ENGLISH
Datasheet
Article No:
136-5385 Digital AC Ammeter, 48x96, 1Phase, 1 or 5 Amps AC, Supply 40-300V ac/dc
136-5387 Digital AC Ammeter, 96x96, 1Phase, 1 or 5 Amps AC, Supply 40-300V ac/dc
136-5388 Digital AC Voltmeter, 48x96, 1Phase, 60…600 Volts LN AC, Supply 40-300V ac/dc
136-5389 Digital AC Voltmeter, 96x96, 1Phase, 60…600 Volts LN AC, Supply 40-300V ac/dc
RS Pro
RS Pro
The RS Pro digital panel meters (DPM) have been designed for industrial
applications, which frequently require precise and onsite adjustment of
the display range. It can be used in industrial automation and for
laboratory uses.
Benefits:
• Fast & Easy Installation on panel without any need of external swivel
screws (clip-in mounting for 96x96 size only)
• True RMS measurement.
• 4 Digits ultra bright LED Display (up to 9999).
• On site Programmable CT/PT Ratios.
• User selectable CT Secondary 1A/5A. ·
• User selectable PT Secondary from 60…600 Volts LN AC.
• Wide auxiliary Power Supply which can accept any input between
40V – 300V AC/DC.
User selectable PT Secondary
The secondary of external Potential Transformer (PT) can be programmed
on site from 660…600 Volts LN AC for Voltage DPM using front panel
keys.
• Storage of MIN / MAX values.
Product Features
User selectable CT Primary
The Primary of current transformer can be programmed on site from 1A
to 999kA for Current DPM using front panel keys.
True RMS measurement
The instrument measures distorted waveform up to 15th Harmonic.
User selectable PT Primary
The Primary of Potential transformer can be programmed on site from 60
VLN to 999 kVLN for Voltage DPM using front panel keys.
On site programmable PT/CT ratios:
It is possible to program primary of external potential Transformer (PT)
for Voltage DPM & primary of external Current Transformer (CT) for
Current DPM on site via front panel keys by entering into Programming
mode.
Onsite selection of Auto scroll / Fixed Screen
User can set the display in auto scrolling mode or fixed screen mode using
front panel keys.
User selectable CT Secondary 5A/1A
The secondary of external Current Transformer (CT) can be programmed
on site to either 5A or 1A for Current DPM using front panel keys.
Issue 1.0
4 digits LED display (up to 9999):
14mm ultra bright 4 digits LED display.
Higher Security
Provides Security with user programmable password protection.
PAGE 1
Function keys:
Using two function keys it is possible to Display various parameters in
Current and Voltage DPM. These function keys are also used for
programming Password, CT/PT Primary & Secondary values, Reset
min/max values, Auto ON/OFF mode selection.
Screen No. storage
In case of power failure, the instrument memorizes the last screen stored.
For every 1 min. the instrument stores the screen no. in the non-volatile
memory.
Min Max storage of parameters possible
The instrument stores minimum and maximum values. Every 60 sec
stored values are updated.
Low back depth
The instrument has very low back depth (behind the panel) of less than
54mm for 96x96 and 68mm for 48x96 type DPM.
Enclosure Protection for dust and water:
Conforms to IP 50 (for front face) IP 20 (for back) & as per IEC60529.
EMC Compatibility
Compliance to International standard IEC 61326.
• Interference Emission
: IEC 61326-1 : 2005, Class A
• Interference Immunity
: IEC 61326-1 : 2005
• Electrostatic discharge
: IEC 61000-4-2 -- 4kV/8kV
contact/air. (ESD)
• EM Field
: IEC 61000-4-3 -- 10 V/m
(80 MHz to 1 GHz)
– 3 V/m (1.4 Ghz to 2 GHz)
-- 1 V/m (2 GHz to 2.7 GHz)
• Burst
: IEC 61000-4-4 -- 2 kV (5/50 ns, 5 kHz)
• Surge
: IEC 61000-4-5 -- 1 kVLL / 2 kVLN.
• Conducted RF
: IEC 61000-4-5 -- 3 V
(150 kHz to 80 Mhz)
• Rated Power Frequency
magnetic Field
: IEC 61000-4-8 -- 30 A/m
• Voltage dip
: IEC 61000-4-11 -- 0% during 1 cycle.
-- 40% during 10/12 cycles.
-- 70% during 25/30 cycles.
• Short interruptions
: IEC 61000-4-11 –
0% during 25/30 cycles.
25 cycles for 50 Hz test.
30 cycles for 60 Hz test.
Technical Specifications
Input Voltage Article No: 136-5388 & 136-5389 Digital AC Voltmeter
Nominal input voltage (AC RMS)
Phase –Neutral 600VL-N AC.
Max continuous input voltage
120% of rated value
Nominal input voltage burden
< 0.3 VA approx.
System PT secondary values
60VLN to 600VLN programmable on site.
System PT primary values
60VLN to 999kVLN programmable on site.
