Valve terminal MPAL-VI, end plate VMPAL-EPL

– applicable regulations for operating safety-engineering systems
– applicable regulations for accident prevention and occupational safety
– documentation for the product
Valve terminal MPAL-VI,
end plate VMPAL-EPL-IPO32
3
Further information
– accessories è www.festo.com/catalogue
– spare parts è www.festo.com/spareparts
Festo AG & Co. KG
Ruiter Straße 82
73734 Esslingen
Germany
+49 711 347-0
www.festo.com
4
Service
Contact the regional Festo contact if you have technical questions
è www.festo.com.
5
Product design
1
Brief description
(Original instructions)
2
8068182
2017-07a
[8068184]
4
Valve terminal MPAL-VI, end plate with I-Port/IO-Link interface . . . . . . . . English
TORX® and IO-Link® are registered trademarks of the respective trademark
owners in certain countries.
1
About this document
This document describes the I-Port/IO-Link interface of the valve terminal. Addi­
tional aspects of use are described in other documents and must be observed
è 1.1 Further applicable documents.
1.1 Further applicable documents
Document
Description MPAL-VI
Description/brief description/operating in­
structions CTEU-...
Assembly instructions MPA
Additional assembly instructions
Table of contents
Detailed description of installation, commis­
sioning, maintenance and conversion of the
valve terminal
Detailed description of the bus node CTEU-...
and their fieldbus protocols
Wall mounting and H-rail mounting of the valve
terminal
Mounting of valve terminal components
Fig. 1
For all available product documentation è www.festo.com/pk
2
3
1
2
4
5.1 I-Port/IO-Link interface
Through the I-Port/IO-Link interface 2 of the end plate VMPAL-EPL-IPO32,
the valve terminal can be connected as follows:
– directly to the fieldbus (through mounting of a CTEU bus node on the valve terminal)
– through a cable to an external I-Port interface
– through a cable to an IO-Link master (è Chap. 9)
Plug connector,
Pin
Allocation
5-pin, M12x1,
A-coded
Fig. 3
1
24 V DC operating voltage supply (UPS)
2
24 V DC load voltage supply (UPL)
3
0 V DC operating voltage supply (UPS)
4
C/Q data communication
5
0 V DC load voltage supply (UPL)
housing
Connection to functional earth è Chap. 6
I-Port/IO-Link interface
5.2 Display components
LED X1 Revision1)
Rev 01
› Rev 02
g
LED is off:
– No 24 V operating voltage supply or undervoltage
LED illuminated green:
– Normal operating status
g
LED illuminated green:
– Data communication is not satisfactory
g
1)
Status and significance
g
g
2.2 Use for intended purpose
The valve terminal is intended for installation in machines and automation techno­
logy systems and must be used exclusively as follows:
– in perfect technical condition
– in its original state without unauthorised modifications; the conversions or
modifications described in the documentation are permitted
– within the limits of the product defined through the technical data
– only in combination with approved components (e.g. valves, drive/displacement
encoder combinations)
– in an industrial environment
Use for intended purpose is described completely in the documentation. Every
other use is considered not intended.
2.3 Training of specialized personnel
The product may be commissioned only by an electrotechnically qualified person,
who is familiar with the following topics:
– installation and operation of control and automation systems
Earthing screw for connection
to functional earth (Torx, T20)
Earth terminal (optional) for con­
nection to functional earth
Fig. 2 Display and connecting elements
Safety
2.1 General safety information
Before work on the product, make sure that the following and been switched off
and secured against being switched on again:
– compressed air supply
– power supply
Observe the handling specifications for electrostatically sensitive devices.
Commission a valve terminal only if it has been completely mounted and connected.
For the electrical power supply, use only PELV circuits in accordance with
IEC 60204-1/EN 60204-1 (Protective extra-low voltage, PELV):
Observe the general requirements IEC 60204-1/EN 60204-1 of the PELV
power circuits.
Use only voltage sources that ensure a reliable electric separation from
the mains network in accordance with IEC 60204-1/EN 60204-1.
Always connect all circuits for operating and load voltage supplies UEL/SEN
and UVAL/OUT.
3
Status LED X1
I-Port/IO-Link interface
LED flashing green (500 ms LED on, 500 ms LED off ):
– Data communication is not satisfactory
g
LED flashing green (900 ms LED on, 100 ms LED off ):
– Normal operating status
g
g
LED flashing red:
– Device errors
g
g
LED illuminated red:
– 24 V load voltage supply not satisfactory (no voltage or
undervoltage; in addition, data communication cannot
be satisfactory)
Revision of the valve terminal è Product labelling
Fig. 4 Status LED X1
6
Earth valve terminal
11 Technical data
General information
Note
Connect one of the earth terminals (è Fig. 2) to the earth potential.
7
Address assignment of the valves
Addresses are allocated in ascending order without gaps, from left to right.
