INSTALLATION INSTRUCTIONS
PACKAGE HEAT PUMPS
RJNL 13 SEER SERIES (3-5 TON)
RJNL 11.0 EER SERIES (6 TON)
RJPL 14 SEER SERIES (3-5 TON)
FEATURING INDUSTRY STANDARD R-410A REFRIGERANT
!
RECOGNIZE THIS SYMBOL AS AN INDICATION OF IMPORTANT SAFETY INFORMATION!
!
WARNING
THESE INSTRUCTIONS ARE INTENDED AS AID TO
QUALIFIED, LICENSED SERVICE PERSONNEL FOR
PROPER INSTALLATION, ADJUSTMENT AND
OPERATION OF THIS UNIT. READ THESE
INSTRUCTIONS THOROUGHLY BEFORE ATTEMPTING
INSTALLATION OR OPERATION. FAILURE TO FOLLOW
THESE INSTRUCTIONS MAY RESULT IN IMPROPER
INSTALLATION, ADJUSTMENT, SERVICE OR
MAINTENANCE POSSIBLY RESULTING IN FIRE,
ELECTRICAL SHOCK, PROPER DAMAGE, PERSONAL
INJURY OR DEATH.
(14 SEER
MODELS ONLY)
ISO 9001:2008
DO NOT DESTROY THIS MANUAL
PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE FOR FUTURE REFERENCE BY A SERVICEMAN
92-23577-77-08
SUPERSEDES 92-23577-77-07
I.TABLE OF CONTENTS
I. Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
II. Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
III. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
A. R-410A Refrigerant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
IV. Checking Product Received . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
V. Equipment Protection From The Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
VI. Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
A. General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
B. Outside Slab Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
C. Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
D. Rooftop Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
VII. Ductwork . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
VIII. Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
IX. Conversion Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
X. Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
XI. Condensate Drain, Outdoor Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
XII. Electrical Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
A. Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
B. Special Instructions for Power
Wiring with Aluminum Conductors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
C. Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
D. Internal Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
E. Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
F. Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
XIII. Indoor Air Flow Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
XIV. Crankcase Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
XV. Pre-Start Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
XVI. Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
XVII. Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
XVIII. Auxiliary Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
A. Control System Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
XIX. Demand Defrost Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
XX. General Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22-37
XXI. Miscellaneous
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38-47
Indoor Airflow Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48-52
Heater Kits Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53-67
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68-77
Charge Charts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78-83
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
➤ Installation Instructions are updated on a regular basis. This is done as product
changes occur or if new information becomes available. In this publication, an arrow (➤)
denotes changes from the previous edition or additional new material.
2
II. SAFETY INFORMATION
! WARNING
THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED, LICENSED
SERVICE PERSONNEL FOR PROPER INSTALLATION, ADJUSTMENT AND
OPERATION OF THIS UNIT. READ THESE INSTRUCTIONS THOROUGHLY
BEFORE ATTEMPTING INSTALLATION OPERATION. FAILURE TO FOLLOW
THESE INSTRUCTIONS MAY RESULT IN IMPROPER INSTALLATION, ADJUSTMENT, SERVICE OR MAINTENANCE POSSIBLY RESULTING IN FIRE, ELECTRICAL SHOCK, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
! WARNING
IMPORTANT: ALL MANUFACTURER PRODUCTS MEET CURRENT FEDERAL
OSHA GUIDELINES FOR SAFETY. CALIFORNIA PROPOSITION 65 WARNINGS
ARE REQUIRED FOR CERTAIN PRODUCTS, WHICH ARE NOT COVERED BY
THE OSHA STANDARDS.
CALIFORNIA'S PROPOSITION 65 REQUIRES WARNINGS FOR PRODUCTS
SOLD IN CALIFORNIA THAT CONTAIN, OR PRODUCE, ANY OF OVER 600 LISTED CHEMICALS KNOWN TO THE STATE OF CALIFORNIA TO CAUSE CANCER
OR BIRTH DEFECTS SUCH AS FIBERGLASS INSULATION, LEAD IN BRASS,
AND COMBUSTION PRODUCTS FROM NATURAL GAS.
ALL “NEW EQUIPMENT” SHIPPED FOR SALE IN CALIFORNIA WILL HAVE
LABELS STATING THAT THE PRODUCT CONTAINS AND/OR PRODUCES
PROPOSITION 65 CHEMICALS. ALTHOUGH WE HAVE NOT CHANGED OUR
PROCESSES, HAVING THE SAME LABEL ON ALL OUR PRODUCTS FACILITATES MANUFACTURING AND SHIPPING. WE CANNOT ALWAYS KNOW
“WHEN, OR IF” PRODUCTS WILL BE SOLD IN THE CALIFORNIA MARKET.
YOU MAY RECEIVE INQUIRIES FROM CUSTOMERS ABOUT CHEMICALS
FOUND IN, OR PRODUCED BY, SOME OF OUR HEATING AND AIR-CONDITIONING EQUIPMENT, OR FOUND IN NATURAL GAS USED WITH SOME OF OUR
PRODUCTS. LISTED BELOW ARE THOSE CHEMICALS AND SUBSTANCES
COMMONLY ASSOCIATED WITH SIMILAR EQUIPMENT IN OUR INDUSTRY AND
OTHER MANUFACTURERS.
• GLASS WOOL (FIBERGLASS) INSULATION
• CARBON MONOXIDE (CO)
• FORMALDEHYDE
• BENZENE
MORE DETAILS ARE AVAILABLE AT THE WEBSITES FOR OSHA
(OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION), AT
WWW.OSHA.GOV AND THE STATE OF CALIFORNIA'S OEHHA (OFFICE OF
ENVIRONMENTAL HEALTH HAZARD ASSESSMENT), AT WWW.OEHHA.ORG.
CONSUMER EDUCATION IS IMPORTANT SINCE THE CHEMICALS AND SUBSTANCES ON THE LIST ARE FOUND IN OUR DAILY LIVES. MOST CONSUMERS ARE AWARE THAT PRODUCTS PRESENT SAFETY AND HEALTH
RISKS, WHEN IMPROPERLY USED, HANDLED AND MAINTAINED.
! WARNING
THE MANUFACTURER’S WARRANTY DOES NOT COVER ANY DAMAGE OR
DEFECT TO THE AIR CONDITIONER CAUSED BY THE ATTACHMENT OR USE
OF ANY COMPONENTS, ACCESSORIES OR DEVICES (OTHER THAN THOSE
AUTHORIZED BY THE MANUFACTURER) INTO, ONTO OR IN CONJUNCTION
WITH THE AIR CONDITIONER. YOU SHOULD BE AWARE THAT THE USE OF
UNAUTHORIZED COMPONENTS, ACCESSORIES OR DEVICES MAY
ADVERSELY AFFECT THE OPERATION OF THE AIR CONDITIONER AND MAY
ALSO ENDANGER LIFE AND PROPERTY. THE MANUFACTURER DISCLAIMS
ANY RESPONSIBILITY FOR SUCH LOSS OR INJURY RESULTING FROM THE
USE OF SUCH UNAUTHORIZED COMPONENTS, ACCESSORIES OR DEVICES.
! WARNING
DISCONNECT ALL POWER TO THE UNIT BEFORE STARTING MAINTENANCE.
FAILURE TO DO SO CAN RESULT IN SEVERE ELECTRICAL SHOCK OR
DEATH.
3
! WARNING
DO NOT, UNDER ANY CIRCUMSTANCES, CONNECT RETURN DUCTWORK TO
ANY OTHER HEAT PRODUCING DEVICE SUCH AS A FIREPLACE INSERT,
STOVE, ETC. UNAUTHORIZED USE OF SUCH DEVICES MAY RESULT IN FIRE,
CARBON MONOXIDE POISONING, EXPLOSION, PROPERTY DAMAGE,
SEVERE PERSONAL INJURY OR DEATH.
! WARNING
THE UNIT MUST BE PERMANENTLY GROUNDED. A GROUNDING LUG IS PROVIDED IN THE ELECTRIC HEAT KIT FOR A GROUND WIRE. (SEE FIGURES 16
AND 17.) FAILURE TO GROUND THIS UNIT CAN RESULT IN FIRE OR ELECTRICAL SHOCK CAUSING PROPERTY DAMAGE, SEVERE PERSONAL INJURY OR
DEATH.
! WARNING
ONLY ELECTRIC HEATER KITS SUPPLIED BY THIS MANUFACTURER AS
DESCRIBED IN THIS PUBLICATION HAVE BEEN DESIGNED, TESTED, AND
EVALUATED BY A NATIONALLY RECOGNIZED SAFETY TESTING AGENCY
FOR USE WITH THIS UNIT. USE OF ANY OTHER MANUFACTURED ELECTRIC
HEATERS INSTALLED WITHIN THIS UNIT MAY CAUSE HAZARDOUS CONDITIONS RESULTING IN PROPERTY DAMAGE, FIRE, BODILY INJURY OR
DEATH.
! WARNING
PROPOSITION 65: THIS APPLIANCE CONTAINS FIBERGLASS INSULATION.
RESPIRABLE PARTICLES OF FIBERGLASS ARE KNOWN TO THE STATE OF
CALIFORNIA TO CAUSE CANCER.
! CAUTION
R-410A systems operate at higher pressures than R-22 systems. Do not use
R-22 service equipment or components on R-410A equipment.
4
!
Recognize this symbol as an indication of Important Safety Information!
! WARNING
IMPORTANT: ALL MANUFACTURER PRODUCTS MEET CURRENT
FEDERAL OSHA GUIDELINES FOR
SAFETY. CALIFORNIA
PROPOSITION 65 WARNINGS ARE
REQUIRED FOR CERTAIN PRODUCTS, WHICH ARE NOT COVERED
BY THE OSHA STANDARDS.
CALIFORNIA'S PROPOSITION 65
REQUIRES WARNINGS FOR PRODUCTS SOLD IN CALIFORNIA THAT
CONTAIN, OR PRODUCE, ANY OF
OVER 600 LISTED CHEMICALS
KNOWN TO THE STATE OF
CALIFORNIA TO CAUSE CANCER
OR BIRTH DEFECTS SUCH AS
FIBERGLASS INSULATION, LEAD
IN BRASS, AND COMBUSTION
PRODUCTS FROM NATURAL GAS.
ALL “NEW EQUIPMENT” SHIPPED
FOR SALE IN CALIFORNIA WILL
HAVE LABELS STATING THAT THE
PRODUCT CONTAINS AND/OR
PRODUCES PROPOSITION 65
CHEMICALS. ALTHOUGH WE HAVE
NOT CHANGED OUR PROCESSES,
HAVING THE SAME LABEL ON ALL
OUR PRODUCTS FACILITATES
MANUFACTURING AND SHIPPING.
WE CANNOT ALWAYS KNOW
“WHEN, OR IF” PRODUCTS WILL
BE SOLD IN THE CALIFORNIA
MARKET.
YOU MAY RECEIVE INQUIRIES
FROM CUSTOMERS ABOUT CHEMICALS FOUND IN, OR PRODUCED
BY, SOME OF OUR HEATING AND
AIR-CONDITIONING EQUIPMENT,
OR FOUND IN NATURAL GAS USED
WITH SOME OF OUR PRODUCTS.
LISTED BELOW ARE THOSE CHEMICALS AND SUBSTANCES COMMONLY ASSOCIATED WITH SIMILAR EQUIPMENT IN OUR INDUSTRY AND OTHER MANUFACTURERS.
• GLASS WOOL (FIBERGLASS)
INSULATION
• CARBON MONOXIDE (CO)
• FORMALDEHYDE
• BENZENE
MORE DETAILS ARE AVAILABLE
AT THE WEBSITES FOR OSHA
(OCCUPATIONAL SAFETY AND
HEALTH ADMINISTRATION), AT
WWW.OSHA.GOV AND THE STATE
OF CALIFORNIA'S OEHHA (OFFICE
OF ENVIRONMENTAL HEALTH
HAZARD ASSESSMENT), AT
WWW.OEHHA.ORG. CONSUMER
EDUCATION IS IMPORTANT SINCE
THE CHEMICALS AND SUBSTANCES ON THE LIST ARE
FOUND IN OUR DAILY LIVES. MOST
CONSUMERS ARE AWARE THAT
PRODUCTS PRESENT SAFETY AND
HEALTH RISKS, WHEN IMPROPERLY USED, HANDLED AND MAINTAINED.
III. INTRODUCTION
This booklet contains the installation and operating instructions for your package heat
pump. There are a few precautions that should be taken to derive maximum satisfaction
from it. Improper installation can result in unsatisfactory operation or dangerous conditions.
Read this booklet and any instructions packaged with separate equipment required to
make up the system prior to installation. Give this booklet to the owner and explain its
provisions. The owner should retain this booklet for future reference.
NOTE: A load calculation must be performed to properly determine the required heating
and cooling for the structure. Also, the duct must be properly designed and installed for
proper airflow. Existing dutwork must be inspected for proper size and sealed system.
Proper airflow is necessary for both user comfort and equipment performance.
IMPORTANT: Proper application, installation and maintenance of this equipment is a
must if consumers are to receiver the full benefit for which they have paid.
A. R-410A REFRIGERANT
All units are factory charged with R-410A refrigerant.
1. Specification of R-410A:
Application: R-410A is not a drop-in replacement for R-22; equipment designs must
accommodate its higher pressures. It cannot be retrofitted into R-22 units.
Pressure: The pressure of R-410A is approximately 60% (1.6 times) greater than R22. Recovery and recycle equipment, pumps, hoses and the like need to have design
pressure ratings appropriate for R-410A. Manifold sets need to range up to 800 psig
high-side and 250 psig low-side with a 550 psig low-side retard. Hoses need to have a
service pressure rating of 800 psig. Recovery cylinders need to have a 400 psig service
pressure rating. DOT 4BA400 or DOT BW400.
Combustibility: At pressures above 1 atmosphere, mixture of R-410A and air can
become combustible. R-410A and air should never be mixed in tanks or supply
lines, or be allowed to accumulate in storage tanks. Leak checking should never
be done with a mixture of R-410A and air. Leak checking can be performed safely
with nitrogen or a mixture of R-410A and nitrogen.
2. Quick Reference Guide For R-410A
• R-410A refrigerant operates at approximately 60% higher pressure (1.6 times) than R22. Ensure that servicing equipment is designed to operate with R-410A.
• R-410A refrigerant cylinders are pink.
• R-410A, as with other HFC’s is only compatible with POE oils.
• Vacuum pumps will not remove moisture from POE oil.
• R-410A systems are to be charged with liquid refrigerants. Prior to March 1999, R410A refrigerant cylinders had a dip tube. These cylinders should be kept upright for
equipment charging. Post March 1999 cylinders do not have a dip tube and should be
inverted to ensure liquid charging of the equipment.
• Do not install a suction line filter drier in the liquid line.
• A liquid line filter drier is standard on every unit.
• Desiccant (drying agent) must be compatible for POE oils and R-410A.
3. Evaporator Coil / TXV
The thermostatic expansion valve is specifically designed to operate with R-410A. DO
NOT use an R-22 TXV. The existing evaporator must be replaced with the factory
specified TXV evaporator specifically designed for R-410A.
4. Tools Required For Installing & Servicing R-410A Models
Manifold Sets:
-Up to 800 PSIG High side
-Up to 250 PSIG Low Side
-550 PSIG Low Side Retard
Manifold Hoses:
-Service Pressure Rating of 800 PSIG
5
Recovery Cylinders:
-400 PSIG Pressure Rating
-Dept. of Transportation 4BA400 or BW400
! CAUTION
R-410A systems operate at higher pressures than R-22 systems. Do not use
R-22 service equipment or components on R-410A equipment.
IV. CHECKING PRODUCT RECEIVED
Upon receiving the unit, inspect it for any damage from shipment. Claims for damage,
either shipping or concealed, should be filed immediately with the shipping company.
Check the unit model number, heating size, electrical characteristics, and accessories to
determine if they are correct.
V. EQUIPMENT PROTECTION FROM THE
V. ENVIRONMENT
The metal parts of this unit may be subject to rust or deterioration in adverse environmental conditions. This oxidation could shorten the equipment’s useful life. Salt spray,
fog or mist in seacoast areas, sulphur or chlorine from lawn watering systems, and various chemical contaminants from industries such as paper mills and petroleum refineries
are especially corrosive.
If the unit is to be installed in an area where contaminants are likely to be a problem, special attention should be given to the equipment location and exposure.
1. Avoid having lawn sprinkler heads spray direction on the unit cabinet.
2. In coastal areas, locate the unit on the side of the building away from the waterfront.
3. Shielding provided by a fence or shrubs may give some protection.
Regular maintenance will reduce the buildup of contaminents and help to protect
the unit’s finish.
! WARNING
DISCONNECT ALL POWER TO THE UNIT BEFORE STARTING MAINTENANCE.
FAILURE TO DO SO CAN RESULT IN SEVERE ELECTRICAL SHOCK OR
DEATH.
1. Frequent washing of the cabinet, fan blade and coil with fresh water will remove
most of the salt or other contaminants that build up on the unit.
2. Regular cleaning and waxing of the cabinet with a good automobile polish will provide some protection.
3. A good liquid cleaner may be used several times a year to remove matter that will
not wash off with water.
Several different types of protective coatings are offered in some areas. These coatings
may provide some benefit, but the effectiveness of such coating materials cannot be verified by the equipment manufacturer.
The best protection is frequent cleaning, maintenance and minimal exposure to
contaminants.
VI. INSTALLATION
A. GENERAL
1. PRE-INSTALLATION CHECK-POINTS
Before attempting any installation, the following points should be carefully considered:
a. Structural strength of supporting members.
(rooftop installation)
b. Clearances and provision for servicing.
c. Power supply and wiring.
d. Air duct connections.
6
FIGURE 1
UNIT DIMENSIONS
RJNL/RJPL 3-5 TON
ILL I316
FIGURE 2
UNIT DIMENSIONS
RJNL/RJPL 3-5 TON
35
ILL I305
7
FIGURE 3
UNIT DIMENSIONS
RJNL/RJPL 3-5 TON
317⁄32
313⁄16
511⁄32
761⁄4
483⁄32
24
ILL I304
FIGURE 4
UNIT DIMENSIONS
RJNL/RJPL 3 TO 5 TON
RETURN AIR FILTER
(REMOVABLE PLATE)
ILL I288
8
FIGURE 5
UNIT DIMENSIONS
BOTTOM VIEW
BASE ELECTRICAL
ENTRY
RJNL 6 TON
CONDENSER
COIL
26
781⁄4
ILL 1316
FIGURE 6
UNIT DIMENSIONS
RJNL 6 TON
8117⁄32
CONDENSER FAN
DISCHARGE GRILLE
261⁄4
301⁄4
CONDENSER COIL
ILL1305
9
FIGURE 7
UNIT DIMENSIONS
RJNL 6 TON
821⁄4
481⁄16
24 ⁄32
1
ILL 1304
FIGURE 8
UNIT DIMENSIONS
RJNL 6 TON
25 1/8
82 1/4
ILL 1288
10
FIGURE 9
FIGURE 10
PACKAGED HEAT PUMP
OUTSIDE SLAB INSTALLATION, BASEMENT OR
CRAWL SPACE DISTRIBUTION SYSTEM
PACKAGED HEAT PUMP
OUTSIDE SLAB INSTALLATION, CLOSET DISTRIBUTION
SYSTEM. SLAB FLOOR CONSTRUCTION
*
12”
18”
*Allow 57" for economizer
on duct side.
ILL I308
ILL I309
FIGURE 11
PACKAGED HEAT PUMP
RIGGING FOR LIFTING
Capacity Tons [kW]
A in. [mm]
B in. [mm]
3.5 [10.6-17.6]
381⁄4 [972]
253⁄4 [654]
6 [21.1]
39 [991]
261⁄8 [664]
Capacity Tons [kW]
Corner Weights by Percentage
A
B
C
D
3.5 [10.6-17.6]
22%
27%
23%
28%
6 [21.1]
23%
29%
21%
27%
11
FIGURE 12
PACKAGED HEAT PUMP
ROOFCURB INSTALLATION
ILL I301
ILL I300
e. Drain facilities and connections.
f. Location for minimum noise.
2. LOCATION
These units are designed for outdoor installations. They can be mounted on a
slab or rooftop. They are not to be installed within any part of a structure such as
an attic, crawl space, closet, or any other place where condenser air flow is
restricted or other than outdoor ambient conditions prevail. Since the application
of the units is of the outdoor type, it is important to consult your local code authorities at the time the first installation is made.
B. OUTSIDE SLAB INSTALLATION
(Typical outdoor slab installations are shown in Figures 9 and 10.)
1. Select a location where external water drainage cannot collect around the unit.
2. Provide a level concrete slab extending 3" beyond all four sides of the unit. The
slab should be sufficient above grade to prevent ground water from entering the
unit. IMPORTANT: To prevent transmission of noise or vibration, slab should not
be connected to building structure.
3. The location of the unit should be such as to provide proper access for inspection
and servicing.
4. Locate unit where operating sounds will not disturb owner or neighbors.
5. Locate unit so roof runoff water does not pour directly on the unit. Provide gutter
or other shielding at roof level. Do not locate unit in an area where excessive
snow drifting may occur or accumulate.
6. It is essential that the unit be elevated above the base pad to allow for condensate drainage and possible refreezing of condensation. Provide a base pad which
is slightly pitched away from the structure. Route condensate off base pad to an
area which will not become slippery and result in personal injury.
7. Where snowfall is anticipated, the height of the unit above the ground level must
be considered. Mount unit high enough to be above average area snowfall and to
allow for proper condensate drainage.
12
FIGURE 13
PACKAGED HEAT PUMP
FLAT ROOFTOP INSTALLATION, ATTIC OR DROP CEILING
DISTRIBUTION SYSTEM. MOUNTED ON
ROOFCURB. CURB MUST BE LEVEL
FIGURE 14
COVER GASKET DETAIL
ILL I631
ILL I310
C. CLEARANCES
The following minimum clearances must be observed for proper unit performance
and serviceability.
1. Provide 48" minimum clearance at the front of the unit. Provide 36" minimum
clearance at the left and right side of the unit for service access.
2. Provide 60" minimum clearance between top of unit and maximum 3 foot overhang.
3. Unit is design certified for application on combustible flooring with 0" minimum
clearance.
4. See Figure 9 for illustration of minimum installation-service clearances.
D. ROOFTOP INSTALLATION
1. Before locating the unit on the roof, make sure that the strength of the roof and
beams is adequate at that point to support the weight involved. (See specification
sheet for weight of unit.) This is very important and user’s responsibility.
2. For rigging and roofcurb details, see Figures 11 and 12. Use field-furnished
spreaders.
3. For roofcurb assembly, see Roofcurb Installation Instructions.
4. If the roofcurb is not used, provisions for disposing of condensate water runoff
during defrosting must be provided.
5. The unit should be placed on a solid and level roofcurb or platform of adequate
strength. See Figure 13.
6. The location of the unit on the roof should be such as to provide proper access for
inspection and servicing.
IMPORTANT: If unit will not be put into service immediately, cover supply and return
openings to prevent excessive condensation.
VII. DUCTWORK
Ductwork should be fabricated by the installing contractor in accordance with local codes
and NFPA90A. Industry manuals may be used as a guide when sizing and designing the
duct system - contact Air Conditioning Contractors of America, 1513 16th St. N.W.,
Washington, D.C. 20036.
13
FIGURE 15
CONDENSATE DRAIN
! WARNING
DO NOT, UNDER ANY CIRCUMSTANCES, CONNECT RETURN DUCTWORK TO
ANY OTHER HEAT PRODUCING DEVICE SUCH AS A FIREPLACE INSERT,
STOVE, ETC. UNAUTHORIZED USE OF SUCH DEVICES MAY RESULT IN FIRE,
CARBON MONOXIDE POISONING, EXPLOSION, PROPERTY DAMAGE,
SEVERE PERSONAL INJURY OR DEATH.
The unit should be placed as close to the space to be air conditioned as possible allowing clearance dimensions as indicated. Ducts should be run as directly as possible to
supply and return outlets. Use of non-flammable waterproof flexible connectors on both
supply and return connections at the unit to reduce noise transmission is recommended.
It is preferable to install the unit on the roof of the structure if the registers or diffusers
are located on the wall or in the ceiling. A slab installation could be considered when the
registers are low on a wall or in the floor.
On ductwork exposed to outside air conditions of temperature and humidity, use a minimum of 2" of insulation and a vapor barrier. Distribution system in attic, furred space or
crawl space should be insulated with at least 2" of insulation with vapor barrier. One-half
to 1" thickness of insulation is usually sufficient for ductwork inside the air conditioned
space.
Balancing dampers should be provided for each branch duct in the supply system.
Ductwork should be properly supported from the structure.
When installing ductwork, consider the following items:
1. Noncombustible flexible connectors should be used between ductwork and unit to
reduce noise and vibration transmission into the ductwork.
2. When auxiliary heaters are installed, use noncombustible flexible connectors and
clearance to combustible material of 0" for the first 3 feet of discharge duct.
Clearance to unit top and side is 0".
VIII.FILTERS
This unit is provided with 2 - 25" x 16" x 1" (3-5 ton) 4 - 16" x 16" x 1" (6 ton) disposable
filters. When replacing filters, ensure they are inserted fully to the back to prevent
bypass.
IX. CONVERSION PROCEDURE
DOWNFLOW TO HORIZONTAL
1. Remove the screws and covers from the outside of the supply and return sections.
2. Install the covers in the bottom supply and return openings with the painted side up.
See Figure 15. Use the existing gasket to seal the covers.
3. Secure the supply cover to the base of the unit with 1 screw, engaging prepunched
tab in unit base.
4. Secure the return cover to the base of the unit with screws, engaging prepunched
holes in the unit base.
14
FIGURE 16
BRANCH CIRCUIT DISCONNECT LOCATION
TABLE A
WIRE SIZES
TO POWER
BRANCH CIRCUIT
DISCONNECT
TO CONTROL
AWG Copper
Wire Size
#12
#10
#8
#6
#4
#3
#2
#1
#0
AWG Aluminum
Wire Size
#10
#8
#6
#4
#2
#1
#0
#00
#000
Connector Type and Size
(or equivalent)
T&B Wire Nut
PT2
T&B Wire Nut
PT3
Ilsco Split Bolt
AK-6
Ilsco Split Bolt
AK-4
Ilsco Split Bolt
AK-2
Ilsco Split Bolt
AK-1/0
Ilsco Split Bolt
AK-1/0
Ilsco Split Bolt
AK-2/0
Ilsco Split Bolt
AK-4/0
X. CONDENSATE DRAIN
The condensate drain connection of the evaporator is 3/4" nominal female pipe thread.
IMPORTANT: Install a condensate trap to ensure proper condensate drainage. See
Figure 15.
XI. CONDENSATE DRAIN, OUTDOOR COIL
The outdoor coil during heating operation will sweat or run water off. The outdoor coil will
also run water off during the defrost cycle. See Section V, Installation, for mounting precautions.
