Version: Dec. 01, 2004
RERV & RERVX
Rotary Energy Recovery
Ventilators
Indoor and Outdoor
Installations
250—20,000 CFM Capacities
RERVLP
Low Profile Indoor
Rotary Energy Recovery
Ventilators
Ideal for Classrooms
500—3300 CFM Capacities
RERV MODEL SERIES
ROTARY ENERGY RECOVERY
VENTILATORS
The following chart lists the available unit models with the CFM range for the supply and
exhaust air, and other unit component data. Refer to the performance data following this
page for fan-motor and recovery efficiency data.
ROTARY ENERGY
RECOVERY WHEEL SUPPLY AND
CASSETTE
EXHAUST FAN
MODEL No.
SIZE AND TYPE
UNIT
MODEL
CFM
RANGE
RERV-256
250 - 600
ECW204
RERV-511
500 - 1100
ECW244
FILTER TYPE,
QUANTITIES AND
SIZES
PLEATED - 30% EFFICIENT
S/A 1 - 20 X 25 X 2
E/A 1 - 20 X 25 X 2
10 X 10
FC DWDI
RERV-1019
1000 -1900
ECW324
RERV-1324
1300 - 2400
ECW364
RERV-1533
1500 - 3300
ECW424
PLEATED - 30% EFFICIENT
S/A 2 - 18 X 20 X 2
E/A 2 - 18 X 20 X 2
12 X 12
FC DWDI
PLEATED - 30% EFFICIENT
S/A 2 - 24 X 24 X 2
E/A 2 - 24 X 24 X 2
RERV-3045
3000 - 4500
ECW484
RERV-3550
3500 - 5000
ECW486
RERV-4055
4000 - 5500
ECW544
15 X 15
FC DWDI
PLEATED - 30% EFFICIENT
S/A 6 - 20 X 20 X 2
E/A 6 - 20 X 20 X 2
RERV-4567
4500 - 6700
ECW604
18 X 18
FC DWDI
RERV-5082
5000 - 8200
ECW664
PLEATED - 30% EFFICIENT
S/A 6 - 20 X 20 X 2
E/A 6 - 20 X 20 X 2
RERV-6098
6000 - 9800
ECW666
RERV-7011
7000 - 11000
ECW726
RERV-15000 11000 - 15000
ECW846
22.13 x 22.13
FC DWDI
PLEATED - 30% EFFICIENT
S/A 6 - 24 X 24 X 2
E/A 6 - 24 X 24 X 2
RERV-20000 15000 - 20000
ECW966
25.25 x25.25
FC DWDI
PLEATED - 30% EFFICIENT
S/A 8 - 24 X 24 X 2
E/A 8 - 24 X 24 X 2
SELI
DEC 08/04
RERV STANDARD FEATURES
ITEM 1: ROTARY ENERGY RECOVERY WHEEL ASSEMBLY
•
CASSETTE SLIDES OUT FOR EASY ACCESS
•
FACTORY SET PURGE ELIMINATES CROSSOVER
•
INTEGRAL WHEEL DRIVE MOTOR, PULLEY,AND BELT(S)
•
SYNTHETIC FIBER-BASED MEDIA IMPREGNATED WITH
A NON-MIGRATING WATER SELECTIVE 4A MOLECULAR DESICCANT
SIEVE
ITEM 2: FRESH AIR SUPPLY BLOWER ASSEMBLY
•
FORWARD CURVE WITH DOUBLE INLET
•
BALL BEARINGS WITH SUPPORTS
•
ADJUSTABLE MOTOR MOUNTS
•
ADJUSTABLE CAST-IRON V-BELT DRIVES
•
TEFC MOTORS
ITEM 3: STALE AIR EXHAUST BLOWER ASSEMBLY
(SAME AS FRESH AIR SUPPLY BLOWER ASSEMBLY)
ITEM 4:
•
•
•
•
•
•
•
CABINET
HEAVY GAUGE SATIN COAT STEEL CABINET
ROOF SEAMS FULLY CAULKED AND FASTENED
ROOF OVER-HANG FLANGE PROVIDED WITH PERIMETER DRIP EDGE
HINGED ACCESS DOORS WITH STAINLESS STEEL LATCHES
AND PERIMETER GASKET
1" INSULATION ON ALL INTERIOR SURFACES
INSULATED DOUBLE SKINNED FLOOR
WEATHER RESISTANT POWDER COAT FINISH
ITEM 5: HEAVY GAGE GALVANIZED STEEL PERIMETER BASE:
•
INTEGRAL CROSS SUPPORTS
•
INTEGRAL LIFTING HOLES
•
FORMED TO OVERLAP PERIMETER OF ROOF CURB
ITEM 6: 2” 30% PLEATED MEDIUM EFFICIENCY SUPPLY AND RETURN
AIR FILTERS
ITEM 7: CONTROL ENCLOSURE:
•
BLOWER MOTOR FUSING, CONTACTS, AND THERMAL OVERLOADS
•
LOW VOLTAGE CONTROL TRANSFORMER WITH FUSES
•
COLOUR CODED WIRING AND NUMBERED TERMINAL STRIP
PRODUCT DESCRIPTION
The Spinnaker Industries Inc. Model Series RERV Packaged
Ventilation Units are designed for indoor and outdoor
applications with efficiency and cost effectiveness in mind.
Air volume capacity ranges from 250 to 20,000 CFM.
Quality features include heavy gauge construction, weather
resistant powder coat finish, quiet running forward curved
blowers with ball bearings, adjustable v-belt drives, hinged
access doors with perimeter gasket, and many other standard
features.
RERV Package Ventilation units incorporate an energy
recovery wheel assembly to recover waste heat energy from
the stale exhaust air to preheat the fresh air during the
winter season, and reject heat energy, thus cooling the fresh
air during the summer season.
The energy recovery wheel assembly is designed to transfer
the sensible or total energy between counter flowing supply
and exhaust air streams. The assembly consists of a
motor driven energy recovery wheel with heavy gauge
galvanized steel casing. The recovery wheel itself is fabricated
from a synthetic fiber-based substrate impregnated with
non-migrating water selective molecular sieve desiccant. The
recovery wheel assembly is UL tested and UL recognized as a
component for heat recovery ventilators. The recovery wheel is
ARI certified using the 84-1991 ASHRAE standard method of
testing and ARI standard 1060.
RERVFEAT
DEC 08/04
RETURN AIR
FROM CONDITIONED
SPACE
SUPPLY AIR
TO CONDITIONED
SPACE
EXHAUST AIR
OUTDOOR AIR
RERV
Standard Features
UNIT CONSTRUCTION
• Constructed for indoor/outdoor use
• 18 ga. satin coat steel casing wall and roof panels
• 18 ga. galvanized steel floor and center partition panels
• 14 ga. galvanized steel base frame with lifting holes
• Casing interior surfaces to be lined with 1” foil faced insulation, 3 Ib /cu.ft minimum density with all
seams foil taped
• Access doors complete with full length stainless steel piano hinges, two stainless steel latches per door and
full perimeter rubber bulb seal gasket
• Powder coated exterior finish (Sky Grey)
ROTARY WHEEL ASSEMBLY
• Heavy gauge galvanized steel casing
• Removable side panels for drive access
• Inboard no-maintenance bearings
• Assembly slides in and out of unit for ease of inspection and removal
• Non-migrating water selective 4A molecular sieve desiccant
• Purge section to eliminate cross over of return air to supply air
• Wheel drive consists of a Drip proof drive motor with automatic
internal thermal overload, fixed pulley, and a durable urethane drive belt
• Performance tested using ASHRAE standard 84-1991 and ARI standard 1060
SUPPLY AND EXHAUST FANS
• Forward curved double inlet wheels
• Ball bearings
• TEFC motors with ball bearings, class B construction
• Variable v-belt drives with adjustable motor mounts
FILTERS
• 2” pleated medium efficient throwaway type
• Fresh air filters on entering side of rotary wheel
• Return air filters on entering side of rotary wheel
ELECTRICAL COMPONENTS
• Supply and exhaust fan motor fuses, contactors, and thermal overloads
• Rotary wheel drive motor contactor
• Control transformer with primary and secondary fuses
• Numbered terminal strip
• Internally pre-wired and operational tested
• ETL approved
FEA1
DEC 08/04
RERV/RERVX
Optional Accessories
DUCT CONNECTION ARRANGEMENTS
• Arrangement H (Horizontal duct connections)
• Arrangement D (Downflow, bottom duct connections)
• Arrangement C (Combination, horizontal supply, bottom return)
ROOF CURBS
•
•
•
•
CLIPLOCK roof curb to suit required arrangement (Shipped loose for field assembly)
Standard heights of 14”, 18” and 24” available
Custom heights and sloped curbs available
Spring isolation roof curb to suit required arrangement, complete with flex connectors
MISCELLANIOUS
•
•
•
•
Spring type vibration isolators (Indoor unit, hung or base mount, shipped loose for field installation)
Flexible duct connectors (Shipped loose for field installation on unit external duct connections)
22 gauge inner cabinet liner
Sensible only energy recovery wheel
HOODS AND DAMPERS
•
•
•
•
•
•
Fresh air inlet hood with entrainment filter and bird screen
Exhaust air discharge hood with bird screen
Fresh air inlet motorized low leakage parallel blade damper with end switch
Exhaust discharge motorized low leakage parallel blade damper with end switch
Gravity damper for exhaust discharge
Recirculation motorized two position damper for night set back function
FROST CONTROL
•
•
•
•
•
On-off frost control
Exhaust only frost control
Electric pre-heat frost protection
Variable frequency drive (VFD) of energy recovery wheel motor for frost control
Recirculation frost control
FREE COOL CONTROL
• Fresh air enthalpy control for free cooling (Recovery wheel shutdown)
• Fresh air ambient temperature control for free cooling (Recovery wheel shutdown)
MISCELLANIOUS ELECTRICAL
• Non-fused disconnect switch
• Variable frequency drives (VFD) for supply and exhaust fan motors (Control by others)
• Two speed motors on supply and exhaust fans (Control by others)
• Time clock - 7 day program, quartz, 100 hour battery backup, override switch
• Dirty filter pressure differential switches (Optional indictor light available)
• Remote on-off switch (Shipped loose for field installation)
• CO2 detector control (Shipped loose for field installation)
• Firestat (Duct mount, shipped loose for field installation)
• Smoke detector (Duct mount, shipped loose for field installation)
• Recovery wheel rotation sensor (Optional indictor light available)
• Programmable microprocessor control
• Air flow monitoring
OP1
DEC 08/04
RERV/RERVX
Optional Energy Saving
Accessory Descriptions
Re-circulation motorized two position damper for night set back
A full capacity re-circulation damper with a two position spring return damper actuator can be factory
mounted in the partition separating the return air plenum from the supply air compartment. This feature
will allow for unoccupied / night set back requirements, providing that some means of remote duct
mounted re-heat (and perhaps re-cool) has been designed into the ventilation supply air ducting system.
Function:
• Supply and Exhaust fan motors: de-energized.
• Energy recovery wheel motor: de-energized.
• Exhaust discharge damper: closes.
• Outside air intake damper: spring returns to closed position.
• Re-circulation damper: powered open.
• Supply fan: energized by re-circulation damper full open end switch and supplies re-circulated
return air back to the supply air duct system.
• Re-heat (and perhaps re-cool) external to the unit: energized as required from space thermostat or
discharge temperature control as supplied by others.
Option includes: Factory installed re-circulation damper, factory installed and wired two position
damper motor with end switch.
(Refer to Section 4, Optional Accessory Wiring Diagram 8)
Fresh air ambient temperature control for free cooling
Two fresh air ambient temperature controls can be factory installed to de-energize the energy recovery
wheel above 55°F and below 75°F. Both temperature controls are field adjustable to suit design
conditions.
This option prevents unnecessary heating of supply air through energy recovery during these outdoor
temperatures.
Option includes: Factory installed 2 ambient temperature controls
(Refer to Section 4, Optional Accessory Wiring Diagram 7)
Fresh air enthalpy control for free cooling
The fresh air enthalpy control has effectively the same function as the fresh air ambient temperature
control. This option includes a fresh air temperature control and a logic controller with an enthalpy sensor.
The fresh air temperature control energizes the energy recovery wheel below 55°F. The enthalpy control
senses the enthalpy of the fresh air, which is a combination of the air temperature and relative humidity.
The enthalpy control will energize the energy recovery wheel above the set point which is actually a range
of fresh air temperature -humidity combinations, for example, from approximately 63°F 80% rh, to 82°F
10% rh, for setting “A”. The enthalpy control has 4 field adjustable settings to suit design conditions.
Option includes: Factory installed enthalpy control and ambient temperature control
(Refer to Section 4, Optional Accessory Wiring Diagram 6)
OP2
DEC 08/04
INDUSTRIES INC.
RERV-256
ROTARY ENERGY RECOVERY
VENTILATOR
250 TO 600 CFM CAPACITY
52"
2"
52"
6"
16"
1-3/16"
25"
22"
41"
13-1/8"
25-1/2"
11-3/8"
56"
56"
6-1/4"
19"
INDOOR UNIT
OUTDOOR UNIT
Belt Drive
Maximum RPM : 1522
Maximum Motor Horsepower : 1
Maximum Motor Frame : 143T
Shipping Weight (less motors) : 881Ibs
Optional Fresh Air Hood with Filter
Pressure Drop Chart (Inches WC)
∆P
CFM
250
425
600
250
CFM
425
600
0.015
0.029
0.042
EXTERNAL STATIC PRESSURE (INCHES WC)
RPM
BHP
RPM
BHP
RPM
BHP
0.1
0.3
0.5
0.7
0.9
1.1
1.3
1.5
760
0.10
934
0.20
1085
0.33
856
0.13
1017
0.25
1159
0.39
942
0.18
1093
0.30
1228
0.46
1020
0.22
1163
0.35
1293
0.52
1093
0.27
1229
0.41
1345
0.59
1160
0.32
1291
0.47
1413
0.66
1223
0.37
1351
0.53
1469
0.73
1283
0.42
1407
0.60
1522
0.81
RERV256
MAR. 31/04
SPINNAKER RESERVES THE RIGHT TO CHANGE ANY OF THE INFORMATION HEREIN WITHOUT NOTICE.
ENERGY
RECOVERY
WHEEL
EFFICIENCY
86.0%
77.6%
70.1%
27 Leading Road Etobicoke, Ontario, Canada M9V 4B7
Tel: (416) 742-0598 Fax: (416) 742-4251
4846 Jennings Lane, Louisville, Kentucky, USA 40218
Tel: 1-800-932-6210 Fax: 1-800-903-7294
INDUSTRIES INC.
RERV-511
ROTARY ENERGY RECOVERY
VENTILATOR
500 TO 1100 CFM CAPACITY
52"
2"
52"
6"
16"
1-3/16"
25"
22"
41"
13-1/8"
25-1/2"
11-3/8"
56"
56"
6-1/4"
19"
INDOOR UNIT
Belt Drive
Maximum RPM : 1675
Maximum Motor Horsepower : 1 1/2
Maximum Motor Frame : 145T
Shipping Weight (less motors) : 891Ibs
OUTDOOR UNIT
Optional Fresh Air Hood with Filter
Pressure Drop Chart (Inches WC)
∆P
CFM
500
800
1100
500
CFM
800
1100
0.035
0.048
0.060
EXTERNAL STATIC PRESSURE (INCHES WC)
RPM
BHP
RPM
BHP
RPM
BHP
0.1
0.3
0.5
0.7
0.9
1.1
1.3
1.5
880
0.18
1078
0.37
1235
0.64
970
0.23
1157
0.45
1311
0.73
1052
0.28
1229
0.52
1382
0.83
1126
0.34
1298
0.59
1449
0.92
1196
0.40
1362
0.67
1510
1.02
1261
0.46
1422
0.75
1567
1.12
1323
0.52
1480
0.83
1622
1.22
1381
0.59
1535
0.91
1675
1.32
RERV511
MAR. 31/04
SPINNAKER RESERVES THE RIGHT TO CHANGE ANY OF THE INFORMATION HEREIN WITHOUT NOTICE.
ENERGY
RECOVERY
WHEEL
EFFICIENCY
81.3%
72.1%
64.0%
27 Leading Road Etobicoke, Ontario, Canada M9V 4B7
Tel: (416) 742-0598 Fax: (416) 742-4251
4846 Jennings Lane, Louisville, Kentucky, USA 40218
Tel: 1-800-932-6210 Fax: 1-800-903-7294
INDUSTRIES INC.
RERV-1019
ROTARY ENERGY RECOVERY
VENTILATOR
1000 TO 1900 CFM CAPACITY
52"
2"
52"
11"
16"
1-3/16"
25"
33"
52"
13-1/8"
25-1/2"
11-3/8"
56"
56"
6-1/4"
19"
INDOOR UNIT
Belt Drive
Maximum RPM : 1699
Maximum Motor Horsepower : 2
Maximum Motor Frame : 145T
Shipping Weight (less motors) : 1000 Ibs
OUTDOOR UNIT
∆P
CFM
1000
1225
1450
1675
1900
1000
0.065
Optional Fresh Air Hood with Filter
Pressure Drop Chart (Inches WC)
CFM
1225
1450
1675
0.074
0.087
0.097
EXTERNAL STATIC PRESSURE (INCHES WC)
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
0.1
0.3
0.5
0.7
0.9
1.1
1.3
1.5
962
0.34
1032
0.47
1099
0.63
1155
0.81
1211
1.01
1061
0.42
1126
0.57
1189
0.74
1240
0.93
1291
1.14
1150
0.51
1212
0.66
1272
0.85
1320
1.05
1368
1.28
1230
0.59
1291
0.76
1349
0.96
1395
1.18
1441
1.42
1305
0.68
1365
0.87
1422
1.08
1467
1.31
1510
1.56
1373
0.77
1435
0.97
1491
1.20
1536
1.44
1577
1.71
1436
0.85
1500
1.07
1555
1.32
1599
1.57
1641
1.85
1495
0.95
1562
1.18
1617
1.44
1661
1.70
1699
1.99
RERV1019
MAR. 31/04
SPINNAKER RESERVES THE RIGHT TO CHANGE ANY OF THE INFORMATION HEREIN WITHOUT NOTICE.
