IC 915
C9
Applications
IC 915 controllers are electronic two-step devices, either dependent or independent or with neutral zone, used to control
temperature, relative humidity and pressure.
Common features
Front panel: IP65
Container: PC+ABS UL94 V-0 plastic resin casing,
polycarbonate window, thermoplastic resin keys
Dimensions: front panel 74x32mm, depth 59mm
(+0.2/-0.1mm)
Operating temperature: -5...55°C
Storage temperature: -30...85°C
Ambient humidity for operation and storage: 10...90% RH
(non-condensing)
Soft Start function present
Installation: panel mounting with 71x29mm drilling template
General features
Display range:
IC 915 NTC/PTC
• NTC probe: -50.0...110.0°C
• PTC probe: -55.0...140.0°C
Display:
no decimal point *
3 and a half digits + sign
1 PTC or NTC *
Analogue inputs:
Connections:
Digital outputs:
IC 912 LX TC/Pt100
• Pt100 probe: -150...650°C
• TcJ probe: -40...750°C
• TcK probe: -40...1350°C
no decimal point *
3 and a half digits + sign
1 V-I (0...1V,0...5V,0...10V,0...20mA,4...20mA)* 1 Pt100 or 1 TcJ/TcK
IC 912 LX P/R/V-I
• -99...100 *
• -99.9...100.0 *
• 999...1000 *
no decimal point *
3 and a half digits + sign
TTL port for connection to Copy Card
1 SPDT 8(3)A 250V +
1 SPST 8(3)A 250V
from -50 to 140
better than 0.5% of end of scale +1
digit
TTL port for connection to Copy Card
1 SPDT 8(3)A 250V +
1 SPST 8(3)A 250V
from -999 to 1000
better than 0.5% of end of scale +1
digit
Resolution:
0.1 °C
0.1 or 1°C *
Power consumption:
• 1.5W for model 12V
• 3W for model 230V
Measurement range:
Accuracy:
Power supply:
Alarm:
• 1.5W for model 12V
• 3W for model 230V
• 12V /12..24V /24V ±10% 50/60Hz • 12V /12..24V /24V ±10% 50/60Hz
• 110...115V /220...230V ±10% 50/60Hz • 110...115V /220...230V ±10% 50/60Hz
optional
optional
TTL port for connection to Copy Card
1 SPDT 8(3)A 250V +
1 SPST 8(3)A 250V
from -150 to 1350
Pt100: 0.5% for whole scale + 1 digit,
0.2% from -150 to 300°C
TcJ: 0.4% for whole scale + 1 digit
TcK: 0.5% for whole scale + 1 digit,
0.3% from -40 to 800°C
Pt100: 0.1°C (0.1°F) up to 199.9°C
1°C (1°F) over
TcJ: 0.1°C (0.1°F) up to 199.9°C
(1°F) over
TcK: 0.1°C (0.1°F)
• 1.5W for model 12V
• 3W for model 230V
• 12V /12..24V /24V ±10% 50/60Hz
• 110...115V /220...230V ±10% 50/60Hz
optional
*(selectable by parameter)
Wiring diagram
IC 915 NTC-PTC
IC 915 P-R-V/I
IC 915 Pt100/TC
out2
230Va
out1
8 9 10
230Va
1 2 3 4 5 6 7
Pb1
out2
out1
12Va
1 2 3 4 5
6 7 8 9 10
12Va
12Va
1 2 3 4 5
Codes
p/n
description
Probe Power supply
IC12C00TCH700 IC 915 temperature NTC/PTC 230V
IC12C00TCD400 IC 915 temperature NTC/PTC 12...24V
IC12J00THD700 IC 915 temperature TC/Pt100
230V
IC12J00THD400 IC 915 temperature TC/Pt100 12...24V
out2
+
-
230Va
8 9 10 11
out2
-
1 2 3 4 5 6 7
out1
V
230Va
Pb1
+12V
I
1 2 4 5 6 7
out1
out2
10 11 12
+
230Va
-
12Va
V
+
230Va
Pb1
+12V
I
+
out1
-
Pb1
+
out2
+
out1
6 7 8 9 10 11
12Va
1 2 4 5
Codes
p/n
description
IR12I00TBD700 IC 915 humidity
IP12A00TRD700 IC 915 pressure
IP12B00TRD700 IC 915 pressure
IC12I00TRN700 IC 915 neutral
6 7
10 11 12
12Va
Probe
Power supply
4...20mA
230V !
EWPA 007 230V
EWPA 030 230V
4...20mA
230V
IC 915 LX
Applications
IC 915 LX controllers are electronic two-step devices, either dependent or independent or with neutral zone, used to
control temperature, relative humidity and pressure and compatible with TelevisSystem and monitoring systems with
ModBus protocol.