XII. ELECTRICAL WIRING
Field wiring must comply with the National Electrical Code* and local ordinances that may
apply.
*C.E.C. in Canada
A. POWER WIRING
1. It is important that proper electrical power is available at the unit. Voltage should not
vary more than 10% from that stamped on the unit rating plate. On three phase
units, phases must be balanced within 3%.
➤ 2. Install a branch circuit disconnect within sight of the unit and of adequate size to
handle the starting current. Refer to Figure 16 for proper location.
3. For branch circuit wiring (main power supply to unit disconnect), the minimum wire
size can be determined from Table C using the circuit ampacity found on the unit
nameplate or from the Electrical Data.
4. This unit incorporates single point electrical connection for unit and electric heat
accessory.
5. Power wiring must be run in grounded rain-tight conduit. Connect the power field
wiring as follows:
a. NO ELECTRIC HEAT - Connect the field wires directly to the contactor pigtails in
the electric heat access area. Connect ground wire to ground lug.
b. WITH ELECTRIC HEAT - Connect the field wires to the terminal block on the
electric heater kit in the electric heat access area. Connect the ground wire to the
ground lug on the heater kit.
NOTE: For field installation of a heater kit, follow the instructions provided with the heater
kit.
15
FIGURE 17
HEATER KIT INSTALLATION
ILL I312
FIGURE 18
WITH ONE OUTDOOR THERMOSTAT
W/EMERGENCY HEAT RELAY
VOLTAGE CONNECTIONS DIAGRAMS
STANDARD
THERMOSTAT
SUB-BASE
R
UNIT CONTROL
WIRE PIGTAILS
RED
W2
BLACK
X
BROWN
B
BLUE
Y1
YELLOW
Y2
ORANGE
G
GRAY
E
THERMOSTAT
SUB-BASE
UNIT CONTROL
WIRE PIGTAILS
R
RED
G
GRAY
B
BLUE
X
BROWN
WHITE
W2
BLACK
Y2
BROWN
RED
E
Y1
OUTDOOR
THERMOSTAT
W/EMERGENCY
HEAT RELAY
BLACK
YELLOW
ORANGE
NOTES: IF EMERGENCY HEAT RELAY AND OUTDOOR THERMOSTATS ARE NOT USED, A JUMPER BETWEEN “W2” AND “E” CAN BE INSTALLED TO TRANSFER
CONTROL OF HEATING TO THE FIRST STAGE WHEN THE SYSTEM SWITCH IS IN THE EMERGENCY HEAT POSITION.
Y2 IS ONLY USED WITH OPTIONAL ECONOMIZER.
6. The pigtail wires in the electric heat access area are factory wired to the contactor in
the control box.
7. DO NOT connect aluminum field wires to electric heat kit power input terminals.
B. SPECIAL INSTRUCTIONS FOR POWER WIRING WITH ALUMINUM
CONDUCTORS.
1. Select the equivalent aluminum wire size from the tabulation below:
2. Attach a length (6" or more) of recommended size copper wire to the unit terminals
L1 and L3 for single phase, L1, L2, L3 for three phase.
3. Splice copper wire pigtails to aluminum wire with U.L. recognized connectors for
copper-aluminum splices. Follow these instructions very carefully to make a positive
and lasting connection;
a. Strip insulation from aluminum conductor.
b. Coat the stripped end of the aluminum wire with the recommended inhibitor and
wire brush aluminum surface through inhibitor. Inhibitors: Brundy, Pentex “A”;
Alcoa, No. 2EJC; T&B KPOR Shield.
16
TABLE C
COPPER WIRE SIZE – AWG (1% VOLTAGE DROP)
Supply
Wire
Length
Feet
300 4
250 4
200 6
150 8
100 10
50 14
3
4
4
6
8
12
2
3
4
6
8
10
2
3
4
4
6
10
1
2
3
4
6
8
1/0 1/0 2/0 2/0 3/0 3/0 3/0 4/0 4/0 4/0
1
1 1/0 1/0 2/0 2/0 2/0 3/0 3/0 3/0
2
2
1
1 1/0 1/0 1/0 2/0 2/0 2/0
4
3
3
2
2
1
1 1/0 1/0 1/0
6
4
4
4
3
3
2
2
2
1
8
6
6
6
4
4
4
3
3
3
4/0
4/0
3/0
1/0
1
2
250
4/0
3/0
2/0
1
2
15
20
25
30
35
40
90
95 100 105 110 115 120 125 130 135 140 145 150 155
45
50
55
60
65
70
75
80
85
250
4/0
3/0
2/0
1
2
250
4/0
3/0
2/0
1
2
250
4/0
3/0
2/0
1/0
2
300
250
4/0
2/0
1/0
1
300
250
4/0
3/0
1/0
1
300
250
4/0
3/0
1/0
1
300
250
4/0
3/0
1/0
1
300
250
4/0
3/0
1/0
1/0
350
350
300
4/0
1/0
1/0
350
350
300
4/0
2/0
1/0
350
350
300
4/0
2/0
1/0
350
350
300
4/0
2/0
2/0
Circuit Ampacity
NOTE:
1. Wire size based on 60ºC type copper conductors below 100 ampacity.
2. Wire size based on 75ºC type copper conductors for 100 ampacity and above.
c. Clean and recoat aluminum conductor with inhibitor.
d. Make the splice using the above listed wire nuts or split bolt connectors.
e. Coat the entire connection with inhibitor and wrap with electrical insulating tape.
WARRANTY MAY NOT APPLY IF CONNECTIONS ARE NOT MADE PER INSTRUCTIONS
C. CONTROL WIRING (Class II)
1. Low voltage wiring should not be run in conduit with power wiring.
2. Control wiring is routed through the 7/8" hole adjacent to the compressor access
panel. See Figure 2. Use a minimum #18 AWG thermostat wire. For wire lengths
exceeding 50', use #16 AWG thermostat wire. The low voltage wires are connected
to the unit pigtails which are supplied with the unit below the unit control box.
3. It is necessary that only heat pump thermostats be used.
4. Figure 18 shows representative low voltage connection diagrams. Read your thermostat installation instructions for any special requirements for your specific thermostat.
NOTE — Units installed in Canada require that an outdoor thermostat (30,000 min.
cycles of endurance) be installed and be wired with C.E.C. Class I wiring.
D. INTERNAL WIRING
1. A diagram of the internal wiring of this unit is located on the inside of the compressor access panel. If any of the original wire as supplied with the appliance must be
replaced, the wire gauge and insulation must be the same as original wiring.
IMPORTANT: Some single phase units are equipped with a single pole contactor.
Caution must be exercised when servicing as only one leg of the power supply is broken with the contactor. Some models are equipped with electrically commutated blower motors which are constantly energized unless the main unit disconnect is in the off
position.
E. GROUNDING
! WARNING
THE UNIT MUST BE PERMANENTLY GROUNDED. A GROUNDING LUG IS PROVIDED IN THE ELECTRIC HEAT ACCESS AREA FOR A GROUND WIRE. FAILURE
TO GROUND THIS UNIT CAN RESULT IN FIRE OR ELECTRICAL SHOCK CAUSING PROPERTY DAMAGE, SEVERE PERSONAL INJURY OR DEATH.
F. THERMOSTAT
The thermostat should be mounted on an inside wall about five feet above the floor in
a location where it will not be affected by unconditioned air, sun, or drafts from open
doors or other sources. READ installation instructions in heat pump thermostat package CAREFULLY because each has some different wiring requirements.
XIII. INDOOR AIR FLOW DATA
Direct-drive blower models are shipped factory wired for the proper speed at a typical
external static. Belt-drive blower models have motor sheaves set for proper CFM at a
typical external static.
17
XIV. CRANKCASE HEAT (OPTIONAL)
Crankcase heat is not required on scroll type compressors, but may be necessary for
difficult starting situations.
XV. PRE-START CHECK
1. Is unit properly located and slightly slanted toward indoor condensate drain?
2. Is ductwork insulated, weatherproofed, with proper spacing to combustible materials?
3. Is air free to travel to and from outdoor coil? (See Figure 9.)
4. Is the wiring correct, tight, and according to unit wiring diagram?
5. Is unit grounded?
6. Are field supplied air filters in place and clean?
7. Do the outdoor fan and indoor blower turn freely without rubbing, and are they tight
on the motor shafts?
8. Is unit elevated to allow for outdoor coil condensate drainage during heating operation and defrost?
XVI. STARTUP
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
Turn thermostat to “OFF,” turn “on” power supply at disconnect switch.
Turn temperature setting as high as it will go.
Turn fan switch to “ON.”
Indoor blower should run. Be sure it is running in the right direction.
Turn fan switch to “AUTO.” Turn system switch to “COOL” and turn temperature setting below room temperature. Unit should run in cooling mode.
Is outdoor fan operating correctly in the right direction?
Is compressor running correctly.
Turn thermostat system switch to “HEAT.” Unit should stop. Wait 5 minutes, then
raise temperature setting to above room temperature. Unit should run in heating
mode and after about 30 to 50 seconds auxiliary heaters, if installed, should come
on.
Check the refrigerant charge using the instructions located on compressor access
panel cover. Replace service port caps. Service port cores are for system access
only and will leak if not tightly capped.
Turn thermostat system switch to proper mode “HEAT” or “COOL” and set thermostat to proper temperature setting. Record the following after the unit has run some
time.
A. Operating Mode _______________________________
B. Discharge Pressure (High) ___________________PSIG
C. Vapor Pressure at Compressor (Low) __________PSIG
D. Vapor Line Temperature at Compressor __________°F.
E. Indoor Dry Bulb______________________________°F.
F. Indoor Wet Bulb _____________________________°F.
G. Outdoor Dry Bulb ____________________________°F.
H. Outdoor Wet Bulb ____________________________°F.
I. Voltage at Contactor ________________________Volts
J. Current at Contactor _______________________Amps
K. Model Number_________________________________
L. Serial Number _________________________________
M.Location______________________________________
N. Owner _______________________________________
O. Date_________________________________________
Adjust discharge air grilles and balance system.
Check ducts for condensation and air leaks.
Check unit for tubing and sheet metal rattles.
Instruct the owner on operation and maintenance.
Leave “INSTALLATION” and ”USE AND CARE“ instructions with owner
XVII. OPERATION
Most single phase units are operated PSC (no start relay or start capacitor). It is important that such systems be off for a minimum of 5 minutes before restarting to allow
equalization of pressures. The thermostat should not be moved to cycle unit without
waiting five minutes. To do so may cause the compressor to stop on an automatic open
overload device or blow a fuse. Poor electrical service can cause nuisance tripping in
overloads or blow fuses.
18
IMPORTANT: The compressor has an internal overload protector. Under some conditions, it can take up to 2 hours for this overload to reset. Make sure overload has had
time to reset before condemning the compressor.
Some units are equipped with a time delay control (TDC1). The control allows the blower
to operate for up to 90 seconds after the thermostat is satisfied.
XVIII. AUXILIARY HEAT
The amount of auxiliary heat required depends on the heat loss of the structure to be
heated and the capacity of the heat pump. It is good practice to install strip heat to maintain at least 60ºF indoor temperatures in case of compressor failure. The auxiliary heat
is energized by the second stage of the thermostat. The amount of electric heat that is
allowed to come on, as determined by the output of the heat pump, may be controlled by
an outdoor thermostat.
! WARNING
ONLY ELECTRIC HEATER KITS SUPPLIED BY THIS MANUFACTURER AS
DESCRIBED IN THIS PUBLICATION HAVE BEEN DESIGNED, TESTED, AND
EVALUATED BY A NATIONALLY RECOGNIZED SAFETY TESTING AGENCY
FOR USE WITH THIS UNIT. USE OF ANY OTHER MANUFACTURED ELECTRIC
HEATERS INSTALLED WITHIN THIS UNIT MAY CAUSE HAZARDOUS CONDITIONS RESULTING IN PROPERTY DAMAGE, FIRE, BODILY INJURY OR
DEATH.
A. CONTROL SYSTEM OPERATION
1. In the cooling mode, the thermostat will, on a call for cooling, energize the compressor contactor and the indoor blower relay. The indoor blower can be operated
continuously by setting the thermostat fan switch at the “ON” position. The reversing valve coil is de-energized.
2. In the heating mode, the first heat stage of the thermostat will energize the compressor contactor and the indoor blower relay. The second heat stage will turn on
one or more supplementary resistance heaters. The reversing valve is energized
except in defrost. If required or considered desirable, the resistance heat may
also be controlled by outdoor thermostats.
XIX. DEMAND DEFROST CONTROL AND
HIGH/LOW PRESSURE CONTROLS
The demand defrost control monitors the outdoor ambient temperature, outdoor coil
temperature and the compressor run time to determine when a defrost cycle is
required.
Enhanced Feature Demand Defrost Control: This defrost control has high and
low pressure control inputs with unique pressure switch logic built into the microprocessor to provide compressor and system protection without nuisance lockouts.
The control cycles the compressor off for 30 seconds at the beginning and the end
of the defrost cycle to eliminate the increased compressor noise caused by rapidly
changing system pressures when the reversing valve switches. See next page for
diagnostic flash codes and sensor resistance values at various temperatures.
DEFROST INITIATION
A defrost will be initiated when the three conditions below are satisfied:
1. The outdoor coil temperature is below 35°F as measured by a good coil sensor,
2. The compressor has operated for at least 34 minutes with the outdoor coil temperature below 35°F and
3. The measured difference between the ambient temperature and the outdoor
coil temperature is greater than the calculated difference determined by the
defrost control microprocessor.
DEFROST TERMINATION
Once a defrost is initiated, the defrost will continue until fourteen minutes has
elapsed or the coil temperature has reached the selected termination temperature.
The factory setting is 70°F but can be changed to 50°F, 60°F, or 80°F by relocating
the jumper on the control board.
19
TEMPERATURE SENSORS
The coil sensor is located on the outdoor coil near the point fed by the distribution
tubes from the expansion device, on the top most cross-over tube. The ambient air
sensor is located outside the control box so it can sense outdoor temperatures.
If the ambient sensor fails, the defrost control will initiate a defrost every 34 minutes
of compressor run time with the coil temperature below 35°F.
If the coil sensor fails, the defrost control will not initiate a defrost.
TEST MODE
The test mode is initiated by shorting the TEST pins. The unit must have an active
heat pump heating call to enter the test mode. In this mode of operation, the enable
temperature is ignored and all timers are sped up. To initiate a manual defrost,
short and hold the TEST pins. Remove the short when the system switches to
defrost mode after the compressor noise abatement delay. The defrost will terminate on time (14 minutes) or when the termination temperature has been reached.
Test Sequence of Operation:
1) Provide a heating call to the heat pump.
2) Short test pins to bypass anti-short cycle timer. (If unit is running, this step is not
necessary.)
3) Short test pins and hold them shorted to enter defrost mode.
4) Release test pins once control exits noise abatement delay.
5) Monitor coil temperature when control exits defrost.
6) Unit should return to heating mode.
TROUBLE SHOOTING DEMAND DEFROST
During the test mode the coil temperature should be monitored. If the system exits
defrost at approximately the termination temperature, the control is operating normlly. If not, check the coil and ambient temperature sensor resistances, using the sensor temperature vs. resistance table at the end of this section.
Immerse the sensor in water and measure the resistance of the sensor. At 35°F the
resistance of the sensor should be approximately 30,000 ohms.
Ensure that the coil sensor is properly installed that is not loose or touching the cabinet.
HIGH/LOW PRESSURE CONTROL MONITORING - ENHANCED
DEFROST CONTROL
Status of high and low pressure controls is monitored by the enhanced feature
demand defrost control and the following actions are taken.
High Pressure Control – Provides active protection in both cooling and heating
modes at all outdoor ambient temperatures. The high pressure control is an automatic reset type and opens at approximately 610 psig and closes at approximately
420 psig. The compressor and fan motor will stop when the high pressure control
opens and will start again if the high side pressure drops to approximately 420 psig
where the automatic reset high pressure control resets. If the high pressure control
opens 3 times within a particular call for heating or cooling operation, the defrost
control will lock out compressor and outdoor fan operation.
Low Pressure Control – Provides active protection in both heating and cooling
modes at all outdoor ambient temperatures. The low pressure control is an automatic reset type and opens at approximately 15 psig and closes at approximately
40 psig. Operation is slightly different between cooling and heating modes.
Cooling Mode: The compressor and fan motor will stop when the low pressure
control opens and will start again when the low side pressure rises to approximately 40 psig after the low pressure control automatically resets. If the low
pressure switch opens 3 times within a particular call for cooling operation, the
defrost control will lock out compressor and outdoor fan operation.
Heating Mode: The compressor and outdoor fan motor will stop when the low
pressure control opens and will start again when the low side pressure rises to
approximately 40 psig when the low pressure control automatically resets. If the
low pressure switch trips 3 times within 120 minutes of operation during a particular call for heating operation, the defrost control will lock out compressor
and outdoor fan operation. If the lock-out due to low pressure occurs at an outdoor ambient temperature below 5°F, the defrost control will automatically exit
20
the lock-out mode when the outdoor ambient temperature rises to 5°F. This feature is necessary since the low pressure control could possibly have opened
due to the outdoor ambient being very low rather than an actual system fault.
Exiting Lock-Out Mode: To exit the lock-out mode, remove 24 volts to the defrost
control by removing power to the unit or by shorting the two defrost control pins
together.
ENHANCED FEATURE DEFROST CONTROL DIAGNOSTIC CODES
LED 1
LED 2
OFF
OFF
ON
ON
OFF
ON
FLASH
FLASH
OFF
FLASH
FLASH
OFF
ON
FLASH
FLASH
ON
Alternate Flashing
Control Board Status
No Power
Coil Sensor Failure
Ambient Sensor Failure
Normal
Low Pressure Lockout (short test pins to reset)
High Pressure Lockout (short test pins to reset)
Low Pressure Control Open
High Pressure Control Open
5 Minute Time Delay
SENSOR TEMPERATURE VS. RESISTANCE TABLE
Degrees C
-20
-10
0
10
20
25
30
40
Degrees F
-4
14
32
50
68
77
86
104
Ohms
96,974
55,298
32,650
19,903
12,493
10,000
8,056
5,324
REPLACEMENT PARTS
Contact your local distributor for a complete parts list.
CHARGE INFORMATION
Refer to the appropriate charge chart included in this manual.
TROUBLESHOOTING
Refer to the troubleshooting chart included in this manual.
WIRING DIAGRAMS
Refer to the appropriate wiring diagram included in this manual.
21
XX. GENERAL DATA - RJNL MODELS
NOMINAL SIZES 3-5 TONS [10.6-17.6 kW]
Model RJNL- Series
1
Cooling Performance
Gross Cooling Capacity Btu [kW]
2
EER/SEER
Nominal CFM/ARI Rated CFM [L/s]
ARI Net Cooling Capacity Btu [kW]
Net Sensible Capacity Btu [kW]
Net Latent Capacity Btu [kW]
Net System Power kW
Heating Performance (Heat Pumps)
High Temp. Btuh [kW] Rating
System Power KW / COP
Low Temp. Btuh [kW] Rating
System Power KW / COP
HSPF (Btu/Watts-hr)
Compressor
No./Type
Outdoor Sound Rating (dB)3
Outdoor Coil - Fin Type
Tube Type
Tube Size in. [mm] OD
Face Area sq. ft. [sq. m]
Rows / FPI [FPcm]
Refrigerant Control
Indoor Coil - Fin Type
Tube Type
Tube Size in. [mm]
Face Area sq. ft. [sq. m]
Rows / FPI [FPcm]
Refrigerant Control
Drain Connection No./Size in. [mm]
Outdoor Fan - Type
No. Used/Diameter in. [mm]
Drive Type/No. Speeds
CFM [L/s]
No. Motors/HP
Motor RPM
Indoor Fan - Type
No. Used/Diameter in. [mm]
Drive Type/No. Speeds
No. Motors
Motor HP
Motor RPM
Motor Frame Size
Filter - Type
Furnished
(NO.) Size Recommended in. [mm x mm x mm]
Refrigerant Charge Oz. [g]
Weights
Net Weight lbs. [kg]
Ship Weight lbs. [kg]
A036CK
A036CL
A036CM
37,800 [11.08]
11.5/13
1200/1200 [566/566]
36,200 [10.61]
27,000 [7.91]
9,200 [2.7]
3.1
37,800 [11.08]
11.5/13
1200/1200 [566/566]
36,200 [10.61]
27,000 [7.91]
9,200 [2.7]
3.1
37,800 [11.08]
11.5/13
1200/1200 [566/566]
36,200 [10.61]
27,000 [7.91]
9,200 [2.7]
3.1
A036DK
Continued ->
37,800 [11.08]
11.5/13
1200/1200 [566/566]
36,200 [10.61]
27,000 [7.91]
9,200 [2.7]
3.1
34,400 [10.08]
2.94/3.4
19,600 [5.74]
2.72/2.1
7.7
34,400 [10.08]
2.94/3.4
19,600 [5.74]
2.72/2.1
7.7
34,400 [10.08]
2.94/3.4
19,600 [5.74]
2.72/2.1
7.7
34,400 [10.08]
2.94/3.4
19,600 [5.74]
2.72/2.1
7.7
1/Copeland Scroll
83
Louvered
Rifled
0.375 [9.5]
16.89 [1.57]
1 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
5.16 [0.48]
3 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/10x10 [254x254]
Direct/3
1
1/2
1075
48
Disposable
Yes
(2)1x25x16 [25x635x406]
1/Copeland Scroll
83
Louvered
Rifled
0.375 [9.5]
16.89 [1.57]
1 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
5.16 [0.48]
3 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/10x10 [254x254]
Belt/Variable
1
1/2
1725
56
Disposable
Yes
(2)1x25x16 [25x635x406]
1/Copeland Scroll
83
Louvered
Rifled
0.375 [9.5]
16.89 [1.57]
1 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
5.16 [0.48]
3 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/10x10 [254x254]
Belt/Variable
1
3/4
1725
56
Disposable
Yes
(2)1x25x16 [25x635x406]
1/Copeland Scroll
83
Louvered
Rifled
0.375 [9.5]
16.89 [1.57]
1 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
5.16 [0.48]
3 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/10x10 [254x254]
Direct/3
1
1/2
1075
48
Disposable
Yes
(2)1x25x16 [25x635x406]
116 [3289]
116 [3289]
116 [3289]
116 [3289]
517 [235]
532 [241]
517 [235]
532 [241]
517 [235]
532 [241]
517 [235]
532 [241]
NOTES:
1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity
is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner
Equipment certification program, which is based on ARI Standard 210/240 or 360.
2. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures.
3. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270.utdoor Sound Rating shown is tested in accordance with ARI Standard 270.
22
GENERAL DATA - RJNL MODELS
NOMINAL SIZES 3-5 TONS [10.6-17.6 kW]
Model RJNL- Series
1
Cooling Performance
Gross Cooling Capacity Btu [kW]
2
EER/SEER
Nominal CFM/ARI Rated CFM [L/s]
ARI Net Cooling Capacity Btu [kW]
Net Sensible Capacity Btu [kW]
Net Latent Capacity Btu [kW]
Net System Power kW
Heating Performance (Heat Pumps)
High Temp. Btuh [kW] Rating
System Power KW / COP
Low Temp. Btuh [kW] Rating
System Power KW / COP
HSPF (Btu/Watts-hr)
Compressor
No./Type
Outdoor Sound Rating (dB)3
Outdoor Coil - Fin Type
Tube Type
Tube Size in. [mm] OD
Face Area sq. ft. [sq. m]
Rows / FPI [FPcm]
Refrigerant Control
Indoor Coil - Fin Type
Tube Type
Tube Size in. [mm]
Face Area sq. ft. [sq. m]
Rows / FPI [FPcm]
Refrigerant Control
Drain Connection No./Size in. [mm]
Outdoor Fan - Type
No. Used/Diameter in. [mm]
Drive Type/No. Speeds
CFM [L/s]
No. Motors/HP
Motor RPM
Indoor Fan - Type
No. Used/Diameter in. [mm]
Drive Type/No. Speeds
No. Motors
Motor HP
Motor RPM
Motor Frame Size
Filter - Type
Furnished
(NO.) Size Recommended in. [mm x mm x mm]
Refrigerant Charge Oz. [g]
Weights
Net Weight lbs. [kg]
Ship Weight lbs. [kg]
A036DL
A036DM
A036JK
37,800 [11.08]
11.5/13
1200/1200 [566/566]
36,200 [10.61]
27,000 [7.91]
9,200 [2.7]
3.1
37,800 [11.08]
11.5/13
1200/1200 [566/566]
36,200 [10.61]
27,000 [7.91]
9,200 [2.7]
3.1
37,800 [11.08]
11.5/13
1200/1200 [566/566]
36,200 [10.61]
27,000 [7.91]
9,200 [2.7]
3.1
A042CK
Continued ->
44,000 [12.89]
11.2/13
1400/1400 [661/661]
42,000 [12.31]
31,200 [9.14]
10,800 [3.16]
3.74
34,400 [10.08]
2.94/3.4
19,600 [5.74]
2.72/2.1
7.7
34,400 [10.08]
2.94/3.4
19,600 [5.74]
2.72/2.1
7.7
34,400 [10.08]
2.94/3.4
19,600 [5.74]
2.72/2.1
7.7
41,000 [12.01]
3.38/3.5
24,400 [7.15]
3.12/2.3
7.7
1/Copeland Scroll
83
Louvered
Rifled
0.375 [9.5]
16.89 [1.57]
1 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
5.16 [0.48]
3 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/10x10 [254x254]
Belt/Variable
1
1/2
1725
56
Disposable
Yes
(2)1x25x16 [25x635x406]
1/Copeland Scroll
83
Louvered
Rifled
0.375 [9.5]
16.89 [1.57]
1 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
5.16 [0.48]
3 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/10x10 [254x254]
Belt/Variable
1
3/4
1725
56
Disposable
Yes
(2)1x25x16 [25x635x406]
1/Copeland Scroll
83
Louvered
Rifled
0.375 [9.5]
16.89 [1.57]
1 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
5.16 [0.48]
3 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/10x10 [254x254]
Direct/3
1
1/2
1075
48
Disposable
Yes
(2)1x25x16 [25x635x406]
1/Copeland Scroll
83
Louvered
Rifled
0.375 [9.5]
16.89 [1.57]
1 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
5.16 [0.48]
3 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/10x10 [254x254]
Direct/3
1
1/2
1075
48
Disposable
Yes
(2)1x25x16 [25x635x406]
116 [3289]
116 [3289]
116 [3289]
120 [3402]
517 [235]
532 [241]
517 [235]
532 [241]
517 [235]
532 [241]
521 [236]
536 [243]
NOTES:
1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity
is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner
Equipment certification program, which is based on ARI Standard 210/240 or 360.
2. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures.
3. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270.utdoor Sound Rating shown is tested in accordance with ARI Standard 270.