1900
0.108
ENERGY
RECOVERY
WHEEL
EFFICIENCY
80.5%
76.7%
73.1%
69.7%
66.4%
27 Leading Road Etobicoke, Ontario, Canada M9V 4B7
Tel: (416) 742-0598 Fax: (416) 742-4251
4846 Jennings Lane, Louisville, Kentucky, USA 40218
Tel: 1-800-932-6210 Fax: 1-800-903-7294
INDUSTRIES INC.
RERV-1324
ROTARY ENERGY RECOVERY
VENTILATOR
1300 TO 2400 CFM CAPACITY
52"
2"
52"
11"
16"
1-3/16"
25"
33"
52"
13-1/8"
25-1/2"
11-3/8"
56"
6-1/4"
56"
19"
INDOOR UNIT
Belt Drive
Maximum RPM : 1655
Maximum Motor Horsepower : 3
Maximum Motor Frame : 182T
Shipping Weight (less motors) : 1030 Ibs
OUTDOOR UNIT
Optional Fresh Air Hood with Filter
Pressure Drop Chart (Inches WC)
∆P
CFM
1300
1575
1850
2125
2400
1300
0.075
1575
0.097
CFM
1850
0.119
2125
0.141
EXTERNAL STATIC PRESSURE (INCHES WC)
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
0.1
0.3
0.5
0.7
0.9
1.1
1.3
1.5
912
0.39
977
0.55
1043
0.74
1125
1.00
1204
1.31
1018
0.49
1075
0.66
1126
0.86
1197
1.12
1271
1.44
1114
0.58
1165
0.77
1211
0.98
1268
1.25
1336
1.58
1202
0.68
1251
0.89
1292
1.11
1343
1.39
1398
1.72
1283
0.79
1330
1.01
1369
1.25
1415
1.54
1463
1.88
1358
0.89
1405
1.13
1441
1.38
1485
1.69
1528
2.04
1429
1.00
1475
1.25
1511
1.52
1553
1.84
1592
2.20
1495
1.11
1542
1.38
1578
1.66
1617
2.00
1655
2.37
RERV1324
MAR. 31/04
SPINNAKER RESERVES THE RIGHT TO CHANGE ANY OF THE INFORMATION HEREIN WITHOUT NOTICE.
2400
0.163
ENERGY
RECOVERY
WHEEL
EFFICIENCY
80.0%
76.3%
72.9%
69.6%
66.5%
27 Leading Road Etobicoke, Ontario, Canada M9V 4B7
Tel: (416) 742-0598 Fax: (416) 742-4251
4846 Jennings Lane, Louisville, Kentucky, USA 40218
Tel: 1-800-932-6210 Fax: 1-800-903-7294
INDUSTRIES INC.
RERV-1533
ROTARY ENERGY RECOVERY
VENTILATOR
1500 TO 3300 CFM CAPACITY
64"
2"
64"
10"
24"
1-3/16"
40"
43"
64"
15-3/4"
36"
13-5/8"
8"
68"
68"
20"
INDOOR UNIT
Belt Drive
Maximum RPM : 1429
Maximum Motor Horsepower : 3
Maximum Motor Frame : 182T
Shipping Weight (less motors) : 1450 Ibs
OUTDOOR UNIT
Optional Fresh Air Hood with Filter
Pressure Drop Chart (Inches WC)
CFM
∆P
CFM
1500
1750
2000
2250
2500
2750
3000
3300
1500
1750
2000
2250
2500
2750
3000
3300
0.065
0.070
0.077
0.085
0.090
0.105
0.120
0.132
EXTERNAL STATIC PRESSURE (INCHES WC)
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
0.1
0.3
0.5
0.7
0.9
1.1
1.3
1.5
715
0.30
749
0.39
787
0.51
823
0.64
861
0.80
898
0.98
934
1.18
1049
1.61
814
0.39
840
0.49
872
0.61
902
0.75
934
0.91
968
1.10
1000
1.31
1108
1.75
904
0.48
926
0.58
952
0.72
977
0.86
1005
1.03
1033
1.22
1063
1.44
1165
1.90
994
0.60
1005
0.69
1027
0.82
1049
0.98
1072
1.16
1097
1.35
1123
1.58
1221
2.05
1082
0.72
1079
0.81
1099
0.94
1117
1.10
1138
1.29
1159
1.49
1182
1.72
1275
2.21
1159
0.85
1158
0.94
1167
1.07
1183
1.22
1201
1.42
1220
1.64
1239
1.86
1327
2.37
1231
0.97
1234
1.09
1232
1.20
1246
1.37
1261
1.56
1278
1.78
1296
2.02
1378
2.53
1296
1.09
1305
1.24
1299
1.35
1306
1.51
1320
1.69
1335
1.93
1350
2.18
1429
2.70
RERV1533
MAR. 31/04
SPINNAKER RESERVES THE RIGHT TO CHANGE ANY OF THE INFORMATION HEREIN WITHOUT NOTICE.
ENERGY
RECOVERY
WHEEL
EFFICIENCY
82.9%
80.3%
77.9%
75.5%
73.2%
71.0%
68.9%
66.4%
27 Leading Road Etobicoke, Ontario, Canada M9V 4B7
Tel: (416) 742-0598 Fax: (416) 742-4251
4846 Jennings Lane, Louisville, Kentucky, USA 40218
Tel: 1-800-932-6210 Fax: 1-800-903-7294
INDUSTRIES INC.
RERV-3045
ROTARY ENERGY RECOVERY
VENTILATOR
3000 TO 4500 CFM CAPACITY
64"
2"
64"
10"
24"
1-3/16"
40"
43"
64"
15-3/4"
36"
13-5/8"
8"
68"
68"
20"
INDOOR UNIT
Belt Drive
Maximum RPM : 1421
Maximum Motor Horsepower : 5
Maximum Motor Frame : 184T
Shipping Weight (less motors) : 1570 Ibs
OUTDOOR UNIT
Optional Fresh Air Hood with Filter
Pressure Drop Chart (Inches WC)
∆P
CFM
3000
3250
3500
3750
4000
4250
4500
3000
3250
3500
CFM
3750
4000
4250
4500
0.120
0.125
0.135
0.145
0.155
0.165
0.185
EXTERNAL STATIC PRESSURE (INCHES WC)
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
0.1
0.3
0.5
0.7
0.9
1.1
1.3
1.5
874
1.00
909
1.27
942
1.49
973
1.74
1012
2.04
1043
2.34
1080
2.69
943
1.20
974
1.42
1005
1.65
1036
1.91
1069
2.20
1099
2.52
1132
2.80
1009
1.33
1038
1.56
1065
1.81
1094
2.08
1125
2.38
1152
2.69
1184
3.07
1072
1.46
1101
1.71
1123
1.96
1150
2.25
1178
2.57
1204
2.89
1234
3.26
1131
1.60
1156
1.84
1179
2.12
1204
2.42
1230
2.75
1254
3.09
1282
3.47
1190
1.74
1211
1.99
1233
2.26
1256
2.58
1281
2.92
1303
3.28
1330
3.67
1247
1.88
1266
2.15
1285
2.43
1307
2.74
1331
3.10
1351
3.47
1376
3.88
1303
2.04
1319
2.30
1336
2.59
1356
2.91
1379
3.27
1398
3.65
1421
4.08
RERV3045
MAR. 31/04
SPINNAKER RESERVES THE RIGHT TO CHANGE ANY OF THE INFORMATION HEREIN WITHOUT NOTICE.
ENERGY
RECOVERY
WHEEL
EFFICIENCY
75.0%
73.2%
71.5%
69.9%
68.2%
66.7%
65.1%
27 Leading Road Etobicoke, Ontario, Canada M9V 4B7
Tel: (416) 742-0598 Fax: (416) 742-4251
4846 Jennings Lane, Louisville, Kentucky, USA 40218
Tel: 1-800-932-6210 Fax: 1-800-903-7294
INDUSTRIES INC.
RERV-3550
ROTARY ENERGY RECOVERY
VENTILATOR
3550 TO 5000 CFM CAPACITY
64"
2"
64"
10"
24"
1-3/16"
40"
43"
64"
15-3/4"
36"
13-5/8"
8"
68"
68"
20"
INDOOR UNIT
Belt Drive
Maximum RPM : 1607
Maximum Motor Horsepower : 7 1/2
Maximum Motor Frame : 213T
Shipping Weight (less motors) : 1570 Ibs
OUTDOOR UNIT
Optional Fresh Air Hood with Filter
Pressure Drop Chart (Inches WC)
∆P
CFM
3550
3800
4050
4300
4550
4800
5000
3550
0.126
3800
0.135
4050
0.143
CFM
4300
0.152
4550
0.161
EXTERNAL STATIC PRESSURE (INCHES WC)
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
0.1
0.3
0.5
0.7
0.9
1.1
1.3
1.5
859
1.33
1132
2.22
1170
2.56
1204
2.93
1242
3.34
1279
3.78
1308
4.16
1146
2.05
1186
2.38
1222
2.74
1254
3.11
1290
3.53
1325
3.99
1354
4.38
1201
2.21
1239
2.55
1273
2.92
1303
3.30
1337
3.73
1371
4.19
1398
4.59
1254
2.37
1291
2.73
1322
3.10
1351
3.49
1383
3.93
1415
4.40
1442
4.81
1306
2.53
1349
2.90
1370
3.28
1397
3.68
1428
4.13
1459
4.61
1484
5.02
1356
2.70
1389
3.07
1417
3.46
1443
3.87
1472
4.33
1502
4.82
1526
5.24
1405
2.87
1436
3.25
1463
3.65
1487
4.07
1516
4.53
1543
5.03
1567
5.46
1453
3.04
1482
3.43
1507
3.83
1531
4.26
1558
4.74
1585
5.24
1607
5.69
RERV3550
APR. 01/04
SPINNAKER RESERVES THE RIGHT TO CHANGE ANY OF THE INFORMATION HEREIN WITHOUT NOTICE.
4800
0.170
5000
0.177
ENERGY
RECOVERY
WHEEL
EFFICIENCY
79.0%
77.4%
76.1%
74.9%
73.6%
72.4%
71.5%
27 Leading Road Etobicoke, Ontario, Canada M9V 4B7
Tel: (416) 742-0598 Fax: (416) 742-4251
4846 Jennings Lane, Louisville, Kentucky, USA 40218
Tel: 1-800-932-6210 Fax: 1-800-903-7294
INDUSTRIES INC.
RERV-4055
ROTARY ENERGY RECOVERY
VENTILATOR
4000 TO 5500 CFM CAPACITY
110"
88"
2"
12"
24"
1-3/16"
40"
70"
34-3/4"
21-7/8"
36"
18-7/8"
92"
114"
13-1/4"
20"
INDOOR UNIT
Belt Drive
Maximum RPM - 1022
Maximum Motor Horsepower - 5
Maximum Motor Frame - 184T
Shipping Weight (less motors) - 2470
OUTDOOR UNIT
Optional Fresh Air Hood with Filter
Pressure Drop Chart (Inches WC)
∆P
CFM
4000
4250
4500
4750
5000
5250
5500
CFM
4000 4250 4500 4750 5000 5250
0.123 0.127 0.135 0.145 0.160 0.168
EXTERNAL STATIC PRESSURE (INCHES WC)
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
0.1
0.3
0.5
0.7
0.9
1.1
1.3
1.5
697
1.32
720
1.51
743
1.73
765
1.97
787
2.22
816
2.53
837
2.82
758
1.49
779
1.70
800
1.93
820
2.17
840
2.44
867
2.75
887
3.06
816
1.67
835
1.89
854
2.13
872
2.38
891
2.65
917
2.98
935
3.30
872
1.86
889
2.09
905
2.33
922
2.59
940
2.87
964
3.21
981
3.53
930
2.07
942
2.29
956
2.54
971
2.81
987
3.10
1009
3.44
1025
3.78
985
2.29
996
2.52
1006
2.76
1019
3.03
1032
3.33
1054
3.68
1068
4.02
1039
2.52
1048
2.75
1057
3.0
1066
3.27
1077
3.56
1097
3.92
1110
4.27
1090
2.75
1098
2.99
1106
3.25
1114
3.52
1123
3.81
1139
4.17
1154
4.53
RERV4055
APR. 22/04
SPINNAKER RESERVES THE RIGHT TO CHANGE ANY OF THE INFORMATION HEREIN WITHOUT NOTICE.
5500
0.176
ENERGY
RECOVERY
WHEEL
EFFICIENCY
74.0%
72.6%
71.3%
70.0%
68.7%
67.4%
66.2%
27 Leading Road Etobicoke, Ontario, Canada M9V 4B7
Tel: (416) 742-0598 Fax: (416) 742-4251
4846 Jennings Lane, Louisville, Kentucky, USA 40218
Tel: 1-800-932-6210 Fax: 1-800-903-7294
INDUSTRIES INC.
RERV-4567
ROTARY ENERGY RECOVERY
VENTILATOR
4500 TO 6700 CFM CAPACITY
110"
88"
2"
6"
26"
1-3/16"
70"
88"
52-3/4"
21-7/8"
18-7/8"
35-1/2"
114"
92"
13-1/4"
20"
INDOOR UNIT
Belt Drive
Maximum RPM - 987
Maximum Motor Horsepower - 7 1/2
Maximum Motor Frame - 213T
Shipping Weight (less motors) - 2830
OUTDOOR UNIT
Optional Fresh Air Hood with Filter
Pressure Drop Chart (Inches WC)
∆P
CFM
4500
5000
5500
6000
6350
6700
5000
0.110
5500
0.123
CFM
6000
6500
0.130
0.145
7000
0.155
EXTERNAL STATIC PRESSURE (INCHES WC)
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
0.1
0.3
0.5
0.7
0.9
1.1
1.3
1.5
513
1.08
547
1.40
577
1.76
608
2.17
669
2.55
696
2.93
573
1.26
602
1.60
628
1.98
654
2.41
712
2.80
737
3.19
640
1.51
656
1.79
678
2.20
700
2.65
755
3.07
778
3.47
706
1.86
719
2.12
727
2.40
746
2.89
797
3.35
818
3.76
764
2.19
779
2.51
811
2.97
791
3.11
839
3.66
858
4.07
816
2.51
832
2.88
841
3.21
844
3.50
885
4.05
897
4.40
963
2.83
880
3.24
891
3.62
8.96
3.96
932
4.50
943
4.85
907
3.15
925
3.59
937
4.02
944
4.42
977
4.95
987
5.32
RERV4567
APR. 01/04
SPINNAKER RESERVES THE RIGHT TO CHANGE ANY OF THE INFORMATION HEREIN WITHOUT NOTICE.
7200
0.160
ENERGY
RECOVERY
WHEEL
EFFICIENCY
76.1%
73.8%
71.6%
69.5%
68.1%
66.7%
27 Leading Road Etobicoke, Ontario, Canada M9V 4B7
Tel: (416) 742-0598 Fax: (416) 742-4251
4846 Jennings Lane, Louisville, Kentucky, USA 40218
Tel: 1-800-932-6210 Fax: 1-800-903-7294
INDUSTRIES INC.
RERV-5082
ROTARY ENERGY RECOVERY
VENTILATOR
5000 TO 8200 CFM CAPACITY
110"
88"
2"
6"
26"
1-3/16"
70"
88"
52-3/4"
21-7/8"
18-7/8"
35-1/2"
114"
13-1/4"
92"
20"
INDOOR UNIT
Belt Drive
Maximum RPM - 982
Maximum Motor Horsepower - 7 1/2
Maximum Motor Frame - 213T
Shipping Weight (less motors) - 2940
OUTDOOR UNIT
Optional Fresh Air Hood with Filter
Pressure Drop Chart (Inches WC)
CFM
∆P
CFM
5000
5500
6000
6500
7000
7500
7850
8200
5000
5500
6000
6500
7000
7500
7850
8200
0.110
0.122
0.133
0.144
0.155
0.166
0.174
0.182
EXTERNAL STATIC PRESSURE (INCHES WC)
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
ENERGY
RECOVERY
WHEEL
EFFICIENCY
0.1
0.3
0.5
0.7
0.9
1.1
1.3
1.5
515
1.29
546
1.62
576
2.00
608
2.44
636
2.91
571
1.49
598
1.85
623
2.25
651
2.71
676
3.20
626
1.68
648
2.07
670
2.49
694
2.98
717
3.50
682
1.90
697
2.28
715
2.73
737
3.24
758
3.37
747
2.29
7.49
2.51
761
2.96
780
3.50
800
3.62
803
2.67
808
2.95
806
3.18
821
3.75
836
4.35
853
3.04
861
3.37
862
3.65
863
3.98
875
4.62
900
3.39
909
3.78
912
4.11
913
4.43
914
4.87
77.8%
710
3.61
726
4.00
744
4.45
748
3.88
763
4.29
779
4.74
785
4.16
799
4.58
814
5.04
822
4.45
834
4.88
848
5.35
858
4.76
869
5.19
882
5.66
895
5.08
904
5.51
916
5.99
930
5.41
938
5.85
949
6.33
966
5.76
973
6.20
982
6.68
68.8%
RERV5082
APR. 01/04
SPINNAKER RESERVES THE RIGHT TO CHANGE ANY OF THE INFORMATION HEREIN WITHOUT NOTICE.
