Model S4000T Intelligent Sensor for Hydrogen Sulfide Gas Detection The information and technical data disclosed in this document may be used and disseminated only for the purposes and to the extent specifically authorized in writing by General Monitors. Instruction Manual 0307 General Monitors reserves the right to change published specifications and designs without prior notice. MANS4000T Part No. Revision MANS4000T H/03-07 S4000T This page intentionally left blank ii S4000T Table of Contents TABLE OF FIGURES ..................................................................................................................VI TABLE OF TABLES...................................................................................................................VII QUICK START GUIDE ................................................................................................................. 8 Mounting and Wiring ...............................................................................................................................8 Tools Required...........................................................................................................................8 Terminal Connections .............................................................................................................................8 1.0 INTRODUCTION .................................................................................................................. 11 1.1 1.2 1.3 Protection for Life .....................................................................................................................11 Special Warnings .....................................................................................................................11 System Integrity Verification ....................................................................................................11 2.0 PRODUCT DESCRIPTION................................................................................................... 13 2.1 General Description .................................................................................................................13 3.0 INSTALLATION.................................................................................................................... 14 3.1 3.2 3.3 3.4 3.5 3.6 Receipt of Equipment...............................................................................................................14 Tools Required.........................................................................................................................14 Choosing Product Locations ....................................................................................................14 3.3.1 Remote Mounting of the Sensor from the Electronics ................................................15 Mounting and Wiring ................................................................................................................16 Terminal Connections ..............................................................................................................17 3.5.1 Terminal Block TB1 – Sensor Connections ................................................................17 3.5.2 Terminal Block TB2 – Power and Signal Connections ...............................................17 3.5.3 DC Power and Ground Connections...........................................................................19 3.5.4 Analog Signal Connections.........................................................................................20 3.5.5 Terminal Block TB3 – Relay Connections ..................................................................20 3.5.6 European Union (EU) Approved Applications.............................................................21 3.5.7 Cable termination in the non-hazardous area.............................................................21 Maintaining the X/P Integrity ....................................................................................................22 4.0 OPERATION......................................................................................................................... 24 4.1 4.2 4.3 4.4 4.5 Start-Up Checklist ....................................................................................................................24 Start-Up ....................................................................................................................................24 Relay Reset..............................................................................................................................24 User Selectable Options ..........................................................................................................25 4.4.1 Model S4000T User Menu Structure ..........................................................................26 4.4.2 Sensor Range .............................................................................................................26 4.4.3 Warning Relay Settings ..............................................................................................27 4.4.4 Alarm Relay Settings...................................................................................................27 4.4.5 MODBUS Channel 1 Settings.....................................................................................28 4.4.6 MODBUS Channel 2 Settings.....................................................................................28 Gas Check Mode .....................................................................................................................29 4.5.1 Procedure for Checking the Calibration: .....................................................................29 iii S4000T 4.6 4.7 Calibration ................................................................................................................................29 4.6.1 Calibration Procedure .................................................................................................30 4.6.2 Aborting Calibration.....................................................................................................31 4.6.3 Remaining Sensor Life................................................................................................31 4.6.4 Initializing the Remaining Sensor Life.........................................................................31 Calibration Equipment..............................................................................................................31 4.7.1 Breaker Bottles and Ampoules ...................................................................................31 4.7.2 H2S Portable Purge Calibrator ....................................................................................32 5.0 MAINTENANCE ................................................................................................................... 33 5.1 5.2 General Maintenance...............................................................................................................33 Storage.....................................................................................................................................33 6.0 TROUBLESHOOTING ......................................................................................................... 34 6.1 Fault Codes & Their Remedies................................................................................................34 6.1.1 F2 - Failed to Complete the Calibration ......................................................................34 6.1.2 F3 - EPROM Checksum Error ....................................................................................34 6.1.3 F4 - Sensor Heater Open Error...................................................................................34 6.1.4 F5 - Sensor Heater Shorted Error...............................................................................34 6.1.5 F6 - Low Supply Voltage.............................................................................................35 6.1.6 F7 - EEPROM Verification Failure ..............................................................................35 6.1.7 F8 - Failure to Complete Setup...................................................................................35 6.1.8 F9 - Gas Check Period Exceeded ..............................................................................35 6.1.9 F10 – Switch Error ......................................................................................................35 7.0 CUSTOMER SUPPORT ....................................................................................................... 36 T 7.1 General Monitors’ Offices.........................................................................................................36 8.0 MODBUS INTERFACE ........................................................................................................ 37 8.1 8.2 8.3 8.4 8.5 8.6 8.7 8.8 Baud Rate ................................................................................................................................37 Data Format .............................................................................................................................37 MODBUS Read Status Protocol (Query/Response)................................................................37 8.3.1 MODBUS Read Query Message ................................................................................37 8.3.2 MODBUS Read Response Message..............................................................................37 MODBUS Write Command Protocol (Query/Response) .........................................................38 8.4.1 MODBUS Write Query Message ................................................................................38 8.4.2 MODBUS Write Response Message ..........................................................................38 Function Codes Supported ......................................................................................................38 Exception Responses and Exception Codes ...........................................................................38 8.6.1 Exception Response ...................................................................................................38 8.6.2 Exception Code...........................................................................................................39 S4000T Command Register Locations ....................................................................................40 S4000T Command Register Details ........................................................................................41 8.8.1 Analog .........................................................................................................................41 8.8.2 Mode ...........................................................................................................................41 8.8.3 Status/Error .................................................................................................................42 8.8.4 Unit Type.....................................................................................................................42 8.8.5 Software Revision .......................................................................................................42 8.8.6 Status Block ................................................................................................................42 8.8.7 Alarm Settings.............................................................................................................42 iv S4000T 8.8.8 8.8.9 8.8.10 8.8.11 8.8.12 8.8.13 8.8.14 8.8.15 8.8.16 8.8.17 8.8.18 8.8.19 8.8.20 8.8.21 8.8.22 8.8.23 8.8.24 8.8.25 8.8.26 Warn Settings..............................................................................................................43 Com1 Address ............................................................................................................43 Com1 Baud Rate.........................................................................................................43 Com1 Data Format......................................................................................................44 Com2 Address ............................................................................................................44 Com2 Baud Rate.........................................................................................................44 Com2 Data Format......................................................................................................44 Reset Alarms...............................................................................................................45 Sensor Life ..................................................................................................................45 Sensor Scale...............................................................................................................45 HazardWatch (Co – Calibration Output) .....................................................................45 Total Receive Errors ...................................................................................................45 Bus Activity Rate %.....................................................................................................45 Function Code Errors ..................................................................................................45 Starting Address Errors...............................................................................................45 Number of Register Errors ..........................................................................................46 RXD CRC Hi Errors.....................................................................................................46 RXD CRC Low Errors .................................................................................................46 Clear Comm Errors .....................................................................................................46 9.0 APPENDIX............................................................................................................................ 