AS-821E
Specifications
SmartScreen™
Model BCY221X
General
SmartScreen™ serves a simple supervisory system that
monitors and controls building controllers (remote units) for
equipment and facilities in a small to medium sized building.
SmartScreen handles up to 99 remote units (CDGP* /
Infilex™ SC / Infilex™ FC).
SmartScreen controls remote units in connection as
follows: Separate ON/OFF, monitoring of operating status
and alarm, measurement, temperature/air volume setting,
weekly/yearly scheduled operation, data collection, and
meter-reading.
By adding the optional printer unit to SmartScreen,
operation/status change record and alarm history can be
printed.
Besides, optional Web-Adapter™ enables remote
monitoring and control through the Web browser.
SmartScreen will thus assist building operators and owner
for building operation.
*CDGP: Compact Data Gathering Panel.
Features
Simple and space-saving
• The compact and lightweight unit:
300mm (W) × 300mm (H) × 112mm (H) (standard model)
• The simple system is equipped with basic functions which
offer convenient building management to monitor
ON/OFF, status, alarm, measurement points, and to set
weekly/yearly schedule and calendar.
• CDGP,
which
manages
ON/OFF,
monitoring,
meter-reading, and measuring, is also designed to fit
inside a power panel or a distribution panel. Additional
control panel is thus unnecessary.
• Slim-sized main unit (SmartScreen without panel: 50 mm
thick) and printer unit can be installed in a standing panel
cabinet such as fire control panel.
Easy operation
• Graphical icons facilitates operation.
• Back-lit color LCD ensures visibility.
Light work for management
• SmartScreen automatically controls the remote units
according to weekly schedule/yearly calendar programs.
• The printer unit (optional) prints equipment operation
record, status change record, and alarm history.
• Data collection function allows to store measurement data
in the CompactFlash® memory and to edit the stored data
using general software applications.
• Meter reading (optional program) facilitates to monthly
manage the totalized points.
• Management names (remote unit and point names)
shown on the display can be modified via Windows®
Hyperterminal on a standard computer.
Easy engineering and installation
• Each remote unit is connected to SmartScreen with LAN
cables.
• Supervisory system is served by connecting remote units
and setting addresses. No complex adjustment is
necessary.
• System configuration is simple because of no
requirements except the connectable number of remote
units.
High accessibility
• Web-Adapter allows you to remotely monitor and operate
your SmartScreen through the Web-browser in your
standard PC.
Multi-languages support (selectable by model numbers)
• Language viewed in the operator interface is selectable
among Japanese, English, Chinese, Taiwanese, and
Korean with model numbers.
1
AS-821E
System Configuration
AHU: Air Handling Unit
AI: Analog Input
DI: Digital Input
DIO: Digital Input/Output
FCU: Fan Coil Unit
Web browser
in your PC
SmartScreen
Pt: Pt RTD Input
RRD: Remote Control Relay Driver Output
SC-bus: Sub Controller Bus
TOT: Totalizer Pulse Input
SC-bus (max. 99 units, max.1 km)
Ethernet
SmartScreen
dedicated LAN,
general office
purpose LAN
CDGP
CDGP
Infilex SC
Infilex FC
(DIO/DI/RRD)
(Model WY7208)
(AI/Pt/TOT)
(Model WY7208)
(Model WY5207)
(Model WY5205W8000/
WY5205W9000)
Chiller plant equipment
Plumbing equipment
Lighting equipment
Sensor
Measuring meter
AHU
FCU
User terminal
User terminal
Model QY7205/QY7290
Model QY7205/QY7290
Figure 1. System configuration example
Model Numbers (main unit)
Model numbers
BCY221
0
1
2
3
4
0W2
1D2
2W2
0
0
1
0
1
Descriptions
SmartScreen base model number
Language: Japanese
Language: English
Language: Chinese
Language: Taiwanese
Language: Korean
Main unit with panel: Main unit installed on the panel
(W) 300 mm × (H) 300 mm × (D) 112 mm, power supply: 100 to 240 V AC, 50/60 Hz
Main unit without panel: Main unit only
(W) 204 mm × (H) 144 mm × (D) 50 mm, power supply: 24 V DC
Main unit with panel: Main unit installed on the panel, with Web-Adapter inside
(W) 300 mm × (H) 300 mm × (D) 112 mm, power supply: 100 to 240 V AC, 50/60 Hz
Fixed
Without meter-reading program
With meter-reading program
Without data collection program
With data collection program
Accessories: 128 MB CompactFlash® memory, CompactFlash® adapter
Notes:
∗ Order the application software for remote data collection (Part No. 83163715-X02) separately.