23
GENERAL DATA - RJNL MODELS
NOMINAL SIZES 3-5 TONS [10.6-17.6 kW]
Model RJNL- Series
1
Cooling Performance
Gross Cooling Capacity Btu [kW]
2
EER/SEER
Nominal CFM/ARI Rated CFM [L/s]
ARI Net Cooling Capacity Btu [kW]
Net Sensible Capacity Btu [kW]
Net Latent Capacity Btu [kW]
Net System Power kW
Heating Performance (Heat Pumps)
High Temp. Btuh [kW] Rating
System Power KW / COP
Low Temp. Btuh [kW] Rating
System Power KW / COP
HSPF (Btu/Watts-hr)
Compressor
No./Type
Outdoor Sound Rating (dB)3
Outdoor Coil - Fin Type
Tube Type
Tube Size in. [mm] OD
Face Area sq. ft. [sq. m]
Rows / FPI [FPcm]
Refrigerant Control
Indoor Coil - Fin Type
Tube Type
Tube Size in. [mm]
Face Area sq. ft. [sq. m]
Rows / FPI [FPcm]
Refrigerant Control
Drain Connection No./Size in. [mm]
Outdoor Fan - Type
No. Used/Diameter in. [mm]
Drive Type/No. Speeds
CFM [L/s]
No. Motors/HP
Motor RPM
Indoor Fan - Type
No. Used/Diameter in. [mm]
Drive Type/No. Speeds
No. Motors
Motor HP
Motor RPM
Motor Frame Size
Filter - Type
Furnished
(NO.) Size Recommended in. [mm x mm x mm]
Refrigerant Charge Oz. [g]
Weights
Net Weight lbs. [kg]
Ship Weight lbs. [kg]
A042CL
A042CM
A042DK
44,000 [12.89]
11.2/13
1400/1400 [661/661]
42,000 [12.31]
31,200 [9.14]
10,800 [3.16]
3.74
44,000 [12.89]
11.2/13
1400/1400 [661/661]
42,000 [12.31]
31,200 [9.14]
10,800 [3.16]
3.74
44,000 [12.89]
11.2/13
1400/1400 [661/661]
42,000 [12.31]
31,200 [9.14]
10,800 [3.16]
3.74
A042DL
Continued ->
44,000 [12.89]
11.2/13
1400/1400 [661/661]
42,000 [12.31]
31,200 [9.14]
10,800 [3.16]
3.74
41,000 [12.01]
3.38/3.5
24,400 [7.15]
3.12/2.3
7.7
41,000 [12.01]
3.38/3.5
24,400 [7.15]
3.12/2.3
7.7
41,000 [12.01]
3.38/3.5
24,400 [7.15]
3.12/2.3
7.7
41,000 [12.01]
3.38/3.5
24,000 [7.03]
3.12/2.3
7.7
1/Copeland Scroll
83
Louvered
Rifled
0.375 [9.5]
16.89 [1.57]
1 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
5.16 [0.48]
3 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/10x10 [254x254]
Belt/Variable
1
1/2
1725
56
Disposable
Yes
(2)1x25x16 [25x635x406]
1/Copeland Scroll
83
Louvered
Rifled
0.375 [9.5]
16.89 [1.57]
1 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
5.16 [0.48]
3 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/10x10 [254x254]
Belt/Variable
1
3/4
1725
56
Disposable
Yes
(2)1x25x16 [25x635x406]
1/Copeland Scroll
83
Louvered
Rifled
0.375 [9.5]
16.89 [1.57]
1 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
5.16 [0.48]
3 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/10x10 [254x254]
Direct/3
1
1/2
1075
48
Disposable
Yes
(2)1x25x16 [25x635x406]
1/Copeland Scroll
83
Louvered
Rifled
0.375 [9.5]
16.89 [1.57]
1 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
5.16 [0.48]
3 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/10x10 [254x254]
Belt/Variable
1
1/2
1725
56
Disposable
Yes
(2)1x25x16 [25x635x406]
120 [3402]
120 [3402]
120 [3402]
120 [3402]
521 [236]
536 [243]
521 [236]
536 [243]
521 [236]
536 [243]
521 [236]
536 [243]
NOTES:
1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity
is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner
Equipment certification program, which is based on ARI Standard 210/240 or 360.
2. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures.
3. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270.utdoor Sound Rating shown is tested in accordance with ARI Standard 270.
24
GENERAL DATA - RJNL MODELS
NOMINAL SIZES 3-5 TONS [10.6-17.6 kW]
Model RJNL- Series
1
Cooling Performance
Gross Cooling Capacity Btu [kW]
2
EER/SEER
Nominal CFM/ARI Rated CFM [L/s]
ARI Net Cooling Capacity Btu [kW]
Net Sensible Capacity Btu [kW]
Net Latent Capacity Btu [kW]
Net System Power kW
Heating Performance (Heat Pumps)
High Temp. Btuh [kW] Rating
System Power KW / COP
Low Temp. Btuh [kW] Rating
System Power KW / COP
HSPF (Btu/Watts-hr)
Compressor
No./Type
Outdoor Sound Rating (dB)3
Outdoor Coil - Fin Type
Tube Type
Tube Size in. [mm] OD
Face Area sq. ft. [sq. m]
Rows / FPI [FPcm]
Refrigerant Control
Indoor Coil - Fin Type
Tube Type
Tube Size in. [mm]
Face Area sq. ft. [sq. m]
Rows / FPI [FPcm]
Refrigerant Control
Drain Connection No./Size in. [mm]
Outdoor Fan - Type
No. Used/Diameter in. [mm]
Drive Type/No. Speeds
CFM [L/s]
No. Motors/HP
Motor RPM
Indoor Fan - Type
No. Used/Diameter in. [mm]
Drive Type/No. Speeds
No. Motors
Motor HP
Motor RPM
Motor Frame Size
Filter - Type
Furnished
(NO.) Size Recommended in. [mm x mm x mm]
Refrigerant Charge Oz. [g]
Weights
Net Weight lbs. [kg]
Ship Weight lbs. [kg]
A042DM
A042JK
A048CK
44,000 [12.89]
11.2/13
1400/1400 [661/661]
42,000 [12.31]
31,200 [9.14]
10,800 [3.16]
3.74
44,000 [12.89]
11.2/13
1400/1400 [661/661]
42,000 [12.31]
31,200 [9.14]
10,800 [3.16]
3.74
50,000 [14.65]
11.2/13
1600/1600 [755/755]
47,500 [13.92]
35,700 [10.46]
11,800 [3.46]
4.22
A048CL
Continued ->
50,000 [14.65]
11.2/13
1600/1600 [755/755]
47,500 [13.92]
35,700 [10.46]
11,800 [3.46]
4.22
41,000 [12.01]
3.38/3.5
24,400 [7.15]
3.12/2.3
7.7
41,000 [12.01]
3.38/3.5
24,400 [7.15]
3.12/2.3
7.7
49,000 [14.36]
3.93/3.6
29,000 [8.5]
3.63/2.3
7.7
49,000 [14.36]
3.93/3.6
29,000 [8.5]
3.63/2.3
7.7
1/Copeland Scroll
83
Louvered
Rifled
0.375 [9.5]
16.89 [1.57]
1 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
5.16 [0.48]
3 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/10x10 [254x254]
Belt/Variable
1
3/4
1725
56
Disposable
Yes
(2)1x25x16 [25x635x406]
1/Copeland Scroll
83
Louvered
Rifled
0.375 [9.5]
16.89 [1.57]
1 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
5.16 [0.48]
3 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/10x10 [254x254]
Direct/3
1
1/2
1075
48
Disposable
Yes
(2)1x25x16 [25x635x406]
1/Copeland Scroll
83
Louvered
Rifled
0.375 [9.5]
16.56 [1.54]
2 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
5.16 [0.48]
4 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/10x10 [254x254]
Direct/3
1
1/2
1075
48
Disposable
Yes
(2)1x25x16 [25x635x406]
1/Copeland Scroll
83
Louvered
Rifled
0.375 [9.5]
16.56 [1.54]
2 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
5.16 [0.48]
4 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/10x10 [254x254]
Belt/Variable
1
1/2
1725
56
Disposable
Yes
(2)1x25x16 [25x635x406]
120 [3402]
120 [3402]
187 [5301]
187 [5301]
521 [236]
536 [243]
521 [236]
536 [243]
535 [243]
550 [249]
535 [243]
550 [249]
NOTES:
1. Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor
heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Units are certified in
accordance with the Unitary Air Conditioner Equipment certification program, which is based on ARI Standard 210/240 or 360.
2. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures.
3. Standard 3/4" P-Trap provided.
25
GENERAL DATA - RJNL MODELS
NOMINAL SIZES 3-5 TONS [10.6-17.6 kW]
Model RJNL- Series
1
Cooling Performance
Gross Cooling Capacity Btu [kW]
2
EER/SEER
Nominal CFM/ARI Rated CFM [L/s]
ARI Net Cooling Capacity Btu [kW]
Net Sensible Capacity Btu [kW]
Net Latent Capacity Btu [kW]
Net System Power kW
Heating Performance (Heat Pumps)
High Temp. Btuh [kW] Rating
System Power KW / COP
Low Temp. Btuh [kW] Rating
System Power KW / COP
HSPF (Btu/Watts-hr)
Compressor
No./Type
Outdoor Sound Rating (dB)3
Outdoor Coil - Fin Type
Tube Type
Tube Size in. [mm] OD
Face Area sq. ft. [sq. m]
Rows / FPI [FPcm]
Refrigerant Control
Indoor Coil - Fin Type
Tube Type
Tube Size in. [mm]
Face Area sq. ft. [sq. m]
Rows / FPI [FPcm]
Refrigerant Control
Drain Connection No./Size in. [mm]
Outdoor Fan - Type
No. Used/Diameter in. [mm]
Drive Type/No. Speeds
CFM [L/s]
No. Motors/HP
Motor RPM
Indoor Fan - Type
No. Used/Diameter in. [mm]
Drive Type/No. Speeds
No. Motors
Motor HP
Motor RPM
Motor Frame Size
Filter - Type
Furnished
(NO.) Size Recommended in. [mm x mm x mm]
Refrigerant Charge Oz. [g]
Weights
Net Weight lbs. [kg]
Ship Weight lbs. [kg]
A048CM
A048DK
A048DL
50,000 [14.65]
11.2/13
1600/1600 [755/755]
47,500 [13.92]
35,700 [10.46]
11,800 [3.46]
4.22
50,000 [14.65]
11.2/13
1600/1600 [755/755]
47,500 [13.92]
35,700 [10.46]
11,800 [3.46]
4.22
50,000 [14.65]
11.2/13
1600/1600 [755/755]
47,500 [13.92]
35,700 [10.46]
11,800 [3.46]
4.22
A048DM
Continued ->
50,000 [14.65]
11.2/13
1600/1600 [755/755]
47,500 [13.92]
35,700 [10.46]
11,800 [3.46]
4.22
49,000 [14.36]
3.93/3.6
29,000 [8.5]
3.63/2.3
7.7
49,000 [14.36]
3.93/3.6
29,000 [8.5]
3.63/2.3
7.7
49,000 [14.36]
3.93/3.6
29,000 [8.5]
3.63/2.3
7.7
49,000 [14.36]
3.93/3.6
29,000 [8.5]
3.63/2.3
7.7
1/Copeland Scroll
83
Louvered
Rifled
0.375 [9.5]
16.56 [1.54]
2 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
5.16 [0.48]
4 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/10x10 [254x254]
Belt/Variable
1
3/4
1725
56
Disposable
Yes
(2)1x25x16 [25x635x406]
1/Copeland Scroll
83
Louvered
Rifled
0.375 [9.5]
16.56 [1.54]
2 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
5.16 [0.48]
4 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/10x10 [254x254]
Direct/3
1
1/2
1075
48
Disposable
Yes
(2)1x25x16 [25x635x406]
1/Copeland Scroll
83
Louvered
Rifled
0.375 [9.5]
16.56 [1.54]
2 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
5.16 [0.48]
4 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/10x10 [254x254]
Belt/Variable
1
1/2
1725
56
Disposable
Yes
(2)1x25x16 [25x635x406]
1/Copeland Scroll
83
Louvered
Rifled
0.375 [9.5]
16.56 [1.54]
2 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
5.16 [0.48]
4 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/10x10 [254x254]
Belt/Variable
1
3/4
1725
56
Disposable
Yes
(2)1x25x16 [25x635x406]
187 [5301]
187 [5301]
187 [5301]
187 [5301]
535 [243]
550 [249]
535 [243]
550 [249]
535 [243]
550 [249]
535 [243]
550 [249]
NOTES:
1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity
is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner
Equipment certification program, which is based on ARI Standard 210/240 or 360.
2. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures.
3. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270.utdoor Sound Rating shown is tested in accordance with ARI Standard 270.
26
GENERAL DATA - RJNL MODELS
NOMINAL SIZES 3-5 TONS [10.6-17.6 kW]
Model RJNL- Series
1
Cooling Performance
Gross Cooling Capacity Btu [kW]
2
EER/SEER
Nominal CFM/ARI Rated CFM [L/s]
ARI Net Cooling Capacity Btu [kW]
Net Sensible Capacity Btu [kW]
Net Latent Capacity Btu [kW]
Net System Power kW
Heating Performance (Heat Pumps)
High Temp. Btuh [kW] Rating
System Power KW / COP
Low Temp. Btuh [kW] Rating
System Power KW / COP
HSPF (Btu/Watts-hr)
Compressor
No./Type
Outdoor Sound Rating (dB)3
Outdoor Coil - Fin Type
Tube Type
Tube Size in. [mm] OD
Face Area sq. ft. [sq. m]
Rows / FPI [FPcm]
Refrigerant Control
Indoor Coil - Fin Type
Tube Type
Tube Size in. [mm]
Face Area sq. ft. [sq. m]
Rows / FPI [FPcm]
Refrigerant Control
Drain Connection No./Size in. [mm]
Outdoor Fan - Type
No. Used/Diameter in. [mm]
Drive Type/No. Speeds
CFM [L/s]
No. Motors/HP
Motor RPM
Indoor Fan - Type
No. Used/Diameter in. [mm]
Drive Type/No. Speeds
No. Motors
Motor HP
Motor RPM
Motor Frame Size
Filter - Type
Furnished
(NO.) Size Recommended in. [mm x mm x mm]
Refrigerant Charge Oz. [g]
Weights
Net Weight lbs. [kg]
Ship Weight lbs. [kg]
A048JK
A060CK
A060CL
50,000 [14.65]
11.2/13
1600/1600 [755/755]
47,500 [13.92]
35,700 [10.46]
11,800 [3.46]
4.22
61,000 [17.87]
11.5/13
2000/2000 [944/944]
59,000 [17.29]
44,050 [12.91]
14,950 [4.38]
5.04
61,500 [18.02]
11.5/13
2000/2000 [944/944]
59,000 [17.29]
44,050 [12.91]
14,950 [4.38]
5.04
A060CM
Continued ->
61,500 [18.02]
11.5/13
2000/2000 [944/944]
59,000 [17.29]
44,050 [12.91]
14,950 [4.38]
5.04
49,000 [14.36]
3.93/3.6
29,000 [8.5]
3.63/2.3
7.7
60,000 [17.58]
4.78/3.6
35,800 [10.49]
4.31/2.4
7.7
60,000 [17.58]
4.78/3.6
35,800 [10.49]
4.31/2.4
7.7
60,000 [17.58]
4.78/3.6
35,800 [10.49]
4.31/2.4
7.7
1/Copeland Scroll
83
Louvered
Rifled
0.375 [9.5]
16.56 [1.54]
2 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
5.16 [0.48]
4 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/10x10 [254x254]
Direct/3
1
1/2
1075
48
Disposable
Yes
(2)1x25x16 [25x635x406]
1/Copeland Scroll
83
Louvered
Rifled
0.375 [9.5]
16.56 [1.54]
2 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
5.16 [0.48]
4 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/11x9 [279x229]
Direct/2
1
1
1100
48
Disposable
Yes
(2)1x25x16 [25x635x406]
1/Copeland Scroll
83
Louvered
Rifled
0.375 [9.5]
16.56 [1.54]
2 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
5.16 [0.48]
4 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/10x10 [254x254]
Belt/Variable
1
3/4
1725
56
Disposable
Yes
(2)1x25x16 [25x635x406]
1/Copeland Scroll
83
Louvered
Rifled
0.375 [9.5]
16.56 [1.54]
2 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
5.16 [0.48]
4 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/10x10 [254x254]
Belt/Variable
1
1
1725
56
Disposable
Yes
(2)1x25x16 [25x635x406]
187 [5301]
195 [5528]
195 [5528]
195 [5528]
535 [243]
550 [249]
565 [256]
580 [263]
565 [256]
580 [263]
565 [256]
580 [263]
NOTES:
1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity
is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner
Equipment certification program, which is based on ARI Standard 210/240 or 360.
2. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures.
3. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270.utdoor Sound Rating shown is tested in accordance with ARI Standard 270.
27
GENERAL DATA - RJNL MODELS
NOMINAL SIZES 3-5 TONS [10.6-17.6 kW]
Model RJNL - Series
A060DK
A060DL
A060DM
Cooling performance1
Gross Cooling Capacity Btu [kW]
EER, SEER2
Nominal CFM/AHRI Rated CFM [L/s]
AHRI Net Cooling Capacity Btu [kW]
Net Sensible Capacity Btu [kW]
Net Latent Capacity Btu [kW]
Net System Power kW
A060JK
Continued ->
61,000 [17.87]
11.5/13
2000/2000 [944/944]
59,000 [17.29]
44,050 [12.91]
14,950 [4.38]
5.04
61,500 [18.02]
11.5/13
2000/2000 [944/944]
59,000 [17.29]
44,050 [12.91]
14,950 [4.38]
5.04
61,500 [18.02]
11.5/13
2000/2000 [944/944]
59,000 [17.29]
44,050 [12.91]
14,950 [4.38]
5.04
61,000 [17.87]
11.5/13
2000/2000 [944/944]
59,000 [17.29]
44,050 [12.91]
14,950 [4.38]
5.04
Heating Performance (Heat Pumps)
High Temp. Btuh [kW] Rating
System Power KW / COP
Low Temp. Btuh [kW] Rating
System Power KW / COP
HSPF (Btu/Watts-hr)
60,000 [17.58]
4.78/3.6
35,800 [10.49]
4.31/2.4
7.7
60,000 [17.58]
4.78/3.6
35,800 [10.49]
4.31/2.4
7.7
60,000 [17.58]
4.78/3.6
35,800 [10.49]
4.31/2.4
7.7
60,000 [17.58]
4.78/3.6
35,800 [10.49]
4.31/2.4
7.7
Compressor
No/Type
1/Copeland Scroll
1/Copeland Scroll
1/Copeland Scroll
1/Copeland Scroll
Outdoor Sound Rating (dB)5
83
83
83
83
Outdoor Coil - Fin Type
Tube Type
Tube Size in. [mm] OD
Face Area sq. ft. [sq. m]
Rows / FPI [FPcm]
Refrigerant Control
Indoor Coil - Fin Type
Tube Type
Tube Size in. [mm]
Face Area sq. ft. [sq. m]
Rows / FPI [FPcm]
Refrigerant Control
Drain Connection No./Size in. [mm]
Outdoor Fan - Type
No. Used/Diameter in. [mm]
Drive Type/No. Speeds
CFM [L/s]
No. Motors/HP
Motor RPM
Indoor Fan - Type
No. Used/Diameter in. [mm]
Drive Type/No. Speeds
No. Motors
Motor HP
Motor RPM
Motor Frame Size
Filter - Type
Furnished
(NO.) Size Recommended in. [mm x mm x mm]
Refrigerant Charge Oz. [g]
Weights
Net Weight lbs. [kg]
Ship Weight lbs. [kg]
Louvered
Rifled
0.375 [9.5]
16.56 [1.54]
2 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
5.16
4 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/10x10 [254x254]
Belt/Variable
1
3/4
1725
56
Disposable
Yes
(2)1x25x16 [25x635x406]
195 [5528]
Louvered
Rifled
0.375 [9.5]
16.56 [1.54]
2 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
5.16
4 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/10x10 [254x254]
Belt/Variable
1
1
1725
56
Disposable
Yes
(2)1x25x16 [25x635x406]
195 [5528]
Louvered
Rifled
0.375 [9.5]
16.56 [1.54]
2 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
5.16
4 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/11x9 [279x229]
Direct/2
1
1
1100
48
Disposable
Yes
(2)1x25x16 [25x635x406]
195 [5528]
Louvered
Rifled
0.375 [9.5]
16.56 [1.54]
2 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
5.16
4 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/11x9 [279x229]
Direct/2
1
1
1100
48
Disposable
Yes
(2)1x25x16 [25x635x406]
195 [5528]
565 [256]
580 [263]
565 [256]
580 [263]
565 [256]
580 [263]
565 [256]
580 [263]
NOTES:
1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not include the effect of fan motor heat. AHRI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner
Equipment certification program, which is based on AHRI Standard 210/240 or 360.
2. EER and/or SEER are rated at AHRI conditions and in accordance with DOE test procedures.
3. Outdoor Sound Rating shown is tested in accordance with AHRI Standard 270.utdoor Sound Rating shown is tested in accordance with ARI Standard 270.
28
GENERAL DATA - RJNL MODELS
NOMINAL SIZES 3-5 TONS [10.6-17.6 kW]
Model RJNL - Series
A072CL
A072CM
A072DL
Cooling performance1
Gross Cooling Capacity Btu [kW]
EER, SEER2
Nominal CFM/AHRI Rated CFM [L/s]
AHRI Net Cooling Capacity Btu [kW]
Net Sensible Capacity Btu [kW]
Net Latent Capacity Btu [kW]
Net System Power kW
A072DM
Continued ->
73,000 [21.39]
11/NA
2400/2125 [1133/1003]
70,000 [20.51]
50,700 [14.85]
19,300 [5.65]
6.37
73,000 [21.39]
11/NA
2400/2125 [1133/1003]
70,000 [20.51]
50,700 [14.85]
19,300 [5.65]
6.37
73,000 [21.39]
11/NA
2400/2125 [1133/1003]
70,000 [20.51]
50,700 [14.85]
19,300 [5.65]
6.37
73,000 [21.39]
11/NA
2400/2125 [1133/1003]
70,000 [20.51]
50,700 [14.85]
19,300 [5.65]
6.37
Heating Performance (Heat Pumps)
High Temp. Btuh [kW] Rating
System Power KW / COP
Low Temp. Btuh [kW] Rating
System Power KW / COP
68,000 [19.92]
5.79/3.44
41,000 [12.01]
5.22/2.3
68,000 [19.92]
5.79/3.44
41,000 [12.01]
5.22/2.3
68,000 [19.92]
5.79/3.44
41,000 [12.01]
5.22/2.3
68,000 [19.92]
5.79/3.44
41,000 [12.01]
5.22/2.3
Compressor
No/Type
1/Scroll
1/Scroll
1/Scroll
1/Scroll
Outdoor Sound Rating (dB)5
83
83
83
83
Outdoor Coil - Fin Type
Tube Type
Tube Size in. [mm] OD
Face Area sq. ft. [sq. m]
Rows / FPI [FPcm]
Refrigerant Control
Indoor Coil - Fin Type
Tube Type
Tube Size in. [mm]
Face Area sq. ft. [sq. m]
Rows / FPI [FPcm]
Refrigerant Control
Drain Connection No./Size in. [mm]
Outdoor Fan - Type
No. Used/Diameter in. [mm]
Drive Type/No. Speeds
CFM [L/s]
No. Motors/HP
Motor RPM
Indoor Fan - Type
No. Used/Diameter in. [mm]
Drive Type/No. Speeds
No. Motors
Motor HP
Motor RPM
Motor Frame Size
Filter - Type
Furnished
(NO.) Size Recommended in. [mm x mm x mm]
Refrigerant Charge Oz. [g]
Weights
Net Weight lbs. [kg]
Ship Weight lbs. [kg]
Louvered
Rifled
0.375 [9.5]
16.56 [1.54]
2 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
6.5 [0.6]
4 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/11x11 [279x279]
Belt/Variable
1
1 1/2
1725
56
Disposable
Yes
(4)1x16x16 [25x406x406]
221 [6265]
Louvered
Rifled
0.375 [9.5]
16.56 [1.54]
2 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
6.5 [0.6]
4 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/11x11 [279x279]
Belt/Variable
1
1 1/2
1725
56
Disposable
Yes
(4)1x16x16 [25x406x406]
221 [6265]
Louvered
Rifled
0.375 [9.5]
16.56 [1.54]
2 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
6.5 [0.6]
4 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/11x11 [279x279]
Belt/Variable
1
1 1/2
1725
56
Disposable
Yes
(4)1x16x16 [25x406x406]
221 [6265]
Louvered
Rifled
0.375 [9.5]
16.56 [1.54]
2 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
6.5 [0.6]
4 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/11x11 [279x279]
Belt/Variable
1
1 1/2
1725
56
Disposable
Yes
(4)1x16x16 [25x406x406]
221 [6265]
620 [281]
635 [288]
620 [281]
635 [288]
620 [281]
635 [288]
620 [281]
635 [288]
NOTES:
1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not include the effect of fan motor heat. AHRI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner
Equipment certification program, which is based on AHRI Standard 210/240 or 360.
2. EER and/or SEER are rated at AHRI conditions and in accordance with DOE test procedures.
3. Outdoor Sound Rating shown is tested in accordance with AHRI Standard 270.utdoor Sound Rating shown is tested in accordance with ARI Standard 270.
29
GENERAL DATA - RJNL MODELS
NOMINAL SIZES 3-5 TONS [10.6-17.6 kW]
Model RJNL - Series
A072YL
Cooling performance1
Gross Cooling Capacity Btu [kW]
EER, SEER2
Nominal CFM/AHRI Rated CFM [L/s]
AHRI Net Cooling Capacity Btu [kW]
Net Sensible Capacity Btu [kW]
Net Latent Capacity Btu [kW]
Net System Power kW
73,000 [21.39]
11/NA
2400/2125 [1133/1003]
70,000 [20.51]
50,700 [14.85]
19,300 [5.65]
6.37
Heating Performance (Heat Pumps)
High Temp. Btuh [kW] Rating
System Power KW / COP
Low Temp. Btuh [kW] Rating
System Power KW / COP
68,000 [19.92]
5.79/3.44
41,000 [12.01]
5.22/2.3
Compressor
No/Type
1/Scroll
Outdoor Sound Rating (dB)5
83
Outdoor Coil - Fin Type
Tube Type
Tube Size in. [mm] OD
Face Area sq. ft. [sq. m]
Rows / FPI [FPcm]
Refrigerant Control
Indoor Coil - Fin Type
Tube Type
Tube Size in. [mm]
Face Area sq. ft. [sq. m]
Rows / FPI [FPcm]
Refrigerant Control
Drain Connection No./Size in. [mm]
Outdoor Fan - Type
No. Used/Diameter in. [mm]
Drive Type/No. Speeds
CFM [L/s]
No. Motors/HP
Motor RPM
Indoor Fan - Type
No. Used/Diameter in. [mm]
Drive Type/No. Speeds
No. Motors
Motor HP
Motor RPM
Motor Frame Size
Filter - Type
Furnished
(NO.) Size Recommended in. [mm x mm x mm]
Refrigerant Charge Oz. [g]
Weights
Net Weight lbs. [kg]
Ship Weight lbs. [kg]
Louvered
Rifled
0.375 [9.5]
16.56 [1.54]
2 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
6.5 [0.6]
4 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/11x11 [279x279]
Belt/Variable
1
1 1/2
1725
56
Disposable
Yes
(4)1x16x16 [25x406x406]
221 [6265]
620 [281]
635 [288]
NOTES:
1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not include the effect of fan motor heat. AHRI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner
Equipment certification program, which is based on AHRI Standard 210/240 or 360.