47 9.1 9.2 9.3 9.4 9.5 9.6 Warranty...................................................................................................................................47 Principle of Operation...............................................................................................................47 Specifications ...........................................................................................................................48 9.3.1 System Specifications .................................................................................................48 9.3.2 Mechanical Specifications...........................................................................................48 9.3.3 Electrical Specifications ..............................................................................................48 9.3.4 Environmental Specifications......................................................................................49 Approvals .................................................................................................................................50 Spare Parts and Accessories...................................................................................................50 9.5.1 Sensors .......................................................................................................................50 9.5.2 Sensor Housing...........................................................................................................50 9.5.3 Sensor Accessories ....................................................................................................51 9.5.4 Calibration Equipment.................................................................................................51 9.5.5 Intelligent Sensor (S4000T) Replacement Parts ........................................................52 9.5.6 Recommended Spare Parts for One (1) Year ............................................................52 FMRC Approval........................................................................................................................53 v S4000T Table of Figures Figure 1: S4000T Outline and Mounting Dimensions............................................................................................. 8 Figure 2: Spring Type Terminal Block Operation ................................................................................................... 9 Figure 3: Screw Type Terminal Block Operation.................................................................................................... 9 Figure 3: Model S4000T Intelligent Sensor .......................................................................................................... 13 Figure 4: S4000T Outline and Mounting Dimensions........................................................................................... 16 Figure 6: Spring Type Terminal Block Operation ................................................................................................. 18 Figure 7: Screw Type Terminal Block Operation.................................................................................................. 18 Figure 8: Wire Strip Length................................................................................................................................... 18 Figure 7: Relay Protection for DC and AC Loads................................................................................................. 21 Figure 8: Relay Reset ........................................................................................................................................... 25 Figure 9: User Menu Structure ............................................................................................................................. 26 Figure 10: Gas Check........................................................................................................................................... 29 Figure 11: Automatic Calibration Mode ................................................................................................................ 30 Figure 12: Calibration in Progress Mode .............................................................................................................. 30 Figure 13: Calibration Complete Mode................................................................................................................. 30 vi S4000T Table of Tables Table 1: TB2 Power and Signal Connections....................................................................................................... 17 Table 2: Ground or Common Connections........................................................................................................... 19 Table 3: Power Connections ................................................................................................................................ 19 Table 4: Analog Signal Connections .................................................................................................................... 20 Table 5: Alarm Relay Connections ....................................................................................................................... 20 Table 6: Warn Relay Connections........................................................................................................................ 20 Table 7: Fault Relay Connections ........................................................................................................................ 21 Table 8: GM Locations.......................................................................................................................................... 36 Table 9: Data Format............................................................................................................................................ 37 Table 10: Exception Codes .................................................................................................................................. 39 Table 11: Command Register Locations .............................................................................................................. 40 Table 12: Command Register Locations, Cont. ................................................................................................... 41 Table 13: Com1 Baud Rate .................................................................................................................................. 43 Table 14: Com1 Data Format ............................................................................................................................... 44 Table 15: Com2 Baud Rate .................................................................................................................................. 44 Table 16: Com2 Data Format ............................................................................................................................... 44 Table 17: Sensor Scale ........................................................................................................................................ 45 Table 18: 24VDC Cable Lengths.......................................................................................................................... 49 Table 19: Analog Output Cable Lengths .............................................................................................................. 49 Table 20: Sensor Cable Lengths .......................................................................................................................... 49 vii S4000T Quick Start Guide Mounting and Wiring Tools Required 1. “5mm” Allen head wrench to remove enclosure lid (included with gas detector). 2. Flat-head screwdriver maximum 3/16 in (5 mm) width for terminal block connections (included with gas detector). 3. Adjustable wrench for conduit or cable bgland connections (not included). The overall and mounting dimensions for the Model S4000T (Figure 1) should be used when making installation determinations. Information on Class I location seals can be found in the NEC, Article 501-5. WARNING: Acetic acid will cause damage to metal components, metal hardware, ceramic IC’s, etc. If damage results from the use of a sealant that outgases acetic acid (RTV silicone), the warranty will be void. Figure 1: S4000T Outline and Mounting Dimensions Terminal Connections The terminal blocks (TB) are located inside the housing and can by accessed by removing the cover. A label on the inside of the housing cover provides details of all the terminal connections. It is recommended that a three-wire (red, black, white) shielded cable be used for making power and output signal connections on the Model S4000C. The Spring Type terminal block accepts 14 AWG to 20 AWG and the Screw Type terminal block accepts 12 AWG to 18 AWG stranded or solid wire. Each wire should be stripped before wiring the Model S4000C Intelligent Sensor. To connect wiring to the Spring Type terminal block, insert a screwdriver into the 8 S4000T orange tab and press down (Figure 2), opening the terminal. Insert the wire into the terminal and release the orange tab, clamping the wire in the terminal. Check the hold of the wire by GENTLY tugging it to ensure it is locked in. To connect wiring to the Screw Type terminal block, (Figure 3) use a screwdriver to loosen the top screw counter clock wise. Insert the wire into the terminal and tighten the top screw clock wise. Check the hold of the wire by GENTLY tugging it to ensure it is locked in. Figure 2: Spring Type Terminal Block Operation Figure 3: Screw Type Terminal Block Operation NOTE: Power must remain disconnected until all other wiring connections have been made. The maximum distance between the Model S4000T and the power supply is 2000 feet or 610 meters (each cable run should be as short as possible). See Section 9.2.3 for cable length specifications. Connect +24VDC to TB2, position 9. Connect the ground or common wire to TB2, position 8. For making power and ground connections to display devices see Figures 2 and 3. The instrument is now ready to operate. Please consult the manual for more information on the instrument’s many features. NOTE: If you have any problems in the set-up or testing of the detector, please refer to the “Trouble Shooting Section”, or call the factory direct. 