75.9%
74.1%
72.3%
70.5%
67.6%
66.5%
27 Leading Road Etobicoke, Ontario, Canada M9V 4B7
Tel: (416) 742-0598 Fax: (416) 742-4251
4846 Jennings Lane, Louisville, Kentucky, USA 40218
Tel: 1-800-932-6210 Fax: 1-800-903-7294
INDUSTRIES INC.
RERV-6098
ROTARY ENERGY RECOVERY
VENTILATOR
6000 TO 9800 CFM CAPACITY
110"
88"
2"
6"
26"
1-3/16"
70"
88"
52-3/4"
21-7/8"
18-7/8"
35-1/2"
114"
92"
13-1/4"
20"
INDOOR UNIT
Belt Drive
Maximum RPM - 1077
Maximum Motor Horsepower - 10
Maximum Motor Frame - 215T
Shipping Weight (less motors) - 3040 lbs
OUTDOOR UNIT
Optional Fresh Air Hood with Filter
Pressure Drop Chart (Inches WC)
CFM
∆P
CFM
6000
6500
7000
7500
8000
8500
9000
9400
9800
6000
6500
7000
7500
8000
8500
9000
9400
9800
0.130
0.145
0.155
0.170
0.188
0.205
0.220
0.229
0.239
EXTERNAL STATIC PRESSURE (INCHES WC)
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
ENERGY
RECOVERY
WHEEL
EFFICIENCY
0.1
0.3
0.5
0.7
0.9
1.1
1.3
1.5
656
2.42
688
2.94
718
3.50
747
4.12
777
4.82
808
5.59
841
6.46
702
2.66
730
3.20
757
3.79
784
4.44
812
5.15
841
5.95
872
6.84
748
2.90
773
3.46
797
4.07
822
4.74
847
5.48
874
6.30
904
7.22
793
3.12
815
3.71
837
4.35
859
5.05
882
5.81
907
6.65
935
7.59
846
3.52
856
3.95
876
4.62
895
5.34
917
6.13
940
7.00
966
7.96
898
3.98
905
4.35
914
4.88
932
5.63
951
6.45
973
7.35
997
8.33
898
3.98
954
4.86
956
5.22
968
5.91
985
6.76
1005
7.68
1028
870
990
4.88
1000
5.36
1003
5.78
1004
6.18
1019
7.06
1037
8.01
1059
9.05
81.6%
861
6.78
875
7.43
892
7.17
905
7.77
922
7.46
934
812
952
7.81
964
8.48
982
8.17
992
8.85
1010
8.53
1021
9.21
1041
8.90
1049
9.59
1070
9.29
1077
9.98
72.7%
RERV6098
APR. 01/04
SPINNAKER RESERVES THE RIGHT TO CHANGE ANY OF THE INFORMATION HEREIN WITHOUT NOTICE.
80.2%
78.8%
77.5%
76.2%
75.0%
73.7%
71.8%
27 Leading Road Etobicoke, Ontario, Canada M9V 4B7
Tel: (416) 742-0598 Fax: (416) 742-4251
4846 Jennings Lane, Louisville, Kentucky, USA 40218
Tel: 1-800-932-6210 Fax: 1-800-903-7294
INDUSTRIES INC.
RERV-7011
ROTARY ENERGY RECOVERY
VENTILATOR
7000 TO 11000 CFM CAPACITY
110"
88"
2"
6"
26"
1-3/16"
70"
88"
52-3/4"
21-7/8"
18-7/8"
35-1/2"
114"
92"
13-1/4"
20"
INDOOR UNIT
Belt Drive
Maximum RPM - 1045
Maximum Motor Horsepower - 15
Maximum Motor Frame - 254T
Shipping Weight (less motors) - 3250
OUTDOOR UNIT
Optional Fresh Air Hood with Filter
Pressure Drop Chart (Inches WC)
CFM
∆P
CFM
7000
7500
8000
8500
9000
9500
10000
10500
11000
7000
7500
8000
8500
9000
9500
0.105
0.115
0.124
0.130
0.138
0.144
1000
0
0.155
1050
0
0.165
ENERGY
RECOVERY
WHEEL
EFFICIENCY
82.0%
EXTERNAL STATIC PRESSURE (INCHES WC)
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
0.1
0.3
0.5
0.7
0.9
1.1
1.3
1.5
624
2.82
648
3.31
679
3.91
710
4.56
741
5.29
771
6.08
802
6.92
831
7.87
860
8.88
664
3.12
686
3.62
715
4.24
744
4.92
773
5.67
802
6.47
831
7.37
860
8.34
887
9.33
705
3.41
724
3.94
752
4.58
778
5.28
805
6.05
832
6.87
860
7.79
887
8.75
914
9.79
745
3.70
762
4.25
798
5.02
812
5.63
837
6.42
862
7.27
889
8.21
914
9.19
940
10.26
785
3.99
800
4.56
823
5.25
845
5.99
869
6.80
893
7.67
918
8.63
942
9.63
966
10.72
824
4.27
837
4.87
858
5.58
878
6.35
901
7.18
923
8.07
947
9.05
969
10.07
992
11.18
864
4.54
874
5.17
892
591
911
6.70
932
7.55
953
8.47
975
9.47
997
10.52
1019
11.64
902
4.80
910
5.46
927
6.23
944
7.04
963
7.93
982
8.87
994
9.75
1024
10.96
1045
12.11
RERV7011
APR. 01/04
SPINNAKER RESERVES THE RIGHT TO CHANGE ANY OF THE INFORMATION HEREIN WITHOUT NOTICE.
11000
0.175
80.8%
79.7%
78.6%
77.5%
76.4%
75.3%
74.3%
73.2%
27 Leading Road Etobicoke, Ontario, Canada M9V 4B7
Tel: (416) 742-0598 Fax: (416) 742-4251
4846 Jennings Lane, Louisville, Kentucky, USA 40218
Tel: 1-800-932-6210 Fax: 1-800-903-7294
INDUSTRIES INC.
RERV-15000
ROTARY ENERGY RECOVERY
VENTILATOR
12000 TO 15000 CFM CAPACITY
104"
135"
2"
3"
1-3/16"
48"
94"
104"
56"
27-1/4"
48"
27-1/4"
12"
108"
139"
30"
INDOOR UNIT
OUTDOOR UNIT
Belt Drive
Maximum RPM - 943
Maximum Motor Horsepower - 20
Maximum Motor Frame - 256T
Shipping Weight (less motors) - 5470
∆P
EXTERNAL STATIC PRESSURE (INCHES WC)
CFM
12000
12500
13000
13500
14000
14500
15000
12000
0.100
Optional Fresh Air Hood wit h Filter
Pressure Drop Chart (Inches WC)
CFM
12500
13000 13500
14000
14500
0.110
0.119
0.125
0.133
0.140
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
0.1
0.3
0.5
0.7
0.9
1.1
1.3
1.5
644
6.25
669
7.03
695
7.89
717
8.75
741
9.69
765
10.71
788
11.78
673
6.72
697
7.52
721
8.40
743
9.28
765
10.23
789
11.27
811
12.36
700
7.20
723
8.02
747
8.92
768
9.81
790
10.78
812
11.84
834
12.94
728
7.70
750
8.53
773
9.45
793
10.36
814
11.35
835
12.42
857
13.54
754
8 .20
776
9.06
798
9.99
817
10.91
837
11.92
858
13.01
879
14.15
781
8.72
801
9.60
822
10.54
841
11.49
860
12.50
880
13.61
901
14.77
806
9.26
826
10.15
846
11.11
864
12.07
883
13.10
903
14.22
922
15.39
832
9.81
850
10.71
870
11.69
887
12.66
905
13.71
925
14.84
943
16.03
RERV15000
APR. 01/04
SPINNAKER RESERVES THE RIGHT TO CHANGE ANY OF THE INFORMATION HEREIN WITHOUT NOTICE.
15000
0.151
ENERGY
RECOVERY
WHEEL
EFFICIENCY
78.0%
77.2%
76.4%
75.6%
74.9%
74.1%
73.3%
27 Leading Road Etobicoke, Ontario, Canada M9V 4B7
Tel: (416) 742-0598 Fax: (416) 742-4251
4846 Jennings Lane, Louisville, Kentucky, USA 40218
Tel: 1-800-932-6210 Fax: 1-800-903-7294
INDUSTRIES INC.
RERV-20000
ROTARY ENERGY RECOVERY
VENTILATOR
16000 TO 20000 CFM CAPACITY
151"
114"
2"
3"
1-3/16"
48"
106"
114"
62-3/4"
31-1/4"
48"
31-1/4"
12"
118"
155"
30"
INDOOR UNIT
Belt Drive
Maximum RPM - 844
Maximum Motor Horsepower - 25
Maximum Motor Frame - 284T
Shipping Weight (less motors) - 6745
OUTDOOR UNIT
Optional Fresh Air Hood with Filter
Pressure Drop Chart (Inches WC)
CFM
∆P
CFM
16000
16500
17000
17500
18000
18500
19000
19500
20000
16000
16500
17000
17500
18000
18500
19000
19500
20000
0.115
0.125
0.136
0.143
0.155
0.164
0.175
0.187
0.195
EXTERNAL STATIC PRESSURE (INCHES WC)
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
ENERGY
RECOVERY
WHEEL
EFFICIENCY
0.1
0.3
0.5
0.7
0.9
1.1
1.3
1.5
575
8.40
591
9.16
610
10.03
626
10.19
641
11.78
657
12.73
674
13.76
601
9.07
616
9.86
634
10.75
650
11.64
665
12.54
680
13.50
697
14.56
626
9.75
641
10.55
658
11.47
673
12.38
688
13.29
703
14.28
718
15.35
651
10.44
665
11.26
681
12.19
696
13.12
710
14.05
724
15.07
739
16.15
675
11.13
688
11.98
704
12.92
718
13.88
731
14.83
745
15.86
760
16.96
698
11.85
711
12.71
726
13.67
740
14.65
753
15.62
766
16.66
781
17.79
721
12.57
733
13.45
748
14.44
761
15.42
774
16.41
787
17.47
801
18.62
743
13.31
755
14.20
770
15.21
782
16.21
794
17.22
807
18.30
820
19.46
77.7%
690
14.78
704
15.82
711
15.60
725
16.65
733
16.42
746
17.49
754
17.24
766
18.33
774
18.07
786
19.18
794
18.91
806
20.04
813
19.76
825
20.90
833
20.63
844
21.79
73.6%
RERV20000
APR. 02/04
SPINNAKER RESERVES THE RIGHT TO CHANGE ANY OF THE INFORMATION HEREIN WITHOUT NOTICE.
77.1%
76.5%
75.9%
75.3%
74.8%
74.2%
73.0%
27 Leading Road Etobicoke, Ontario, Canada M9V 4B7
Tel: (416) 742-0598 Fax: (416) 742-4251
4846 Jennings Lane, Louisville, Kentucky, USA 40218
Tel: 1-800-932-6210 Fax: 1-800-903-7294
MODEL SERIES RERV
ROTARY ENERGY RECOVERY VENTILATORS
DUCT CONNECTIONS
UNIT MODEL
RERV-256
RERV-511
RERV-1019
RERV-1324
RERV-1533
RERV-3045
RERV-3550
RERV-4055
RERV-4567
RERV-5082
RERV-6098
RERV-7011
RERV-15000
RERV-20000
A
52
52
52
52
64
64
64
88
88
88
88
88
104
114
B
52
52
52
52
64
64
64
110
110
110
110
110
135
151
C
41
41
52
52
64
64
64
70
88
88
88
88
104
114
D
14
14
14
14
20
20
20
30
30
30
30
30
40
47
E
20
20
20
20
22
22
22
35
35
35
35
35
47
47
F
13-1/8
13-1/8
13-1/8
13-1/8
15-3/4
15-3/4
15-3/4
21-7/8
21-7/8
21-7/8
21-7/8
21-7/8
27-1/4
31-1/4
G
11-3/8
11-3/8
11-3/8
11-3/8
13-5/8
13-5/8
13-5/8
18-7/8
18-7/8
18-7/8
18-7/8
18-7/8
27-1/4
31-1/4
H
5
5
5
5
6-1/2
6-1/2
6-1/2
10
10
10
10
10
12
15
J
22
22
33
33
43
43
43
34-3/4
52-3/4
52-3/4
52-3/4
52-3/4
6
6
L
3
3
3
3
3
3
3
3
3
3
3
3
4
4
M
7
7
7
7
8
8
8
6
6
6
6
6
6
6
N
3
3
3
3
3
3
3
8
8
8
8
8
4
4
P
11
11
17
17
19
19
19
17
24
24
24
24
4
4
ARRANGEMENT D - DOWNFLOW
BOTTOM DUCT CONNECTIONS
ARRANGEMENT H
HORIZONTAL DUCT CONNECTIONS
ARRANGEMENT C
COMBINATION DUCT CONNECTIONS
RERVDUCT
JUNE 17/04
SPINNAKER RESERVES THE RIGHT TO CHANGE ANY OF THE INFORMATION HEREIN WITHOUT NOTICE.
27 Leading Road Etobicoke, Ontario, Canada M9V 4B7
Tel: (416) 742-0598 Fax: (416) 742-4251
4846 Jennings Lane, Louisville, Kentucky, USA 40218
Tel: 1-800-932-6210 Fax: 1-800-903-7294
Q
3
3
3
3
3
3
3
3
3
3
3
3
4
4
INDOOR FRESH AIR INLET AND
EXHAUST AIR DISCHARGE DAMPERS
TO SUIT
MODEL SERIES RERV/RERVX
OPTIONAL
FRESH AIR INTAKE
MOTORIZED DAMPER
ASSEMBLY
OPTIONAL
EXHAUST AIR DISCHARGE
MOTORIZED DAMPER
ASSEMBLY
OPTIONAL
EXHAUST AIR DISCHARGE
GRAVITY DAMPER
ASSEMBLY
RERV-DMP1
MAR. 10/04
SPINNAKER RESERVES THE RIGHT TO CHANGE ANY OF THE INFORMATION HEREIN WITHOUT NOTICE.
27 Leading Road Etobicoke, Ontario, Canada M9V 4B7
Tel: (416) 742-0598 Fax: (416) 742-4251
4846 Jennings Lane, Louisville, Kentucky, USA 40218
Tel: 1-800-932-6210 Fax: 1-800-903-7294
CLIPLOCK 1000 ROOF CURB
MODEL SERIES RERV
TO SUIT
FEATURES:
ARRANGEMENT D/C
HEAVY GAUGE GALVANIZED STEEL CONSTRUCTION
2 x 3" WOOD PERIMETER NAILER
PATENTED CLIPLOCK DESIGN FOR EASE OF ASSEMBLY
NEOPRENE GASKET
OPTIONS:
STAINLESS STEEL OR ALUMINUM CONSTRUCTION
INTERNAL 1" INSULATION
CLIPLOCK CORNER DETAIL
TOP EDGE
WOOD NAILER STRIP
BOTTOM FLANGE
TYPICAL SLOT
TYPICAL LOCKING TAB
NOTE: SEE CLIPLOCK 1000 INSTALLATION INSTRUCTIONS
FOR COMPLETE ASSEMBLY AND INSTALLATION
PROCEDURES AND REQUIREMENTS.
RERVRCA2
DEC 01 / 04
SPINNAKER RESERVES THE RIGHT TO CHANGE ANY OF THE INFORMATION HEREIN WITHOUT NOTICE.
27 Leading Road Etobicoke, Ontario, Canada M9V 4B7
Tel: (416) 742-0598 Fax: (416) 742-4251
4846 Jennings Lane, Louisville, Kentucky, USA 40218
Tel: 1-800-932-6210 Fax: 1-800-903-7294
CLIPLOCK 1000 ROOF CURB
MODEL SERIES RERV
TO SUIT
ARRANGEMENT H
FEATURES:
HEAVY GAUGE GALVANIZED STEEL CONSTRUCTION
2 x 3" WOOD PERIMETER NAILER
PATENTED CLIPLOCK DESIGN FOR EASE OF ASSEMBLY
OPTIONS:
STAINLESS STEEL OR ALUMINUM CONSTRUCTION
NEOPRENE GASKET
INTERNAL 1" INSULATION
CLIPLOCK CORNER DETAIL
TOP EDGE
WOOD NAILER STRIP
BOTTOM FLANGE
TYPICAL SLOT
TYPICAL LOCKING TAB
NOTE: SEE CLIPLOCK 1000 INSTALLATION INSTRUCTIONS
FOR COMPLETE ASSEMBLY AND INSTALLATION
PROCEDURES AND REQUIREMENTS.
RERVRCA1
DEC 01 / 04
SPINNAKER RESERVES THE RIGHT TO CHANGE ANY OF THE INFORMATION HEREIN WITHOUT NOTICE.
27 Leading Road Etobicoke, Ontario, Canada M9V 4B7
Tel: (416) 742-0598 Fax: (416) 742-4251
4846 Jennings Lane, Louisville, Kentucky, USA 40218
Tel: 1-800-932-6210 Fax: 1-800-903-7294
CLIPLOCK ROOF CURB
RERV-15000 AND RERV 20000
TO SUIT
FEATURES:
HEAVY GAUGE GALVANIZED STEEL CONSTRUCTION
2 x 3" WOOD PERIMETER NAILER
PATENTED CLIPLOCK DESIGN FOR EASE OF ASSEMBLY
ARRANGEMENT D/C
OPTIONS:
STAINLESS STEEL OR ALUMINUM CONSTRUCTION
NEOPRENE GASKET
INTERNAL 1" INSULATION
CLIPLOCK CORNER DETAIL
TOP EDGE
WOOD NAILER STRIP
BOTTOM FLANGE
TYPICAL SLOT
TYPICAL LOCKING TAB
NOTE: SEE CLIPLOCK 1000 INSTALLATION INSTRUCTIONS
FOR COMPLETE ASSEMBLY AND INSTALLATION
PROCEDURES AND REQUIREMENTS.