Input Current Article No: 136-5385 & 136-5387 Digital AC Ammeter
Nominal input current
5A AC RMS
System CT secondary values
1A & 5A programmable on site.
System CT primary values
From 1A up to 999kA (for 1 or 5 Amp )
Max continuous input current
120% of rated value
Nominal input current burden
< 0.2 VA approx. per phase
Auxiliary Supply:
External Aux
Frequency range
VA burden
Issue 1.0
40 V – 300V AC/DC (± 5 % )
45 to 65 Hz
3 VA Approx.
PAGE 2
Technical Specifications Continued
Environmental:
Operating temperature
Storage temperature
Relative humidity
Warm up time
Shock
Vibration
0 to +50°C
-25°C to +70°C
0... 90% non-condensing
Minimum 3 minute
15g in 3 planes
10... 55 Hz, 0.15mm amplitude
Enclosure:
Front
Back
IP 50.
IP 20.
Dimensions and Weights:
a) 96x96 DPM
Bezel size
Panel cut-out
Overall depth
Weight
96 mm x 96 mm DIN 43 718.
92 +0.8 mm x 92 + 0.8 mm.
55 mm.
300 gm. Approx.
b) 48x96 DPM
Bezel size
Panel cut-out
Overall depth
Weight
96 mm x 48 mm DIN 43 718
92 + 0.8 mm x 43.5 + 0.6 mm.
68 mm.
250 gm. Approx.
Overload Withstand:
Voltage
Current
2 x rated value for 1 second, repeated 10 times at 10 second intervals
20x rated value for 1 second, repeated 5 times at 5 min intervals
Operating Measuring Ranges:
Voltage Range
Current Range
Frequency
10… 120% of rated value
10 … 120% of rated value
45...65 Hz
Reference conditions for Accuracy:
Reference temperature
Input waveform
Input frequency
Auxiliary supply voltage
Auxiliary supply frequency
23°C +/- 2°C
Sinusoidal (distortion factor 0.005)
50 or 60 Hz ±2%
Rated Value ±1%
Rated Value ±1%
Accuracy:
Voltage
Current
±0.5% of range + 1 Digit (10... 100% of Nominal value)
±0.5% of range + 1 Digit (10... 100% of Nominal value)
Issue 1.0
PAGE 3
Technical Specifications Continued
Influence of Variations:
Temperature coefficient:
(for rated value range of use (0…50°C))
0.025%/°C for Voltage
0.05%/°C for Current
Display update rate:
Response time to step input
1 sec approx.
Applicable Standards:
EMC
Safety
IP for water & dust
IEC 61326-1: 2005
IEC 61010-1-2001 , Permanently connected use
IEC60529
Safety:
Pollution degree:
Installation category:
High Voltage Test
2
III
3.3 kV AC, 50Hz for 1 minute between Aux. and measuring inputs
Electrical Connections
A) For 96x96 DPM
Connection for 136-5388 & 136-5389
Digital AC Voltmeter
Connection for 136-5385 & 136-5387
Digital AC Ammeter
B) For 48x96 PDM
Connection for 136-5388 & 136-5389
Digital AC Voltmeter
Issue 1.0
Connection for 136-5385 & 136-5387
Digital AC Ammeter
PAGE 4
Installation:
Easy Clip in installation on Panel for 96 x 96 size:
A) For 96x96 DPM
B) For 48x96 DPM
Issue 1.0
PAGE 5
Ordering Information:
Article No: 136-5385
RS Pro
48X96mm, 1 Phase (Single Phase), AC Ammeter 14mm display
Input. 1 or 5 Amps AC,
Voltage supply. 40-300V AC/DC auxiliary
(Programmable CT primary and secondary values & Storage of MIN/MAX Values)
Article No: 136-5387
RS Pro
96X96mm, 1 Phase (Single Phase), AC Ammeter 14mm display
Input. 1 or 5 Amps AC,
Voltage supply. 40-300V AC/DC auxiliary
(Programmable CT primary and secondary values & Storage of MIN/MAX Values)
Article No: 136-5388
RS Pro
48X96mm, 1 Phase (Single Phase), AC Voltmeter 14mm display
Input. 60…600 Volts LN AC,
Voltage Supply. 40-300V AC/DC auxiliary
(Programmable PT primary and secondary values & Storage of MIN/MAX Values)
Article No: 136-5389
RS Pro
96X96mm, 1 Phase (Single Phase), AC Voltmeter 14mm display
Input. 60…600 Volts LN AC,
Voltage Supply. 40-300V AC/DC auxiliary
(Programmable PT primary and secondary values & Storage of MIN/MAX Values)
Articles No: 136-5388 & 136-5389 Digital AC Voltmeter
Network type
Displayed Parameter
3) 1 Phase 2 wire
a. Phase Voltage V
b. Max Voltage V
c. Min Voltage V
Articles No: 136-5385 & 136-5387 Digital AC Ammeter
Network type
Displayed Parameter
2) 1 Phase 2 wire
a. Phase Current A
b. Max Phase Current A
c. Min Phase Current A
Issue 1.0
PAGE 6
Download PDF