DATASHEET NF12‐180B Battery Picture & Terminal Layout
Introduction
Genergy NF (Front Terminal) series is designed for
telecommunication UPS/EPS system with 12-year design
life in float service. The battery is featured of high
consistency, excellent performance and reliable standby
service life.
Battery Features
○ Long service life in floating condition
○ High consistency in standby system
○ Stable quality and high pass rate
○ Low self-discharge rate
Terminal Type: T14
Electrical Specification
Design floating Life @ 20°C (68°F) …………………… 12 years
Nominal Capacity @ 25°C /77°F
20 hour rate 9.52A to 1.75Vpc …………………… 190 Ah
10 hour rate 18.1A to 1.75Vpc …………………… 181 Ah
Internal Resistance
(Fully charged battery @ 25°C /77°F )……………. 6.0 mΩ
Max. Discharge Current @ 25°C /77°…………………1440 A (5S)
Dimension & Weight
Charge Methods: Constant voltage charge @ 25°C /77°F
Dimension (± 2mm)
Cycle Use ………………………………………14.7 ~ 14.9V
Max. Curren ………………………………………… 54 A
Length
Standby Use………………………………………13.6 - 13.8V
Operating Temperature Range
Width
Height
Weight
(± 2%)
Total Height
546 mm
125 mm
317 mm
323 mm
56.3 kg
21.5 inch
4.9 inch
12.5 inch
12.7 inch
124.1 lbs
.Discharge ……………………………………… -15 ~ 50°C
Charge
……………………………………… 0 ~ 50°C
Typical Applications
Storage
……………………………………… -15 ~ 50°C
Recommended Operating Temp ……..…....……………15 ~ 25°C
○ Telecommunications
○ Power Utility
Self-Discharge
○ Data Center
○ UPS & EPS
3% of capacity declined per month @ 20°C (68°F).
Constant Current Discharge (Amperes @ 25°C /77°F)
V/cell
10min
15min
20min
25min
30min
35min
40min
45min
50min
55min
1hr
2hr
3hr
4hr
5hr
10hr
20hr
1.60
1.65
477.7
454.4
364.7
346.9
317.2
303.6
269.8
260.3
222.4
217.0
206.6
201.8
190.9
186.5
175.2
171.2
159.5
155.9
143.8
140.7
128.1
125.4
74.46
72.91
51.76
50.88
43.23
42.43
34.69
33.98
18.50
18.50
9.69
9.69
1.70
1.75
426.4
398.5
325.5
304.2
287.0
270.4
248.4
236.6
209.9
202.8
195.4
189.0
180.9
175.2
166.3
161.4
151.8
147.6
137.3
133.9
122.7
120.1
71.36
69.81
49.81
48.74
41.54
40.65
33.26
32.55
18.32
18.14
9.61
9.52
1.80
368.2
281.1
252.0
223.0
193.9
181.1
168.3
155.5
142.7
129.9
117.0
68.05
47.67
39.67
31.66
17.79
9.34
2hr
3hr
Constant Power Discharge (Watts/cell @ 25°C /77°F)
V/cell
10min
15min
20min
25min
30min
35min
40min
45min
50min
55min
1hr
4hr
5hr
10hr
20hr
1.60
1.65
799.5
777.6
610.3
593.6
537.9
522.0
465.5
450.5
393.1
378.9
368.5
355.5
343.9
332.1
319.3
308.6
294.7
285.2
270.1
261.8
245.5
238.4
142.72 101.39
138.59 100.51
83.70
82.98
66.00
65.46
35.41
35.12
18.73
18.58
1.70
1.75
749.1
718.5
571.9
548.5
502.8
482.4
433.7
416.4
364.7
350.4
342.7
329.7
320.8
308.9
298.8
288.2
276.9
267.4
255.0
246.7
233.0
225.9
135.48
131.35
99.62
98.55
82.27
81.47
64.93
64.39
34.83
34.55
18.43
18.28
1.80
683.4
521.7
458.7
395.7
332.6
313.7
294.7
275.7
256.7
237.8
218.8
127.21
97.66
80.76
63.86
34.26
18.13
*The mentioned data are derived from of sample test result, for reference only.
ANDA‐OLSEN AS Blindheim Industrivei 2E NO‐6020 Aalesund Norway Tel +47 70 17 89 70 Fax +47 70 17 89 71 post@anda‐olsen.no www.anda‐olsen.no Org.nr. NO 935692113 MVA DATASHEET NF12‐180B (%) (CA) (V/cell)
120
0.25
2.75
80
0.20
2.50
60
0.15
2.25
40
0.10
2.00
20
0.05
1.75
0
0
(25°C)
Discharge Characteristic (25°C)
2 . 17
2 . 00
CHARGED VOLUME
Battery Voltage(V)
100
Constant Voltage Charging Characteristic
(V/cell)
Charge Characteristic Curve
Voltage
Current
Charged
Volume
Graphs
CHARGE VOLTAGE
1 . 83
0.175C 0.1C 0.05C
0.25C
1 . 67
2C
1 . 50
1C 0.65C
1 . 33
≈
0 1
0
CHARGING CURRENT
0
2
4
6
8
10 12
Charging Time (hours)
14
16
18
2 3
20
5
10
min
20 30
60
2 3
5
h
10
20 30
Discharge Time
Temperature Effects On Float Life
Cycle Service Life V.S. Depth Of Discharge
120
15
10
Capacity (%)
Life (years)
100
2.30 V / cell
5
80
60
100% D.O.D
50% D.O.D
30% D.O.D
40
20
0
10
20
30
40
0
50
100
200
300
Temperature (°C)
90
Capacity (%)
Charging Voltage (V)
2.4
80
70
2.3
60
2.2
50
-10
0
10
20
30
40
Ambient Temperature (°C )
50
400
60
Life Characteristics Of Standby Use
100
100
80
80
Capacity (%)
120
Capacity (%)
40°C
2
4
30°C
6
20°C
8
10
12
14
Storage Time: months
16
18
20
Temperature Effects On Capacity
120
Testing conditions: f loating voltage: 2.27 to 2.3 V / cell
Ambient temperature: 25° C ( 77° F)
40
60
40
20
20
4
ANDA‐OLSEN AS Blindheim Industrivei 2E 1000 1100
100
2.5
0
90
0
110
2.6
60
50
60 70
80
0
0
0
0
Number of Cycles (cycles)
Self-Discharge Characteristic
(V/cell)
Charging Voltage V.S. Temperature
40
0
6
Life (year)
NO‐6020 Aalesund Norway 0
-20
8
Tel +47 70 17 89 70 Fax +47 70 17 89 71 -10
0
10
20
Temperature (°C)
post@anda‐olsen.no www.anda‐olsen.no 30
40
50
Org.nr. NO 935692113 MVA 
Download PDF