RERVRC9
DEC 01 / 04
SPINNAKER RESERVES THE RIGHT TO CHANGE ANY OF THE INFORMATION HEREIN WITHOUT NOTICE.
27 Leading Road Etobicoke, Ontario, Canada M9V 4B7
Tel: (416) 742-0598 Fax: (416) 742-4251
4846 Jennings Lane, Louisville, Kentucky, USA 40218
Tel: 1-800-932-6210 Fax: 1-800-903-7294
CLIPLOCK ROOF CURB
RERV-15000 AND RERV 20000
TO SUIT
ARRANGEMENT H
RERVRC8
DEC 01 / 04
SPINNAKER RESERVES THE RIGHT TO CHANGE ANY OF THE INFORMATION HEREIN WITHOUT NOTICE.
27 Leading Road Etobicoke, Ontario, Canada M9V 4B7
Tel: (416) 742-0598 Fax: (416) 742-4251
4846 Jennings Lane, Louisville, Kentucky, USA 40218
Tel: 1-800-932-6210 Fax: 1-800-903-7294
SERIES 4000 ISOLATION CURB
MODEL SERIES RERV
FEATURES:
ONE PIECE FULLY ASSEMBLED CONSTRUCTION
HEAVY GAUGE STEEL
ARRANGEMENT D / C
MITERED CORNERS, CONTINUOUSLY WELDED TO GUARD
AGAINST WATER LEAKAGE
FLEXIBLE NON-ABRASIVE WEATHER SEAL
FREE STANDING 2" DEFLECTION SPRINGS WITH LACQUER
BASED POLY-VYNYL FINISH
NEOPRENE COVERED NON-SKID SPRING BASE PLATE WITH
RAISED ACOUSTICAL CUP
SUPPLY AND RETURN AIR OPENING FLEX CONNECTORS
C
D
J
H
3
22-1/2"
3
G
F
B
E
A
RERVIC1
APR. 28/04
SPINNAKER RESERVES THE RIGHT TO CHANGE ANY OF THE INFORMATION HEREIN WITHOUT NOTICE.
27 Leading Road Etobicoke, Ontario, Canada M9V 4B7
Tel: (416) 742-0598 Fax: (416) 742-4251
4846 Jennings Lane, Louisville, Kentucky, USA 40218
Tel: 1-800-932-6210 Fax: 1-800-903-7294
SERIES 4000 ISOLATION CURB
MODEL SERIES RERV
FEATURES:
ONE PIECE FULLY ASSEMBLED CONSTRUCTION
HEAVY GAUGE STEEL
ARRANGEMENT H
MITERED CORNERS, CONTINUOUSLY WELDED TO GUARD
AGAINST WATER LEAKAGE
FLEXIBLE NON-ABRASIVE WEATHER SEAL
FREE STANDING 2" DEFLECTION SPRINGS WITH LACQUER
BASED POLY-VYNYL FINISH
NEOPRENE COVERED NON-SKID SPRING BASE PLATE WITH
RAISED ACOUSTICAL CUP
SUPPLY AND RETURN AIR OPENING FLEX CONNECTORS
C
D
3
22-1/2"
3
B
A
RERVIC2
APR. 28/04
SPINNAKER RESERVES THE RIGHT TO CHANGE ANY OF THE INFORMATION HEREIN WITHOUT NOTICE.
27 Leading Road Etobicoke, Ontario, Canada M9V 4B7
Tel: (416) 742-0598 Fax: (416) 742-4251
4846 Jennings Lane, Louisville, Kentucky, USA 40218
Tel: 1-800-932-6210 Fax: 1-800-903-7294
SERIES 4000 ISOLATION CURB
RERV-15000 AND RERV-20000
FEATURES:
ONE PIECE FULLY ASSEMBLED CONSTRUCTION
HEAVY GAUGE STEEL
ARRANGEMENT D / C
MITERED CORNERS, CONTINUOUSLY WELDED TO GUARD
AGAINST WATER LEAKAGE
FLEXIBLE NON-ABRASIVE WEATHER SEAL
FREE STANDING 2" DEFLECTION SPRINGS WITH LACQUER
BASED POLY-VYNYL FINISH
NEOPRENE COVERED NON-SKID SPRING BASE PLATE WITH
RAISED ACOUSTICAL CUP
SUPPLY AND RETURN AIR OPENING FLEX CONNECTORS
C
D
J
H
22-1/2"
3
3
G
F
B
E
A
RERVIC9
APR. 29/04
SPINNAKER RESERVES THE RIGHT TO CHANGE ANY OF THE INFORMATION HEREIN WITHOUT NOTICE.
27 Leading Road Etobicoke, Ontario, Canada M9V 4B7
Tel: (416) 742-0598 Fax: (416) 742-4251
4846 Jennings Lane, Louisville, Kentucky, USA 40218
Tel: 1-800-932-6210 Fax: 1-800-903-7294
SERIES 4000 ISOLATION CURB
RERV-15000 AND RERV-20000
FEATURES:
ONE PIECE FULLY ASSEMBLED CONSTRUCTION
HEAVY GAUGE STEEL
ARRANGEMENT H
MITERED CORNERS, CONTINUOUSLY WELDED TO GUARD
AGAINST WATER LEAKAGE
FLEXIBLE NON-ABRASIVE WEATHER SEAL
FREE STANDING 2" DEFLECTION SPRINGS WITH LACQUER
BASED POLY-VYNYL FINISH
NEOPRENE COVERED NON-SKID SPRING BASE PLATE WITH
RAISED ACOUSTICAL CUP
SUPPLY AND RETURN AIR OPENING FLEX CONNECTORS
C
D
22-1/2"
3
3
B
A
RERVIC8
APR. 30/04
SPINNAKER RESERVES THE RIGHT TO CHANGE ANY OF THE INFORMATION HEREIN WITHOUT NOTICE.
27 Leading Road Etobicoke, Ontario, Canada M9V 4B7
Tel: (416) 742-0598 Fax: (416) 742-4251
4846 Jennings Lane, Louisville, Kentucky, USA 40218
Tel: 1-800-932-6210 Fax: 1-800-903-7294
RERVX MODEL SERIES
ROTARY ENERGY RECOVERY
VENTILATORS
The following chart lists the available unit models with the CFM range for the supply and
exhaust air, and other unit component data. Refer to the performance data following this page
for fan-motor and recovery efficiency data.
ROTARY ENERGY
RECOVERY WHEEL SUPPLY AND
CASSETTE
EXHAUST FAN
MODEL No.
SIZE AND TYPE
UNIT
MODEL
CFM
RANGE
RERVX-256
250 - 600
ECW204
RERVX-511
500 - 1100
ECW244
FILTER TYPE,
QUANTITIES AND
SIZES
PLEATED - 30% EFFICIENT
S/A 1 - 20 X 25 X 2
E/A 1 - 20 X 25 X 2
10 X 10
FC DWDI
RERVX-1019
1000 -1900
ECW324
RERVX-1324
1300 - 2400
ECW364
RERVX-1533
1500 - 3300
ECW424
PLEATED - 30% EFFICIENT
S/A 2 - 18 X 20 X 2
E/A 2 - 18 X 20 X 2
12 X 12
FC DWDI
PLEATED - 30% EFFICIENT
S/A 2 - 24 X 24 X 2
E/A 2 - 24 X 24 X 2
RERVX-3045
3000 - 4500
ECW484
RERVX-3550
3500 - 5000
ECW486
RERVX-4055
4000 - 5500
ECW544
15 X 15
FC DWDI
PLEATED - 30% EFFICIENT
S/A 6 - 20 X 20 X 2
E/A 6 - 20 X 20 X 2
RERVX-4567
4500 - 6700
ECW604
18 X 18
FC DWDI
RERVX-5082
5000 - 8200
ECW664
PLEATED - 30% EFFICIENT
S/A 6 - 20 X 20 X 2
E/A 6 - 20 X 20 X 2
RERVX-6098
6000 - 9800
ECW666
RERVX-7011
7000 - 11000
ECW726
RERVX-15000 11000 - 15000
ECW846
22.13 x 22.13
FC DWDI
PLEATED - 30% EFFICIENT
S/A 6 - 24 X 24 X 2
E/A 6 - 24 X 24 X 2
RERVX-20000 15000 - 20000
ECW966
25.25 x25.25
FC DWDI
PLEATED - 30% EFFICIENT
S/A 8 - 24 X 24 X 2
E/A 8 - 24 X 24 X 2
SEL1X
DEC 08/04
RERVX STANDARD FEATURES
ITEM 1: ROTARY ENERGY RECOVERY WHEEL ASSEMBLY
•
CASSETTE SLIDES OUT FOR EASY ACCESS
•
FACTORY SET PURGE ELIMINATES CROSSOVER
•
INTEGRAL WHEEL DRIVE MOTOR, PULLEY,AND BELT(S)
•
SYNTHETIC FIBER-BASED MEDIA IMPREGNATED WITH
A NON-MIGRATING WATER SELECTIVE 4A MOLECULAR DESICCANT
SIEVE
ITEM 2: FRESH AIR SUPPLY BLOWER ASSEMBLY
•
FORWARD CURVE WITH DOUBLE INLET
•
BALL BEARINGS WITH SUPPORTS
•
ADJUSTABLE MOTOR MOUNTS
•
ADJUSTABLE CAST-IRON V-BELT DRIVES
•
TEFC MOTORS
ITEM 3: STALE AIR EXHAUST BLOWER ASSEMBLY
(SAME AS FRESH AIR SUPPLY BLOWER ASSEMBLY)
ITEM 4:
•
•
•
•
•
•
•
CABINET
HEAVY GAUGE SATIN COAT STEEL CABINET
ROOF SEAMS FULLY CAULKED AND FASTENED
ROOF OVER-HANG FLANGE PROVIDED WITH PERIMETER DRIP EDGE
HINGED ACCESS DOORS WITH STAINLESS STEEL LATCHES
AND PERIMETER GASKET
1" INSULATION ON ALL INTERIOR SURFACES
INSULATED DOUBLE SKINNED FLOOR
WEATHER RESISTANT POWDER COAT FINISH
ITEM 5: HEAVY GAGE GALVANIZED STEEL PERIMETER BASE:
•
INTEGRAL CROSS SUPPORTS
•
INTEGRAL LIFTING HOLES
•
FORMED TO OVERLAP PERIMETER OF ROOF CURB
ITEM 6:
2” 30% PLEATED MEDIUM EFFICIENCY SUPPLY AND RETURN
AIR FILTERS
ITEM 7: CONTROL ENCLOSURE:
•
BLOWER MOTOR FUSING, CONTACTS, AND THERMAL OVERLOADS
•
LOW VOLTAGE CONTROL TRANSFORMER WITH FUSES
•
COLOUR CODED WIRING AND NUMBERED TERMINAL STRIP
ITEM 8:
•
•
REHEAT AND RECOOL COMPONENT SECTION
EXTERIOR BOX FOR COIL CONNECTIONS SHOWN
SEE LIST OF AVAILABLE OPTION ACCESSORIES FOR VARIOUS TYPES
PRODUCT DESCRIPTION
The Spinnaker Industries Inc. Model Series RERVX
Packaged Ventilation Units are designed for indoor and
outdoor applications with efficiency and cost effectiveness in
mind. Quality features include heavy gauge construction,
weather resistant powder coat finish, quiet running forward
curved blowers with ball bearings, adjustable v-belt drives,
hinged access doors with perimeter gasket, and many other
standard features.
RERVX Model Series units incorporate an energy recovery
wheel assembly to recover waste heat energy from stale
exhaust air with optional heating and cooling components
specifically designed to maintain supply discharge air at
desired conditions. Unit models range from 250
to 20,000 CFM nominal air volume capacities. A variety
of optional heating and cooling components and controls
are available to suit practically any application requirement.
Refer to the “Optional heating and cooling components” in the
catalog for additional information.
The recovery wheel assembly is UL tested and UL recognized
as a component for heat recovery ventilators. The recovery
wheel is ARI certified using the 84-1991 ASHRAE standard
method of testing and ARI standard 1060.
RERVXFEAT
DEC 08/04
RETURN AIR
FROM CONDITIONED
SPACE
SUPPLY AIR
TO CONDITIONED
SPACE
EXHAUST AIR
OUTDOOR AIR
RERVX
Standard Features
UNIT CONSTRUCTION
• Constructed for indoor/outdoor use
• 18 ga. satin coat steel casing wall and roof panels
• 18 ga. galvanized steel floor and center partition panels
• 14 ga. galvanized steel base frame with lifting holes
• Casing interior surfaces to be lined with 1” foil faced insulation, 3 Ib /cu.ft minimum density with all
seams foil taped
• Access doors complete with full length stainless steel piano hinge, two stainless steel latches per door, and
full perimeter rubber bulb seal gasket.
• Powder coated exterior finish (Sky Grey)
ROTARY WHEEL ASSEMBLY
• Heavy gauge galvanized steel casing
• Removable side panels for drive access
• Inboard no-maintenance bearings
• Assembly slides in and out of unit for ease of inspection and removal
• Non-migrating water selective 4A molecular sieve desiccant
• Purge section to eliminate cross over of return air to supply air
• Wheel drive consists of a standard drive motor with automatic
internal thermal overload, fixed pulley, and a durable urethane drive belt
• Performance tested using ASHRAE standard 84-1991 and ARI standard 1060
CHILLED WATER COIL (Optional)
• Copper tubes, aluminum fins, galvanized steel frame
• ARI Certified and rated in accordance with ARI 410
• Stainless steel drain pan
HOT WATER COIL (Optional)
• Copper tubes, aluminum fins, galvanized steel frame
• Rated in compliance with ARI 410
SUPPLY AND EXHAUST FANS
• Forward curved double inlet wheels
• Ball bearings
• TEFC motors with ball bearings, class B construction
• Variable v-belt drives with adjustable motor mounts
FILTERS
• 2” pleated medium efficient throwaway type
• Fresh air filters on entering side of rotary wheel
• Return air filters on entering side of rotary wheel
ELECTRICAL COMPONENTS
• Supply and exhaust fan motor fuses, contactors, and thermal overloads
• Rotary wheel drive motor contactor
• Control transformer with primary and secondary fuses
• Numbered terminal strip
• Internally pre-wired and operational tested
• ETL approved
FEA1X - DEC 08/04
RERV/RERVX
Optional Accessories
DUCT CONNECTION ARRANGEMENTS
• Arrangement H (Horizontal duct connections)
• Arrangement D (Downflow, bottom duct connections)
• Arrangement C (Combination, horizontal supply, bottom return)
ROOF CURBS
•
•
•
•
CLIPLOCK roof curb to suit required arrangement (Shipped loose for field assembly)
Standard heights of 14”, 18” and 24” available
Custom heights and sloped curbs available
Spring isolation roof curb to suit required arrangement, complete with flex connectors
MISCELLANIOUS
•
•
•
•
Spring type vibration isolators (Indoor unit, hung or base mount, shipped loose for field installation)
Flexible duct connectors (Shipped loose for field installation on unit external duct connections)
22 gauge inner cabinet liner
Sensible only energy recovery wheel
HOODS AND DAMPERS
•
•
•
•
•
•
Fresh air inlet hood with entrainment filter and bird screen
Exhaust air discharge hood with bird screen
Fresh air inlet motorized low leakage parallel blade damper with end switch
Exhaust discharge motorized low leakage parallel blade damper with end switch
Gravity damper for exhaust discharge
Recirculation motorized two position damper for night set back function
FROST CONTROL
•
•
•
•
•
On-off frost control
Exhaust only frost control
Electric pre-heat frost protection
Variable frequency drive (VFD) of energy recovery wheel motor for frost control
Recirculation frost control
FREE COOL CONTROL
• Fresh air enthalpy control for free cooling (Recovery wheel shutdown)
• Fresh air ambient temperature control for free cooling (Recovery wheel shutdown)
MISCELLANIOUS ELECTRICAL
• Non-fused disconnect switch
• Variable frequency drives (VFD) for supply and exhaust fan motors (Control by others)
• Two speed motors on supply and exhaust fans (Control by others)
• Time clock - 7 day program, quartz, 100 hour battery backup, override switch
• Dirty filter pressure differential switches (Optional indictor light available)
• Remote on-off switch (Shipped loose for field installation)
• CO2 detector control (Shipped loose for field installation)
• Firestat (Duct mount, shipped loose for field installation)
• Smoke detector (Duct mount, shipped loose for field installation)
• Recovery wheel rotation sensor (Optional indictor light available)
• Programmable microprocessor control
• Air flow monitoring
OP1
DEC 08/04
RERV/RERVX
Optional Energy Saving
Accessory Descriptions
Re-circulation motorized two position damper for night set back
A full capacity re-circulation damper with a two position spring return damper actuator can be factory
mounted in the partition separating the return air plenum from the supply air compartment. This feature
will allow for unoccupied / night set back requirements, providing that some means of remote duct
mounted re-heat (and perhaps re-cool) has been designed into the ventilation supply air ducting system.
Function:
• Supply and Exhaust fan motors: de-energized.
• Energy recovery wheel motor: de-energized.
• Exhaust discharge damper: closes.
• Outside air intake damper: spring returns to closed position.
• Re-circulation damper: powered open.
• Supply fan: energized by re-circulation damper full open end switch and supplies re-circulated
return air back to the supply air duct system.
• Re-heat (and perhaps re-cool) external to the unit: energized as required from space thermostat or
discharge temperature control as supplied by others.
Option includes: Factory installed re-circulation damper, factory installed and wired two position
damper motor with end switch.