2. EER and/or SEER are rated at AHRI conditions and in accordance with DOE test procedures.
3. Outdoor Sound Rating shown is tested in accordance with AHRI Standard 270.utdoor Sound Rating shown is tested in accordance with ARI Standard 270.
30
GENERAL DATA - RJPL MODELS
NOMINAL SIZES 3-5 TONS [10.6-17.6 kW]
Model RJPL - Series
A036CK
A036CL
A036CM
Cooling performance1
Gross Cooling Capacity Btu [kW]
EER, SEER2
Nominal CFM/AHRI Rated CFM [L/s]
AHRI Net Cooling Capacity Btu [kW]
Net Sensible Capacity Btu [kW]
Net Latent Capacity Btu [kW]
Net System Power kW
A036DK
Continued ->
37,800 [11.08]
12/14
1200/1200 [566/566]
36,800 [10.78]
27,200 [7.97]
9,600 [2.81]
2.99
37,800 [11.08]
12/14
1200/1200 [566/566]
36,800 [10.78]
27,200 [7.97]
9,600 [2.81]
2.99
37,800 [11.08]
12/14
1200/1200 [566/566]
36,800 [10.78]
27,200 [7.97]
9,600 [2.81]
2.99
37,800 [11.08]
12/14
1200/1200 [566/566]
36,800 [10.78]
27,200 [7.97]
9,600 [2.81]
2.99
Heating Performance (Heat Pumps)
High Temp. Btuh [kW] Rating
System Power KW / COP
Low Temp. Btuh [kW] Rating
System Power KW / COP
HSPF (Btu/Watts-hr)
33,600 [9.84]
2.79/3.48
19,400 [5.68]
2.56/2.22
8
33,600 [9.84]
2.79/3.48
19,400 [5.68]
2.56/2.22
8
33,600 [9.84]
2.79/3.48
19,400 [5.68]
2.56/2.22
8
33,600 [9.84]
2.79/3.48
19,400 [5.68]
2.56/2.22
8
Compressor
No/Type
1/Copeland Scroll
1/Copeland Scroll
1/Copeland Scroll
1/Copeland Scroll
Outdoor Sound Rating (dB)5
83
83
83
83
Outdoor Coil - Fin Type
Tube Type
Tube Size in. [mm] OD
Face Area sq. ft. [sq. m]
Rows / FPI [FPcm]
Refrigerant Control
Indoor Coil - Fin Type
Tube Type
Tube Size in. [mm]
Face Area sq. ft. [sq. m]
Rows / FPI [FPcm]
Refrigerant Control
Drain Connection No./Size in. [mm]
Outdoor Fan - Type
No. Used/Diameter in. [mm]
Drive Type/No. Speeds
CFM [L/s]
No. Motors/HP
Motor RPM
Indoor Fan - Type
No. Used/Diameter in. [mm]
Drive Type/No. Speeds
No. Motors
Motor HP
Motor RPM
Motor Frame Size
Filter - Type
Furnished
(NO.) Size Recommended in. [mm x mm x mm]
Refrigerant Charge Oz. [g]
Weights
Net Weight lbs. [kg]
Ship Weight lbs. [kg]
Louvered
Rifled
0.375 [9.5]
16.89 [1.57]
1 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
5.16 [0.48]
3 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/10x10 [254x254]
Direct/3
1
1/2
1075
48
Disposable
Yes
(2)1x25x16 [25x635x406]
116 [3289]
Louvered
Rifled
0.375 [9.5]
16.89 [1.57]
1 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
5.16 [0.48]
3 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/10x10 [254x254]
Direct/3
1
1/2
1725
56
Disposable
Yes
(2)1x25x16 [25x635x406]
116 [3289]
Louvered
Rifled
0.375 [9.5]
16.89 [1.57]
1 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
5.16 [0.48]
3 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/10x10 [254x254]
Belt/Variable
1
3/4
1725
56
Disposable
Yes
(2)1x25x16 [25x635x406]
116 [3289]
Louvered
Rifled
0.375 [9.5]
16.89 [1.57]
1 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
5.16 [0.48]
3 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/10x10 [254x254]
Belt/Variable
1
1/2
1075
48
Disposable
Yes
(2)1x25x16 [25x635x406]
116 [3289]
517 [235]
532 [241]
517 [235]
532 [241]
517 [235]
532 [241]
517 [235]
532 [241]
NOTES:
1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not include the effect of fan motor heat. AHRI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner
Equipment certification program, which is based on AHRI Standard 210/240 or 360.
2. EER and/or SEER are rated at AHRI conditions and in accordance with DOE test procedures.
3. Outdoor Sound Rating shown is tested in accordance with AHRI Standard 270.utdoor Sound Rating shown is tested in accordance with AHRI Standard 270.
31
GENERAL DATA - RJPL MODELS
NOMINAL SIZES 3-5 TONS [10.6-17.6 kW]
Model RJPL - Series
A036DL
A036DM
A036JK
Cooling performance1
Gross Cooling Capacity Btu [kW]
EER, SEER2
Nominal CFM/AHRI Rated CFM [L/s]
AHRI Net Cooling Capacity Btu [kW]
Net Sensible Capacity Btu [kW]
Net Latent Capacity Btu [kW]
Net System Power kW
A042CK
Continued ->
38,500 [11.28]
12/14
1200/1200 [566/566]
36,800 [10.78]
27,200 [7.97]
9,600 [2.81]
2.99
38,500 [11.28]
12/14
1200/1200 [566/566]
36,800 [10.78]
27,200 [7.97]
9,600 [2.81]
2.99
37,800 [11.08]
12/14
1200/1200 [566/566]
36,800 [10.78]
27,200 [7.97]
9,600 [2.81]
2.99
43,500 [12.75]
11.6/14
1400/1400 [661/661]
42,000 [12.31]
31,750 [9.3]
10,250 [3]
3.64
Heating Performance (Heat Pumps)
High Temp. Btuh [kW] Rating
System Power KW / COP
Low Temp. Btuh [kW] Rating
System Power KW / COP
HSPF (Btu/Watts-hr)
33,600 [9.84]
2.79/3.48
19,400 [5.68]
2.56/2.22
8
33,600 [9.84]
2.79/3.48
19,400 [5.68]
2.56/2.22
8
33,600 [9.84]
2.79/3.48
19,400 [5.68]
2.56/2.22
8
40,000 [11.72]
3.23/3.6
24,200 [7.09]
2.94/2.4
8
8
Compressor
No/Type
1/Copeland Scroll
1/Copeland Scroll
1/Copeland Scroll
1/Copeland Scroll
Outdoor Sound Rating (dB)5
83
83
83
83
Outdoor Coil - Fin Type
Tube Type
Tube Size in. [mm] OD
Face Area sq. ft. [sq. m]
Rows / FPI [FPcm]
Refrigerant Control
Indoor Coil - Fin Type
Tube Type
Tube Size in. [mm]
Face Area sq. ft. [sq. m]
Rows / FPI [FPcm]
Refrigerant Control
Drain Connection No./Size in. [mm]
Outdoor Fan - Type
No. Used/Diameter in. [mm]
Drive Type/No. Speeds
CFM [L/s]
No. Motors/HP
Motor RPM
Indoor Fan - Type
No. Used/Diameter in. [mm]
Drive Type/No. Speeds
No. Motors
Motor HP
Motor RPM
Motor Frame Size
Filter - Type
Furnished
(NO.) Size Recommended in. [mm x mm x mm]
Refrigerant Charge Oz. [g]
Weights
Net Weight lbs. [kg]
Ship Weight lbs. [kg]
Louvered
Rifled
0.375 [9.5]
16.89 [1.57]
1 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
5.16 [0.48]
3 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/10x10 [254x254]
1
1/2
1725
56
Disposable
Yes
(2)1x25x16 [25x635x406]
116 [3289]
Louvered
Rifled
0.375 [9.5]
16.89 [1.57]
1 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
5.16 [0.48]
3 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/10x10 [254x254]
Belt/VariableBelt/Variable
1
1/2
1725
56
Disposable
Yes
(2)1x25x16 [25x635x406]
116 [3289]
Louvered
Rifled
0.375 [9.5]
16.89 [1.57]
1 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
5.16 [0.48]
3 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/10x10 [254x254]
Belt/Variable
1
1/2
1075
48
Disposable
Yes
(2)1x25x16 [25x635x406]
116 [3289]
Louvered
Rifled
0.375 [9.5]
16.89 [1.57]
1 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
5.16 [0.48]
3 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/10x10 [254x254]
Direct/3
1
1/2
1075
48
Disposable
Yes
(2)1x25x16 [25x635x406]
120 [3402]
517 [235]
532 [241]
517 [235]
532 [241]
517 [235]
532 [241]
521 [236]
536 [243]
NOTES:
1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not include the effect of fan motor heat. AHRI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner
Equipment certification program, which is based on AHRI Standard 210/240 or 360.
2. EER and/or SEER are rated at AHRI conditions and in accordance with DOE test procedures.
3. Outdoor Sound Rating shown is tested in accordance with AHRI Standard 270.utdoor Sound Rating shown is tested in accordance with AHRI Standard 270.
32
GENERAL DATA - RJPL MODELS
NOMINAL SIZES 3-5 TONS [10.6-17.6 kW]
Model RJPL - Series
A042CL
A042CM
A042DK
Cooling performance1
Gross Cooling Capacity Btu [kW]
EER, SEER2
Nominal CFM/AHRI Rated CFM [L/s]
AHRI Net Cooling Capacity Btu [kW]
Net Sensible Capacity Btu [kW]
Net Latent Capacity Btu [kW]
Net System Power kW
A042DL
Continued ->
44,000 [12.89]
11.6/14
1400/1400 [661/661]
42,000 [12.31]
31,750 [9.3]
10,250 [3]
3.64
44,000 [12.89]
11.6/14
1400/1400 [661/661]
42,000 [12.31]
31,750 [9.3]
10,250 [3]
3.64
43,500 [12.75]
11.6/14
1400/1400 [661/661]
42,000 [12.31]
31,750 [9.3]
10,250 [3]
3.64
44,000 [12.89]
11.6/14
1400/1400 [661/661]
42,000 [12.31]
31,750 [9.3]
10,250 [3]
3.64
Heating Performance (Heat Pumps)
High Temp. Btuh [kW] Rating
System Power KW / COP
Low Temp. Btuh [kW] Rating
System Power KW / COP
HSPF (Btu/Watts-hr)
40,000 [11.72]
3.23/3.6
24,200 [7.09]
2.94/2.4
8
40,000 [11.72]
3.23/3.6
24,200 [7.09]
2.94/2.4
8
40,000 [11.72]
3.23/3.6
24,200 [7.09]
2.94/2.4
8
40,000 [11.72]
3.23/3.6
24,200 [7.09]
2.94/2.4
8
Compressor
No/Type
1/Copeland Scroll
1/Copeland Scroll
1/Copeland Scroll
1/Copeland Scroll
Outdoor Sound Rating (dB)5
83
83
83
83
Outdoor Coil - Fin Type
Tube Type
Tube Size in. [mm] OD
Face Area sq. ft. [sq. m]
Rows / FPI [FPcm]
Refrigerant Control
Indoor Coil - Fin Type
Tube Type
Tube Size in. [mm]
Face Area sq. ft. [sq. m]
Rows / FPI [FPcm]
Refrigerant Control
Drain Connection No./Size in. [mm]
Outdoor Fan - Type
No. Used/Diameter in. [mm]
Drive Type/No. Speeds
CFM [L/s]
No. Motors/HP
Motor RPM
Indoor Fan - Type
No. Used/Diameter in. [mm]
Drive Type/No. Speeds
No. Motors
Motor HP
Motor RPM
Motor Frame Size
Filter - Type
Furnished
(NO.) Size Recommended in. [mm x mm x mm]
Refrigerant Charge Oz. [g]
Weights
Net Weight lbs. [kg]
Ship Weight lbs. [kg]
Louvered
Rifled
0.375 [9.5]
16.89 [1.57]
1 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
5.16 [0.48]
3 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/10x10 [254x254]
Belt/Variable
1
1/2
1725
56
Disposable
Yes
(2)1x25x16 [25x635x406]
120 [3402]
Louvered
Rifled
0.375 [9.5]
16.89 [1.57]
1 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
5.16 [0.48]
3 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/10x10 [254x254]
Belt/Variable
1
3/4
1725
56
Disposable
Yes
(2)1x25x16 [25x635x406]
120 [3402]
Louvered
Rifled
0.375 [9.5]
16.89 [1.57]
1 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
5.16 [0.48]
3 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/10x10 [254x254]
Direct/3
1
1/2
1075
48
Disposable
Yes
(2)1x25x16 [25x635x406]
120 [3402]
Louvered
Rifled
0.375 [9.5]
16.89 [1.57]
1 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
5.16 [0.48]
3 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/10x10 [254x254]
Belt/Variable
1
1/2
1725
56
Disposable
Yes
(2)1x25x16 [25x635x406]
120 [3402]
521 [236]
536 [243]
521 [236]
536 [243]
521 [236]
536 [243]
521 [236]
536 [243]
NOTES:
1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not include the effect of fan motor heat. AHRI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner
Equipment certification program, which is based on AHRI Standard 210/240 or 360.
2. EER and/or SEER are rated at AHRI conditions and in accordance with DOE test procedures.
3. Outdoor Sound Rating shown is tested in accordance with AHRI Standard 270.utdoor Sound Rating shown is tested in accordance with AHRI Standard 270.
33
GENERAL DATA - RJPL MODELS
NOMINAL SIZES 3-5 TONS [10.6-17.6 kW]
Model RJPL - Series
A042DM
A042JK
A048CK
Cooling performance1
Gross Cooling Capacity Btu [kW]
EER, SEER2
Nominal CFM/AHRI Rated CFM [L/s]
AHRI Net Cooling Capacity Btu [kW]
Net Sensible Capacity Btu [kW]
Net Latent Capacity Btu [kW]
Net System Power kW
A048CL
Continued ->
44,000 [12.89]
11.6/14
1400/1400 [661/661]
42,000 [12.31]
31,750 [9.3]
10,250 [3]
3.64
43,500 [12.75]
11.6/14
1400/1400 [661/661]
42,000 [12.31]
31,750 [9.3]
10,250 [3]
3.64
49,000 [14.36]
11.6/14
1600/1600 [755/755]
47,500 [13.92]
36,200 [10.61]
11,300 [3.31]
4.09
50,000 [14.65]
11.6/14
1600/1600 [755/755]
47,500 [13.92]
36,200 [10.61]
11,300 [3.31]
4.09
Heating Performance (Heat Pumps)
High Temp. Btuh [kW] Rating
System Power KW / COP
Low Temp. Btuh [kW] Rating
System Power KW / COP
HSPF (Btu/Watts-hr)
40,000 [11.72]
3.23/3.6
24,200 [7.09]
2.94/2.4
8
40,000 [11.72]
3.23/3.6
24,200 [7.09]
2.94/2.4
8
49,000 [14.36]
3.76/3.8
29,800 [8.73]
3.48/2.4
8
49,000 [14.36]
3.76/3.8
29,800 [8.73]
3.48/2.4
8
Compressor
No/Type
1/Copeland Scroll
1/Copeland Scroll
1/Copeland Scroll
1/Copeland Scroll
Outdoor Sound Rating (dB)5
83
83
83
83
Outdoor Coil - Fin Type
Tube Type
Tube Size in. [mm] OD
Face Area sq. ft. [sq. m]
Rows / FPI [FPcm]
Refrigerant Control
Indoor Coil - Fin Type
Tube Type
Tube Size in. [mm]
Face Area sq. ft. [sq. m]
Rows / FPI [FPcm]
Refrigerant Control
Drain Connection No./Size in. [mm]
Outdoor Fan - Type
No. Used/Diameter in. [mm]
Drive Type/No. Speeds
CFM [L/s]
No. Motors/HP
Motor RPM
Indoor Fan - Type
No. Used/Diameter in. [mm]
Drive Type/No. Speeds
No. Motors
Motor HP
Motor RPM
Motor Frame Size
Filter - Type
Furnished
(NO.) Size Recommended in. [mm x mm x mm]
Refrigerant Charge Oz. [g]
Weights
Net Weight lbs. [kg]
Ship Weight lbs. [kg]
Louvered
Rifled
0.375 [9.5]
16.89 [1.57]
1 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
5.16 [0.48]
4 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/10x10 [254x254]
Belt/Variable
1
3/4
1725
56
Disposable
Yes
(2)1x25x16 [25x635x406]
120 [3402]
Louvered
Rifled
0.375 [9.5]
16.89 [1.57]
1 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
5.16 [0.48]
4 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/10x10 [254x254]
Direct/3
1
1/2
1075
48
Disposable
Yes
(2)1x25x16 [25x635x406]
120 [3402]
Louvered
Rifled
0.375 [9.5]
16.56 [1.54]
2 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
5.16 [0.48]
4 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/10x10 [254x254]
Direct/3
1
1/2
1075
48
Disposable
Yes
(2)1x25x16 [25x635x406]
187 [5301]
Louvered
Rifled
0.375 [9.5]
16.56 [1.54]
2 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
5.16 [0.48]
4 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/10x10 [254x254]
Belt/Variable
1
1/2
1725
56
Disposable
Yes
(2)1x25x16 [25x635x406]
187 [5301]
521 [236]
536 [243]
521 [236]
536 [243]
535 [243]
550 [249]
535 [243]
550 [249]
NOTES:
1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not include the effect of fan motor heat. AHRI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner
Equipment certification program, which is based on AHRI Standard 210/240 or 360.
2. EER and/or SEER are rated at AHRI conditions and in accordance with DOE test procedures.
3. Outdoor Sound Rating shown is tested in accordance with AHRI Standard 270.utdoor Sound Rating shown is tested in accordance with AHRI Standard 270.
34
GENERAL DATA - RJPL MODELS
NOMINAL SIZES 3-5 TONS [10.6-17.6 kW]
Model RJPL - Series
A048CM
A048DK
A048DL
Cooling performance1
Gross Cooling Capacity Btu [kW]
EER, SEER2
Nominal CFM/AHRI Rated CFM [L/s]
AHRI Net Cooling Capacity Btu [kW]
Net Sensible Capacity Btu [kW]
Net Latent Capacity Btu [kW]
Net System Power kW
A048DM
Continued ->
50,000 [14.65]
11.6/14
1600/1600 [755/755]
47,500 [13.92]
36,200 [10.61]
11,300 [3.31]
4.09
49,000 [14.36]
11.6/14
1600/1600 [755/755]
47,500 [13.92]
36,200 [10.61]
11,300 [3.31]
4.09
50,000 [14.65]
11.6/14
1600/1600 [755/755]
47,500 [13.92]
36,200 [10.61]
11,300 [3.31]
4.09
50,000 [14.65]
11.6/14
1600/1600 [755/755]
47,500 [13.92]
36,200 [10.61]
11,300 [3.31]
4.09
Heating Performance (Heat Pumps)
High Temp. Btuh [kW] Rating
System Power KW / COP
Low Temp. Btuh [kW] Rating
System Power KW / COP
HSPF (Btu/Watts-hr)
49,000 [14.36]
3.76/3.8
29,800 [8.73]
3.48/2.4
8
49,000 [14.36]
3.76/3.8
29,800 [8.73]
3.48/2.4
8
49,000 [14.36]
3.76/3.8
29,800 [8.73]
3.48/2.4
8
49,000 [14.36]
3.76/3.8
29,800 [8.73]
3.48/2.4
8
Compressor
No/Type
1/Copeland Scroll
1/Copeland Scroll
1/Copeland Scroll
1/Copeland Scroll
Outdoor Sound Rating (dB)5
83
83
83
83
Outdoor Coil - Fin Type
Tube Type
Tube Size in. [mm] OD
Face Area sq. ft. [sq. m]
Rows / FPI [FPcm]
Refrigerant Control
Indoor Coil - Fin Type
Tube Type
Tube Size in. [mm]
Face Area sq. ft. [sq. m]
Rows / FPI [FPcm]
Refrigerant Control
Drain Connection No./Size in. [mm]
Outdoor Fan - Type
No. Used/Diameter in. [mm]
Drive Type/No. Speeds
CFM [L/s]
No. Motors/HP
Motor RPM
Indoor Fan - Type
No. Used/Diameter in. [mm]
Drive Type/No. Speeds
No. Motors
Motor HP
Motor RPM
Motor Frame Size
Filter - Type
Furnished
(NO.) Size Recommended in. [mm x mm x mm]
Refrigerant Charge Oz. [g]
Weights
Net Weight lbs. [kg]
Ship Weight lbs. [kg]
Louvered
Rifled
0.375 [9.5]
16.56 [1.54]
2 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
5.16 [0.48]
4 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/10x10 [254x254]
Belt/Variable
1
3/4
1725
56
Disposable
Yes
(2)1x25x16 [25x635x406]
187 [5301]
Louvered
Rifled
0.375 [9.5]
16.56 [1.54]
2 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
5.16 [0.48]
4 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/10x10 [254x254]
Direct/3
1
1/2
1075
48
Disposable
Yes
(2)1x25x16 [25x635x406]
187 [5301]
Louvered
Rifled
0.375 [9.5]
16.56 [1.54]
2 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
5.16 [0.48]
4 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/10x10 [254x254]
Belt/Variable
1
1/2
1725
56
Disposable
Yes
(2)1x25x16 [25x635x406]
187 [5301]
Louvered
Rifled
0.375 [9.5]
16.56 [1.54]
2 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
5.16 [0.48]
4 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/10x10 [254x254]
Belt/Variable
1
3/4
1725
56
Disposable
Yes
(2)1x25x16 [25x635x406]
187 [5301]
535 [243]
550 [249]
535 [243]
550 [249]
535 [243]
550 [249]
535 [243]
550 [249]
NOTES:
1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not include the effect of fan motor heat. AHRI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner
Equipment certification program, which is based on AHRI Standard 210/240 or 360.
2. EER and/or SEER are rated at AHRI conditions and in accordance with DOE test procedures.
3. Outdoor Sound Rating shown is tested in accordance with AHRI Standard 270.utdoor Sound Rating shown is tested in accordance with AHRI Standard 270.
35
GENERAL DATA - RJPL MODELS
NOMINAL SIZES 3-5 TONS [10.6-17.6 kW]
Model RJPL - Series
A048JK
A060CK
A060CL
Cooling performance1
Gross Cooling Capacity Btu [kW]
EER, SEER2
Nominal CFM/AHRI Rated CFM [L/s]
AHRI Net Cooling Capacity Btu [kW]
Net Sensible Capacity Btu [kW]
Net Latent Capacity Btu [kW]
Net System Power kW
A060CM
Continued ->
49,000 [14.36]
11.6/14
1600/1600 [755/755]
47,500 [13.92]
36,200 [10.61]
11,300 [3.31]
4.09
61,000 [17.87]
11.7/14
2000/1850 [944/873]
59,500 [17.43]
43,600 [12.77]
15,900 [4.66]
5.05
61,000 [17.87]
11.7/14
2000/1850 [944/873]
59,500 [17.43]
43,600 [12.77]
15,900 [4.66]
5.05
61,000 [17.87]
11.7/14
2000/1850 [944/873]
59,500 [17.43]
43,600 [12.77]
15,900 [4.66]
5.05
Heating Performance (Heat Pumps)
High Temp. Btuh [kW] Rating
System Power KW / COP
Low Temp. Btuh [kW] Rating
System Power KW / COP
HSPF (Btu/Watts-hr)
49,000 [14.36]
3.76/3.8
29,800 [8.73]
3.48/2.4
8
59,500 [17.43]
4.8/3.6
36,400 [10.67]
4.47/2.2
8
59,500 [17.43]
4.8/3.6
36,400 [10.67]
4.47/2.2
8
59,500 [17.43]
4.8/3.6
36,400 [10.67]
4.47/2.2
8
Compressor
No/Type
1/Copeland Scroll
1/Copeland Scroll
1/Copeland Scroll
1/Copeland Scroll
Outdoor Sound Rating (dB)5
83
83
83
83
Outdoor Coil - Fin Type
Tube Type
Tube Size in. [mm] OD
Face Area sq. ft. [sq. m]
Rows / FPI [FPcm]
Refrigerant Control
Indoor Coil - Fin Type
Tube Type
Tube Size in. [mm]
Face Area sq. ft. [sq. m]
Rows / FPI [FPcm]
Refrigerant Control
Drain Connection No./Size in. [mm]
Outdoor Fan - Type
No. Used/Diameter in. [mm]
Drive Type/No. Speeds
CFM [L/s]
No. Motors/HP
Motor RPM
Indoor Fan - Type
No. Used/Diameter in. [mm]
Drive Type/No. Speeds
No. Motors
Motor HP
Motor RPM
Motor Frame Size
Filter - Type
Furnished
(NO.) Size Recommended in. [mm x mm x mm]
Refrigerant Charge Oz. [g]
Weights
Net Weight lbs. [kg]
Ship Weight lbs. [kg]
Louvered
Rifled
0.375 [9.5]
16.56 [1.54]
2 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
5.16 [0.48]
4 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/10x10 [254x254]
Direct/3
1
1/2
1075
48
Disposable
Yes
(2)1x25x16 [25x635x406]
187 [5301]
Louvered
Rifled
0.375 [9.5]
16.56 [1.54]
2 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
5.16 [0.48]
4 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/11x9 [279x229]
Direct/2
1
1
1100
48
Disposable
Yes
(2)1x25x16 [25x635x406]
195 [5528]
Louvered
Rifled
0.375 [9.5]
16.56 [1.54]
2 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
5.16 [0.48]
4 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/10x10 [254x254]
Belt/Variable
1
3/4
1725
56
Disposable
Yes
(2)1x25x16 [25x635x406]
195 [5528]
Louvered
Rifled
0.375 [9.5]
16.56 [1.54]
2 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
5.16 [0.48]
4 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/10x10 [254x254]
Belt/Variable
1
1
1725
56
Disposable
Yes
(2)1x25x16 [25x635x406]
195 [5528]
535 [243]
550 [249]
565 [256]
580 [263]
565 [256]
580 [263]
565 [256]
580 [263]
NOTES:
1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not include the effect of fan motor heat. AHRI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner
Equipment certification program, which is based on AHRI Standard 210/240 or 360.