9 S4000T Worldwide service is available by calling: Lake Forest, California (24 hr. service) Toll Free: +1-800-446-4872 Phone: +1-949-581-4464 Fax: +1-949-581-1151 Houston, Texas Phone: +1-281-855-6000 Fax: +1-281-855-3290 Ireland Phone: +353-91-751175 Fax: +353-91-751317 Singapore Phone: +65-6748-3488 Fax: +65-6748-1911 United Arab Emirates Phone: +971-4-8815751 Fax: +971-4-8817927 United Kingdom Phone: +44-1625-619583 Fax: +44-1625-619098 10 S4000T 1.0 Introduction 1.1 Protection for Life General Monitors’ mission is to benefit society by providing solutions through industry leading safety products, services, and systems that save lives and protect capital resources from the dangers of hazardous flames, gases, and vapors. This manual provides instruction for installing and operating General Monitors’ Model S4000T for Hydrogen Sulfide Gas Detection. While the S4000T is easy to install and operate, this manual should be read in full and the information contained herein understood before attempting to place the system in service. The safety products you have purchased should be handled carefully and installed, calibrated, and maintained in accordance with the respective product instruction manual. Remember these products are for your safety. 1.2 Special Warnings The Model S4000T Intelligent Sensor contains components, which can be damaged by static electricity. Special care must be taken when wiring the system to ensure that only the connection points are touched. Hydrogen Sulfide (H2S) is an extremely toxic gas, and exposure may result in a loss of consciousness or death. 1.3 System Integrity Verification To ensure operation at optimum performance, General Monitors recommends that certain maintenance items be performed. Commissioning Safety Systems Before power-up, verify wiring, terminal connections and stability of mounting for all integral safety equipment including, but not limited to: • Power supplies • Control modules • Field detection devices • Signaling / output devices • Accessories connected to field and signaling devices After the initial application of power (and any factory specified warm-up period) to the safety system, verify that all signal outputs, to and from devices and modules, are within the manufacturers’ specifications. Initial calibration / calibration checking / testing should be performed per the manufacturer’s recommendations and instructions. 11 S4000T Proper system operation should be verified by performing a full, functional test of all component devices of the safety system, ensuring that the proper levels of alarming occur. Fault/Malfunction circuit operation should be verified. Periodic Testing/Calibration of Field Devices Periodic testing/calibrating should be performed per the manufacturer’s recommendations and instructions. Testing/Calibrating procedures should include, but not be limited to: • Verify zero reading • Apply a known concentration of gas, and verify accuracy • Verify integrity of all optical surfaces and devices • For flame detectors, use the appropriate test lamp When testing produces results outside of the manufacturer’s specifications, re-calibration or repair/replacement of the suspect device(s) should be performed as necessary. Calibration intervals should be independently established through a documented procedure, including a calibration log, maintained by plant personnel or third party testing services. Periodic System Verification The following system verifications should be performed at least annually: Verify wiring, terminal connections and stability of mounting for all integral safety equipment including, but not limited to: • Power supplies • Control modules • Field detection devices • Signaling / output devices • Accessories connected to field and signaling devices Calibration intervals should be independently established through a documented procedure, including a calibration log maintained by plant personnel or third party testing services. 12 S4000T 2.0 Product Description 2.1 General Description The Model S4000T is an intelligent sensor for the detection of Hydrogen Sulfide (H2S) gas. The microprocessor-based electronics process information at the sensor site, within an explosionproof housing. A digital display provides indications and display codes that can be viewed through a window in the cover. A red LED above the digital display signifies an ALARM condition, while a red LED below the digital display signifies a WARN condition. Analog signal (4-20mA) optional Dual Redundant MODBUS communications and relays, provide remote and/or discrete indications of the sensor’s operation. The Model S4000T Intelligent Sensor is rated explosion-proof for use in the following hazardous areas: • CSA/FM: Class I, Division 1, Groups B, C, D and Class I, Zone 1, Ex d IIB+H2, T6 • ATEX: EEx d IIB T6 (Tamb=-40°C to +40°C) Figure 4: Model S4000T Intelligent Sensor 13 S4000T 3.0 Installation 3.1 Receipt of Equipment All equipment shipped by General Monitors is pre-packed in shock absorbing containers, which provide protection against physical damage (original containers should be kept for future shipping or storage needs). Shipping container contents should be carefully removed and checked against the packing list. If any damage has occurred or there is any discrepancy in the order, please notify General Monitors as soon as possible. All correspondence with General Monitors must specify the equipment part number and serial number. The factory tests each unit; however, a complete system checkout is suggested upon initial installation to ensure system integrity. WARNING: Installation and maintenance must be carried out by suitably skilled and competent personnel only. WARNING: The Model S4000T Intelligent Sensor contains components, which can be damaged by static electricity. Special care must be taken when wiring the system to ensure that only the connection points are touched. 3.2 Tools Required 1. “5mm” Allen head wrench to remove enclosure lid (included with gas detector). 2. Flat-head screwdriver maximum 3/16 in (5 mm) width for terminal block connections (included with gas detector). 3. Adjustable wrench for conduit or cable gland connections (not included). 3.3 Choosing Product Locations There are no standard rules for sensor placement, since the optimum sensor location is different for each application. The customer must evaluate conditions at the facility to make this determination. Generally, the Model S4000T Intelligent Sensor should be easily accessible for calibration checks. • The transmitter should be mounted pointing down to prevent water build-up on the sensor head. • The transmitter should not be placed where contaminating substances may coat it. • Although the Model S4000T is RFI resistant, it should not be mounted in close proximity to radio transmitters or similar equipment. • Locate the Model S4000T where prevailing air currents contain the maximum concentration of gas. 14 S4000T • Locate the Model S4000T near possible sources of gas leaks. • Observe the Model S4000T’s temperature specification and locate the unit away from concentrated sources of heat. • Transmitters should be mounted in an area that is as free from wind, dust, water, shock, and vibration as possible. See Section 9.3.4 for the environmental specifications of the unit. If dust and rain cannot be avoided, we recommend the use of our splash guard (GM P/N 10395-1). Sensors may be adversely affected by prolonged exposure to certain materials. Loss of sensitivity or corrosion may be gradual if such materials are present in low concentrations, or it may be rapid at high concentrations. The more important materials adversely affecting sensors are: • Silicones (often contained in greases and aerosols) • Halides: compounds containing Fluorine, Chlorine, Bromine and Iodine • Heavy metals, e.g. Tetraethyl Lead • Caustic and Acidic liquids and vapors • Glycol The presence of contaminants in an area does not necessarily preclude the use of a Model S4000T Intelligent Sensor. The feasibility of using a sensor in such areas must be determined by an analysis of the specific factors in each application, and General Monitors should be consulted before attempting any such installation. Sensors used in these areas usually require more frequent calibration checks than normal, and typically have a shorter life. In many such applications the standard two-year warranty would not apply. IMPORTANT: Each H2S Sensor is shipped with a red plastic cap fitted over the sensor head. Inside the cap is a desiccant. DO NOT remove this cap until you are ready to power the system. SAVE the cap and RE-CAP the sensor anytime the system power is off for more than one hour. WARNING: General Monitors discourages the painting of sensor assemblies. If the sensor head is painted over, the gas will not be able to diffuse into the sensor. If the assembly cover is painted over, the digital display cannot be read. 3.3.1 Remote Mounting of the Sensor from the Electronics If it is necessary to remotely mount the sensor from the electronics and the housing, the maximum distance can be no greater than 3700 feet (1125) meters, using 14 AWG wire. Sensors that are remotely mounted, must be placed in an explosion-proof rated sensor housing (GM P/N 10252-1), and the cable run must be contained in a conduit running from the sensor housing to the electronics. See Section 9.6, for FMRC approval requirements. 15 S4000T 3.4 Mounting and Wiring WARNING: The conduit entries should be sealed per the NEC 500-3d, or Canadian Electrical Code Handbook (Part 1, Section 18-154). Additional benefit of conduit seals is the prevention of water entering the housing through the conduit entry. WARNING: Unused cable entry holes must be sealed with an approved explosion-proof plug. Red caps supplied by General Monitors are for dust protection only and must not be left on the unit when installed. The overall and mounting dimensions for the Model S4000T (Figure 5) should be used when making installation determinations. A complete list of the mechanical specifications can be found in Section 9.3.2. To prevent possible corrosion due to moisture or condensation, it is recommended that the conduit connected to the Model S4000T housing be sealed, or contain a drain loop. Each conduit run from a hazardous location to a non-hazardous location should be sealed so that gases, vapors, and/or flames cannot pass beyond the seal. The purpose of seals in a Class I hazardous location, is to prevent the passage of gases, vapors, or flames from one electrical installation to another, through the conduit system. It is not necessary to seal the Model S4000T housing to maintain its explosion-proof integrity; however, conduit runs containing wires attached to the Model S4000T’s relay contacts must be sealed (Section 3.5). Information on Class I location seals can be found in the NEC, Article 501-5. Figure 5: S4000T Outline and Mounting Dimensions WARNING: Acetic acid will cause damage to metal components, metal hardware, ceramic IC’s, etc. If damage results from the use of a sealant that outgases acetic acid (RTV silicone), the warranty will be void. 16 S4000T Once correctly installed, the Model S4000T requires little or no maintenance, other than periodic calibration checks to ensure system integrity. General Monitors recommends that a schedule be established and followed. NOTE: The system’s full two-year warranty will be voided if customer personnel or third parties damage the system during repair attempts. Sensor heads exposed to the elements may require the accessory mounting threads to be lubricated. Grease must not be used. As an alternate, PTFE (Teflon) tape may be used on sensor accessory threads. NOTE: Do not use any material or substance on threads that contact the sensor housing. The removal of particulate matter from sensor accessories may be done through the use of an appropriate halogen-free solvent. Water and/or ethanol are examples of suitable solvents. The accessories should be thoroughly dried, with compressed air if necessary, before refitting to the sensor body. 3.5 Terminal Connections The terminal blocks (TB) are located inside of the housing and can by accessed by removing the cover. A label on the inside of the housing cover provides details of all the terminal connections. 3.5.1 Terminal Block TB1 – Sensor Connections TB1 contains the four sensor connections, white (W), black (B), red (R) and green (G). Remove the display board by loosening the two captive screws on the board and lifting it straight up. Connect the color-coded wires from the sensor to the matching colored terminals on TB1. The label on the inside of the cover can serve as a guide. Replace the display board, by pressing it into place, and tightening the two captive screws. WARNING: Do not connect +24VDC to TB1. Damage to the electronics or sensor may result. 