(Refer to Section 4, Optional Accessory Wiring Diagram 8)
Fresh air ambient temperature control for free cooling
Two fresh air ambient temperature controls can be factory installed to de-energize the energy recovery
wheel above 55°F and below 75°F. Both temperature controls are field adjustable to suit design
conditions.
This option prevents unnecessary heating of supply air through energy recovery during these outdoor
temperatures.
Option includes: Factory installed 2 ambient temperature controls
(Refer to Section 4, Optional Accessory Wiring Diagram 7)
Fresh air enthalpy control for free cooling
The fresh air enthalpy control has effectively the same function as the fresh air ambient temperature
control. This option includes a fresh air temperature control and a logic controller with an enthalpy sensor.
The fresh air temperature control energizes the energy recovery wheel below 55°F. The enthalpy control
senses the enthalpy of the fresh air, which is a combination of the air temperature and relative humidity.
The enthalpy control will energize the energy recovery wheel above the set point which is actually a range
of fresh air temperature -humidity combinations, for example, from approximately 63°F 80% rh, to 82°F
10% rh, for setting “A”. The enthalpy control has 4 field adjustable settings to suit design conditions.
Option includes: Factory installed enthalpy control and ambient temperature control
(Refer to Section 4, Optional Accessory Wiring Diagram 6)
OP2
DEC 08/04
RERVX MODEL SERIES
ROTARY ENERGY RECOVERY VENTILATORS
ARRANGEMENT D - WITH COILS
RERVXSD
NOV/26/04
SPINNAKER RESERVES THE RIGHT TO CHANGE ANY OF THE INFORMATION HEREIN WITHOUT NOTICE.
27 Leading Road Etobicoke, Ontario, Canada M9V 4B7
Tel: (416) 742-0598 Fax: (416) 742-4251
4846 Jennings Lane, Louisville, Kentucky, USA 40218
Tel: 1-800-932-6210 Fax: 1-800-903-7294
RERVX MODEL SERIES
ROTARY ENERGY RECOVERY VENTILATORS
ARRANGEMENT H - WITH COILS
RERVXSH
NOV/ 26 /04
SPINNAKER RESERVES THE RIGHT TO CHANGE ANY OF THE INFORMATION HEREIN WITHOUT NOTICE.
27 Leading Road Etobicoke, Ontario, Canada M9V 4B7
Tel: (416) 742-0598 Fax: (416) 742-4251
4846 Jennings Lane, Louisville, Kentucky, USA 40218
Tel: 1-800-932-6210 Fax: 1-800-903-7294
INDOOR FRESH AIR INLET AND
EXHAUST AIR DISCHARGE DAMPERS
TO SUIT
MODEL SERIES RERV/RERVX
OPTIONAL
FRESH AIR INTAKE
MOTORIZED DAMPER
ASSEMBLY
OPTIONAL
EXHAUST AIR DISCHARGE
MOTORIZED DAMPER
ASSEMBLY
OPTIONAL
EXHAUST AIR DISCHARGE
GRAVITY DAMPER
ASSEMBLY
RERV-DMP1
MAR. 10/04
SPINNAKER RESERVES THE RIGHT TO CHANGE ANY OF THE INFORMATION HEREIN WITHOUT NOTICE.
27 Leading Road Etobicoke, Ontario, Canada M9V 4B7
Tel: (416) 742-0598 Fax: (416) 742-4251
4846 Jennings Lane, Louisville, Kentucky, USA 40218
Tel: 1-800-932-6210 Fax: 1-800-903-7294
*CLIPLOCK 1000 ROOF CURB
MODEL SERIES RERVX
ARRANGEMENT D/C
WITH COILS
FEATURES:
HEAVY GAUGE GALVANIZED STEEL CONSTRUCTION
2 x 3" WOOD PERIMETER NAILER
PATENTED CLIPLOCK DESIGN FOR EASE OF ASSEMBLY
OPTIONS:
STAINLESS STEEL OR ALUMINUM CONSTRUCTION
NEOPRENE GASKET
INTERNAL 1" INSULATION
CLIPLOCK CORNER DETAIL
TOP EDGE
WOOD NAILER STRIP
BOTTOM FLANGE
TYPICAL SLOT
TYPICAL LOCKING TAB
NOTE: SEE CLIPLOCK 1000 INSTALLATION INSTRUCTIONS
FOR COMPLETE ASSEMBLY AND INSTALLATION
PROCEDURES AND REQUIREMENTS.
RERVXRCA2
NOV/26/04
SPINNAKER RESERVES THE RIGHT TO CHANGE ANY OF THE INFORMATION HEREIN WITHOUT NOTICE.
27 Leading Road Etobicoke, Ontario, Canada M9V 4B7
Tel: (416) 742-0598 Fax: (416) 742-4251
4846 Jennings Lane, Louisville, Kentucky, USA 40218
Tel: 1-800-932-6210 Fax: 1-800-903-7294
*CLIPLOCK 1000 ROOF CURB
MODEL SERIES RERVX
ARRANGEMENT H
WITH COILS
FEATURES:
HEAVY GAUGE GALVANIZED STEEL CONSTRUCTION
2 x 3" WOOD PERIMETER NAILER
PATENTED CLIPLOCK DESIGN FOR EASE OF ASSEMBLY
OPTIONS:
STAINLESS STEEL OR ALUMINUM CONSTRUCTION
NEOPRENE GASKET
INTERNAL 1" INSULATION
CLIPLOCK CORNER DETAIL
TOP EDGE
WOOD NAILER STRIP
BOTTOM FLANGE
TYPICAL SLOT
TYPICAL LOCKING TAB
NOTE: SEE CLIPLOCK 1000 INSTALLATION INSTRUCTIONS
FOR COMPLETE ASSEMBLY AND INSTALLATION
PROCEDURES AND REQUIREMENTS.
RERVXRCA1
NOV 26/04
SPINNAKER RESERVES THE RIGHT TO CHANGE ANY OF THE INFORMATION HEREIN WITHOUT NOTICE.
27 Leading Road Etobicoke, Ontario, Canada M9V 4B7
Tel: (416) 742-0598 Fax: (416) 742-4251
4846 Jennings Lane, Louisville, Kentucky, USA 40218
Tel: 1-800-932-6210 Fax: 1-800-903-7294
*CLIPLOCK 1000 ROOF CURB
MODEL SERIES RERVX
ARRANGEMENT H
WITH COILS
FEATURES:
HEAVY GAUGE GALVANIZED STEEL CONSTRUCTION
2 x 3" WOOD PERIMETER NAILER
PATENTED CLIPLOCK DESIGN FOR EASE OF ASSEMBLY
OPTIONS:
STAINLESS STEEL OR ALUMINUM CONSTRUCTION
NEOPRENE GASKET
INTERNAL 1" INSULATION
CLIPLOCK CORNER DETAIL
TOP EDGE
WOOD NAILER STRIP
BOTTOM FLANGE
TYPICAL SLOT
TYPICAL LOCKING TAB
NOTE: SEE CLIPLOCK 1000 INSTALLATION INSTRUCTIONS
FOR COMPLETE ASSEMBLY AND INSTALLATION
PROCEDURES AND REQUIREMENTS.
RERVXRCA1
NOV 26/04
SPINNAKER RESERVES THE RIGHT TO CHANGE ANY OF THE INFORMATION HEREIN WITHOUT NOTICE.
27 Leading Road Etobicoke, Ontario, Canada M9V 4B7
Tel: (416) 742-0598 Fax: (416) 742-4251
4846 Jennings Lane, Louisville, Kentucky, USA 40218
Tel: 1-800-932-6210 Fax: 1-800-903-7294
*CLIPLOCK ROOF CURB
RERVX-15000 AND RERVX-20000
EXTENDED CABINET WITH COILS
FEATURES:
HEAVY GAUGE GALVANIZED STEEL CONSTRUCTION
2 x 3" WOOD PERIMETER NAILER
PATENTED CLIPLOCK DESIGN FOR EASE OF ASSEMBLY
ARRANGEMENT D/C
OPTIONS:
STAINLESS STEEL OR ALUMINUM CONSTRUCTION
NEOPRENE GASKET
INTERNAL 1" INSULATION
CLIPLOCK CORNER DETAIL
TOP EDGE
WOOD NAILER STRIP
BOTTOM FLANGE
TYPICAL SLOT
TYPICAL LOCKING TAB
NOTE: SEE CLIPLOCK 1000 INSTALLATION INSTRUCTIONS
FOR COMPLETE ASSEMBLY AND INSTALLATION
PROCEDURES AND REQUIREMENTS.
RERVXRC9
NOV/ 26 / 04
SPINNAKER RESERVES THE RIGHT TO CHANGE ANY OF THE INFORMATION HEREIN WITHOUT NOTICE.
27 Leading Road Etobicoke, Ontario, Canada M9V 4B7
Tel: (416) 742-0598 Fax: (416) 742-4251
4846 Jennings Lane, Louisville, Kentucky, USA 40218
Tel: 1-800-932-6210 Fax: 1-800-903-7294
*CLIPLOCK ROOF CURB
RERVX-15000 AND RERVX-20000
EXTENDED CABINET WITH COILS
FEATURES:
HEAVY GAUGE GALVANIZED STEEL CONSTRUCTION
2 x 3" WOOD PERIMETER NAILER
PATENTED CLIPLOCK DESIGN FOR EASE OF ASSEMBLY
ARRANGEMENT H
OPTIONS:
STAINLESS STEEL OR ALUMINUM CONSTRUCTION
NEOPRENE GASKET
INTERNAL 1" INSULATION
CLIPLOCK CORNER DETAIL
TOP EDGE
WOOD NAILER STRIP
BOTTOM FLANGE
TYPICAL SLOT
TYPICAL LOCKING TAB
NOTE: SEE CLIPLOCK 1000 INSTALLATION INSTRUCTIONS
FOR COMPLETE ASSEMBLY AND INSTALLATION
PROCEDURES AND REQUIREMENTS.
RERVXRC8
NOV 26 / 04
SPINNAKER RESERVES THE RIGHT TO CHANGE ANY OF THE INFORMATION HEREIN WITHOUT NOTICE.
27 Leading Road Etobicoke, Ontario, Canada M9V 4B7
Tel: (416) 742-0598 Fax: (416) 742-4251
4846 Jennings Lane, Louisville, Kentucky, USA 40218
Tel: 1-800-932-6210 Fax: 1-800-903-7294
COIL PRESSURE DROP
Model No.
CFM
RERVX-256
250
425
600
500
800
1100
1000
1225
1450
1675
1900
1300
1575
1850
2125
2400
1500
1750
2000
2250
2500
2750
3000
3300
3000
3250
3500
3750
4000
4250
4500
3550
3800
4050
4300
4550
4800
5000
4500
5000
5500
6000
6350
6700
RERVX-511
RERVX-1019
RERVX-1324
RERVX-1533
RERVX-3045
RERVX-3550
RERVX-4567
Velocity
Cooling Coil
Heating Coil
(FPM) Maxium Air PD in W.G. Maxium Air PD in W.G.
109
0.03"
0.01"
186
0.08"
0.01"
262
0.17"
0.03"
218
0.12"
0.02"
349
0.31"
0.04"
480
0.60"
0.07"
213
0.09"
0.02"
261
0.13"
0.03"
309
0.19"
0.03"
357
0.28"
0.04"
405
0.37"
0.05"
277
0.15"
0.03"
336
0.26"
0.04"
395
0.36"
0.05"
453
0.47"
0.06"
485
0.53"
0.16"
169
0.06"
0.01"
198
0.08"
0.02"
226
0.09"
0.02"
254
0.12"
0.02"
282
0.14"
0.03"
311
0.18"
0.03"
339
0.22"
0.04"
373
0.33
0.05"
339
0.22"
0.04"
367
0.26"
0.05"
395
0.38"
0.05"
424
0.45"
0.06"
452
0.49"
0.06"
480
0.57"
0.07"
489
0.59"
0.16"
401
0.39"
0.05"
438
0.47"
0.06"
457
0.50"
0.07"
485
0.58"
0.07"
452
0.49"
0.14"
477
0.54"
0.15"
497
0.57"
0.16"
386
0.31"
0.02"
429
0.38"
0.03"
471
0.56"
0.03"
411
0.39"
0.03"
432
0.44"
0.03"
459
0.51"
0.03"
Values for pressure drop were obtained using the following assumptions.
1. Six row cooling coil and two row heating coil.
2. A fin style that provides a medium efficiency heat transfer rate with a lower
pressure drop.
RERVXCP
DEC 08/04
COIL OPTIONS:
Coil options include cooling
and heating coils. All coils have
a casing constructed of galvanized
steel with a minimum material
thickness of 0.06". The coil tubing
is seamless copper with a
minimum of 0.016" wall thickness
and aluminum plate fin material
thickness a minimum of 0.006"
with 12 FPI or less.All coils have a
recessed vent and drain located
on exterior connections.
COOLING COIL:
Cooling coils are available 2, 4 or 6
rows deep. All cooling coils are
provided with a stainless steel
drain pan and condensate drain
pipe that extends out through the
side of the unit to allow
connections to a P- trap by others.
DX COILS:
DX coils are provided with
distributors to receive expansion
valves at the liquid connections.
An access panel is provided to
allow liquid line connections to be
made in the interior of the unit
HOT WATER COILS:
Hot water coils are available 1 or 2
rows deep.
ELECTRIC HEAT COILS:
Electric heat coils are available
and include the following features:
UL listed, multiple stage control, air
proving switch, 24 volt control
circuit fusing when over 48 amps.
Heater shall require a separate
power connection from the RERV
control panel.
COIL PRESSURE DROP
Model No.
RERVX-5082
CFM
5000
5500
6000
6500
7000
7500
7850
8200
RERVX-6098 6000
6500
7000
7500
8000
8500
9000
9400
9800
RERVX-7011 7000
7500
8000
8500
9000
9500
10000
10500
11000
RERVX-15000 12000
12500
13000
13500
14000
14500
15000
RERVX-20000 16000
16500
17000
17500
18000
18500
19000
19500
20000
Velocity
Cooling Coil
Heating Coil
(FPM) Maxium Air PD in W.G. Maxium Air PD in W.G.
429
0.38"
0.03"
471
0.56"
0.03"
411
0.39"
0.03"
446
0.46"
0.03"
480
0.54"
0.04"
406
0.37"
0.03"
425
0.39"
0.03"
444
0.44"
0.03"
411
0.39"
0.03"
446
0.46"
0.03"
480
0.54"
0.04"
406
0.37"
0.03"
433
0.42"
0.03"
460
0.47"
0.03"
487
0.53"
0.04"
460
0.47"
0.03"
480
0.50"
0.04"
480
0.54"
0.04"
406
0.37"
0.03"
433
0.42"
0.03"
460
0.47"
0.03"
487
0.53"
0.04"
465
0.47"
0.03"
490
0.51"
0.04"
470
0.46"
0.04"
492
0.52"
0.04"
368
0.29"
0.02"
383
0.34"
0.03"
399
0.36"
0.03"
414
0.38"
0.03"
429
0.43"
0.03"
444
0.46"
0.03"
460
0.48"
0.04"
400
0.36"
0.03"
413
0.38"
0.03"
425
0.40"
0.03"
438
0.42"
0.03"
450
0.47"
0.04"
463
0.49"
0.04"
475
0.51"
0.04"
488
0.53"
0.04"
500
0.55"
0.04"
Values for pressure drop were obtained using the following assumptions.
1. Six row cooling coil and two row heating coil.
2. A fin style that provides a medium efficiency heat transfer rate with a lower
pressure drop.
RERVXCP2
DEC 08/04
COIL OPTIONS:
Coil options include cooling
and heating coils. All coils have
a casing constructed of galvanized
steel with a minimum material
thickness of 0.06". The coil tubing
is seamless copper with a
minimum of 0.016" wall thickness
and aluminum plate fin material
thickness a minimum of 0.006"
with 12 FPI or less.All coils have a
recessed vent and drain located
on exterior connections.
COOLING COIL:
Cooling coils are available 2, 4 or 6
rows deep. All cooling coils are
provided with a stainless steel
drain pan and condensate drain
pipe that extends out through the
side of the unit to allow
connections to a P- trap by others.
DX COILS:
DX coils are provided with
distributors to receive expansion
valves at the liquid connections.
An access panel is provided to
allow liquid line connections to be
made in the interior of the unit
HOT WATER COILS:
Hot water coils are available 1 or 2
rows deep.
ELECTRIC HEAT COILS:
Electric heat coils are available
and include the following features:
UL listed, multiple stage control, air
proving switch, 24 volt control
circuit fusing when over 48 amps.
Heater shall require a separate
power connection from the RERV
control panel.
Electrical Data
RERV/RERVX MODEL SERIES
ROTARY ENERGY RECOVERY
VENTILATORS
Unit voltages include 115, 208, and 230 single phase
and three phase, 460 and 575 three phase. Standard
electrical features include fan motor fuses, contactors,
and overloads, rotary wheel motor fuses and contactor,
control transformer with primary and secondary fuses,
and a 24 volt numbered terminal strip for remote wiring
connections as required.
115/1/60
STANDARD UNIT
The charts below show standard unit minimum circuit
ampacities and standard units with electric preheat
minimum circuit ampacities. The ampacity values listed
below are based on units with the same horse power for
the supply and exhaust fan motors. Contact the factory for
unit ampacities for unit selections of different horse
powers.
Note: Contact factory for single phase pre-heat requirements.
