS) . ..........................11
Flow Proving Switch (DPS)............................................11
Hot Gas Reheat..............................................................11
Hot Gas Reheat Sequence of Operation – .
On/Off Control...............................................................12
Hot Gas Reheat Control Options.................................12
Special Considerations..................................................12
Indoor Pool Dehumidifying During Winter Months .12
INSTALLATION.......................................................................13
Vertical Unit Installation...............................................13
Unit Location.................................................................13
Typical Unit Installation ...............................................13
Horizontal Unit Installation ........................................13
Ductwork and Sound Attenuation Considerations...14
PIPING.....................................................................................15
OPERATING LIMITS................................................................15
2
EQUIPMENT SELECTION.......................................................15
UNIT OPERATING LIMITS­—EC MODEL................................15
ANTIFREEZE CORRECTION DATA.........................................16
WATERSIDE PRESSURE DROP..............................................17
CAPACITY DATA....................................................................18
EC072 (2300 Nominal CFM) .........................................18
EC096 (2800 Nominal CFM) .........................................19
EC120 (4000 Nominal CFM) .........................................20
EC150 (5000 Nominal CFM) .........................................21
EC151 (5000 Nominal CFM) .........................................22
EC180 (6000 Nominal CFM) .........................................23
EC181 (6000 Nominal CFM) .........................................24
EC210 (7000 Nominal CFM) .........................................25
EC240 (8000 Nominal CFM) .........................................26
EC242 (8000 Nominal CFM) .........................................27
EC300 (10000 Nominal CFM) . .....................................28
EC360 (12000 Nominal CFM) . .....................................29
ELECTRICAL DATA.................................................................30
Belt Drive Motor............................................................30
BLOWER MOTOR PERFORMANCE......................................31
Belt Drive Motor............................................................31
PHYSICAL DATA.....................................................................32
EC Model........................................................................32
HORIZONTAL CABINET CORNER WEIGHTS........................33
VERTICAL UNIT DIMENSIONS..............................................33
EC072-120 Single Blower Large Vertical.....................33
EC151-181 Single Blower Large Vertical.....................34
EC210-360 Dual Blower Large Vertical........................35
HORIZONTAL UNIT DIMENSIONS........................................36
EC072-150 Large Horizontal.........................................36
EC180-242 Large Horizontal.........................................37
SERVICE CLEARANCES..........................................................38
EC072 thru 181 Large Vertical......................................38
EC210 thru 360 Large Vertical......................................38
EC072 thru 150 Large Horizontal................................38
EC180 thru 242 Large Horizontal................................38
GUIDE SPECIFICATIONS........................................................39
UNIT LOCATION.....................................................................42
SOUND...................................................................................42
NEGATIVE PRESSURE............................................................42
DUCT AIR DELIVERY SYSTEM..............................................42
Subject to change without prior notice Revised 07 - 16
EC SERIES POOL DEHUMIDIFIERS
PERFORMANCE DATA
Cooling 86˚F
Model
Cooling 59˚F
Cooling 77˚F
GPM
Capacity Btuh
EER Btuh/W
Capacity Btuh
EER Btuh/W
Capacity
Btuh
EER
Btuh/W
EC072
16
72000
13.0
80400
18.6
75600
14.2
EC096
21
96000
14.0
116000
20.6
104000
15.4
EC120
28
124000
13.2
134000
18.3
127200
14.7
EC150
35
157000
16.0
185000
24.0
166000
17.9
EC151
35
147000
16.0
175000
24.0
155000
17.9
EC180
42
182000
14.2
195000
20.0
185000
15.4
EC181
42
170000
14.2
185000
20.0
175000
15.4
EC210
50
220000
14.6
292000
22.5
250000
17.2
EC240
60
248000
14.4
310000
21.1
275000
16.0
EC242
60
248000
14.4
310000
21.1
275000
16.0
EC300
75
295000
13.0
365000
18.8
318000
14.0
EC360
90
386000
14.8
472000
22.0
412000
16.4
Subject to change without prior notice Revised 07 - 16
3
DXAIR POOL DEHUMIDIFICATION
SYSTEMS
DXair specializes in humidity control for indoor pools by
providing efficient green technology for residential and
commercial natatoriums in an extremely small footprint.
Our DXair pool dehumidifiers are the leading dehumidifiers
in the market today based on our designs and options,
which assures that you are buying a unit that you can trust.
DXair is always on the forefront of product development
and innovative design to optimize the performance of
DXair units. Our products are designed and manufactured
to the highest quality, reflecting the no-compromise
standards for which DXair is renowned in order to provide
our customers with the highest level of humidity control
and comfort. Along with a large variety of options and the
added benefit of many units being designed for tight
retrofitted spaces, DXair products are extremely energy
efficient and come with the DXair quality you expect. DXair
products are an ideal choice for new construction,
residential, hospitality, and other commercial new
construction or retrofit markets.
DXair engineering efforts have been focused on providing
a greener world for future generations. Faced with today’s
tough environmental challenges and with global warming,
DXair is more committed than ever to develop solutions
which utilize sustainable energy sources in order to
conserve our planet’s resources. With our design, we
provide the least amount of refrigerant per ton in our
reduced refrigerant management systems
The EC Model dehumidifier is the result of our nearly 30+
years of research, development, and experience in the US
market. The model contains the most flexible air humidity
control technology available today, and is designed for
reliability while reducing installation costs and providing
the comfort and cost savings you'd expect from DXair.
EC MODEL
DXair EC Model pool dehumidifiers provide the best
combination of performance and efficiency available.
Safety devices are built into each unit to provide the
maximum system protection possible.
Quality
The EC Model features (as standard) G-60 galvanized
steel cabinet and stainless steel drain pan to ensure long
life. To help prevent formicary corrosion, evaporator coils
with DuoGuard™ coil protection can be applied as an
option. Rigorous factory testing helps to ensure fewer
hassles from the start while our 40+ years of experience
in designing pool dehumidifiers is your assurance of the
highest quality product.
Proven and Tested Technologies
4
DXair pool dehumidification systems are manufactured with rigorous
standards and factory tested to ensure trustworthy operation over the
life of the unit. ISO 9001 and ISO 14001 certified facilities provide
consistent quality in every unit built.
EC SERIES POOL DEHUMIDIFIERS
Drain Pan
High-Density
Compressor Blankets
(Optional)
Schrader Charging Valves
for Servicing
Advantages of DXair Technology
Quiet Operation
• Least amount of refrigerant per ton
All panels are insulated with ½" thick, 1.5 lb./cu. ft.
dual-density fiberglass insulation for both thermal
insulation and noise reduction. Noise reduction is a critical
consideration of the unit’s design. For vibration isolation,
all compressors are mounted on rubber grommets.
Compressor rubber isolators are necessary in preventing
vibration transmission from the compressor to the unit
cabinet and duct work. Vertical cabinets have an insulated
divider panel between the blower compartment and the
compressor section to minimize the transmission of
compressor noise, and to permit operational service testing
without air bypass.
• Field cleanable evaporator coils
• Smallest footprint in the industry
• Free flow low horse power blowers
• Super extended warranties
• Reduced refrigerant management RRMs
• Optimum comfort
• Two single-step compressors for 2-stage operation
• Simple installation and operation
• Low installation costs
• Lower operating costs
• Flexibility in designing and installation
• Energy efficiency
• Superior quality
• Quiet operation
Flexible Installation
All air handling units are available in horizontal and vertical
configurations. Additional options of return air and supply
air are offered as standard, providing configuration
flexibility. For ease of installation, horizontal units are
provided with hanging supports. All horizontal units are
equipped with angle or box section supports for hanging
the unit. Field supplied spring or rubber isolation must be
installed to isolate the unit from the building structure.
Subject to change without prior notice Revised 07 - 16
For additional sound attenuation, high-density compressor
blankets and fiber free closed cell foam insulation are
available as options on all EC Models.
Serviceability
All units are designed to be serviced from the front of the
unit. Standard schrader valves along with easily accessible
electrical box components, make diagnosing and servicing
the unit a simple task. Insulated bulkheads in all EC Models
separate the compressor section from the blower section,
allowing the unit to be serviced easily during operation.
Sizable panels are removable to facilitate servicing of the
unit. Separate electrical knockouts in the unit corner post
allow for easy and safe routing of high and low voltage
lines to the inside of the cabinet. These service friendly
features benefit equipment owners with easier service
access which saves time and money.
5
EC SERIES POOL DEHUMIDIFIERS
DXAIR EC MODELS 072-360
• 12 Models from 6 through 30 tons
• Units are available in both horizontal and vertical
configurations depending on size. Additionally, several
options of return and supply air are offered as standard,
providing configuration flexibility.
• All units are designed with dual refrigeration circuits for
staged operation. Horizontal unit sizes 120, 180 and 242
have dual blower assemblies. Vertical unit sizes 210 to 360
have dual blower assemblies.
UNIT CONFIGURATIONS
EC072-181 Vertical Single Blower Large Commercial Units
Optional Blower
Orientation (979-032)
(Rotate 180°)
Front Return
Standard Blower
Orientation
Blower
Access
Figure 1
Blower & Motor
Access
Blower & Motor
Access
Condenser Water Out
Condensate Drain
Blower Motor
Orientation
Condenser Water In
Electrical
Connections
Controls, Compressors, Refrigeration
Components Access
Top Supply (FFT)
Rear Supply (FFR)
Rear Return
Blower Motor Orientation
Condenser Water Out
Standard Blower
Orientation
Blower
Access
Blower
Access
Blower & Motor
Access
Blower & Motor
Access
Optional Blower
Orientation (979-032)
(Rotate 180°)
Blower Motor
Orientation
Condensate Drain
Condenser Water In
Electrical
Connections
Controls, Compressors, Refrigeration
Components Access
Top Supply (FBT)
Front Supply (FBF)
EC210-360 Vertical Dual Blower Large Commercial Units
Optional Blower Orientation
(979-032)
(Rotate 180°)
Front Return
Blower
Access
Standard Blower
Orientation
Blower & Motor
Access
Blower
Access
Figure 2
Condenser Water Out
Blower & Motor
Access
Condensate Drain
Blower Motor
Orientation
Condenser Water In
Controls, Compressors, Refrigeration
Components Access
Electrical Connections
Top Supply (FFT)
Rear Supply (FFR)
Optional Blower Orientation
(979-032)
(Rotate 180°)
Rear Return
Blower
Access
Standard Blower
Orientation
Blower & Motor
Access
Blower Motor Orientation
Blower
Access
Condenser Water Out
Blower & Motor
Access
Condensate Drain
Condenser Water In
Controls, Compressors, Refrigeration
Components Access
Electrical Connections
6
Front Supply (FBF)
Top Supply (FBT)
Subject to change without prior notice Revised 07 - 16
EC SERIES POOL DEHUMIDIFIERS
UNIT CONFIGURATIONS
EC072-150 Horizontal Large Commercial Units
Figure 3
Controls, Compressors
Access
Electrical Box
Condensate Drain
Electrical Connections
Compressors,
Refrigeration Components
Access
Condenser Water Out
Compressors, Refrigeration
Components Access
Condenser Water Out
Condenser Water In
Condensate Drain
Condenser Water In
Blower & Motor
Access
Blower Motor
Orientation
072, 096 & 150 (SLS Only)
Condensate Drain
Blower Motor
Orientation
120 (SLS Only )
EC180-242 Horizontal Commercial Units
Figure 4
Compressors, Refrigeration
Components Access
Controls, Compressors
Access
Condenser Water Out
Condensate Drain
Condenser Water In
Condensate Drain
Electrical Box
Electrical Connections
Blower & Motor
Access
Blower Motor
Orientation
EC180 & EC242 (SLS)
Subject to change without prior notice Revised 07 - 16
7
EC SERIES POOL DEHUMIDIFIERS
2" 4-Sided Filter
Rack Option
Belt Drive,
and Motor
FEATURES, FUNCTIONS AND
BENEFITS
Cabinet
The EC Model cabinetry is constructed using heavy-gauge,
G-60 galvanized steel. This type of steel provides superior
corrosion protection for units installed indoors.
All interior surfaces are lined with ½" thick, 1.5 lb./cu.ft.
dual-density, fiberglass insulation for thermal insulation
and acoustical attenuation. This insulation is noncombustible, non-hydroscopic and does not support
fungal growth. The unit insulation also meets NFPA 90A
and 90B for fire protection, UL 181 for erosion, and is
certified to meet the GreenGuard™ Indoor Air Quality
Standard for Low Emitting Products.
Protection against corrosion is a feature in the Large EC
Model. A stainless steel drain pan will last the lifetime of
the unit and resist corrosion and cracking that may occur
with painted steel, galvanized steel or plastic materials.
Filter Racks and Options
Two-sided filter racks accommodating a 1" filter are
standard on all EC units. A two-sided 2" filter rack is
optional to accommodate a nominal 1" or a 2" thick filter.
Four sided filter racks are available as an option and
minimize unfiltered air from entering the unit. Filter doors
allow for easy routine maintenance and changing of the air
filter. A 1" return duct collar is integral to the filter rack
eliminating the need for field mounted duct collars. Units
are shipped with a standard MERV-5 1" construction filter.
8
Blower and Motor
All fan assemblies are belt-driven double width, double
inlet (DWDI), forward curved, and precisely balanced to
ensure smooth operation. The blower housing and fan
wheels are designed for quiet, low velocity operation,
which helps keep high frequency fan wheel noise to a
minimum. The fan motors are 1725 or 3450 RPM, 56
frame sealed ball bearing type, permanently lubricated and
have thermal overload protection.
Evaporator Coil and DuoGuard™ (Option)
Air handling sections come standard with a copper tube
aluminum fin evaporator coil. Available as an option is the
DuoGuard™ evaporator coil protection system.
DuoGuard™ Protection® - Tin Electro-Plated Copper
Tubing with High-Tech Polymer Coated Aluminum Fins will
aid in protecting the evaporator coil from most forms of
corrosive elements in the airstream. The tin plating
provides a best-in-class protection of the copper tubing
from formicary corrosion while the fin coating provides
protection against salt spray and other corrosive elements.
DuoGuard™ protected coils are able to exceed 1000 hours
salt spray per ASTM standard B-117.
Refrigerant Circuit
EC Models are designed using the optimum combination
of compressor and field cleanable coils to provide peak
performance.
Heavy-duty compressors are used in all units. Scroll or
reciprocating compressors offer optimum performance for
each unit size.
Subject to change without prior notice Revised 07 - 16
EC SERIES POOL DEHUMIDIFIERS
DuoGuard™ Evaporator Coil
Protection (Optional)
Variable Frequency
Drive (Optional)
Refrigerant to water heat exchangers are coaxial tube-intube type providing a robust construction, ensuring years of
trouble free operation. Coaxial coils are selected and
designed for peak performance, offering the best
combination of low water pressure drop and maximum heat
transfer in both the cooling and heating modes. Standard
coaxial coils have a copper interior water tube and a steel
outer shell. Optional cupro-nickel coils are available for
applications where the water is of lower quality.
Scroll and
Reciprocating Compressors
High and low pressure switches are factory installed in the
refrigerant circuit, protecting the unit against high pressure
conditions or loss of refrigerant charge.
Schrader service valves are standard on the high and low
pressure lines of all units, allowing connection of gauges
for service diagnostics and to evacuate, reclaim or recharge
refrigerant into the system. Optional Schrader valves are
available with the connection to field installed water
regulating valves.
Air coils are state of the art, employing lanced fin and rifled
tubing for maximum heat transfer. Large face areas result
in lower face velocity reducing sound while ensuring high
latent heat removal for maximum dehumidification in the
cooling mode.
Thermal Expansion Valves come standard on the EC and
are designed to vary the flow of refrigerant depending on
the load. TXV’s provide unit optimization and a more stable
control over a wider range of operating conditions.
EC Model units are rated to withstand 600 PSIG working
refrigerant pressure and 400 PSIG working water pressure.
All EC Model are provided with filter driers to ensure that no
residual water or other foreign material is present to
contaminate the refrigerant system and lead to premature
failure.
Subject to change without prior notice Revised 07 - 16
(Panels removed for internal view of the EC Model)
9
EC SERIES POOL DEHUMIDIFIERS
Coax Coil
Four-way Reversing Valve
UNIT PROTECTION MODULE (UPM)
Each EC Model is built in the factory with a Unit Protection
Module (UPM) that controls the unit operation and monitors
the safety controls that protect the unit. The UPM interfaces
with the thermostat or human-machine interface (HMI).
