Eurotherm Epack 1PH Data Issue-4

Adaptable power control
EPack-1PH compact SCR power controllers
Designed for fast integration and optimum efficiency
Product at a glance
OEMs and system integrators need to be able to react quickly to
customer needs while maximizing resources. Whether replacing
an existing product or designing a new process, the design of
the EPack™ power controller has been carefully considered for
fast and easy panel installation, commissioning and integration
into wider systems, lowering equipment costs, and manufacturing
times for you and your customers.
End users continually need to improve operational efficiency and
productivity. EPack power controllers can deliver real savings,
significantly reducing your energy costs. Get the best from your
operations; quick and easy to install, integrate and commission.
A compact size does not compromise powerful and versatile
features that minimize costs and improve productivity and quality.
Key features:
•Nominal load current from 1 amp to 125 amps
•Voltage up to 500V
•Compact DIN Rail and bulkhead mounting
format
•Configurable via Eurotherm iTools (PC
software) or front panel
•Plug and play Ethernet communications with
Zero configuration networking (zeroconf)
•V , I or True power control
2
2
•Controls comprehensive range of loads:
resistive, infrared, transformer primary,
> See EPack™ compact SCR power controllers’ brochure
HA031554 to discover how EPack can add value to your business
EPack 1-PH is a compact fully featured power controller
from Eurotherm, combining a high level of functionality and
configurability with simplicity of setup and operation. The
combination of advanced configurable firing modes allows close
matching to load characteristics for maximum process efficiency.
EPack is highly configurable and may be adapted for current
and future needs using a software key to purchase additional
functionality when needed.
molybdenum disilicide, silicon carbide,...
•Energy usage measurement
•Advanced load diagnostics
•Integrated dual port Ethernet switch for
“daisy chained” communications
•Modbus® TCP, Ethernet IP or Profinet
protocols
•Defend OEM knowledge and IP (OEM
Security)
2
eurotherm.co.uk/epack
EPACK-1PH Data Sheet
Specifications
General
Power
Directive
EMC directive 2014/30/EU
Nominal current
1 to 125 amps
Low Voltage Directive 2014/35/EU
Nominal voltage
100V to 500V +10%/–15%
Safety specification
EN60947-4-3:2014
Accuracy
+2% of full scale - from 100 to 500V +10%/–15%
EMC emissions specification
EN60947-4-3:2014 - Class A product
Frequency
47Hz to 63Hz
EMC immunity specification
EN60947-4-3:2014
Protection
High speed fuses
Vibration tests
EN60947-1 annex Q category E
Type of loads
Shock tests
EN60947-1 annex Q category E
AC51 Resistive or slightly inductive load (cos phi>0.8)
AC-55b Infra Red (With Derating)
Approvals
AC-56a Transformer Primary or MOSI
Europe CE according to EN60947-4-3:2014 (identical
(e.g. Molybdenum disilicide)
to IEC60947-4-3:2014)
Time temperature dependant loads
US & Canada UL60947-4-1 CAN/CSA C22.2 NO.60947-4-1-14
(e.g.Silicon Carbide)
with SCCR at 100kA
China Product not listed in catalogue of products subject to China Compulsory Certification (CCC)
Russian & Baltic countries EAC and Pattern approval pending
CE: 16 to 63A > IP10 according to EN60529
Protection
80 to 125A > IP20 according to EN60529
Control
Auxillary power supply
100V to 500V +10%/–15% or 24 ac/dc (±20%)
Control setpoint
Analogue or logic input or digital comms
Analogue input signal
UL: open type
Voltage Range: 0-5V, 1-5 V, 0-10V or 2-10V
Impedance: 140 k Ohms typical (0-10V signal)
Condition of use
Current Range: 0-20mA or 4-20mA
Atmosphere