∗ Use CompactFlash memory supplied with the SmartScreen. This memory is also available separately from the SmartScreen (Part No.
83164897-002). With another CompactFlash memory (commercial product), SmartScreen operation is not assured.
Safety Instructions
Please read instructions carefully and use the product as specified in this manual. Be sure to keep this manual near by for
ready reference.
Usage Restrictions
This product is targeted for general air conditioning. Do not use this product in a situation where human life may be affected. If
this product is used in a clean room or a place where reliability or control accuracy is particularly required, please contact
Yamatake’s sales representative. Yamatake Corporation will not bear any responsibility for the results produced by the
operators.
 CAUTION



•
Installation and wiring must be performed by qualified personnel in accordance with all applicable safety standards.
•
This product must be operated within its operating ranges specified in this manual. Failure to comply will cause
equipment damages.
This product must be operated under the operating conditions (power, temperature, humidity, vibration, shock,
installation position, atmospheric condition, etc) specified in this manual to prevent equipment damages.
•
Trademark information:
SmartScreen and Web-Adapter are trademarks or registered trademarks of Yamatake Corporation in Japan or in other countries.
CompactFlash is a U.S. registered trademark of SanDisk Corporation.
Ethernet is a U.S. registered trademark of Xerox Corporation.
Microsoft and Windows are either registered trademarks or trademarks of Microsoft Corporation in the United States and/or other countries.
2
AS-821E
Optional Part Numbers
Auxiliary devices shown below are optional. In addition to the SmartScreen LCD unit, order your necessary auxiliary device(s).
Printer unit
Part number
83161238-101
83161239-101
83161239-102
Description
Printer unit with panel and cable for SmartScreen connection
Power supply: 100 to 240 V AC, 50/60 Hz (50 VA)
Cable length: 0.7 m for communication / 0.4 m for power supply
Printer unit without panel and cable for SmartScreen connection
Power supply: 5 V DC (30 W)
Cable length: 0.7 m for communication / 0.4 m for power supply
Printer unit without panel and cable for SmartScreen connection
Power supply: 5 V DC (30 W)
Cable length: 0.7 m for communication / 2.0 m for power supply
Power supply unit
Part number
Type
83162593-002
Power supply unit for the main unit without panel (DIN-rail mounting)
83162593-102
Power supply unit for the printer unit without panel (DIN-rail mounting)
83162593-001
Power supply unit for the main unit without panel (DIN-rail mounting)
83162593-101
Power supply unit for the printer unit without panel (DIN-rail mounting)
∗ Note:
SmartScreen main unit/printer unit without panel requires the above power supply unit.
Input
200 V AC to 240 V AC
200 V AC to 240 V AC
100 V AC to 120 V AC
100 V AC to 120 V AC
Output
24 V DC
5 V DC
24 V DC
5 V DC
Web remote control unit (Web-Adapter™)
Part number
Description
83162756
Web-Adapter base model number.
-201
Language: Japanese
-202
Language: English
-203
Language: Chinese
-204
Language: Taiwanese
-205
Language: Korean
Notes:
∗ Web-Adapter is a personal Web-server to browse information SmartScreen provides. Power supply for Web-Adapter is required
separately from SmartScreen.
∗ Web-Adapter (above) is additionally required to remotely control SmartScreen without Web-Adapter.
Hardware Specifications
SmartScreen
System
(1/2)
Items
Rated power Main unit with panel
supply
Main unit without panel
Power
Main unit with panel
consumption
Main unit without panel
Grounding
Ambient conditions
Battery backup for power failure
Dimension
Weight
Display
Main unit with panel
Main unit without panel
Main unit with panel
Main unit without panel
Color
Type
Languages
Screen types
Communication
with remote unit
Operation
LED indication
Transmission type (line)/ speed
Transmission distance / number of units
Connectable remote unit types
Cable
Specifications
100 to 240 V AC (85 to 264 V AC), 50/60 Hz
24 V DC ±10%
Max. 66 VA
Max. 21 W
Single grounding with 100 Ω or lower ground resistance
5 to 40 °C, 20 to 80 %RH (non-condensing)
Backup time: 48 hours (data memory, schedule programmed operation)
Battery: Lithium battery
300 mm (W) × 300 mm (H) × 112 mm (D)
204 mm (W) × 144 mm (H) × 50 mm (D)
5.1 kg
1.0 kg
Bezel: Equivalent to Munsell 5.2 Y 7.9 / 1.0
Back-lit color LCD (5.7 inch)
Japanese/English/Chinese/Taiwanese/Korean (selectable with model number)
Graphic icons
Icon indication on the window type screen (to display monitoring, setting, and
scheduling, etc.)