UNIT
MODEL
0.5
0.75
1
RERV-256
RERV-511
RERV-1019
29.9
29.9
29.9
36.4
36.4
36.4
34.4
34.4
34.4
FAN MOTOR HORSE POWER
1.5
2
3
5
46.7
46.7
7.5
10
15
7.5
10
15
69.4
208/1/60
STANDARD UNIT
UNIT
MODEL
RERV-256
RERV-511
RERV-1019
RERV-1324
RERV-1533
RERV-3045
RERV-3550
RERV-4055
RERV-4567
RERV-5082
0.5
0.75
1
16.5
16.5
16.5
15.8
15.8
20.0
20.0
20.0
19.3
19.3
19.0
19.0
19.0
18.3
18.3
FAN MOTOR HORSE POWER
1.5
2
3
5
25.7
25.7
25.1
25.1
25.1
26.1
28.3
28.3
28.3
38.2
37.6
37.6
37.6
37.9
40.8
40.8
40.8
ED1 Rev 2
Electrical Data
RERV/RERVX MODEL SERIES
ROTARY ENERGY RECOVERY
VENTILATORS
230/1/60
STANDARD UNIT
UNIT
MODEL
RERV-256
RERV-511
RERV-1019
RERV-1324
RERV-1533
RERV-3045
RERV-3550
RERV-4055
RERV-4567
RERV-5082
FAN MOTOR HORSE POWER
1.5
2
3
5
0.5
0.75
1
15.0
15.0
15.0
14.3
14.3
18.2
18.2
18.2
17.6
17.6
17.2
17.2
17.2
16.6
16.6
23.5
23.5
22.8
22.8
22.8
24.0
25.8
25.8
25.8
7.5
10
15
34.7
34.1
34.1
34.1
34.5
37.1
37.1
37.1
208/3/60
STANDARD UNIT
UNIT
FAN MOTOR HORSE POWER
MODEL
0.5
0.75
1
RERV-256
RERV-511
RERV-1019
RERV-1324
RERV-1533
RERV-3045
RERV-3550
RERV-4055
RERV-4567
RERV-5082
RERV-6098
RERV-7011
RERV-15000
RERV-20000
12.5
12.5
12.5
11.8
11.8
14.0
14.0
14.0
13.3
13.3
18.0
18.0
18.0
17.3
17.3
1.5
2
21.2
21.2
20.6
20.6
20.6
20.6
23.8
23.8
23.8
24.0
23.3
23.3
23.3
23.3
26.6
26.6
26.6
3
5
29.3
29.3
29.3
29.3
32.6
32.6
32.6
32.1
32.1
41.6
41.6
44.8
44.8
44.8
44.3
44.3
7.5
10
15
20
25
80.3
80.3
80.3
80.3
107.8
107.8
107.8
135.5
135.5
168.7
56.7
64.6
64.6
64.1
64.1
64.1
ED1 Rev 2
Electrical Data
RERV/RERVX MODEL SERIES
ROTARY ENERGY RECOVERY
VENTILATORS
208/3/60
STANDARD UNIT WITH ELECTRIC PRE-HEAT
UNIT
MODEL
RERV-256
RERV-511
RERV-1019
RERV-1324
RERV-1533
RERV-3045
RERV-3550
RERV-4055
RERV-4567
RERV-5082
RERV-6098
RERV-7011
RERV-15000
RERV-20000
PRE-HEAT
KW
6
6
12
12
15
20
20
20
30
30
50
50
70
90
FAN MOTOR HORSE POWER
0.5
0.75
1
33.3
33.3
54.1
53.5
63.9
34.8
34.8
55.6
55.0
65.4
38.8
38.8
59.6
59.0
69.4
1.5
2
42.0
62.9
62.3
72.7
90.1
90.1
93.3
128.0
128.0
65.6
65.0
75.4
92.8
92.8
96.1
130.8
130.8
3
5
7.5
71.0
81.4
98.8
98.8
102.1
136.8
136.8
205.8
205.8
111.1
111.1
114.3
149.0
149.0
218.0
218.0
10
15
20
25
254.0
254.0
320.3
390.4
281.5
348.3
418.4
378.0
448.1
481.4
112.1
168.8
168.8
237.8
237.8
303.3
230/3/60
STANDARD UNIT
UNIT
MODEL
RERV-256
RERV-511
RERV-1019
RERV-1324
RERV-1533
RERV-3045
RERV-3550
RERV-4055
RERV-4567
RERV-5082
RERV-6098
RERV-7011
RERV-15000
RERV-20000
0.5
0.75
1
11.2
11.2
11.2
10.6
10.6
12.7
12.7
12.7
12.1
12.1
16.2
16.2
16.2
15.6
15.6
1.5
FAN MOTOR HORSE POWER
2
3
5
7.5
19.2
19.2
18.6
18.6
18.6
18.6
21.6
21.6
21.6
21.7
21.1
21.1
21.1
21.1
24.1
24.1
24.1
26.6
26.6
26.6
26.6
29.6
29.6
29.6
29.1
29.1
37.6
37.6
40.6
40.6
40.6
40.1
40.1
10
15
20
25
72.6
72.6
72.6
72.6
97.6
97.6
97.6
124.3
124.3
153.8
52.3
58.6
58.6
58.1
58.1
58.1
ED1 Rev 2
Electrical Data
RERV/RERVX MODEL
SERIES
ROTARY ENERGY RECOVERY
VENTILATORS
230/3/60
STANDARD UNIT WITH ELECTRIC PRE-HEAT
UNIT
MODEL
PRE-HEAT
RERV-256
RERV-511
RERV-1019
RERV-1324
RERV-1533
RERV-3045
RERV-3550
RERV-4055
RERV-4567
RERV-5082
RERV-6098
RERV-7011
RERV-15000
RERV-20000
KW
6
6
12
12
15
20
20
20
30
30
50
50
70
90
0.5
0.75
1
30.0
30.0
48.9
48.3
57.7
31.6
31.6
50.4
49.8
59.2
35.1
35.1
53.9
53.3
62.7
1.5
38.2
56.9
56.3
65.7
81.4
81.4
84.4
115.8
115.8
FAN MOTOR HORSE POWER
2
3
5
7.5
10
59.4
58.8
68.2
83.9
83.9
86.9
118.3
118.3
64.3
73.7
89.4
89.4
92.4
123.8
123.8
186.2
186.2
100.4
100.4
103.4
134.8
134.8
197.2
197.2
15
20
25
254.7
317.2
379.6
344.2
406.6
436.6
115.1
152.8
152.8
215.2
215.2
275.7
229.7
229.7
291.7
354.1
460/3/60
STANDARD UNIT
UNIT
MODEL
RERV-256
RERV-511
RERV-1019
RERV-1324
RERV-1533
RERV-3045
RERV-3550
RERV-4050
RERV-4567
RERV-5082
RERV-6098
RERV-7011
RERV-15000
RERV-20000
0.5
0.75
1
4.4
4.4
4.4
5.0
5.0
5.2
5.2
5.2
5.8
5.8
6.9
6.9
6.9
7.5
7.5
1.5
8.4
8.4
9.0
9.0
9.0
9.3
9.3
9.3
9.3
FAN MOTOR HORSE POWER
2
3
5
7.5
9.7
10.3
10.3
10.3
10.5
10.5
10.5
10.5
13.0
13.0
13.0
13.3
13.3
13.3
13.3
13.7
13.7
18.5
18.8
18.8
18.8
18.8
19.2
19.2
10
15
20
25
35.4
35.4
39.2
39.2
47.9
51.9
51.9
65.4
65.4
80.4
27.8
27.8
27.8
28.2
28.2
31.2
ED1 Rev 2
Electrical Data
RERV/RERVX MODEL
SERIES
ROTARY ENERGY RECOVERY
VENTILATORS
460/3/60
STANDARD UNIT WITH ELECTRIC PRE-HEAT
UNIT
MODEL
RERV-256
RERV-511
RERV-1019
RERV-1324
RERV-1533
RERV-3045
RERV-3550
RERV-4055
RERV-4567
RERV-5082
RERV-6098
RERV-7011
RERV-15000
RERV-20000
PREHEAT
KW
6
6
12
12
15
20
20
20
30
30
50
50
70
90
FAN MOTOR HORSE POWER
0.5
0.75
1
13.8
13.8
23.3
23.9
28.6
14.6
14.6
24.0
24.6
29.4
16.3
16.3
25.8
26.4
31.1
1.5
2
17.8
27.3
27.9
32.6
40.5
40.7
40.7
56.4
56.4
28.5
29.1
33.9
41.7
42.0
42.0
57.7
57.7
3
5
31.9
36.6
44.5
44.7
44.7
60.4
60.4
92.2
92.2
50.0
50.2
50.2
65.9
65.9
97.7
97.7
7.5
10
15
20
25
114.0
114.0
149.1
180.5
126.5
161.9
193.3
000.0
175.4
206.8
221.8
59.1
74.9
74.9
106.7
106.7
141.1
575/3/60
STANDARD UNIT
UNIT
MODEL
RERV-256
RERV-511
RERV-1019
RERV-1324
RERV-1533
RERV-3045
RERV-3550
RERV-4055
RERV-4567
RERV-5082
RERV-6098
RERV-7011
RERV-15000
RERV-20000
0.5
0.75
1
3.4
3.4
3.4
3.8
3.8
3.9
3.9
3.9
4.3
4.3
5.7
5.7
5.7
6.1
6.1
1.5
6.7
6.7
7.1
7.1
7.1
7.3
7.3
7.3
7.3
FAN MOTOR HORSE POWER
2
3
5
7.5
7.7
8.1
8.1
8.1
8.3
8.3
8.3
8.3
10.3
10.3
10.3
10.6
10.6
10.6
10.6
10.9
10.9
14.8
15.1
15.1
15.1
15.1
15.4
15.4
10
15
20
25
28.4
28.4
32.6
32.6
38.4
42.9
42.9
53.9
53.9
65.1
22.7
22.3
22.3
22.7
22.7
26.4
ED1 Rev 2
Electrical Data
RERV/RERVX MODEL SERIES
ROTARY ENERGY RECOVERY
VENTILATORS
575/3/60
STANDARD UNIT WITH ELECTRIC PRE-HEAT
UNIT
MODEL
RERV-256
RERV-511
RERV-1019
RERV-1324
RERV-1533
RERV-3045
RERV-3550
RERV-4050
RERV-4567
RERV-5082
RERV-6098
RERV-7011
RERV-15000
RERV-20000
PRE-HEAT
KW
6
6
12
12
15
20
20
20
30
30
50
50
70
90
0.5
0.75
1
10.9
10.9
18.5
18.9
22.7
11.4
11.4
19.0
19.4
23.2
13.2
13.2
20.8
21.1
24.9
1.5
FAN MOTOR HORSE POWER
2
3
5
7.5
10
14.2
21.8
22.1
25.9
32.2
32.4
32.4
45.0
45.0
22.8
23.1
26.9
33.2
33.4
33.4
46.0
46.0
25.4
29.2
35.4
35.7
35.7
48.3
48.3
73.8
73.8
39.9
40.2
40.2
52.8
52.8
78.3
78.3
15
20
25
101.3
130.9
156.0
141.9
167.0
178.2
48.0
60.0
60.0
85.5
85.5
114.4
91.3
91.3
120.6
145.7
ED1 Rev 2
RERV AND RERVX BASIC UNIT
WIRING DIAGRAM (SINGLE PHASE)
6000033
JUNE 21/04
SPINNAKER RESERVES THE RIGHT TO CHANGE ANY OF THE INFORMATION HEREIN WITHOUT NOTICE.
27 Leading Road Etobicoke, Ontario, Canada M9V 4B7
Tel: (416) 742-0598 Fax: (416) 742-4251
4846 Jennings Lane, Louisville, Kentucky, USA 40218
Tel: 1-800-932-6210 Fax: 1-800-903-7294
RERV AND RERVX BASIC UNIT
WIRING DIAGRAM (3 PHASE)
VOLTAGE: 208/230/460/575
6000032
JUNE 21/04
SPINNAKER RESERVES THE RIGHT TO CHANGE ANY OF THE INFORMATION HEREIN WITHOUT NOTICE.
27 Leading Road Etobicoke, Ontario, Canada M9V 4B7
Tel: (416) 742-0598 Fax: (416) 742-4251
4846 Jennings Lane, Louisville, Kentucky, USA 40218
Tel: 1-800-932-6210 Fax: 1-800-903-7294
RERV AND RERVX BASIC UNIT
WIRING DIAGRAM (3 PHASE)
VOLTAGE: 208/230/460/575
6000035
JUNE 21/04
SPINNAKER RESERVES THE RIGHT TO CHANGE ANY OF THE INFORMATION HEREIN WITHOUT NOTICE.
27 Leading Road Etobicoke, Ontario, Canada M9V 4B7
Tel: (416) 742-0598 Fax: (416) 742-4251
4846 Jennings Lane, Louisville, Kentucky, USA 40218
Tel: 1-800-932-6210 Fax: 1-800-903-7294
RERV AND RERVX BASIC UNIT
WIRING DIAGRAM (3 PHASE)
WITH OPTIONAL ELECTRIC PREHEAT
VOLTAGE: 208/230/460/575
L1
L2
L3
SCR CONTROL
24 VAC
4
TH
6000036
JUNE 21/04
SPINNAKER RESERVES THE RIGHT TO CHANGE ANY OF THE INFORMATION HEREIN WITHOUT NOTICE.
27 Leading Road Etobicoke, Ontario, Canada M9V 4B7
Tel: (416) 742-0598 Fax: (416) 742-4251
4846 Jennings Lane, Louisville, Kentucky, USA 40218
Tel: 1-800-932-6210 Fax: 1-800-903-7294
RERV AND RERVX BASIC UNIT
WIRING DIAGRAM (3 PHASE)
WITH OPTIONAL ELECTRIC PREHEAT
VOLTAGE: 208/230/460/575
L1
L2
L3
SCR CONTROL
24 VAC
4
TH
+
6000038
JUNE 21/04
SPINNAKER RESERVES THE RIGHT TO CHANGE ANY OF THE INFORMATION HEREIN WITHOUT NOTICE.
27 Leading Road Etobicoke, Ontario, Canada M9V 4B7
Tel: (416) 742-0598 Fax: (416) 742-4251
4846 Jennings Lane, Louisville, Kentucky, USA 40218
Tel: 1-800-932-6210 Fax: 1-800-903-7294
RERV AND RERVX
GENERAL SPECIFICATION
Packaged recovery ventilation units shall be Spinnaker Industries Inc. Model Series RERV and RERVX. Units shall be
factory assembled, wired and tested prior to shipment. Units shall bear the ETL label. Field wiring shall require a single
point power connection and a numbered terminal strip for low voltage remote wiring connections.
UNIT CONSTRUCTION
Unit construction to suit indoor or outdoor applications. All exterior cabinet screws shall be stainless steel. Unit casing shall
be minimum 18 gauge satin coat steel with weather resistant powder coat finish. Units with bear metal or an air dried paint
finish will not be accepted. All seams to be sealed with weather resistant caulking. All interior cabinet surfaces shall be
lined with 1” thick, 3 lbs/cu ft density foil faced insulation, with seems foil taped. Access doors and center partitions to be
lined with ¼” thick foil faced polyethylene bubble insulation, with seams foil taped. The floor shall be double skinned to
protect the 2” thick, minimum 1.5 lbs/cu ft density insulation. The base shall be constructed with heavy gauge galvanized
steel with integral supports. Perimeter base frame designed to be such that it overhangs when mounted on a roof curb.
Access doors to be fully welded and hinged with a full length stainless steel piano hinge, two stainless steel latches per
door and dual durometer extruded flexible vinyl seal rated to –40 deg. F. Units with lift off access doors will not be
accepted.
ENERGY RECOVERY WHEEL ASSEMBLY
The energy recovery wheel assembly casing shall be constructed with heavy gauge galvanized steel, reinforced at sealing
surfaces, removable end panels for drive access, inboard no-maintenance permanently sealed roller bearings for small
assemblies, external pillow block bearings for large assemblies, and an adjustable non-contact neoprene bulb peripheral
and inner seal. The wheel assembly shall slide in and out of the unit on a galvanized steel track for ease of inspection and
maintenance.
The wheel media shall be constructed of a corrugated synthetic fiber-based substrate impregnated with a non-migrating
water selective 4A molecular sieve desiccant uniformly and permanently dispersed throughout the matrix structure. The
wheel media shall be spirally wound to form fluted honeycomb geometry so as to eliminate internal wheel bypass. Wheel
layers that can be separated or spread apart by airflow are unacceptable due to the possibility of channeling and
performance degradation. Face flatness of the wheel shall be maximized (+/- 0.032 inches) in order to minimize wear on
inner seal surfaces and minimize cross leakage. The wheel shall be complete with a purge section, minimizing cross over
of return air into supply air, with a non-contact bulb seal. Wheels with large pore size desiccants like silica gel, that are
coated, bonded, or synthesized onto the media or without a purge section will not be accepted. The wheel shall consist of
evenly spaced galvanized steel spokes, a galvanized steel outer band, and an aluminum center hub.
The standard drive system shall consist of a standard motor, fixed pulley, and link type drive belt constructed from a high
performance polyurethane elastomer reinforced with multiple plies of polyester fabric. The drive pulley and belt shall drive
the wheel from inside the assembly casing. Wheels with drive pulleys and belts that are exposed will not be accepted.
Single phase drive motors shall have integral automatic reset thermal overload protection. Three phase drive motors shall
have a manual reset thermal overload mounted in the unit control enclosure.
Wheel media shall be in accordance with NFPA, and be UL tested and UL recognized as a component for heating and
heating-cooling appliance accessories. Energy recovery wheels shall be rigorously performance tested using the ASHRAE
84-1991 and ARI 1060 standard method of testing. Recovery wheels shall be ARI certified and must bear the ARI
certification stamp.