Non-corrosive, non-explosive, non-conductive
Input resistance: 100 ohms to allow for three
Degree of pollution
Degree 2
units wired in series to be driven from a single
Storage temperature
–25°C to 70°C (maximum)
Usage temperature
0 to 45°C at 1000m
Resolution
11 bits
0 to 40°C at 2000m
Linearity
±0.1% of Scale
1000m maximum at 45°C
Firing mode
Phase angle, Intelligent Half cycle,
Altitude
controller’s analogue output
Variable Modulation Burst firing (Default 16
2000m maximum at 40°C
Derating curves
cycles), Fix modulation period (default 2
Altitude (meters)
seconds), Logic mode
Control mode
2000
V control, I control, True Power control,
2
2
Open loop with feed forward and Trim modes,
Threshold limit or by transfer V <-> I or P<-> I
2
1750
Two digital inputs
1500
2
2
Both configurable (input 1 enable by default)
Voltage inputs Active level (high): 4.4V<Vin<30V
Non-active level (low): -30V<Vin<2.3V
1250
Input impedance: 27kW (typ.) for voltage input
mode
1000
Contact closure inputs Source current: 10mA min; 15mA max
40
41
42
43
44
Open contact (non active) resistance: >500W
45
Operating temperature (°C)
Closed contact (active) resistance: <150ohms
Absolute Maximum ±30V or ±25mA
Mechanical details
Unit
Height
Width
Depth
Weight
16 to 32A
129.2 mm
51 mm
136.2 mm
0.8 kg
40 to 63A
129.2 mm
72 mm
158.2 mm
0.95 kg
80 to 100A
197.6 mm
80 mm
202.1 mm
1.8 kg
125A
197.6 mm
120 mm
202.1 mm
2.5 kg
Fuse without microswitch
Fuse with microswitch
Current
rating
Fuse holder
size
Dimensions
(H x W x D)
Fuse holder
size
Dimensions
(H x W x D)
≤25A
10x38
88.5x17.5x64.5
14x51
110.8x26.5x76.5
32A
14x51
110.8x26.5x76.5
14x51
110.8x26.5x76.5
40A
14x51
110.8x26.5x76.5
14x51
110.8x26.5x76.5
50A
22x58
127.5x35x76.5
22x58
127.5x35x76.5
63A
27x60
149.4x40x93.5
27x60
149.4x40x93.5
80A
27x60
149.4x40x93.5
27x60
149.4x40x93.5
100A
27x60
149.4x40x93.5
27x60
149.4x40x93.5
125A
27x60
149.4x40x93.5
27x60
149.4x40x93.5
One Alarm Relay
Changeover relay 2A rms - 264V rms normally
energised. (250V rms max for UL)
This relay will be de-energised in case of
serious alarms: short circuit thyristor, open
circuit, fuse blown, missing main, chop off and
networkdips
Communications
Connection
Dual port Ethernet - RJ45 Integral switch
Protocols
Modbus TCP, Ethernet IP or Profinet
Baud rate
10/100 full or half duplex
Display
Technology
TFT
Size
1.5”
Messages
Messages for configuration, monitoring and
diagnostics
eurotherm.co.uk/epack
EPACK-1PH Data Sheet
Mechanical details
Connector details (pinout)
16A to 32A & 40A to 63A
I/O Details
Input Connectors
Digital Inputs
View on upper face
EPack (auxiliary) supply power
(low voltage option shown)
Contact inputs
500Ω to ∞ = Open
0Ω to 150Ω = Closed
150Ω to 500Ω= Undefined
51mm
(2.01in)
46.7mm
(1.84in)
Load power
input
Phase reference
(neutral)
4.4V to 30V = High
–30V to +2.3V = Low
2.3V to 4.4V = Undefined
1
Voltage level inputs
1
V/mA input
174mm (6.85in)
117mm (4.61in)
147mm (5.79in)
Analogue Input
121mm (4.76in)
129.2mm (5.09in)
View on right-hand face
163.5mm (6.44in)
1
0 to 10V
1 to 5V
2 to 10V
0 to 5V
0 to 20mA
4 to 20mA
32A unit shown;
other units similar
Safety earth
connection (M5)
Relay Output
136.2mm (5.36in)
Front view
View on lower face
nc
Com
I/O connector
no
Weight : 0.800 Kg
Load power output
Relay output
View on lower face
Switching characteristics
(resistive loads)
Vmax: 264V RMS
Vmin: 1V dc
Imax: 2A RMS
Imin: 1mA
Power supply details
16A to 63A
View on upper face
View on upper face
24V
AC/DC
EPack (auxiliary) supply power
(low voltage option shown)
Auxiliary voltage
alternatives
(as specified at
time-of-order)
72mm
(2.83in)
46.7mm
(1.84in)
Phase reference
(neutral)
32A unit shown;
other units similar