3.5.2 Terminal Block TB2 – Power and Signal Connections TB2 contains the connections for Power, Relay Reset, Remote Calibration, MODBUS and 020mA Output Signal. The terminal connections are as follows: TB2 position 1 2 3 4 5 6 7 8 9 Function 0-20mA Output CH1 MODBUS CH1 MODBUS + CH2 MODBUS CH2 MODBUS + Remote Calibration Relay Reset Ground +24VDC Power Table 1: TB2 Power and Signal Connections 17 S4000T It is recommended that a three-wire (red, black, white) shielded cable be used for making power and output signal connections on the Model S4000C. The Spring Type terminal block accepts 14 AWG to 20 AWG and the Screw Type terminal block accepts 12 AWG to 18 AWG stranded or solid wire. Each wire should be stripped before wiring the Model S4000C Intelligent Sensor. To connect wiring to the Spring Type terminal block, insert a screwdriver into the orange tab and press down (Figure 6), opening the terminal. Insert the wire into the terminal and release the orange tab, clamping the wire in the terminal. Check the hold of the wire by GENTLY tugging it to ensure it is locked in. To connect wiring to the Screw Type terminal block, (Figure 7) use a screwdriver to loosen the top screw counter clock wise. Insert the wire into the terminal and tighten the top screw clock wise. Check the hold of the wire by GENTLY tugging it to ensure it is locked in. Figure 6: Spring Type Terminal Block Operation Figure 7: Screw Type Terminal Block Operation Figure 8: Wire Strip Length 18 S4000T NOTE: Up to 12 AWG wire can be used if it is carefully stripped (on a Screw Type terminal only-Figure 8). 3.5.3 DC Power and Ground Connections The customer must provide Primary DC power, unless one of the following General Monitors’ Modules is being used with the Model S4000T: • DT230 Dual-Channel Readout/Relay Display Module • TA202A Trip Amplifier Module with a PS002 Power Supply & Relay Module The following General Monitors’ Modules provide power connections for the Model S4000T, but need a customer supplied DC source: • DT210 Eight-Channel Readout/Relay Display Module • TA202A Trip Amplifier Module without a PS002 Since the Model S4000T is designed to operate continuously, a power switch is not included, in order to prevent accidental system shutdown. NOTE: Power must remain disconnected until all other wiring connections have been made. The maximum distance between the Model S4000T and the power supply is 2000 feet or 610 meters (each cable run should be as short as possible). See Section 9.3.3 for cable length specifications. Connect +24VDC to TB2, position 9. Connect the ground or common wire to TB2, position 8. For making power and ground connections to display devices see Table 2 and Table 3. FROM TO Model S4000T Model DT210 Model DT230 Model TA202A TB2-8 “COM” Rear COMMON Rear Pin 3 or 6 “COM” Rear Pin 30d or 30z Table 2: Ground or Common Connections FROM TO Model S4000T Model DT210 Model DT230 Model TA202A TB2-9 “+24 VDC” Rear CH 1 - 8 24V Rear Pin 4 or 7 “DC OUT” Rear Pin 28d or 28z Table 3: Power Connections 19 S4000T 3.5.4 Analog Signal Connections The Model S4000T Intelligent Transmitter provides a 4 to 20mA output signal. This signal can be sent up to 9000 feet (2740 meters) to: • A General Monitors readout/relay display module, or • An industrial analog to digital converter, or • A computer-based monitor, • A PLC, or • A DCS. The 4 to 20mA signal provides for control room or other locations remote to the Model S4000T to display indications of operation and alarm conditions. To connect the 4 to 20mA output signal with another unit, connect the wire into TB2, position 1, labeled 4-20mA OUT. For making output signal connections to display devices, refer to the specific manual for that device (Table 4). FROM TO Model S4000T Model DT210 Model DT230 Model TA202A TB2-1 4-20mA Output Rear CH 1 – 8 4-20mA Rear Pin 2 or 5 Analog In Rear Pin 26d or 26z Table 4: Analog Signal Connections If a device other than a General Monitors readout/relay display module is being used, the DC ground, COM, of both systems must be connected together. 3.5.5 Terminal Block TB3 – Relay Connections TB3 contains the connections for the Relay Contacts (optional). The function for the Warn and Alarm Relay connections vary, according to the normal state of the relay. Use the following as a guide for determining the Normally Open (NO) and the Normally Closed (NC) contact: TB3 position 1 2 3 Relay Contact (De-Energized) Normally Closed Common Normally Open Relay Contact (Energized) Normally Open Common Normally Closed Table 5: Alarm Relay Connections TB3 position 4 5 6 Relay Contact (De-Energized) Normally Closed Common Normally Open Relay Contact (Energized) Normally Open Common Normally Closed Table 6: Warn Relay Connections 20 S4000T TB3 position 7 8 9 Relay Contact (Energized) Normally Open Common Normally Closed Table 7: Fault Relay Connections *NOTE: Fault relay is normally energized. Relay will change state after power up. WARNING: Contact with PCB components should be avoided to prevent damage by static electricity. All wire connections are made to the Terminal Blocks. WARNING: Relay contacts must be protected against transient and over voltage conditions (Figure 9). Figure 9: Relay Protection for DC and AC Loads North American Approved Applications - The ALARM relay contact ratings are 8A @ 250 VAC and 8A @ 30 VDC resistive max. European Union (EU) Approved Applications - The ALARM relay contact ratings are 8A, 30 V RMS/42.4 V peak or 8A @ 30 VDC resistive max. 3.5.6 European Union (EU) Approved Applications Interconnecting cables must have an overall screen, or screen and armor. Cables BS5308 Part 2, Type 2, or equivalent are suitable. NOTE: The terms ‘screen’ and ‘shield’ are equivalent for the purpose of this manual. The cable armor must be terminated in a suitable cable gland at the detector, to ensure a positive electrical connection. 3.5.7 Cable termination in the non-hazardous area • The cable armor must be connected to safety earth in the safe area. • The cable screen (drain wire) must be connected to an instrument earth in the safe area. 21 S4000T • The power supply OV return must be connected to an instrument earth in the safe area. • The interconnecting cables should be segregated from power and other noisy cables. Avoid proximity to cables associated with radio transmitters, welders, switch mode power supplies, inverters, battery chargers, ignition systems, generators, switch gear, arc lights and other high frequency or high power switching process equipment. In general, maintain separation of at least 1 meter between instrument and other cables. Greater separations are required where long parallel cable runs are unavoidable. Avoid running instrument cable trenches close to lightning conductor earthing pits. • Complete all cable insulation testing before connecting the cable at either end. WARNING: Under NO circumstances should equipment be connected or disconnected when under power. This is contrary to hazardous area regulations and may lead to serious damage to the equipment. Equipment damaged in this manner is not covered under warranty. 3.6 Maintaining the X/P Integrity The Model S4000T is rated explosion-proof for the following hazardous locations: • CSA/FM: Class I, Division 1, Groups B, C, D and Class I, Zone 1, Ex d IIB+H2, T6 and • ATEX: EEx d IIB T6 (Tamb=-40°C to +40°C) Some of the factors that influence the explosion-proof integrity of the Model S4000T housing are: • Strength of the enclosure material • Thickness of the enclosure walls • Flame path between the housing and cover • Flame path of threaded joints The acceptable limits for explosion-proof housings that are used in Class I hazardous locations are defined in CSA Standard C22.2 No.30-M1986, FM 3615 and EN50014. Anytime the cover of the Model S4000T housing is removed or the cover bolts are loosened, the flame path between the lid and the housing is affected. If power is to be left on while removing the cover or loosening the cover bolts on the Model S4000T, it will be necessary to declassify the area. When replacing the cover, the gap between the lid and the housing should be less than .0015 inch (.038 mm). Make sure that the flame path is clear of dirt and debris before replacing the cover. This can be verified by tightening the cover bolts to a torque setting of 50 inch-pounds or by using a feeler gauge to ensure the gap between the cover and the housing is less than .0015 inch (.038 mm). There are four entry holes, one each on the left and right sides, and two on the bottom of the Model S4000T housing. These holes are dedicated for the sensor, the reset switch and conduit. Each hole is tapped for ¾” NPT threads. If a particular entry hole is not used, it must be 22 S4000T plugged during operation in the field. The factory installs plugs in the unused entry holes, except one. A red plastic cap is placed into the remaining hole and must be removed before conduit can be attached to the housing. The Model S4000T will have the following items placed in the three remaining entry holes, at the factory: • A sensor, if present (otherwise a red plastic cap) • A reset switch, if present (otherwise an aluminum housing plug – optional) • An aluminum housing plug The sensor, reset switch and aluminum-housing plug have seven threads. Each of these components is screwed into the housing using five to seven turns. If it becomes necessary to replace the sensor, reset switch and/or the aluminum-housing plug, the user must use five to seven turns to ensure the explosion-proof integrity of the housing is maintained. 23 S4000T 4.0 Operation 4.1 Start-Up Checklist Prior to starting the system, verify the following: 1. Inhibit any external devices, such as Trip Amplifiers, PLC’s, or DCS systems. 2. Verify that the optional settings are set for the desired configuration. 3. Verify that the unit is properly mounted. Ensure the conduit/cable gland entries are pointed downward. 4. Verify that the signal wiring is correct. 5. Verify that the power supply is connected properly. The Model S4000T is powered by +24VDC (20 to 36 VDC voltage range). The detector will output a low voltage fault (F6) at 18.5 VDC or below. 6. Make sure the lid is securely installed or the area has been de-classified. 4.2 Start-Up Before applying power to the system for the first time, all wiring connections should be checked for correctness and the housing cover replaced. Upon first power-up, the sensor may take up to fifteen minutes to stabilize. At the initial application of power, the unit will test all of the LED segments by displaying “88.8”. The software revision letter will then be displayed for a few seconds. The unit will then enter Operational Mode and the current gas concentration at the sensor will be displayed. For details of Calibrating and Gas Checking the unit, see Sections 4.5 and 4.6. 4.3 Relay Reset If the Warn and Alarm relays are configured as latching, they must be manually reset, after an alarm occurs. This can be accomplished by three different methods: 1. The relays can be reset via the MODBUS Interface (Section 8.8.15). 2. The relays can be reset via the magnetic switch using a magnet. Place the magnet over the GM Logo on the cover of the unit. After three seconds the display will show “rSt”. Remove the magnet at this time and the relays will be reset (Figure 10). 24 S4000T Figure 10: Relay Reset 3. The relays can be reset via the Remote Reset input terminals on TB2. Connect a normally open switch between terminal TB2-7 and TB2-8. Closing the switch momentarily will reset the relays. General Monitors explosion-proof switch, P/N 300511 can be used for this purpose. See Section 9.5 for ordering instructions. NOTE: Red LED’s above and below the digital display indicate that the Alarm and Warn relays are active. Latching relays can only be reset if the gas concentration has fallen below the respective relay set point. 