The main purpose of the UPM is to protect the compressor
by monitoring the different states of switches and sensors.
This module provides time delays and protects the unit
against freezing of the water-to-refrigerant and air-torefrigerant heat exchangers as well as condensate overflow.
This level of protection helps provide the peace of mind that
comes with offering DXair products to the customer.
UPM Control Board Features
• Condensate Overflow Protection — The UPM controller
continuously monitors the drain pan for high condensate
water level, and if this exceeds normal operating levels, the
compressor operation is interrupted to protect against drain
pan overflow.
• Anti-Short Cycle Timer — 5 minute delay on break timer to
prevent compressor short cycling.
• Random Start — Each controller has a unique random start
delay ranging from 270 to 300 seconds after power is applied to
the board. This will prevent the simultaneous start of multiple
units after a power outage.
• Low Pressure Bypass Timer — The low pressure switch is
bypassed for 120 seconds after a call for compressor operation
to prevent nuisance low pressure lockouts during cold
start-up.
• Brownout/Surge/Power Interruption Protection—
Prevents compressor operation should the voltage drop below
10% of unit rated value. The unit will restart once the voltage
is within tolerance and the random start has timed out.
• Malfunction (Alarm) Output — The controller has a set of
contacts for remote fault indication. This can be either a
10
UPM Control Board
steady output or can be set to pulse with the fault code.
Two connections are available; one to provide a 24 volt
output, the other to provide a dry contact.
• Test Service Mode — A dip switch setting is provided to
reduce all time delay settings to 10 seconds maximum
during troubleshooting for verification of unit operation.
• LED Fault Indication (2-Stage) — Two LED indicators are
provided as follows:
• Green: Power LED indicates 18-30 VAC present at
the board.
• Red: Fault indicator with blink codes identifying the
particular fault. This information is available via the
malfunction (alarm) output contacts.
1 Blink - High Pressure
2 Blinks - Low Pressure
3 Blinks - High Pressure (2-stage)
4 Blinks - Low Pressure (2-stage)
5 Blinks - Low Fluid Temperature
6 Blinks - Condensate Overflow
7 Blinks - Brownout condition
• Intelligent Reset—If a fault condition is initiated, the
5 minute delay on break time period is initiated and
the unit will restart after this delay expires. The UPM is
configurable for either 2 or 4 fault occurrences before
going into a hard lockout. The selection is made
through a DIP switch setting on the board. If the fault
condition still exists or reoccurs twice or four times
within one hour, the unit will go into a hard lockout
and requires a manual lockout reset. A condensate
overflow fault will, however, put the unit into a hard
lockout immediately.
• Lockout Reset—A hard lockout can be reset by turning the
unit thermostat off and then back on or by shutting off unit
power at the circuit breaker. The method of reset is selectable
by the dip switch on the board.
Subject to change without prior notice Revised 07 - 16
EC SERIES POOL DEHUMIDIFIERS
Water Connections
All water connections are heavy-duty bronze FPT fittings
securely fastened to the unit corner post.
electrical building loads. Energy management systems can
be used to centrally control devices like HVAC units and
lighting systems across multiple applications sites.
ADDITIONAL OPTIONS
Flow Proving Switch (DPS)
• 100VA transformer
• Inverter duty motor
• Relays - EMS, blower monitor, compressor monitor, and
pump/valve
• Phase monitor
• Pump/valve relay
• Fire alarm relay/dual power
• Wire to 208V
• 1/2" Closed cell foam insulation
• Take-Apart construction
• 100% outside air
• Rotate blower
• Cooling only
Take-Apart Construction
Where there is a restriction in the available height to the
access of a mechanical space, the EC unit is available in a
take-apart construction. The unit is built so that the
condensing section can be field separated from the air
handling section and both transported separately into the
mechanical space where they would be reassembled. The unit
is built with the refrigerant lines in both sections capped and
with a holding charge of nitrogen in each section. It is the
installer’s responsibility to reassemble the unit and join all
refrigerant lines, evacuate and charge the refrigerant system.
The blower motor, condensate sensor and freeze protection
wires would be wired to the condensing section. The takeapart option is only available on vertical units, allow for an
increase of approximately 3" in the height of the unit.
Energy Management Switch (EMS)
This switch allows you to connect to an energy management
system that can turn the unit off and on. Energy
management systems are commonly used by individual
commercial entities to monitor, measure, and control their
Subject to change without prior notice Revised 07 - 16
The function of the flow proving switch is to prevent or stop
compressor operation should the condenser fluid supply fail.
This will prevent the unit from locking out on a safety
requiring a manual reset to restart. The switch is piped
between the liquid entering and leaving connections. Should
the pressure drop fall below set value, the switch will open
de-energizing the DPS relay, thereby stopping the compressor.
The blower operation will not be affected by this option.
Hot Gas Reheat
Hot gas reheat (HGR) allows the user to control space
temperature and humidity levels within the conditioned
space. Excessive moisture in the space can promote mold
growth leading to damage in the structure or interior
surfaces, as well as reducing the air quality and creating an
unhealthy environment.
Possible causes of excess humidity could be by the unit having
to operate under a widely varying load, an oversized short
cycling unit, a high percentage of unconditioned outside air
being introduced into the space, a high latent load in the
space or any location where humidity infiltration is a problem.
The HGR unit is controlled by wall mounted thermostat
and humidistat device(s) to control temperature and
humidity. By utilizing a humidistat in addition to the
thermostat, we are able to monitor the humidity levels in
the space as well. The HGR option allows cooling and
dehumidification to satisfy both the thermostat and
humidistat while preventing over cooling of the space
while in the dehumidification mode.
Once the thermostat reaches set point temperature and
the humidity is above set point, the unit controller will
energize the reheat valve operating the unit in hot gas
reheat mode, first cooling and dehumidifying, then
reheating the air using hot refrigerant gas before delivering
it to the space. By reheating the air along a constant
sensible heat line, the relative humidity of the leaving air is
reduced. This option offers significant energy savings over
11
EC SERIES POOL DEHUMIDIFIERS
the traditional means of reheating air with electric or hot
water heating coils.
In the reheat mode, the compressor discharge gas is diverted
through the reheat valve to the reheat coil which is located
downstream of the cooling coil. The superheated refrigerant
gas reheats the air leaving the cooling coil. The hot refrigerant
gas then passes though the water to refrigerant coil where it
is condensed to a liquid. From this point the rest of the cooling
cycle is completed. There are two check valves to prevent
refrigerant flow into the reheat coil during standard cooling
cycles. A small copper bleeder line is connected to the outlet
line of the reheat coil and between the expansion valve outlet
and distributor to the air coil. This line is necessary to let any
liquid/oil that may have migrated to the reheat coil during
reheat to escape during standard cooling mode.
Hot Gas Reheat Sequence of Operation –
On/Off Control
The sequence of operation in the cooling
and heating
Caution
mode is the same.
In the reheat mode, on a call from the humidistat, the
reheat relay coil is energized through the “H” circuit. The
cooling relay remains de-energized enabling the reheat
solenoid. The blower relay, reversing valve and compressor
contactor are energized through contacts on the reheat
relay. (Note: The reheat mode always operates in the
cooling mode.) Should the temperature in the space
increase above set point, the compressor terminal Y is
energized, which will de-energize the reheat valve putting
the unit into straight cooling mode. A call for cooling will
always take precedence over hot gas reheat.
Special Considerations
Some applications require special attention to maximize
the performance of the hot gas reheat function.
Indoor Pool Dehumidifying During
Winter Months
It is important to remember that when in the reheat/
dehumidification mode the pool dehumidifier is cooling and
reheating. A secondary means of heating the space during
the dehumidification mode should be provided. The indoor
space temperature must be kept at least 2° F above the pool
water temperature, with normal settings of 80°F to 84°F
pool water temperature, 82°F to 86°F air temperature at
50-60 percent relative humidity. If this is not done the warm
pool water attempts to heat the space and the humidity
levels increase exponentially. The dehumidifier is normally
sized to handle the design latent load moisture removal.
Protective coatings such as Bronze Glow
Coating are highly recommended for all pool
applications, due to the highly corrosive
chemical environment.
Hot Gas Reheat Control Options
There are several ways to control pool dehumidifier with
hot gas reheat. You should choose the means that best
suits your specific application. Please refer to the Hot Gas
Reheat wiring diagrams for typical thermostat wiring. Most
compatible thermostats in conjunction with a humidistat
are acceptable for use.
“O” output for reversing valve energized in
cooling mode is required.
Combination thermostat/humidistat are also available.
12
Subject to change without prior notice Revised 07 - 16
EC SERIES POOL DEHUMIDIFIERS
Typical Unit Installation
Figure 7
Figure 8
INSTALLATION
Vertical Unit Installation
Large Vertical units are typically installed in a mechanical
room. If installed in a confined space, ensure adequate
space (not recommended) for return air to the unit.
Sufficient space must be provided for filter replacement and
access to the compressors and blower compartment for
service.
Unit Location
Any mechanical device will, at some point in time, require
servicing and repair. With this in mind, sufficient space
must be provided around the unit for service personnel to
perform maintenance or repair.
Units are not designed for outdoor installation. Avoid
locations where the unit may be exposed to freezing
conditions or where the humidity levels could cause
condensation on the unit panels for example when
exposed to outdoor ambient conditions.
Subject to change without prior notice Revised 07 - 16
Horizontal Unit Installation
Large horizontal units are supplied with angle or box
section supports for suspension. Field supplied hanging
rods, spring or rubber isolators should be used to isolate
the unit from the building structure to prevent vibration
transmission to the building. Units should be located
directly below a structural member so that it is securely
anchored.
A horizontal unit should be positioned to allow for removal
of the filters and access panels. Allow at least 24"
clearance on each side of the unit for service and 36" in
front of the unit for maintenance access. The filter needs to
be slid out and sufficient space must be provided to allow
this.
Do not install the unit above any piping or electrical
raceways. The unit should be able to be removed to the
floor without major rearrangement of other mechanical or
ceiling components.
13
EC SERIES POOL DEHUMIDIFIERS
Ductwork and
Sound Attenuation Considerations
Lining the first five feet of
supply duct reduces noise
Turns attenuate
blower noise
Take-offs should be at least
five feet away from the
plenum
Figure 9 Supply Air Ducting
Sound is becoming an increasingly important factor in all HVAC
installations. The EC Model has been designed to minimize
sound, but sound acoustical design plays an important part of the
sound level in the space.
Most of the problems associated with HVAC generated
sound can be avoided by paying close attention to duct
design and equipment placement.
A discharge flange is provided on all horizontal unit models
for fastening of ductwork. We recommend using a flexible
collar between the discharge flange and the duct
transformation to reduce vibration transmission from the
cabinet and to simplify disconnection of the unit from the
ceiling ductwork.
Flex
duct
Flex
duct
Return air
filter and grill
Figure 10 Return Air Ducting
Return air to the unit could be either free return or ducted.
The filter rack is provided with a 1" flange should a ducted
return be used. We recommend using a flexible collar
14
between the return flange and the duct transformation to
reduce vibration transmission from the cabinet and to simplify
disconnection of the unit from the ductwork.
Sound is transmitted down the ductwork and it is important to
avoid direct line of sight between the unit and the space, both on
the return or supply side. To accomplish this, design the duct runs
with two 90° turns.
As a general recommendation, duct interiors should have an
acoustic / thermal lining of least 1/2" thick over the entire duct run
or a minimum of the first 5 feet of the supply trunk. DXair
recommends fiber-free insulation for ducts and internally within
the unit (as an option).
Line the last five diameters of duct before each outlet with a
one-inch thick sound blanket. Line elbows and transition pieces,
as well as a short distance upstream and downstream of the
fittings.
Elbows, tees and dampers can create turbulence or distortion in
the airflow. Using aerodynamic fittings will help in reducing this
effect. Place a straight length of duct, 5 to 10 times the duct
width, before the next fitting to smooth out airflow.
Diffusers that are located in the bottom of a trunk duct can also
produce noise.
Balancing dampers should be located several duct widths
upstream from an air outlet.
Ductwork should be mounted and supported using isolation
devices that absorb vibration.
Applications such as a hotel that uses single duct discharges
are susceptible to noise. These applications typically have low
static pressures and short duct lengths. In these applications
the discharge duct must be fully lined and have a square elbow
without turning vanes. A velocity not exceeding 500 to 600
fpm is recommended. Return air for these applications should
enter through a sidewall grille and route up the stud space to a
ceiling plenum.
For horizontal systems mounted in the ceiling plenum, an
insulated return plenum is sometimes placed at the return air
opening to further attenuate line-of-sight sound transmission
through return openings. A secondary drain pan is required under
all above grade installations.
Subject to change without prior notice Revised 07 - 16
EC SERIES POOL DEHUMIDIFIERS
PIPING
Condensate Drain Piping
Condensate piping can be made of steel, copper or PVC
pipe. In most cases, PVC pipe eliminates the need to wrap
insulation around the pipe to prevent sweating.
All EC Models provide a standard FPT condensate drain
connection installed in the unit (reference install manual for
exact diameter based on capacity of unit). The condensate
piping must be trapped at the unit and pitched away from
the unit not less than ¼" per foot. A vent is required after
the trap so that the condensate will drain away from the
unit. The vent can also act as a cleanout if the trap becomes
clogged. The condensate drain should not be directly piped
to a drain/waste/vent stack. See local codes for the correct
application of condensate piping to drains.
OPERATING LIMITS
EC Models are capable of operating over a wide range of
conditions.
• Maximum and minimum fluid conditions are at unit
rated flow rate.
UNIT OPERATING LIMITS­—EC MODEL
Operating Limits­– Cooling & Heating
Standard
Unit
Minimum evaporator entering air db/wb °F
68/57
Rated air coil entering air db/wb °F
80/67
Maximum evaporator entering air db/wb °F
95/85
Minimum water coil entering fluid temperature °F
50
Water loop typical coil entering fluid range temperature °F
70/90
Maximum water coil entering fluid temperature °F
110
Minimum evaporator entering air db °F
50
Rated air coil entering air °F
68
Maximum evaporator entering air db °F
80
Normal water coil entering fluid range °F
50-80
Minimum water coil entering Fluid °F
50
.
*Antifreeze solution is required at these fluid temperatures.
Units are designed to be installed in an air conditioned space.
• Maximum and minimum operating limits may not
be combined. If one value is at either maximum or
minimum, the other two should be at normal
operating range.
EQUIPMENT SELECTION
To ensure that you get the optimal performance from
your DXair dehumidifier. it is important that they be
selected accurately to match your design conditions
and criteria.
Prior to making equipment selections the zone
conditions need to be determined.
Subject to change without prior notice Revised 07 - 16
15
EC SERIES POOL DEHUMIDIFIERS
ANTIFREEZE CORRECTION DATA
Antifreeze Correction
Cooling
Antifreeze Type
Water
Avg. Water Temp 90 °F
Antifreeze %
WPD Correction
Factor EWT 30 °F
Total Cap.