Neutral
reference
Load power
input
158.2mm (6.23in)
Front view
View on lower face
1 2 3 4 5
I/O connector
174mm (6.85in)
117mm (4.61in)
Safety earth
connection (M5)
147mm (5.79in)
From Supply
power for load
121mm (4.76in)
129.2mm (5.09in)
163.5mm (6.44in)
View on right-hand face
Lift-up flap
Centre pin
not connected
Access to supply
termination
screw head
Access to load
termination
screw head
Pull-down flap
Safety earth
04 01 02
To load
Weight : 0.950 Kg
Relay output
Load power output
Flat bladed
screw head
0.6 x 4.5mm
Screwdriver/Torque wrench screwdriver or 0.8 x 4.5mm
bit details for line and load termination recommended
Insulated handle
60mm min
3
eurotherm.co.uk/epack
EPACK-1PH Data Sheet
Mechanical details
Connector details (pinout)
80A to 100A
I/O Details
View on upper face
24V
AC/DC
Phase reference (neutral)
N/L2
Front view
175.46mm (6.91 in)
Analogue Input
0 to 10V
1 to 5V
2 to 10V
0 to 5V
0 to 20mA
4 to 20mA
32A unit shown;
other units similar
2/T1
Access to load
termination
screw head
1
V/mA input
231.00mm (9.09 in)
Door catch
1
Voltage level inputs
197.6mm (7.78 in)
Door catch
1
500Ω to ∞ = Open
0Ω to 150Ω = Closed
150Ω to 500Ω= Undefined
Access to supply
termination
screw head
182mm (7.17 in)
218.25mm (8.59 in)
321.23mm (12.65 in)
Contact inputs
4.4V to 30V = High
–30V to +2.3V = Low
2.3V to 4.4V = Undefined
View on right hand side
Wire guide (2 places)
1/L1
CL
202.1 mm (7.96 in)
46.7mm (1.84 in)
Input Connectors
Digital Inputs
90.5mm
(3.56 in)
EPack (auxiliary) supply power
(low voltage option shown)
80mm
(3.15 in)
Load power input
Safety earth
connection
(M6 nut)
Relay Output
Load power output
nc
I/O connector
80mm
(3.15 in)
130.50mm
(5.14 in)
1 2 3 4 5
Relay output
04 01 02
The safety earth connection
must be made using
a listed ring type crimp
Com
no
View on lower face
View on lower face
125A
Power Supply Connection Details
80A to 125A
View on upper face
View on upper face
120mm
(4.72 in)
24V
AC/DC
90.5mm
(3.56 in)
Load power input
EPack (auxiliary) supply power
(low voltage option shown)
Phase reference (neutral)
Switching characteristics
(resistive loads)
Vmax: 264V RMS
Vmin: 1V dc
Imax: 2A RMS
Imin: 1mA
N/L2
CL
From supply
power
for load
Supply voltage
alternatives
(as specified at
time of order)
100A unit
shown
125A units
similar
24V
AC/DC
Front view
46.7mm (1.84 in)
202.1 mm (7.96 in)
View on right hand side
Wire guide (2 places)
24V
AC/DC
175.46mm (6.91 in)
231.00mm (9.09 in)
197.6mm (7.78 in)
Door catch
182mm (7.17 in)
218.25mm (8.59 in)
Door catch
Centre
pin not
connected
Access to load
termination
screw head
1/L1
Open the door
by pressing on
the catches
(two places)
Safety earth (M6 nut)
Must be made with
a listed ring type crimp
2/T1
Access to load
termination
screw head
Load power output
I/O connector
Relay output
04 01 02
The safety earth connection
must be made using
a listed ring type crimp
80mm
(3.15 in)
150.33mm
(5.92 in)
Safety earth
connection
(M6 nut)
To load
Insulated handle
View on lower face
Neutral
reference
(either pin
Access to supply
termination
screw head
2/T1
1 2 3 4 5
321.23mm (12.65 in)
1/L1
N/L2
Access to supply
termination
screw head
60mm min
Screwdriver/Torque wrench screwdriver
bit details for line and load termination
Flat bladed
screw head
1 x 5.5mm
or 1.2 x 6.5mm
recommended
4
eurotherm.co.uk/epack
EPACK-1PH Data Sheet
Order Codes
The EPack power controller is ordered using a short code for hardware and chargeable software options and an optional
extended code section configuration of commissioning options.
If the extended code is not used, the software configuration is completed using a quick start procedure or using Eurotherm
iTools software.