4.4 User Selectable Options The Model S4000T Intelligent Sensor includes many selectable options to provide the user with the most flexible H2S gas detector possible. These options include Selectable Sensor Range, Warn and Alarm Relay Set Points and Configuration, and MODBUS Communications Settings. These allow the unit to operate with a wide variety of PLC and DCS Systems. The following sections explain the available options and how they can be customized. A flow diagram is included to help the user in understanding the process of reviewing and changing the available options (Figure 11). NOTE: If the unit was ordered without relays or MODBUS communications, changing the relay or MODBUS settings will have no effect on the operation of the unit. 25 S4000T 4.4.1 Model S4000T User Menu Structure Operate “rSt” Reset Relays “AC” “- -” N Enter Gas Check Mode “SE” N Set Sensor Range 20,50,100 ppm “Sr” Enter Calibration Mode “Co” N Gas Detected? “Fi” N Enable “Fi” Disable “Fi” Reset Sensor Life? N “Lo” Y Y Gas Removed? Reset Sensor Life to 100% Warm Relay “Hi” Alarm Relay Energized or De-Energized Latching or Non-Latching Setpoint “Fi” Energized or De-Energized Latching or Non-Latching Setpoint “Fi” Apply Gas and Remove When Complete “CH1” Modbus Channel 1 “CH2” Modbus Channel 1 Baud Rate Data Format Address “Fi” Baud Rate Data Format Address “Fi” N “Fi” Finished Y Figure 11: User Menu Structure NOTE: “Co” represents Calibration Output. When “Co” is enabled and calibration is successful, the analog output goes from 1.5 mA to 3.2 mA for 5 seconds, settling at the desired value of 4mA. 4.4.2 Sensor Range The Sensor Range is selectable between 0-20ppm, 0-50ppm, or 0-100ppm depending on the installed sensor. To adjust the Sensor Range of the Model S4000T, apply the magnet to the GM Logo on the cover of the unit until “SE” is displayed, then remove the magnet. This puts the unit into Setup Mode. After a few seconds “Sr” will be displayed. Apply and remove the magnet to adjust the Sensor Range. The current Sensor Range will be displayed. To change the sensor 26 S4000T range, apply and remove the magnet repeatedly, until the desired range is displayed. Once the desired range is displayed, wait 3 seconds and “Fi” will be displayed. Apply and remove the magnet, to return to the next level of the Setup menu. When “Fi” is displayed again, apply and remove the magnet to return to normal operation. NOTE: When the Sensor Range is changed, the Warning and Alarm set points are automatically scaled to the new range. The unit must now be calibrated to the new range (Section 4.6.1). 4.4.3 Warning Relay Settings To adjust the Warning Relay Settings of the Model S4000T, apply the magnet to the GM Logo on the cover of the unit until “SE” is displayed, then remove the magnet. This puts the unit into Setup Mode. After a few seconds “Lo” will be displayed. Apply and remove the magnet to change the Warning or “Low” alarm settings. First, the Energized/De-Energized state of the relay is displayed by either “En” or “dE” being displayed respectively. Apply and remove the magnet until the desired state is displayed. After a few seconds the Latching/Non-Latching state of the relay is displayed by either “La” or “nL”. Apply and remove the magnet until the desired state is displayed. After a few seconds, the current Warning relay set point is displayed. Apply and remove the magnet until the desired set point is displayed. Once the desired set point value is displayed, wait 3 seconds and “Fi” will be displayed. Apply and remove the magnet to return to the next level of the Setup menu. When “Fi” is displayed again, apply and remove the magnet to return to normal operation. The default Warning relay settings are: non-latching, de-energized, 30% FS set point. The maximum allowable set point is 50ppm. NOTE: The Warn Relay set point cannot be set higher than the Alarm Relay set point. 4.4.4 Alarm Relay Settings To adjust the Alarm Relay Settings of the Model S4000T, apply the magnet to the GM Logo on the cover of the unit until “SE” is displayed, then remove the magnet. This puts the unit into Setup Mode. After a few seconds “Hi” will be displayed. Apply and remove the magnet, to change the Alarm or “High” alarm settings. First, the Energized/De-Energized state of the relay is displayed by either “En” or “dE” being displayed respectively. Apply and remove the magnet, until the desired state is displayed. After a few seconds the Latching/Non-Latching state of the relay is displayed by either “La” or “nL”. Apply and remove the magnet, until the desired state is displayed. After a few seconds the current Alarm relay set point is displayed. Apply and remove the magnet until the desired set point is displayed. Once the desired set point value is displayed, wait 3 seconds and “Fi” will be displayed. Apply and remove the magnet to return to the next level of the Setup menu. When “Fi” is displayed again, apply and remove the magnet, to return to normal operation. 27 S4000T The default Alarm relay settings are: latching, de-energized, 60% FS set point. NOTE: The Alarm Relay set point cannot be set lower than the Warning Relay set point. 4.4.5 MODBUS Channel 1 Settings To adjust the MODBUS Channel 1 settings of the Model S4000T, apply the magnet to the GM Logo on the cover of the unit until “SE” is displayed, then remove the magnet. This puts the unit into Setup Mode. After a few seconds “CH1” will be displayed. Apply and remove the magnet, to change the MODBUS Channel 1 settings. First, the current Baud Rate MODBUS Channel 1 is displayed. If another baud rate is to be selected, apply and remove the magnet until the desired baud rate is displayed. The choices are: 19.2k baud “19.2”, 9600 baud “96”, 4800 baud “48”, or 2400 baud “24”. After a few seconds, the current Data Format for MODBUS Channel 1 is displayed. If another data format is to be selected, apply and remove the magnet until the desired data format is displayed. The choices are: 8-N-1 “8n1”, 8-N-2 “8n2”, 8-E-1 “8E1”, or 8-O-1 “8O1”. After a few seconds, the current address for MODBUS Channel 1 is displayed. Apply and remove the magnet until the desired address is displayed. Once the desired address is displayed, wait 3 seconds and “Fi” will be displayed. Apply and remove the magnet, to return to the next level of the Setup menu. When “Fi” is displayed again, apply and remove the magnet, to return to normal operation. Default settings for Channel 1 are: address 1, 19.2k baud, 8-N-1. NOTE: The address can be adjusted from 1 - 247. Channel 1 and Channel 2 addresses may be the same. 4.4.6 MODBUS Channel 2 Settings To adjust the MODBUS Channel 2 Settings of the Model S4000T, apply the magnet to the GM Logo on the cover of the unit until “SE” is displayed, then remove the magnet. This puts the unit into Setup Mode. After a few seconds “CH2” will be displayed. Apply and remove the magnet to change the MODBUS Channel 2 settings. First, the current Baud Rate MODBUS Channel 2 is displayed. If another baud rate is to be selected, apply and remove the magnet until the desired baud rate is displayed. The choices are: 19.2k baud “19.2”, 9600 baud “96”, 4800 baud “48”, or 2400 baud “24”. After a few seconds, the current Data Format for MODBUS Channel 2 is displayed. If another data format is to be selected, apply and remove the magnet until the desired data format is displayed. The choices are: 8-N-1 “8n1”, 8-N-2 “8n2”, 8-E-1 “8E1”, or 8-O-1 “8O1”. After a few seconds, the current address for MODBUS Channel 2 is displayed. Apply and remove the magnet until the desired address is displayed. Once the desired address is displayed, wait 3 seconds and “Fi” will be displayed. Apply and remove the magnet to return to the next level of the Setup menu. When “Fi” is displayed again, apply and remove the magnet to return to normal operation. 28 S4000T Default settings for Channel 2 are: address 2, 19.2 kbaud, 8-N-1. NOTE: The address can be adjusted from 1 - 247. Channel 1 and Channel 2 addresses may be the same. 4.5 Gas Check Mode The sensor’s response can be checked without activating external alarms by placing the Model S4000T in Gas Check Mode. In this mode, the alarm relays are inhibited and the analog output is fixed at 1.5mA. 4.5.1 Procedure for Checking the Calibration: Place the magnet over the GM Logo on the cover of the Model S4000T. Remove the magnet when a flashing pair of bars, “- -” (Figure 12), appear on the display (about ten seconds). Apply the test gas to the sensor, and the value of the gas concentration will be indicated by the flashing display and should stabilize in one to two minutes. Figure 12: Gas Check When the reading has stabilized and the test is complete, remove the gas and the unit will return to normal operation, when the concentration drops below 5% full-scale. If, after the reading has stabilized the sensor is to be calibrated, simply apply the magnet to the GM Logo on the housing cover, and the unit will enter Calibration Mode. Gas Check Mode can be aborted if gas has not been applied to the sensor. Simply reapply the magnet to the GM Logo on the cover and the unit will return to normal operation. NOTE: The test gas concentration must be at least 10% full-scale before the unit will complete the Gas Check sequence. If the Model S4000T is placed in the Gas Check mode and no gas is applied for twelve minutes, the unit will revert to a Fault condition. Reapplying the magnet over the GM Logo will return the unit to normal operation. 4.6 Calibration General Monitors recommends that the Model S4000T Intelligent Sensor be calibrated one hour after start-up, and again 24 hours after initial start-up, and that the calibration be checked at least every ninety (90) days, to ensure system integrity. General Monitors is not implying that the customer should expect problems with sensor life or stability, but “frequent” calibration checks merely ensure the integrity of the life protecting equipment. The above statement is not intended to discourage the customer from checking calibration more frequently. Frequent calibration checks are recommended for environments that have 29 S4000T problems, such as mud collecting on the sensor head, sensors accidentally being painted over, etc. General Monitors recommends that a calibration schedule be established and followed. A logbook should also be kept showing calibration dates and dates of sensor replacement. 4.6.1 Calibration Procedure If Hydrogen Sulfide (H2S) gas is suspected to be present, it will be necessary to purge the sensor environment with clean air. Entering Calibration Mode automatically disables the alarm circuits by sending a 1.5mA output signal and disabling the Warn and Alarm relays, if present. This will also prevent activation of the remote relay contacts when using a General Monitors Readout/Relay Display Module with the Model S4000T. To enter Calibration Mode, place the magnet over the GM Logo on the cover of the unit (Figure 4) and hold it there until “AC” (Figure 13) appears on the display (about ten seconds). The display will flash the Remaining Sensor Life (Section 4.6.3) for a few seconds. Ensure that the sensor is seeing clean air during this time. Figure 13: Automatic Calibration Mode Apply the calibration gas concentration to the sensor (50% FS of the desired range of H2S). The display will change from “AC” (Automatic Calibration) to “CP” (Calibration in Progress) indicating that the sensor is responding to the calibration gas (Figure 14). Figure 14: Calibration in Progress Mode After three to five minutes, the display will change from “CP” to “CC” (Figure 15), indicating that the calibration is complete. Figure 15: Calibration Complete Mode Remove the gas and wait for the unit to return to normal operation. The display will indicate a few percent full-scale and then drop to “0”. 30 S4000T The unit is now calibrated and the new SPAN value has been stored in the non-volatile memory (EEPROM). 4.6.2 Aborting Calibration If calibration is to be aborted, and gas has not been applied, wait ninety seconds and reapply the magnet. The unit will return to normal operation with the previous calibration values unchanged. NOTE: Once gas has been applied, it is not possible to abort a calibration. If the Model S4000T is placed in the Calibration Mode, and no gas is applied for twelve minutes, the unit will revert to a Fault (F2) condition. Re-applying the magnet over the GM Logo will return the unit to operational mode with the previous calibration values unchanged. 