Sens. Cap
Power
0
1.000
1.000
1.000
1.000
5
0.997
0.997
1.004
1.060
10
0.994
0.994
1.006
1.125
15
0.990
0.990
1.009
1.190
25
0.983
0.983
1.016
1.300
5
0.997
0.997
1.003
1.060
10
0.996
0.996
1.005
1.100
15
0.994
0.994
1.008
1.140
5
0.998
0.998
1.002
1.160
10
0.996
0.996
1.004
1.230
15
0.992
0.992
1.006
1.280
25
0.986
0.986
1.009
1.400
5
0.997
0.997
1.003
1.060
Propylene Glycol
Methanol
Ethanol
Ethylene Glycol
16
Subject to change without prior notice Revised 07 - 16
EC SERIES POOL DEHUMIDIFIERS
WATERSIDE PRESSURE DROP
Model
EC072
EC096
EC120
EC150
EC151
EC180
EC181
EC210
EC240
EC242
EC300
EC360
GPM
Pressure Drop (PSIG)
Pressure Drop (ft of H2O)
10
2.6
6.0
12
3.6
8.3
14
4.8
11.0
16
18
6.1
7.5
14.0
17.3
12
14
2.5
3.3
5.7
7.5
18
5.1
11.8
21
24
6.8
8.6
15.6
19.8
16
20
2.1
3.1
4.9
7.3
24
4.4
10.1
28
32
5.8
7.3
13.3
16.9
20
25
1.4
2.1
3.3
4.9
30
3.0
6.8
35
50
3.9
7.4
9.0
17.1
20
25
1.4
2.1
3.3
4.9
30
3.0
6.8
35
50
3.9
7.4
9.0
17.1
22
27
1.7
2.5
3.9
5.7
32
3.3
7.7
42
52
5.4
8.0
12.5
18.4
22
27
1.7
2.5
3.9
5.7
32
3.3
7.7
42
52
5.4
8.0
12.5
18.4
30
40
2.6
4.3
5.9
9.9
50
6.4
14.9
60
70
8.9
11.8
20.6
27.2
30
40
1.6
2.7
3.7
6.2
50
4.0
9.3
60
75
5.6
8.3
12.9
19.2
30
40
1.6
2.7
3.7
6.2
50
4.0
9.3
60
75
5.6
8.3
12.9
19.2
40
50
2.7
4.0
6.2
9.3
60
5.6
12.9
75
85
8.3
10.4
19.2
24.1
50
70
3.7
6.7
8.5
15.5
80
8.5
19.7
90
100
10.6
12.8
24.4
29.5
NOTE: Based on 70° F pure entering water
Subject to change without prior notice Revised 07 - 16
17
EC SERIES POOL DEHUMIDIFIERS
CAPACITY DATA
EC072 2300 NOMINAL CFM (without Max Evap Option)
Horizontal & Vertical Configurations
Cooling
Entering Fluid
Temp (°F)
Water Flow (GPM)
9
50
12
18
9
60
12
18
9
70
12
18
9
80
12
18
9
85
12
18
9
90
12
18
9
100
12
18
9
110
12
18
18
Pressure Drop PSI
(FOH)
2.3
(5.3)
3.9
(8.9)
8.0
(18.5)
2.2
(5.1)
3.7
(8.6)
7.7
(17.9)
2.1
(5.0)
3.6
(8.3)
7.5
(17.3)
2.1
(4.8)
3.5
(8.1)
7.2
(16.7)
2.0
(4.7)
3.4
(7.9)
7.1
(16.5)
2.0
(4.7)
3.4
(7.8)
7.0
(16.2)
2.0
(4.5)
3.3
(7.6)
6.8
(15.7)
1.9
(4.4)
3.2
(7.4)
6.6
(15.3)
Entering Air Temp
(db/wb) °F
Total Capacity
(MBTUH)
Sensible Capacity
(MBTUH)
Heat of Rejection
(MBTUH)
Power Input (kW)
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
81.4
87.5
93.8
83.6
90.0
96.6
85.9
92.6
99.6
77.0
82.8
88.8
79.0
85.1
91.5
81.2
87.6
94.2
72.2
77.8
83.6
74.2
80.1
86.1
76.2
82.3
88.8
67.5
72.7
78.1
69.2
74.8
80.6
71.1
76.9
82.9
64.9
70.1
75.4
66.7
72.1
77.6
68.5
74.1
80.2
62.6
67.5
72.6
64.1
69.3
74.9
65.8
71.4
77.1
57.9
62.4
67.2
59.3
64.0
69.1
60.8
65.7
71.1
52.8
57.2
61.6
54.1
58.7
63.3
55.5
60.3
65.2
61.2
63.5
65.6
62.0
64.4
66.5
62.9
65.3
67.5
58.9
61.3
63.5
59.9
62.2
64.4
60.8
63.2
65.7
57.2
59.3
61.6
57.8
60.2
62.5
58.8
61.4
63.4
54.9
57.4
59.9
55.8
58.1
60.5
56.4
59.2
61.8
54.2
56.4
58.7
54.5
57.2
59.8
55.3
58.2
60.2
52.9
55.2
57.7
53.6
56.1
58.4
54.2
56.7
59.7
49.5
52.3
56.0
50.2
54.3
56.4
50.8
54.9
57.1
47.5
50.0
52.3
48.0
50.6
53.1
48.7
51.2
53.7
93.8
100.1
106.6
95.7
102.2
109.0
97.6
104.4
111.5
90.1
96.2
102.4
91.8
98.1
104.7
93.6
100.2
106.9
86.0
92.0
98.1
87.7
93.9
100.2
89.3
95.7
102.4
82.0
87.7
93.5
83.5
89.5
95.6
85.1
91.2
97.5
79.8
85.5
91.3
81.4
87.2
93.1
82.9
88.9
95.3
77.8
83.3
88.9
79.1
84.9
90.9
80.6
86.7
92.6
73.7
78.9
84.3
75.0
80.3
86.0
76.2
81.8
87.7
69.3
74.4
79.5
70.4
75.7
81.1
71.7
77.1
82.6
4.0
4.0
4.0
3.8
3.8
3.7
3.7
3.6
3.5
4.4
4.4
4.4
4.2
4.2
4.2
4.0
4.0
3.9
4.8
4.8
4.8
4.6
4.6
4.6
4.5
4.4
4.4
5.2
5.2
5.3
5.0
5.1
5.1
4.9
4.9
4.9
5.4
5.4
5.5
5.2
5.3
5.3
5.1
5.1
5.1
5.6
5.6
5.7
5.4
5.5
5.5
5.3
5.3
5.3
5.9
6.0
6.1
5.8
5.9
6.0
5.7
5.8
5.8
6.2
6.4
6.5
6.2
6.3
6.4
6.1
6.2
6.3
EER
20.3
21.9
23.6
21.8
23.7
25.8
23.5
25.8
28.4
17.5
18.8
20.2
18.7
20.2
22.0
20.1
21.9
23.9
15.1
16.2
17.3
16.0
17.3
18.7
17.1
18.6
20.2
13.0
13.9
14.9
13.7
14.8
15.9
14.6
15.7
17.1
12.1
12.9
13.8
12.7
13.7
14.7
13.4
14.5
15.7
11.3
12.0
12.7
11.8
12.6
13.5
12.4
13.4
14.4
9.8
10.4
11.0
10.2
10.9
11.5
10.7
11.4
12.2
8.5
8.9
9.4
8.8
9.3
9.9
9.2
9.8
10.4
Subject to change without prior notice Revised 07 - 16
EC SERIES POOL DEHUMIDIFIERS
CAPACITY DATA
EC096 2800 NOMINAL CFM (without Max Evap Option)
Horizontal & Vertical Configurations
Cooling
Entering Fluid
Temp (°F)
50
60
Water Flow (GPM)
12
2.6
(6.0)
16
4.4
(10.1)
24
9.1
(21.1)
12
2.5
(5.8)
16
4.2
(9.8)
24
8.8
(20.3)
12
70
16
24
12
80
16
24
12
85
16
24
12
90
16
24
12
100
16
24
12
110
Pressure Drop PSI
(FOH)
16
24
2.4
(5.7)
4.1
(9.5)
8.5
(19.7)
2.4
(5.5)
4.0
(9.2)
8.2
(19.0)
2.3
(5.4)
3.9
(9.0)
8.1
(18.7)
2.3
(5.3)
3.9
(8.9)
8.1
(18.5)
2.2
(5.1)
3.7
(8.6)
7.8
(17.9)
2.2
(5.0)
3.6
(8.4)
7.5
(17.4)
Entering Air Temp
(db/wb) °F
Total Capacity
(MBTUH)
Sensible Capacity
(MBTUH)
Heat of Rejection
(MBTUH)
Power Input (kW)
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
106.9
113.9
121.3
109.3
116.7
124.4
111.9
119.6
127.7
102.6
109.4
116.5
104.9
112.1
119.4
107.4
114.8
122.5
98.2
104.6
111.4
100.4
107.1
114.3
102.7
109.8
117.3
93.5
99.7
106.1
95.6
102.2
108.7
97.8
104.7
111.6
91.1
97.2
103.2
93.2
99.6
106.1
95.4
102.1
108.9
88.7
94.5
100.6
90.7
96.8
103.1
92.8
99.2
106.0
83.8
89.2
94.7
85.9
91.4
97.2
87.8
93.9
100.1
78.8
83.9
88.7
80.6
85.7
91.2
82.5
88.1
93.6
77.7
80.0
82.1
78.7
81.1
83.2
79.7
82.2
84.3
75.6
78.0
79.9
76.7
79.0
81.6
77.7
80.1
82.8
73.6
76.2
78.0
74.6
77.3
79.1
75.6
78.4
80.3
71.7
73.9
76.2
72.6
74.8
77.8
73.7
76.0
78.8
70.8
72.8
75.7
71.6
73.7
76.2
72.6
74.7
77.3
69.8
72.3
74.2
70.7
73.2
75.7
71.5
74.1
76.1
67.7
70.3
72.7
68.1
71.1
73.6
68.9
71.5
74.0
65.2
67.7
70.7
65.9
68.9
71.5
66.8
69.3
72.4
122.9
130.3
138.0
124.7
132.3
140.3
126.5
134.4
142.7
120.0
127.2
134.7
121.6
129.0
136.6
123.3
131.0
138.9
117.1
123.9
131.1
118.5
125.6
133.1
120.1
127.4
135.2
114.1
120.8
127.6
115.4
122.4
129.2
116.8
124.0
131.2
112.6
119.3
125.7
113.9
120.7
127.6
115.2
122.3
129.5
111.2
117.5
124.1
112.4
118.9
125.6
113.7
120.4
127.6
108.5
114.4
120.4
109.7
115.7
121.9
110.8
117.2
123.8
106.1
111.7
117.0
106.9
112.5
118.4
107.9
113.9
119.8
5.0
5.1
5.1
4.7
4.7
4.7
4.4
4.4
4.4
5.6
5.6
5.7
5.3
5.3
5.3
5.0
5.0
4.9
6.2
6.3
6.3
5.9
5.9
6.0
5.6
5.6
5.6
6.9
7.0
7.0
6.6
6.6
6.6
6.3
6.3
6.3
7.3
7.3
7.4
7.0
7.0
7.0
6.6
6.6
6.6
7.7
7.7
7.8
7.3
7.4
7.4
7.0
7.0
7.0
8.5
8.5
8.6
8.2
8.2
8.2
7.8
7.8
7.9
9.4
9.5
9.5
9.1
9.1
9.1
8.7
8.8
8.8
Subject to change without prior notice Revised 07 - 16
EER
21.2
22.5
23.9
23.1
24.7
26.3
25.3
27.2
29.3
18.3
19.4
20.5
19.8
21.1
22.5
21.5
23.1
24.8
15.8
16.7
17.6
17.0
18.1
19.2
18.3
19.6
21.0
13.5
14.3
15.1
14.5
15.4
16.4
15.6
16.7
17.8
12.5
13.3
14.0
13.4
14.3
15.1
14.4
15.4
16.4
11.6
12.2
12.9
12.4
13.1
13.9
13.3
14.1
15.1
9.9
10.4
11.0
10.5
11.2
11.8
11.2
12.0
12.7
8.4
8.9
9.3
8.9
9.4
10.0
9.4
10.1
10.7
19
EC SERIES POOL DEHUMIDIFIERS
CAPACITY DATA
EC120 4000 NOMINAL CFM (without Max Evap Option)
Horizontal & Vertical Configurations
Cooling
Entering Fluid
Temp (°F)
Water Flow (GPM)
15
50
20
30
15
60
20
30
15
70
20
30
15
80
20
30
15
85
20
30
15
90
20
30
15
100
20
30
15
110
20
30
20
Pressure Drop PSI
(FOH)
2.0
(4.6)
3.3
(7.7)
6.9
(16.0)
1.9
(4.4)
3.2
(7.5)
6.7
(15.5)
1.9
(4.3)
3.1
(7.2)
6.5
(15.0)
1.8
(4.2)
3.0
(7.0)
6.3
(14.5)
1.8
(4.1)
3.0
(6.9)
6.2
(14.2)
1.7
(4.0)
2.9
(6.8)
6.1
(14.0)
1.7
(3.9)
2.8
(6.6)
5.9
(13.6)
1.6
(3.8)
2.8
(6.4)
5.7
(13.2)
Entering Air Temp
(db/wb) °F
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
Total Capacity
(MBTUH)
132.0
141.2
150.7
134.9
144.5
154.4
138.0
148.0
158.3
126.7
135.6
144.7
129.5
138.7
148.2
132.4
142.0
151.9
121.0
129.7
138.1
123.7
132.5
141.5
126.5
135.6
145.1
115.3
123.3
131.6
117.8
126.4
134.8
120.5
129.4
138.5
112.1
120.3
128.0
114.6
123.1
131.6
117.2
125.8
135.0
109.3
117.0
124.5
111.7
119.6
127.9
114.2
122.7
131.2
102.8
110.5
117.7
105.3
112.6
120.5
107.6
115.4
123.8
96.9
103.9
110.8
99.0
106.3
113.6
101.1
108.7
116.3
Sensible Capacity
(MBTUH)
99.0
102.2
105.1
100.3
103.4
106.4
101.2
104.7
107.8
96.2
99.6
102.7
97.4
100.8
104.0
98.6
102.1
105.5
93.6
96.9
100.8
94.8
98.6
102.1
95.9
99.9
103.4
90.9
94.8
98.2
92.0
95.5
99.5
93.1
96.8
100.2
90.0
93.1
97.5
91.0
94.3
97.7
92.2
95.9
99.0
88.2
91.9
96.3
89.3
93.4
96.9
90.4
94.1
98.1
86.4
89.6
94.1
86.6
91.3
95.6
87.6
92.2
95.5
83.0
86.8
90.9
84.0
87.8
92.0
84.9
88.8
93.5
Heat of Rejection
(MBTUH)
153.8
163.7
173.7
156.1
166.3
176.7
158.6
169.0
179.9
149.9
159.4
169.0
152.0
161.8
171.8
154.2
164.4
174.7
146.0
155.1
164.1
147.9
157.1
166.6
149.9
159.4
169.3
142.1
150.7
159.5
143.8
152.8
161.8
145.6
154.9
164.5
140.1
148.8
156.9
141.6
150.6
159.6
143.3
152.4
161.9
138.4
146.7
154.7
139.9
148.3
157.0
141.4
150.4
159.2
134.5
142.9
150.5
136.1
143.8
152.1
137.4
145.5
154.3
131.7
139.3
146.7
132.8
140.5
148.3
133.9
141.9
149.7
Power Input (kW)
6.7
6.8
6.9
6.4
6.5
6.6
6.1
6.2
6.2
7.3
7.4
7.5
7.0
7.1
7.1
6.7
6.8
6.8
8.0
8.1
8.1
7.7
7.7
7.8
7.4
7.4
7.4
8.8
8.9
8.9
8.5
8.5
8.5
8.1
8.1
8.1
9.2
9.3
9.3
8.9
8.9
8.9
8.5
8.5
8.5
9.7
9.7
9.8
9.3
9.3
9.4
9.0
9.0
9.0
10.7
10.7
10.8
10.3
10.3
10.3
9.9
9.9
9.9
11.8
11.8
11.9
11.4
11.4
11.4
11.0
11.0
11.0
EER
19.6
20.7
21.9
21.0
22.2
23.5
22.4
23.9
25.4
17.3
18.3
19.3
18.4
19.6
20.8
19.7
21.0
22.4
15.1
16.0
17.0
16.1
17.1
18.2
17.2
18.4
19.6
13.1
13.9
14.8
13.9
14.9
15.8
14.9
15.9
17.0
12.2
13.0
13.7
12.9
13.8
14.7
13.8
14.8
15.8
11.3
12.0
12.7
12.0
12.8
13.7
12.7
13.7
14.6
9.6
10.3
10.9
10.2
10.9
11.7
10.9
11.6
12.5
8.2
8.8
9.3
8.7
9.3
10.0
9.2
9.9
10.6
Subject to change without prior notice Revised 07 - 16
EC SERIES POOL DEHUMIDIFIERS
CAPACITY DATA
EC150 5000 NOMINAL CFM (without Max Evap Option)