Depending on the integrated electrical interlinking module, a valve position occu­
pies the following number of addresses:
Electrical interlinking module
Number of oc­
Number of
cupied ad­
valve positions
Type
Housing colour dresses per
valve position
Individual electrical interlinking module
VMPAL-EVAP-…-1
Grey
1
1
VMPAL-EVAP-…-2
Black
2
1
4-fold electrical interlinking module
VMPAL-EVAP-…-1-4
Grey
1
4
VMPAL-EVAP-…-2-4
Black
2
4
Black
0 (signals are
passed through)
–5 … +50 °C
Ambient temperature
Storage temperature
–20 … +40 °C
Degree of protection (in accordance with
EN 60529)
IP65 1)
Protection against electric shock
(Protection against direct and indirect con­
tact in accordance with IEC/DIN EN60204-1)
Through the use of PELV circuits
(Protected Extra-Low Voltage)
CE marking (see declaration of conformity)
è www.festo.com/sp
In accordance with EU EMC Directive 2)
Materials
AL, PA, PPA, PE, PBT, NBR, galvanized steel, nickelplated brass, stainless steel
Tightening torque
1)
2)
Bus node on valve terminal
0.8 Nm (±20 %)
Earthing screw
1.0 Nm (±20 %)
Requirement: valve terminal (possibly with bus node) completely mounted, plug connector inserted or
provided with protective cap. Observe that connected devices might only satisfy a lower degree of
protection, a smaller temperature range, etc.
The product is intended for use in industrial environments. If the product is used in a low-voltage net­
work that also supplies residential areas, actions against interference may be required.
Fig. 7
Pneumatics
Number of valve positions
Max. 32
Medium
Compressed air in accordance with ISO 8573-1:2010 [7:4:4]
unlubricated or lubricated (oil: VG32)
Lubricated operation possible (in which case lubricated operation
will always be required)
Notes on the operating/
pilot medium
Operating pressure
Electrical interlinking module of the power supply module
VMPAL-EVAP-20-SP
è Description MPAL-VI
Dimensions
Observe the following points to avoid malfunctions from electromagnetic inter­
ference:
Use a large-cross-section earth conductor that is as short as possible.
The earth conductor should ideally be a braided conductor, alternatively
a cable with a cross section of at least 2.5 mm², preferably 4 mm², and a max­
imum length of 20 cm. A different cable may be required depending on the in­
stallation situation.
Connect the earth terminal with low resistance and low impedance
to the earth potential.
0
With int. pilot air
3 … 8 bar
With ext. pilot air
Dependent on the valve sub-base types used è Description MPAL-VI
Fig. 8
Fig. 5
Electrical data
If one valve occupies both addresses of a valve position:
– Solenoid coil 14 occupies the less significant address.
– Solenoid coil 12 occupies the higher-value address.
Power supply valve terminal 1)
Address assignment does not depend on it is equipped with blanking
plates or valve plates.
Additional information è Description MPAL-VI
8
Installation and commissioning
Installation and commissioning of the pneumatics as well as maintenance
and modification of the valve terminal è Description MPAL-VI
Operating voltage
(UPS)
Load voltage (UPL)
50h
51h
Fig. 6
00h
12h
Device errors
Switch device off and back on. If the error is still present,
the device is defective and needs to be replaced.
Error
Error in the load voltage supply
Check the load voltage supply
Warning
24 V DC (±10 %)
Valve terminal intrinsic current consumption at 24 V
Operating voltage
supply (UPS)
Load voltage supply
(UPL)
Current consumption (per
coil, with LED) at 24 V
Nominal pick-up
current
Pick-up duration
9
IO-Link mode
The valve terminal can also be operated as an IO-Link device. The IODD configura­
tion file required for this can be downloaded at è www.festo.com/sp.
10 Malfunction and error handling
Malfunctions and statuses are transmitted in the form of event codes to the master.
Event code
Malfunction and error handling
Type
MSB LSB
24 V DC (±25 %)
Nominal current with
current reduction
Mains buffering time
(only operating
voltage UPS)
1)
30 mA
30 mA
MPA1
MPA14
MPA20
50 mA
50 mA
110 mA
10 mA
23 mA
Approx. 20 ms
10 mA
10 ms
The operating voltage supply is provided via the CTEU bus node or IO-Link master.
The load voltage supply is through the CTEU bus node or, for IO-Link, through a separate feed.
Separate fuses are required for operating and load voltage.
Fig. 9
I-Port/IO-Link
Cable specifications:
Wire cross section
Min. 1 mm²
Max. length, unshielded
20 m
IO-Link characteristics:
Specification
Revision 1.1 (backwards compatible)
Baud rate
COM 3 (230.4 kBaud)
COM 2 (38.4 kBaud)
4 bytes (1 … 32 valves)
Output Data
Fig. 10
Download PDF