Analog touchscreen
Power supply, alarm, power failure shutdown, equipment running
Voltage transmission (SC-bus) / 4800 bps
Max. 1km / Max. 99 remote units connectable.
CDGP (DIO/DI/RRD/AI/TOT/Pt) / Infilex FC / Infilex SC
LAN cable (recommended LAN cable: compliant with EIA-568,
category 3 or over, φ0.5 mm × 4 P)
3
AS-821E
(2/2)
Items
Connection to
PC (DOS/V)
Data collection*1
Web remote
control unit
(Web-Adapter)*2
Cable
Specifications
RS-232 cross cable serial port connection (female D-sub 9 pins)
CompactFlash® memory
Ethernet®
TCP/IP
Adapter interface
TELNET server
Dimension
Power supply capacity
128 MB CompactFlash memory
10BASE-T × 1
1 session (socket communication)
1 session (for setting)
110 mm (W) × 113 mm (H) × 27.6 mm (D)
5 V DC, 1.0 A
Notes:
∗1 Use CompactFlash memory supplied with the SmartScreen. This memory is also available separately from the SmartScreen (Part No.
83164897-002). With third-party CompactFlash memory (commercial product), SmartScreen operation is not assured.
∗2 Web-Adapter is installed in Model BCY221XW2 SmartScreen. To combine Web-Adapter with other SmartScreen models, additionally
order optional Web-Adapter.
Panel of the panel-installed model SmartScreen/printer unit
Item
Specification
SECC-C (Electrolytic zinc-coated carbon steel sheets)
Housing: 1.2 mm, door: 1.0 mm
Equivalent to Munsell 6.1 Y 7.3 / 0.6
Material
Thickness
Color
Printer unit (optional)
Item
Printer unit with panel
Printer unit without panel
Printer unit with panel
Printer unit without panel
Printer unit with panel
Printer unit without panel
Printer unit with panel
Printer unit without panel
Power supply
Power
consumption
Dimensions
Weight
Printing method
Specification
100 to 240 V AC (85 to 264 V AC), 50/60 Hz
5 V DC
Max. 50 VA
Max. 30 W
300 mm (W) × 300 mm (H) × 102 mm (D)
102 mm (W) × 117 mm (H) × 66 mm (D)
4.5 kg
0.3 kg
Line thermal
Black ink
48 characters per line (ANK conversion)
Thermal paper roll (58 mm wide)
Wiring Specifications
Items
SC-bus
Power supply cable
DI input (Fire alarm input)
DO output (Batch alarm output)
Ethernet
Input/output specifications
Voltage transmission
Speed: 4800 bps (with no redundancy)
100 to 240 V AC, 50/60 Hz
Potential free N.O. contact input
(24 V DC, 5 mA)
Potential free N.O. contact output
(24 V DC, 100 mA)
10BASE-T
Wiring specification (recommended wires)
LAN cable (compliant with EIA-568, category 3
or over, φ0.5 mm × 4 P)
JIS*1 VCT 2.0 mm²
JCS*2 CPEV 0.9 mm
JIS CVV 1.25 mm²
JCS CPEV 0.9 mm
JIS CVV 1.25 mm²
LAN cable (compliant with EIA-568, category 3
or over, φ0.5 mm × 4 P)
Length
1 km
⎯
50 m
50 m
100 m
Notes:
∗1 JIS: Japanese Industrial Standards
∗2 JCS: Japanese Electric Wire and Cable Makers’ Association Standards
Input/output rating
Items
Batch alarm output
Fire alarm input
Specifications
Potential free N.O. contact maintained output
Contact rating: 24 V DC
Applied current: 100 mA
Batch alarm is output when alarm monitoring point tells alarm.
Potential free N.O. contact input or potential free transistor input
Current: 5 mA DC
Voltage: 24 V DC
Fire alarm is input by contact/transistor that makes ON at fire event.
4
Remarks
Terminals are provided on the
back side of the main unit.
AS-821E
Software Specifications
Individual ON/OFF and point monitoring function
• Turns on and off each equipment connected to, and
monitors the operating status and the alarm.