2. EER and/or SEER are rated at AHRI conditions and in accordance with DOE test procedures.
3. Outdoor Sound Rating shown is tested in accordance with AHRI Standard 270.utdoor Sound Rating shown is tested in accordance with AHRI Standard 270.
36
GENERAL DATA - RJPL MODELS
NOMINAL SIZES 3-5 TONS [10.6-17.6 kW]
Model RJPL - Series
A060DK
A060DL
A060DM
A060JK
Cooling performance1
Gross Cooling Capacity Btu [kW]
EER, SEER2
Nominal CFM/AHRI Rated CFM [L/s]
AHRI Net Cooling Capacity Btu [kW]
Net Sensible Capacity Btu [kW]
Net Latent Capacity Btu [kW]
Net System Power kW
61,000 [17.87]
11.7/14
2000/1850 [944/873]
59,500 [17.43]
43,600 [12.77]
15,900 [4.66]
5.05
61,000 [17.87]
11.7/14
2000/1850 [944/873]
59,500 [17.43]
43,600 [12.77]
15,900 [4.66]
5.05
61,000 [17.87]
11.7/14
2000/1850 [944/873]
59,500 [17.43]
43,600 [12.77]
15,900 [4.66]
5.05
61,000 [17.87]
11.7/14
2000/1850 [944/873]
59,500 [17.43]
43,600 [12.77]
15,900 [4.66]
5.05
Heating Performance (Heat Pumps)
High Temp. Btuh [kW] Rating
System Power KW / COP
Low Temp. Btuh [kW] Rating
System Power KW / COP
HSPF (Btu/Watts-hr)
59,500 [17.43]
4.8/3.6
36,400 [10.67]
4.47/2.2
8
59,500 [17.43]
4.8/3.6
36,400 [10.67]
4.47/2.2
8
59,500 [17.43]
4.8/3.6
36,400 [10.67]
4.47/2.2
8
59,500 [17.43]
4.8/3.6
36,400 [10.67]
4.47/2.2
8
Compressor
No/Type
1/Copeland Scroll
1/Copeland Scroll
1/Copeland Scroll
1/Copeland Scroll
Outdoor Sound Rating (dB)5
83
83
83
83
Outdoor Coil - Fin Type
Tube Type
Tube Size in. [mm] OD
Face Area sq. ft. [sq. m]
Rows / FPI [FPcm]
Refrigerant Control
Indoor Coil - Fin Type
Tube Type
Tube Size in. [mm]
Face Area sq. ft. [sq. m]
Rows / FPI [FPcm]
Refrigerant Control
Drain Connection No./Size in. [mm]
Outdoor Fan - Type
No. Used/Diameter in. [mm]
Drive Type/No. Speeds
CFM [L/s]
No. Motors/HP
Motor RPM
Indoor Fan - Type
No. Used/Diameter in. [mm]
Drive Type/No. Speeds
No. Motors
Motor HP
Motor RPM
Motor Frame Size
Filter - Type
Furnished
(NO.) Size Recommended in. [mm x mm x mm]
Refrigerant Charge Oz. [g]
Weights
Net Weight lbs. [kg]
Ship Weight lbs. [kg]
Louvered
Rifled
0.375 [9.5]
16.56 [1.54]
2 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
5.16 [0.48]
4 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/11x9 [279x229]
Direct/2
1
1
1100
48
Disposable
Yes
(2)1x25x16 [25x635x406]
195 [5528]
Louvered
Rifled
0.375 [9.5]
16.56 [1.54]
2 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
5.16 [0.48]
4 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/10x10 [254x254]
Belt/Variable
1
3/4
1725
48
Disposable
Yes
(2)1x25x16 [25x635x406]
195 [5528]
Louvered
Rifled
0.375 [9.5]
16.56 [1.54]
2 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
5.16 [0.48]
4 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/10x10 [254x254]
Belt/Variable
1
1
1725
56
Disposable
Yes
(2)1x25x16 [25x635x406]
195 [5528]
Louvered
Rifled
0.375 [9.5]
16.56 [1.54]
2 / 22 [9]
TX Valves
Louvered
Rifled
0.375 [9.5]
5.16 [0.48]
4 / 13 [5]
TX Valves
1/0.75 [19.5]
Propeller
1/24 [609.6]
Direct/1
4000 [1888]
1 at 1/3 HP
1075
FC Centrifugal
1/11x9 [279x229]
Direct/2
1
1
1100
48
Disposable
Yes
(2)1x25x16 [25x635x406]
195 [5528]
565 [256]
580 [263]
565 [256]
580 [263]
565 [256]
580 [263]
565 [256]
580 [263]
NOTES:
1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not include the effect of fan motor heat. AHRI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner
Equipment certification program, which is based on AHRI Standard 210/240 or 360.
2. EER and/or SEER are rated at AHRI conditions and in accordance with DOE test procedures.
3. Outdoor Sound Rating shown is tested in accordance with AHRI Standard 270.utdoor Sound Rating shown is tested in accordance with AHRI Standard 270.
37
XXI. MISCELLANEOUS
Compressor Motor
Unit Information
ELECTRICAL DATA – RJNL- SERIES
A036CK
A036CL
A036CM
A036DK
A036DL
A036DM
Unit Operating
Voltage Range
187-253
187-253
187-253
414-506
414-506
414-506
Volts
208/230
208/230
208/230
460
460
460
Minimum Circuit
Ampacity
19/19
18/18
19/19
11
10
10
Minimum Overcurrent
Protection Device Size
25/25
20/20
25/25
15
15
15
Maximum Overcurrent
Protection Device Size
25/25
25/25
25/25
15
15
15
No.
1
1
1
1
1
1
Volts
208/230
208/230
208/230
460
460
460
Phase
3
3
3
3
3
3
RPM
3450
3450
3450
3450
3450
3450
HP, Compressor 1
2 1/2
2 1/2
2 1/2
2 1/2
2 1/2
2 1/2
10.4/10.4
5.8
5.8
5.8
Evaporator Fan
Condenser Motor
Amps (RLA), Comp. 1
38
10.4/10.4 10.4/10.4
Amps (LRA), Comp. 1
88/88
88/88
88/88
38
38
38
No.
1
1
1
1
1
1
Volts
208/230
208/230
208/230
460
460
460
Phase
1
1
1
1
1
1
HP
1/3
1/3
1/3
1/3
1/3
1/3
Amps (FLA, each)
1.5/1.5
1.5/1.5
1.5/1.5
1
1
1
Amps (LRA, each)
3/3
3/3
3/3
1.9
1.9
1.9
No.
1
1
1
1
1
1
Volts
208/230
208/230
208/230
460
460
460
Phase
1
3
3
1
3
3
HP
1/2
1/2
3/4
1/2
1/2
3/4
Amps (FLA, each)
2.7/2.7
2.2/2.2
3.2/3.2
1.5
1.1
1.6
Amps (LRA, each)
6.5/6.5
10.6/10.6
16.8/16.8
3.6
5.3
8.4
Compressor Motor
Unit Information
ELECTRICAL DATA – RJNL- SERIES
A036JK
A042CK
A042CL
A042CM A042DK
A042DL
Unit Operating
Voltage Range
187-253
187-253
187-253
187-253
414-506
414-506
Volts
208/230
208/230
208/230
208/230
460
460
Minimum Circuit
Ampacity
27/27
23/23
22/22
22/22
11
10
Minimum Overcurrent
Protection Device Size
35/35
30/30
25/25
30/30
15
15
Maximum Overcurrent
Protection Device Size
40/40
35/35
30/30
35/35
15
15
No.
1
1
1
1
1
1
Volts
208/230
208/230
208/230
208/230
460
460
Phase
1
3
3
3
3
3
RPM
3450
3450
3450
3450
3450
3450
HP, Compressor 1
2 1/2
3
3
3
3
3
13.5/13.5
13.5/13.5
6
6
Evaporator Fan
Condenser Motor
Amps (RLA), Comp. 1
16.7/16.7 13.5/13.5
Amps (LRA), Comp. 1
79/79
88/88
88/88
88/88
44
44
No.
1
1
1
1
1
1
Volts
208/230
208/230
208/230
208/230
460
460
Phase
1
1
1
1
1
1
HP
1/3
1/3
1/3
1/3
1/3
1/3
Amps (FLA, each)
1.5/1.5
1.5/1.5
1.5/1.5
1.5/1.5
1
1
Amps (LRA, each)
3/3
3/3
3/3
3/3
1.9
1.9
No.
1
1
1
1
1
1
Volts
208/230
208/230
208/230
208/230
460
460
Phase
1
1
3
3
1
3
HP
1/2
1/2
1/2
3/4
1/2
1/2
Amps (FLA, each)
2.7/2.7
2.7/2.7
2.2/2.2
3.2/3.2
1.5
1.1
Amps (LRA, each)
6.5/6.5
6.5/6.5
10.6/10.6
16.8/16.8
3.6
5.3
39
Evaporator Fan
Condenser Motor
Compressor Motor
Unit Information
ELECTRICAL DATA – RJNL- SERIES
40
A042DM
A042JK
A048CK
A048CL A048CM A048DK
Unit Operating
Voltage Range
414-506
187-253
187-253
187-253
187-253
414-506
Volts
460
208/230
208/230
208/230
208/230
460
Minimum Circuit
Ampacity
11
28/28
23/23
22/22
23/23
11
Minimum Overcurrent
Protection Device Size
15
35/35
30/30
25/25
30/30
15
Maximum Overcurrent
Protection Device Size
15
45/45
35/35
35/35
35/35
15
No.
1
1
1
1
1
1
Volts
460
208/230
208/230
208/230
208/230
460
Phase
3
1
3
3
3
3
RPM
3450
3450
3450
3450
3450
3450
HP, Compressor 1
3
3
3 1/2
3 1/2
3 1/2
3 1/2
Amps (RLA), Comp. 1
6
17.9/17.9
13.7/13.7
13.7/13.7
13.7/13.7
6.2
Amps (LRA), Comp. 1
44
112/112
83.1/83.1
83.1/83.1
83.1/83.1
41
No.
1
1
1
1
1
1
Volts
460
208/230
208/230
208/230
208/230
460
Phase
1
1
1
1
1
1
HP
1/3
1/3
1/3
1/3
1/3
1/3
Amps (FLA, each)
1
1.5/1.5
1.5/1.5
1.5/1.5
1.5/1.5
1
Amps (LRA, each)
1.9
3/3
3/3
3/3
3/3
1.9
No.
1
1
1
1
1
1
Volts
460
208/230
208/230
208/230
208/230
460
Phase
3
1
1
3
3
1
HP
3/4
1/2
1/2
1/2
3/4
1/2
Amps (FLA, each)
1.6
2.7/2.7
2.7/2.7
2.2/2.2
3.2/3.2
1.5
Amps (LRA, each)
8.4
6.5/6.5
6.5/6.5
10.6/10.6
16.8/16.8
3.6
Evaporator Fan
Condenser Motor
Compressor Motor
Unit Information
ELECTRICAL DATA – RJNL- SERIES
A048DL A048DM
A048JK
A060CK
A060CL
A060CM
Unit Operating
Voltage Range
414-506
414-506
187-253
187-253
187-253
187-253
Volts
460
460
208/230
208/230
208/230
208/230
Minimum Circuit
Ampacity
11
11
33/33
25/25
26/26
26/26
Minimum Overcurrent
Protection Device Size
15
15
40/40
30/30
30/30
30/30
Maximum Overcurrent
Protection Device Size
15
15
50/50
40/40
40/40
40/40
No.
1
1
1
1
1
1
Volts
460
460
208/230
208/230
208/230
208/230
Phase
3
3
1
3
3
3
RPM
3450
3450
3450
3450
3450
3450
HP, Compressor 1
3 1/2
3 1/2
3 1/2
5
5
5
Amps (RLA), Comp. 1
6.2
6.2
21.8/21.8
16/16
16/16
16/16
Amps (LRA), Comp. 1
41
41
117/117
110/110
110/110
110/110
No.
1
1
1
1
1
1
Volts
460
460
208/230
208/230
208/230
208/230
Phase
1
1
1
1
1
1
HP
1/3
1/3
1/3
1/3
1/3
1/3
Amps (FLA, each)
1
1
1.5/1.5
2.2/2.2
2.2/2.2
2.2/2.2
Amps (LRA, each)
1.9
1.9
3/3
4.7/4.7
4.7/4.7
4.7/4.7
No.
1
1
1
1
1
1
Volts
460
460
208/230
208/230
208/230
208/230
Phase
3
3
1
1
3
3
HP
1/2
3/4
1/2
1
3/4
1
Amps (FLA, each)
1.1
1.6
2.7/2.7
7.6/7.6
3.2/3.2
3.8/3.8
Amps (LRA, each)
5.3
8.4
6.5/6.5
0/0
16.8/16.8
24/24
41
Evaporator Fan
Condenser Motor
Compressor Motor
Unit Information
ELECTRICAL DATA – RJNL- SERIES
42
A060DK
A060DL
A060DM
A060JK
A072CL
A072CM
A072DL
Unit Operating
Voltage Range
414-506
414-506
414-506
187-253
187-253
187-253
414-506
Volts
460
460
460
208/230
208/230
208/230
460
Minimum Circuit
Ampacity
13
13
14
39/39
34/34
34/34
17
Minimum Overcurrent
Protection Device Size
15
15
20
45/45
40/40
40/40
20
Maximum Overcurrent
Protection Device Size
20
20
20
60/60
50/50
50/50
25
No.
1
1
1
1
1
1
1
Volts
460
460
460
208/230
208/230
208/230
460
Phase
3
3
3
1
3
3
3
RPM
3450
3450
3450
3450
3450
3450
3450
HP, Compressor 1
5
5
5
5
7 1/2
7 1/2
7 1/2
Amps (RLA), Comp. 1
7.8
7.8
7.8
26.4/26.4
21.2/21.2 21.2/21.2
Amps (LRA), Comp. 1
52
52
52
134/134
123/123
123/123
62
No.
1
1
1
1
1
1
1
Volts
460
460
460
208/230
208/230
208/230
460
Phase
1
1
1
1
1
1
1
HP
1/3
1/3
1/3
1/3
1/3
1/3
1/3
Amps (FLA, each)
1
1
1
2.2/2.2
1.8/1.8
1.8/1.8
1
Amps (LRA, each)
2.4
2.4
2.4
4.7/4.7
3.3/3.3
3.3/3.3
2.2
No.
1
1
1
1
1
1
1
Volts
460
460
460
208/230
208/230
208/230
460
Phase
1
3
3
1
3
3
3
HP
1
3/4
1
1
1 1/2
1 1/2
1 1/2
Amps (FLA, each)
1.7
1.6
1.9
2.8/2.8
5.8/5.8
5.8/5.8
2.8
Amps (LRA, each)
0
8.4
12
0/0
34/34
34/34
17
10.9
ELECTRICAL DATA – RJNL- SERIES
Evaporator Fan
Condenser Motor
Compressor Motor
Unit Information
A072DM A072YL
Unit Operating
Voltage Range
414-506
518-633
Volts
460
575
Minimum Circuit
Ampacity
17
14
Minimum Overcurrent
Protection Device Size
20
15
Maximum Overcurrent
Protection Device Size
25
20
No.
1
1
Volts
460
575
Phase
3
3
RPM
3450
3450
HP, Compressor 1
7 1/2
7 1/2
Amps (RLA), Comp. 1
10.9
8.3
Amps (LRA), Comp. 1
62
50
No.
1
1
Volts
460
575
Phase
1
1
HP
1/3
1/3
Amps (FLA, each)
1
0.8
Amps (LRA, each)
2.2
1.6
No.
1
1
Volts
460
575
Phase
3
3
HP
1 1/2
1 1/2
Amps (FLA, each)
2.8
2.3
Amps (LRA, each)
17
13
43
ELECTRICAL DATA – RJPL- SERIES
Compressor Motor
Unit Information
-A036CK -A036CL -A036CM -A036DK -A036DL -A036DM -A036JK
Unit Operating
Voltage Range
187-253
187-253
187-253
414-506
414-506
414-506
187-253
Minimum Circuit
Ampacity
17/17
18/18
18/18
10
10
10
24/24
Minimum Overcurrent
Protection Device Size
20/20
20/20
25/25
15
15
15
30/30
Maximum Overcurrent
Protection Device Size
25/25
25/25
25/25
15
15
15
40/40
No.
1
1
1
1
1
1
1
Volts
208/230
208/230
208/230
460
460
460
208/230
Phase
3
3
3
3
3
3
1
HP
2.5
2.5
2.5
2.5
2.5
2.5
2.5
RPM
3450
3450
3450
3450
3450
3450
3450
10.4/10.4
5.8
5.8
5.8
16.7/16.7
Evaporator Fan
Condenser Motor
Amps (RLA)
44
10.4/10.4 10.4/10.4
Amps (LRA)
88/88
88/88
88/88
38
38
38
79/79
No.
1
1
1
1
1
1
1
Volts
208/230
208/230
208/230
460
460
460
208/230
Phase
1
1
1
1
1
1
1
HP
1/3
1/3
1/3
1/3
1/3
1/3
1/3
Amps (FLA)
1.5
1.5
1.5
1
1
1
1.5
Amps (LRA)
3
3
3
1.9
1.9
1.9
3
No.
1
1
1
1
1
1
1
Volts
208/230
208/230
208/230
460
460
460
208/230
Phase
1
3
3
1
3
3
1
HP
1/2
1/2
3/4
1/2
1/2
3/4
1/2
Amps (FLA)
1.6
2.8
3.4
1.0
1.4
1.6
1.6
Amps (LRA)
0
10.6
16.8
0
5.3
8.4
0
ELECTRICAL DATA – RJPL- SERIES
Compressor Motor
Unit Information
-A042CK -A042CL -A042CM -A042DK -A042DL -A042DM -A042JK
Unit Operating
Voltage Range
187-253
187-253
187-253
414-506
414-506
414-506
187-253
Minimum Circuit
Ampacity
21/21
22/22
22/22
10
10
11
26/26
Minimum Overcurrent
Protection Device Size
25/25
25/25
30/30
15
15
15
35/35
Maximum Overcurrent
Protection Device Size
30/30
30/30
35/35
15
15
15
40/40
No.
1
1
1
1
1
1
1
Volts
208/230
208/230
208/230
460
460
460
208/230
Phase
3
3
3
3
3
3
1
HP
3
3
3
3
3
3
3
RPM
3450
3450
3450
3450
3450
3450
3450
13.5/13.5
6
6
6
17.9/17.9
Evaporator Fan
Condenser Motor
Amps (RLA)
13.5/13.5 13.5/13.5
Amps (LRA)
88/88
88/88
88/88
44
44
44
112/112
No.
1
1
1
1
1
1
1
Volts
208/230
208/230
208/230
460
460
460
208/230
Phase
1
1
1
1
1
1
1
HP
1/3
1/3
1/3
1/3
1/3
1/3
1/3
Amps (FLA)
1.5
1.5
1.5
1
1
1
1.5
Amps (LRA)
3
3
3
1.9
1.9
1.9
3
No.
1
1
1
1
1
1
1
Volts
208/230
208/230
208/230
460
460
460
208/230
Phase
1
3
3
1
3
3
1
HP
1/2
1/2
3/4
3/4
1/2
3/4
1/2
Amps (FLA)
1.9
2.8
3.4
1.2
1.4
1.6
1.9
Amps (LRA)
0
10.6
16.8
0
5.3
8.4
0
45
Evaporator Fan
Condenser Motor
Compressor Motor
Unit Information
ELECTRICAL DATA – RJPL- SERIES
46
-A048CK -A048CL -A048CM -A048DK -A048DL -A048DM
-A048JK
Unit Operating
Voltage Range
187-253
187-253
187-253
414-506
414-506
414-506
187-253
Minimum Circuit
Ampacity
21/21
22/22
23/23
10
11
11
31/31
Minimum Overcurrent
Protection Device Size
25/25
25/25
30/30
15
15
15
40/40
Maximum Overcurrent
Protection Device Size
30/30
35/35
35/35
15
15
15
50/50
No.
1
1
1
1
1
1
1
Volts
208/230
208/230
208/230
460
460
460
208/230
Phase
3
3
3
3
3
3
1
HP
3.5
3.5
3.5
3.5
3.5
3.5
3.5
RPM
3450
3450
3450
3450
3450
3450
3450
Amps (RLA)
13.7/13.7 13.7/13.7
13.7/13.7
6.2
6.2
6.2
21.8/21.8
Amps (LRA)
83.1/83.1 83.1/83.1
83.1/83.1
41
41
41
117/117
No.
1
1
1
1
1
1
1
Volts
208/230
208/230
208/230
460
460
460
208/230
Phase
1
1
1
1
1
1
1
HP
1/3
1/3
1/3
1/3
1/3
1/3
1/3
Amps (FLA)
1.5
1.5
1.5
1
1
1
1.5
Amps (LRA)
3
3
3
1.9
1.9
1.9
3
No.
1
1
1
1
1
1
1
Volts
208/230
208/230
208/230
460
460
460
208/230
Phase
1
3
3
1
3
3
1
HP
1/2
1/2
3/4
3/4
1/2
3/4
1/2
Amps (FLA)
1.9
2.8
3.4
1.2
1.4
1.6
1.9
Amps (LRA)
0
10.6
16.8
0
5.3
8.4
0
Evaporator Fan
Condenser Motor
Compressor Motor
Unit Information
ELECTRICAL DATA – RJPL- SERIES
-A060CK -A060CL -A060CM -A060DK -A060DL -A060DM
-A060JK
Unit Operating
Voltage Range
187-253
187-253
187-253
414-506
414-506
414-506
187-253
Minimum Circuit
Ampacity
25/25
26/26
26/26
13
13
13
39/39
Minimum Overcurrent
Protection Device Size
30/30
30/30
30/30
15
15
15
45/45
Maximum Overcurrent
Protection Device Size
40/40
40/40
40/40
20
20
20
60/60
No.
1
1
1
1
1
1
1
Volts
208/230
208/230
208/230
460
460
460
208/230
Phase
3
3
3
3
3
3
1
HP
5
5
5
5
5
5
5
RPM
3450
3450
3450
3450
3450
3450
3450
Amps (RLA)
16/16
16/16
16/16
7.8
7.8
7.8
26.4/26.4
Amps (LRA)
110/110
110/110
110/110
52
52
52
134/134
No.
1
1
1
1
1
1
1
Volts
208/230
208/230
208/230
460
460
460
208/230
Phase
1
1
1
1
1
1
1
HP
1/3
1/3
1/3
1/3
1/3
1/3
1/3
Amps (FLA)
2.2
2.2
2.2
1
1
1
2.2
Amps (LRA)
4.7
4.7
4.7
2.4
2.4
2.4
4.7
No.
1
1
1
1
1
1
1
Volts
208/230
208/230
208/230
460
460
460
208/230
Phase
1
3
3
1
3
3
1
HP
1
3/4
1
1
3/4
1
1
Amps (FLA)
2.8
3.4
3.8
1.7
1.6
1.9
2.8
Amps (LRA)
0
16.8
24
0
8.4
12
0
47
48
Low
Low
Low
Low
3.0
3.5
4.0
5.0
1750 / 2250
1400 / 1800
1225 / 1575
1050 / 1350
Manufacturer
Recommended
Airflow Range
(Min / Max) CFM
11x9
1
2 Speed
10x10
1/2
3 Speed
10x10
1/2
3 Speed
10x10
1/2
3 Speed
Blower Size/
Motor HP #
of Speeds
Motor Speed
From Factory
Low
Med
High
Low
Nominal
Cooling
Capacity
Tons
3.0
3.5
4.0
5.0
1750 / 2250
1400 / 1800
1225 / 1575
1050 / 1350
Manufacturer
Recommended
Airflow Range
(Min / Max) CFM
11x9
1
2 Speed
10x10
1/2
3 Speed
10x10
1/2
3 Speed
10x10
1/2
3 Speed
Blower Size/
Motor HP #
of Speeds
DIRECT-DRIVE BLOWER 230/460 AIRFLOW PERFORMANCE
Motor Speed
From Factory
Nominal
Cooling
Capacity
Tons
DIRECT-DRIVE BLOWER 208 AIRFLOW PERFORMANCE
High
Low
High
Med
Low
Motor
Speed
High
Low
High
Med
Low
Motor
Speed
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
0.10
1455
[687]
578
1601
[756]
659
1964
[927]
847
1974
[932]
490
2185
[1031]
675
0.10
1275
[602]
493
1397
[659]
561
1766
[833]
735
1974
[932]
490
2185
[1031]
675
0.20
1423
[627]
565
1561
[737]
636
1902
[898]
811
1935
[913]
505
2148
[1014]
685
0.20
1235
[583]
481
1344
[634]
537
1719
[811]
719
1935
[913]
505
2148
[1014]
685
0.40
1181
[557]
452
1297
[612]
508
1617
[763]
671
1860
[878]
545
2076
[980]
720
0.50
1132
[534]
431
1249
[589]
488
1550
[732]
639
1823
[860]
555
2040
[963]
735
0.60
1045
[493]
402
1147
[541]
454
1465
[691]
603
1788
[844]
575
2005
[946]
750
1753
[827]
600
1970
[930]
770
0.70
External Static Pressure-Inches W.C.
1719
[811]
605
1935
[913]
780
0.80
0.30
1388
[655]
549
1517
[716]
613
1839
[868]
780
1897
[895]
510
2112
[997]
700
0.40
1345
[635]
528
1466
[692]
589
1771
[836]
751
1860
[878]
545
2076
[980]
720
0.50
1289
[608]
502
1401
[661]
562
1693
[799]
721
1823
[860]
555
2040
[963]
735
0.60
1214
[573]
472
1317
[622]
529
1602
[756]
688
1788
[844]
575
2005
[946]
750
1753
[827]
600
1970
[930]
770
0.70
External Static Pressure-Inches W.C.