FANS
Supply and exhaust fans shall be forward curved double width double inlet with ball bearings. Fan drive shaft shall be
polished with keyways for drive pulley mounting. Unit fans with machined flats on fan shafts for drive pulley mounting will
not be accepted. Fans shall have ball bearings suitable for operation in ambient temperatures of –65 to 250 deg. F with a
minimum L10 life in excess of 100,000 hours at maximum cataloged operating speeds. Fan bearings shall be permanently
lubricated and sealed, mounted in resilient neoprene rings. Fan housings shall have extruded holes for base side
mounting. Fans in units with air flow capacity greater than 2500 CFM shall have welded steel angle frames. Fans in units
with air flow capacity greater than 5000 CFM shall have welded steel angle frames with T bar supports with cast iron pillow
block bearings with grease nipples. Fan motors shall be rated continuous duty, ball bearing construction, and have class F
insulation. Variable pitch v-belt drives, of cast iron construction and adjustable motor mounts to be provided. Units with
fans, motors, and drives that do not meet the above criteria will not be accepted.
Page 1 of 4
GS1 REV 4
RERV AND RERVX
GENERAL SPECIFICATION
FILTERS
The supply entering and exhaust entering sides of the recovery wheel shall be complete with 2" deep medium efficiency
pleated filters. Units without supply and exhaust filters will not be accepted.
CONTROLS AND ELECTRICAL
Unit controls shall be mounted with in an integral enclosure with inner hinged access plates and exterior hinged access door
so that fan access doors remain fully closed to maintain accurate fan performance during control adjustment. The exterior
hinged access door shall be the same construction as the other unit access doors with two latches that require a screw driver
to open. Two ½” trade size knockouts shall be provided on the side of the unit that leads into the electrical control enclosure.
Unit controls shall include: supply and exhaust fan motor fuses, contactors, and manual reset thermal overloads, energy
recovery wheel drive motor contactor, and control transformers with primary and secondary fusing. Unit wiring shall be color
coded with a numbered terminal strip for low voltage wiring and field connections. Unit shall have single point power input
terminals. Units without separate motor fusing and contactors will not be accepted
OUTDOOR UNITS
Outdoor units shall be provided with factory installed fresh air inlet and exhaust hoods. Hoods are constructed with minimum
18 gauge satin coat steel with the same finish as the unit. Fresh air inlet hoods are complete with removable washable inlet
filters with galvanized steel wire mesh on the entering and leaving air sides of the filter that doubles as bird screen. Exhaust
hoods are complete with a galvanized steel wire mesh bird screen. All flanges that meet the unit shall be sealed with caulking.
All exposed screws shall be stainless steel.
ACCEPTANCE
Verify prior to bidding that the units meet the specified construction, and scheduled performance and electrical characteristics.
Units that do not meet the specified construction, accessories, or scheduled performance and electrical characteristics will not
be accepted.
ADDITIONAL ACCESSORIES
ROOF CURBS
Roof curbs shall of knock down constructed with minimum 18 gauge galvanized steel with perimeter wood nailer and patented
Cliplock corner clips to facilitate field assembly without the use of tools. Adhesive backed foam gasket seal shall be provided
loose for field installation to act as a seal between the unit and the roof curb. Bolt together roof curbs will not be accepted.
SPRING ISOLATION ROOF CURB
Spring isolation roof curbs shall consist of an isolation head assembly and a knock down Cliplock roof curb to allow early
shipment of the curb portion for installation before unit arrival. The isolation head assembly will ship with the unit for installation
prior to unit mounting. The isolation head assembly shall have 1” deflection open type spring isolators mounted within a full
perimeter fully welded two piece frame constructed from minimum 18 gauge satin coat steel with baked enamel finish that
matches unit finish, complete with a full perimeter dual durometer extruded flexible vinyl seal rated to –40 deg. F to allow
movement and maintain a water resistant seal. Flex connectors shall factory installed in the duct openings of the isolation
head for down flow applications only. The knock down Cliplock roof curb shall be constructed with minimum 18 gauge
galvanized steel with perimeter wood nailer and patented Cliplock corner clips to facilitate field assembly without the use of
tools.
Page 2 of 4
GS1 REV 4
RERV AND RERVX
GENERAL SPECIFICATION
FRESH AIR MOTORIZED INLET DAMPER
Units shall be complete with factory installed and wired fresh air inlet two position motorized damper assemblies constructed
with minimum 20 gauge galvanized steel, stainless steel edge seals, galvanized steel linkage and damper rod. Damper motor
shall be spring return, 24 volt powered, and complete with an end switch for unit fan activation when damper is fully open.
Outdoor applications will require the damper assembly to be mounted within the fresh air hood. Indoor applications will require
the damper assembly to be mounted within a sleeve constructed from minimum 18 gauge satin coat steel with baked enamel
finish that matches unit finish. All flanges that meet the unit shall be sealed with caulking.
EXHAUST AIR MOTORIZED DISHCHARGE DAMPER
Units shall be complete with factory installed and wired exhaust air discharge two position motorized damper assemblies
constructed with minimum 20 gauge galvanized steel, stainless steel edge seals, galvanized steel linkage and damper rod.
Damper motor shall be spring return, 24 volt powered, and complete with an end switch for unit fan activation when damper is
fully open. Outdoor applications will require the damper assembly to be mounted within the exhaust air hood. Indoor
applications will require the damper assembly to be mounted within a sleeve constructed from minimum 18 gauge satin coat
steel with baked enamel finish that matches unit finish.
EXHAUST AIR GRAVITY TYPE DISHCHARGE DAMPER
Units shall be complete with factory installed exhaust air discharge gravity type damper assemblies constructed from extruded
aluminum. Outdoor applications will require the damper assembly to be mounted within the exhaust air hood. Indoor
applications will require the damper assembly to be mounted within a sleeve constructed from minimum 18 gauge satin coat
steel with baked enamel finish that matches unit finish.
FROST CONTROLS
ON-OFF FROST CONTROL
Units shall include an ambient temperature control that will shut the unit off when the outdoor ambient temperature drops below
the required set point.
EXHAUST ONLY FROST CONTROL
Units shall include a pressure differential switch and an adjustable on delay timer relay. If frost occurs, the pressure increase
cause the pressure differential switch to shut the supply fan off and leave the exhaust fan operating until the warm indoor air
defrosts the wheel and the pressure across the wheel is reduced to normal.
ELECTRIC PREHEAT FROST CONTROL
Units shall include a factory installed and wired electric pre-heater to maintain a minimum fresh air temperature entering the
recovery wheel to prevent a frost condition. The pre-heater shall have open type helically coiled elements constructed of nickelchrome wire that is resistant to oxidation, and abrasion. Frame and control enclosure shall be constructed of galvanized steel.
Pre-heater controls shall include automatic reset thermal cut-out, contactor, airflow proving switch, 24 volt control transformer,
and full SCR control. Staged pre-heaters will not be accepted. A modulating 0-10vdc discharge temperature control shall be
factory mounted in the unit control enclosure with the sensor mounted in the unit fresh air plenum sensing the discharge air
temperature of the pre-heater and wired back to the pre-heater to control the SCR. Capacity of the pre-heater shall be as listed
in the schedule. Pre-heater source power wiring shall connect to the single point power input terminal of the unit.
RE-CIRCULATION FROST CONTROL
Units shall include a two position motorized re-circulation damper, pressure differential switch and an adjustable on delay timer
relay. If frost occurs, the pressure increase will cause the pressure differential switch to open the recirculation damper, shut
the exhaust fan off and close the fresh air damper. The exhaust air will now be re-circulated for a period of time governed by the
delay time relay.
Page 3 of 4
GS1 REV 4
RERV AND RERVX
GENERAL SPECIFICATION
COOLING AND HEATING COILS
Cooling Coil: Direct expansion and chilled water coils shall be factory tested and rated in accordance with ARI 410.
Coils shall have copper tubes with permanently expanded aluminum fin, 12 FPT or less and a galvanized steel frame. Direct expansion
coils shall be equipped with distributors to receive expansion valves at the liquid connections. Direct expansion coils shall
include a stainless steel drain pan.
Hot Water Coil: Hot water coils shall be factory tested and rated in accordance with ARI 410. Coils shall have copper tubes
with permanently expanded aluminum fin, 12 FPT or less and a galvanized steel frame.
OTHER ACCESSORIES (Specifications available upon request)
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Recovery Wheel variable frequency drive (VFD) for frost control
Flexible duct connectors (Shipped loose for field installation on unit external duct connections)
22 gauge inner cabinet liner
Fresh air enthalpy control for free cooling (Recovery wheel shutdown)
Fresh air ambient temperature control for free cooling (Recovery wheel shutdown)
Non-fused disconnect switch
Variable frequency drives (VFD) for supply and exhaust fan motors
Time clock - 7 day program, quartz, 100 hour battery backup, override switch
Dirty filter pressure differential switches) (Optional indictor light available)
Remote on-off switch (Shipped loose for field installation)
CO2 detector control (Shipped loose for field installation)
Recovery wheel rotation sensor (Optional indictor light available)
Programmable microprocessor control
Air flow monitoring
Page 4 of 4
GS1 REV 4
RERV X -255-H-1151
INPUT VOLTAGE:
1151 - 115/1/60
2081 - 208/1/60
2301 - 230/1/60
2083 - 208/3/60
2303 - 230/3/60
4603 - 460/3/60
5753 - 575/3/60
ARRANGEMENT:
H - HORIZONTAL FLOW
D - DOWN FLOW
C - SUPPLY HORIZONTAL,
BOTTOM RETURN
RERV & RERVX UNIT MODEL No:
256 ( 250 TO 600 CFM )
511 ( 500 TO 1100 CFM )
1019 ( 1000 TO 1900 CFM )
1324 ( 1300 TO 2400 CFM )
1533 ( 1500 TO 3300 CFM )
3045 ( 3000 TO 4500 CFM )
3550 ( 3500 TO 5000 CFM )
4055 ( 4000 TO 5500 CFM )
4567 ( 4500 TO 6700 CFM )
5082 ( 5000 TO 8200 CFM )
6098 ( 6000 TO 9800 CFM )
7011 ( 7000 TO 11000 CFM )
15000 (11000 TO 15000 CFM )
20000 (15000 TO 20000 CFM )
RERVLP UNIT MODEL No:
511 ( 500 TO 1100 CFM
1019 ( 1000 TO 1900 CFM
1324 ( 1300 TO 2400 CFM
1533 ( 1500 TO 3300 CFM
)
)
)
)
TYPE OF UNIT
X - UNITS WITH COILS
LP - LOW PROFILE INDOOR UNITS
SPINNAKER MODEL SERIES
MODEL ID NOV 30/04
RERVLP MODEL SERIES
ROTARY ENERGY RECOVERY
VENTILATORS
The following chart lists the available unit models with the CFM range for the supply and
exhaust air, and other unit component data. Refer to the performance data following this
page for fan-motor and recovery efficiency data.
UNIT
MODEL
CFM
RANGE
RERVLP-511
500 - 1100
ROTARY ENERGY
RECOVERY WHEEL SUPPLY AND
CASSETTE
EXHAUST FAN
MODEL No.
SIZE AND TYPE
FILTER TYPE
AND
SIZE
PLEATED - 30% EFFICIENT
20 X 25 X 2
ECW244
10 X 10
FC DWDI
RERVLP-1019
1000 -1900
ECW324
RERVLP-1324
1300 - 2400
ECW364
RERVLP-1533 1500 - 3300
ECW424
PLEATED - 30% EFFICIENT
18 X 20 X 2
12 X 12
FC DWDI
PLEATED - 30% EFFICIENT
24 X 24 X 2
LP SEL1
RERVLP
Standard Features
UNIT CONSTRUCTION
• Constructed for indoor use
• 20 gauge galvanized steel casing
• Casing interior surfaces to be lined with foil faced insulation.
• Center partitions and access doors to be lined with ½” and 1” foil faced insulation with all seams foil taped.
• Lift-off access doors complete with full perimeter rubber bulb seal gasket and ½ foil faced in insulation.
ROTARY WHEEL ASSEMBLY
• Heavy gauge galvanized steel casing
• Assembly slides in and out of unit for ease of inspection and removal
• Non-migrating water selective molecular sieve desiccant
• Wheel drive consists of a Drip proof drive motor, fixed pulley, and drive belt of hollow urethane construction.
• Performance tested using ASHRAE standard 84-1991
SUPPLY AND EXHAUST FANS
• Forward curved DWDI double width double inlet wheels
• Ball bearings
• ODP motors with ball bearings.
• Cast iron “B” section variable v-belt drives with adjustable motor mounts
FILTERS
• 2” pleated medium efficient throwaway type
• Fresh air filters on entering side of rotary wheel
• Return air filters on entering side of rotary wheel
CONTROLS AND ELECTRICAL
• Supply and exhaust fan motor fuses and contactors
• Rotary wheel drive motor fuses and contactor
• Control transformer with primary and secondary fuses
• Numbered terminal strip
• Internally pre-wired and operational tested
• ETL approved
FEA1LP
DEC 08/04
RERVLP-511
ROTARY ENERGY RECOVERY
VENTILATOR
500 TO 1100 CFM CAPACITY
CFM
500
800
1100
EXTERNAL STATIC PRESSURE (INCHES WC)
RPM
BHP
RPM
BHP
RPM
BHP
0.1
0.3
0.5
0.7
0.9
1.1
1.3
1.5
880
0.18
1078
0.37
1235
0.64
970
0.23
1157
0.45
1311
0.73
1052
0.28
1229
0.52
1382
0.83
1126
0.34
1298
0.59
1449
0.92
1196
0.40
1362
0.67
1510
1.02
1261
0.46
1422
0.75
1567
1.12
1323
0.52
1480
0.83
1622
1.22
1381
0.59
1535
0.91
1675
1.32
RERVLP511
OCT 08/04
SPINNAKER RESERVES THE RIGHT TO CHANGE ANY OF THE INFORMATION HEREIN WITHOUT NOTICE.
ENERGY
RECOVERY
WHEEL
EFFICIENCY
81.3%
72.1%
64.0%
27 Leading Road Etobicoke, Ontario, Canada M9V 4B7
Tel: (416) 742-0598 Fax: (416) 742-4251
4846 Jennings Lane, Louisville, Kentucky, USA 40218
Tel: 1-800-932-6210 Fax: 1-800-903-7294
RERVLP-1019
ROTARY ENERGY RECOVERY
VENTILATOR
1000 TO 1900 CFM CAPACITY
CFM
1000
1225
1450
1675
1900
EXTERNAL STATIC PRESSURE (INCHES WC)
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
0.1
0.3
0.5
0.7
0.9
1.1
1.3
1.5
962
0.34
1032
0.47
1099
0.63
1155
0.81
1211
1.01
1061
0.42
1126
0.57
1189
0.74
1240
0.93
1291
1.14
1150
0.51
1212
0.66
1272
0.85
1320
1.05
1368
1.28
1230
0.59
1291
0.76
1349
0.96
1395
1.18
1441
1.42
1305
0.68
1365
0.87
1422
1.08
1467
1.31
1510
1.56
1373
0.77
1435
0.97
1491
1.20
1536
1.44
1577
1.71
1436
0.85
1500
1.07
1555
1.32
1599
1.57
1641
1.85
1495
0.95
1562
1.18
1617
1.44
1661
1.70
1699
1.99
RERVLP1019
OCT 08/04
SPINNAKER RESERVES THE RIGHT TO CHANGE ANY OF THE INFORMATION HEREIN WITHOUT NOTICE.
ENERGY
RECOVERY
WHEEL
EFFICIENCY
80.5%
76.7%
73.1%
69.7%
66.4%
27 Leading Road Etobicoke, Ontario, Canada M9V 4B7
Tel: (416) 742-0598 Fax: (416) 742-4251
4846 Jennings Lane, Louisville, Kentucky, USA 40218
Tel: 1-800-932-6210 Fax: 1-800-903-7294
RERVLP-1324
ROTARY ENERGY RECOVERY
VENTILATOR
1300 TO 2400 CFM CAPACITY
CFM
1300
1575
1850
2125
2400
EXTERNAL STATIC PRESSURE (INCHES WC)
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
0.1
0.3
0.5
0.7
0.9
1.1
1.3
1.5
912
0.39
977
0.55
1043
0.74
1125
1.00
1204
1.31
1018
0.49
1075
0.66
1126
0.86
1197
1.12
1271
1.44
1114
0.58
1165
0.77
1211
0.98
1268
1.25
1336
1.58
1202
0.68
1251
0.89
1292
1.11
1343
1.39
1398
1.72
1283
0.79
1330
1.01
1369
1.25
1415
1.54
1463
1.88
1358
0.89
1405
1.13
1441
1.38
1485
1.69
1528
2.04
1429
1.00
1475
1.25
1511
1.52
1553
1.84
1592
2.20
1495
1.11
1542
1.38
1578
1.66
1617
2.00
1655
2.37
RERVLP1324
OCT 08/04
SPINNAKER RESERVES THE RIGHT TO CHANGE ANY OF THE INFORMATION HEREIN WITHOUT NOTICE.