•
•
Meter-reading function and data output to PC (optional)
• Totalizes the measured meter-reading values per point.
Also, regularly adds up the values for a month and
displays the result data on the screen. (Max. 40 points)
Monitors and measures the analog values such as:
current, voltage, electric power, temperature, and
humidity.
•
Monitors and totalizes the value of the pulse inputs such
as: gas, water, and electric power.
Individual control function
• Changes the setpoint (temperature) and fan speed
(L/M/H) of FCU
•
Outputs the monthly data (totalized meter-reading values
for a month) to your PC via RS-232 cable. The output
data in CSV format is editable using software applications
such as Microsoft® Excel. The data contains system
number, name, and reading of the previous totalized data
and the totalized data two times before.
Command/COS (change of status) history/alarm
history display
Displays the history of the commands, changes of status,
alarm event and recovery. 360 items max. are displayed.
Items are deleted chronologically from the oldest when the
items count more than 360.
Changes the setpoint (temperature) of AHU.
List monitoring function
Monitors the points per type such as: ON/OFF (of
AHU/FCU, lighting and general equipment), status, alarm,
analog values to measure, and the values of the pulse
inputs to totalize.
AI high/low limit monitoring function
• Alerts when an AI value exceeds the preset high/low limit.
Weekly scheduled operation function
Automatically turns on and off the general equipment,
lighting, FCU/AHU according to the weekly scheduled
timer. Master schedule allows to set the schedules for
each day of the week. Also, executable schedule allows to
set the special schedules, such as overtime working hours
for the coming week. (Up to 40 schedules can be set.)
•
Yearly calendar operation function
Allows you to set the schedules for holidays and special
days with the yearly calendar. Even if the schedules are
different for each tenant in a building, up to 40 schedules
can be set.
Data collecting function (optional)
• Automatically and periodically (every 1/10/30/60 mins.)
collects AI, TOT, DI, DO, PRA (parameter) points and
saves them as CSV data in a 128 MB CompactFlash
memory. (Max. 100 points)
Transfers alarms to other facilities by combining with the
event interlock function.
Name change function
Changes the names of remote unit points and CDGP
points shown on the screen, using a PC with RS-232 cable
connection.
•
Event interlock function
Controls interlock ON/OFF with status change and alarm
as a trigger. For example, equipment such as outdoor
AHU, all heat exchanger, or chiller can be controlled by the
status of FCU or AHU. The ON/OFF operation of lighting
and AHU/FCU can be interlocked by an access signal
(max. 40 systems, 16 input points per system, 8 output
points per system).
Up to 100 points of the data in the CompactFlash memory
is editable using applications software such as Microsoft
Excel.
Record function (optional)
Prints out the desired information from the displayed
history record list in combination with the optional printer
unit.
Remote control function (optional)
Allows you to control SmartScreen (point monitoring and
operation, schedule change, history record management)
with your PC (where Microsoft® Internet Explorer 4.0 or
greater is installed) via Ethernet.
Power failure restoration control function
After the power restoration, restarts the equipment, AHU,
and FCU to recover their status before the power failure.
Batch stop for fire alarm
Stops all of the equipment, FCU and AHU with a fire alarm
input. (CDGP points allow to select target equipment/AHU
/FCU for this function.)
Remote alarm signal function (optional)
Sends alarm event and recovery status to e-mail server.
(Max. 6 addresses)
Cooling/ heating switchover function
Allows you to changeover cooling/heating mode of
FCU/AHU manually on operation screen or by an external
contact input. (2 systems max. are set.)
Remote data collecting function
Allows a remote PC to collect AI, TOT, DI, DO, PRA points
and history record (commands, COS, alarms). The
collected data is saved in CSV format in hard disk.
(Dedicated application software requires to be installed in
your PC. SmartScreen data collecting function needs to be
selected as well for this function.)
5
AS-821E
Dimensions (unit: mm)
300
101
99.5
48
99.5
4
100
98
116
121
300
58
63
48
104
Figure 2. SmartScreen: Main unit with panel
Figure 3. Printer unit with panel
101
12.1
72.5
116
38
Figure 4. SmartScreen: Main unit without panel
Figure 5. Printer unit without panel
Power supply unit dimensions
(Common to Part Nos. 83162593-001, -002, -101, -102 )
Terminal pitch
Clear acrylic
terminal cover
(9)
(4.8)
Figure 6. LED details
Adjustment knob of
output voltage
2 M3 screws (faced)
(Max. 6mm deep)
Cover
(Optional)
RS-232C/485
(89)
(107)
113.0
Terminal screw
(Max. 6 mm deep)
DC T u
(24)
(3.6)
(90)
(9)
SW
110.0
27.6
NET MON
(1.2)
10BT
Figure 7. Web remote control unit (Web-Adapter)
Figure 8. Power supply unit
6
53.1
49.3
AS-821E
Screen Examples
1. Main Menu
2. Equipment List
Leads you to monitor, control and data screens.