Common features
Front panel: IP65
Container: PC+ABS UL94 V-0 plastic resin casing,
polycarbonate window, thermoplastic resin keys
Dimensions: front panel 74x32mm, depth 59mm
Installation: panel mounting with 71x29mm drilling template
General features
Display range:
Display:
Analogue inputs:
Digital inputs:
Connections:
Digital outputs:
Measurement range:
Accuracy:
Resolution:
Power consumption:
Power supply:
*(selectable by parameter)
IC 915 LX NTC/PTC
• NTC probe: -50.0...110.0°C
• PTC probe: -55.0...140.0°C
(+0.2/-0.1mm)
Operating temperature: -5...55°C
Storage temperature: -30...85°C
Ambient humidity for operation and storage: 10...90% RH
(non-condensing)
Soft Start function present
IC 915 LX TC/Pt100
• Pt100 probe: -150...650°C
• TcJ probe: -40...750°C
• TcK probe: -40...1350°C
no decimal point *
no decimal point *
3 and a half digits + sign
3 and a half digits + sign
1 PTC or NTC *
1 V-I (0...1V,0...5V,0...10V,0...20mA,4...20mA)* 1 Pt100 or 1 TcJ/TcK
1 clean contact at extra low safety
1 clean contact at extra low safety
not available
voltage
voltage
TTL port for connection to Copy
TTL port for connection to Copy
TTL port for connection to Copy
Card, TelevisSystem and systems
Card, TelevisSystem and systems
Card, TelevisSystem and systems
with ModBus protocol
with ModBus protocol
with ModBus protocol
1 SPDT 8(3)A 250V +
1 SPDT 8(3)A 250V +
1 SPDT 8(3)A 250V +
1 SPDT 8(3)A 250V
1 SPDT 8(3)A 250V
1 SPDT 8(3)A 250V
from -999 to 1000
from -150 to 1350
from -50 to 140
better than 0.5% of end of scale +1 better than 0.5% of end of scale +1 Pt100: 0.5% for whole scale + 1 digit,
digit
0.2% from -150 to 300°C
digit
TcJ: 0.4% for whole scale + 1 digit
TcK: 0.5% for whole scale + 1 digit,
0.3% from -40 to 800°C
0.1 or 1°C *
Pt100: 0.1°C (0.1°F) up to 199.9°C
0.1 or 1°C *
1°C (1°F) over
TcJ: 0.1°C (0.1°F) up to 199.9°C
(1°F) over
TcK: 0.1°C (0.1°F)
• 1.5W for model 12V
• 1.5W for model 12V
• 1.5W for model 12V
• 3W for model 230V
• 3W for model 230V
• 3W for model 230V
• 12V /12..24V /24V ±10% 50/60Hz • 12V /12..24V /24V ±10% 50/60Hz • 12V /12..24V /24V ±10% 50/60Hz
• 110...115V /220...230V ±10% 50/60Hz • 110...115V /220...230V ±10% 50/60Hz • 110...115V /220...230V ±10% 50/60Hz
IC 915 LX P/R/V-I
• -99...100 *
• -99.9...100.0 *
• 999...1000 *
no decimal point *
3 and a half digits + sign
Wiring diagram
IC 915 LX NTC-PTC
IC 915 LX P-R-V/I
230Va
230Va
8 9 10 11
230Va
1 2 3 4 5 6 7
Pb1
out2
out1
12Va
1 2 3 4 5
6 7 8 9 10 11
12Va
12Va
1 2 3 4 5
Codes
p/n
description
ProbePower supply
IC12JI0XHD700 IC 915 LX temperature TC/Pt100230V
IC12CI0XCD700 IC 915 LX temperature NTC/PTC230V
IR12I00XBD700 IC 915 LX humidity 4...20mA
230V
Pb1
+12V
I
out1
DI1
out2
V
+
-
230Va
8 9 10 11
out2
-
1 2 3 4 5 6 7
out1
IC 915 LX Pt100/TC
out2
230Va
Pb1
+12V
I
1 2 4 5 6 7
out1
8 9 10 11 12
DI1
out2
+
230Va
-
12Va
V
+
out1
+
Pb1 D.I.
-
out2
+
out1
+
C10
6 7 8 9 10 11
12Va
1 2 4 5
6 7 8 9 10 11 12
12Va
Codes
p/n
description
Probe Power supply
IP12I00XRD700 IC 915 LX pressure 4...20mA 230V
IC12I00XRN700 IC 915 LX neutral
4...20mA 230V
Download PDF