ENERGY
RECOVERY
WHEEL
EFFICIENCY
80.0%
76.3%
72.9%
69.6%
66.5%
27 Leading Road Etobicoke, Ontario, Canada M9V 4B7
Tel: (416) 742-0598 Fax: (416) 742-4251
4846 Jennings Lane, Louisville, Kentucky, USA 40218
Tel: 1-800-932-6210 Fax: 1-800-903-7294
RERVLP-1533
ROTARY ENERGY RECOVERY
VENTILATOR
1500 TO 3300 CFM CAPACITY
CFM
1500
1750
2000
2250
2500
2750
3000
3300
RERVLP1533
OCT 08/04
EXTERNAL STATIC PRESSURE (INCHES WC)
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
0.1
0.3
0.5
0.7
0.9
1.1
1.3
1.5
715
0.30
749
0.39
787
0.51
823
0.64
861
0.80
898
0.98
934
1.18
1049
1.61
814
0.39
840
0.49
872
0.61
902
0.75
934
0.91
968
1.10
1000
1.31
1108
1.75
904
0.48
926
0.58
952
0.72
977
0.86
1005
1.03
1033
1.22
1063
1.44
1165
1.90
994
0.60
1005
0.69
1027
0.82
1049
0.98
1072
1.16
1097
1.35
1123
1.58
1221
2.05
1082
0.72
1079
0.81
1099
0.94
1117
1.10
1138
1.29
1159
1.49
1182
1.72
1275
2.21
1159
0.85
1158
0.94
1167
1.07
1183
1.22
1201
1.42
1220
1.64
1239
1.86
1327
2.37
1231
0.97
1234
1.09
1232
1.20
1246
1.37
1261
1.56
1278
1.78
1296
2.02
1378
2.53
1296
1.09
1305
1.24
1299
1.35
1306
1.51
1320
1.69
1335
1.93
1350
2.18
1429
2.70
SPINNAKER RESERVES THE RIGHT TO CHANGE ANY OF THE INFORMATION HEREIN WITHOUT NOTICE.
ENERGY
RECOVERY
WHEEL
EFFICIENCY
82.9%
80.3%
77.9%
75.5%
73.2%
71.0%
68.9%
66.4%
27 Leading Road Etobicoke, Ontario, Canada M9V 4B7
Tel: (416) 742-0598 Fax: (416) 742-4251
4846 Jennings Lane, Louisville, Kentucky, USA 40218
Tel: 1-800-932-6210 Fax: 1-800-903-7294
Electrical Data
RERVLP MODEL SERIES
ROTARY ENERGY RECOVERY
VENTILATORS
Unit voltages include 115, 208, and 230 single phase
and three phase, 460 and 575 three phase. Standard
electrical features include fan motor fuses,
contactors, and overloads, rotary wheel motor fuses
and contactor, control transformer with primary and
secondary fuses, and a 24 volt numbered terminal
strip for remote wiring connections as required.
115/1/60
STANDARD UNIT
The charts below show standard unit minimum circuit
ampacities and standard units with electric preheat
minimum circuit ampacities. The ampacity values listed
below are based on units with the same horse power for
the supply and exhaust fan motors. Contact the factory
for unit ampacities for unit selections of different horse
powers.
Note: Contact factory for single phase pre-heat requirements.
UNIT
MODEL
0.5
0.75
1
RERVLP-511
RERVLP-1019
29.9
29.9
36.4
36.4
34.4
34.4
FAN MOTOR HORSE POWER
1.5
2
3
5
46.7
46.7
7.5
10
15
7.5
10
15
7.5
10
15
69.4
208/1/60
STANDARD UNIT
UNIT
MODEL
0.5
0.75
1
RERVLP-511
RERVLP-1019
RERVLP-1324
RERVLP-1533
16.5
16.5
15.8
15.8
20.0
20.0
19.3
19.3
19.0
19.0
18.3
18.3
FAN MOTOR HORSE POWER
1.5
2
3
5
25.7
25.7
25.1
25.1
38.2
37.6
37.6
230/1/60
STANDARD UNIT
UNIT
MODEL
0.5
0.75
1
RERVLP-511
RERVLP-1019
RERVLP-1324
RERVLP-1533
15.0
15.0
14.3
14.3
18.2
18.2
17.6
17.6
17.2
17.2
16.6
16.6
FAN MOTOR HORSE POWER
1.5
2
3
5
23.5
23.5
22.8
22.8
34.7
34.1
34.1
LP ED1 Rev 0
Electrical Data
RERVLP MODEL SERIES
ROTARY ENERGY RECOVERY
VENTILATORS
208/3/60
STANDARD UNIT
UNIT
MODEL
0.5
0.75
1
1.5
FAN MOTOR HORSE POWER
2
3
5
RERVLP-511
RERVLP-1019
RERVLP-1324
RERVLP-1533
12.5
12.5
11.8
11.8
14.0
14.0
13.3
13.3
18.0
18.0
17.3
17.3
21.2
21.2
20.6
20.6
24.0
23.3
23.3
7.5
10
15
7.5
10
15
7.5
10
15
7.5
10
15
29.3
29.3
230/3/60
STANDARD UNIT
UNIT
MODEL
0.5
0.75
1
RERVLP-511
RERVLP-1019
RERVLP-1324
RERV-LP1533
11.2
11.2
10.6
10.6
12.7
12.7
12.1
12.1
16.2
16.2
15.6
15.6
FAN MOTOR HORSE POWER
1.5
2
3
5
19.2
19.2
18.6
18.6
21.7
21.1
21.1
26.6
26.6
460/3/60
STANDARD UNIT
UNIT
MODEL
0.5
0.75
1
RERVLP-511
RERVLP-1019
RERVLP-1324
RERVLP-1533
4.4
4.4
5.0
5.0
5.2
5.2
5.8
5.8
6.9
6.9
7.5
7.5
FAN MOTOR HORSE POWER
1.5
2
3
5
8.4
8.4
9.0
9.0
9.7
10.3
10.3
13.0
13.0
575/3/60
STANDARD UNIT
UNIT
FAN MOTOR HORSE POWER
MODEL
0.5
0.75
1
1.5
2
3
RERVLP-511
RERVLP-1019
RERVLP-1324
RERVLP-1533
3.4
3.4
3.8
3.8
3.9
3.9
4.3
4.3
5.7
5.7
6.1
6.1
6.7
6.7
7.1
7.1
7.7
8.1
8.1
10.3
10.3
5
LP ED1 Rev 0
RERVLP
Optional Accessories
DUCT CONNECTION ARRANGEMENTS
• Arrangement H (Horizontal duct connections)
MISCELLANIOUS
• Spring type vibration isolators (Indoor unit, hung or base mount, shipped loose for field installation)
• Flexible duct connectors (Shipped loose for field installation on unit external duct connections)
• Sensible only energy recovery wheel
FROST CONTROL
• On-off frost control
• Exhaust only frost control
FREE COOL CONTROL
• Fresh air enthalpy control for free cooling (Recovery wheel shutdown)
• Fresh air ambient temperature control for free cooling (Recovery wheel shutdown)
MISCELLANIOUS ELECTRICAL
• Non-fused disconnect switch
• Time clock - 7 day program, quartz, 100 hour battery backup, override switch (Shipped loose)
• Dirty filter pressure differential switches
• Dirty filter indictor light
• Remote indictor light with panel
• Remote on-off switch (Shipped loose for field installation)
• CO2 detector control (Shipped loose for field installation)
• Firestat (Duct mount shipped loose for field installation)
• Smoke detector (Duct mount shipped loose for field installation)
• Recovery wheel rotation sensor
• Programmable microprocessor control
• On-site startup: Commissioning and owner instruction
LP OP1 REV 0
RERVLP
Optional Energy Saving
Accessory Descriptions
Fresh air ambient temperature control for free cooling
Two fresh air ambient temperature controls can be factory installed to de-energize the energy recovery
wheel above 55°F and below 75°F. Both temperature controls are field adjustable to suit design
conditions.
This option prevents unnecessary heating of supply air through energy recovery during these outdoor
temperatures.
Option includes: Factory installed 2 ambient temperature controls
Fresh air enthalpy control for free cooling
The fresh air enthalpy control has effectively the same function as the fresh air ambient temperature
control. This option includes a fresh air temperature control and a logic controller with an enthalpy sensor.
The fresh air temperature control energizes the energy recovery wheel below 55°F. The enthalpy control
senses the enthalpy of the fresh air, which is a combination of the air temperature and relative humidity.
The enthalpy control will energize the energy recovery wheel above the set point which is actually a range
of fresh air temperature -humidity combinations, for example, from approximately 63°F 80% rh, to 82°F
10% rh, for setting “A”. The enthalpy control has 4 field adjustable settings to suit design conditions.
Option includes: Factory installed enthalpy control and ambient temperature control
LP OP2
RERV/RERVX
System Applications
Supplying Ducted Air Handlers
Outdoor Air
RERV Unit
Air Handlers
(Fan Coils)
Exhaust Air
Indoor Air
Supply Air
Supplying a Packaged Rooftop Unit
RERV Unit
Packaged
Rooftop Unit
Supply Air
Outdoor Air
Exhaust Air
Indoor Air
Stand Alone Independent of HAVAC System
RERV Unit
Outdoor Air
Packaged
Rooftop Unit
Exhaust Air
Indoor Air
Supply Air
RERVLP GENERAL SPECIFICATION
Packaged recovery ventilation units shall be Spinnaker Industries Inc. Model Series RERVLP. Units shall be factory
assembled, wired and tested prior to shipment. Units shall bear the ETL label. Field wiring shall require a single point
power connection and a numbered terminal strip for low voltage remote wiring connections.
UNIT CONSTRUCTION
Unit construction to suit indoor applications. All exterior cabinet screws shall be stainless steel. Unit casing shall be
minimum 20 gauge galvanized steel. All interior cabinet surfaces shall be lined with 1” thick, 3 lbs/cu ft density foil faced
insulation, with seems foil taped. Access doors and center partitions to be lined with 1/2 thick foil faced insulation. Access
doors and panel to be lift off style.
ENERGY RECOVERY WHEEL ASSEMBLY
The energy recovery wheel assembly casing shall be constructed with heavy gauge galvanized steel, reinforced at sealing
surfaces, removable end panels for drive access, inboard no-maintenance permanently sealed roller bearings for small
assemblies, external pillow block bearings for large assemblies, and an adjustable non-contact neoprene bulb peripheral
and inner seal. The wheel assembly shall slide in and out of the unit on a galvanized steel track for ease of inspection and
maintenance.
The wheel media shall be constructed of a corrugated synthetic fiber-based substrate impregnated with a non-migrating
water selective 4A molecular sieve desiccant uniformly and permanently dispersed throughout the matrix structure. The
wheel media shall be spirally wound to form a fluted honeycomb geometry so as to eliminate internal wheel bypass. Wheel
layers that can be separated or spread apart by airflow are unacceptable due to the possibility of channeling and
performance degradation. Face flatness of the wheel shall be maximized (+/- 0.032 inches) in order to minimize wear on
inner seal surfaces and minimize cross leakage. The wheel shall be complete with a purge section, minimizing cross over
of return air into supply air, with a non-contact bulb seal. Wheels with large pore size desiccants like silica gel, that are
coated, bonded, or synthesized onto the media or without a purge section will not be accepted. The wheel shall consist of
evenly spaced galvanized steel spokes, a galvanized steel outer band, and an aluminum center hub.
The standard drive system shall consist of a drip proof motor, fixed pulley, and link type drive belt constructed from a high
performance polyurethane elastomer reinforced with multiple plies of polyester fabric. The drive pulley and belt shall drive
the wheel from inside the assembly casing. Wheels with drive pulleys and belts that are exposed will not be accepted.
Single phase drive motors shall have integral automatic reset thermal overload protection. Three phase drive motors shall
have a manual reset thermal overload mounted in the unit control enclosure.
Wheel media shall be in accordance with NFPA, and be UL tested and UL recognized as a component for heating and
heating-cooling appliance accessories. Energy recovery wheels shall be rigorously performance tested using the ASHRAE
84-1991 and ARI 1060 standard method of testing. Recovery wheels shall be ARI certified and must bear the ARI
certification stamp.
FANS
Supply and exhaust fans shall be forward curved double width double inlet with ball bearings. Fan drive shaft shall be
polished with keyways for drive pulley mounting. Unit fans with machined flats on fan shafts for drive pulley mounting will
not be accepted. Fans shall have ball bearings suitable for operation in ambient temperatures of –65 to 250 deg. F with a
minimum L10 life in excess of 100,000 hours at maximum cataloged operating speeds. Fan bearings shall be permanently
lubricated and sealed, mounted in resilient neoprene rings. Fan housings shall have extruded holes for base side
mounting. Fans in units with air flow capacity greater than 2500 CFM shall have welded steel angle frames. Fan motors
shall be rated continuous duty, ball bearing construction, and have class F insulation. Variable pitch v-belt drives, of cast
iron construction and adjustable motor mounts to be provided. Units with fans, motors, and drives that do not meet the
above criteria will not be accepted.
FILTERS
The supply entering and exhaust entering sides of the recovery wheel shall be complete with 2" deep medium efficiency
pleated filters. Units without supply and exhaust filters will not be accepted.
GS1LP
DEC 08/04
Page 1 of 2
RERVLP GENERAL SPECIFICATION
CONTROLS AND ELECTRICAL
Unit controls shall be mounted within an integral enclosure with an inner hinged access door and an exterior lift off access
panel. The exterior lift off access panel shall be the same construction as the other unit access panels
Unit controls shall include: supply and exhaust fan motor fuses, contactors, and manual reset thermal overloads, energy
recovery wheel drive motor contactor, and control transformers with primary and secondary fusing. Unit wiring shall be
color coded with a numbered terminal strip for low voltage wiring and field connections. Unit shall have single point power
input terminals. Units without separate motor fusing and contactors will not be accepted
ACCEPTANCE
Verify prior to bidding that the units meet the specified construction, and scheduled performance and electrical
characteristics. Units that do not meet the specified construction, accessories, or scheduled performance and electrical
characteristics will not be accepted.
FROST CONTROLS
ON-OFF FROST CONTROL
Units shall include an ambient temperature control that will shut the unit off when the outdoor ambient temperature drops
below the required set point.
EXHAUST ONLY FROST CONTROL
Units shall include a pressure differential switch and an adjustable on delay timer relay. If frost occurs, the pressure
increase cause the pressure differential switch to shut the supply fan off and leave the exhaust fan operating until the
warm indoor air defrosts the wheel and the pressure across the wheel is reduced to normal.
OTHER ACCESSORIES (Specifications available upon request)
• Non-fused disconnect switch
• Sensible only energy recovery wheel
• Time clock - 7 day program, quartz, 100 hour battery backup, override switch
• Dirty filter pressure differential switches
• Dirty filter indictor light
• Remote Indictor light with panel
• CO2 detector control
• Firestat
• Smoke detector
• Recovery wheel rotation sensor
• Remote on-off switch
• Fresh air enthalpy control for free cooling (Recovery wheel shutdown)
• Fresh air ambient temperature control for free cooling (Recovery wheel shutdown)
• Spring type vibration isolators for an indoor or based mount unit
• Flexible duct connectors
• Programmable microprocessor control
GS1LP
DEC 08/04
Page 2 of 2
RERV Limited Warranty
COVERAGE AND TERMS
RERV Model Series units and all RERV accessories as manufactured by Spinnaker Industries, are warranted
to the original buyer to be free from defects in materials or workmanship provided that these units and
accessories have been installed and maintained in accordance with instructions and operated under normal
conditions. Spinnaker Industries sole obligation under this Limited Warranty is to repair or replace, at its
opinion, free of charge to the customer (except as provided below), FOB factory, any part determined by
Spinnaker Industries (in its sole discretion) to be defective. Warranty terms, from original ship date are as
follows:
• Energy recovery wheel assembly
(excluding drive belts, seals, and motors)….……..………5 Years
• Recovery wheel belts, seals, and motors…………………2 Years
• All other components………………………………………..1 Year
EXCLUSIONS
Spinnaker Industries Limited Warranty does not cover defects, reduced performance, or failure caused,
directly or indirectly, by improper installation, abuse, misuse, misapplication, improper maintenance, lack of
maintenance, negligence, accident, or normal deterioration, including wear and tear. This Limited Warranty
shall not apply to items that require replacement due to normal wear i.e. fan drive belts, filters, etc., or to
failures, defects, or reduced performance resulting, directly or indirectly, from use of its products exposed to
corrosive gasses or liquids.
Spinnaker Industries Limited Warranty does not include costs for transportation (including, without limitation,
freight and return freight charges, costs, and insurance), costs for removal or re-installation of parts or
equipment, cranes and hoisting, premiums for overtime, labor for performing repairs or replacement made in
the field, roofing contractors or any other sub trades. Spinnaker Industries is not responsible for damages
occurring during transport of any product to or from its facilities.
RETURN PROCEDURE
To return defective parts under these warranty terms, please contact Spinnaker Industries at 1-800932-6210 to confirm the ship to address. The serial number located on the rating label of the unit must be
provided so that the original ship date of the unit can be verified. All defective parts must be authorized for
return and shipped pre-paid to Spinnaker Industries for inspection. A purchase order must be received prior
to shipment of repaired or replacement parts. Repaired or replacement parts will be invoiced and shipped
collect FOB Factory. A credit will be issued only if the defective parts are deemed the responsibility of
Spinnaker Industries. Spinnaker Industries is not responsible for any damage or lose occurring during
shipment to or from Spinnaker Industries.
THE OBLIGATION AND LIABILITY OF Spinnaker Industries UNDER THIS LIMITED WARRANTY DOES NOT
INCLUDE LOSSES, DIRECT OR INDIRECT, FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES. THIS
LIMITED WARRANTY IS PROVIDED EXCLUSIVELY TO THE ORIGINAL BUYER OF PRODUCTS AND MAY
NOT BE ASSIGNED OR OTHERWISE TRANSFERRED.
THIS LIMITED WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESED OR IMPLIED,
INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, AND
THERE ARE NO WARRANTIES WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF.
RERV WARRANTY REV 0
Quick and Easy Hints for using Adobe!
• Show / Hide Navigation Pane, allows the user to see, or to hide
bookmarks on the left side of the screen.
• Fit in Window, allows the user to view the selected file at the
maximum size of their viewing window. (height or width)
Located on the right side of the page.
• Fit Width, allows the user to view the selected file at the
maximum width of their viewing window, located on the right
side of the page. This will allow the user to read any blurry
text. To increase the width of your viewing window, drag the
scroll bar to the left.
Please notice the positions of the scroll bar and the size of the viewing window.
Please notice the position of the scroll bar and the size of the viewing window.
Download PDF
Similar pages