4.6.3 Remaining Sensor Life The Model S4000T Intelligent Sensor provides an estimate of remaining sensor life, in percent remaining, to provide the user with an early warning of the need for sensor replacement. The remaining sensor life is updated each time the unit is calibrated. The current remaining sensor life estimate is displayed during the zeroing portion of a calibration sequence. It can also be read via the MODBUS interface (Section 8.0). NOTE: The remaining sensor life provides an estimate of the amount of life remaining for the sensor. This estimate can be affected by many factors, including environmental conditions, poisons, etc. It should be used only as an estimate for preventive maintenance and logistic purposes. 4.6.4 Initializing the Remaining Sensor Life The remaining sensor life estimate must be initialized each time a new Hydrogen Sulfide Sensor is installed. The initialization should be done during the first calibration of a newly installed sensor. After the sensor has been on power for a minimum of one hour, enter calibration mode as described in Section 4.6. While the display is flashing the remaining sensor life estimate during zeroing, apply the magnet to the GM Logo on the cover. The flashing number will change to “100”, indicating the sensor has 100% of remaining sensor life. Complete the calibration per Section 4.6.1. 4.7 Calibration Equipment 4.7.1 Breaker Bottles and Ampoules General Monitors offers ampoules with breaker bottles as a method of reliably introducing calibration gas to the Model S4000T. The ampoule is placed inside the breaker bottle into the breaker slot, and the breaker bottle is placed over the sensor. The ampoule should contain 50% FS of H2S of the sensor range. Follow the calibration procedure in Section 4.6. When the display indicates “AC”, break the ampoule by turning the thumbscrew on the side of the breaker bottle clockwise. The display will change to “CP” indicating that the sensor is seeing the gas. When the display reads “CC”, the calibration is complete. Remove the breaker bottle and allow the sensor to see clean air. It will return to normal operation once the gas at the sensor is below 5% of full-scale. See Section 9.5 for available equipment. 31 S4000T 4.7.2 H2S Portable Purge Calibrator An alternate method for introducing calibration or test gas to the Model S4000T is available. The H2S Portable Purge Calibrator is a compact, practical, accurate and safe system for field calibration of H2S Sensors. The bottle is filled with a hydrogen sulfide (H2S) in air mixture and is available in 7 concentrations. The temperature limitation for operation and storage is 0°F to +130°F (-18°C to +54°C). NOTE: Do not store the cylinder with the regulator fully engaged in the cylinder valve. Use the calibration procedure listed below for H2S Portable Purge calibrations: Make sure the Portable Purge Calibrator contains a gas concentration equivalent to 50% of fullscale for the unit that is going to be calibrated. 1. Ensure that the sensor is seeing clean air. If it is suspected that hydrogen sulfide gas is present, it will be necessary to purge the sensor environment with clean air. 2. Place the gas cup over the sensor and initiate the calibration sequence, by placing the magnet over the GM Logo on the cover of the unit. 3. When the letters “AC” appear in the display window remove the magnet and apply the calibration gas (50% of full-scale) by opening the valve on the cylinder. 4. When the sensor begins to see the gas, the display will change from “AC” to “CP” to indicate “Calibration in Progress”. 5. When the calibration sequence is complete, the display will change from “CP” to “CC” to indicate “Calibration Complete”. 6. Remove the gas by closing the valve on the cylinder, and remove the cup allowing the sensor to see clean air. The display will change from “CC” to indicate a few parts per million (ppm) and then drop to “0”. The unit is now calibrated and the new values have been stored in the EEPROM (non-volatile memory). See Section 9.5 for available equipment. 32 S4000T 5.0 Maintenance 5.1 General Maintenance WARNING: Disconnect or inhibit external devices such as Trip Amplifiers, PLC’s, or DCS systems before performing any maintenance. European Union (EU) Approved Applications: The following grease compound is recommended for use: PBC Polybutylcuprysil, (or equivalent), which has BASEEFA Health & Safety Executive component approval No. 1051U for use as a jointing compound on flameproof electrical enclosures. This is available from General Monitors. The neoprene rubber gasket should also be lubricated with Type P80 lubricant available from General Monitors (P/N 610-010). 5.2 Storage The Model S4000T H2S Gas Detector should be stored in a clean, dry area and within the temperature and humidity ranges quoted in the Appendix under Environmental Specifications. Insert red dust caps into any vacant cable entry holes. 33 S4000T 6.0 Troubleshooting CAUTION: Component level repair must be undertaken either by General Monitors’ personnel, or by competent authorized service engineers. SMT PCB repair shall only be performed at a General Monitors’ facility. Failure to comply with this requirement will invalidate the warranty. Be sure to inhibit or disconnect external alarm wiring before making any check, which might send the unit into alarm, if an alarm condition will cause a problem. 6.1 Fault Codes & Their Remedies The Model S4000T has self-diagnostics incorporated into the microprocessor’s program. If a fault is detected, the output signal will drop to 0mA, the Fault relay will de-energize and a fault code will be displayed. The output signal will inform a remote display module that the Model S4000T is in the Fault Mode. The display will indicate a fault code that can be viewed at the sensor site. There are nine fault conditions that are monitored by the microprocessor as follows: 6.1.1 F2 - Failed to Complete the Calibration This fault will occur if the unit is placed in the calibration mode and no gas has been applied within twelve minutes, or if gas has been left on for more than 12 minutes. ACTION – Remove gas, if present. Apply magnet to GM Logo on the cover to clear fault. Recalibrate, if necessary. 6.1.2 F3 - EPROM Checksum Error This fault indicates that the contents of the Model S4000T’s program memory have changed. This usually occurs when powering the unit up after a lightning strike or large voltage transient on the power or signal lines to the unit. ACTION - The unit must be returned to the factory or authorized service center for repair. 6.1.3 F4 - Sensor Heater Open Error This fault indicates that one of the sensor circuit leads is open-circuited. ACTION - Check the integrity of all sensor connections, and ensure that the cable from the Model S4000T to the remote sensor is not damaged. If this does not correct the problem, replace the sensor and recalibrate. 6.1.4 F5 - Sensor Heater Shorted Error This fault indicates that one of the sensor circuit leads is short-circuited. ACTION - Check the integrity of all sensor connections, and ensure that the cable from the Model S4000T to the remote sensor is not damaged. If this does not correct the problem, replace the sensor and recalibrate. 34 S4000T 6.1.5 F6 - Low Supply Voltage This fault occurs if the supply voltage at the S4000T drops below +18.5VDC. ACTION - Ensure that the supply voltage is at least +20VDC at the Model S4000T. NOTE: With long supply leads, a considerable voltage drop may occur, due to the electrical resistance of the leads. The maximum cable resistance, which the Model S4000T can tolerate, is dependent on the supply voltage. A maximum of 20 ohms per conductor (40 ohms loop), at +24VDC minimum, or a maximum of 10 ohms per conductor (20 ohms loop), at +20VDC minimum. 6.1.6 F7 - EEPROM Verification Failure This fault occurs when an attempt to verify the setup/calibration parameters just written to the EEPROM memory fails. ACTION - The unit must be returned to the factory or authorized service center for repair. 6.1.7 F8 - Failure to Complete Setup This fault occurs if the unit is left in setup mode for more than 6 minutes. ACTION - Exit setup mode. Enter setup mode again if it is necessary, to change any user selectable options. 6.1.8 F9 - Gas Check Period Exceeded If the Model S4000T is left in the gas check mode for more than twelve minutes with Test Gas applied, this fault will occur. ACTION - Place the magnet over the GM Logo on the cover to return the unit to normal operation. NOTE: Anytime a sensor is replaced, the unit should be disconnected from all alarms, as the unit may go upscale upon power-up. 6.1.9 F10 – Switch Error This fault occurs if either the remote test, remote calibrate, or magnetic switch are closed for more than two minutes. ACTION – Check the wiring on the Remote Reset and Remote Calibrate switches. Once the short circuit is cleared, the unit will return to normal operation. If the magnetic switch is shorted, the unit must be returned to the factory or to an authorized service center for service. 35 S4000T 7.0 Customer Support 7.1 General Monitors’ Offices Area UNITED STATES Phone/Fax/Email Toll Free: +1-800-446-4872 Phone: +1-949-581-4464 Fax: +1-949-581-1151 Email: info@generalmonitors.com Corporate Office: 26776 Simpatica Circle Lake Forest, CA 92630 9776 Whithorn Drive Houston, TX 77095 Phone: +1-281-855-6000 Fax: +1-281-855-3290 Email: gmhou@generalmonitors.com UNITED KINGDOM Heather Close Lyme Green Business Park Macclesfield, Cheshire, United Kingdom, SK11 0LR IRELAND Ballybrit Business Park Galway, Republic of Ireland SINGAPORE No. 2 Kallang Pudding Rd. #09-16 Mactech Building Singapore 349307 MIDDLE EAST LOB12, #G20 P.O. Box 61209 Jebel Ali, Dubai United Arab Emirates Phone: +44-1625-619-583 Fax: +44-1625-619-098 Email: info@generalmonitors.co.uk Phone: +353-91-751175 Fax: +353-91-751317 Email: info@gmil.ie Phone: +65-6-748-3488 Fax: +65-6-748-1911 Email: genmon@gmpacifica.com.sg Phone: +971-4-8815751 Fax: +971-4-8817927 Email: gmme@emirates.net.ae Table 8: GM Locations 36 S4000T 8.0 MODBUS Interface 8.1 Baud Rate The Baud Rate is selectable via the MODBUS Communications Interface. The selectable baud rates are 19200, 9600, 4800, or 2400 bits per second. 8.2 Data Format The Data Format is selectable via the MODBUS Communications Interface. The selectable data formats are as follows: Data Bits 8 8 8 8 Parity None Even Odd None Stop Bit 1 1 1 2 Format 8-N-1 8-E-1 8-O-1 8-N-2 Table 9: Data Format 8.3 MODBUS Read Status Protocol (Query/Response) 8.3.1 MODBUS Read Query Message Byte 1st 2nd 3rd 4th 5th 6th 7th MODBUS Slave Address Function Code Starting Address Hi** Starting Address Lo** No. Of Registers Hi No. Of Registers Lo CRC Lo Range 1-247* (Decimal) 03 00 00-FF (Hex) 00 01 00-FF (Hex) Referenced to S4000T S4000T ID (Address) Read Holding Registers Not Used by S4000T S4000T Commands Not Used by S4000T No. Of 16 Bit Registers CRC Lo Byte 8th CRC Hi 00-FF (Hex) CRC Hi Byte *NOTE: Address 0 is reserved for broadcast mode and will not be supported at this time. ** NOTE: Start Address can be a maximum of 9999 Address Locations (0000-270E). 8.3.2 MODBUS Read Response Message Byte 1st 2nd 3rd 4th 5th 6th 7th MODBUS Slave Address Function Code Byte Count Data Hi Data Lo CRC Lo CRC Hi Range 1-247* (Decimal) 03 02 00-FF (Hex) 00-FF (Hex) 00-FF (Hex) 00-FF (Hex) 37 Referenced to S4000T S4000T ID (Address) Read Holding Registers No. Of Data Bytes S4000T Hi Byte Status Data S4000T Lo Byte Status Data CRC Lo Byte CRC Hi Byte S4000T 8.4 MODBUS Write Command Protocol (Query/Response) 8.4.1 MODBUS Write Query Message Byte 1st 2nd 3rd 4th 5th 6th 7th 8th MODBUS Slave Address Function Code Register Address Hi Register Address Lo Preset Data Hi Preset Data Lo CRC Lo CRC Hi Range 1-247* (Decimal) 06 00 00-FF (Hex) 00-FF (Hex) 00-FF (Hex) 00-FF (Hex) 00-FF (Hex) Referenced to S4000T S4000T ID (Address) Preset Single Register Not Used by S4000T S4000T Commands S4000T Hi Byte Command Data S4000T Lo Byte Command Data CRC Lo Byte CRC Hi Byte *NOTE: Address 0 is reserved for broadcast mode and will not be supported at this time. **NOTE: Start Address can be a maximum of 9999 Address Locations (0000-270E). 