Leads you to the lists (per point type) of the monitoring points.
MAIN MENU
Equipment
Equipment
Remote Units
HVAC
Lighting
Control
Data Management
Others
Status Monitor
Sys Management
System Command
Alarm Monitor
Analog
Totalizer
3. HVAC List
4. Status Monitoring
Displays the list of HVAC points (units). ON/OFF can be
controlled, and status and alarm can be monitored.
1/13
Displays the list of status and alarm points. Both the status and
status + alarm of each point can be monitored.
Status Monitor
HVAC
(Unit/Pnt
name)
(Unit/Pnt
name)
(Unit/Pnt
name)
(Unit/Pnt
name)
1/50
(Point
name)
(Unit/Pnt
name
(Unit/Pnt
name)
(Unit/Pnt
name)
(Unit/Pnt
name)
(Point
name)
(Point
name)
(Point
name)
(Point
name)
(Unit/Pnt
name)
(Unit/Pnt
name)
(Unit/Pnt
name)
(Unit/Pnt
name)
(Point
name)
(Point
name)
(Point
name)
(Point
name)
(Unit/Pnt
name)
(Unit/Pnt
name)
(Unit/Pnt
name)
(Unit/Pnt
name)
(Point
name)
(Point
name)
(Point
name)
(Point
name)
(Point
name)
(Point
name)
(Point
name)
OFF ON
5. Analog Point List
6. Remote Units List
Displays the list of analog measurement point.
Displays the list of remote units including FCU and AHU.
Remote units are shown in the order of their address. Each
remote unit is separately started up or shut down.
Analog
1/50
1.1
Remote Units
1/5
Analog 1
61.4 %
1.3 Analog 3
56 V
4.1 Analog 1
18.43 %
6.1 Analog 1
23.5 A
1.2 Analog 2
37.0 %
1.4 Analog 4
10.4 A
4.2 Analog 2
32.2 %
31.1 Analog 1
123.0 V
7. Point List
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
Allows you to set a standard weekly schedule.
Point List
Master Schedule
40/40
(Controller No.13)
1
2
8. Master Schedule
Allows you to monitor and control detailed points of a remote unit.
Unit 13
1
ON/OFF 1
Schedule ON
2
ON/OFF 2
Fail Man
8:00
ON
:
OFF
7
19:00
OFF
:
:
:
:
:
0
6
12
18
24 h
Sat →
Sun
Holi
Sp1
Sp2
Schedule Mon→ Calendr Schedule
Copy
Weekdy No. 2 Download
AS-821E
9. Year Calendar
10. History display
Allows you to set the holidays and special days of the year.
Displays unit running status, status changes, and alarm history.
Calendar
All History
1/40
’98. 1
Sun Mon Tue Wen Thu
1
4
5
6
7
8
11 12 13 14 15
18 19 20 21 22
25 26 27 28 29
Schedule
Download
Calendar
Copy
Week Holi
Fri
2
9
16
23
30
Alarm Return Unit 99
98- 1- 1
9:15
1 ON/OFF
Schedule ON
Sys ON
97-12-29 11:21
Sat
3
10
17
24
31
Alm Occurred Unit 99
97-12-30 20:34
1 ON/OFF
Fail DDC
OFF
Unit Err Unit 95
97-12-28 16:55
Spe1 Spe2
Del
11. Data Collection Menu (optional)
12. Data collection detail setting (optional)
Displays the menu for data collection.
Allows you to set the details of the data collection.
Data Collection
Detailed Setting
3/3
Write to PC Card
Detailed Setting
Group 9
Delete PC Card
Card Format
Group 10
DEL
Group 9 Cycle
10 Min
DEL
Group 10 Cycle
60 Min
1 Min 10 Min 30 Min 60 Min
Specifications are subject to change without notice.
Building Systems Company
http://www.yamatake.com
Rev. 10.0 Mar. 2010
AS-821E
(J: AS-821 Rev. 6.0)
Printed in Japan.
8
Download PDF