Horizontal & Vertical Configurations
Cooling
Entering Fluid
Temp (°F)
Water Flow (GPM)
18.8
50
25
37.6
18.8
60
25
37.6
18.8
70
25
37.6
18.8
80
25
37.6
18.8
85
25
37.6
18.8
90
25
37.6
18.8
100
25
37.6
18.8
110
25
37.6
Pressure Drop PSI
(FOH)
1.4
(3.2)
2.3
(5.3)
4.8
(11.0)
1.3
(3.0)
2.2
(5.1)
4.6
(10.6)
1.3
(2.9)
2.1
(4.9)
1.2
(10.3)
2.1
(2.9)
4.3
(4.8)
1.2
(9.9)
2.0
(2.8)
2.0
(4.7)
4.2
(9.8)
1.2
(2.8)
2.0
(4.6)
4.0
(9.6)
1.2
(2.7)
1.9
(4.5)
4.0
(9.3)
1.1
(2.6)
1.9
(4.4)
3.9
(9.1)
Entering Air Temp
(db/wb) °F
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
Total Capacity
(MBTUH)
159.4
169.7
180.4
162.8
173.5
184.3
166.3
177.4
188.6
152.8
162.8
172.8
156.0
166.1
177.0
159.2
169.9
181.2
145.6
155.5
165.2
148.7
158.9
169.1
151.9
162.5
173.1
138.5
147.9
157.3
141.5
151.3
161.3
144.7
154.5
165.2
135.1
144.2
153.5
137.9
147.2
157.1
140.8
150.7
160.7
131.4
140.2
149.6
134.2
143.3
153.0
137.0
146.5
156.3
124.1
132.6
141.3
126.6
135.3
144.8
129.1
138.3
148.1
116.2
124.5
132.9
118.7
127.4
136.2
121.1
130.2
139.1
Subject to change without prior notice Revised 07 - 16
Sensible Capacity
(MBTUH)
124.0
128.0
132.1
125.1
129.3
134.2
126.5
130.8
135.8
120.8
125.0
130.3
122.1
127.1
130.9
124.0
128.6
132.4
115.5
122.4
127.5
116.9
123.7
128.9
121.1
125.1
130.2
112.6
119.4
124.8
116.2
120.8
125.2
114.4
122.7
126.6
110.4
118.0
122.7
111.7
119.8
124.3
115.9
120.6
126.0
108.8
113.9
117.8
110.0
115.1
122.5
111.2
119.6
124.5
105.4
110.2
115.3
106.6
112.1
115.8
108.3
113.3
117.2
102.7
107.5
112.3
103.8
108.0
112.6
104.8
109.1
114.7
Heat of Rejection
(MBTUH)
183.4
194.3
205.6
186.2
197.4
208.7
189.0
200.6
212.3
178.3
188.8
199.3
180.8
191.4
202.8
183.2
194.4
206.2
172.8
183.2
193.4
175.1
185.8
196.4
177.5
188.6
199.6
167.7
177.7
187.6
169.9
180.1
190.6
172.2
182.4
193.5
165.5
175.1
185.0
167.4
177.1
187.4
169.4
179.7
190.0
163.1
172.4
182.3
164.9
174.5
184.6
166.8
176.6
186.8
158.7
167.8
177.0
160.2
169.3
179.2
161.6
171.2
181.3
154.5
163.3
172.2
155.7
164.9
174.1
157.0
166.4
175.6
Power Input (kW)
7.3
7.4
7.5
7.0
7.1
7.1
6.7
6.7
6.8
8.0
8.0
8.1
7.7
7.7
7.7
7.3
7.4
7.4
8.7
8.8
8.8
8.4
8.4
8.4
8.1
8.1
8.1
9.6
9.6
9.6
9.2
9.2
9.2
8.9
8.9
8.9
10.0
10.1
10.1
9.7
9.7
9.7
9.3
9.3
9.3
10.5
10.6
10.6
10.1
10.2
10.2
9.8
9.8
9.7
11.6
11.7
11.7
11.2
11.2
11.3
10.8
10.8
10.8
12.9
13.0
13.0
12.5
12.5
12.5
12.1
12.1
12.0
EER
21.7
22.9
24.2
23.2
24.5
25.9
24.9
26.3
27.9
19.1
20.2
21.3
20.3
21.6
22.9
21.7
23.1
24.5
16.7
17.7
18.7
17.7
18.9
20.0
18.9
20.1
21.4
14.5
15.4
16.3
15.4
16.4
17.5
16.3
17.5
18.7
13.5
14.3
15.2
14.3
15.2
16.2
15.1
16.2
17.3
12.5
13.3
14.1
13.2
14.1
15.0
14.0
15.0
16.0
10.7
11.4
12.1
11.3
12.0
12.9
11.9
12.8
13.7
9.0
9.6
10.2
9.5
10.2
10.9
10.0
10.8
11.6
21
EC SERIES POOL DEHUMIDIFIERS
CAPACITY DATA
EC151 5000 NOMINAL CFM (without Max Evap Option)
Horizontal & Vertical Configurations
Cooling
Entering Fluid
Temp (°F)
Water Flow (GPM)
18.8
50
25
37.6
18.8
60
25
37.6
18.8
70
25
37.6
18.8
80
25
37.6
18.8
85
25
37.6
18.8
90
25
37.6
18.8
100
25
37.6
18.8
110
25
37.6
22
Pressure Drop PSI
(FOH)
1.4
(3.2)
2.3
(5.3)
4.8
(11.0)
1.3
(3.0)
2.2
(5.1)
4.6
(10.6)
1.3
(2.9)
2.1
(4.9)
4.4
(10.3)
1.2
(2.9)
2.1
(4.8)
4.3
(9.9)
1.2
(2.8)
2.0
(4.7)
4.2
(9.8)
1.2
(2.8)
2.0
(4.6)
4.2
(9.6)
1.2
(2.7)
1.9
(4.5)
4.0
(9.3)
1.1
(2.6)
1.9
(4.4)
3.9
(9.1)
Entering Air Temp
(db/wb) °F
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
Total Capacity
(MBTUH)
155.7
166.2
176.2
160.0
169.9
180.3
163.2
174.0
184.6
149.5
158.9
168.6
152.9
162.5
172.3
156.2
166.3
176.8
142.9
151.3
161.6
145.6
155.5
165.4
148.7
158.6
168.9
134.4
147.4
152.6
137.9
148.0
153.9
141.2
150.8
161.3
131.3
139.0
147.1
134.0
146.6
152.0
139.5
147.3
156.9
127.9
135.4
144.0
130.3
139.4
152.3
133.0
145.7
151.2
120.3
128.3
134.9
122.8
130.8
136.5
125.5
134.0
140.8
112.5
119.9
128.2
115.1
123.1
130.9
117.5
125.7
132.9
Sensible Capacity
(MBTUH)
119.3
127.1
131.3
123.9
128.6
132.9
125.9
129.5
134.5
120.4
124.6
129.3
121.4
126.0
131.3
122.8
127.2
131.7
117.8
119.4
126.2
118.7
123.5
127.5
120.0
124.2
128.6
110.6
110.6
116.8
113.3
120.0
126.0
113.9
121.0
125.7
110.6
116.7
119.0
114.1
110.8
116.9
111.1
119.8
124.4
108.2
114.4
117.4
110.1
117.1
101.4
108.7
110.7
116.9
105.0
109.4
113.9
106.2
111.3
120.5
107.2
111.9
121.3
101.6
106.3
110.3
102.3
107.2
112.0
103.4
107.9
116.0
Heat of Rejection
(MBTUH)
179.6
190.7
201.3
183.2
193.7
204.6
185.7
197.1
208.2
174.9
184.9
195.0
177.6
187.7
198.0
180.2
190.8
201.8
170.0
178.8
189.7
171.9
182.3
192.7
174.3
184.7
195.3
163.5
177.3
182.8
166.1
176.7
183.0
168.7
178.7
189.6
161.6
169.8
178.3
163.4
176.6
182.3
168.1
176.2
186.3
159.4
167.5
176.5
160.9
170.4
184.1
162.8
176.0
181.7
154.8
163.3
170.4
156.3
164.7
170.7
157.9
166.8
173.9
150.7
158.6
167.4
152.1
160.5
168.8
153.3
161.9
169.4
Power Input (kW)
7.3
7.4
7.4
7.0
7.0
7.1
6.7
6.7
6.7
8.0
8.0
8.1
7.6
7.7
7.7
7.3
7.3
7.4
8.7
8.7
8.8
8.4
8.4
8.4
8.0
8.0
8.1
9.5
9.6
9.6
9.2
9.2
9.2
8.8
8.8
8.8
10.0
10.0
10.1
9.6
9.7
9.7
9.3
9.3
9.3
10.5
10.5
10.6
10.1
10.1
10.2
9.8
9.8
9.7
11.6
11.6
11.7
11.2
11.2
11.2
10.8
10.8
10.8
12.9
13.0
13.0
12.5
12.5
12.5
12.1
12.1
12.0
EER
21.4
22.6
23.7
22.9
24.2
25.5
24.5
25.9
27.4
18.8
19.8
20.9
20.0
21.2
22.4
21.3
22.7
24.0
16.4
17.3
18.4
17.4
18.5
19.7
18.5
19.7
21.0
14.1
15.4
15.9
15.0
16.1
16.7
16.0
17.1
18.3
13.1
13.9
14.6
13.9
15.2
15.7
15.0
15.9
16.9
12.2
12.9
13.6
12.9
13.8
15.0
13.6
14.9
15.5
10.4
11.0
11.6
11.0
11.7
12.2
11.6
12.4
13.1
8.7
9.3
9.9
9.2
9.8
10.5
9.7
10.4
11.0
Subject to change without prior notice Revised 07 - 16
EC SERIES POOL DEHUMIDIFIERS
CAPACITY DATA
EC180 6000 NOMINAL CFM (without Max Evap Option)
Horizontal & Vertical Configurations
Cooling
Entering Fluid
Temp (°F)
Water Flow (GPM)
22.6
50
30
45
22.6
60
30
45
22.6
70
30
45
22.6
80
30
45
22.6
85
30
45
22.6
90
30
45
22.6
100
30
45
22.6
110
30
45
Pressure Drop PSI
(FOH)
1.9
(4.4)
3.2
(7.3)
6.6
(15.2)
1.8
(4.2)
3.1
(7.1)
6.4
(14.7)
1.8
(4.1)
3.0
(6.8)
6.1
(14.2)
1.7
(4.0)
2.9
(6.6)
5.9
(13.7)
1.7
(3.9)
2.8
(6.5)
5.9
(13.5)
1.7
(3.9)
2.8
(6.4)
5.8
(13.3)
1.6
(3.7)
2.7
(6.2)
5.6
(12.9)
1.6
(3.6)
2.6
(6.0)
5.4
(12.5)
Entering Air Temp
(db/wb) °F
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
Total Capacity
(MBTUH)
183.3
194.9
207.0
186.8
198.9
211.5
190.5
203.1
216.2
175.9
187.3
198.8
179.4
191.2
203.1
183.0
195.2
207.8
168.4
179.3
190.4
171.7
182.8
194.5
174.9
186.6
198.9
160.4
171.1
181.6
163.5
174.6
185.8
166.9
178.0
190.1
156.4
166.9
177.2
159.5
170.4
181.0
162.6
173.9
185.3
152.6
162.5
173.0
155.5
166.1
176.5
158.6
169.5
180.6
144.4
154.0
163.9
147.2
157.2
167.5
150.0
160.2
171.1
135.9
144.8
154.2
138.5
147.8
157.6
141.1
150.8
161.3
Subject to change without prior notice Revised 07 - 16
Sensible Capacity
(MBTUH)
141.0
146.4
151.0
142.8
147.8
152.3
144.2
149.2
153.6
138.1
143.0
148.4
139.5
144.4
150.1
140.9
145.8
151.0
134.4
139.6
145.4
135.9
141.9
146.8
138.0
143.4
148.4
131.7
136.5
142.3
133.2
137.9
143.2
134.2
140.0
144.3
130.1
134.6
140.5
131.4
136.1
142.2
132.9
137.5
143.0
127.5
133.5
138.1
129.0
134.2
140.3
130.4
135.6
141.1
123.9
129.4
134.5
125.2
130.7
135.9
126.4
132.8
137.3
120.2
126.5
131.8
121.4
127.7
133.0
122.5
128.9
133.5
Heat of Rejection
(MBTUH)
212.4
224.5
237.2
215.0
227.7
240.8
218.0
231.0
244.6
206.6
218.6
230.8
209.3
221.6
234.1
212.1
224.8
237.9
201.1
212.7
224.4
203.6
215.2
227.5
205.9
218.1
230.8
195.4
206.7
217.9
197.5
209.2
221.1
200.0
211.7
224.3
192.6
203.9
214.8
194.7
206.2
217.5
196.9
208.7
220.6
190.2
200.8
212.0
192.1
203.3
214.3
194.2
205.6
217.3
185.0
195.3
205.9
186.7
197.3
208.3
188.5
199.2
210.7
179.9
189.5
199.6
181.5
191.3
201.7
183.0
193.2
204.2
Power Input (kW)
8.8
8.9
8.9
8.5
8.5
8.6
8.1
8.2
8.2
9.5
9.6
9.7
9.2
9.2
9.3
8.8
8.9
8.9
10.4
10.4
10.5
10.0
10.0
10.1
9.6
9.7
9.7
11.3
11.3
11.4
10.9
10.9
11.0
10.5
10.5
10.6
11.7
11.8
11.9
11.4
11.4
11.5
11.0
11.0
11.1
12.3
12.3
12.4
11.9
11.9
12.0
11.5
11.5
11.6
13.4
13.5
13.6
13.0
13.1
13.1
12.6
12.6
12.7
14.7
14.7
14.8
14.3
14.3
14.3
13.9
13.9
13.9
EER
20.8
22.0
23.1
22.0
23.4
24.7
23.4
24.9
26.5
18.5
19.5
20.5
19.5
20.7
21.9
20.7
22.0
23.4
16.3
17.2
18.1
17.2
18.2
19.3
18.2
19.3
20.5
14.3
15.1
15.9
15.0
16.0
16.9
15.9
16.9
18.0
13.3
14.1
14.9
14.0
14.9
15.8
14.8
15.8
16.8
12.4
13.2
13.9
13.1
13.9
14.7
13.8
14.7
15.6
10.8
11.4
12.1
11.3
12.0
12.8
11.9
12.7
13.5
9.3
9.8
10.4
9.7
10.4
11.0
10.2
10.9
11.6
23
EC SERIES POOL DEHUMIDIFIERS
CAPACITY DATA
EC181 6000 NOMINAL CFM (without Max Evap Option)
Horizontal & Vertical Configurations
Cooling
Entering Fluid
Temp (°F)
Water Flow (GPM)
22.6
50
30
45
22.6
60
30
45
22.6
70
30
45
22.6
80
30
45
22.6
85
30
45
22.6
90
30
45
22.6
100
30
45
22.6
110
30
45
24
Pressure Drop PSI
(FOH)
1.9
(4.4)
3.2
(7.3)
6.6
(15.2)
1.8
(4.2)
3.1
(7.1)
6.4
(14.7)
1.8
(4.1)
3.0
(6.8)
6.1
(14.2)
1.7
(4.0)
2.9
(6.6)
5.9
(13.7)
1.7
(3.9)
2.8
(6.5)
5.9
(13.5)
1.7
(3.9)
2.8
(6.4)
5.8
(13.3)
5.8
(3.7)
2.7
(6.2)
5.6
(12.9)
1.6
(3.6)
2.6
(6.0)
5.4
(12.5)
Entering Air Temp
(db/wb) °F
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
Total Capacity
(MBTUH)
176.9
187.9
200.0
180.4
191.9
204.2
183.1
195.1
208.9
169.2
180.1
191.4
172.6
183.7
195.5
176.3
188.3
200.3
160.5
169.2
180.9
166.9
175.7
186.8
168.1
179.8
191.3
152.7
161.8
168.9
155.8
163.2
176.0
157.6
167.8
176.6
148.6
157.6
166.7
151.9
160.9
168.4
155.0
162.6
175.9
142.7
149.9
162.3
147.7
153.9
165.5
150.5
159.9
167.6
135.8
141.0
159.6
138.8
147.9
151.1
141.4
150.3
159.5