8.4.2 MODBUS Write Response Message Byte 1st 2nd 3rd 4th 5th 6th 7th 8th MODBUS Slave Address Function Code Register Address Hi Register Address Lo Preset Data Hi Preset Data Lo CRC Lo CRC Hi Range 1-247* (Decimal) 06 00 00-FF (Hex) 00-FF (Hex) 00-FF (Hex) 00-FF (Hex) 00-FF (Hex) Referenced to S4000T S4000T ID (Address) Preset Single Register Not Used by S4000T S4000T Commands S4000T Hi Byte Command Data S4000T Lo Byte Command Data CRC Lo Byte CRC Hi Byte 8.5 Function Codes Supported Function Code 03 (Read Holding Registers) will be used to read status from the slave unit. Function Code 06 (Preset Single Register) will be used to write a command to the slave unit. 8.6 Exception Responses and Exception Codes 8.6.1 Exception Response In a normal communications query and response, the master device sends a query to the S4000T and the S4000T receives the query without a communications error and handles the query normally within the master device’s allowable timeout. The S4000T then returns a normal response to the master. An abnormal communications produces one of four possible events: 1. If the S4000T does not receive the query due to a communications error, then no response is returned from the S4000T and the master device will eventually process a timeout condition for the query. 2. If the S4000T receives the query, but detects a communication error (CRC, etc.), then no response is returned from the S4000T and the master device will eventually process a timeout condition for the query. 3. If the S4000T receives the query without a communications error, but cannot process 38 S4000T the response to the master within the master’s timeout setting, then no response is returned from the S4000T. The master device will eventually process a timeout condition for the query. In order to prevent this condition from occurring, the maximum response time for the S4000T is 200 milliseconds. Therefore, the master’s timeout setting should be set to 200 milliseconds or greater. 4. If the S4000T receives the query without a communications error, but cannot process it due to reading or writing to a non-existent S4000T command register, then the S4000T will return an exception response message informing the master of the error. The exception response message (ref. No. 4 above) has two fields that differentiate it from a normal response: Byte 1st 2nd 3rd 4th 5th MODBUS Slave Address Function Code Exception Code CRC Lo CRC Hi Range 1-247* (Decimal) 83 or 86 (Hex) 01 - 06 (Hex) 00-FF (Hex) 00-FF (Hex) Referenced to S4000T S4000T ID (Address) MSB is set with Function Code Appropriate Exception Code (See Below) CRC Lo Byte CRC Hi Byte 8.6.2 Exception Code Exception Code Field: In a normal response, the S4000T returns data and status in the data field, which was requested in the query from the master. In an exception response, the S4000T returns an exception code in the data field, which describes the S4000T condition that caused the exception. Below is a list of exception codes that are supported by the S4000T: Code 01 Name Illegal Function 02 Illegal Data Address 03 Illegal Data Value 04 Slave Device Failure 05 Acknowledge 06 Device Busy Description The function code received in the query is not an allowable action for the S4000T The data address received in the query is not an allowable address for the S4000T. A value contained in the query data field is not an allowable value for the S4000T. An unrecoverable error occurred while the S4000T was attempting to perform the requested action. The S4000T has accepted the request and is processing it, but a long duration of time will be required to do so. This response is returned to prevent a timeout error from occurring in the master. The S4000T is engaged in processing a long-duration program command. The master should retransmit the message later when the slave is free. Table 10: Exception Codes 39 S4000T 8.7 S4000T Command Register Locations Parameter Analog Mode Status/Error Not Used Unit Type Software Rev Status Block Not Used Alarm Settings Warn Settings Com1 Addr. Com1 Baud Com1 Data Format Com2 Addr. Com2 Baud Com2 Data Format Not Used Reset Alarms Sensor Life Sensor Scale HazardWatch (Co) Not Used Total Receive Errors Bus Activity Rate % Function Code Errors Starting Addr. Errors Function 0-20mA Current Output Indicates and Controls Mode Indicates Errors N/A Identifies the S4000T in Decimal Indicates the Software Revision Returns Analog, Mode, Status, Error, and Sensor Life N/A Read or change settings for the high alarm Read or change settings for the low alarm Read or change settings for the Com1 Address Read or change settings for the Com1 Baud Rate Read or change settings for the Com1 Data Format Read or change settings for the Com2 Address Read or change settings for the Com2 Baud Rate Read or change settings for the Com2 Data Format N/A Reset any latched alarms Read the Remaining Sensor Life Change the Scale for the H2S sensors on the S4000T Indicates Calibration Success N/A Total # of Receive Errors Bus Activity Rate in % of This Addressed Node vs. Other Addressed Nodes Total # of Function Code Errors Total # of Starting Address Errors Bit Access R R/W R Register Address 0000 0001 0002 Value 16-Bit R 0004 Master I/O Address 40001 40002 40003 40004 40005 ASCII 2Char 6bytes R 0005 40006 R 0006 40007 Type Value Bit Multi Scale 16-Bit Bit (0-15) R/W 000D 40008-40013 40014 Bit (0-15) R/W 000E 40015 Value 8-Bit R/W 000F 40016 Bit (0-7) R/W 0010 40017 Bit (0-7) R/W 0011 40018 Value 8-Bit R/W 0012 40019 Bit (0-7) R/W 0013 40020 Bit (0-7) R/W 0014 40021 Bit Bit (0) (0) W R 0016 0017 40022 40023 40024 Value 8-Bit R/W 0018 40025 Value 8-Bit R/W 0019 40026 Value 8-Bit R 0020 40027-40032 40033 R 0021 40034 Decimal Value 8-Bit R 0022 40035 Value 8-Bit R 0023 40036 Table 11: Command Register Locations 40 S4000T Parameter Function Type Scale Access No. of Register Errors RXD CRC Hi Errors RXD CRC Low Errors Not Used Total # of Register Errors Value 8-Bit Total # of RXD CRC Hi Errors Value Total # of RXD CRC Low Errors N/A Value Clear All Comm Errors Bit Clear Comm Errors R Register Address 0024 Master I/O Address 40037 8-Bit R 0025 40038 8-Bit R 0026 40039 40040-40045 W 0027 002C 002D (0) 40046 Table 12: Command Register Locations, Cont. 8.8 S4000T Command Register Details 8.8.1 Analog A read returns a value, which is proportional to the 0-20mA output current. The current is based on a 16-bit value. The scaling is 0 - 65535 decimal which corresponds to 0 - 21.7mA. 8.8.2 Mode A read returns the present mode of the S4000T. A write command changes the mode to the requested mode. Exception: Returns an Exception Code 01 (illegal function) if an illegal write is requested. A calibrate command returns an Exception Code 01 (Acknowledge 05). The operation will take a long time to complete. Function Calibration Complete Spanning Zero Complete, Waiting for Gas Zeroing Calibration Mode Calibration Check Mode Run Mode Startup Mode Bit Position 7 MSB 6 5 4 3 2 1 0 LSB 41 Access Read Read Read Read Read/Write Read/Write Read Read S4000T 8.8.3 Status/Error A read returns the Alarm state and Errors that are occurring at the present time, which are indicated, by bit position. Function Alarm Warn Fault Not Used Not Used Not Used Not Used Switch Error Setup Error Calibration Check Timeout EEPROM Error EPROM Error Sensor Error Fail to Calibrate Low Supply Voltage Bit Position 15 MSB 14 13 12 11 10 9 8 7 6 5 4 3 2 1 Access Read Read Read Read Read Read Read Read Read Read Read Read Read Read Read 8.8.4 Unit Type A read returns the Decimal Value 4000. This identifies the S4000C. A read returns the Decimal Value 4001. This identifies the S4000T. 8.8.5 Software Revision A read returns the software revision of the S4000T in 2 ASCII characters. 8.8.6 Status Block A read returns a 6-byte message containing the analog (2 bytes), Mode (1 byte), Status/Error (2 bytes), and Sensor Life (1 byte) in that order. For the format of each byte, refer to the appropriate individual commands. 8.8.7 Alarm Settings A read returns the present Alarm settings of the S4000T. A write command changes the settings to the requested values. The set points are programmable in 5% FS steps (1% FS steps for 20ppm range). A 1 in the 9th bit position means the output is latching, a 0 means it is Non-Latching. A 1 in the 8th bit position means the output is normally energized a 0 means it is normally De-Energized. The Alarm set point cannot be set below the Warn set point. Factory default is: 60% FS, latching, de-energized. Exception: Returns an Exception Code 01 (illegal function) if an illegal write is requested. 42 S4000T Byte High Low Function Not Used Not Used Not Used Not Used Not Used Not Used Latching/Non-Latching Energized/De-Energized Set point Bit Position 15 MSB 14 13 12 11 10 9 8 (7-0) Access Read Read Read Read Read Read R/W R/W R/W 8.8.8 Warn Settings A read returns the present Warn settings of the S4000T. A write command changes the settings to the requested values. The set points are programmable in 5% FS steps (1% FS steps for 20ppm range). A 1 in the 9th bit position means the output is latching, a 0 means it is Non-Latching. A 1 in the 8th bit position means the output is normally energized a 0 means it is normally De-Energized. The Warn set point cannot be set above the Alarm set point. Factory default is: 30% FS, nonlatching, de-energized. The maximum allowable set point is 50ppm. Exception: Returns an Exception Code 01 (illegal function) if an illegal write is requested. Byte High Low Function Not Used Not Used Not Used Not Used Not Used Not Used Latching/Non-Latching Energized/De-Energized Set point Bit Position 15 MSB 14 13 12 11 10 9 8 (7-0) Access Read Read Read Read Read Read R/W R/W R/W 8.8.9 Com1 Address A read command returns the current address for Com1. A write command changes the address to the requested value. Valid addresses are 1-247 decimal. Factory default is 1. Exception: If the address is not in range an Illegal data value (03) is returned. 8.8.10 Com1 Baud Rate A read command returns the current baud rate for Com1. A write command changes the baud rate to the requested values. Valid settings are shown in the table below. Factory default is 19,200. Baud Rate Value Access 2400 24 Read/Write 4800 48 Read/Write 9600 96 Read/Write 19,200 192 Read/Write Table 13: Com1 Baud Rate Exception: If the baud rate is not in range, an illegal data value (03) is returned. 43 S4000T 8.8.11 Com1 Data Format A read command returns the current data format for Com1. Write command changes the data format to the requested values. Valid settings are shown in the table below. Default format is 8-N-1. Data 8 8 8 8 Parity None Even Odd None Stop 1 1 1 2 Format 8-N-1 8-E-1 8-O-1 8-N-2 Data(Bits 9-8) 0 1 2 3 Access Read/Write Read/Write Read/Write Read/Write Table 14: Com1 Data Format Exception: If the data format is not in range, an illegal data value (03) is returned. 8.8.12 Com2 Address A read command returns the current address for Com2. A write command changes the address to the requested values. Valid addresses are 1-247 decimal. Factory default is 2. Exception: If the address is not in range an Illegal data value (03) is returned. 8.8.13 Com2 Baud Rate A read command returns the current baud rate for Com2. A write command changes the baud rate to the requested values. Valid settings are shown in the table below. Factory default is 19,200. Baud Rate 2400 4800 9600 19,200 Value 24 48 96 192 Access Read/Write Read/Write Read/Write Read/Write Table 15: Com2 Baud Rate Exception: If the baud rate is not in range an illegal data value (03) is returned. 8.8.14 Com2 Data Format A read command returns the current data format for Com2. Write command changes the data format to the requested values. Valid settings are shown in the table below. Factory default is 8-N-1. Data 8 8 8 8 Parity None Even Odd None Stop 1 1 1 2 Format 8-N-1 8-E-1 8-O-1 8-N-2 Data(Bits 9-8) 0 1 2 3 Access Read/Write Read/Write Read/Write Read/Write Table 16: Com2 Data Format Exception: If the data format is not in range an illegal data value (03) is returned. 44 S4000T 8.8.15 Reset Alarms A write to this register with a data value of 1 will reset any latched alarms provided the current gas level is below the alarm set point. 8.8.16 Sensor Life A read returns the current estimate of remaining sensor life in percentage. 8.8.17 Sensor Scale A read returns the current H2S sensor scale selected: 0-20ppm, 0-50ppm, 0-100ppm. A write changes the scale to the desired scale. If the scale is changed, a calibration fault is generated, forcing the operator to calibrate the unit. H2S Sensor Scale 0-20 ppm 0-50 ppm 0 –100 ppm Value (decimal) 20 50 100 Table 17: Sensor Scale 8.8.18 HazardWatch (Co – Calibration Output) A read to this register will return the status of the HazardWatch Option. 