1719
[811]
605
1935
[913]
780
0.80
CFM [L/s] Air Delivery/Watts-230/460 VOLTS
0.30
1210
[571]
468
1319
[622]
522
1671
[789]
697
1897
[895]
510
2112
[997]
700
CFM [L/s] Air Delivery/Watts-208 VOLTS
1686
[796]
625
1900
[897]
805
0.90
1686
[796]
625
1900
[897]
805
0.90
1.00
1.00
INDOOR AIRFLOW PERFORMANCE FOR 3-5 TON PACKAGE HEAT PUMPS – RJNL
DIRECT DRIVE
Low (Tap 2)
Low (Tap 2)
Low (Tap 2)
Low (Tap 2)
3.0
3.5
4.0
5.0
1750 / 2250
1400 / 1800
1225 / 1575
1050 / 1350
Manufacturer
Nominal
Recommended
Cooling
Capacity Motor Speed Air-Flow Range
Tons
From Factory (Min / Max) CFM
High
Low
High
Low
High
Low
Low
10x10
1 HP [746]
2 Speed
(X-13 Motor) High
10x10
3/4 HP [559]
2 Speed
(X-13 Motor)
10x10
3/4 HP [559]
2 Speed
(X-13 Motor)
10x10
1/2 HP [373]
2 Speed
(X-13 Motor)
Blower Size/
Motor HP # Motor
of Speeds Speed
DIRECT-DRIVE BLOWER 208/230/460 AIRFLOW PERFORMANCE
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
0.10
1448
674
230
1618
712
299
1641
724
292
1735
755
340
1771
848
422
1954
914
547
1914
778
496
2185
846
675
0.20
1413
720
245
1577
755
315
1603
764
307
1704
796
360
1739
890
445
1908
949
565
1882
805
514
2148
871
685
CFM Air
CFM
AirDelivery/RPM/Watts-208/230/460
Delivery/RPM/Watts-208/230 Volts
Volts
External Static Pressure-Inches W.C.
0.30
0.40
0.50
0.60
0.70
0.80
1367
1325
1285
1242
1196
1106
771
818
862
907
953
1019
260
274
288
301
314
330
1516
1482
1443
1395
1359
1312
807
851
894
941
978
1019
332
350
364
380
391
402
1570
1534
1504
1468
1410
1359
806
852
895
933
985
1032
323
343
363
377
396
412
1674
1631
1598
1560
1527
1481
835
879
917
956
995
1044
378
396
411
427
443
464
1708
1670
1642
1607
1568
1511
925
963
996
1032
1076
1121
462
478
493
509
529
544
1878
1840
1797
1771
1692
1603
984
1016
1055
1083
1114
1133
585
601
619
634
634
605
1851
1817
1783
1753
1703
1688
835
861
894
926
959
988
533
544
565
584
604
618
2112
2076
2040
2005
1970
1935
895
920
950
984
1008
1042
700
720
735
750
770
780
1900
1061
805
0.90
1006
1091
350
1261
1061
414
1316
1076
430
1437
1084
479
1236
1161
460
1457
1154
550
1042
1137
392
1252
1132
446
1336
1133
482
1.00
INDOOR AIRFLOW PERFORMANCE FOR 3-5 TON PACKAGE HEAT PUMPS – RJPL
DIRECT DRIVE
49
50
—
—
—
—
315
340
380
420
465
500
—
—
—
—
625
655
685
730
755
790
0.1 [.02]
RPM WATTS
—
—
910
—
1350
—
875
930
1295
1310
830
910
1265
1290
800
870
1225
1245
830
1210
710
770
1165
685
940
1075
1100
1125
550
630
690
1005
1040
1080
525
570
650
970
985
1020
505
550
600
935
955
975
490
535
570
890
915
935
455
505
550
825
850
875
890
390
435
475
530
755
790
825
850
—
—
—
360
390
430
475
520
585
—
—
—
690
720
750
780
820
850
0.1 [.02]
RPM WATTS
740
810
865
935
—
—
—
—
1315
1335
1350
1365
—
—
—
—
685
745
815
890
960
—
—
1290
N
1030
1270
1315
1335
1350
1365
—
—
640
685
760
830
910
995
1060
1140
1235
1250
1270
1290
1315
1340
1355
1365
600
640
700
770
845
930
1010
1100
1190
1205
1230
1250
1270
1295
1315
1340
570
600
660
725
790
860
900
1050
1140
1160
1180
1205
1225
1250
1275
1300
530
560
630
680
735
800
880
965
1100
1115
1140
1160
1180
1205
1225
1255
490
520
580
635
695
740
835
900
1060
1070
1100
1115
1140
1155
1185
1205
470
500
560
590
645
710
790
865
1010
1030
1055
1075
1090
1115
1145
1170
455
470
500
565
600
660
750
810
975
995
1010
1035
1055
1080
1115
1130
435
455
480
530
570
625
690
760
920
945
970
990
1015
1035
1060
1090
415
435
465
500
530
600
640
715
880
895
920
945
970
990
1015
1045
395
420
450
480
500
555
600
665
835
855
875
895
920
945
970
1000
365
395
425
460
485
540
580
630
770
795
820
850
870
895
925
950
330
350
L
390
430
465
515
560
610
695
725
750
780
810
840
870
900
Factory sheave settngs are shown in bold print.
RPM RANGE 1090 - 1365
N (FIELD-SUPPLIED)
3/4
6.4 PITCH DIAMETER
ADJUSTABLE 4.0 - 5.0 PITCH DIAMETER
M
685
1300
650
1260
620
1215
580
1170
540
1115
490
1075
460
1040
440
1000
420
945
400
900
390
865
1.5 [.37]
RPM WATTS
375
1.1 [.27]
RPM WATTS
810
EXTERNAL STATIC PRESSURE - INCHES OF WATER
0.6 [.15]
0.7 [.17]
0.8 [.20]
0.9 [.22]
1.0 [.25]
RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS
340
0.5 [.12]
RPM WATTS
745
0.4 [.10]
RPM WATTS
—
—
0.3 [.07]
RPM WATTS
—
—
0.2 [.05]
RPM WATTS
RPM RANGE 1090 - 1365
N (FIELD-SUPPLIED)
3/4
6.4 PITCH DIAMETER
ADJUSTABLE 4.0 - 5.0 PITCH DIAMETER
4 TON
NOTE: Bold lines separate L, M and N drives respectively.
DRIVE PACKAGE
L
M
MOTOR H.P.
1/2 (3/4 - 575V)
3/4
BLOWER SHEAVE
6.9 PITCH DIAMETER
6.4 PITCH DIAMETER
MOTOR SHEAVE
ADJUSTABLE 2.8 - 3.8 PITCH DIAMETER
ADJUSTABLE 3.4 - 4.4 PITCH DIAMETER
TURNS OPEN
0
1
2
3
4
5
6
0
1
2
3
4
5
6
RPM
990 945 895 850 800 750 695 1270 1225 1170 1115 1065 1015 965
1200
[566]
1300
[614]
1400
[661]
1500
[708]
1600
[755]
1700
[802]
1800
[850]
1900
[897]
2000
[944]
AIR
FLOW
CFM
[L/s]
CAPACITY
4 TON HEAT PUMP (13 SEER)
VOLTAGE 208-230, 460 - 3 PHASE
DRIVE PACKAGE
L
M
MOTOR H.P.
1/2 (3/4 - 575V)
3/4
BLOWER SHEAVE
6.9 PITCH DIAMETER
6.4 PITCH DIAMETER
MOTOR SHEAVE
ADJUSTABLE 2.4 - 3.4 PITCH DIAMETER
ADJUSTABLE 3.4 - 4.4 PITCH DIAMETER
TURNS OPEN
0
1
2
3
4
5
6
0
1
2
3
4
5
6
RPM
935 875 830 780 730 680 625 1295 1230 1185 1135 1085 1000 955
Factory sheave settngs are shown in bold print.
1.4 [.35]
RPM WATTS
885
1365
840
1325
800
1280
780
1245
730
1200
680
750
1160
1185
640
1110
1135
605
1040
505
990
480
955
450
915
435
870
415
795
1.3 [.32]
RPM WATTS
820
1350
785
1295
740
1255
720
1220
660
1180
590
545
1010
470
975
445
935
430
890
400
850
385
L
365
730
1.2 [.30]
RPM WATTS
760
1325
725
1280
685
1230
645
1195
615
1150
575
630
1110
1135
540
1070
1090
500
990
440
955
415
915
400
875
370
830
350
770
330
700
N
710
1305
675
1260
645
1220
590
1165
565
1125
495
M
660
1285
630
1250
600
1200
560
1145
520
1100
475
530
1060
1085
450
1010
1040
450
630
1270
600
1230
540
1180
540
1115
485
1080
430
405
430
610
1255
560
1210
530
1160
500
1100
465
1065
435
450
1015
1040
410
970
990
390
590
1235
540
1190
510
1140
470
1080
445
1040
410
990
390
960
375
975
955
935
920
410
390
375
360
935
915
895
875
385
365
345
330
1.5 [.37]
RPM WATTS
890
875
850
830
1.4 [.35]
RPM WATTS
365
340
325
315
1.3 [.32]
RPM WATTS
850
830
805
780
1.2 [.30]
RPM WATTS
345
325
310
300
1.1 [.27]
RPM WATTS
800
780
750
730
EXTERNAL STATIC PRESSURE - INCHES OF WATER
0.6 [.15]
0.7 [.17]
0.8 [.20]
0.9 [.22]
1.0 [.25]
RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS
330
315
295
290
0.5 [.12]
RPM WATTS
735
710
680
665
0.4 [.10]
RPM WATTS
315
300
275
—
0.3 [.07]
RPM WATTS
3-3.5 TON
670
640
625
—
0.2 [.05]
RPM WATTS
NOTE: Bold lines separate L, M and N drives respectively.
900
[425]
1000
[472]
1100
[519]
1200
[566]
1300
[614]
1400
[661]
1500
[708]
1600
[755]
1700
[802]
1800
[850]
AIR
FLOW
CFM
[L/s]
CAPACITY
3 & 3.5 TON HEAT PUMP (13 SEER)
VOLTAGE 208-230, 460 - 3 PHASE
INDOOR AIRFLOW PERFORMANCE – RJNL
—
—
—
—
455
485
550
615
680
755
825
—
—
—
780
800
830
860
895
940
970
1015
975
945
915
880
850
815
795
780
—
—
895
915
945
970
1005
1030
1065
1100
490
540
590
655
705
780
830
925
870
895
930
955
995
1015
1040
530
605
655
735
795
880
870
840
815
840
425
405
370
0
1095
1
1040
1145
1100
1060
1040
1015
995
965
940
915
895
875
2
995
3
940
4
890
5
835
1055
965
880
820
730
675
675
570
510
440
425
0.5 [.12]
RPM WATTS
“L”
3/4
6.4 PITCH DIAMETER
2.8-3.8 PITCH DIAMETER - ADJ.
Factory sheave settings are shown in bold.
TURNS OPEN
RPM
DRIVE PACKAGE
MOTOR H.P.
BLOWER SHEAVE
MOTOR SHEAVE
1005
910
830
760
700
640
540
530
470
415
385
0.4 [.10]
RPM WATTS
450
805
795
780
0.3 [.07]
RPM WATTS
470
390
—
—
0.2 [.05]
RPM WATTS
“L”
—
0.1 [.02]
RPM WATTS
NOTE: L-Drive left of bold line, M-Drive right of bold line.
1400
[661]
1500
[708]
1600
[755]
1700
[802]
1800
[850]
1900
[897]
2000
[944]
2100
[991]
2200
[1038]
2300
[1085]
2400
[1133]
AIR
FLOW
CFM
[L/s]
CAPACITY5 TON - 13 SEER
VOLTAGE
208-230, 460 - 3 PHASE
6
780
1175
1150
1120
1090
1055
1035
1010
990
965
945
930
1225
1180
1155
1130
1105
1070
1055
1035
1015
995
970
1
1360
1140
1050
980
910
830
775
710
640
600
540
490
1175
1095
1020
950
875
810
760
680
640
595
540
1300
1265
1240
1210
1180
1160
1140
1120
1105
1080
1065
1210
1125
1055
995
910
850
785
725
680
615
570
2
1305
3
1250
4
1195
“M”
1
6.4 PITCH DIAMETER
3.4-4.4 PITCH DIAMETER - ADJ.
1260
1225
1195
1170
1145
1120
1100
1075
1060
1045
1030
EXTERNAL STATIC PRESSURE–INCHES OF WATER
0.7 [.17]
0.8 [.20]
0.9 [.22]
RPM WATTS RPM WATTS RPM WATTS
0
1405
1085
1025
940
870
790
720
660
605
560
500
460
0.6 [.15]
RPM WATTS
5 TON
5
1145
1340
1310
1275
1250
1225
1200
1175
1160
1145
1135
1105
1370
1350
1320
1290
1260
1245
1225
1200
1180
1165
1150
1315
1230
1140
1060
980
915
850
790
730
675
615
1.10 [.27]
RPM WATTS
6
1095
1255
1175
1100
1020
950
890
810
755
705
650
595
1.0 [.25]
RPM WATTS
1400
1375
1360
1335
1320
1290
1260
1245
1225
1215
1195
1375
1260
1180
1100
1035
960
880
815
750
700
645
1.20 [.30]
RPM WATTS
—
1405
1385
1370
1350
1335
1320
1300
1275
1255
1235
—
1320
1225
1150
1075
1000
930
855
790
735
660
1.30 [.32]
RPM WATTS
—
—
—
1400
1385
1375
1365
1355
1340
1320
1300
—
—
—
1200
1120
1050
985
905
840
775
705
—
—
—
—
—
1405
1390
1375
1365
1355
1340
—
—
—
—
—
1100
1020
940
880
805
745
1.50 [.37]
RPM WATTS
“M”
1.40 [.35]
RPM WATTS
INDOOR AIRFLOW PERFORMANCE – RJNL
51
52
917
950
985
1020
1057
1096
2500 [1180]
2600 [1227]
2700 [1274]
2800 [1321]
2900 [1368]
1477
1345
1224
1112
1009
917
834
1125
1088
1052
1017
983
951
920
873
1536
1401
1276
1160
1055
959
1154
1118
1083
1049
1016
985
955
914
1597
1458
1330
1211
1103
1004
990
1183
1148
1114
1081
1049
1019
900
849
5
1211
1177
1144
1112
1081
1726
1582
1446
1321
1206
1100
1004
1
6
1240
1206
1174
1143
1113
1085
1058
1381
0
1795
1647
1508
1380
1261
1152
1053
1
1326
1267
1235
1204
1174
1145
1118
1091
0.06
[.01]
0.04
[.01]
0.08
[.02]
0.08
[.02]
0.08
[.02]
0.05
[.01]
0.03
[.01]
0.08
[.02]
0.08
[.02]
0.07
[.02]
Wet Coil
Downflow
] Designates Metric Conversions
Concentric Grill RXRN-FA65 or RXRN-FA75 &
Transition RXMC-CC04
Horizontal Economizer RA Damper Open
Downflow Economizer RA Damper Open
2000
[944]
1900
[897]
CFM
[L/s]
[
1866
1715
1573
1441
1319
1207
1104
1272
2
1295
1263
1233
1204
1176
1150
1125
1220
3
4
2016
1858
1709
1571
1442
1323
1214
1163
1322
1291
1262
1234
1207
1182
1158
1.5 [1118.5]
AK66
1VP-50
M
1940
1785
1640
1505
1379
1264
1158
1108
5
—
1319
1291
1264
1238
1213
1190
—
1
6
1933
1781
1639
1508
1385
1273
1222
—
1346
1319
1293
1268
1245
1334
—
2011
1856
1711
1575
1450
0.09
[.02]
0.09
[.02]
0.09
[.02]
0.05
[.01]
0.07
[.02]
2100
[991]
0.09
[.02]
0.09
[.02]
0.10
[.02]
0.06
[.01]
0.10
[.02]
0.10
[.02]
0.12
[.03]
0.07
[.02]
0.10
[.02]
0.10
[.02]
0.13
[.03]
0.08
[.02]
0.10
[.02]
0.10
[.02]
0.15
[.04]
0.08
[.02]
0.11
[.03]
0.11
[.03]
0.17
[.04]
0.09
[.02]
0.11
[.03]
0.11
[.03]
0.19
[.05]
0.09
[.02]
0.11
[.03]
Resistance — Inches of Water [kPa]
0.08
0.08
0.09
0.10
0.10
[.02]
[.02]
[.02]
[.02]
[.02]
2400
[1133]
2700
[1274]
2300
[1085]
2600
[1227]
2200
[1038]
2500
[1180]
0.12
[.03]
0.12
[.03]
0.21
[.05]
0.10
[.02]
0.11
[.03]
2800
[1321]
0.12
[.03]
0.12
[.03]
0.23
[.06]
0.10
[.02]
0.12
[.03]
2900
1368]
Factory sheave settings are shown in bold type.
Do not set motor sheave below minimum or above maximum turns open shown.
Re-adjustment of sheave required to achieve rated airflow at ARI minimum External Static Pressure
Drive data shown is for horizontal airflow with dry coil. Add component resistance (below) to duct resistance to determine total External Static Pressure.
956
4
1660
1519
1387
1265
1153
1052
1024
COMPONENT AIRFLOW RESISTANCE — 6 TON [21.1kW]
NOTES: 1.
2.
3.
4.
1002
1103
RPM
1052
3
2
0
Turns Open
1
L
1.5 [1118.5]
AK66
1VP-44
Drive Package
Motor H.P. [W]
Blower Sheave
Motor Sheave
958
1051
1254
—
—
1347
1322
1298
1276
1398
—
—
1933
1784
1646
1517
1286
—
—
1375
1351
1328
1306
1465
—
—
2012
1861
1719
1587
—
—
—
1379
1357
1336
1317
1533
—
—
—
1939
1794
1659
1348
—
—
—
1407
1386
1366
—
—
—
2020
1872
1733
1605
1486
1377
1331
1315
1418
1312
1299
1282
1352
1250
1267
1249
1289
1190
1234
1215
1229
1133
1201
1181
1171
1078
1168
1147
1115
1026
1135
1113
1062
976
1101
1078
1012
929
1066
1043
964
885
1032
1007
919
842
997
971
876
803
962
935
835
766
926
899
797
731
890
862
1188
1277
1287
1300
1130
1216
1252
1266
1074
1157
1217
1232
1021
1101
1181
1198
971
1047
1146
1163
923
995
1128
1110
947
877
1092
1073
900
834
1057
1036
856
793
1.5 [.37]
W
RPM
1020
999
1.4 [.35]
W
RPM
815
755
1.3 [.32]
W
RPM
984
962
1.2 [.30]
W
RPM
776
720
1.1 [.27]
W
RPM
947
924
1.0 [.25]
W
RPM
740
687
External Static Pressure — Inches of Water [kPa]
0.7 [.17]
0.8 [.20]
0.9 [.22]
W
RPM
W
RPM
W
RPM
910
886
0.6 [.15]
W
RPM
706
656
0.5 [.12]
W
RPM
872
847
0.4 [.10]
W
RPM
—
—
0.3 [.07]
W
RPM
—
—
0.2 [.05]
W
RPM
NOTE: L-Drive left of bold line, M-Drive right of bold line.
885
2300 [1085]
2400 [1133]
762
—
—
854
2100 [991]
2200 [1038]
—
—
—
—
1900 [897]
0.1 [.02]
RPM
W
Model RJNL-A072
Voltage 208/230, 460, 575 — 3 Phase
2000 [944]
Air Flow
CFM [L/s]
AIRFLOW PERFORMANCE — 6 TON [21.1kW] — SIDEFLOW
INDOOR AIRFLOW PERFORMANCE – RJNL
No. of
Sequence
Steps
—
1
1
1
1
1
—
1
1
1
1
1
—
1
1
1
1
1
—
1
1
1
1
1
RXJJHeater Kit
Nominal kW
No Heat
A06J
A10J
A12J
A15J
A20J
No Heat
A06J
A10J
A12J
A15J
A20J
No Heat
A06J
A10J
A12J
A15J
A20J
No Heat
A06J
A10J
A12J
A15J
A20J
RJNLA036JK
RJNLA042JK
RJNLA048JK
RJNLA060JK
Unit
Model
Number
—
4.2/5.6
7.2/9.6
8.4/11.2
10.8/14.4
14.4/19.2
—
4.2/5.6
7.2/9.6
8.4/11.2
10.8/14.4
14.4/19.2
—
4.2/5.6
7.2/9.6
8.4/11.2
10.8/14.4
14.4/19.2
—
4.2/5.6
7.2/9.6
8.4/11.2
10.8/14.4
14.4/19.2
—
14.33/19.1
24.56/32.75
28.66/38.21
36.84/49.13
49.13/65.5
—
14.33/19.1
24.56/32.75
28.66/38.21
36.84/49.13
49.13/65.5
—
14.33/19.1
24.56/32.75
28.66/38.21
36.84/49.13
49.13/65.5
—
14.33/19.1
24.56/32.75
28.66/38.21
36.84/49.13
49.13/65.5
Rated Heater
Heater
kW @
KBTU/Hr @
208/240 V
208/240 V
Heater Kit
—
20.2/23.3
34.6/40
40.4/46.7
51.9/60
69.3/80
—
20.2/23.3
34.6/40
40.4/46.7
51.9/60
69.3/80
—
20.2/23.3
34.6/40
40.4/46.7
51.9/60
69.3/80
—
20.2/23.3
34.6/40
40.4/46.7
51.9/60
69.3/80
Heater
Amp. @
208/240 V
Heat Pump
39/39
65/69
83/89
90/98
104/114
126/139
33/33
59/63
77/83
84/92
98/108
120/133
28/28
54/58
72/78
79/87
93/103
115/128
45/60
70/80
90/90
90/100
110/110
150/150
40/50
60/70
80/80
90/90
100/100
125/125
35/45
60/60
80/80
80/80
100/100
125/125
45/60
70/80
90/100
100/110
125/125
150/150
40/50
70/70
90/90
100/100
110/110
150/150
35/45
60/60
80/80
90/90
110/110
150/150
Over Current
Unit Min. Ckt Protective Device Size
Ampacity @
208-240V
Min/Max
Min/Max
@ 208 V
@240 V
27/27
35/40
35/40
53/57
60/60
60/60
71/77
70/70
80/80
78/86
80/80
90/90
92/102
100/100
110/110
114/127
125/125
150/150
Single Power Supply For Both Unit And Heater Kit
—
26/30
44/50
51/59
65/75
87/100
—
26/30
44/50
51/59
65/75
87/100
—
26/30
44/50
51/59
65/75
87/100
—
26/30
44/50
51/59
65/75
87/100
Min. Ckt.
Ampacity
208/240V
—
30/30
45/50
60/60
70/80
90/100
—
30/30
45/50
60/60
70/80
90/100
—
30/30
45/50
60/60
70/80
90/100
—
30/30
45/50
60/60
70/80
90/100
Max. Fuse
Size
208/240V
Heater Kit
39/39
39/39
39/39
39/39
39/39
39/39
33/33
33/33
33/33
33/33
33/33
33/33
28/28
28/28
28/28
28/28
28/28
28/28
45/60
45/60
45/60
45/60
45/60
45/60
40/50
40/50
40/50
40/50
40/50
40/50
35/45
35/45
35/45
35/45
35/45
35/45
45/60
45/60
45/60
45/60
45/60
45/60
40/50
40/50
40/50
40/50
40/50
40/50
35/45
35/45
35/45
35/45
35/45
35/45
Over Current
Min. Circuit Protective Device Size
Ampacity
208/240V
Min/Max
Min/Max
@ 208 V
@ 240 V
27/27
35/40
35/40
27/27
35/40
35/40
27/27
35/40
35/40
27/27
35/40
35/40
27/27
35/40
35/40
27/27
35/40
35/40
Heat Pump
Separate Power Supply For Both Unit And Heater Kit
208-240 VOLT, THREE PHASE, 60 HZ, AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION
AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION – RJNL
53
54
No. of
Sequence
Steps
—
1
1
1
1
1
—
1
1
1
1
1
—
1
1
1
1
1
—
1
1
1
1
1
RXJJHeater Kit
Nominal kW
No Heat
A06C
A10C
A12C
A15C
A20C
No Heat
A06C
A10C
A12C
A15C
A20C
No Heat
A06C
A10C
A12C
A15C
A20C
No Heat
A06C
A10C
A12C
A15C
A20C
RJNLA036CK
RJNLA042CK
RJNLA048CK
RJNLA060CK
Unit
Model
Number
—
4.2/5.6
7.2/9.6
8.4/11.2
10.8/14.4
14.4/19.2
—
4.2/5.6
7.2/9.6
8.4/11.2
10.8/14.4
14.4/19.2
—
4.2/5.6
7.2/9.6
8.4/11.2
10.8/14.4
14.4/19.2
—
4.2/5.6
7.2/9.6
8.4/11.2
10.8/14.4
14.4/19.2
—
14.33/19.1
24.56/32.75
28.66/38.21
36.84/49.13
49.13/65.5
—
14.33/19.1
24.56/32.75
28.66/38.21
36.84/49.13
49.13/65.5
—
14.33/19.1
24.56/32.75
28.66/38.21
36.84/49.13
49.13/65.5
—
14.33/19.1
24.56/32.75
28.66/38.21
36.84/49.13
49.13/65.5
Rated Heater
Heater
kW @
KBTU/Hr @
208/240 V
208/240 V
Heater Kit
—
11.7/13.5
20/23.1
23.4/27
30.1/34.7
40/46.3
—
11.7/13.5
20/23.1
23.4/27
30.1/34.7
40/46.3
—
11.7/13.5
20/23.1
23.4/27
30.1/34.7
40/46.3
—
11.7/13.5
20/23.1
23.4/27
30.1/34.7
40/46.3
Heater
Amp. @
208-240 V
Heat Pump
25/25
40/42
50/54
55/59
63/69
75/83
23/23
38/40
48/52
53/57
61/67
73/81
23/23
38/40
48/52
53/57
61/67
73/81
30/40
50/50
60/60
70/70
70/70
90/90
30/35
40/45
50/50
60/60
60/60
80/80
30/35
40/45
50/50
60/60
60/60
80/80
30/40
50/50
70/70
70/70
80/80
100/100
30/35
40/45
60/60
60/60
70/70
90/90
30/35
40/45
60/60
60/60
70/70
80/80
Over Current
Unit Min. Ckt Protective Device Size
Ampacity @
208-240V
Min/Max
Min/Max
@ 208 V
@240 V
19/19
25/25
25/25
34/36
35/35
40/40
44/48
45/45
50/50
49/53
50/50
60/60
57/63
60/60
70/70
69/77
70/70
80/80
Single Power Supply For Both Unit And Heater Kit
—
15/17
25/29
30/34
38/44
50/58
—
15/17
25/29
30/34
38/44
50/58
—
15/17
25/29
30/34
38/44
50/58
—
15/17
25/29
30/34
38/44
50/58
Min. Ckt.