127.3
136.9
136.7
129.6
138.7
140.8
132.4
140.7
156.2
Sensible Capacity
(MBTUH)
137.6
142.9
146.8
139.2
144.5
149.1
140.4
145.4
150.2
134.8
139.7
144.7
136.3
141.9
146.7
137.4
142.1
147.4
131.9
140.5
136.6
127.5
137.7
142.9
134.2
138.7
144.1
127.7
128.8
145.3
129.0
139.7
134.7
127.9
139.9
148.9
125.8
126.8
133.5
126.6
128.2
144.7
128.0
138.8
133.2
122.6
137.3
130.9
124.8
137.5
133.7
126.5
127.7
144.3
119.9
134.0
107.1
121.3
127.6
140.3
122.9
124.1
131.0
116.1
119.5
135.6
118.1
123.5
136.9
118.7
120.6
106.7
Heat of Rejection
(MBTUH)
207.7
219.3
232.0
210.5
222.5
235.3
212.5
224.9
239.2
201.7
213.2
225.1
204.3
216.0
228.3
207.3
219.7
232.2
194.9
204.1
216.6
200.6
209.9
221.6
200.9
213.1
225.1
189.4
199.2
206.8
191.6
199.4
213.0
192.6
203.2
212.4
186.6
196.2
205.9
189.0
198.6
206.4
191.2
199.1
213.1
182.0
189.7
203.0
186.0
192.7
205.0
187.9
197.8
205.9
178.1
183.8
203.7
180.1
189.8
193.3
181.7
191.2
200.9
173.1
183.4
183.5
174.3
183.9
186.4
176.1
184.9
201.2
Power Input (kW)
9.3
9.4
9.5
9.0
9.0
9.1
8.7
8.7
8.7
10.1
10.1
10.2
9.7
9.8
9.8
9.4
9.4
9.4
10.9
10.9
11.0
10.5
10.6
10.6
10.2
10.2
10.2
11.8
11.8
11.9
11.4
11.4
11.5
11.0
11.1
11.1
12.2
12.3
12.4
11.9
11.9
12.0
11.5
11.5
11.6
12.8
12.8
12.9
12.4
12.4
12.5
12.0
12.1
12.1
13.9
13.9
14.1
13.5
13.6
13.6
13.1
13.2
13.2
15.2
15.2
15.2
14.8
14.8
14.8
14.4
14.4
14.5
EER
18.9
20.0
21.1
20.0
21.2
22.5
21.1
22.4
24.0
16.8
17.8
18.8
17.8
18.8
19.9
18.8
20.0
21.2
14.8
15.5
16.4
15.8
16.6
17.6
16.5
17.6
18.7
13.0
13.7
14.2
13.7
14.3
15.3
14.3
15.2
16.0
12.1
12.8
13.5
12.8
13.5
14.1
13.5
14.1
15.2
11.2
11.7
12.6
11.9
12.4
13.2
12.5
13.3
13.9
9.8
10.1
11.3
10.3
10.9
11.1
10.8
11.4
12.1
8.4
9.0
9.0
8.8
9.4
9.5
9.2
9.8
10.8
Subject to change without prior notice Revised 07 - 16
EC SERIES POOL DEHUMIDIFIERS
CAPACITY DATA
EC210 7000 NOMINAL CFM (without Max Evap Option)
Horizontal & Vertical Configurations
Cooling
Entering Fluid
Temp (°F)
Water Flow (GPM)
26.2
50
35
52.6
26.2
60
35
52.6
26.2
70
35
52.6
26.2
80
35
52.6
26.2
85
35
52.6
26.2
90
35
52.6
26.2
100
35
52.6
26.2
110
35
52.6
Pressure Drop PSI
(FOH)
2.1
(4.9)
3.6
(8.3)
7.5
(17.3)
2.1
(4.8)
3.5
(8.0)
7.2
(16.7)
2.0
(4.6)
3.4
(7.8)
7.0
(16.2)
1.9
(4.5)
3.3
(7.5)
6.8
(15.6)
1.9
(4.4)
3.2
(7.4)
6.7
(15.4)
1.9
(4.3)
3.2
(7.3)
6.6
(15.2)
1.8
(4.2)
3.1
(7.1)
6.4
(14.7)
1.8
(4.1)
3.0
(6.9)
6.2
(14.3)
Entering Air Temp
(db/wb) °F
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
Total Capacity
(MBTUH)
233.5
248.9
264.8
238.7
254.8
271.5
244.2
260.7
278.6
224.5
239.4
254.1
229.5
244.6
260.6
234.8
250.6
267.3
215.1
229.2
243.8
219.9
234.7
250.0
224.6
240.4
256.5
205.2
218.6
232.1
209.8
223.5
238.5
214.6
229.1
244.4
200.1
212.9
226.8
204.6
218.4
232.2
209.4
223.8
238.8
194.9
207.8
220.9
199.0
212.4
226.2
203.6
217.7
232.6
184.2
196.2
208.5
188.3
201.2
213.6
192.8
205.8
219.4
173.4
185.1
196.3
177.2
189.4
201.8
181.3
194.1
206.6
Subject to change without prior notice Revised 07 - 16
Sensible Capacity
(MBTUH)
175.0
180.3
185.7
177.0
186.8
192.6
179.2
190.2
195.2
170.5
176.1
182.9
172.7
179.5
185.3
174.8
182.0
187.9
166.1
172.1
177.6
168.2
174.3
180.0
171.3
176.6
182.6
161.9
167.9
174.7
164.0
171.0
175.8
166.0
173.2
179.3
159.6
166.6
171.3
161.6
167.7
174.8
163.6
169.9
175.8
157.5
163.4
169.3
160.3
166.6
172.5
162.2
168.5
173.7
153.8
160.1
166.1
155.7
161.2
168.8
156.9
164.0
170.4
149.4
154.6
161.7
150.7
156.5
162.6
152.6
158.2
165.4
Heat of Rejection
(MBTUH)
272.3
289.0
306.1
276.4
293.6
311.4
280.6
298.0
317.0
265.7
281.8
297.6
269.4
285.6
302.6
273.5
290.2
308.0
258.9
274.1
289.9
262.4
278.2
294.6
265.7
282.5
299.6
251.9
266.5
281.2
255.1
269.9
286.0
258.5
273.9
290.2
248.5
262.4
277.5
251.5
266.4
281.2
254.8
270.2
286.2
245.0
259.1
273.4
247.6
262.0
276.9
250.7
265.7
281.7
238.2
251.4
264.9
240.7
254.7
268.0
243.6
257.6
272.1
232.1
245.0
257.4
234.1
247.4
260.9
236.5
250.3
263.6
Power Input (kW)
12.0
12.2
12.4
11.5
11.7
11.8
10.9
11.1
11.2
13.0
13.2
13.4
12.4
12.6
12.8
11.9
12.0
12.2
14.0
14.2
14.4
13.5
13.7
13.8
12.9
13.1
13.2
15.2
15.4
15.6
14.6
14.8
15.0
14.1
14.2
14.3
15.8
16.0
16.2
15.3
15.4
15.6
14.7
14.8
14.9
16.5
16.7
16.9
15.9
16.1
16.2
15.3
15.5
15.6
18.0
18.2
18.4
17.4
17.5
17.7
16.8
16.9
17.0
19.6
19.8
20.0
19.0
19.2
19.3
18.4
18.5
18.6
EER
19.5
20.4
21.3
20.8
21.9
22.9
22.4
23.6
24.8
17.3
18.2
19.0
18.5
19.4
20.4
19.8
20.9
22.0
15.3
16.1
16.9
16.3
17.2
18.1
17.4
18.4
19.4
13.5
14.2
14.9
14.3
15.1
15.9
15.3
16.1
17.1
12.6
13.3
14.0
13.4
14.2
14.9
14.3
15.1
16.0
11.8
12.4
13.1
12.5
13.2
13.9
13.3
14.1
14.9
10.3
10.8
11.4
10.9
11.5
12.1
11.5
12.2
12.9
8.8
9.3
9.8
9.3
9.9
10.4
9.9
10.5
11.1
25
EC SERIES POOL DEHUMIDIFIERS
CAPACITY DATA
EC240 8000 NOMINAL CFM (without Max Evap Option)
Horizontal & Vertical Configurations
Cooling
Entering Fluid
Temp (°F)
Water Flow (GPM)
30
50
40
60
30
60
40
60
30
70
40
60
30
80
40
60
30
85
40
60
30
90
40
60
30
100
40
60
30
110
40
60
26
Pressure Drop PSI
(FOH)
1.7
(3.9)
2.8
(6.5)
5.9
(13.6)
1.6
(3.8)
2.7
(6.3)
5.7
(13.1)
1.6
(3.6)
2.6
(6.1)
5.5
(12.7)
1.5
(3.5)
2.6
(5.9)
5.3
(12.3)
1.5
(3.5)
2.5
(5.8)
5.2
(12.1)
1.5
(3.4)
2.5
(5.7)
5.2
(11.9)
1.4
(3.3)
2.4
(5.6)
5.0
(11.6)
1.4
(3.2)
2.3
(5.4)
4.9
(11.2)
Entering Air Temp
(db/wb) °F
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
Total Capacity
(MBTUH)
269.0
285.7
303.4
274.1
291.9
310.0
280.0
298.5
317.1
258.3
274.9
291.9
263.7
281.0
298.7
269.3
287.4
305.8
247.5
263.6
279.8
252.8
269.1
285.9
258.3
275.1
292.8
236.5
251.8
266.8
241.5
257.5
273.2
246.7
263.3
279.9
230.5
245.7
260.4
235.4
250.8
266.6
240.4
256.6
273.6
224.9
239.1
254.5
229.7
244.6
260.0
234.6
250.6
266.2
212.3
225.8
240.1
216.9
232.4
247.2
221.8
236.9
253.0
200.4
213.6
226.8
204.8
219.0
232.3
209.6
223.3
237.5
Sensible Capacity
(MBTUH)
198.4
205.5
210.6
201.7
207.8
214.3
204.0
210.1
217.3
194.5
200.5
206.1
196.8
202.8
208.7
199.1
205.2
211.4
189.5
195.4
201.6
191.8
198.9
205.3
193.9
201.5
207.9
184.3
190.5
198.1
186.4
192.9
200.4
188.5
195.3
202.8
182.5
188.2
195.5
184.6
191.5
198.0
186.9
193.8
199.2
179.2
186.8
194.1
181.3
188.8
195.3
183.4
190.1
198.0
176.0
183.3
190.5
177.7
184.1
190.7
178.9
185.9
193.5
170.9
177.1
184.0
172.6
178.0
186.1
173.1
181.6
189.5
Heat of Rejection
(MBTUH)
312.2
330.5
350.1
316.0
335.4
355.1
320.5
340.6
360.8
304.2
322.4
341.2
308.2
327.1
346.4
312.5
332.0
352.0
296.4
314.2
332.0
300.2
318.0
336.4
304.2
322.5
341.7
288.9
305.8
322.4
292.3
309.8
327.0
296.0
314.0
331.9
284.7
301.6
317.9
288.0
304.9
322.3
291.4
308.9
327.5
281.4
297.0
314.1
284.4
300.7
317.6
287.6
304.9
322.0
273.4
288.3
304.2
276.0
293.1
309.4
279.2
295.6
313.1
267.0
281.9
296.6
269.4
285.0
299.8
272.4
287.2
302.6
Power Input (kW)
13.2
13.5
13.9
12.6
12.9
13.3
12.0
12.3
12.6
14.3
14.7
15.0
13.8
14.1
14.4
13.2
13.4
13.7
15.6
15.9
16.3
15.0
15.3
15.6
14.4
14.6
14.9
17.0
17.3
17.6
16.4
16.6
16.9
15.7
15.9
16.2
17.7
18.0
18.3
17.1
17.3
17.6
16.4
16.7
16.9
18.5
18.8
19.1
17.9
18.1
18.4
17.2
17.4
17.7
20.3
20.6
20.9
19.6
19.9
20.1
18.9
19.1
19.3
22.3
22.6
22.9
21.6
21.8
22.0
20.9
21.0
21.2
EER
20.3
21.1
21.8
21.7
22.6
23.4
23.3
24.2
25.2
18.0
18.7
19.4
19.2
20.0
20.8
20.5
21.4
22.3
15.9
16.6
17.2
16.9
17.6
18.4
18.0
18.8
19.7
13.9
14.6
15.2
14.8
15.5
16.2
15.7
16.5
17.3
13.0
13.6
14.2
13.8
14.5
15.1
14.6
15.4
16.2
12.1
12.7
13.3
12.8
13.5
14.1
13.6
14.4
15.1
10.5
11.0
11.5
11.1
11.7
12.3
11.7
12.4
13.1
9.0
9.5
9.9
9.5
10.0
10.5
10.0
10.6
11.2
Subject to change without prior notice Revised 07 - 16
EC SERIES POOL DEHUMIDIFIERS
CAPACITY DATA
EC242 8000 NOMINAL CFM (without Max Evap Option)
Horizontal & Vertical Configurations
Cooling
Entering Fluid
Temp (°F)
Water Flow (GPM)
30
50
40
60
30
60
40
60
30
70
40
60
30
80
40
60
30
85
40
60
30
90
40
60
30
100
40
60
30
110
40
60
Pressure Drop PSI
(FOH)
1.7
(3.9)
2.8
(6.5)
5.9
(13.6)
1.6
(3.8)
2.7
(6.3)
5.7
(13.1)
1.6
(3.6)
2.6
(6.1)
5.5
(12.7)
1.5
(3.5)
2.6
(5.9)
5.3
(12.3)
1.5
(3.5)
2.5
(5.8)
5.2
(12.1)
1.5
(3.4)
2.5
(5.7)
5.2
(11.9)
1.4
(3.3)
2.4
(5.6)
5.0
(11.6)
1.4
(3.2)
2.3
(5.4)
4.9
(11.2)
Entering Air Temp
(db/wb) °F
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
Total Capacity
(MBTUH)
262.0
277.4
296.0
267.6
283.5
303.2
273.3
290.0
309.8
251.6
266.3
284.4
255.5
273.7
291.0
261.0
279.8
298.0
239.7
256.5
272.4
244.7
262.2
278.8
250.1
268.1
286.0
229.7
244.7
259.3
234.5
250.2
266.0
239.5
255.9
272.6
224.0
238.8
253.7
228.7
244.0
259.1
233.6
249.5
265.9
218.2
232.5
247.1
222.8
237.8
253.0
227.6
243.2
259.1
206.7
219.9
239.7
210.7
224.9
237.6
214.9
230.5
245.7
194.0
208.1
219.0
197.3
211.4
232.2
202.1
213.8
227.0
Subject to change without prior notice Revised 07 - 16
Sensible Capacity
(MBTUH)
195.2
199.5
207.6
197.0
201.8
209.1
199.3
204.0
212.8
190.6
195.3
203.4
191.1
199.5
205.9
193.3
202.0
208.3
183.6
192.6
198.8
185.8
194.9
201.2
187.9
197.2
202.6
181.1
187.8
195.8
183.3
190.0
196.6
185.4
192.3
198.7
178.7
185.0
191.4
180.7
187.5
195.4
182.8
189.9
196.3
176.1
182.8
189.1
178.1
184.7
191.4
180.2
187.1
193.7
171.2
177.9
171.9
174.0
179.8
184.1
176.7
180.7
187.3
165.8
170.6
181.6
169.4
176.0
165.8
171.1
181.9
191.4
Heat of Rejection
(MBTUH)
305.2
322.2
342.5
309.6
326.9
348.4
313.9
332.0
353.4
297.4
313.7
333.5
299.9
319.7
338.5
304.1
324.4
344.0
288.5
306.9
324.4
292.1
311.0
329.2
296.0
315.4
334.9
282.0
298.5
314.6
285.3
302.4
319.7
288.7
306.4
324.6
278.2
294.5
311.1
281.3
298.1
314.5
284.6
301.9
319.7
274.5
290.3
306.6
277.4
293.9
310.5
280.6
297.5
314.8
267.8
282.4