0x01 enables this option, 0x00 disables this option, similar to the write. NOTE: Only Com1 can support read/write to this register. 8.8.19 Total Receive Errors A read indicates the total MODBUS Comm Receive Errors that occurred in the slave device. The maximum count is 255 and then the counter will rollover to zero and begin counting again. The total errors are an accumulation of the individual communication errors listed below: 8.8.20 Bus Activity Rate % A read indicates the Bus Activity Rate in percent of this Slave’s addressed node versus other addressed nodes. Range of this value is in hex (0-64) which translates to decimal (0-100%). 8.8.21 Function Code Errors A read indicates the number of Function Code Errors that occurred in the slave device. The maximum count is 255 and then the counter will rollover to zero and begin counting again. 8.8.22 Starting Address Errors The counter is incremented for each address that does not equal the device address. A read indicates the number of Starting Address Errors that occurred in the slave device. The maximum count is 255 and then the counter will rollover to zero and begin counting again. 45 S4000T 8.8.23 Number of Register Errors A read indicates the Number of Register Errors that occurred in the slave device. The maximum count is 255 and then the counter will rollover to zero and begin counting again. 8.8.24 RXD CRC Hi Errors A read indicates the number of RXD CRC Hi Byte Errors that occurred in the slave device. The maximum count is 255 and then the counter will rollover to zero and begin counting again. 8.8.25 RXD CRC Low Errors A read indicates the number of RXD CRC Low Byte Errors that occurred in the slave device. The maximum count is 255 and then the counter will rollover to zero and begin counting again. 8.8.26 Clear Comm Errors A Read or Write resets all the MODBUS Comm Error counters to zero. 46 S4000T 9.0 Appendix 9.1 Warranty General Monitors warrants the Model S4000T to be free from defects in workmanship or material under normal use and service within two years from the date of shipment. General Monitors will repair or replace without charge any such equipment found to be defective during the warranty period. Full determination of the nature of, and responsibility for, defective or damaged equipment will be made by General Monitors’ personnel. Defective or damaged equipment must be shipped to the General Monitors’ plant or representative from which the original shipment was made. In all cases this warranty is limited to the cost of the equipment supplied by General Monitors. The customer will assume all liability for the misuse of this equipment by its employees or other personnel. All warranties are contingent upon proper use in the application for which the product was intended and does not cover products which have been modified or repaired without General Monitors’ approval, or which have been subjected to neglect, accident, improper installation or application, or on which the original identification marks have been removed or altered. Except for the express warranty stated above, General Monitors disclaims all warranties with regard to the products sold, including all implied warranties of merchantability and fitness and the express warranties stated herein are in lieu of all obligations or liabilities on the part of General Monitors for damages including, but not limited to, consequential damages arising out of, or in connection with, the performance of the product. 9.2 Principle of Operation General Monitors uses a proprietary Metal Oxide Semiconductor (MOS) film on the sensor for detecting Hydrogen Sulfide (H2S) gas. The MOS film is deposited onto a substrate between two electrodes. With no gas present, the measured resistance between these two electrodes is very high (in the mega-ohms). As H2S adsorbs onto the film, the resistance between the two electrodes decreases (to kilo-ohms). This decrease in resistance is logarithmically proportional to the concentration of H2S that is present. The change in resistance is converted to a change in voltage, and amplified by the input circuit. This amplified signal is fed to an Analog to Digital (A/D) Converter, converted to a digital signal and sent to the microprocessor to be processed. The process of H2S adsorbing onto the MOS film is most effective at an elevated temperature. On the outer edge of the substrate is a heater ring. The temperature of this heater ring is measured with a thermistor, and kept constant by a circuit located inside the body of the sensor. As H2S adsorbs onto the film, electrons move more freely from one electrode to the other. This is represented as a decrease in resistance. The process of H2S adsorbing onto the MOS film is completely reversible. As the concentration of H2S decreases (H2S desorbs), the resistance between the electrodes will increase. 47 S4000T 9.3 Specifications 9.3.1 System Specifications Sensor Type: Sensor Life: Repeatability: Response Time: Measuring Ranges: Modes: Electrical Classification: Warranty: Continuous diffusion, adsorption type Metal Oxide Semiconductor (MOS) 3 to 5 years typical +2 ppm or 10% of the applied gas, whichever is greater T50<1 minute (screen) T50<2 minutes (sintered) with full scale gas applied 0-20 ppm, 0-50 ppm, 0-100 ppm Calibration, gas check, setup CSA/FM: Class I, Division 1, Groups B, C, D and Class I, Zone 1, Ex d IIB+H2, T6. ATEX: EEx d IIB T6 (Tamb=-40°C to +40°C) Two years 9.3.2 Mechanical Specifications Length: Height: Width: Weight: Mounting Holes: 6.4 inches (161mm) 3.4 inches (86mm) 4.1 inches (104mm) 5.5 lbs. (2.5 kg) 5.0 inches (127mm) (center to center) 9.3.3 Electrical Specifications Input Power: Power Consumption 24 VDC nominal, 20 to 36 VDC, 350mA max. Start-up 270mA, Normal Operation 120mA Relay Ratings: 8A @ 250 VAC/8A @ 30 VDC resistive max. (3x) SPDT - Warning, Alarm & Fault Analog Signal: 0-20mA (650 ohms max. load) Malfunction 0mA Gas Check 1.5mA Setup mode 1.5mA Calibration 1.5mA Zero reading 4mA±0.2mA 0-100% scale 4-20mA Over-range 20-22mA Three-digit digital display with gas concentration, Warn and Alarm LED’s, calibration prompts, fault codes, and setup options Dual Redundant MODBUS RTU, suitable for linking up to 128 units or up to 247 units with repeaters 2400, 4800, 9600, or 19200 BPS Open AO, calibration error, sensor heater error, low DC supply, EEPROM, EPROM, setup error, gas check time exceeded, switch error. Complies with EN50081-2, EN50082-2 Status Indicators: RS-485 Output: Baud Rate: Faults Monitored: RFI/EMI Protection: 48 S4000T Cable Requirements: 3-wire shielded cable. Max. distance between S4000T and power source @ 24 VDC nominal AWG 14 16 18 20 FEET 3430 1550 1050 650 METERS 1040 410 320 200 Table 18: 24VDC Cable Lengths Max. distance for analog output (650 ohms max): AWG 14 16 18 20 FEET 9000 5200 3800 2400 METERS 2740 1585 1160 730 Table 19: Analog Output Cable Lengths Max. distance between the transmitter and sensor with one way resistance of 10 ohms (20Ohm loop): AWG 14 16 18 20 FEET 3700 2400 1500 1000 METERS 1125 730 460 300 Table 20: Sensor Cable Lengths European Union (EU) Approved Applications: PSU noise and ripple voltage 1.0Vpp max. The customer supplied PSU must comply with IEC 1010-1, limiting current to 8A under Fault conditions, in order to comply with CE Marking requirements. 9.3.4 Environmental Specifications Operating Temperature Range CSA/FM: Electronics Standard Sensor High Temp Sensor ATEX: Electronics (T6) -40°F to 167°F (-40°C to 75°C) -40°F to 167°F (-40°C to 75°C) -40°F to 195°F (-40°C to 90°C) -40°F to 104°F (-40°C to + 40°C) Storage Temperature Range: -58°F to 185°F (-50°C to +85°C) Operating Humidity Range: 5% to 100% RH, non-condensing 49 S4000T 9.4 Approvals CSA, FM, ATEX, CE Marking, GOST permission to use Compiles with ISA-92.0.01, Part 1-1998 performance requirements 9.5 Spare Parts and Accessories To order spare parts and/or accessories, please contact the nearest General Monitors’ Representative or, General Monitors directly, and give the following information: • Part Number of Spare Part or Accessory • Description of Spare Part or Accessory • Quantity of Spare Part or Accessory 9.5.1 Sensors 50445-1 0 to 100ppm, Aluminum Body, Wire Screen Arrestor 50445-5 0 to 50ppm, Aluminum Body, Wire Screen Arrestor 50445-9 0 to 20ppm, Aluminum Body, Wire Screen Arrestor 50448-1HT 0 to 100ppm, Stainless Steel Body, Wire Screen Arrestor, High Temp 50448-5HT 0 to 50ppm, Stainless Steel Body, Wire Screen Arrestor, High Temp 50448-9HT 0 to 20ppm, Stainless Steel Body, Wire Screen Arrestor, High Temp 51457-1L 0 to 100ppm, Stainless Steel Body, Sintered Steel Arrestor 51457-5L 0 to 50ppm, Stainless Steel, Sintered Steel Arrestor 51457-9L 0 to 20ppm, Stainless Steel, Sintered Steel Arrestor 50460-1 Sensor Simulator 9.5.2 Sensor Housing 10252-1 Universal Housing 50 S4000T 9.5.3 Sensor Accessories 10041-1 Duct Mounting Plate 10044-1 Dust Guard Kit - 1 Guard, 12 Replaceable Screens 10042-1 Replaceable Screens, Box of 12 10395-1 Splash Guard Assembly 10110-1 Dust Guard Assembly 1800822 Dust Guard, Sintered SST 10066 Sensor Flow Chamber 9.5.4 Calibration Equipment 50000 Breaker Bottle, Single 50004-3 Individual Ampoules, 10 ppm (12 minimum) 50004-21 Individual Ampoules, 25 ppm (12 minimum) 50004-13 Individual Ampoules, 50 ppm (12 minimum) 50008-9 12 Ampoules at 50ppm (0-100ppm scale) 50008-16 12 Ampoules at 25ppm (0-50ppm scale) 50008-10 12 Ampoules at 10ppm (0-20ppm scale) 50009-9 12 Ampoules at 50ppm, includes breaker bottle (0-100ppm scale) 50009-16 12 Ampoules at 25ppm, includes breaker bottle (0-50ppm scale) 50009-10 12 Ampoules at 10ppm, includes breaker bottle (0-20ppm scale) 1400250-1 10ppm H2S Portable Purge Calibration Assembly 1400250-3 25ppm H2S Portable Purge Calibration Assembly 1400250-5 50ppm H2S Portable Purge Calibration Assembly 1400255-1 10ppm H2S Replacement Cylinder 1400255-3 25ppm H2S Replacement Cylinder 1400255-5 50ppm H2S Replacement Cylinder 51 S4000T Case for Portable Purge Assembly 922-016 Replacement Regulator (0.2 L/min) Replacement Hose 960-345 Hose Clamp, 5/16” 960-346 Hose Clamp, ¼” 1400152-1 Calibration Cup 9.5.5 Intelligent Sensor (S4000T) Replacement Parts 31161-1 Control Board Electronics 31151-1 Output Board Electronics 31156-1 Display Board Electronics 31170-2 Enclosure Cover Assembly with Window 31195-2 Enclosure Base Assembly 30051-1 Explosion-Proof SPST Switch 30060-1 Calibration Magnet Cover Assy., O-Ring 9.5.6 Recommended Spare Parts for One (1) Year 30060-1 Extra Calibration Magnet (Qty. 1) 52 S4000T 9.6 FMRC Approval Factory Mutual Research Corporation 1151 Boston-Providence Turnpike Norwood, Massachusetts 02062 Approval of the transmitter does not include or imply approval of apparatus, to which the transmitter may be connected and which processes the electronic signal for the eventual end use. In order to maintain FMRC approved system, the control instrument, to which the subject instrument is connected, must also be FMRC approved. The following sensors have been FMRC approved for use with the Model S4000T: • 50445-1 Aluminum Body H2S Gas Specific MOS Sensor, 0 to 100 ppm • 50445-5 Aluminum Body H2S Gas Specific MOS Sensor, 0 to 50 ppm • 50445-9 Aluminum Body H2S Gas Specific MOS Sensor, 0 to 20 ppm • 50448-1HT Stainless Steel Body H2S Gas Specific MOS Sensor, 0 to 100 ppm • 50448-5HT Stainless Steel Body H2S Gas Specific MOS Sensor, 0 to 50 ppm • 50448-9HT Stainless Steel Body H2S Gas Specific MOS Sensor, 0 to 20 ppm The following apparatus have been FMRC approved (although they have not been verified as part of a Model S4000T system): • Model DT210 Eight-Channel Readout/Relay Display Module with Power Supply and Relay Module • Model DT230 Dual-Channel Readout/Relay Display Module 53 S4000T ADDENDUM Product Disposal Considerations This product may contain hazardous and/or toxic substances. EU Member states shall dispose according to WEEE regulations. For further General Monitors’ product WEEE disposal information please visit: www.generalmonitors.com/customer_support/faq_general.html All other countries or states: please dispose of in accordance with existing federal, state and local environmental control regulations. 54