Ampacity
208/240V
—
15/20
25/30
30/35
40/45
50/60
—
15/20
25/30
30/35
40/45
50/60
—
15/20
25/30
30/35
40/45
50/60
—
15/20
25/30
30/35
40/45
50/60
Max. Fuse
Size
208/240V
Heater Kit
25/25
25/25
25/25
25/25
25/25
25/25
23/23
23/23
23/23
23/23
23/23
23/23
23/23
23/23
23/23
23/23
23/23
23/23
30/40
30/40
30/40
30/40
30/40
30/40
30/35
30/35
30/35
30/35
30/35
30/35
30/35
30/35
30/35
30/35
30/35
30/35
30/40
30/40
30/40
30/40
30/40
30/40
30/35
30/35
30/35
30/35
30/35
30/35
30/35
30/35
30/35
30/35
30/35
30/35
Over Current
Min. Circuit Protective Device Size
Ampacity
208/240V
Min/Max
Min/Max
@ 208 V
@ 240 V
19/19
25/25
25/25
19/19
25/25
25/25
19/19
25/25
25/25
19/19
25/25
25/25
19/19
25/25
25/25
19/19
25/25
25/25
Heat Pump
Separate Power Supply For Both Unit And Heater Kit
208-240 VOLT, THREE PHASE, 60 HZ, AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION
AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION – RJNL
No. of
Sequence
Steps
—
1
1
1
1
1
—
1
1
1
1
1
—
1
1
1
1
1
—
1
1
1
1
1
—
1
1
1
RXJJHeater Kit
Nominal kW
No Heat
A06C
A10C
A12C
A15C
A20C
No Heat
A06C
A10C
A12C
A15C
A20C
No Heat
A06C
A10C
A12C
A15C
A20C
No Heat
A06C
A10C
A12C
A15C
A20C
No Heat
A15C
A20C
A24C
RJNLA036CL
RJNLA042CL
RJNLA048CL
RJNLA060CL
A072CL
Unit
Model
Number
—
10.8/14.4
14.4/19.2
18/24
—
4.2/5.6
7.2/9.6
8.4/11.2
10.8/14.4
14.4/19.2
—
4.2/5.6
7.2/9.6
8.4/11.2
10.8/14.4
14.4/19.2
—
4.2/5.6
7.2/9.6
8.4/11.2
10.8/14.4
14.4/19.2
—
4.2/5.6
7.2/9.6
8.4/11.2
10.8/14.4
14.4/19.2
—
36.84/49.13
49.13/65.5
61.41/81.88
—
14.33/19.1
24.56/32.75
28.66/38.21
36.84/49.13
49.13/65.5
—
14.33/19.1
24.56/32.75
28.66/38.21
36.84/49.13
49.13/65.5
—
14.33/19.1
24.56/32.75
28.66/38.21
36.84/49.13
49.13/65.5
—
14.33/19.1
24.56/32.75
28.66/38.21
36.84/49.13
49.13/65.5
Rated Heater
Heater
kW @
KBTU/Hr @
208/240 V
208/240 V
Heater Kit
—
30.1/34.7
40/46.3
50/57.7
—
11.7/13.5
20/23.1
23.4/27
30.1/34.7
40/46.3
—
11.7/13.5
20/23.1
23.4/27
30.1/34.7
40/46.3
—
11.7/13.5
20/23.1
23.4/27
30.1/34.7
40/46.3
—
11.7/13.5
20/23.1
23.4/27
30.1/34.7
40/46.3
Heater
Amp. @
208/240 V
Heat Pump
34/34
72/78
84/92
97/107
26/26
41/43
51/55
56/60
64/70
76/84
22/22
37/39
47/51
52/56
60/66
72/80
22/22
37/39
47/51
52/56
60/66
72/80
40/50
80/80
90/90
100/100
30/40
45/50
60/60
60/60
70/70
80/80
25/35
40/45
50/50
60/60
60/60
80/80
25/30
40/45
50/50
60/60
60/60
80/80
40/50
80/80
100/100
110/110
30/40
45/50
60/60
70/70
80/80
90/90
25/35
40/45
60/60
60/60
70/70
80/80
25/30
40/45
60/60
60/60
70/70
80/80
Over Current
Unit Min. Ckt Protective Device Size
Ampacity @
208-240V
Min/Max
Min/Max
@ 280 V @ 240 V
18/18
20/25
20/25
33/35
35/35
35/40
43/47
45/45
50/50
48/52
50/50
60/60
56/62
60/60
70/70
68/76
70/70
80/80
Single Power Supply For Both Unit And Heater Kit
—
38/44
50/58
63/73
—
15/17
25/29
30/34
38/44
50/58
—
15/17
25/29
30/34
38/44
50/58
—
15/17
25/29
30/34
38/44
50/58
—
15/17
25/29
30/34
38/44
50/58
Min. Ckt.
Ampacity
208/240V
—
40/45
50/60
70/80
—
15/20
25/30
30/35
40/45
50/60
—
15/20
25/30
30/35
40/45
50/60
—
15/20
25/30
30/35
40/45
50/60
—
15/20
25/30
30/35
40/45
50/60
Max. Fuse
Size
208/240V
Heater Kit
34/34
34/34
34/34
34/34
26/26
26/26
26/26
26/26
26/26
26/26
22/22
22/22
22/22
22/22
22/22
22/22
22/22
22/22
22/22
22/22
22/22
22/22
40/50
40/50
40/50
40/50
30/40
30/40
30/40
30/40
30/40
30/40
25/35
25/35
25/35
25/35
25/35
25/35
25/30
25/30
25/30
25/30
25/30
25/30
40/50
40/50
40/50
40/50
30/40
30/40
30/40
30/40
30/40
30/40
25/35
25/35
25/35
25/35
25/35
25/35
25/30
25/30
25/30
25/30
25/30
25/30
Over Current
Min. Circuit Protective Device Size
Ampacity
208/240V
Min/Max
Min/Max
@ 208 V @ 240 V
18/18
20/25
20/25
18/18
20/25
20/25
18/18
20/25
20/25
18/18
20/25
20/25
18/18
20/25
20/25
18/18
20/25
20/25
Heat Pump
Separate Power Supply For Both Unit And Heater Kit
208/240 VOLT, THREE PHASE, 60 HZ, AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION
AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION – RJNL
55
56
No. of
Sequence
Steps
—
1
1
1
1
1
—
1
1
1
1
1
—
1
1
1
1
1
—
1
1
1
1
1
—
1
1
1
RXJJHeater Kit
Nominal kW
No Heat
A06C
A10C
A12C
A15C
A20C
No Heat
A06C
A10C
A12C
A15C
A20C
No Heat
A06C
A10C
A12C
A15C
A20C
No Heat
A06C
A10C
A12C
A15C
A20C
No Heat
A15C
A20C
A24C
RJNLA036CM
RJNLA042CM
RJNLA048CM
RJNLA060CM
A072CM
Unit
Model
Number
—
10.8/14.4
14.4/19.2
18/24
—
4.2/5.6
7.2/9.6
8.4/11.2
10.8/14.4
14.4/19.2
—
4.2/5.6
7.2/9.6
8.4/11.2
10.8/14.4
14.4/19.2
—
4.2/5.6
7.2/9.6
8.4/11.2
10.8/14.4
14.4/19.2
—
4.2/5.6
7.2/9.6
8.4/11.2
10.8/14.4
14.4/19.2
—
36.84/49.13
49.13/65.5
61.41/81.88
—
14.33/19.1
24.56/32.75
28.66/38.21
36.84/49.13
49.13/65.5
—
14.33/19.1
24.56/32.75
28.66/38.21
36.84/49.13
49.13/65.5
—
14.33/19.1
24.56/32.75
28.66/38.21
36.84/49.13
49.13/65.5
—
14.33/19.1
24.56/32.75
28.66/38.21
36.84/49.13
49.13/65.5
Heater
Rated Heater
KBTU/Hr @
kW @
208/240 V
208/240 V
Heater Kit
—
30.1/34.7
40/46.3
50/57.7
—
11.7/13.5
20/23.1
23.4/27
30.1/34.7
40/46.3
—
11.7/13.5
20/23.1
23.4/27
30.1/34.7
40/46.3
—
11.7/13.5
20/23.1
23.4/27
30.1/34.7
40/46.3
—
11.7/13.5
20/23.1
23.4/27
30.1/34.7
40/46.3
Heater
Amp. @
208/240 V
Heat Pump
34/34
72/78
84/92
97/107
26/26
41/43
51/55
56/60
64/70
76/84
23/23
38/40
48/52
53/57
61/67
73/81
22/22
37/39
47/51
52/56
60/66
72/80
40/50
80/80
90/90
100/100
30/40
45/50
60/60
60/60
70/70
80/80
30/35
40/45
50/50
60/60
70/70
80/80
30/35
40/45
50/50
60/60
70/70
80/80
40/50
80/80
100/100
110/110
30/40
45/50
60/60
70/70
80/80
90/90
30/35
40/45
60/60
60/60
70/70
90/90
30/35
40/45
60/60
60/60
70/70
90/90
Over Current
Unit Min. Ckt Protective Device Size
Ampacity @
208-240 V
Min/Max
Min/Max
@ 208 V @ 240 V
19/19
25/25
25/25
34/36
35/35
40/40
44/48
45/45
50/50
49/53
50/50
60/60
57/63
60/60
70/70
69/77
70/70
80/80
Single Power Supply For Both Unit And Heater Kit
—
38/44
50/58
63/73
—
15/17
25/29
30/34
38/44
50/58
—
15/17
25/29
30/34
38/44
50/58
—
15/17
25/29
30/34
38/44
50/58
—
15/17
25/29
30/34
38/44
50/58
Min. Ckt.
Ampacity
208/240V
—
40/45
50/60
70/80
—
15/20
25/30
30/35
40/45
50/60
—
15/20
25/30
30/35
40/45
50/60
—
15/20
25/30
30/35
40/45
50/60
—
15/20
25/30
30/35
40/45
50/60
Max. Fuse
Size
208/240V
Heater Kit
34/34
34/34
34/34
34/34
26/26
26/26
26/26
26/26
26/26
26/26
23/23
23/23
23/23
23/23
23/23
23/23
22/22
22/22
22/22
22/22
22/22
22/22
40/50
40/50
40/50
40/50
30/40
30/40
30/40
30/40
30/40
30/40
30/35
30/35
30/35
30/35
30/35
30/35
30/35
30/35
30/35
30/35
30/35
30/35
40/50
40/50
40/50
40/50
30/40
30/40
30/40
30/40
30/40
30/40
30/35
30/35
30/35
30/35
30/35
30/35
30/35
30/35
30/35
30/35
30/35
30/35
Over Current
Min. Circuit Protective Device Size
Ampacity
208/240V
Min/Max
Min/Max
@ 208 V @ 240 V
19/19
25/25
25/25
19/19
25/25
25/25
19/19
25/25
25/25
19/19
25/25
25/25
19/19
25/25
25/25
19/19
25/25
25/25
Heat Pump
Separate Power Supply For Both Unit And Heater Kit
208/240 VOLT, THREE PHASE, 60 HZ, AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION
AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION – RJNL
No. of
Sequence
Steps
—
1
1
1
1
1
—
1
1
1
1
1
—
1
1
1
1
1
—
1
1
1
1
1
RXJJHeater Kit
Nominal kW
No Heat
A06D
A10D
A12D
A15D
A20D
No Heat
A06D
A10D
A12D
A15D
A20D
No Heat
A06D
A10D
A12D
A15D
A20D
No Heat
A06D
A10D
A12D
A15D
A20D
RJNLA036DK
RJNLA042DK
RJNLA048DK
RJNLA060DK
Unit
Model
Number
—
5.6
9.6
11.2
14.4
19.2
—
5.6
9.6
11.2
14.4
19.2
—
5.6
9.6
11.2
14.4
19.2
—
5.6
9.6
11.2
14.4
19.2
—
19.1
32.75
38.21
49.13
65.5
—
19.1
32.75
38.21
49.13
65.5
—
19.1
32.75
38.21
49.13
65.5
—
19.1
32.75
38.21
49.13
65.5
Heater
Rated Heater
KBTU/Hr @
kW @
480 V
480 V
Heater Kit
—
6.7
11.6
13.5
17.4
23.3
—
6.7
11.6
13.5
17.4
23.3
—
6.7
11.6
13.5
17.4
23.3
—
6.7
11.6
13.5
17.4
23.3
Heater
Amp. @
480 V
Heat Pump
13
22
28
30
35
43
11
20
26
28
33
41
11
20
26
28
33
41
15/20
25/25
30/30
30/30
35/35
45/45
15/15
20/20
30/30
30/30
35/35
40/40
15/15
20/20
30/30
30/30
35/35
40/40
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Over Current
Unit Min. Ckt Protective Device Size
Ampacity @
480 V
Min/Max
Min/Max
@ 480 V @ 480 V
11
15/15
—
20
20/20
—
26
25/25
—
28
30/30
—
33
35/35
—
41
40/40
—
Single Power Supply For Both Unit And Heater Kit
—
9
15
17
22
30
—
9
15
17
22
30
—
9
15
17
22
30
—
9
15
17
22
30
Min. Ckt.
Ampacity
480V
—
15
15
20
25
30
—
15
15
20
25
30
—
15
15
20
25
30
—
15
15
20
25
30
Max. Fuse
Size
480V
Heater Kit
13
13/0
13/0
13/0
13/0
13/0
11
11/0
11/0
11/0
11/0
11/0
11
11/0
11/0
11/0
11/0
11/0
15/20
15/20
15/20
15/20
15/20
15/20
15/15
15/15
15/15
15/15
15/15
15/15
15/15
15/15
15/15
15/15
15/15
15/15
—
0/0
0/0
0/0
0/0
0/0
—
0/0
0/0
0/0
0/0
0/0
—
0/0
0/0
0/0
0/0
0/0
Over Current
Min. Circuit Protective Device Size
Ampacity
480V
Min/Max
Min/Max
@ 480 V @ 480 V
11
15/15
—
11/0
15/15
0/0
11/0
15/15
0/0
11/0
15/15
0/0
11/0
15/15
0/0
11/0
15/15
0/0
Heat Pump
Separate Power Supply For Both Unit And Heater Kit
480 VOLT, THREE PHASE, 60 HZ, AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION
AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION – RJNL
57
58
No. of
Sequence
Steps
—
1
1
1
1
1
—
1
1
1
1
1
—
1
1
1
1
1
—
1
1
1
1
1
—
1
1
1
RXJJHeater Kit
Nominal kW
No Heat
A06D
A10D
A12D
A15D
A20D
No Heat
A06D
A10D
A12D
A15D
A20D
No Heat
A06D
A10D
A12D
A15D
A20D
No Heat
A06D
A10D
A12D
A15D
A20D
No Heat
A15C
A20C
A24C
RJNLA036DL
RJNLA042DL
RJNLA048DL
RJNLA060DL
RJNLA072DL
Unit
Model
Number
—
14.4
19.2
24
—
5.6
9.6
11.2
14.4
19.2
—
5.6
9.6
11.2
14.4
19.2
—
5.6
9.6
11.2
14.4
19.2
—
5.6
9.6
11.2
14.4
19.2
—
49.13
65.5
81.88
—
19.1
32.75
38.21
49.13
65.5
—
19.1
32.75
38.21
49.13
65.5
—
19.1
32.75
38.21
49.13
65.5
—
19.1
32.75
38.21
49.13
65.5
Rated Heater
Heater
kW @
KBTU/Hr @
480 V
480 V
Heater Kit
—
17.4
23.3
28.9
—
6.7
11.6
13.5
17.4
23.3
—
6.7
11.6
13.5
17.4
23.3
—
6.7
11.6
13.5
17.4
23.3
—
6.7
11.6
13.5
17.4
23.3
Heater
Amp. @
480 V
Heat Pump
17
39
47
54
13
22
28
30
35
43
11
20
26
28
33
41
10
19
25
27
32
40
20/25
40/40
50/50
60/60
15/20
25/25
30/30
30/30
35/35
45/45
15/15
20/20
30/30
30/30
35/35
40/40
15/15
20/20
30/30
30/30
35/35
40/40
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Over Current
Unit Min. Ckt Protective Device Size
Ampacity @
480 V
Min/Max
Min/Max
@ 480 V @ 480 V
10
15/15
—
19
20/20
—
25
25/25
—
27
30/30
—
32
35/35
—
40
40/40
—
Single Power Supply For Both Unit And Heater Kit
—
22
30
37
—
9
15
17
22
30
—
9
15
17
22
30
—
9
15
17
22
30
—
9
15
17
22
30
Min. Ckt.
Ampacity
480V
—
25
30
40
—
15
15
20
25
30
—
15
15
20
25
30
—
15
15
20
25
30
—
15
15
20
25
30
Max. Fuse
Size
480V
Heater Kit
17
17/0
17/0
17/0
13
13/0
13/0
13/0
13/0
13/0
11
11/0
11/0
11/0
11/0
11/0
10
10/0
10/0
10/0
10/0
10/0
20/25
20/25
20/25
20/25
15/20
15/20
15/20
15/20
15/20
15/20
15/15
15/15
15/15
15/15
15/15
15/15
15/15
15/15
15/15
15/15
15/15
15/15
—
0/0
0/0
0/0
—
0/0
0/0
0/0
0/0
0/0
—
0/0
0/0
0/0
0/0
0/0
—
0/0
0/0
0/0
0/0
0/0
Over Current
Min. Circuit Protective Device Size
Ampacity
480V
Min/Max
Min/Max
@ 480 V @ 480 V
10
15/15
—
10/0
15/15
0/0
10/0
15/15
0/0
10/0
15/15
0/0
10/0
15/15
0/0
10/0
15/15
0/0
Heat Pump
Separate Power Supply For Both Unit And Heater Kit
480 VOLT, THREE PHASE, 60 HZ, AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION
AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION – RJNL
No. of
Sequence
Steps
—
1
1
1
1
1
—
1
1
1
1
1
—
1
1
1
1
1
—
1
1
1
1
1
—
1
1
1
RXJJHeater Kit
Nominal kW
No Heat
A06D
A10D
A12D
A15D
A20D
No Heat
A06D
A10D
A12D
A15D
A20D
No Heat
A06D
A10D
A12D
A15D
A20D
No Heat
A06D
A10D
A12D
A15D
A20D
No Heat
A15D
A20D
A24D
RJNLA036DM
RJNLA042DM
RJNLA048DM
RJNLA060DM
RJNLA072DM
Unit
Model
Number
—
14.4
19.2
24
—
5.6
9.6
11.2
14.4
19.2
—
5.6
9.6
11.2
14.4
19.2
—
5.6
9.6
11.2
14.4
19.2
—
5.6
9.6
11.2
14.4
19.2
—
49.13
65.5
81.88
—
19.1
32.75
38.21
49.13
65.5
—
19.1
32.75
38.21
49.13
65.5
—
19.1
32.75
38.21
49.13
65.5
—
19.1
32.75
38.21
49.13
65.5
Heater
Rated Heater
KBTU/Hr @
kW @
480 V
480 V
Heater Kit
—
17.4
23.3
28.9
—
6.7
11.6
13.5
17.4
23.3
—
6.7
11.6
13.5
17.4
23.3
—
6.7
11.6
13.5
17.4
23.3
—
6.7
11.6
13.5
17.4
23.3
Heater
Amp. @
480 V
Heat Pump
17
39
47
54
14
23
29
31
36
44
11
20
26
28
33
41
11
20
26
28
33
41
20/25
40/40
50/50
60/60
20/20
25/25
30/30
35/35
40/40
45/45
15/15
20/20
30/30
30/30
35/35
45/45
15/15
20/20
30/30
30/30
35/35
40/40
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Over Current
Unit Min. Ckt Protective Device Size
Ampacity @
480 V
Min/Max
Min/Max
@ 480 V @ 480 V
10
15/15
—
19
20/20
—
25
25/25
—
27
30/30
—
32
35/35
—
40
40/40
—
Single Power Supply For Both Unit And Heater Kit
—
22
30
37
—
9
15
17
22
30
—
9
15
17
22
30
—
9
15
17
22
30
—
9
15
17
22
30
Min. Ckt.
Ampacity
480V
—
25
30
40
—
15
15
20
25
30
—
15
15
20
25
30
—
15
15
20
25
30
—
15
15
20
25
30
Max. Fuse
Size
480V
Heater Kit
17
17/0
17/0
17/0
14
14/0
14/0
14/0
14/0
14/0
11
11/0
11/0
11/0
11/0
11/0
11
11/0
11/0
11/0
11/0
11/0
20/25
20/25
20/25
20/25
20/20
20/20
20/20
20/20
20/20
20/20
15/15
15/15
15/15
15/15
15/15
15/15
15/15
15/15
15/15
15/15
15/15
15/15
—
0/0
0/0
0/0
—
0/0
0/0
0/0
0/0
0/0
—
0/0
0/0
0/0
0/0
0/0
—
0/0
0/0
0/0
0/0
0/0
Over Current
Min. Circuit Protective Device Size
Ampacity
480V
Min/Max
Min/Max
@ 480 V @ 480 V
10
15/15
—
10/0
15/15
0/0
10/0
15/15
0/0
10/0
15/15
0/0
10/0
15/15
0/0
10/0
15/15
0/0
Heat Pump
Separate Power Supply For Both Unit And Heater Kit
480 VOLT, THREE PHASE, 60 HZ, AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION
AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION – RJNL
59
60
RJNLA072YL
Unit
Model
Number
No. of
Sequence
Steps
—
1
1
1
RXJJHeater Kit
Nominal kW
No Heat
A15Y
A20Y
A24Y
—
14.4
19.2
24
—
49.13
65.5
81.88
Rated Heater
Heater
kW @
KBTU/Hr @
600 V
600 V
Heater Kit
—
13.9
18.8
23.1
Heater
Amp. @
600 V
Heat Pump
Over Current
Unit Min. Ckt Protective Device Size
Ampacity @
600V
Min/Max
Min/Max
@ 600 V
@600 V
14
15/20
—
32
35/35
—
38
40/40
—
43
45/45
—
Single Power Supply For Both Unit And Heater Kit
—
18
24
29
Min. Ckt.
Ampacity
600V
—
20
25
30
Max. Fuse
Size
600V
Heater Kit
Over Current
Min. Circuit Protective Device Size
Ampacity
600V
Min/Max
Min/Max
@ 60 V
@ 600 V
14
15/20
—
14/0
15/20
0/0
14/0
15/20
0/0
14/0
15/20
0/0
Heat Pump
Separate Power Supply For Both Unit And Heater Kit
600 VOLT, THREE PHASE, 60 HZ, AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION
AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION
No. of
Sequence
Steps
—
1
1
1
1
1
—
1
1
1
1
1
—
1
1
1
1
1
—
1
1
1
1
1
RXJJHeater Kit
Nominal kW
No Heat
A06J
A10J
A12J
A15J
A20J
No Heat
A06J
A10J
A12J
A15J
A20J
No Heat
A06J
A10J
A12J
A15J
A20J
No Heat
A06J
A10J
A12J
A15J
A20J
RJPLA036JK
RJPLA042JK
RJPLA048JK
RJPLA060JK
Unit
Model
Number
—
4.2/5.6
7.2/9.6
8.4/11.2
10.8/14.4
14.4/19.2
—
4.2/5.6
7.2/9.6
8.4/11.2
10.8/14.4
14.4/19.2
—
4.2/5.6
7.2/9.6
8.4/11.2
10.8/14.4
14.4/19.2
—
4.2/5.6
7.2/9.6
8.4/11.2
10.8/14.4
14.4/19.2
—
14.33/19.1
24.56/32.75
28.66/38.21
36.84/49.13
49.13/65.5
—
14.33/19.1
24.56/32.75
28.66/38.21
36.84/49.13
49.13/65.5
—
14.33/19.1
24.56/32.75
28.66/38.21
36.84/49.13
49.13/65.5
—
14.33/19.1
24.56/32.75
28.66/38.21
36.84/49.13
49.13/65.5
Rated Heater
Heater
kW @
KBTU/Hr @
208/240 V
208/240 V
Heater Kit
—
20.2/23.3
34.6/40
40.4/46.7
51.9/60
69.3/80
—
20.2/23.3
34.6/40
40.4/46.7
51.9/60
69.3/80
—
20.2/23.3
34.6/40
40.4/46.7
51.9/60
69.3/80
—
20.2/23.3
34.6/40
40.4/46.7
51.9/60
69.3/80
Heater
Amp. @
208-240 V
Heat Pump
39/39
65/69
83/89
90/98
104/114
126/139
31/31
57/61
75/81
82/90
96/106
118/131
26/26
52/56
70/76
77/85
91/101
113/126
45/60
70/80
90/90
90/100
110/110
150/150
40/50
60/70
80/80
90/90
100/100
125/125
35/40
60/60
70/70
80/80
100/100
125/125
45/60
70/80
90/100
100/110
125/125
150/150
40/50
70/70
90/90
90/90
110/110
150/150
35/40
60/60
80/80
90/90
110/110
150/150
Over Current
Unit Min. Ckt Protective Device Size
Ampacity @
208-240V
Min/Max
Min/Max
@ 208 V
@240 V
24/24
30/40
30/40
50/54
50/60
60/60
68/74
70/70
80/80
75/83
80/80
90/90
89/99
90/90
100/100
111/124
125/125
125/125
Single Power Supply For Both Unit And Heater Kit
—
26/30
44/50
51/59
65/75
87/100
—
26/30
44/50
51/59
65/75
87/100
—
26/30
44/50
51/59
65/75
87/100
—
26/30
44/50
51/59
65/75
87/100
Min. Ckt.