304.3
269.9
285.5
299.6
272.2
289.3
305.8
260.7
276.4
288.4
261.8
277.3
300.2
264.7
277.6
292.0
Power Input (kW)
13.2
13.5
13.9
12.6
12.9
13.2
12.0
12.3
12.6
14.3
14.6
15.0
13.7
14.0
14.3
13.1
13.4
13.7
15.5
15.9
16.2
15.0
15.2
15.5
14.4
14.6
14.9
16.9
17.2
17.5
16.3
16.6
16.9
15.7
15.9
16.2
17.7
18.0
18.3
17.1
17.3
17.6
16.4
16.7
16.9
18.5
18.8
19.1
17.9
18.1
18.4
17.2
17.4
17.6
20.3
20.5
20.9
19.6
19.8
20.0
18.9
19.1
19.3
22.3
22.6
22.8
21.6
21.8
22.1
20.9
21.0
21.2
EER
19.9
20.6
21.4
21.2
22.0
22.9
22.7
23.6
24.6
17.6
18.3
19.0
18.6
19.5
20.3
19.9
20.9
21.8
15.4
16.2
16.8
16.4
17.2
18.0
17.4
18.4
19.2
13.6
14.2
14.8
14.4
15.1
15.8
15.2
16.1
16.9
12.7
13.3
13.9
13.4
14.1
14.8
14.2
15.0
15.8
11.8
12.4
13.0
12.5
13.1
13.8
13.2
14.0
14.7
10.2
10.7
11.5
10.7
11.4
11.9
11.4
12.1
12.7
8.7
9.2
9.6
9.1
9.7
10.5
9.7
10.2
10.7
27
EC SERIES POOL DEHUMIDIFIERS
CAPACITY DATA
EC300 10000 NOMINAL CFM (without Max Evap Option)
Horizontal & Vertical Configurations
Cooling
Entering Fluid
Temp (°F)
Water Flow (GPM)
37.6
50
50
75
37.6
60
50
75
37.6
70
50
75
37.6
80
50
75
37.6
85
50
75
37.6
90
50
75
37.6
100
50
75
37.6
110
50
75
28
Pressure Drop PSI
(FOH)
2.5
(5.9)
4.2
(9.8)
8.8
(20.3)
2.5
(5.7)
4.1
(9.5)
8.5
(19.6)
2.4
(5.5)
4.0
(9.1)
8.2
(19.0)
2.3
(5.3)
3.8
(8.9)
8.0
(18.4)
2.3
(5.2)
3.8
(8.7)
7.8
(18.1)
2.2
(5.1)
3.7
(8.6)
7.7
(17.8)
2.2
(5.0)
3.6
(8.3)
7.5
(17.3)
2.1
(4.8)
3.5
(8.1)
7.3
(16.8)
Entering Air Temp
(db/wb) °F
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
Total Capacity
(MBTUH)
323.5
343.9
363.9
330.2
351.3
372.5
337.2
359.0
381.7
310.8
330.5
350.5
317.4
337.6
357.9
324.2
345.5
366.5
299.3
316.3
336.7
305.7
323.6
344.7
310.7
330.6
353.1
285.5
302.1
321.4
289.9
308.4
329.1
296.6
317.1
337.2
277.8
295.4
313.5
282.8
302.3
321.6
289.3
309.3
329.0
269.7
287.8
305.4
275.6
294.5
313.0
281.4
301.4
320.6
254.5
272.5
289.5
261.1
278.5
295.6
267.1
285.1
303.5
239.8
255.9
271.4
244.8
260.8
277.7
250.6
267.0
282.7
Sensible Capacity
(MBTUH)
238.4
244.4
252.1
241.3
247.8
254.5
244.1
251.2
259.7
232.7
239.0
245.6
235.6
242.8
250.5
238.6
245.1
253.3
227.5
233.8
243.6
230.2
236.3
246.5
232.1
240.3
249.6
221.3
226.9
237.9
223.2
231.1
240.8
225.5
235.9
243.8
219.7
227.3
235.0
219.8
230.1
236.5
222.0
232.9
240.8
213.7
224.3
232.2
216.2
227.0
234.8
219.5
229.7
237.7
207.7
217.1
224.3
208.3
220.5
230.0
215.1
223.2
231.2
203.1
212.4
218.1
205.7
214.1
217.1
207.8
217.5
229.7
Heat of Rejection
(MBTUH)
385.2
407.6
429.6
390.3
413.3
436.4
395.8
419.3
443.8
375.8
397.5
419.5
380.7
402.7
424.8
385.8
408.8
431.5
368.5
387.3
409.8
373.0
392.6
415.6
375.9
397.5
421.7
359.5
377.9
399.3
361.6
381.9
404.5
366.1
388.4
410.2
354.3
373.9
394.0
357.0
378.3
399.7
361.3
383.0
404.4
349.0
369.2
388.8
352.7
373.3
393.7
356.1
377.7
398.7
340.3
360.3
379.4
344.5
363.6
382.4
348.0
367.5
387.7
333.1
351.2
368.8
335.5
353.3
372.1
338.6
356.4
373.8
Power Input (kW)
18.7
19.1
19.5
18.1
18.4
18.8
17.4
17.7
18.1
20.0
20.5
20.9
19.3
19.7
20.1
18.6
19.0
19.3
21.6
22.0
22.4
20.9
21.2
21.6
20.1
20.4
20.7
23.4
23.7
24.2
22.5
22.9
23.3
21.7
22.1
22.4
24.3
24.7
25.2
23.5
23.8
24.2
22.7
23.0
23.3
25.3
25.8
26.2
24.5
24.8
25.2
23.6
24.0
24.3
27.6
28.0
28.5
26.7
27.1
27.4
25.9
26.1
26.4
30.2
30.6
31.0
29.3
29.6
30.0
28.4
28.6
28.9
EER
17.3
18.0
18.6
18.3
19.1
19.8
19.4
20.3
21.1
15.5
16.2
16.8
16.4
17.1
17.8
17.4
18.2
19.0
13.8
14.4
15.0
14.7
15.3
16.0
15.5
16.2
17.0
12.2
12.7
13.3
12.9
13.5
14.1
13.6
14.4
15.1
11.4
12.0
12.5
12.1
12.7
13.3
12.8
13.5
14.1
10.6
11.2
11.7
11.3
11.9
12.4
11.9
12.6
13.2
9.2
9.7
10.2
9.8
10.3
10.8
10.3
10.9
11.5
7.9
8.4
8.8
8.4
8.8
9.3
8.8
9.3
9.8
Subject to change without prior notice Revised 07 - 16
EC SERIES POOL DEHUMIDIFIERS
CAPACITY DATA
EC360 12000 NOMINAL CFM (without Max Evap Option)
Horizontal & Vertical Configurations
Cooling
Entering Fluid
Temp (°F)
Water Flow (GPM)
45
50
60
90
45
60
60
90
45
70
60
90
45
80
60
90
45
85
60
90
45
90
60
90
45
100
60
90
45
110
60
90
Pressure Drop PSI
(FOH)
3.1
(7.1)
5.1 (11.9)
10.7
(24.7)
2.9
(6.8)
5.0
(11.5)
10.3
(23.8)
2.9
(6.6)
4.8
(11.1)
9.7
(23.1)
2.8
(6.4)
4.7
(10.8)
9.7
(22.3)
2.7
(6.3)
4.6
(10.6)
4.5
(22.0)
2.7
(6.2)
4.5
(10.4)
9.4
(21.6)
2.6
(6.0)
4.4
(10.1)
9.1
(21.0)
2.5
(5.9)
4.3
(9.8)
8.8
(20.4)
Entering Air Temp
(db/wb) °F
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
75/63
80/67
85/71
Total Capacity
(MBTUH)
419.8
446.2
473.3
428.5
456.1
484.3
437.6
466.0
495.7
403.7
429.3
455.6
412.4
439.0
466.4
421.3
449.0
476.9
387.1
411.8
436.3
395.4
421.2
446.7
404.2
430.9
457.6
369.6
392.9
416.9
377.7
401.9
427.7
386.1
411.3
438.2
360.7
383.3
406.8
368.6
392.2
416.9
376.8
401.4
427.3
351.6
374.2
397.3
359.3
382.9
407.0
366.8
391.9
416.6
332.4
353.8
375.7
339.7
362.1
385.8
347.7
370.7
394.8
313.6
334.0
354.6
320.5
341.3
362.9
327.4
349.8
372.0
Subject to change without prior notice Revised 07 - 16
Sensible Capacity
(MBTUH)
305.0
313.2
321.2
308.8
316.9
324.8
311.3
320.7
328.1
298.1
306.1
314.0
300.4
309.7
317.7
304.1
313.4
323.9
289.4
298.4
309.1
293.0
302.0
313.0
296.5
305.7
317.1
281.5
292.3
301.7
284.9
295.9
303.6
288.3
299.7
307.5
277.5
288.9
298.4
280.9
292.3
301.8
284.2
296.0
305.5
273.4
283.4
292.7
276.7
286.8
296.4
281.4
290.4
301.9
267.5
277.6
287.4
270.0
280.7
288.6
271.9
283.9
293.9
257.8
268.3
277.8
260.9
273.0
283.0
264.0
274.1
286.0
Heat of Rejection
(MBTUH)
494.5
523.6
553.3
501.6
531.7
562.5
509.2
540.0
572.2
482.0
510.3
539.3
488.8
517.9
547.9
495.9
526.0
556.2
469.7
497.0
524.1
475.9
504.1
532.1
482.5
511.6
540.6
457.4
483.2
509.9
463.0
489.6
518.0
469.1
496.5
525.9
451.3
476.4
502.7
456.7
482.6
509.8
462.4
489.2
517.4
445.4
470.6
496.4
450.4
476.5
503.1
455.3
482.7
509.6
433.1
457.1
481.8
437.6
462.4
488.7
442.8
468.0
494.4
422.8
445.8
469.2
426.5
449.7
473.8
430.5
455.0
479.5
Power Input (kW)
22.9
23.4
23.9
22.1
22.5
23.0
21.3
21.7
22.1
24.5
25.0
25.6
23.7
24.1
24.6
22.8
23.2
23.6
26.4
26.9
27.4
25.5
25.9
26.3
24.5
24.9
25.3
28.5
29.0
29.5
27.5
27.9
28.4
26.5
26.9
27.3
29.7
30.2
30.7
28.7
29.1
29.5
27.7
28.0
28.4
30.9
31.4
31.9
29.9
30.3
30.7
28.8
29.2
29.5
33.6
34.1
34.6
32.6
32.9
33.4
31.5
31.8
32.1
36.8
37.2
37.7
35.6
36.0
36.4
34.5
34.8
35.1
EER
18.3
19.1
19.8
19.4
20.2
21.1
20.6
21.5
22.4
16.5
17.2
17.8
17.4
18.2
19.0
18.5
19.4
20.2
14.7
15.3
15.9
15.5
16.3
17.0
16.5
17.3
18.1
13.0
13.6
14.1
13.7
14.4
15.1
14.6
15.3
16.1
12.1
12.7
13.3
12.9
13.5
14.1
13.6
14.3
15.1
11.4
11.9
12.5
12.0
12.6
13.3
12.7
13.4
14.1
9.9
10.4
10.9
10.4
11.0
11.6
11.1
11.7
12.3
8.5
9.0
9.4
9.0
9.5
10.0
9.5
10.1
10.6
29
EC SERIES POOL DEHUMIDIFIERS
ELECTRICAL DATA
Belt Drive Motor
Model
EC072
Voltage
Code
Voltage/
Ph/Hz
1
208-230/1/60
Compressor
Voltage
Min/Max
197/253
Belt Drive Motor
Quantity
RLA
LRA
Motor
Quantity
FLA
2
13.0
74
1
7
Compressor Services
Total Unit
Min Circuit Max Fuse
Amps
Amps
36.3
45
Cold Wind Resistance
Single
Phase R-C
Single
Phase S-C
Three
Phase
Line-Line
0.82
1.63
-
Run
Capacitor
(μF/V)
40/370*
3
208-230/3/60
197/253
2
7.8
68
1
3.6
21.2
25
-
-
1.15
-*
4
460/3/60
414/506
2
3.9
34
1
1.8
10.6
15
-
-
4.61
-*
1
208-230/1/60
197/253
2
15.7
84
1
8.4/9.8*
47.6/45.1*
50/60*
0.54
1.60
-
45/370*
3
208-230/3/60
197/253
2
11.0
88
1
4.8/6.2*
29.5/31.0*
40/40*
-
-
0.93
-*
EC096
4
460/3/60
414/506
2
5.4
44
1
2.4/3.1*
14.6/15.2*
15/20*
-
-
3.59
-*
5
575/3/60
518/632
2
4.4
36
1
2.0/2.6*
11.9/12.5*
15/15*
-
-
5.68
-*
1
208-230/1/60
197/253
2
26.3
134
1
9.8
69.0
90
0.45
0.79
-
80/370*
3
208-230/3/60
197/253
2
15.6
110
1
6.2/9.2*
41.3/44.3*
50/50*
-
-
0.68
-
EC120
EC150
EC151
EC180
EC181
EC210
EC240
EC242
EC300
EC360
4
460/3/60
414/506
2
7.8
52
1
3.1/4.3*
20.6/21.9*
25/25*
-
-
3.20
-
5
575/3/60
518/632
2
5.8
39
1
2.6/3.7*
15.7/16.8*
20/20*
-
-
5.33
-
3
208-230/3/60
197/253
2
19.2
136
1
9.2
52.4
70
-
-
0.60
-
4
460/3/60
414/506
2
8.7
66
1
4.3
23.9
30
-
-
2.52
-
5
575/3/60
518/632
2
6.9
55
1
3.7
19.2
25
-
-
3.74
-
3
208-230/3/60
197/253
2
19.2
136
1
9.2
52.4
70
-
-
0.60
-
4
460/3/60
414/506
2
8.7
66
1
4.3
23.9
30
-
-
2.52
-
5
575/3/60
518/632
2
6.9
55
1
3.7
19.2
25
-
-
3.74
-
3
208-230/3/60
197/253
2
22.4
149
2
6.2
62.8
80
-
-
0.56
-
4
460/3/60
414/506
2
10.6
75
2
3.2
30.1
40
-
-
2.27
-
5
575/3/60
518/632
2
7.7
54
2
2.6
22.5
30
-
-
3.56
-
3
208-230/3/60
197/253
2
22.4
149
1
12.2
62.6
80
-
-
0.56
-
4
460/3/60
414/506
2
10.6
75
1
6.1
30.0
40
-
-
2.27
-
5
575/3/60
518/632
2
7.7
54
1
5.4
22.7
30
-
-
3.56
-
3
208-230/3/60
197/253
2
29.5
195
2
4.8
76.0
100
-
-
0.40
-
4
460/3/60
414/506
2
14.7
95
2
2.4
37.9
50
-
-
1.59
-
5
575/3/60
518/632
2
12.2
80
2
2
31.5
40
-
-
2.55
-
3
208-230/3/60
197/253
2
30.1
225
2
6.2
80.1
110
-
-
0.35
-
4
460/3/60
414/506
2
16.7
114
2
3.1
43.8
60
-
-
1.36
-
5
575/3/60
518/632
2
12.2
80
2
2.6
32.6
40
-
-
2.55
-
3
208-230/3/60
197/253
2
30.1
225
2
6.2
80.1
110
-
-
0.35
-
4
460/3/60
414/506
2
16.7
114
2
3.1
43.8
60
-
-
1.36
-
5
575/3/60
518/632
2
12.2
80
2
2.6
32.6
40
-
-
2.55
-
3
208-230/3/60
197/253
2
48.1
245
2
9.2
126.6
150
-
-
0.28
-
4
460/3/60
414/506
2
18.6
125
2
4.3
50.5
60
-
-
1.24
-
5
575/3/60
518/632
2
14.7
100
2
3.7
40.5
50
-
-
1.88
-
3
208-230/3/60
197/253
2
55.8
340
2
12.2
150.0
200
-
-
0.21
-
4
460/3/60
414/506
2
26.9
173
2
6.1
72.7
90
-
-
0.83
-
5
575/3/60
518/632
2
23.7
132
2
5.4
64.1
80
-
-
1.27
-
NOTES: *First value is for vertical configurations and second value is for horizontals. Resistance value tolerance +/- 7%. All resistance values
must be measured with compressor at room temperature.