EPack controllers may be upgraded with additional chargeable options at any time using a software key order code.
Product coding
1
2
3
EPACK-1PH
14
4
5
6
7
XXX
15
16
17
9
8
11
10
12
13
XXX
18
19
20
21
22
23
XXX
7
Model
EPACK-1PH
1
Maximum current
16A
25A
32A
40A
50A
63A
80A
100A
125A
2
Reserved
Control Option
V2
I2
V2CL
PWRCL
5
V2 control (standard)
I2 control
V2 with current
limitation by threshold
Power control with
current limit
Transfer Option
I2 Transfer
XXX
TFR
6
500V max
24V ac/dc
Reserved
XXX
4
16 amps
25 amps
32 amps
40 amps
50 amps
63 amps
80 amps
100 amps
125 amps
Auxillary Power Supply
500V
24V
3
Power Controller
Energy Option
XXX
EMS
Energy measurement
Comms Option
Modbus TCP
(standard)
Ethernet/IP
Profinet
TCP
IP
PN
8
OEM security
XXX
OEM
9
OEM security
Warranty
XXX
WL005
USWL3
Standard Warranty
5 Year Warranty
US Extended Warranty
10 Custom Labelling
XXX
FXXXX
Standard (Eurotherm)
Special Label
11 Graphical wiring
XXX
GWE
Standard configuration
(no graphical edition)
Graphical Wiring Editor
HSM
Without fuse
High speed fuse
without microswitch
High speed fuse
with microswitch
13 Configuration
XXXXX
LC
14 Nominal load current
nnnA
1 - Value field 1
15 Nominal line voltage
100V
110V
115V
120V
127V
200V
208V
220V
230V
240V
277V
380V
400V
415V
440V
460V
480V
500V
100
110
115
120
127
200
208
220
230
240
277
380
400
415
440
460
480
500
volts
volts
volts
volts
volts
volts
volts
volts
volts
volts
volts
volts
volts
volts
volts
volts
volts
volts
16 Load type
12 Fuse
XXX
HSP
Optional configuration
Default
Long code
XX
TR
Resistive
Transformer primary
17 Heater type
XX
CSI
SWIR
Resistive
Silicon Carbide
Short Wave Infra-Red
18 Firing mode
PA
IHC
BF
FX
LGC
Phase angle
Intelligent half cycle
Variable Modulation
Burst firing (default 16
cycles)
Fix modulation period
(default 2 seconds)
Logic mode
19 Analog Input Function
XX
SP
HR
IL
TS
None
Setpoint
Setpoint limit
Current limit
Current transfer span
20 Analog input type
0V
1V
2V
5V
0A
4A
0-10 volts
1-5 volts
2-10 volts
0-5 volts
0-20 mA
4-20mA
21 Digital Input 2 Function
XX
AK
RS
SP
FB
None
Alarm
acknowledgement
Remote setpoint
selection
Digital setpoint
Fuse blown
22 Digital Input 1 Function
XXX
EN
Reserved
Enable
5
eurotherm.co.uk/epack
EPACK-1PH Data Sheet
Software upgrade options
1
1
Serial number
No change
Upgrade 16A
Upgrade 16A
Upgrade 25A
Upgrade 40A
Upgrade 40A
Upgrade 50A
Upgrade 80A
100A
V2-PWRCL
V2CL-PWRCL
4
XXX
TFR
5
6
to
to
to
to
to
to
to
25A
32A
32A
50A
63A
63A
Control option
XXX
V2-V2CL
4
no change
Upgrade V2 to
V2CL
Upgrade V2 to
PWRCL
Upgrade I2 to
PWR
7
8
Comms option
No change
Ethernet/IP
Profinet
Graphical wiring
XXX
GWE
8
6
No change
Energy measurement
XXX
IP
PN
7
5
Energy option
XXX
TFR
Current ratings
XXX
16A-25A
16A-32A
25A-32A
40A-50A
40A-63A
50A-63A
80A-100A
3
3
Serial number instrument
nnnn
2
2
No change
Graphical wiring
editor
OEM security
XXX
OEM
No change
OEM security
Transfer option
No change
I2 Transfer
Faraday Close, Durrington
Worthing, West Sussex, BN13 3PL
Phone: + 44 (01903 268500
www.eurotherm.co.uk
Document Number HA031520 Issue 4 © 2017 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies.