ATP SERIES
Rev. 1.14
ATP SERIES AC Current Transducers
AC Current Transducers
ATP Series Powered AC Current Transducers sense currents
from 0–200 A and provide a proportional analog VDC or
mA output. Powered by 120 VAC or 24 VAC/VDC, the
ATP Series Powered AC Current Transducers eliminate the
need for costly power supplies or voltage rectifiers inside the
control panel. Designed for motor control applications with
standard sinusoidal waveforms, the ATP Series Powered AC
Current Transducers feature user-selectable input ranges, a
choice of outputs and split-core or solid-core enclosures.
AC Current Transducer Applications
AC Current Transducer Features
Commercial and Industrial Motor Control Centers
•120 VAC power supply option allows for powering off
of readily available supplies; ideal for pumping, water/
wastewater, boiler and other industrial applications.
•Eliminates the need for 24 VDC power supply or AC
rectifiers within the control panel; saves space, material
and labor associated with power supplies.
Fast, Accurate RMS Measurement
•Unique ‘average responding’ algorithm provides RMS
output on pure sine wave and constant speed loads,
offering improved accuracy over two-piece solutions.
Heater Failure Detection
Isolation Output
•Output is magnetically isolated from the input for
enhanced safety and elimination of insertion losses.
Jumper Selectable Input Ranges
•Each unit has multiple input range capability and can be
used for a variety of applications, reducing the need for
separate models.
AC Current Transducer Connections
For additional Application Examples,
see page 102 and www.nktechnologies.com
Notes:
Terminals are deadfront captive screw terminals.
Use 12–22 AWG solid or stranded.
Test &
Evaluation Units
Fo r
OEMs
42
Free program expedites
evaluation process.
See page 1 for details.
3511 Charter Park Drive • San Jose, CA 95136
800.959.4014 • www.nktechnologies.com • sales@nktechnologies.com
ATP SERIES
AC Current Transducer Specifications
AC Current Transducer Dimensions
FF Case
-005 Model
-010 Model
-420 Model
Output Signal
0–5 VDC
0–10 VDC
4–20 mA
2.75"
Output Limit
112% (5.6 V)
112% (11.2
V)
112% (22.4
mA)
Loading
25 KΩ min.: VDC Models
500 Ω max.: 4–20 mA Models
Response Time
100 ms (10–90% step change)
Frequency Range
40–100 Hz standard. Special calibration for
frequencies 100–400 Hz, consult factory.
Accuracy
1.0% FS
Power Supply
120 VAC or 24 VAC/VDC, 2 VA max
Isolation Voltage
Tested to 5 KV
Input Ranges
0–200 A Jumper-selectable
Sensing Aperture
• -FF Case: 0.55” (14 mm) dia.
• -SP Case: 0.85” (21.6 mm) sq.
Case
UL94 V0 Flammability Rated
Environmental
-4 to 122°F (-20 to 50°C)
0–95% RH, non-condensing
0.92"
Ø 0.19"
2.16"
Ø 0.55"
2.18"
SP Case
AC Current Transducers
3.30"
3.50"
3.00"
AC Current Transducer Ordering Information
Sample Model Number: ATP1-420-120-SP
1.19"
Ø
0.19"
Powered AC current transducer, jumper-selectable 0–10/20/50 A
range, 4–20 mA output, 120 VAC power supply, split-core enclosure.
(1)
2.40"
ATP
(2)
–
(3)
–
(4)
–
(1) Full Scale Range
0.85"
2.25"
0.85"
0
2A&5A
1
10, 20, 50 A
2
100, 150, 200 A
(2) Output Signal
005
0–5 VDC
010
0–10 VDC
420
4–20 mA
(3) Power Supply
120
120 VAC
24U
24 VAC/DC with isolated output
(4) Case Style
FF
Solid-core
SP
Split-core
3511 Charter Park Drive • San Jose, CA 95136
800.959.4014 • www.nktechnologies.com • sales@nktechnologies.com