30
Subject to change without prior notice Revised 07 - 16
EC SERIES POOL DEHUMIDIFIERS
BLOWER MOTOR PERFORMANCE
Belt Drive Motor
Model
Motor
Sheave
Rated
Airflow
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
1.00
1.10
1.20
–
–
–
–
–
–
–
–
2420
2160
1900
1700
–
–
2980
2800
2610
2400
2100
1800
–
–
–
–
Open
2780
2590
2350
2050
1780
–
–
–
–
–
–
–
Closed
–
–
–
–
–
–
–
2800
2650
2450
2300
2200
Closed
EC072
EC096
EC120
Half Open
2,300
–
–
3480
3340
3230
3075
2880
2690
2555
2355
–
–
Open
3110
2965
2835
2615
2460
2275
–
–
–
–
–
–
Closed
–
–
–
–
–
–
–
–
4400
4150
3830
3600
–
–
–
4660
4490
4240
3959
4600
3000
–
–
–
4680
4490
4270
4000
3700
3370
–
–
–
–
–
–
Half Open
Half Open
2,800
4,000
Open
–
–
–
–
–
–
7120
6920
6530
6080
5660
5120
–
–
–
6860
6530
6120
5780
5380
4880
4090
–
–
Open
6770
6300
5880
5430
4970
4340
3750
–
–
–
–
–
Closed
–
–
–
–
–
–
7120
6920
6530
6080
5660
5120
–
–
–
6860
6530
6120
5780
5380
4880
4090
–
–
6770
6300
5880
5430
4970
4340
3750
–
–
–
–
–
–
–
–
–
–
–
7200
6940
6560
6150
5710
5140
–
–
7200
6930
6580
6200
5800
5450
4920
–
–
–
Open
6780
6350
5970
5540
5050
4510
–
–
–
–
–
–
Closed
–
–
–
–
–
–
7200
6940
6560
6150
5710
5140
–
–
7200
6930
6580
6200
5800
5450
4920
–
–
–
Open
6780
6350
5970
5540
5050
4510
–
–
–
–
–
–
Closed
–
–
–
–
–
–
–
–
–
–
7800
7500
–
–
–
–
–
8600
8200
7600
6900
5240
–
–
Open
8840
8400
8000
7560
7000
6400
–
–
–
–
–
–
Closed
–
–
–
–
–
–
–
–
9000
8800
8330
7660
7200
6000
–
–
Closed
EC150
EC151
Half Open
Half Open
5,000
5,000
Open
Closed
EC180
EC181
EC210
EC240
EC242
EC300
Half Open
Half Open
Half Open
6,000
6,000
7,000
–
–
–
–
9320
8980
8480
7900
Open
9360
8980
8540
8000
7400
6740
–
–
–
–
–
–
Closed
–
–
–
–
–
–
–
–
–
–
8120
7500
–
–
–
–
–
–
8280
7700
7000
5800
–
–
Open
–
–
8340
7800
7200
6540
–
–
–
–
–
–
Closed
–
–
–
–
10000
9650
9300
8950
8600
8200
–
–
–
10500
10100
9700
8900
8500
8100
–
–
–
–
–
9900
9100
8700
8300
–
–
–
–
–
–
–
–
Half Open
Half Open
Half Open
8,000
8,000
10,000
Open
Model
Motor
Sheave
Rated
Airflow
Closed
EC360
External Static Pressure (in wc Wet coil and filter included)
Half Open
Open
12,000
External Static Pressure (in wc Wet coil and filter included)
0.2
0.3
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
2.2
–
–
–
–
–
–
–
–
–
–
12900
10800
–
–
–
–
–
13050
11850
10350
7500
–
–
–
12200
11575
10950
9600
7800
–
–
–
–
–
–
–
Subject to change without prior notice Revised 07 - 16
31
EC SERIES POOL DEHUMIDIFIERS
PHYSICAL DATA
EC Model
EC Model
Compressor Type (Qty 2)
Refrigeration Charge (oz)*
Max Water Working Pressure (PSIG/kPa)
Number of Refrigeration Circuits
EC072
EC096
EC120
EC150
EC151
EC180
Reciprocating
Reciprocating
Scroll
Scroll
Scroll
Scroll
124
148
166
204
194
234
450/3100
450/3100
450/3100
450/3100
450/3100
450/3100
2
2
2
2
2
2
Tube-Fin
Evaporator Coil
Coil Type
Tube-Fin
Tube-Fin
Tube-Fin
Tube-Fin
Tube-Fin
Air Coil Dimensions Vertical (H x L)
18 x 28 (2)
20 x 32.5 (2)
20 x 32.5 (2)
-
24 x 43 (2)
-
Air Coil Dimensions Horizontal (H x L)
18 x 28 (2)
20 x 32.5 (2)
20 x 32.5 (2)
24 x 65
-
24 x 65
3
3
3
3
3
3
Belt Drive/1
Belt Drive/1
Belt Drive/1
Belt Drive/1
Belt Drive/1
Belt Drive/2
1x1
1 1/2 x 1
(2 x 1 for HZ)
2x1
(3 x 1 for HZ)
3x1
3x1
2x2
12 x 12 x 1
12 x 12 x 1
12 x 9 x 2 for HZ
15 x 15 x 1 for VT
15 x 15 x 1
15 x 15 x 1
12 x 12 x 2
Connection Type
FPT
FPT
FPT
FPT
FPT
FPT
Size
1"
1"
1 1/4"
1 1/2"
1 1/2"
1 1/2"
Coaxial
Coaxial
Coaxial
Coaxial
Coaxial
Coaxial
0.42
0.64
0.87
1.06
1.06
1.06
Row(s)
Motor & Blower
Fan Motor Type/Speeds
Fan Motor (HP x Qty)
Blower Wheel Size (Dia. x W x Qty)
Water Coil
Water Coil Type
Coil Volume (gal)
Vertical Cabinet
20 x 34.5 (2)
20 x 34.5 (2)
20 x 34.5 (2)
-
24 x 24 (4)
-
Weight - Operating (lbs)
Nominal size of Standard Filter - 1" (H x L)
670
702
935
-
1050
-
Weight - Shipping (lbs)
715
752
980
-
1140
-
Horizontal Cabinet
Nominal size of Standard Filter - 1" (H x L)
20 x 34.5 (2)
20 x 34.5 (2)
20 x 34.5 (2)
24 x 34 (2)
-
24 x 34 (2)
Weight - Operating (lbs)
670
702
935
1060
-
1530
Weight - Shipping (lbs)
715
752
980
1150
-
1620
EC Model
EC181
EC210
EC240
EC242
EC300
EC360
Compressor Type (Qty 2)
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Refrigeration Charge (oz)
224
260
290
290
290
576
450/3100
450/3100
450/3100
450/3100
450/3100
450/3100
2
2
2
2
2
2
Max Water Working Pressure (PSIG/kPa)
Number of Refrigeration Circuits
Evaporator Coil
Coil Type
Air Coil Dimensions Vertical (H x L)
Tube-Fin
Tube-Fin
Tube-Fin
Tube-Fin
Tube-Fin
Tube-Fin
24 x 43 (2)
20 x 32.5 (4)
20 x 32.5 (4)
-
20 x 32.5 (4)
30 x 32.5 (2)
Air Coil Dimensions Horizontal (H x L)
-
-
-
34 x 65
-
-
Row(s)
3
3
3
3
3
3
Belt Drive/1
Belt Drive/2
Belt Drive/2
Belt Drive/2
Belt Drive/2
Belt Drive/2
5x1
1 1/2 x 2
2x2
2x2
3x2
5x2
15 x 15 x 1
15 x 15 x 2
15 x 15 x 2
15 x 15 x 2
15 x 15 x 2
15 x 15 x 2
FPT
Motor & Blower
Fan Motor Type/Speeds
Fan Motor (HP x Qty)
Blower Wheel Size (Dia. x W x Qty)
Water Coil
Connection Type
FPT
FPT
FPT
FPT
FPT
Size
1 1/2"
2"
2"
2"
2"
2"
Water Coil Type
Coaxial
Coaxial
Coaxial
Coaxial
Coaxial
Coaxial
1.06
3.04
3.40
3.40
3.40
3.31
Coil Volume (gal)
Vertical Cabinet
Nominal size of Standard Filter - 1" (H x L)
24 x 24 (4)
20 x 34.5 (4)
20 x 34.5 (4)
-
20 x 34.5 (4)
30 x 34.5 (4)
Weight - Operating (lbs)
1090
1090
1310
-
1530
1650
Weight - Shipping (lbs)
1180
1180
1400
-
1630
1750
Horizontal Cabinet
Nominal size of Standard Filter - 1" (H x L)
-
-
-
17.25 x 34.5 (4)
-
-
Weight - Operating (lbs)
-
-
-
1655
-
-
Weight - Shipping (lbs)
-
-
-
1755
-
-
*Refrigerant charge total
32
Subject to change without prior notice Revised 07 - 16
EC SERIES POOL DEHUMIDIFIERS
HORIZONTAL CABINET CORNER WEIGHTS
Configuration
Left Hand Evaporator
Model
Lbs
kg
Lbs
kg
Lbs
kg
Lbs
kg
Lbs
kg
Lbs
kg
EC072
EC096
EC120
EC150
EC180
EC242
Total
Left
Front*
Right
Front*
Left
Back
Right
Back
670
305
702
319
935
425
1060
482
1530
695
1655
752
147
67
155
70
206
94
233
106
337
153
365
166
274
125
287
130
382
174
434
197
626
285
677
308
137
62
143
65
191
87
216
98
312
142
337
153
112
51
117
53
156
71
177
80
255
116
276
125
* Front is control box end.
VERTICAL UNIT DIMENSIONS
Rear Supply: Supply Height
Rear Supply: Supply Width
Rear Supply: Top to Supply
Water In
R/A Duct Width
24.00
6.00
9.00
17.50
28.00
2.00
7.00
14.75
8.50
2.75
34.00
38.00
40.00
1'' FPT
3/4" FPT
20 x 34.5 (2)
20.00
24.00
6.00
9.00
17.50
28.00
2.00
7.00
14.75
8.50
2.75
34.00
38.00
40.00
1'' FPT
3/4" FPT
20 x 34.5 (2)
EC120
42.00
32.00
62.00
22.00
20.00
24.00
6.00
9.00
17.50
28.00
2.00
7.00
15.00
9.00
3.00
34.00
38.00
40.00
1 1/4'' FPT
3/4" FPT
20 x 34.5 (2)
Recommended
Connection
Condensate Drain
Connections
Condenser Water
E
Filter Rack Height
D
Height
C
R/A Duct Flange
Bottom to
Condensate Drain
Water Out
to Supply
B
Filter Size - 1" Thick
Top Supply: Front to Supply
20.00
22.00
A
Replacement Nominal
Top Supply: Supply Width
22.00
62.00
Rear Supply: Right Side
Top Supply: Supply Depth
62.00
32.00
Supply
Height
32.00
42.00
Top Supply: Left Side to
Depth
42.00
EC096
Rails
Width
EC072
Distance Between Base
Model
EC072-120 Single Blower Large Vertical
NOTE: All dimensions in inches unless otherwise noted. All dimensions within +-0.125”. Specifications subject to change without notice.
Service Access | Access to:
1
2
3
Controls, Compressors, Refrigeration Components
Blower & Motor
Blower
Figure 11
Subject to change without prior notice Revised 07 - 16
33
EC SERIES POOL DEHUMIDIFIERS
VERTICAL UNIT DIMENSIONS
Rear Supply: Supply Height
Rear Supply: Supply Width
Rear Supply: Top to Supply
Water In
R/A Duct Width
24.00
5.00
17.50
17.50
28.00
2.00
12.12
17.00
10.50
3.00
44.25
48.00
50.00
1 1/2'' FPT
3/4" FPT
24 x 24 (4)
EC181
52.50
32.00
70.00
22.00
20.00
24.00
5.00
17.50
17.50
28.00
2.00
12.12
17.00
10.50
3.00
44.25
48.00
50.00
1 1/2'' FPT
3/4" FPT
24 x 24 (4)
Recommended
Connection
Condensate Drain
Connections
Condenser Water
E
Filter Rack Height
D
Height
C
R/A Duct Flange
Bottom to
Condensate Drain
Water Out
to Supply
B
Filter Size - 1" Thick
Top Supply: Front to Supply
20.00
A
Replacement Nominal
Top Supply: Supply Width
22.00
Rear Supply: Right Side
Top Supply: Supply Depth
70.00
Supply
Height
32.00
Top Supply: Left Side to
Depth
52.50
Rails
Width
EC151
Distance Between Base
Model
EC151-181 Single Blower Large Vertical
NOTE: All dimensions in inches unless otherwise noted. All dimensions within +-0.125”. Specifications subject to change without notice.
Service Access
Access to:
1
2
3
Controls, Compressors,
Refrigeration Components
Blower & Motor
Blower
Figure 12
34
Subject to change without prior notice Revised 07 - 16
EC SERIES POOL DEHUMIDIFIERS
VERTICAL UNIT DIMENSIONS
14.00 17.50 28.00
2.00
7.00
10.00 18.00
8.75
2.75
34.00
4.50
40.00 38.00
2'' FPT
1 1/4'' FPT
20 x 34.5 (4)
EC300 80.00 32.00 66.50 22.00 20.00 24.00
6.00
9.00
14.00 17.50 28.00
2.00
7.00
10.00 18.00
8.75
2.75
34.00
4.50
40.00 38.00
2'' FPT
1 1/4'' FPT
20 x 34.5 (4)
EC360 80.00 32.00 86.50 22.00 20.00 24.00
6.00
9.00
14.00 17.50 28.00
2.00
7.00
10.00 17.00
9.00
3.50
34.00
4.50
60.00 58.00
2'' FPT
1 1/4'' FPT
30 x 34.5 (4)
Recommended
Connection
Condensate Drain
Connections
Condenser Water
E
Filter Rack Height
D
Height
C
R/A Duct Flange
Bottom to
Condensate Drain
Water Out
b/t Supply Ducts
B
Filter Size - 1" Thick
Distance Between R/A Ducts
9.00
A
Replacement Nominal
R/A Duct Width
6.00
to Supply
Rear Supply: Distance
EC240 80.00 32.00 66.50 22.00 20.00 24.00
Rear Supply: Right Side
20 x 34.5 (4)
Rear Supply: Top to Supply
1 1/4'' FPT
Rear Supply: Supply Width
2'' FPT
b/t Supply Ducts
40.00 38.00
Rear Supply: Supply Height
4.50
Supply
Top Supply: Distance
34.00
Top Supply: Left Side to
2.75
Top Supply: Front to Supply
8.75
Top Supply: Supply Width
10.00 18.00
Top Supply: Supply Depth
7.00
Rails
2.00
Height
14.00 17.50 28.00
Distance Between Base
9.00
Depth
6.00
Width
EC210 80.00 32.00 62.00 22.00 20.00 24.00
Model
Water In
EC210-360 Dual Blower Large Vertical
NOTE: All dimensions in inches unless otherwise noted. All dimensions within +-0.125”. Specifications subject to change without notice.
Service Access
Access to:
Front Return
Optional Blower
Orientation (979-033)
1
2
3
Controls, Compressors,
Refrigeration Components
Blower & Motor
Blower
Standard Blower
Orientation
Top Supply (FFT)
Rear Supply (FFR)
Optional Blower
Orientation (979-033)
Rear Return
Standard Blower
Orientation
Figure 13
Front Supply (FBF)
Subject to change without prior notice Revised 07 - 16
Top Supply (FBT)
35
EC SERIES POOL DEHUMIDIFIERS
HORIZONTAL UNIT DIMENSIONS
Filter Size - 1" Thick
28.00
2.75
28.00
14.50
15.50
13.50
10.50
5.50
1'' FPT
3/4" FPT
20 x 34.5 (2)
EC096
38.00
78.00
21.50
2.00
20.50
18.50
66.00
26.25
3.50
28.00
19.25
15.50
13.50
10.50
5.50
1'' FPT
3/4" FPT
20 x 34.5 (2)
EC120
38.00
78.00
21.50
2.00
20.50
18.50
66.00
27.50
3.38
28.00
16.75
12.50
13.50
5.25
5.50
1 1/4'' FPT
3/4" FPT
20 x 34.5 (2)
EC150
42.00
82.00
26.75
2.00
20.50
18.50
66.00
24.00
2.75
24.00
17.75
18.50
16.00
14.00
5.50
1 1/2'' FPT
3/4" FPT
24 x 34 (2)
Recommended
66.00
Connection
18.50
Condensate Drain
20.50
Connections
2.00
Condenser Water
Rear to Supply
21.50
Distance b/t
Supply Height
78.00
Supply Ducts
Supply Width
38.00
Width
EC072
R/A Duct
Water Out Height
M
Front to Water Out
L
Water In Height
K
Front to Water In
J
R/A Duct Flange Height
H
Filter Rack Height
G
Cab End to Filter Rack
F
Height
E
Depth
C
Width
B
Model
A
Replacement Nominal
EC072-150 Large Horizontal
NOTE: All dimensions in inches unless otherwise noted. All dimensions within +-0.125”. Specifications subject to change without notice.