Ampacity
208/240V
—
30/30
45/50
60/60
70/80
90/100
—
30/30
45/50
60/60
70/80
90/100
—
30/30
45/50
60/60
70/80
90/100
—
30/30
45/50
60/60
70/80
90/100
Max. Fuse
Size
208/240V
Heater Kit
39/39
39/39
39/39
39/39
39/39
39/39
31/31
31/31
31/31
31/31
31/31
31/31
26/26
26/26
26/26
26/26
26/26
26/26
45/60
45/60
45/60
45/60
45/60
45/60
40/50
40/50
40/50
40/50
40/50
40/50
35/40
35/40
35/40
35/40
35/40
35/40
45/60
45/60
45/60
45/60
45/60
45/60
40/50
40/50
40/50
40/50
40/50
40/50
35/40
35/40
35/40
35/40
35/40
35/40
Over Current
Min. Circuit Protective Device Size
Ampacity
208/240V
Min/Max
Min/Max
@ 208 V
@ 240 V
24/24
30/40
30/40
24/24
30/40
30/40
24/24
30/40
30/40
24/24
30/40
30/40
24/24
30/40
30/40
24/24
30/40
30/40
Heat Pump
Separate Power Supply For Both Unit And Heater Kit
208-240 VOLT, THREE PHASE, 60 HZ, AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION
AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION – RJPL
61
62
No. of
Sequence
Steps
—
1
1
1
1
1
—
1
1
1
1
1
—
1
1
1
1
1
—
1
1
1
1
1
RXJJHeater Kit
Nominal kW
No Heat
A06C
A10C
A12C
A15C
A20C
No Heat
A06C
A10C
A12C
A15C
A20C
No Heat
A06C
A10C
A12C
A15C
A20C
No Heat
A06C
A10C
A12C
A15C
A20C
RJPLA036CK
RJPLA042CK
RJPLA048CK
RJPLA060CK
Unit
Model
Number
—
4.2/5.6
7.2/9.6
8.4/11.2
10.8/14.4
14.4/19.2
—
4.2/5.6
7.2/9.6
8.4/11.2
10.8/14.4
14.4/19.2
—
4.2/5.6
7.2/9.6
8.4/11.2
10.8/14.4
14.4/19.2
—
4.2/5.6
7.2/9.6
8.4/11.2
10.8/14.4
14.4/19.2
—
14.33/19.1
24.56/32.75
28.66/38.21
36.84/49.13
49.13/65.5
—
14.33/19.1
24.56/32.75
28.66/38.21
36.84/49.13
49.13/65.5
—
14.33/19.1
24.56/32.75
28.66/38.21
36.84/49.13
49.13/65.5
—
14.33/19.1
24.56/32.75
28.66/38.21
36.84/49.13
49.13/65.5
Rated Heater
Heater
kW @
KBTU/Hr @
208/240 V
208/240 V
Heater Kit
—
11.7/13.5
20/23.1
23.4/27
30.1/34.7
40/46.3
—
11.7/13.5
20/23.1
23.4/27
30.1/34.7
40/46.3
—
11.7/13.5
20/23.1
23.4/27
30.1/34.7
40/46.3
—
11.7/13.5
20/23.1
23.4/27
30.1/34.7
40/46.3
Heater
Amp. @
208-240 V
Heat Pump
25/25
40/42
50/54
55/59
63/69
75/83
21/21
36/38
46/50
51/55
59/65
71/79
21/21
36/38
46/50
51/55
59/65
71/79
30/40
45/50
60/60
60/60
70/70
80/80
25/30
40/45
50/50
60/60
60/60
80/80
25/30
40/45
50/50
60/60
60/60
80/80
30/40
45/50
60/60
60/60
70/70
90/90
25/30
40/45
60/60
60/60
70/70
80/80
25/30
40/45
50/50
60/60
70/70
80/80
Over Current
Unit Min. Ckt Protective Device Size
Ampacity @
208-240V
Min/Max
Min/Max
@ 208 V
@240 V
17/17
20/25
20/25
32/34
35/35
35/35
42/46
45/45
50/50
47/51
50/50
60/60
55/61
60/60
70/70
67/75
70/70
80/80
Single Power Supply For Both Unit And Heater Kit
—
15/17
25/29
30/34
38/44
50/58
—
15/17
25/29
30/34
38/44
50/58
—
15/17
25/29
30/34
38/44
50/58
—
15/17
25/29
30/34
38/44
50/58
Min. Ckt.
Ampacity
208/240V
—
15/20
25/30
30/35
40/45
50/60
—
15/20
25/30
30/35
40/45
50/60
—
15/20
25/30
30/35
40/45
50/60
—
15/20
25/30
30/35
40/45
50/60
Max. Fuse
Size
208/240V
Heater Kit
25/25
25/25
25/25
25/25
25/25
25/25
21/21
21/21
21/21
21/21
21/21
21/21
21/21
21/21
21/21
21/21
21/21
21/21
30/40
30/40
30/40
30/40
30/40
30/40
25/30
25/30
25/30
25/30
25/30
25/30
25/30
25/30
25/30
25/30
25/30
25/30
30/40
30/40
30/40
30/40
30/40
30/40
25/30
25/30
25/30
25/30
25/30
25/30
25/30
25/30
25/30
25/30
25/30
25/30
Over Current
Min. Circuit Protective Device Size
Ampacity
208/240V
Min/Max
Min/Max
@ 208 V
@ 240 V
17/17
20/25
20/25
17/17
20/25
20/25
17/17
20/25
20/25
17/17
20/25
20/25
17/17
20/25
20/25
17/17
20/25
20/25
Heat Pump
Separate Power Supply For Both Unit And Heater Kit
208-240 VOLT, THREE PHASE, 60 HZ, AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION
AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION – RJPL
No. of
Sequence
Steps
—
1
1
1
1
1
—
1
1
1
1
1
—
1
1
1
1
1
—
1
1
1
1
1
RXJJHeater Kit
Nominal kW
No Heat
A06C
A10C
A12C
A15C
A20C
No Heat
A06C
A10C
A12C
A15C
A20C
No Heat
A06C
A10C
A12C
A15C
A20C
No Heat
A06C
A10C
A12C
A15C
A20C
RJPLA036CL
RJPLA042CL
RJPLA048CL
RJPLA060CL
Unit
Model
Number
—
4.2/5.6
7.2/9.6
8.4/11.2
10.8/14.4
14.4/19.2
—
4.2/5.6
7.2/9.6
8.4/11.2
10.8/14.4
14.4/19.2
—
4.2/5.6
7.2/9.6
8.4/11.2
10.8/14.4
14.4/19.2
—
4.2/5.6
7.2/9.6
8.4/11.2
10.8/14.4
14.4/19.2
—
14.33/19.1
24.56/32.75
28.66/38.21
36.84/49.13
49.13/65.5
—
14.33/19.1
24.56/32.75
28.66/38.21
36.84/49.13
49.13/65.5
—
14.33/19.1
24.56/32.75
28.66/38.21
36.84/49.13
49.13/65.5
—
14.33/19.1
24.56/32.75
28.66/38.21
36.84/49.13
49.13/65.5
Rated Heater
Heater
kW @
KBTU/Hr @
208/240 V
208/240 V
Heater Kit
—
11.7/13.5
20/23.1
23.4/27
30.1/34.7
40/46.3
—
11.7/13.5
20/23.1
23.4/27
30.1/34.7
40/46.3
—
11.7/13.5
20/23.1
23.4/27
30.1/34.7
40/46.3
—
11.7/13.5
20/23.1
23.4/27
30.1/34.7
40/46.3
Heater
Amp. @
208-240 V
Heat Pump
26/26
41/43
51/55
56/60
64/70
76/84
22/22
37/39
47/51
52/56
60/66
72/80
22/22
37/39
47/51
52/56
60/66
72/80
30/40
45/50
60/60
60/60
70/70
80/80
25/35
40/45
50/50
60/60
70/70
80/80
25/30
40/45
50/50
60/60
60/60
80/80
30/40
45/50
60/60
70/70
80/80
90/90
25/35
40/45
60/60
60/60
70/70
90/90
25/30
40/45
60/60
60/60
70/70
90/90
Over Current
Unit Min. Ckt Protective Device Size
Ampacity @
208-240V
Min/Max
Min/Max
@ 208 V
@240 V
18/18
20/25
20/25
33/35
35/35
40/40
43/47
45/45
50/50
48/52
50/50
60/60
56/62
60/60
70/70
68/76
70/70
80/80
Single Power Supply For Both Unit And Heater Kit
—
15/17
25/29
30/34
38/44
50/58
—
15/17
25/29
30/34
38/44
50/58
—
15/17
25/29
30/34
38/44
50/58
—
15/17
25/29
30/34
38/44
50/58
Min. Ckt.
Ampacity
208/240V
—
15/20
25/30
30/35
40/45
50/60
—
15/20
25/30
30/35
40/45
50/60
—
15/20
25/30
30/35
40/45
50/60
—
15/20
25/30
30/35
40/45
50/60
Max. Fuse
Size
208/240V
Heater Kit
26/26
26/26
26/26
26/26
26/26
26/26
22/22
22/22
22/22
22/22
22/22
22/22
22/22
22/22
22/22
22/22
22/22
22/22
30/40
30/40
30/40
30/40
30/40
30/40
25/35
25/35
25/35
25/35
25/35
25/35
25/30
25/30
25/30
25/30
25/30
25/30
30/40
30/40
30/40
30/40
30/40
30/40
25/35
25/35
25/35
25/35
25/35
25/35
25/30
25/30
25/30
25/30
25/30
25/30
Over Current
Min. Circuit Protective Device Size
Ampacity
208/240V
Min/Max
Min/Max
@ 208 V
@ 240 V
18/18
20/25
20/25
18/18
20/25
20/25
18/18
20/25
20/25
18/18
20/25
20/25
18/18
20/25
20/25
18/18
20/25
20/25
Heat Pump
Separate Power Supply For Both Unit And Heater Kit
208-240 VOLT, THREE PHASE, 60 HZ, AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION
AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION – RJPL
63
64
No. of
Sequence
Steps
—
1
1
1
1
1
—
1
1
1
1
1
—
1
1
1
1
1
—
1
1
1
1
1
RXJJHeater Kit
Nominal kW
No Heat
A06C
A10C
A12C
A15C
A20C
No Heat
A06C
A10C
A12C
A15C
A20C
No Heat
A06C
A10C
A12C
A15C
A20C
No Heat
A06C
A10C
A12C
A15C
A20C
RJPLA036CM
RJPLA042CM
RJPLA048CM
RJPLA060CM
Unit
Model
Number
—
4.2/5.6
7.2/9.6
8.4/11.2
10.8/14.4
14.4/19.2
—
4.2/5.6
7.2/9.6
8.4/11.2
10.8/14.4
14.4/19.2
—
4.2/5.6
7.2/9.6
8.4/11.2
10.8/14.4
14.4/19.2
—
4.2/5.6
7.2/9.6
8.4/11.2
10.8/14.4
14.4/19.2
—
14.33/19.1
24.56/32.75
28.66/38.21
36.84/49.13
49.13/65.5
—
14.33/19.1
24.56/32.75
28.66/38.21
36.84/49.13
49.13/65.5
—
14.33/19.1
24.56/32.75
28.66/38.21
36.84/49.13
49.13/65.5
—
14.33/19.1
24.56/32.75
28.66/38.21
36.84/49.13
49.13/65.5
Rated Heater
Heater
kW @
KBTU/Hr @
208/240 V
208/240 V
Heater Kit
—
11.7/13.5
20/23.1
23.4/27
30.1/34.7
40/46.3
—
11.7/13.5
20/23.1
23.4/27
30.1/34.7
40/46.3
—
11.7/13.5
20/23.1
23.4/27
30.1/34.7
40/46.3
—
11.7/13.5
20/23.1
23.4/27
30.1/34.7
40/46.3
Heater
Amp. @
208-240 V
Heat Pump
26/26
41/43
51/55
56/60
64/70
76/84
23/23
38/40
48/52
53/57
61/67
73/81
22/22
37/39
47/51
52/56
60/66
72/80
30/40
45/50
60/60
60/60
70/70
80/80
30/35
40/45
50/50
60/60
70/70
80/80
30/35
40/45
50/50
60/60
70/70
80/80
30/40
45/50
60/60
70/70
80/80
90/90
30/35
45/45
60/60
60/60
70/70
90/90
30/35
40/45
60/60
60/60
70/70
90/90
Over Current
Unit Min. Ckt Protective Device Size
Ampacity @
208-240V
Min/Max
Min/Max
@ 208 V
@240 V
18/18
25/25
25/25
33/35
35/35
40/40
43/47
45/45
50/50
48/52
50/50
60/60
56/62
60/60
70/70
68/76
70/70
80/80
Single Power Supply For Both Unit And Heater Kit
—
15/17
25/29
30/34
38/44
50/58
—
15/17
25/29
30/34
38/44
50/58
—
15/17
25/29
30/34
38/44
50/58
—
15/17
25/29
30/34
38/44
50/58
Min. Ckt.
Ampacity
208/240V
—
15/20
25/30
30/35
40/45
50/60
—
15/20
25/30
30/35
40/45
50/60
—
15/20
25/30
30/35
40/45
50/60
—
15/20
25/30
30/35
40/45
50/60
Max. Fuse
Size
208/240V
Heater Kit
26/26
26/26
26/26
26/26
26/26
26/26
23/23
23/23
23/23
23/23
23/23
23/23
22/22
22/22
22/22
22/22
22/22
22/22
30/40
30/40
30/40
30/40
30/40
30/40
30/35
30/35
30/35
30/35
30/35
30/35
30/35
30/35
30/35
30/35
30/35
30/35
30/40
30/40
30/40
30/40
30/40
30/40
30/35
30/35
30/35
30/35
30/35
30/35
30/35
30/35
30/35
30/35
30/35
30/35
Over Current
Min. Circuit Protective Device Size
Ampacity
208/240V
Min/Max
Min/Max
@ 208 V
@ 240 V
18/18
25/25
25/25
18/18
25/25
25/25
18/18
25/25
25/25
18/18
25/25
25/25
18/18
25/25
25/25
18/18
25/25
25/25
Heat Pump
Separate Power Supply For Both Unit And Heater Kit
208-240 VOLT, THREE PHASE, 60 HZ, AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION
AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION – RJPL
No. of
Sequence
Steps
—
1
1
1
1
1
—
1
1
1
1
1
—
1
1
1
1
1
—
1
1
1
1
1
RXJJHeater Kit
Nominal kW
No Heat
A06D
A10D
A12D
A15D
A20D
No Heat
A06D
A10D
A12D
A15D
A20D
No Heat
A06D
A10D
A12D
A15D
A20D
No Heat
A06D
A10D
A12D
A15D
A20D
RJPLA036DK
RJPLA042DK
RJPLA048DK
RJPLA060DK
Unit
Model
Number
—
5.6
9.6
11.2
14.4
19.2
—
5.6
9.6
11.2
14.4
19.2
—
5.6
9.6
11.2
14.4
19.2
—
5.6
9.6
11.2
14.4
19.2
—
19.1
32.75
38.21
49.13
65.5
—
19.1
32.75
38.21
49.13
65.5
—
19.1
32.75
38.21
49.13
65.5
—
19.1
32.75
38.21
49.13
65.5
Rated Heater
Heater
kW @
KBTU/Hr @
480 V
480 V
Heater Kit
—
6.7
11.6
13.5
17.4
23.3
—
6.7
11.6
13.5
17.4
23.3
—
6.7
11.6
13.5
17.4
23.3
—
6.7
11.6
13.5
17.4
23.3
Heater
Amp. @
480 V
Heat Pump
13
22
28
30
35
43
10
19
25
27
32
40
10
19
25
27
32
40
15/20
25/25
30/30
30/30
35/35
45/45
15/15
20/20
25/25
30/30
35/35
40/40
15/15
20/20
25/25
30/30
35/35
40/40
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Over Current
Unit Min. Ckt Protective Device Size
Ampacity @
480 V
Min/Max
Min/Max
@ 480 V @ 480 V
10
15/15
—
19
20/20
—
25
25/25
—
27
30/30
—
32
35/35
—
40
40/40
—
Single Power Supply For Both Unit And Heater Kit
—
9
15
17
22
30
—
9
15
17
22
30
—
9
15
17
22
30
—
9
15
17
22
30
Min. Ckt.
Ampacity
480V
—
15
15
20
25
30
—
15
15
20
25
30
—
15
15
20
25
30
—
15
15
20
25
30
Max. Fuse
Size
480V
Heater Kit
13
13/0
13/0
13/0
13/0
13/0
10
10/0
10/0
10/0
10/0
10/0
10
10/0
10/0
10/0
10/0
10/0
15/20
15/20
15/20
15/20
15/20
15/20
15/15
15/15
15/15
15/15
15/15
15/15
15/15
15/15
15/15
15/15
15/15
15/15
—
0/0
0/0
0/0
0/0
0/0
—
0/0
0/0
0/0
0/0
0/0
—
0/0
0/0
0/0
0/0
0/0
Over Current
Min. Circuit Protective Device Size
Ampacity
480V
Min/Max
Min/Max
@ 480 V @ 480 V
10
15/15
—
10/0
15/15
0/0
10/0
15/15
0/0
10/0
15/15
0/0
10/0
15/15
0/0
10/0
15/15
0/0
Heat Pump
Separate Power Supply For Both Unit And Heater Kit
480 VOLT, THREE PHASE, 60 HZ, AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION
AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION – RJPL
65
66
No. of
Sequence
Steps
—
1
1
1
1
1
—
1
1
1
1
1
—
1
1
1
1
1
—
1
1
1
1
1
RXJJHeater Kit
Nominal kW
No Heat
A06D
A10D
A12D
A15D
A20D
No Heat
A06D
A10D
A12D
A15D
A20D
No Heat
A06D
A10D
A12D
A15D
A20D
No Heat
A06D
A10D
A12D
A15D
A20D
RJPLA036DL
RJPLA042DL
RJPLA048DL
RJPLA060DL
Unit
Model
Number
—
5.6
9.6
11.2
14.4
19.2
—
5.6
9.6
11.2
14.4
19.2
—
5.6
9.6
11.2
14.4
19.2
—
5.6
9.6
11.2
14.4
19.2
—
19.1
32.75
38.21
49.13
65.5
—
19.1
32.75
38.21
49.13
65.5
—
19.1
32.75
38.21
49.13
65.5
—
19.1
32.75
38.21
49.13
65.5
Rated Heater
Heater
kW @
KBTU/Hr @
480 V
480 V
Heater Kit
—
6.7
11.6
13.5
17.4
23.3
—
6.7
11.6
13.5
17.4
23.3
—
6.7
11.6
13.5
17.4
23.3
—
6.7
11.6
13.5
17.4
23.3
Heater
Amp. @
480 V
Heat Pump
13
22
28
30
35
43
11
20
26
28
33
41
10
19
25
27
32
40
15/20
25/25
30/30
30/30
35/35
45/45
15/15
20/20
30/30
30/30
35/35
40/40
15/15
20/20
30/30
30/30
35/35
40/40
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Over Current
Unit Min. Ckt Protective Device Size
Ampacity @
480 V
Min/Max
Min/Max
@ 480 V @ 480 V
10
15/15
—
19
20/20
—
25
25/25
—
27
30/30
—
32
35/35
—
40
40/40
—
Single Power Supply For Both Unit And Heater Kit
—
9
15
17
22
30
—
9
15
17
22
30
—
9
15
17
22
30
—
9
15
17
22
30
Min. Ckt.
Ampacity
480V
—
15
15
20
25
30
—
15
15
20
25
30
—
15
15
20
25
30
—
15
15
20
25
30
Max. Fuse
Size
480V
Heater Kit
13
13/0
13/0
13/0
13/0
13/0
11
11/0
11/0
11/0
11/0
11/0
10
10/0
10/0
10/0
10/0
10/0
15/20
15/20
15/20
15/20
15/20
15/20
15/15
15/15
15/15
15/15
15/15
15/15
15/15
15/15
15/15
15/15
15/15
15/15
—
0/0
0/0
0/0
0/0
0/0
—
0/0
0/0
0/0
0/0
0/0
—
0/0
0/0
0/0
0/0
0/0
Over Current
Min. Circuit Protective Device Size
Ampacity
480V
Min/Max
Min/Max
@ 480 V @ 480 V
10
15/15
—
10/0
15/15
0/0
10/0
15/15
0/0
10/0
15/15
0/0
10/0
15/15
0/0
10/0
15/15
0/0
Heat Pump
Separate Power Supply For Both Unit And Heater Kit
480 VOLT, THREE PHASE, 60 HZ, AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION
AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION – RJPL
No. of
Sequence
Steps
—
1
1
1
1
1
—
1
1
1
1
1
—
1
1
1
1
1
—
1
1
1
1
1
RXJJHeater Kit
Nominal kW
No Heat
A06D
A10D
A12D
A15D
A20D
No Heat
A06D
A10D
A12D
A15D
A20D
No Heat
A06D
A10D
A12D
A15D
A20D
No Heat
A06D
A10D
A12D
A15D
A20D
RJPLA036DM
RJPLA042DM
RJPLA048DM
RJPLA060DM
Unit
Model
Number
—
5.6
9.6
11.2
14.4
19.2
—
5.6
9.6
11.2
14.4
19.2
—
5.6
9.6
11.2
14.4
19.2
—
5.6
9.6
11.2
14.4
19.2
—
19.1
32.75
38.21
49.13
65.5
—
19.1
32.75
38.21
49.13
65.5
—
19.1
32.75
38.21
49.13
65.5
—
19.1
32.75
38.21
49.13
65.5
Rated Heater
Heater
kW @
KBTU/Hr @
480 V
480 V
Heater Kit
—
6.7
11.6
13.5
17.4
23.3
—
6.7
11.6
13.5
17.4
23.3
—
6.7
11.6
13.5
17.4
23.3
—
6.7
11.6
13.5
17.4
23.3
Heater
Amp. @
480 V
Heat Pump
13
22
28
30
35
43
11
20
26
28
33
41
11
20
26
28
33
41
15/20
25/25
30/30
30/30
35/35
45/45
15/15
20/20
30/30
30/30
35/35
40/40
15/15
20/20
30/30
30/30
35/35
40/40
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Over Current
Unit Min. Ckt Protective Device Size
Ampacity @
480 V
Min/Max
Min/Max
@ 480 V @ 480 V
10
15/15
—
19
20/20
—
25
25/25
—
27
30/30
—
32
35/35
—
40
40/40
—
Single Power Supply For Both Unit And Heater Kit
—
9
15
17
22
30
—
9
15
17
22
30
—
9
15
17
22
30
—
9
15
17
22
30
Min. Ckt.
Ampacity
480V
—
15
15
20
25
30
—
15
15
20
25
30
—
15
15
20
25
30
—
15
15
20
25
30
Max. Fuse
Size
480V
Heater Kit
13
13/0
13/0
13/0
13/0
13/0
11
11/0
11/0
11/0
11/0
11/0
11
11/0
11/0
11/0
11/0
11/0
15/20
15/20
15/20
15/20
15/20
15/20
15/15
15/15
15/15
15/15
15/15
15/15
15/15
15/15
15/15
15/15
15/15
15/15
—
0/0
0/0
0/0
0/0
0/0
—
0/0
0/0
0/0
0/0
0/0
—
0/0
0/0
0/0
0/0
0/0
Over Current
Min. Circuit Protective Device Size
Ampacity
480V
Min/Max
Min/Max
@ 480 V @ 480 V
10
15/15
—
10/0
15/15
0/0
10/0
15/15
0/0
10/0
15/15
0/0
10/0
15/15
0/0
10/0
15/15
0/0
Heat Pump
Separate Power Supply For Both Unit And Heater Kit
480 VOLT, THREE PHASE, 60 HZ, AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION
AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION – RJPL
67
FIGURE 19
WIRING DIAGRAM
68
FIGURE 20
WIRING DIAGRAM
69
FIGURE 21
WIRING DIAGRAM
70
FIGURE 22
WIRING DIAGRAM
71
FIGURE 23
WIRING DIAGRAM
72
FIGURE 24
WIRING DIAGRAM
73
FIGURE 25
WIRING DIAGRAM
74
FIGURE 26
WIRING DIAGRAM
75
FIGURE 27
WIRING DIAGRAM
76
FIGURE 28
WIRING DIAGRAM
77
78
79
80
5 TON – 13 SEER
81
5 TON – 14 SEER
82
6 TON HP (R410A)
600
115
GISP - ERUSSERP EGRAHCSID
550
105
500
95
450
85
400
75
65
350
55
300
OUTDOOR AMBIENT (°F DB)
SYSTEM CHARGE CHART (COOLING)
250
200
100
120
140
160
180
200
220
SUCTION PRESSURE - PSIG
600
80
SYSTEM CHARGE CHART (HEATING)
550
500
60
450
400
350
300
250
200
20
40
60
80
100
120
140
160
180
200
INDOOR AMBIENT (°F DB)
GISP - ERUSSERP EGRAHCSID
70
220
SUCTION PRESSURE - PSIG
92-102380-06-00
83
!
TROUBLE SHOOTING CHART
WARNING
DISCONNECT ALL POWER TO UNIT BEFORE SERVICING. CONTACTOR MAY BREAK ONLY ONE SIDE. FAILURE
TO SHUT OFF POWER CAN CAUSE ELECTRICAL SHOCK RESULTING IN PERSONAL INJURY OR DEATH.
SYMPTOM
Unit will not run
POSSIBLE CAUSE
• Power off or loose electrical connection
• Thermostat out of calibration-set too high
• Defective contactor
•
•
•
•
Condenser fan runs, compressor
doesn’t
Insufficient cooling
Compressor short cycles
Blown fuses
Transformer defective
High pressure control open (if provided)
Interconnecting low voltage wiring damaged
• Run capacitor defective (single phase only)
• Loose connection
• Check for correct voltage at compressor contactor in control
box
• Reset
• Check for 24 volts at contactor coil - replace if contacts are
open
• Replace fuses
• Check wiring-replace transformer
• Reset-also see high head pressure remedy• Replace thermostat wiring
• Compressor stuck, grounded or open motor winding,
open internal overload.
• Low voltage condition
• Low voltage condition
• Replace
• Check for correct voltage at compressor check & tighten all connections
• Wait at least 2 hours for overload to reset.
If still open, replace the compressor.
At compressor terminals, voltage must be within 10% of rating
• Add start kit components
•
•
•
•
•
•
•
•
•
•
Improperly sized unit
Improper airflow
Incorrect refrigerant charge
Air, non-condensibles or moisture in system
Incorrect voltage
• Incorrect voltage
• Defective overload protector
• Refrigerant undercharge
Registers sweat
REMEDY
Recalculate load
Check - should be approximately 400 CFM per ton.
Charge per procedure attached to unit service panel
Recover refrigerant, evacuate & recharge, add filter drier
At compressor terminals, voltage must be within 10% of rating
plate volts when unit is operating.
• At compressor terminals, voltage must be ±10% of
nameplate marking when unit is operating.
• Replace - check for correct voltage
• Add refrigerant
• Low evaporator airflow
• Increase speed of blower or reduce restriction - replace air
filter
High head-low vapor pressures
•
•
•
•
Restriction in liquid line, expansion device or filter drier
Flow check piston size too small
Incorrect capillary tubes
TXV does not open
•
•
•
•
Remove or replace defective component
Change to correct size piston
Change coil assembly
Replace TXV
High head-high or normal vapor
pressure - Cooling mode
•
•
•
•
Dirty condenser coil
Refrigerant overcharge
Condenser fan not running
Air or non-condensibles in system
•
•
•
•
Clean coil
Correct system charge
Repair or replace
Recover refrigerant, evacuate & recharge
High head-high or normal vapor
pressure - Heating mode
•
•
•
•
Low air flow - condenser coil
Refrigerant overcharge
Air or non-condensibles in system
Dirty condenser coil
•
•
•
•
Check filters - correct to speed
Correct system charge
Recover refrigerant, evacuate & recharge
Check filter - clean coil
Low head-high vapor pressures
• Defective Compressor valves
• Replace compressor
Low vapor - cool compressor iced evaporator coil
• Low evaporator airflow
• Operating below 65°F outdoors
• Moisture in system
• TXV limiting refrigerant flow
• Increase speed of blower or reduce restriction - replace air
filter
• Add Low Ambient Kit
• Recover refrigerant - evacuate & recharge - add filter drier
• Replace TXV
• Excessive load
• Defective compressor
• Recheck load calculation
• Replace
• TXV hunting
• Air or non-condensate in system
• Check TXV bulb clamp - check air distribution on coil - replace
TXV
• Recover refrigerant, evacuate & recharge
• Air or non-condensibles in system
• Recover refrigerant, evacuate & recharge
High vapor pressure
Fluctuating head & vapor
pressures
Gurgle or pulsing noise at
expansion device or liquid line
SEE DEMAND DEFROST CONTROL SECTION FOR DEFROST BOARD FLASH CODES (6 TON UNIT ONLY).
84