Service Access
Access to:
1
2
3
Controls, Compressors,
Refrigeration Components
Blower & Motor
Blower
Figure 14
36
Subject to change without prior notice Revised 07 - 16
EC SERIES POOL DEHUMIDIFIERS
HORIZONTAL UNIT DIMENSIONS
Filter Size - 1" Thick
22.00
6.25
22.00
16.00
27.75
17.25
5.00
4.00
1 1/2'' FPT
1 1/4'' FPT
24 x 34 (2)
EC242
60.25
106.50
36.00
2.00
34.75
32.75
67.00
24.50
7.25
24.50
19.62
23.75
19.75
7.75
9.75
2'' FPT
1 1/4'' FPT
17.25 x 34.5 (4)
Recommended
67.00
Connection
22.00
Condensate Drain
24.00
Connections
2.00
Condenser Water
Rear to Supply
25.25
Distance b/t
Supply Height
106.50
Supply Ducts
Supply Width
60.25
Width
EC180
R/A Duct
Water Out Height
M
Front to Water Out
L
Water In Height
K
Front to Water In
J
R/A Duct Flange Height
H
Filter Rack Height
G
Cab End to Filter Rack
F
Height
E
Depth
C
Width
B
Model
A
Replacement Nominal
EC180-242 Large Horizontal
NOTE: All dimensions in inches unless otherwise noted. All dimensions within +-0.125”. Specifications subject to change without notice.
Service Access
Access to:
1
2
3
Controls, Compressors,
Refrigeration Components
Blower & Motor
Blower
Figure 15
Subject to change without prior notice Revised 07 - 16
NOTE: SLS only.
37
EC SERIES POOL DEHUMIDIFIERS
SERVICE CLEARANCES
EC072 thru 181 Large Vertical
NOTE: * Blower motor and Blower housing access is required on BOTH SIDES of the unit
*Blower Wheel/Housing
18" Minimum
24" Optimum
Blower
*Blower Motor
Sheave/Pulley/Belt Access
18" Minimum
24" Optimum
Compressor
Figure 16
Compressor Accesss and
Electrical/Control Access
36" Minimum
Electrical
Control
Box
Front of Unit
EC210 thru 360 Large Vertical
NOTE: * Blower motor and Blower housing access is required on BOTH SIDES of the unit
*Blower Wheel/Housing
18" Minimum
24" Optimum
*Blower Wheel/Housing
18" Minimum
24" Optimum
*Blower Motor
Sheave/Pulley/Belt Access
18" Minimum
24" Optimum
Blower
Blower
Motor
*Blower Motor
Sheave/Pulley/Belt Access
18" Minimum
24" Optimum
Blower
Motor
Compressor
Figure 17
Blower
Compressor
Electrical
Control
Box
Compressor Access and
Electrical/Control Access
36" Minimum
Front of Unit
EC072 thru 150 Large Horizontal
Electrical
Control
Box
Electrical/Compressor Access
36" Minimum
Air Coil
Blower
Blower
Motor
Compressors
Figure 18
Compressor/Refrigerant Access
36" Minimum
EC180 thru 242 Large Horizontal
Compressor/Refrigerant Access
36" Minimum
Electrical
Control
Box
Electrical/Compressor Access
36" Minimum
Compressors
Air Coil
Blower
Motor
Blower
Blower
Motor
Blower Access
24" Minimum
Blower
Figure 19
NOTE: The local electric codes may require 36" or more clearance at all electrical control boxes.
38
Subject to change without prior notice Revised 07 - 16
EC SERIES POOL DEHUMIDIFIERS
GUIDE SPECIFICATIONS
General
Furnish and install DXair dehumidifier as indicated on the
plans with capacities and characteristics as listed in the
schedule and the specifications that follow. The units shall
be manufactured in an ISO 9001 certified facility.
Horizontal/Vertical Dehumidifiers
DXair dehumidifiers shall be designed to operate
throughout the range of entering fluid temperature of
50°F to 110°F in the cooling mode.
All equipment in this section must meet or exceed the DOE
mandated minimum EERs as listed in ASHRAE 90.1.
Basic Construction
Units shall have the air flow arrangement as shown on the
plans. If units with these arrangements are not used, the
contractor supplying the DXair dehumidifier is responsible
for any extra costs incurred by other trades and must
submit detailed mechanical drawings showing ductwork
requirements and changes or relocation of any other
mechanical or electrical system. If other arrangements
make servicing difficult the contractor must provide access
panels and clear routes to ease service. The architect must
approve all changes 10 days prior to bid.
All DXair dehumidifiers shall have stainless steel drain pans
to comply with this project’s IAQ requirements. Painted/
coated steel or plastic material shall not be permitted.
All DXair dehumidifiers shall be fabricated from heavygauge sheet metal steel. All interior surfaces shall be lined
with ½" thick, multi density acoustic insulation. Insulation
within the air handling section shall not have any exposed
edges. All insulation must meet NFPA 90A, UL 181 and be
certified to meet the GreenGuard™ Indoor Air Quality
Standard for Low Emitting Products. One blower access
panel and two compressor compartment access panels
shall be removable with supply and return air ductwork in
place.
Unit compressors shall have rubber isolators to the prevent
transmission of vibration to the structure.
Subject to change without prior notice Revised 07 - 16
All units shall have a factory installed two sided filter rack
capable of accepting one inch filters. Units shall have a 1"
thick throwaway type glass fiber filter as standard. The
filter rack shall incorporate a 1" duct flange. The
contractor shall purchase one spare set of filters and
replace factory-shipped filters upon completion of start-up.
Cabinets shall have separate holes and knockouts for
entrance of line voltage and low voltage control wiring.
Supply and return liquid connections shall be copper FPT
fittings and shall be securely mounted flush to the cabinet
allowing for connection to a flexible hose without the use
of a back-up wrench. Liquid connections which protrude
through the cabinet shall not be allowed.
Condensate overflow protection shall be provided as
standard for horizontal and vertical package units.
Fan and Motor Assembly
The fan(s) shall be belt driven DWDI forward curved type
with dynamically balanced wheel(s). The fan motor(s) shall
be 1725 or 3450 RPM 56 frame sealed ball bearing type.
The motor(s) shall be permanently lubricated and have
thermal overload protection.
The fan and motor assembly must be capable of
overcoming the external static pressures as shown on the
schedule. External static pressure rating of the unit shall be
based on a wet coil. Ratings based on a dry coil shall NOT
be acceptable.
Refrigerant Circuit
Units shall use R-410A refrigerant. Units that use R-22
refrigerant shall not be allowed.
All units shall have a factory sealed and fully charged
refrigerant circuit with the following components:
A. Hermetic compressor: Hermetic reciprocating, or scroll
compressors shall be specifically designed for R-410A
refrigerant and shall be internally sprung (if
reciprocating), externally isolated and with thermal
overload protection.
39
EC SERIES POOL DEHUMIDIFIERS
GUIDE SPECIFICATIONS
B. Refrigerant metering thermal expansion valves.
Electrical
C. Finned tube refrigerant to air heat exchanger.
Refrigerant to air heat exchangers shall utilize
enhanced aluminum fins and rifled copper tube
construction rated to withstand 600 PSIG refrigerant
working pressure. All air coils shall have non-ferrous
aluminum end plates.
A control box shall be located within the unit and shall
contain a transformer, controls for the compressor,
reversing valve and fan motor operation and shall have a
terminal block for low voltage field wiring connections.
The transformer shall be rated for a minimum 100VA. All
units shall be name-plated for use with time delay fuses or
HACR circuit breakers. Unit controls shall be 24 volts.
D. DuoGuard™ Coil Protection System – A corrosion
protection option for refrigerant to air heat exchangers
that features tin plating of the copper tubing and
coating of the aluminum fins with a protective film.
The tin plating shall provide best in class protection of
the copper tubing from formicary corrosion while the
fin coating provides protection against salt spray and
other corrosive elements. DuoGuard™ protected coils
will exceed 1000 hours salt spray per ASTM standard
B-117.
E. Coaxial (tube in tube) refrigerant to liquid heat
exchanger. Refrigerant to liquid heat exchangers shall
be of copper inner water tube and steel outer
refrigerant tube design rated to withstand 600 PSIG
working refrigerant pressure and 400 PSIG working
liquid pressure.
F. Cupro-nickel water coil (option) – The refrigerant to
liquid heat exchanger shall be of cupro-nickel inner
liquid tube construction.
G. Safety controls including both a high pressure and low
pressure switch shall be provided on both circuits.
Temperature sensors shall not replace these safety
switches. See the controls section of this specification
for additional information.
H. Access fittings shall be factory installed on high and
low pressure refrigerant lines to facilitate field service.
I.
Activation of any safety device shall prevent
compressor operation via a lockout circuit, in the
affected circuit. The lockout circuit shall be reset at the
thermostat or at the contractor supplied disconnect
switch. Units which may be reset at the disconnect
switch only shall not be acceptable. A condensate
alarm on package units shall prevent both compressors
from operating.
J. Service valves on split system condensing sections
must incorporate a Schrader service port to facilitate
field service.
40
Solid-State Safety Circuit
All DXair dehumidifiers shall have a solid-state UPM safety
control circuit with the following features:
1. Freeze Protection: the optional freeze protection
sensor shall be mounted close to the water coil to
monitor refrigerant temperature between water coil
and the thermal expansion valve for all horizontal and
vertical package units.
2. The refrigerant to air coil shall have a sensor mounted
after the expansion valve to monitor refrigeration and
temperature. Should the temperature drop below the
set point, the compressor shall be disabled.
3. Condensate overflow protection: A condensate sensor
shall activate the lockout circuit upon sensing a high
level of condensate in the drain pan and immediately
put the unit into a hard lockout.
4. Anti-short cycle time delay on compressor operation.
5. Random start on power up mode.
6. Brown out/Surge/Power Interruption protection.
7. Low Pressure Switch 120 second bypass timer.
8. Shutdown on high or low refrigerant pressure safety
switch inputs, and shutdown for the optional
freezestat or high level condensate sensor.
9. Alarm output which closes for selectable dry contact
closure or 24 VAC remote fault indication.
10. Alarm output selectable for constant output for
general alarm notification, or pulse output for
annunciation of the specific fault alarm.
11. Reset unit at thermostat or disconnect.
Subject to change without prior notice Revised 07 - 16
EC SERIES POOL DEHUMIDIFIERS
GUIDE SPECIFICATIONS
12. Automatic intelligent reset. Unit shall automatically
reset after a safety shut down and restart the unit after
the anti-short cycle timer and random start timer
expire. Should a fault re-occur within 60 minutes after
reset, then a permanent lockout will occur. Reset
attempts shall be selectable for either 2 or 4 tries.
Condensate overflow shall put the unit into a hard
lockout on the first fault.
13. Ability to defeat time delays for servicing.
14. A light emitting diode (LED) to indicate safety alarms
shall be provided for each circuit. The LED shall
annunciate the following alarms: high refrigerant
pressure, low refrigerant pressure, low liquid
temperature, a high level of condensate in the drain
pan, or brown out/surge/ power interruption. The LED
will display each fault condition as soon as the fault
occurs. If a permanent lockout occurs, then the fault
LED will display the type of fault until the unit is reset.
15. 1.ETL listed, and RFI, ESD, and transient protected.
Options
A. Extra quiet construction: Optional compressor blankets
shall be provided on units, for additional sound
attenuation.
B. Hot Gas Reheat: Vertical or horizontal package units as
noted on the schedule shall be equipped with optional
Hot Gas Reheat (HGRH). HGRH shall be either on/off
control as noted in the specifications.
On/Off HGRH shall be controlled by a humidistat
connected to the unit H terminal and shall start the unit in
the reheat mode should the humidity be above setpoint
once the thermostat control is satisfied.
Other Factory Installed Options:
• Relays
• Phase protection monitor
• Phase monitor
• Fire alarm/dual power
• Boilerless control
Subject to change without prior notice Revised 07 - 16
41
EC SERIES POOL DEHUMIDIFIERS
UNIT LOCATION
SOUND
DO NOT STORE pool equipment and/or pool chemicals in
the mechanical space designed for the DXair
Dehumidification System. Failure to follow these
instructions may void your warranty as chemicals are highly
corrosive and destructive to any HVAC system.
Sound is becoming an increasingly important factor in all
HVAC Installations. Most of the problems associated with
HVAC generated noise can be avoided by paying close
attention to the equipment placement in properly designed
mechanical space and the duct work/air delivery system.
Any mechanical device will, at some point in time, require
servicing and repair. With this in mind, sufficient mechanical
space must be designed and sufficient clearances around
each horizontal and vertical unit must be provided. 30-36”
clearance is required around the unit and access panels. This
equipment is not recommended to be located or installed in
the pool room above an open pool, closets, crawl spaces
without the proper access, “trap” door type accessible
spaces. The proper space must be allocated to install the
system, clearances required, peripheral installation,
ductwork and bypass installation. Failure to provide the
appropriate space may void your warranty.
Proper clearances for installation of peripherals and space
must be allowed for the proper duct work installation.
Choking down ductwork in this mechanical space will have
negative air flow effects for your pool room. Sufficient space
must be provided for filter replacement and access to the
compressors. Units should be set on a piece of rubber,
neoprene or other vibration absorbing material at least 1/3½” thick. The pad should extend ¾” over the entire base of
the unit. Avoid direct line of sight to the unit. Install a sound
baffle over any door that has a return air grille.
Horizontal units are typically suspended above the ceiling
by four (field supplied) 3/8” threaded rods fastened to the
unit by factory supplier hanger bracket kits. This kit
includes rubber isolators to help prevent transmission of
vibration and noise to the building structure. Units should
be located directly below a structural member, so that it is
securely anchored. A horizontal unit always requires the
proper clearances (18” clearance on either side of the unit
for service and 36” in the front of the unit for maintenance
access). The filter needs to be slid out and sufficient space
must be provided to allow this.
Do not install any unit above any piping or electrical
raceways. This unit must be able to be removed at any time
without major re-arrangement of other mechanical or
ceiling components.
42
NEGATIVE PRESSURE
A negative pressure fan must be installed in the pool room
to prevent moisture migration. This is mandatory for all
indoor pool room environments.
DUCT AIR DELIVERY SYSTEM
DXair requires a very high standard of duct systems for our
equipment. All specifications for the air delivery system
must be met and all ASHRAE and ACCA Manuals
pertaining to properly sized duct work must be followed.
Air delivery is critical to these structures. A continuous loop
of duct is recommended at a .20 static on supply and a .07
on one high return air. All diffusers should be double
deflection and moving air 6-12” from all glass or surfaces
that are prone to condensation. Diffusers are not designed
“blowing down”, “blowing over” a pool area, they must
be deflected at surfaces that can reach Dew Point
Temperature. Diffusers are not built into the walls between
windows blowing across an open pool.
We do not recommend blowing air across an open pool ;
this serves to increase the evaporation of pool water and
create a chill effect on the patrons. Blowing air across an
open pool does not resolve chloramine issues; this is a
water quality issue that must be addressed by those proper
balancing of pool water at all times; it is not a HVAC issue.
Square throats and restrictions in the air delivery system
must be minimized. If square throats are used, the proper
elbows/radius and turning vanes are required. The more
restrictive air flow in a duct system, the less likely this system
will control the environment properly and may place
additional stress due to lack of air flow on the system itself.
No fiberboard duct or flex duct should be used in these
systems unless approved in writing by DXair Engineering.
All skylights must be addressed with air flow. If ducting
cannot reach these areas, ceiling fans blowing up must be
installed between the skylights to move air into them and
prevent condensation.
Subject to change without prior notice Revised 07 - 16
EC SERIES POOL DEHUMIDIFIERS
NOTES
Subject to change without prior notice Revised 07 - 16
43
DXair EC Series
Pool Dehumidifiers
Revised 07 - 16
Copyright © 2016 DXair. All rights reserved. Subject to change without notice.